This document is a comprehensive Test Pit Report for the VA Sousley Campus in Lexington, Kentucky, detailing underground utility investigations conducted by IMEG. The report includes 20 test pit locations, systematically documenting various underground utilities such as electric ducts, water pipes, communication conduits, storm pipes, gas lines, and unidentified pipes. Each test pit report provides detailed information including utility type, pipe material, depth, coordinates, elevation, condition, and ground composition, with most utilities noted as being in good to fair condition.

The test pit investigations were performed using a Vivax-Paradigm Vac truck, with crews exposing utilities at varying depths ranging from 0.91 feet to 6.85 feet beneath the surface. The utilities discovered include rough poured concrete electric ducts, plastic and ductile iron water pipes (domestic and fire protection), communication conduits, storm pipes, gas pipes, and several unidentified metallic and non-metallic lines. The reports consistently note sunny weather conditions and predominantly clay soil types, with survey markers placed using steel pins and color-coded ribbons to identify different utility types.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IMEG (P) 703-334-5657

Heritage Village Plaza Suite 101 (F) 703-334-5657 Gainesville, VA 20155 www.utilityprofessionalsinc.com

TEST PIT REPORT – VA SOUSLEY CAMPUS

IMEG CONTACTS: Joe Zink: 703-268-3222

Location: Lexington, KY

DATE MARKED: 9/8/23 STAFF: Taylor & Blair

WEATHER

CONDITIONS:

Sunny

EQUIPMENT USED: Vivax-Paradigm Vac truck

TEST PIT NO: 1 Survey Marker: Steel pin

FIELD NOTES AND

OBSERVATIONS:

Crew exposed a 20’’ by 12’’ Rough Poured Concrete Electric Duct with a top depth of 3.50’ and a bottom depth of 5.00’. Crew also exposed a 11’’ OD Private Ductile Iron Fire Protection Water Pipe at a top depth of 2.41’.

Utility requested to be exposed: Electric Line

Utility found or exposed: (A) 20’’ by 12’’ Rough Poured Concrete Electric Duct

(B) 11’’ OD Private Ductile Iron Fire Protection Water Pipe

Test Pit Coordinates: N: 59311.54 E: 57605.69

Cut Depth (From Top of Utility): (A) 3.50’

(B) 2.41’

Size and Material: 14.5’’ by 12’’ Rough Poured Concrete Duct in Good Condition

11’’ OD Ductile Iron Pipe in Good Condition

Pavement or ground type: Grass

Soil or ground type: Clay

Type of survey marker and ribbon color: Steel Pin/Red Ribbon

Location of survey mark: Center of Duct

*See Site Utility Drawing

Linnea.K.Shaw Text Box

APPENDIX K

Top View

Side View

Electric Duct

3.50’

Top Depth Duct

5.00’

Bottom Depth Duct

Elevation of Utility

(Top of Duct) – 928.48’

(Bottom of Duct) - 926.98’

(Top of Pipe) - 929.57’

Survey Marker Elevation – 931.98’

Water Pipe

2.41’

Top Depth Pipe

CONDITIONS:

TEST PIT NO: 2 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed an 18’’ by 12’’ Rough Poured Concrete Electric Duct with a top depth of 3.95’ and a bottom depth of 4.91’. Crew also exposed a 0.5’’ ground cable at a top depth of 3.89’.

Utility requested to be exposed: Electric Line

Utility found or exposed: (A) 18’’ by 12’’ Rough Poured Concrete Electric Duct

(B) 0.5’’ Ground Cable

Test Pit Coordinates: N: 59764.72 E: 57069.24

Cut Depth (From Top of Utility): 3.95’

Size and Material: 18’’ by 12’’ Rough Poured Concrete Duct in Good Condition

0.5’’ Ground Cable in Good Condition

3.95’

Top Depth

4.91’

Bottom Depth

(Top of Duct) – 927.92’

(Bottom of Duct) - 926.96’

(Top of Ground) - 927.98

Survey Marker Elevation – 931.87’

Ground Cable

3.89’

DATE MARKED: 9/7/23 STAFF: Taylor & Blair

CONDITIONS:

TEST PIT NO: 3 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 9’’ OD Private Plastic Domestic Water Pipe at a top depth of 3.60’.

