This document is a Request for Information (RFI) for the EHRM Infrastructure Upgrade Albion Clinic project located at the Tennessee Valley Healthcare System Albion Street VA Clinic in Nashville, TN. The project involves furnishing labor, materials, and equipment to prepare the site for building operations per the drawings and specifications.

The RFI contains questions from the contractor READIGOV related to various aspects of the project, including data cabling, grounding and bonding, existing infrastructure, room phasing, electrical panels, core switching, asbestos, and receptacle requirements. The government responded to each question, often directing the contractor to refer to the specifications, drawings, and Statement of Work for additional details. The solicitation has a set-aside for Service-Disabled Veteran-Owned Small Businesses, a value range of $100,000 to $250,000, and requires a site visit. Proposals are due by the date stated in the document.

View the file

Other files

File Type Posted
36C24924R0098 0008.docx DOCX document
36C24924R0098 0007.docx DOCX document
36C24924R0098 0006.docx DOCX document
RFI 12-22 - PCG.pdf PDF
RFI Sheet for 36C24924R0098 Meharry Clinic Room 150 TR Room Upgrade .xlsx XLSX spreadsheet
36C24924R0098 0005.docx DOCX document
Albion Clinic Lobby - 626-22-705QA - EHRM Infrastructure Upgrade Albion Clinic Pre-Bid Site Visit 2.pdf PDF
RFI 01 - NetPlanner Systems - 10-15-24.pdf PDF
RFI 02 - NetPlanner Systems - 10-15-24.pdf PDF
RFI 1-11 - PCG.pdf PDF
36C24924R0098 0004.docx DOCX document
Pre-bid site visit Sign in - Albion Street.pdf PDF
Albion Clinic meeting spot site visit 2.pdf PDF
36C24924R0098 0003.docx DOCX document
Albion Clinic meeting spot.pdf PDF
36C24924R0098 0002.docx DOCX document
Amendment RFI Response.docx DOCX document
36C24924R0098 0001.docx DOCX document
RFI Form.docx DOCX document
Contractor EMR Certification Form.docx DOCX document
Calculation of Self Performed Work.docx DOCX document
Wage Determination.docx DOCX document
22-153 BD Dwgs.pdf PDF
22-153 BD Specs.pdf PDF
36C24924R0098_1.docx DOCX document
UEI _ TAX ID.docx DOCX document
ATTACHMENT 6- Schedule-of-Values-Sample Template.xlsx XLSX spreadsheet
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION (RFI)

36C24924R0098

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 1 DATE: SPEC/DWG. REFERENCE:

Floor Plans / Drawing

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

VA HEFP SEP (SOCAMES 16) Design Alert 16 The VA recently released Design Alert 16 specifying Work Area Outlet (WAO) counts and density. Based on the section “If in construction”, the direction from the VA states if there are more than two (2) drops per WAO, consider reducing to two (2).

Design Alert 16 also states that two (2) Category 6A cables fit within a 3/4” conduit with 40% fill capacity, and if this is the case the existing conduit can be reused.

1.The floor plans show each WAO having three (3) drops, two (2) data and one (1) voice. Will Design Alert 16 impact this project, or should contractor bid as shown with 1V/2D to each outlet?

2.If bid as shown, should the bid assume existing conduit can be reused and does not require upsizing the conduit to fit three (3) CAT6A cables?

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

mailto:Brian.Bentley@va.gov VHATVHKiteK Text Box Design Alert 16 does not apply. Existing can reused if deemed necessary.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 2 DATE: 10/16 SPEC/DWG. REFERENCE:

Drawings

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

Sheet E-002, Technology General Notes #25 states to provide J-hooks where cable tray is not shown. There is no horizontal cable tray shown in the design drawings.

1.Please provide existing cable tray routing, if any existing, for horizontal distribution to WAOs.

2.If there is no existing cable tray, provide what type of horizontal routing is existing, e.g. j-hooks or conduit.

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

You will only be working in the areas specified on drawings/specs. Refer to drawings and specs what to use if neccessary.

mailto:Brian.Bentley@va.gov

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 3 DATE: 10/16 SPEC/DWG. REFERENCE:

Ceiling Type

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

1. What type of existing ceiling is present within the project scope of work area?

2. Will telecommunications cabling be routed above drop ceiling throughout the Community Based Outpatient Clinic (CBOC), or is there an interstitial space that will be used?

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

Standard Ceiling tiles. Please see drawings and specs on where construction will be.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 4 DATE: 10/16 SPEC/DWG. REFERENCE:

Grounding and Bonding

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

Keynote 3, on ET401, states to “run grounding conductor for SBB to primary bonding busbar (PBB). The PBB does not exist run TBB to the electrode system, as defined in section 250 of NFPA 70.” The TBB within the design drawings is currently shown as #1/0, but sizing will need to be based on the distance ran per TIA standards.

There will be a significant large cost difference between grounding from the new SBB to an existing PBB, or to the electrode system.

1.Please confirm if there is an existing PBB within the Albion Clinic that can be connected via grounding conductor and provide the location of the PBB.

2. If confirmation is not provided regarding an existing PBB being available, please provide direction on whether the bid should assume connection to the grounding electrode system instead of connection to an existing PBB. Provide the location of the building grounding electrode system.

