36C24919R0128-0001006.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24919R0128
About this file
36C24919R0128 0001 Drawings 07-18-262_Elec_FCD.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24919R0128-0004001.pdf | ||
| 36C24919R0128-0004000.docx | DOCX document | |
| 36C24919R0128-0003004.pdf | ||
| 36C24919R0128-0003005.pdf | ||
| 36C24919R0128-0003000.docx | DOCX document | |
| 36C24919R0128-0003008.pdf | ||
| 36C24919R0128-0003001.pdf | ||
| 36C24919R0128-0003006.pdf | ||
| 36C24919R0128-0003003.pdf | ||
| 36C24919R0128-0003007.pdf | ||
| 36C24919R0128-0003002.pdf | ||
| 36C24919R0128-0003009.pdf | ||
| 36C24919R0128-0002000.docx | DOCX document | |
| 36C24919R0128-0001005.pdf | ||
| 36C24919R0128-0001002.pdf | ||
| 36C24919R0128-0001008.pdf | ||
| 36C24919R0128-0001000.docx | DOCX document | |
| 36C24919R0128-0001004.pdf | ||
| 36C24919R0128-0001007.pdf | ||
| 36C24919R0128-0001003.pdf | ||
| 36C24919R0128-0001001.pdf | ||
| 36C24919R0128-000.docx | DOCX document | |
| 36C24919R0128-003.pdf | ||
| 36C24919R0128-005.xlsx | XLSX spreadsheet | |
| 36C24919R0128-002.pdf | ||
| 36C24919R0128-001.docx | DOCX document | |
| 36C24919R0128-004.docx | DOCX document |
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J
L L
ELECTRICAL ABBREVIATIONS LIST
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORDCOORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED
PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND
WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE
WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND
THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED
MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO
AVOID CONFLICT DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR
SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO
INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR
MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE
ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT
UNLESS NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND
CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,
LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
APPROVED THIRD PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE
SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC
PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE
MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT
BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS
DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
SHORT CIRCUIT CURRENT CALCULATIONS WILL BE
PERFORMED ON THE ELECTRICAL SYSTEM USING A
BOLTED THREE PHASE FAULT CONDITION FOR
CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND
MECHANICAL STRESS TO THE SYSTEM FOR
CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT
VALUES WILL BE USED OUTSIDE THE WORK AREA, FOR
THE STARTING POINT OF THE CALCULATIONS.
METHOD OF SHORT CIRCUIT
CURRENT CALCULATIONS
USING OHM'S LAW AND THE KNOWN RESISTIVITY
CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM
PER FOOT) FOR COPPER CONDUCTORS, OUR INTENT IS
TO CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO
AS NOT TO EXCEED THE RECOMMENDED VOLTAGE DROP
OF 3% FOR BRANCH CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE DROP
CALCULATIONS
ELECTRICAL SYMBOL LEGEND
120V DUPLEX RECEPTACLE
(NORMAL POWER CIRCUIT) SEE NOTE 1
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET AND
COVER PLATE SHALL BE RED IN COLOR
(CRITICAL POWER CIRCUIT) SEE NOTE 1
120V QUADRUPLEX RECEPTACLE SEE NOTE 1
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
SEE NOTE 1
JUNCTION BOX, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
NOTE 1: ALL RECEPTACLES AND DEVICES LOCATED ON PERIMETER WALLS
SHALL BE 20" AFF TO THE BOTTOM OF THE DEVICE (MINIMUM.)
SPECIAL RECEPTACLE SEE NOTE 1
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE SEE NOTE 118"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
PRESSURE MONITORPM
LIGHTNING PROTECTION AIR TERMINAL
LIGHTING SYMBOL LEGEND
2' X 2' RECESSED DIRECT/INDIRECT TROFFER
2' X 4' RECESSED DIRECT/INDIRECT TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY
VS: VACANCY SENSOR
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
48"
CENTER
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE
LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
OS
OS
LS
--- 4' LINEAR LED STRIPLIGHT - CHAIN SUSPENDED
LIGHTING FIXTURE SCHEDULE
A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE
FOR MISMATCHED OR INACCURATE PART NUMBERS.
B. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.
C. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE
SUBMITTALS.
D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH
THE LIGHT FIXTURE SHOP DRAWINGS, FOR A COMPLETE REVIEW.