Utility requested to be exposed: Water Pipe

Utility found or exposed: Private Plastic Domestic Water Pipe

Test Pit Coordinates: N: 59653.76 E: 57204.51

Cut Depth (From Top of Utility): 3.60’

Size and Material: 9’’ OD Plastic Water Pipe in Good Condition

Type of survey marker and ribbon color: Steel Pin/Blue Ribbon

Location of survey mark: Center of Pipe

3.60’

Top of Utility

(Top) –930.12’

Survey Marker Elevation – 933.72’

CONDITIONS:

TEST PIT NO: 4 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 11’’ OD Private Ductile Iron Fire Protection Water Pipe at a top depth of 3.60’.

Utility found or exposed: Private Ductile Iron Fire Protection Water Pipe

Test Pit Coordinates: N: 59656.98 E: 57207.37

Cut Depth (From Top of Utility): 3.60’

Size and Material: 11’’ OD Ductile Iron Water Pipe in Good Condition

Top of Utility

(Top) –930.16’

Survey Marker Elevation – 933.76’

CONDITIONS:

TEST PIT NO: 5 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed two 2’’ Plastic Communication Conduits at a top depth of 2.05’.

Utility requested to be exposed: Communication Line

Utility found or exposed: Two Plastic Communication Conduits

Test Pit Coordinates: N: 59690.28 E: 57178.75

Cut Depth (From Top of Utility): 2.05’

Size and Material: 2’’ Plastic Conduits in Good Condition

Soil or ground type: Compacted Clay and Rock

Type of survey marker and ribbon color: Steel Pin/Orange Ribbon

Location of survey mark: Center of Two Conduits

Communication Conduits

2.05’

Top of Utility

(Top) –930.71’

Survey Marker Elevation – 932.76’

CONDITIONS:

TEST PIT NO: 6 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 2.5’’ Plastic Communication Conduit at a top depth of 2.75’.

Utility found or exposed: Plastic Communication Conduit

Test Pit Coordinates: N: 59659.65 E: 57216.16

Cut Depth (From Top of Utility): 2.75’

Size and Material: 2.5’’ Plastic Conduit in Good Condition

Location of survey mark: Center of Conduit

Communication Conduit

2.75’

Top of Utility

(Top) –930.01’

Survey Marker Elevation – 932.76’

CONDITIONS:

TEST PIT NO: 7 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 25’’ OD Terracotta Storm Pipe at a top depth of 6.56’.

Utility requested to be exposed: Storm Pipe

Utility found or exposed: Terracotta Storm Pipe

Test Pit Coordinates: N 59673.24 E: 57222.18

Cut Depth (From Top of Utility): 6.56’

Size and Material: 25’’ OD Terracotta Pipe in Good Condition

Type of survey marker and ribbon color: Steel Pin/Green Ribbon

Storm Pipe

6.56’

Top of Utility

(Top) –927.47’

Survey Marker Elevation – 934.03’

CONDITIONS:

TEST PIT NO: 8 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 2.5’’ Plastic Communication Conduit at a top depth of 1.62’.

Utility found or exposed: Plastic Communication Conduit

Test Pit Coordinates: N: 59699.81 E: 57166.87

Cut Depth (From Top of Utility): 1.62’

Size and Material: 2.5’’ Plastic Conduit in Good Condition

1.62’

Top of Utility

(Top) –931.04’

Survey Marker Elevation – 932.66’

DATE MARKED: 9/9/23 STAFF: Taylor & Blair

CONDITIONS:

TEST PIT NO: 9 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 4.5’’ Plastic Gas Pipe at a top depth of 0.96’.

Utility requested to be exposed: Gas Pipe

Utility found or exposed: Plastic Gas Pipe

Test Pit Coordinates: N: 59716.03 E: 56470.67

Cut Depth (From Top of Utility): 0.96’

Size and Material: 4.5’’ Plastic Pipe in Good Condition

Type of survey marker and ribbon color: Steel Pin/Yellow Ribbon

Gas Pipe

0.96’

Top of Utility

(Top) –936.91’

Survey Marker Elevation – 937.87’

CONDITIONS:

TEST PIT NO: 10 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 4.5’’ Plastic Gas Pipe at a top depth of 1.11’.

Test Pit Coordinates: N: 59295.14 E: 56739.28

Cut Depth (From Top of Utility): 1.11’

Size and Material: 4.5’’ Plastic Pipe in Good Condition

Soil or ground type: Clay and Sand

1.11’

Top of Utility

(Top) –914.91’

Survey Marker Elevation – 916.02’

DATE MARKED: 9/13/23 STAFF: Taylor & Blair

CONDITIONS:

TEST PIT NO: 11 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 10’’ OD Terracotta Storm Pipe at a top depth of 5.84’.

