36C24919R0128-0004001.pdf
PDF 187 KB Posted
- Solicitation number
- 36C24919R0128
About this file
36C24919R0128 0004 18-262 USP 800 ACY Addendum 2 with Spec.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24919R0128-0004000.docx | DOCX document | |
| 36C24919R0128-0003004.pdf | ||
| 36C24919R0128-0003005.pdf | ||
| 36C24919R0128-0003000.docx | DOCX document | |
| 36C24919R0128-0003008.pdf | ||
| 36C24919R0128-0003001.pdf | ||
| 36C24919R0128-0003006.pdf | ||
| 36C24919R0128-0003003.pdf | ||
| 36C24919R0128-0003007.pdf | ||
| 36C24919R0128-0003002.pdf | ||
| 36C24919R0128-0003009.pdf | ||
| 36C24919R0128-0002000.docx | DOCX document | |
| 36C24919R0128-0001005.pdf | ||
| 36C24919R0128-0001002.pdf | ||
| 36C24919R0128-0001008.pdf | ||
| 36C24919R0128-0001000.docx | DOCX document | |
| 36C24919R0128-0001006.pdf | ||
| 36C24919R0128-0001004.pdf | ||
| 36C24919R0128-0001007.pdf | ||
| 36C24919R0128-0001003.pdf | ||
| 36C24919R0128-0001001.pdf | ||
| 36C24919R0128-000.docx | DOCX document | |
| 36C24919R0128-003.pdf | ||
| 36C24919R0128-005.xlsx | XLSX spreadsheet | |
| 36C24919R0128-002.pdf | ||
| 36C24919R0128-001.docx | DOCX document | |
| 36C24919R0128-004.docx | DOCX document |
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Raleigh, NC | Indianapolis, IN | Pittsburgh, PA | Virginia Beach, VA Atlanta, GA | Minneapolis, MN | Fort Collins, CO | Las Vegas, NV www.acg-pa.com
Addendum #2
USP 800 Pharmacy Compliance for York Project # 626-308 Tennessee Valley Healthcare System, Murfreesboro Campus
May 28, 2019 From: Denny M. Murphy RA, AIA
Notice to Contractor:
The following addendum is issued as part of the Contract Documents. The work shall be carried out in accordance with the Contract Documents including these clarifications.
Item 2.1
In Specification section 09 06 00 add the basis of design for the expansion joint covers as specified in
SECTION 07 95 13 EXPANSION JOINT COVER ASSEMBLIES so that paragraph 2.5 DIVISION 05 –
METALS reads as follows:
A. SECTION 05 50 00, METAL FABRICATION
Item Finish
Steel Ladders Paint or powder coat
B. SECTION 07 95 13, EXPANSION JOINT COVER ASSEMBLIES
Material Finish Manufacturer Mfg. Color Name/No.
Exterior Wall
Cover Plate Frame
Thermoplastic Joint
Stainless steel0r Aluminum
Available in Kynar® or dark bronze anodized to match existing window trim
Johns Manville Expand-O-Gard
Style F
Exterior Wall / Roof
Cover Plate Frame
Thermoplastic Joint
Stainless steel Neo Neoprene*
Thickness:
0.060" (1.52 mm)
US 32D
stainless
Johns Manville Expand-O-Flash US32D / Black www.acg-pa.com Document Type 2
Item 2.2
Add the attached specification SECTION 08087 00 ARCHITECTURAL WINDOW FILM for the film to be applied to the existing windows that will be covered up in the new addition, shown in Detail 4 / A-304.
Denny Murphy | Project Architect 1151 Kildaire Farm Rd, Suite 120, Cary, NC 27511 P| 919-838-7629 C| 919-601-1549 E| jdoe@acg-pa.com W| www.acg-pa.com
CC: Alex Kramer, file
Alvin C. York VAMC May 28, 2019 Addendum 2 USP 800 Pharmacy Compliance Final Construction Documents Murfreesboro, TN Project No. 626-308
SECTION 08 87 00
ARCHITECTURAL WINDOW FILMS
PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Interior/Exterior Window Film
1.2 RELATED SECTIONS
This window film is to be applied to the existing windows that will be covered up by the addition of the new project per detail 5 / A-304
1.3 REFERENCES
A. ASTM International (ASTM)
1. ASTM E 903 - Standard Methods of Test for Solar Absorbance, Reflectance and Transmittance of Materials Using Integrating Spheres.
2. ASTM E 308 - Standard Recommended Practice for Spectrophotometry and Description of Color in CIE 1931 System.
1.4 SUBMITTALS
A. Manufacturer's Product Data for specified products.
B. Samples: 4 inch by 4 inch Samples of specified color and pattern for verification.
C. Submit operation and maintenance data for installed products, including precautions against harmful cleaning materials and methods.
1.5 QUALITY ASSURANCE
A. Obtain all products in this section from a single Manufacturer with a minimum of 10 years’ experience.
B. Installer: Installation shall be performed by a trained and qualified installer, specialized and experienced in work required for this project.
1.6 PRODUCT DELIVERY, STORAGE, AND HANDLING
A. Deliver products in manufacturer's original, unopened, undamaged containers with identification labels intact.
B. Product must remain in original plastic bag and boxes and have storage conditions as follows:
1. 40 °F – 90 °F (4 °C - 32 °C)
2. Out of direct sunlight
3. Clean dry area
4. Original container
5. Do not stack boxes over six (6) units high. Excessive weight can damage the film
6. Handle products in accordance with manufacturer's instructions.
1.7 PROJECT/SITE CONDITIONS
A. Confirm appropriate substrate is suitable for mounting of glass finish components prior to start of installation.
B. Apply materials when environmental conditions are within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer’s absolute limits. Application temperature range is 60 °F – 100 °F (16 °C – 38 °C).
C. Environmental Limitations: Do not install until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
1.8 WARRANTY
A. Manufacturer's Warranty: Submit manufacturer's standard warranty document by authorized manufacturer.
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. Basis of Design:
3M Company – Commercial Solutions Division [CSD] 3M Center, Building 0220-12-E-04 St. Paul, MN 55144-1000, USA 1-888-650-3497
2.2 MATERIAL PROPERTIES
A. General: Glass finishes field-applied application to glass or plastic material as visual opaque or decorative film.
B. Film: Vinyl C. Adhesive: Acrylic, Pressure Sensitive, Permanent D. Liner: Silicone-coated Polyester E. Thickness (Film and Adhesive without Liner):
1. Dusted - 3.2 mils (81 microns)
2. Frosted - 4.7 mils (120 microns)
F. Fire Performance: Surface burning characteristics when tested in accordance with ASTM E84, Class A:
1. Flame Spread: 25 maximum.
2. Smoke Developed: 450 maximum. C. Consult with authorized installation specialist for project specifics.
END OF SECTION