GENERAL NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:1
A
M
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER
A1 1' X 4' CLEAN ROOM FIXTURE WITH
POLYCARBONATE LENS; IP65 RATED; FLUSH
INTEGRATION WITH 2" THICK CLEANROOM
WALKABLE CEILING SYSTEM;
RECESSED
FLANGE
LED; 4835 LUMENS;
82 CRI; 3500K
0-10V DIMMABLE
TO 5% DRIVER
120 V 50 W AES AES3ROL14 45L35K DCC DV 2F 2H SYM
A2 1' X 4' CLEAN ROOM FIXTURE WITH
POLYCARBONATE LENS; IP65 RATED; FLUSH
INTEGRATION WITH 2" THICK CLEANROOM
WALKABLE CEILING SYSTEM;
RECESSED
FLANGE
LED; 7191 LUMENS;
82 CRI; 3500K
0-10V DIMMABLE
TO 5% DRIVER
120 V 74 W AES AES3ROL14 67L35K DCC DV 2F 2H SYM
B 1' X 4' TROFFER; SEALED AND GASKETED RECESSED
GRID
LED; 5403 LUMENS;
82 CRI; 3500K
0-10V DIMMABLE
TO 5% DRIVER
120 V 49 W KENALL CSEDO14 45L35K DCC DV 5F 2H SYM
D EXTERIOR 15" DIAMETER X 4" HIGH ROUND
SURFACE MOUNT; WHITE POLYCARBONATE
DOME LENS; DAMP LOCATION RATED
SURFACE LED; 2109 LUMENS;
80 CRI; 3500K
ELECTRONIC LED
DRIVER
120 V 19 W KENALL RHR15 W PP 15L40K DV
E1 CONTEMPORARY LED SINGLE FACED EXIT
SIGN WITH BLACK POWDER PAINT ALUMINUM
HOUSING, BRUSHED ALUMINUM FACE, RED
LETTERS, AND CHEVRON ARROWS AS
SHOWN ON PLANS.
UNIVERSAL LED --- 120 V 5 W LITHONIA LES 1 R 120/277
F 4' LINEAR LED STRIPLIGHT WITH LENS CHAIN
SUSPEND
LED; 4585 LUMENS;
80 CRI; 4000K
ELECTRONIC LED
DRIVER
120 V 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 40K 80CRI
WH
F EM 4' LINEAR LED STRIPLIGHT WITH LENS AND
90 MINUTE NICKEL CADMIUM BATTERY BACK
UP.
CHAIN
SUSPEND
LED; 4585 LUMENS;
80 CRI; 4000K
ELECTRONIC LED
DRIVER
120 V 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 40K 80CRI
WH E15WLCP
DocuSign Envelope ID: CAB83445-0213-4068-9A58-FA45CCC7AD48
5/7/2019
GFI
VFDVFD
V F
D V
F D
27 302625.5 27 302625.5
3-HWP-11 3-HWP-10
3-CWP-11 3-CWP-10
'2N3P' - 5
'Q3P' - 20, 22, 24
'Q3P' - 14, 16, 18
'N3P' - 8, 10, 12
'N3P' - 2, 4, 6
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
WALL RATING LEGEND
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
/7
/2
:1
:1
A
M
EP101
BASEMENT POWER PLAN
2 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/2" = 1'-0"
BASEMENT POWER PLAN
A. COORDINATE EXACT LOCATION OF DISCONNECTS
WITH PUMP INSTALLERS, TO MAINTAIN
CLEARNACE.
1 COORDINATE VFD LOCATION WITH PLUMBING
CONTRACTOR PRIOR TO ROUGH-IN.
A C
A C
CLNG
J
C
LN
G
J
CLNG
J
C
LN
G
J
GFI
AC
GFI
AC
GFI
AC
A C
A C
AC
48"
48"
CLNG
J
J
J
GFI
AC
A
IV BUFFER
G12CC
HD BUFFER
G12HH
HD ANTEROOM
G12GG
HD STAGING
G12X
DELIVERY/ RECYCLING
/WASTE PICKUP
G12U
RECEIVING TEARDOWN
G12V
OPEN STORAGE
G12Z
CORRIDOR
G12W
OFFICE
G12AA
'2N3P'-7
'2N3P'-1
'2N3P'-3
'2C3P'-3
'2C3P'-11
25.5 26 27 30 34 37 40
B
C
D
E
F
G
IV BUFFER
G12MM
IV ANTEROOM
G12DD
IV PREP
G12R
ANTE
G12S
CHEMO
G12T
'2C3P'-1
'2C3P'-5
'2C3P'-7
'2C3P'-9
OPEN STORAGE
G12Z
'2C3P'-13
'2C3P'-15
'2C3P'-17
'2C3P'-2
'2C3P'- 4
'2C3P'- 6 '2C3P'- 8
'2C3P'- 24
'2C3P'- 10 '2C3P'- 12
'2C3P'- 18
'2C3P'- 20
'2C3P'- 22
'2C3P'- 26
'2C3P'- 19
'2C3P'- 19
'2C3P'- 21
'2N3P'- 9
'2N3P'- 11
'2N3P'- 9
'2C3P'-25
'2C3P'-27
'2C3P'-29
'2C3P'- 28
25.5 26 27 30 34
'L3A'
'2L3A'
'Q3A'
'2Q3A'
'2C3A'
'C3A'
'2N3A'
'2N3A1'
'N3A'ELEC G23
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
WALL RATING LEGEND
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
/7
/2
:1
:2
A
M
EP102
GROUND FLOOR POWER PLAN
3 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
0 2 4 8
NORTH
PLAN
A. ALL GLOVE BOXES SHALL BE PROVIDED WITH
DEDICATED POWER CIRCUITS.