Utility requested to be exposed: Storm Pipe

Utility found or exposed: Terracotta Storm Pipe

Test Pit Coordinates: N: 59192.55 E: 56900.52

Cut Depth (From Top of Utility): 5.84’

Size and Material: 10’’ OD Terracotta Pipe in Good Condition

Storm Pipe

5.84’

Top of Utility

(Top) –915.02’

Survey Marker Elevation – 920.86’

CONDITIONS:

TEST PIT NO: 12 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 12’’ OD Metal Sanitary Pipe encases in rough poured concrete with a 20’’ diameter at a top depth of 3.55’. The 12’’ pipe size and material was observed from closest access point. Actual top depth of utility could not be determined due to poured concrete.

Utility requested to be exposed: Sanitary Pipe

Utility found or exposed: Metal Sanitary Pipe covered in Rough Poured Concrete

Test Pit Coordinates: N: 59202.39 E: 56876.95

Cut Depth (From Top of Concrete): 3.55’

Size and Material: 12’’ OD Metal Pipe, Condition can not be determined due to poured concrete

Soil or ground type: Clay and Rock

Poured Concrete

3.55’

(Top of concrete) – 915.74’

Survey Marker Elevation – 919.29’

CONDITIONS:

TEST PIT NO: 13 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 30’’ by 13’’ Rough Poured Concrete Communication Duct with a top depth of 2.21’ and a bottom depth of 3.34’.

Utility found or exposed: 30’’ by 13’’ Rough Poured Concrete Communication Duct

Test Pit Coordinates: N: 59231.13 E: 56824.24

Cut Depth (From Top of Utility): 2.21’

Size and Material: 30’’ by 13’’ Rough Poured Concrete Duct in Good Condition

Communication Duct

2.21’

3.34’

(Top of Duct) – 915.61’

(Bottom of Duct) - 914.48’

Survey Marker Elevation – 917.82’

COM DUCT

CONDITIONS:

TEST PIT NO: 14 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed an 18’’ by 22’’ Rough Poured Concrete Electric Duct with a top depth of 2.25’ and a bottom depth of 4.05’.

Utility requested to be exposed: Electric Line

Utility found or exposed: 18’’ by 22’’ Rough Poured Concrete Electric Duct

Test Pit Coordinates: N: 59230.75 E: 56824.84

Cut Depth (From Top of Utility): 2.25’

Size and Material: 18’’ by 22’’ Rough Poured Concrete Duct in Good Condition

2.25’

4.05’

(Top of Duct) – 915.57’

(Bottom of Duct) - 913.77’

Survey Marker Elevation – 917.82’

CONDITIONS:

TEST PIT NO: 15 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 4.5’’ OD Plastic Gas Pipe at a top depth of 1.43’. Crew also exposed a 1.5’’ OD Metal Unidentified Pipe at a top depth of 1.06’

Utility requested to be exposed: Gas Pipe

Utility found or exposed: (A) Plastic Gas Pipe

(B) Unknown Metal Pipe

Test Pit Coordinates: N: 59197.96 E: 56902.87

Cut Depth (From Top of Utility): (A) 1.43’

(B) 1.06’

Size and Material: 4.5’’ OD Plastic Pipe in Good Condition

1.5’’ OD Metal Pipe in Fair Condition

Soil or ground type: Clay and Sand

Location of survey mark: Center of Gas Pipe

1.43’

Top of Utility

Elevation of Utility

(Top Gas) –919.14’

(Top Unidentified) - 919.51’

Survey Marker Elevation – 920.57’

Unknown Pipe

1.06’

Top of Utility

CONDITIONS:

TEST PIT NO: 16 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 9’’ OD Private Ductile Iron Domestic Water Pipe at a top depth of 2.63’.

Utility found or exposed: Private Ductile Iron Domestic Water Pipe

Test Pit Coordinates: N: 59199.66 E: 56889.98

Cut Depth (From Top of Utility): 2.63’

Size and Material: 9’’ OD Ductile Iron Water Pipe in Good Condition

2.63’

Top of Utility

(Top) –916.75’

Survey Marker Elevation – 919.38’

CONDITIONS:

TEST PIT NO: 17 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 11’’ OD Private Ductile Iron Fire Protection Water Pipe at a top depth of 2.91’.