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

mailto:Brian.Bentley@va.gov VHATVHKiteK Text Box See drawings and specs. Spec 27 05 26 - 9 section H helps. There were two site visits scheduled to analyze.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 5 DATE: 10/16 SPEC/DWG. REFERENCE:

Existing Infrastructure

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

Keynote 1 on ET101 states “All data devices shown are existing and are to be replaced with new devices and cut-in boxes. Run new CAT 6A cable to each data drop. Cables to remain if existing cables are CAT 6. Coordinate with

COR.”

1. Please provide clarification on which cables within the project scope exist as CAT 6.

2. Please provide clarification, will junction boxes (cut-in boxes) and faceplates be existing to remain, or will all Work Area Outlet (WAO) junction boxes and faceplates be replaced with new?

3.Can conduits to WAO be reused?

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

1. There were two site visits to see the existing cable

2. Existing to remain

3. Yes

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 6 DATE: 10/16 SPEC/DWG. REFERENCE:

Room Phasing

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

It is understood that the Contractor will furnish the Telecom Room Phasing Plan.

The existing rack in same location as new rack.

1. How many hopper switches will the VA provide for alleviating down time between the old rack demolition, and the new rack instllation?

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

See specs, drawings, and SOW. Plan accordingly to alleviate any downtime for Clinical operations.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 7 DATE: 10/16 SPEC/DWG. REFERENCE:

Existing Panel Schedules (Electrical) REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

The existing panel schedules shown within the drawings, LM Section 1 and LM Section 2, show a new three-pole breaker for rack power.

1. Please confirm what the existing condition is for both panels, Section 1 and 2. Are the existing breakers spare, space, single pole breakers, existing three pole breakers? What modification is required?

2. Have calculations been performed to confirm the existing panels can handle the new loads per NEC 220.87? Or is 30-day metering required?

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

1) See Specs and drawings.

2) AE designed this with new loads in mind.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 8 DATE: 10/16 SPEC/DWG. REFERENCE:

Core Switch REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

ET601 shows a new rack mounted fiber MDA-1 core switch and patch panel. Keynote #2 states to provide 24 strand OM4 multimode fiber optic cabling from existing Demarc 150 to fiber rack in Room 150. Keynote #3 states to provide 24 strand OM4 multimode fiber optic cabling from MDA-1 to Cisco Core Switch.

1. Is the new core switch, referenced in keynote #3, Government Furnished Government Installed (GFGI)?

2. Are two (2) 24-strand OM4 cables required to be provided between the existing internet service provider fiber box in Room 150, and the MDA-1 Core Switch, or are keynote #2 and #3 referencing the same connection and same 24-strand fiber?

3. Will the Contractor be required to coordinate with the internet service provider for new fiber connection between existing internet service provider fiber box in Room 150, or will the internet service provider provide the fiber connection?

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

1) View Specs, Drawings, and Drawing notes

2) two (2)

3) Contractor will have to coordinate.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 9 DATE: 10/16 SPEC/DWG. REFERENCE:

Asbestos

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

REPLY:

1. Are there any known asbestos concerns within the scope of work area?

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

There are no known asbestos concerns within the scope of work area.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 10 DATE: 10/16 SPEC/DWG. REFERENCE:

POTS Scope

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

Drawings illustrate 1V/2D (voice drop, two data drops) Work Area Outlets (WAO). Based on other project experience, the VA does not use Plain Old Telephone System (POTS).

1. Is the phone system POTS or VoIP?

2. If VoIP, can the WAO be 2D only?

3. If POTS, what is the scope?

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

It's IP. Refer to scope, specs, and drawings.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 11 DATE: 10/16 SPEC/DWG. REFERENCE:

Rack Clearances

REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

Sheet ET401 shows equipment within the new rack clearance, and full clearance is not provided due to the space of the room.

1. Is the rack clearance shown on ET401 acceptable to the VA?

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

Refer to specs and drawings.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 12 DATE: 10/16 SPEC/DWG. REFERENCE:

Schneider Switch REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

Sheet ET401, key note #11, states to “Connect back to NETBOTZ 755 APC Schneider switch. Provide APC NETBOTZ camera/humidity/temp sensor.”

1. Is the Schneider switch existing? And if so, where is it located?

2. If the Schneider switch is to be new, is it Government Furnished Government Installed (GFGI)?

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

Refer to specs and drawings. There were two site visits to investigate.

PROJECT NUMBER: 626-22-705QA Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents.

When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.

PROJECT TITLE: EHRM Infrastructure Upgrade Albion Clinic

PROJECT LOCATION: Albion Street VA Clinic, 1818 Albion St Suite 114, Nashville, TN 37208

TO:

Brian Bentley Brian.Bentley@va.gov

RFI NO.: 13 DATE: 10/16 SPEC/DWG. REFERENCE:

Receptacle Requirement REPLY NEEDED BY: Oct 19

INFORMATION NEEDED:

Sheet ET401, keynote #5 states “two twist-lock receptacles, NEMA L21-30R, mounted to the side of the cable tray, for rack mounted zone power distribution unit (Z-PDU), 30A/3PH/4W+G.”

Detail 2/ET502 calls out both above rack receptacles being 208V, 20A, three phase circuit, terminating in a NEMA L21-20R locking receptacle.

1.Please confirm which receptacle is required, L21-30R or L21-20R.

REPLY:

REPLY FROM: DATE:

ATTACHMENTS: COPY TO:

SUBMITTED BY: READIGOV, POC Lisa Dean City/State: Palm Harbor, Florida

PHONE NO.: (239) 405-5067

refer to specs and drawings.