B. ALL REFRIGERATORS SHALL BE PROVIDED WITH
DEDICATED POWER CIRCUITS.
Scale: 1/4" = 1'-0"
GROUND FLOOR POWER PLAN
1 NOT A REQUIRED EGRESS.
Scale: 1/4" = 1'-0"
GROUND FLOOR POWER PLAN ELEC G23 0 2 4 8
NORTH
PLAN
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
ELEC
RM G23
M M
M
M
M M
M
CLNG
J
J
J
A
7 8 13 25.5 26 27 30 34 37 40
B
C
D
E
F
G
GG
57-TU-3
FFU-A
FFU-A
FFU-A
FFU-B
57-TU-2
FFU-A
2C3P-23
2C3P-31
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:2
A
M
EP103
GROUND FLOOR MECHANICAL POWER
PLAN
4 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
GROUND FLOOR MECHANICAL POWER PLAN 0 4 8 16
NORTH
PLAN
01 01
01 PROVIDE MOTOR RATED SWITCH AT EACH
UNIT FOR LOCAL SERVICE DISCONNECT.
DN
G
FI
W P
J
VFD VFD VFD VFD VFD VFD
A
'Q3P'-1,3,5'Q3P'-7,9,11
'2N3P'-26
'2N3P' - 24
'N3P'
'2N3P'
'2C3P'
'Q3P'
7 8 13 25.5 26 27 30 34 37 40
B
C
D
E
F
G
GG
RTU
RTU
AHU-57
AHU-56
AHU-56-EF
'2C3P' - 41
'2C3P' - 39
6 6
'2C3P' - 14, 16
'Q3P' - 13, 15, 17
'Q3P' - 19, 21, 23
'Q3P' - 25, 27, 29
'Q3P-25,27,29'
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
WALL RATING LEGEND
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
/7
/2
:1
:2
A
M
EP104
FIRST FLOOR POWER PLAN
5 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
Scale: 1/4" = 1'-0"
FIRST FLOOR POWER PLAN
1 PROVIDE RACK CONSTRUCTED OF ANGLE
IRON WITH UNISTRUT CROSSBRACING, OF
LENGTH AND DURABILITY SUFFICIENT TO
SUPPORT VFD'S AS SHOWN. BOLT RACK TO
MECHANICAL PLATFORM AND SUPPORT
FROM MECHANICAL PLATFORM.
2 NEMA 3R RATED, 60A FUSIBLE DISCONNECT
FOR CONDENSING UNIT.
3 MOUNT RECEPTACLE TO EDGE OF CATWALK
SO AS NOT TO BE A TRIP HAZARD.
4 TRANSFORMER SUSPENDED FROM
STRUCTURE ON THREADED ROD.
5 CONTROL POWER JUNCTION BOX.
COORDINATE LOCATION WITH MECHANICAL
CONTRACTOR. CIRCUIT TO CIRCUITS 2C3P-14
AND 2C3P-16, TWO 120 VOLT CIRCUITS.
6 RECEPTACLE FOR HEAT TRACE.
COORDINATE WITH HVAC CONTRACTOR.
LABEL RECEPTACLE AS GFI PROTECTED.
7 ENCLOSED CIRCUIT BREAKER FEEDING
TRANSFORMER TC3P.
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
A. SEE SHEET E-602 FOR MECHANICAL EQUIPMENT
CONNECTION SCHEDULE.
DN
T
A
7 8 13 25.5 26 27 30 34 37 40
B
C
D
E
F
G
GG
(TYPICAL)
(TYPICAL)
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
WALL RATING LEGEND
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
/7
/2
:1
:2
A
M
EP105
LIGHTNING PROTECTION PLAN
6 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
0 4 8 16
NORTH
PLAN
01 PROVIDE MOTOR RATED SWITCH AT EACH
UNIT FOR LOCAL SERVICE DISCONNECT.