Test Pit Coordinates: N: 59196.42 E: 56890.01

Cut Depth (From Top of Utility): 2.91’

Size and Material: 11’’ OD Ductile Iron Water Pipe in Good Condition

2.91’

Top of Utility

(Top) –916.71’

Survey Marker Elevation – 919.62’

CONDITIONS:

TEST PIT NO: 18 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 14.5’’ by 12’’ Rough Poured Concrete Electric Duct with a top depth of 1.62’ and a bottom depth of 2.69’.

Utility found or exposed: 14.5’’ by 12’ Rough Poured Concrete Electric Duct

Test Pit Coordinates: N: 59311.54 E: 57605.69

Cut Depth (From Top of Utility): 1.62’

Size and Material: 14.5’’ by 12’’ Rough Poured Concrete Duct in Good Condition

1.62’

2.69’

(Top of Duct) – 940.07’

(Bottom of Duct) - 939.00’

Survey Marker Elevation – 941.69’

CONDITIONS:

TEST PIT NO: 19 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 11’’ OD Private Plastic Domestic Water Pipe at a top depth of 4.15’.

Test Pit Coordinates: N: 59297.54 E: 57604.33

Cut Depth (From Top of Utility): 4.15’

Size and Material: 11’’ OD Plastic Water Pipe in Good Condition

4.15’

Top of Utility

(Top) –937.51’

Survey Marker Elevation – 941.66’

CONDITIONS:

TEST PIT NO: 20 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 11’’ OD Private Ductile Iron Fire Protection Water Pipe at a top depth of 4.15’.

Test Pit Coordinates: N: 59299.94 E: 57606.79

Cut Depth (From Top of Utility): 4.15’

Size and Material: 11’’ OD Water Pipe in Good Condition

4.15’

Top of Utility

(Top) –937.62’

Survey Marker Elevation – 941.77’

TEST PIT REPORT – PROJECT #596-21-104

DATE MARKED: 3/18/23 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 1 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 4.5’’ OD Private Plastic Communication Conduit at a top depth of 1.96’.

Utility requested to be exposed: Communication Conduit

Utility found or exposed: Private Plastic Communication Conduit

Test Pit Coordinates: N: 58664.18 E: 56362.26

Cut Depth (From Top of Utility): 1.96’

Size and Material: 4.5’’ OD Plastic Communication Conduit in Good Condition

1.96’

Top of Utility

(Top) –908.26’

Survey Marker Elevation – 910.22’

DATE MARKED: 3/19/24 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 2 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 25’’ by 14’’ Rough Poured Concrete Electric Duct with a top depth of 2.43’ and a bottom depth of 3.60’.

Utility found or exposed:25’’ by 14’’ Rough Poured Concrete Electric Duct

Test Pit Coordinates: N: 58676.11 E: 56371.42

Cut Depth (From Top of Utility): 2.43’

Size and Material: 25’’ by 14’’ Rough Poured Concrete Duct in Good Condition

Soil or ground type: Clay, Rock, and Gravel

2.43’

(Top of Duct) – 907.61’

(Bottom of Duct) - 906.44’

Survey Marker Elevation – 910.04’

DATE MARKED: 3/19/23 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 3 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 1.5’’ OD Steel Chiller Pipe at a top depth of 2.79’. Utility is labeled as chiller lines according to records.

Utility requested to be exposed: Chiller Pipe

Utility found or exposed: Steel Chiller Pipe

Test Pit Coordinates: N: 58680.28 E: 56374.70

Cut Depth (From Top of Utility): 2.79’

Size and Material: 1.5’’ OD Steel Chiller Pipe in Good Condition

Soil or ground type: Clay and Gravel

Chiller Pipe

2.79’

Top of Utility

(Top) –907.20’

Survey Marker Elevation – 909.99’

CONDITIONS:

TEST PIT NO: 4 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed three 1’’ OD Steel Chiller Pipes at a top depth of 1.51’. Utility is labeled as chiller lines according to records.

Utility found or exposed: Three Steel Chiller Pipe

Test Pit Coordinates: N: 58683.78 E: 56377.47

Cut Depth (From Top of Utility): 1.51’

Size and Material: Three 1’’ OD Steel Chiller Pipe in Fair Condition

Chiller Pipes

1.51’

Top of Utility

(Top) –908.45’

Survey Marker Elevation – 909.96’

CONDITIONS:

TEST PIT NO: 5 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed two 2’’ OD Metallic Unidentified Lines and a 1.5’’ OD Non-Metallic Unidentified Line at a top depth of 2.61’.

