VA Mountain Home VERDA Utility Water System Specification.pdf
PDF 290 KB Posted
- Solicitation number
- 36C24923B0014
About this file
This document outlines specifications for a VERDA Utility Water Quality System to be installed at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The system will include series sediment filtration with 5 micron and 0.5 micron pleated polypropylene filters, water softening to reduce feed water hardness for utility water heaters, electric water heaters to produce hot utility water at 140 degrees Fahrenheit with 600 gallon per hour recovery capacity, and recirculation of hot utility water. The modular system will integrate additional future water treatments if desired. It will be monitored through an expandable cloud-based predictive maintenance and monitoring system. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is soliciting proposals for installation of this VERDA Utility Water Quality System in the Sterile Processing Supply area to replace multiple point-of-use filters and upgrade functionality to meet AAMI standards for utility water quality in central sterile processing.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Office: 802.748.2322 US Toll Free: 800.748.2322 Fax: 802.748.2323
2176 Portland Street, P.O. Box 672, St. Johnsbury, VT 05819 www.verdawater.com
©VERDA 2020
THE MATERIAL AND INFORMATION CONTAINED HEREIN IS CONFIDENTIAL AND IS THE PROPERTY OF VERDA AND IS NOT TO BE USED, DISCLOSED, COPIED, TRANSFERRED, OR REPRODUCED WITHOUT THE PRIOR WRITTEN PERMISSION OF
VERDA.
6/2/2023 11:08 AM Document ID: FRM-095_B Page 1 of 5
The VERDA Utility Water Quality System:
A single point treatment for all Central Sterile Processing Utility Water is recommended to address issues with multiple point-of-use filters, current low hot water temperature, and the desire for functionality upgrades in the future. The proposed system is comprised of the following elements:
• Series sediment filtration o 5µm pleated polypropylene filter (98% retention of particles 5 microns and larger i.e., dirt, rust) o 0.5µm pleated polypropylene filter (98% retention of particles 0.5 microns and larger i.e., silt)
• Water softening o Softening of feed water for Utility Water heaters
• Utility Hot Water o Electric water heaters for hot Utility Water production
• Recirculation of hot Utility Water o Ensures consistent hot water temperatures are maintained at point-of-use faucets and SPD equipment (e.g., ultrasonic, washer-disinfectors) o Constant water flow to eliminate stagnant hot water in the Utility Water piping network, which is prone to bacteria growth, even though it is chlorinated
• Modular interconnected palletized systems o This design feature streamlines the integration, reducing both the installation time and on-site plumbing labor and materials costs o The modular design also allows for the integration of additional water treatments (e.g., pH balancing, TOC reduction) o In the future, the modular system, when additional water treatment options are desired, provides a lower cost initial set-up lower upgrade costs
• Predictive Maintenance and Monitoring System o Expandable, cloud-based monitoring system o Alarmed to alert via text or email
©VERDA 2020
THE MATERIAL AND INFORMATION CONTAINED HEREIN IS CONFIDENTIAL AND IS THE PROPERTY OF VERDA AND IS NOT
6/2/2023 11:08 AM Document ID: FRM-095_B Page 2 of 5
The proposed VERDA Utility Water Quality Treatment System includes the following requirements and specifications:
System requirements
1. Feed water:
a. Back flow / RPZ valve by facility if required
b. AAMI TIR34 / Proposed ST-108 compliant Utility Water:
i. Hardness < 150 mg/L
ii. Conductivity < 500 µS/cm
iii. 6 < pH < 91
iv. Chlorides < 250mg/L
v. TOC < 1mg/L2
vi. Total alkalinity < 400 mg/L3
vii. Color and Turbidity – Colorless, Clear, no residues
viii. Bacteria < 500 CFU/mL4
c. Minimum flow rate: 125 gpm
d. Minimum dynamic pressure: 70 psig
e. Maximum temperature: 70 °F
2. Environmental:
a. Temperature: 60 - 80 °F
b. Relative humidity: 10 – 90 % non-condensing
Note: estimated heat generation = 24,000 BTUs
3. Spatial: Rectangular - Approximately 3’-6” Deep x 16’-0” Wide x 6’-8” High
1. Includes only equipment space requirement, additional space for access and maintenance required depending on layout and final room design.
System interfaces
1. Feed water:
a. 2” NPT, female connection
2. Product water:
a. Ambient Utility Water supply: 2” NPT, female
1 Proposed ST-108 pH range of 6.5 to 9.5 2 Proposed ST-108 not have a requirement for Utility Water TOC 3 No requirement for Alkalinity in TIR:34, but there is for Proposed ST-108 4 No requirement for Bacteria in TIR:34 (only a bacteria requirement for Utility Water in TIR:34 after high level disinfection.