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
LIGHTNING PROTECTION PLAN
1. LIGHTNING PROTECTION SYSTEM SHALL BE
DESIGNED AND INSTALLED TO THE CRITERIA OF
A MASTER-LABEL LISTED SYSTEM, AND
CONNECTED INTO THE EXISTING LIGHTING
PROTECTION SYSTEM OF THE EXISTING
BUILDING. WHILE THE NEW ADDITION CANNOT BE
MASTER-LABEL LISTED AS IT IS BEING
CONNECTED INTO A NON-LISTED EXISTING
LIGHTNING PROTECTION SYSTEM, THE SYSTEM
SHALL BE INSPECTED AND A LETTER INDICATING
THAT NO ISSUES EXIST IN THE DESIGN OR
INSTALLATION OF THE NEW SYSTEM, WHICH
WOULD PREVENT IT FROM BEING LISTED IN THE
FUTURE.
2. THE LIGHTNING PROTECTION SYSTEM SHALL
CONFORM TO THE LATEST EDITION OF NFPA 70,
NFPA 780, AND UL96A. EXCEPT WHERE
REQUIREMENTS IN EXCESS ARE INDICATED OR
SPECIFIED.
3. SECURE AIR TERMINALS AND ROOF
CONDUCTORS WITH ADHESIVE BASES
COMPATIBLE WITH THE ROOF MATERIAL.
4. ISOLATED METAL BODIES THAT SHOW NO
CONDUCTANCE TO GROUND SHALL NOT
REQUIRE BONDING.
5. GROUNDED METAL BODIES THAT ARE WITHIN 6
FEET OF THE MAIN CONDUCTOR SHALL BE
BONDED TO THE SYSTEM.
6. ALL LIGHTNING CONDUCTORS ARE TO MAINTAIN
A HORIZONTAL OR DOWNWARD PATH. ALL
BENDS IN THE CONDUCTOR SHALL HAVE A
RADIUS OF 8 INCHES OR GREATER AND SHALL
HAVE AN ANGLE BEND OF 90 DEGREES OR
GREATER.
7. CONDUCTORS SHALL BE FASTENED A MAXIMUM
OF 3 FEET ON CENTER.
OS
OS
OS
OS
OS
OS
OS
OS
OS
LVD
LVD
LV
D
LVD
LVD
LVD
PC
LV
D
LVD
LV
D
LVD
LV
D
OS
OS
OS
OS
A
B
B B
B
B
B
A1
B
HD BUFFER
G12HH HD ANTEROOM
G12GG
DELIVERY/ RECYCLING
/WASTE PICKUP
G12U
RECEIVING TEARDOWN
G12V
OPEN STORAGE
G12Z
CORRIDOR
G12W
IV ANTEROOM
G12DD
B
A2
A2 A2
A2
A2
B
B B
A1
B B
A1 A1
EM
EM
EM
EM
EM
PAT ED BOOTHS
G13
IV PREP
G12R
ANTE
G12S
CHEMO
G12T
D D
E1
E1
E1
E1
RCD
RCD2
RCD
RCD
RCD
RCD
RCD
RCD
RCD
B
B
'2N3P - 24
'2N3P - 28
'2L3A - 34
'2L3A' - 36
7 8 13 25.5 26 27 30 34 37 40
B
C
D
E
F
G
GG
IV BUFFER
G12MM
HD STAGING
G12X
OFFICE
G12AA
B
B B
A2
IV BUFFER
G12CC
B EM
OPEN STORAGE
G12Z
EM
EM
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
WALL RATING LEGEND
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
/7
/2
:1
:1
A
M
EL101
GROUND FLOOR LIGHTING PLAN
7 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
0 4 8 16
NORTH
PLAN
1 CLEAN ROOM LED FIXTURE MANUAL AND
AUTOMATIC SWITCHES PROVIDED WITH
MODULAR CLEANROOM PACKAGE
CONTACTOR SHALL PROVIDE HOMERUN
CIRCUIT WIRING.
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
GROUND FLOOR LIGHTING PLAN
A. ALL FIXTURES SHALL BE RECESSED SEALED AND
GASKETED LED LIGHTING FIXTURES.
B. FOR FIXTURE TYPE REFER TO LIGHTING FIXTURE
SCHEDULE SHEET E-001.
C. ALL LIGHTING CONDUCTORS SHALL BE 2-12 AWG,
1-12 AWG EG IN 3/4" EMT UNLESS NOTED
OTHERWISE.
D. ALL EXIT SIGNS SHALL BE CIRCUITED FROM
EMERGENCY LIGHTING CIRCUIT INDICATED BUT
AHEAD OF ANY SWITCHING.
E. CONTRACTOR MUST VERIFY COMPATIBILITY OF
ALL LIGHTING CONTROLS WITH THE LED DRIVERS
TO BE CONTROLLED. COORDINATE ALL TIME
DELAY, AUTO DIM, PRESET DIMMING LEVELS,
PHOTO SENSOR CALIBRATION, SENSOR
SENSITIVITY AND CONFIGURATIONS WITH THE VA.