Utility requested to be exposed: Unidentified Line

Utility found or exposed: Two Metallic Unidentified Line

One Non-Metallic Unidentified Line

Test Pit Coordinates: N: 58692.67 E: 56384.48

Cut Depth (From Top of Utility): 2.61’

Size and Material: Two 2’’ OD Metallic Lines in Good Condition

One 1.5’’ OD Non-Metallic Line in Good Condition

Type of survey marker and ribbon color: Steel Pin/Pink Ribbon

Location of survey mark: Center of Center Line

Unidentified Lines

2.61’

Top of Utility

(Top) –907.29’

Survey Marker Elevation – 909.90’

CONDITIONS:

TEST PIT NO: 6 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 7’’ OD Ductile Iron Unidentified Pipe at a top depth of 3.17’.

Utility requested to be exposed: Unidentified Line

Utility found or exposed: Unidentified Ductile Iron Pipe

Test Pit Coordinates: N: 58732.78 E: 56374.87

Cut Depth (From Top of Utility): 3.17’

Size and Material: 7’’ OD Ductile Iron Unidentified Pipe in Good Condition

Soil or ground type: Clay, Rock, and Gravel

Unidentified Pipe

3.17’

Top of Utility

(Top) –905.91’

Survey Marker Elevation – 909.08’

DATE MARKED: 3/13/24 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 7 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 21’’ by 4’’ Rough Poured Concrete Electric Duct with a top depth of 1.44’ and a bottom depth of 1.79’.

Utility found or exposed:21’’ by 4’’ Rough Poured Concrete Electric Duct

Test Pit Coordinates: N: 58737.44 E: 56374.66

Cut Depth (From Top of Utility): 1.44’

Size and Material: 21’’ by 4’’ Rough Poured Concrete Duct in Good Condition

1.44’

1.79’

(Top of Duct) – 907.35’

(Bottom of Duct) – 907.00’

Survey Marker Elevation – 908.79’

DATE MARKED: 3/13/23 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 8 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed an 8.5’’ OD Private Plastic Domestic Water Pipe at a top depth of 3.75’.

Test Pit Coordinates: N: 58739.98 E: 56372.05

Cut Depth (From Top of Utility): 3.75’

Size and Material: 8.5’’ OD Plastic Domestic Water Pipe in Good Condition

Soil or ground type: Clay and Rocks

3.75’

Top of Utility

(Top) –905.01’

Survey Marker Elevation – 908.76’

CONDITIONS:

TEST PIT NO: 9 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed an end of a 3.5’’ OD Private Steel Telephone Conduit at a top depth of 1.88’. A 1’’ Telephone Cable exits the end of the conduit and is direct buried at a cut depth of 1.91’

Utility requested to be exposed: Telephone Line

Utility found or exposed: 3.5’’ OD Private Steel Telephone Conduit

1’’ Telephone Cable

Test Pit Coordinates: N: 58768.53 E: 56363.79

Cut Depth (From Top of Utility): Conduit – 1.88’ Cable – 1.91’

Size and Material: 3.5’’ OD Steel Telephone Conduit in Poor Condition

1’’ Telephone Cable in Good Condition

Soil or ground type: Clay and Rocks

Telephone Cable

1.88’

1.91’

(Conduit Top) –906.15’

(Cable Top) –906.12’

Survey Marker Elevation – 908.03’

Telephone Conduit

CONDITIONS:

TEST PIT NO: 10 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 7’’ OD Private Ductile Iron Drain Pipe at a top depth of 1.94’.

Utility requested to be exposed: Drain Pipe

Utility found or exposed: Private Ductile Iron Drain Pipe

Test Pit Coordinates: N: 58767.75 E: 56358.83

Cut Depth (From Top of Utility): 1.94’

Size and Material: 7’’ OD Private Ductile Iron Drain Pipe in Good Condition

Drain Pipe

1.94’

Top of Utility

(Top) –906.28’

Survey Marker Elevation – 908.22’

CONDITIONS:

TEST PIT NO: 11 & 12 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed Six 2.5’’ OD Private Plastic Communication Conduits at a top depth of 0.91’. Test holes 11 an 12 were combined into one test hole marker due to being a conduit run.

Utility requested to be exposed: Two Communication Lines

Utility found or exposed: Six 2.5’’ OD Private Plastic Communication Conduits

Test Pit Coordinates: N: 58773.47 E: 56356.29

Cut Depth (From Top of Utility): 0.91’

Size and Material: Six 2.5’’ OD Private Plastic Communication Conduits in Good Condition

Location of survey mark: Center of Conduits

Communication Conduits

0.91’

Top of Utility

(Top) –907.08’

Survey Marker Elevation – 907.99’

& 12

DATE MARKED: 3/1/23 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 13 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 10’’ OD Coated Metallic Unidentified Pipe at a top depth of 2.81’. A 7’’ OD Terracotta Unidentified Pipe was exposed at a top depth of 1.41’ perpendicular to the Coated Metallic Pipe.