©VERDA 2020
THE MATERIAL AND INFORMATION CONTAINED HEREIN IS CONFIDENTIAL AND IS THE PROPERTY OF VERDA AND IS NOT
6/2/2023 11:08 AM Document ID: FRM-095_B Page 3 of 5
b. Hot Utility Water supply: 1-1/2” NPT, female
c. Hot Utility Water return: 1” NPT, female
3. Drain:
a. 3” minimum – floor drain / sink
1. 3” minimum drain trunk line routed along the perimeter of the room behind the pallets with air gap dump into floor drain / sink. 2X 2” standpipes to be located behind the softener pallet, 1X 2” standpipe located behind each of the three other pallets. Standpipes to be located a maximum of 18” above floor level. Vent / trap per local codes.
4. Electrical:
a. Sediment Filtration Pallet:
1. 1x 120V, 60Hz, 20A GFCI outlet, dedicated circuit (quad)
b. Softening Pallet:
1. 2X 120V, 60Hz, 20A GFCI outlet, dedicated circuit (duplex)
c. Brine Pallet:
1. 1X 120V, 60Hz, 20A GFCI outlet, dedicated circuit (quad)
d. Water heater pallet:
1. 2X 480V, 60Hz, three-phase, 65A FLA (54kW), MOP per local code
2. 1X 120v, 60Hz, 1-phase, 20A GFCI, dedicated duplex
5. System Weights & Footprint:
a. Sediment Filtration Pallet: ≈500lbs empty, ≈600lbs full; 50”L x 40”D x 78”H
b. Softening Pallet: ≈500lbs empty, ≈700lbs full; 50”L x 40”D x 78”H
c. Expansion & Brine Pallet: ≈400lbs empty, ≈700lbs full; 40”L x 40”D x 78”H
d. Heating Pallet: ≈700lbs empty, ≈2600lbs full; 72”L x 40”D x 78”H
System Performance
1. Ambient Utility Water:
a. Temperature: equal to feed water temperature (< 70 °F)
b. Maximum flow rate: 125 gpm
2. Hot Utility Water:
a. Temperature: 140 °F
b. Maximum flow rate: 60 gpm
c. Recovery: 600 gph
System Features – UTILITY WATER TREATMENT SYSTEM
1. Sediment filtration: Two high flow commercial / industrial grade stainless steel cartridge-style filter housings plumbed in series with filter 1, filter 2, and filter 1 and 2
©VERDA 2020
THE MATERIAL AND INFORMATION CONTAINED HEREIN IS CONFIDENTIAL AND IS THE PROPERTY OF VERDA AND IS NOT
6/2/2023 11:08 AM Document ID: FRM-095_B Page 4 of 5 bypasses. The upstream filter will remove contaminants 5 micron and larger with a progressive 25-1 µm filter while the downstream filter will remove contaminants down to 0.5 microns in size for fine particles. Filter inlet and outlet pressure gauges included.
2. Water heater feed water softening: Twin-alternating commercial / industrial grade 300,000 grain capacity softener tanks reduce the heater feed water hardness to maximize water heater life. Alternating control valves automatically open / close when softener requires regeneration. Softener 1, softener 2, and softener 1 and 2 bypasses included.
3. Water heating: Redundant 119 gallon, 54kW, commercial / industrial grade water heaters provide 140°F hot Utility Water with a 600 gph recovery capacity. Heater 1, heater 2, and heater 1 and 2 bypasses included.
4. Hot Utility Water recirculation: A recirculation pump on the Hot Utility Water return ensures that on demand hot water is always available. Bypass included.
5. Sampling ports: Five sampling ports throughout the system allow for easy water sampling to ensure AAMI compliance.
6. Modular configuration: The system can easily be reconfigured to accommodate future treatment needs
Features – Monitoring and Services
1. VERDA Universe Remote Monitoring SCADA System. Expandable, cloud-based monitoring system. Monitoring 11 signals, including but not limited to pressure, temperature, and hardness, 9 which are analog and 2 which are digital that will ensure proper function of the equipment. Parameters will be alarmed to alert via text or email to VERDA team and facility personnel as requested.
2. All monthly, quarterly, and annual testing is included based on the current release of AAMI TIR:34. Emergency testing is provided separately based on time and materials.
Standard rates are quoted below.
3. Quarterly and annual preventive maintenance is included.
4. Management of consumables is included. Actual cost of consumables is to be billed on an open purchase order. Labor to replace consumables is included provided the frequency corresponds to scheduled, quarterly preventive maintenance visits.
Replacement in between, if necessary, will be billed on a time and materials basis.
Standard rates are quoted below.
5. Included is customer access to VERDA’s on-line customer portal. All reports and documentation can be securely accessed through a browser and on smart devices.
6. Water Testing in accordance TIR:34 as follows:
©VERDA 2020
THE MATERIAL AND INFORMATION CONTAINED HEREIN IS CONFIDENTIAL AND IS THE PROPERTY OF VERDA AND IS NOT
6/2/2023 11:08 AM Document ID: FRM-095_B Page 5 of 5
• TOC – Monthly
• pH – Monthly
• Hardness – Annually
• Ionic Contaminants (copper, iron, manganese, chloride) – Annually
• The facility will be responsible for checking resistivity daily