T
A
F
F EM
F
F EM F
F F
F F EM
F EM F F
F F EM F
F F F
'2N3P' - 25
7 8 13 25.5 26 27 30 34 37 40
B
C
D
E
F
G
GG
F
F
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
WALL RATING LEGEND
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
/7
/2
:1
:1
A
M
EL102
FIRST FLOOR LIGHTING PLAN
8 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
0 4 8 16
NORTH
PLAN
Scale: 1/4" = 1'-0"
FIRST FLOOR LIGHTING PLAN
1 CHAIN HANG FIXTURES FROM STRUCTURE.
COORDINATE EXACT LOCATION WITH OTHER
DISCIPLINES SO AS NOT TO CONFLICT WITH
EQUIPMENT.
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
A. FOR FIXTURE TYPE REFER TO LIGHTING FIXTURE
SCHEDULE SHEET E-001.
B. ALL LIGHTING CONDUCTORS SHALL BE 2-12 AWG,
1-12 AWG EG IN 3/4" EMT UNLESS NOTED
OTHERWISE.
C. ALL EXIT SIGNS SHALL BE CIRCUITED FROM
EMERGENCY LIGHTING CIRCUIT INDICATED BUT
AHEAD OF ANY SWITCHING.
D. CONTRACTOR MUST VERIFY COMPATIBILITY OF
ALL LIGHTING CONTROLS WITH THE LED DRIVERS
TO BE CONTROLLED. COORDINATE ALL TIME
DELAY, AUTO DIM, PRESET DIMMING LEVELS,
PHOTO SENSOR CALIBRATION, SENSOR
SENSITIVITY AND CONFIGURATIONS WITH THE VA.
E. EMERGENCY LIGHTS ARE CIRCUITED TO 2L3A-32
USING 2-12 AWG, 1-12 AWG EG, IN 3/4" CONDUIT.
PROVIDE NEW 1 POLE 20 AMP BREAKER IN
EXISTING SQUARD D TYPE NQ PANEL.
1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE
BLOCKS*. MAX DIAM OF CIRCULAR THROUGH OPENING IS 32-1/2 IN. (826 MM).
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
1A. STEEL SLEEVE (OPTIONAL, NOT SHOWN) - NOM 12 IN. (305 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE SLEEVE CAST INTO CONCRETE FLOOR OR WALL. SLEEVE TO BE FLUSH WITH OR PROJECT MAX 2 IN. (51MM) FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL.
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM)(POINT CONTACT) TO MAX 1-3/8 IN. (35 MM).
PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING
TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
A1. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
B. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.
C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED CERAMIC (ALUMINA SILICA) FIBER BLANKET, MINERAL WOOL BATT OR GLASS FIBER INSULATION MATERIAL USED AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF SOLID CONCRETE OR CONCRETE BLOCK WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4). AS AN ALTERNATE WHEN MAX PIPE SIZE IS 10 IN. (254 MM) DIAM AND WHEN MAX ANNULAR SPACE IS 1 IN. (25 MM), A MIN 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED CERAMIC FIBER BLANKET OR MINERAL WOOL BATT PACKING MATERIAL MAY BE RECESSED MIN 1/2 IN. (13 MM) FROM BOTTOM SURFACE OF FLOOR OR FROM EITHER SIDE OF SOLID CONCRETE WALL.
4. FILL,VOID OR CAVITY MATERIALS* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR SPACE TO THE
MIN THICKNESS SHOWN IN THE FOLLOWING TABLE:
(A) BR = POLYETHYLENE BACKER ROD.
CF = CERAMIC FIBER BLANKET.
GF = GLASS FIBER INSULATION.
MW = MINERAL-WOOL BATT.
(B) CAULK INSTALLED FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL.
(C) CAULK INSTALLED FLUSH WITH BOTTOM SURFACE OF FLOOR OR ONE SURFACE OF SOLID (NON-
CONCRETE BLOCK) WALL.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT.
(NOTE: W RATING APPLIES ONLY WHEN FB-3000 WT SEALANT IS USED.)
*BEARING THE UL CLASSIFICATION MARKING
MAX PIPE DIAM
IN. (MM)
10 (254)
10 (254)
30 (762)
MAX ANNULAR
SPACE IN. (MM)
1 (25)
1 (25)
2-1/2 (64)
PACKING MATL
TYPE (a)
BR, CF, GF OR MW
CF OR MW
BR, CF, GF OR MW
MIN. CAULK THKNS
IN. (MM)
1/2 (13) (b)
1/2 (13) (c)
1 (25) (b)
System No. C-AJ-1001 June 15, 2005 F Rating - 3 Hr T Rating - 0 Hr
W Rating - Class I (See Item 4)
SECTION A-A
4 4 1
A
A
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE
CONSTRUCTED
OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION
DESIGNS
IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC
WITH
NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)
WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES.
THE
GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE
AS
SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF
OPENING IS 26 IN. (660 MM).