Utility requested to be exposed: Unidentified Line

Utility found or exposed: Coated Metallic Unidentified Pipe

Terracotta Unidentified Pipe

Test Pit Coordinates: N: 58801.55 E: 56343.09

Cut Depth (From Top of Utility): Coated Metallic – 2.81’ Terracotta – 1.41’

Size and Material: 10’’ OD Coated Metallic Unidentified Pipe in Good Condition

7’’ OD Terracotta Unidentified Pipe in Good Condition

Soil or ground type: Clay, Rocks, Roots, and Stone Dust

Location of survey mark: Center of Metallic Pipe

Metallic Pipe

1.41’

2.81’

(Terracotta Top) –906.16’

(Metallic Top) – 904.76’

Survey Marker Elevation – 907.57’

Terracotta Pipe

DATE MARKED: 3/12/23 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 14 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 12’’ OD Ductile Iron Chiller Pipe at a top depth of 2.97’. A 6’’ OD Plastic Unidentified Pipe was exposed at a top depth of 1.25’ perpendicular to the Chiller Pipe.

Utility requested to be exposed: Chiller Line

Utility found or exposed: Ductile Iron Chiller Pipe

Plastic Unidentified Pipe

Test Pit Coordinates: N: 58817.08 E: 56334.83

Cut Depth (From Top of Utility): Chiller – 2.97’ Plastic – 1.25’

Size and Material: 12’’ OD Ductile Iron Chiller Pipe in Good Condition

6’’ OD Plastic Unidentified Pipe in Good Condition

Location of survey mark: Center of Chiller Pipe

1.25’

2.97’

(Plastic Top) –906.18’

(Chiller Top) – 904.46’

Survey Marker Elevation – 907.43’

Plastic Pipe

CONDITIONS:

TEST PIT NO: 15 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 10’’ OD Ductile Iron Chiller Pipe at a top depth of 3.10’.

Utility requested to be exposed: Chiller Line

Test Pit Coordinates: N: 58818.69 E: 56332.79

Cut Depth (From Top of Utility): 3.10’

Size and Material: 10’’ OD Ductile Iron Chiller Pipe in Good Condition

3.10’

Top of Utility

(Top) –904.42’

Survey Marker Elevation – 907.52’

CONDITIONS:

TEST PIT NO: 16 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 2.5’’ OD Plastic Gas Pipe at a top depth of 1.68’.

Test Pit Coordinates: N: 58856.12 E: 56315.24

Cut Depth (From Top of Utility): 1.68’

Size and Material: 2.5’’ OD Plastic Gas Pipe in Good Condition

Soil or ground type: Clay, Sand, and Roots

1.68’

Top of Utility

(Top) –907.73’

Survey Marker Elevation – 909.41’

CONDITIONS:

TEST PIT NO: 17 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 4.5’’ OD Steel Coated Gas Pipe at a top depth of 1.46’. Pipe coating showed signs of rust and wear.

Utility found or exposed: Steel Coated Gas Pipe

Test Pit Coordinates: N: 58884.01 E: 56295.64

Cut Depth (From Top of Utility): 1.46’

Size and Material: 4.5’’ OD Plastic Gas Pipe in Fair Condition

Soil or ground type: Clay, Sand, and Roots

1.46’

Top of Utility

(Top) –909.83’

Survey Marker Elevation – 911.29’

DATE MARKED: 3/14/23 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 18 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 13.5’’ OD Plastic Chiller Pipe at a top depth of 3.27’.

Utility found or exposed: Plastic Chiller Pipe

Test Pit Coordinates: N: 59105.28 E: 56590.76

Cut Depth (From Top of Utility): 3.27’

Size and Material: 13.5’’ OD Plastic Chiller Pipe in Fair Condition

3.27’

Top of Utility

(Top) –909.04’

Survey Marker Elevation – 912.31’

CONDITIONS:

TEST PIT NO: 19 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 25’’ ID Cast Iron Drain Pipe at a top depth of 6.85’. Inner diameter of pipe was measured from nearest structure.

Utility requested to be exposed: Drain Pipe

Utility found or exposed: Cast Iron Drain Pipe

Test Pit Coordinates: N: 59105.56 E: 56590.45

Cut Depth (From Top of Utility): 6.85’

Size and Material: 25’’ ID Cast Iron Drain Pipe in Good Condition

Drain Pipe

6.85’

Top of Utility

(Top) –905.48’

Survey Marker Elevation – 912.33’

CONDITIONS:

TEST PIT NO: 20 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 11’’ OD Ductile Iron Chiller Pipe at a top depth of 3.62’.

Test Pit Coordinates: N: 59106.39 E: 56589.53

Cut Depth (From Top of Utility): 3.62’

Size and Material: 11’’ OD Ductile Iron Chiller Pipe in Good Condition

3.62’

Top of Utility

(Top) –908.83’

Survey Marker Elevation – 912.45’

CONDITIONS:

TEST PIT NO: 21 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed an 8.5’’ OD Metallic Unidentified Pipe at a top depth of 4.27’.

Utility requested to be exposed: Unidentified Pipe

Utility found or exposed: Metallic Unidentified Pipe

Test Pit Coordinates: N: 59305.78 E: 56866.26

Cut Depth (From Top of Utility): 4.27’

Size and Material: 8.5’’ OD Metallic Unidentified Pipe in Good Condition

Unidentified Pipe

4.27’

Top of Utility

(Top) –914.40’

Survey Marker Elevation – 918.67’

CONDITIONS:

TEST PIT NO: 22 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 12’’ OD Plastic Chiller Pipe at a top depth of 4.31’.

Utility found or exposed: Plastic Chiller Pipe

Test Pit Coordinates: N: 59308.19 E: 56864.47

Cut Depth (From Top of Utility): 4.31’

Size and Material: 12’’ OD Plastic Chiller Pipe in Good Condition

4.31’

Top of Utility

(Top) –914.16’

Survey Marker Elevation – 918.47’

CONDITIONS:

TEST PIT NO: 23 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed an 8.5’’ OD Ductile Iron Chiller Pipe at a top depth of 4.57’.

Test Pit Coordinates: N: 59308.88 E: 56863.45

Cut Depth (From Top of Utility): 4.57’

Size and Material: 8.5’’ OD Ductile Iron Chiller Pipe in Good Condition

4.57’

Top of Utility

(Top) –913.96’

Survey Marker Elevation – 918.53’

CONDITIONS:

TEST PIT NO: 24 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 10.5’’ OD Ductile Iron Fire Protection Water Pipe at a top depth of 2.52’.

Utility found or exposed: Ductile Iron Fire Protection Water Pipe

Test Pit Coordinates: N: 58781.46 E: 57242.63

Cut Depth (From Top of Utility): 2.52’

Size and Material: 10.5’’ OD Ductile Iron Fire Protection Water Pipe in Good Condition

Pavement or ground type: 6’’ of Pavement

2.52’

Top of Utility

(Top) –931.74’

Survey Marker Elevation – 934.26’

CONDITIONS:

TEST PIT NO: 25 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed a 8.5’’ OD Plastic Domestic Water Pipe at a top depth of 2.57’.

Utility found or exposed: Plastic Domestic Water Pipe

Test Pit Coordinates: N: 58784.46 E: 57245.15

Cut Depth (From Top of Utility): 2.57’

Size and Material: 8.5’’ OD Plastic Domestic Water Pipe in Good Condition

Pavement or ground type: 5’’ of Pavement

2.57’

Top of Utility

(Top) –931.68’

Survey Marker Elevation – 934.25’

CONDITIONS:

TEST PIT NO: 26 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed an 8.5’’ OD Cast Iron Water Pipe at a top depth of 3.92’.

Utility requested to be exposed: Water Line

Utility found or exposed: Cast Iron Water Pipe

Test Pit Coordinates: N: 58786.78 E: 57246.04

Cut Depth (From Top of Utility): 3.92’

Size and Material: 8.5’’ OD Cast Iron Water Pipe in Good Condition

Pavement or ground type: 6.5’’ of Pavement

3.92’

Top of Utility

(Top) –930.32’

Survey Marker Elevation – 934.24’

Water

CONDITIONS:

TEST PIT NO: 27 Survey Marker: Steel pin

OBSERVATIONS:

Crew exposed two 1’’ OD Metallic Unidentified lines at a top depth of 3.07’.