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND
PERIPHERY
OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12
IN.
(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL
ELECTRICAL METALLIC TUBING
D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL
GAS
PIPING MAY BE USED:
1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
OMEGA FLEX INC
2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
TITEFLEX CORP
A BUNDY CO
3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
WARD MFG INC
3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM)
THICKNESS
OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH
SURFACES
OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT
CONTACT
LOCATION ON BOTH SIDES OF WALL.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL
ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT
AND
THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,
*BEARING THE UL CLASSIFICATION MARKING
SYSTEM NO.W-L-1001
JUNE 15, 2005
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
MAX PIPE OR
CONDUIT DIAM
IN. (mm)
1 (25)
1 (25)
4 (102)
6 (152)
12 (305)
F RATING
HR
1 OR 2
3 OR 4
1 OR 2
3 OR 4
1 OR 2
T RATING
HR
0+, 1 OR 2
3 OR 4
SECTION A-A
1B
1A
3A
A
AIR TERMINAL
NOTES:
1. SEE PLATE E-001 FOR LEGEND.
2. ALL SPLICES BELOW GRADE SHALL BE THE
EXOTHERMIC WELD TYPE.
3. AIR TERMINALS SHALL EXTEND NO LESS THAN 24
INCHES ABOVE THE ROOF.
4. ALL METAL EQUIPMENT ON THE ROOF SHALL BE
BONDED TO THE LIGHTNING PROTECTION SYSTEM.
5. THRU ROOF FLASHING SHALL BE COPPER WITH 8 INCH
ROUND BASE AND VERTICAL TUBE WITH NEOPRENE
SEAL. FLASHING SHALL BE THE PRODUCT OF THE
MANUFACTURER OF THE LIGHTNING PROTECTION
SYSTEM. A MEMBRANE FLASHING SHALL BE PROVIDED
OVER THE THRU ROOF FLASHING.
MAIN CONDUCTOR
CLIP CABLE SUPPORT
SEALING WASHER
(M
IN
LIGHTING
ZONE (a)
LIGHTING
ZONE (b)
RCD2
(AS NEEDED)
SEQUENCE OF OPERATION:
• OCCUPANCY SENSOR CONTROLS ALL LUMINAIRES WITHIN
ROOM
• LIGHT LEVEL SENSOR CONTROLS DIMMING OF LIGHTING ZONE
CLOSEST TO WINDOWS
• ALL ZONES SET TO MANUAL ON-AUTO OFF UNLESS DIRECTED
OTHERWISE BY THE VA
• LIGHTING CONTROL DEVICE MUST COMPLY WITH NEC 700.23
LINE VOLTAGE CIRCUIT
b1 a,b b
LVDS S
a
LVD
OS OS
LS
LOW VOLTAGE
OCCUPANCY
SENSOR
LOW VOLTAGE LIGHT LEVEL
SENSOR (AS NEEDED)
LIGHTING
CONTROLLER WITH 2
RELAYS AND
2 CHANNELS OF
0-10V DIMMING
LOW VOLTAGE
DIMMER SWITCHES
(AS NEEDED)
DAYLIGHTING
ZONE (b1)
LIGHTING
ZONE (a)
DAYLIGHTING
ZONE
RCD
(AS NEEDED)
SEQUENCE OF OPERATION:
• OCCUPANCY SENSOR CONTROLS ALL LUMINAIRES WITHIN
ROOM
• LIGHT LEVEL SENSOR CONTROLS DIMMING OF LIGHTING ZONE
CLOSEST TO WINDOWS
• ALL ZONES SET TO MANUAL ON-AUTO OFF UNLESS DIRECTED
OTHERWISE BY THE VA
• LIGHTING CONTROL DEVICE MUST COMPLY WITH NEC 700.23
LINE VOLTAGE CIRCUIT
LVDS
OS OS
LS
LOW VOLTAGE
OCCUPANCY
SENSOR
LOW VOLTAGE LIGHT LEVEL
SENSOR (AS NEEDED)
LIGHTING CONTROLLER
WITH 1 RELAYS AND 1
CHANNEL OF 0-10V
DIMMING
LOW VOLTAGE
DIMMER SWITCHES
(AS NEEDED)
STEP 1. FILE STRUCTURE CONNECTION AREA (3 IN. X 3. IN.
MIN)
TO BARE SHINY METAL AND CLEAN.
NOTES:
1. ALL CABLES AND WELDS SHALL BE MINIMUM 3 INCHES APART.
2. STANDARD WELD CARTRIDGES SHALL BE USED FOR STEEL
SURFACES. FOR DIP USE XF-19 WELD CARTRIDGES.
STEP 2. STRIP INSULATION FROM WIRE. ATTACH
SLEEVE
(REQUIRED ON NO.4 AWG WIRE AND
SMALLER).