Utility requested to be exposed: Unidentified Line

Utility found or exposed: Two Metallic Unidentified Lines

Test Pit Coordinates: N: 58796.15 E: 57254.92

Cut Depth (From Top of Utility): 3.07’

Size and Material: Two 1’’ OD Metallic Unidentified Lines in Good Condition

Pavement or ground type: 7’’ of Pavement

Location of survey mark: Center of two lines

Unidentified Lines

3.07’

Top of Utility

(Top) –931.05’

Survey Marker Elevation – 934.12’

DATE MARKED: 3/16/23 STAFF: Taylor & Danny

CONDITIONS:

TEST PIT NO: 28 Survey Marker: Steel pin

OBSERVATIONS:

Crew attempted to expose utility at four different locations 28, 28A, 28B, and 28C. Field crew observed concrete slab between 3.5’’ and 4.5’’ under asphalt. VA Hospital and field crew were not comfortable cutting into the concrete slab without confirmation of purpose and use.

Utility requested to be exposed: N/A

Utility found or exposed: N/A

Test Pit Coordinates: N: 58835.14 E: 57196.32

N: 58834.42 E: 57192.68

N: 58836.51 E: 57194.26

N: 58831.91 E: 57200.30

Cut Depth (From Top of Utility): N/A

Size and Material: N/A

Pavement or ground type: 3.5’’ to 4.5’’ of Pavement

Soil or ground type: N/A

Type of survey marker and ribbon color: Steel Pin

Location of survey mark: N/A

Title Page
Cover Letter
1.0 INTRODUCTION
2.0 METHODOLOGY
2.1 Literature Review
2.2 Methodology for Field Investigation
2.3 Methodology for Delineating Streams
3.0 FINDINGS
3.1 Literature Review
3.1.1 Literature Review Summary
3.2 Field Investigation Findings
3.2.1 Wetland Summary
3.2.2 Stream Summary
4.0 REGULATORY DISCUSSION
5.0 WATERSHED CLASSIFICATION/BUFFER REQUIREMENTS
5.1 State Riparian Buffer Requirements
5.2 Local Buffer Requirements
6.0 CONCLUSIONS
Figures
Photographic Log
Cover
Preface
Contents
How Soil Surveys Are Made
Soil Map
Soil Map
Legend
Map Unit Legend
Map Unit Descriptions
Fayette County Area, Part of Fayette County, Kentucky
EkA—Elk silt loam, 0 to 2 percent slopes
EkB—Elk silt loam, 2 to 6 percent slopes
FaD3—Fairmount very rocky silty clay loam, 6 to 30 percent slopes, severely eroded (fairmount-Rock outcrop complex)
Hu—Huntington silt loam, 0 to 4 percent slopes, occasionally flooded
Md—Made land, over silty materials
MnC—McAfee silt loam, 6 to 12 percent slopes
MpC2—McAfee silty clay loam, 6 to 12 percent slopes, eroded
MpD2—McAfee silty clay loam, 12 to 20 percent slopes, eroded
MuB—Mercer silt loam, 2 to 6 percent slopes
Ne—Newark silt loam, 0 to 2 percent slopes, occasionally flooded
Ua—Urban land-Armour-Maury complex (Urban land)
uBlmA—Bluegrass-Maury silt loams, 0 to 2 percent slopes
uBlmB—Bluegrass-Maury silt loams, 2 to 6 percent slopes
uMlmC—Maury-Bluegrass silt loams, 6 to 12 percent slopes
References
Cross Section 1 - 1 yr
Cross Section 1 - 2 yr
Cross Section 1 - 10 yr
Cross Section 1 - 25 yr
Cross Section 1 - 50 yr
Cross Section 1 - 100 yr
Cross Section 2 - 1 yr
Cross Section 2 - 2 yr
Cross Section 2 - 10 yr
Cross Section 2 - 25 yr
Cross Section 2 - 50 yr
Cross Section 2 - 100 yr
Cross Section 3 - 1 yr
Cross Section 3 - 2 yr
Cross Section 3 - 10 yr
Cross Section 3 - 25 yr
Cross Section 3 - 50 yr
Cross Section 3 - 100 yr
US Fish and Wildlife Email Confirmation - No Effect 8-2-2024
20240802 NE Consistency KY_FLD_OFFICE_SA
United States Department of the Interior
FISH AND WILDLIFE SERVICE
Qualification interview
IPaC User Contact Information
20240802 NE Consistency NLEB_RW
United States Department of the Interior
FISH AND WILDLIFE SERVICE
Determination key result
Qualification interview
Project questionnaire
IPaC User Contact Information

File details come from the government source that posted it. Updated .