STEP 3. HOLD MOLD FIRMLY WITH OPENING AWAY FROM
OPERATOR AND IGNITE WITH FLINT GUN.
STEP 4. REMOVE SLAG FROM CONNECTION AND
PEEN
WELD FOR SOUNDNESS.
STEP 5. COVER CONNECTION AND EXPOSED STRUCTURE
SURFACE WITH AN EPOXY COATING.
HANDLE
GRAPHITE COVER
STARTING POWDER
METAL WELDING POWDER
GRAPHITE MOLD
WIRE
PIPE WALL
METAL DISC
ECLEUL
SPRING NUT
CONDUIT FITTING
JUNCTION BOX
(SIZE AS
REQUIRED)
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
BEAM
CLAMP,
TYP.
CONDUIT
TRAPEZE PER
SD260533-03, TYP. CONDUIT,
TYP.
STEEL
EXPANSION
ANCHOR
STRUCTURAL MEMBER
(BEAM , JOIST, ETC.), TYP.
SEISMIC OR
EXPANSION
JOINT. FIELD
VERIFY
ACTUAL
CONDITIONS &
LOCATIONS.
FLOOR OR ROOF
STRUCTURE. FIELD VERIFY
ACTUAL CONDITIONS, TYP.
PROVIDE 127MM (5") OF SLACK AT
MIDPOINT BETWEEN TWO END OF
FLEXIBLE GALVANIZED STEEL
CONDUIT. PROVIDE GREEN INSULATED
COPPER EQUIPMENT GROUNDING
CONDUCTOR WITH FLEXIBLE CONDUIT.
914mm
(3'-0") MAX
PROVIDE EXTRA
CABLE TO MAKE
COMPLETE LOOP
AROUND BOX
PERIMETER
GENERAL NOTE:
1. DETAIL IS APPLICABLE ONLY FOR CONDUITS SMALLER THAN 76MM (3").
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:1
A
M
E-501
ELECTRICAL DETAILS
9 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
Scale: N.T.S.
UL PENETRATION DETAIL C-AJ-1001
Scale: N.T.S.
UL PENETRATION DETAIL W-L-1001
Scale: N.T.S.
LIGHTNING PROTECTION AIR TERMINAL
Scale: N.T.S.
DUAL RELAY ROOM CONTROLLER DIAGRAM
Scale: N.T.S.
SINGLE RELAY ROOM CONTROLLER DIAGRAM
Scale: N.T.S.
EXOTHERMIC WELD - WIRE TO PIPE
Scale: N.T.S.
GROUNDING MECHANICAL BOND
Scale: N.T.S.
CONDUIT EXPANSION JOINT CROSSING - FLEXIBLE
CONDUIT
NEW 'N3A'
480Y/277V
NEW 'N3P'
480Y/277V
200A MLO
45 KVA
480V-208Y/120V
'TN3P'
BOND TO BUILDING
STEEL AND COLD
WATER PIPE
6 AWG GEC
NEW '2N3P'
208Y/120V
125A MCB
45 KVA
480V-208Y/120V
'TC3P'
BOND TO BUILDING
STEEL AND COLD
WATER PIPE
NEW '2C3P'
208Y/120V
125A MCB
NEW 'Q3P'
480Y/277V
150A MLO
200A
6 AWG GEC
60A
125A
INTERSTITIAL
SPACE
ELEC
ROOM
G23
125A
150A MTS
100A MTS
60A
150A
150A
EXISTING 'C3A'
480Y/277V
EXISTING 'Q3A'
480Y/277V
60A
150A
4-3/0 AWG, 1-4 AWG EG
IN 2" CONDUIT
4-6 AWG, 1-10 AWG EG
IN 1 1/4" CONDUIT
4-1/0 AWG, 1-6 AWG EG
IN 2" CONDUIT
3-6 AWG, 1-10 AWG EG
IN 1" CONDUIT
3-6 AWG, 1-10 AWG EG
IN 1" CONDUIT
4-1 AWG, 1-6 AWG EG
IN 1 1/2" CONDUIT
4-1 AWG, 1-6 AWG EG
IN 1 1/2" CONDUIT
EXISTING
INCOMING
FEEDER
4-1/0 AWG, 1-6 AWG EG
IN 2" CONDUIT
N E
L
N E
L
4-6 AWG, 1-10 AWG EG
IN 1 1/4" CONDUIT
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:1
A
M
E-601
ONE-LINE DIAGRAM
10 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: No Scale
ONE-LINE DIAGRAM
1 EXISTING 600A SQUARE D TYPE HCM PANEL.
INSTALL ONE 3 POLE, 150A BREAKER AS
SHOWN TO SERVE NEW PANEL Q3P.
2 REPLACE EXISTING 400A GE TYPE NHB
PANEL WITH NEW PANEL AS SHOWN.
RECONNECT EXISTING FEEDERS TO NEW
PANEL.
3 EXISTING 400A 480V PANEL. INSTALL ONE 3
POLE, 60A BREAKER AS SHOWN TO SERVE
ENCLOSED CIRCUIT BREAKER.
EQUIPMENT CONDUCTOR SCHEDULE
TAG DESCRIPTION VOLTS PHASE LOAD MOCP CONDUCTORS NEUTRAL GROUND CONDUIT PLUG DISCONNECT TYPE
3-SF-10 AIR HANDLING UNIT 480 3 3 HP 3 12 12 3/4" 30A FUSIBLE DISC
3-SF-11 AIR HANDLING UNIT 480 3 3 HP 3 12 12 3/4" 30A FUSIBLE DISC
AHU-56-EF EXHAUST FAN 480 3 1 1/2 HP 3 12 12 3/4" 30A FUSIBLE DISC
3-CU-10 CONDENSING UNIT 480 3 32 MCA 40A 3 8 10 1" 60A FUSIBLE DISC
3-CU-11 CONDENSING UNIT 480 3 32 MCA 40A 3 8 10 1" 60A FUSIBLE DISC
3-HWP-10 HOT WATER PUMP 480 3 3/4 HP 3 12 12 3/4" 30A FUSIBLE DISC
3-HWP-11 HOT WATER PUMP 480 3 3/4 HP 3 12 12 3/4" 30A FUSIBLE DISC
3-CHWP-10 CHILLED WATER PUMP 480 3 1 HP 3 12 12 3/4" 30A FUSIBLE DISC
3-CHWP-11 CHILLED WATER PUMP 480 3 1 HP 3 12 12 3/4" 30A FUSIBLE DISC
20A
20A
20A
20A
20A
20A
20A
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:1
A
M
E-602
ELECTRICAL SCHEDULES
11 11KM CR
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
PANEL '2C3P'
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 75
PANEL / FEEDER (TOTAL KVA) 27.05
TOTAL DEMAND AMPERES PER PHASE 82 76 67
NOTE: ALL MOTOR CIRCUIT BREAKERS SHALL BE HACR RATED.
NOTE 1: THIS BREAKER SHALL BE A 30mA GFI TYPE BREAKER FOR HEAT TRACE.
TOTAL... 11.10 10.40 10.10 9.82 9.17 8.07
SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00
DEDICATED RECEPT 4.20 3.60 2.70 100% 4.20 3.60 2.70
NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 200A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00
MCB RATING 125A ALL OTHERS 1.00 1.00 0.00 100% 1.00 1.00 0.00
MINIMUM AIC (K AMPS) 10 MOTORS AND
EQUIPMENT
LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00
SERVICE ENTR. RATED YES X NO >10KVA@50% 1.29 1.24 2.04
MAIN CIRCUIT BREAKER X YES NO GENERAL USE
RECEPT
5.90 5.80 7.40
<=10 KVA@100% 3.33 3.33 3.33
ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00
MOUNTING SURFACE A B C A B C
C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE
LOAD TYPE
CONNECTED KVA
NEC DEM...
DEMAND KVA
11.10 10.40 10.10 TOTAL
SUB TOTAL 6.40 5.50 5.70 4.70 4.90 4.40 SUB TOTAL
HEAT TRACE RECEP (NOTE 1) --- --- 1.00 1P-20 41 42 1P-20 --- --- 0.00 SPARE
HEAT TRACE RECEP (NOTE 1) --- 1.00 --- 1P-20 39 40 1P-20 --- 0.00 --- SPARE
SPARE 0.00 --- --- 1P-20 37 38 1P-20 0.00 --- --- SPARE
SPARE --- --- 0.00 1P-20 35 36 1P-20 --- --- 0.00 SPARE
SPARE --- 0.00 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE
FAN HEPA FILTERS 1.00 --- --- 1P-20 31 32 1P-20 0.00 --- --- SPARE
RCPT - G12DD --- --- 0.40 1P-20 29 30 1P-20 --- --- 0.00 SPARE
REFRIDGE - G12Z --- 1.30 --- 1P-20 27 28 1P-20 --- 0.40 --- RCPT - G12GG
REFRIDGE - G12Z 1.30 --- --- 1P-20 25 26 1P-20 0.90 --- --- DOOR - G12GG
FAN HEPA FILTERS --- --- 1.00 1P-20 23 24 1P-20 --- --- 0.90 DOOR - G12HH
COMPUTER - G12Z --- 0.60 --- 1P-20 21 22 1P-20 --- 0.90 --- DOOR - G12DD
HAC CABINETS - G12GG, G12DD 0.80 --- --- 1P-20 19 20 1P-20 0.90 --- --- DOOR - G12CC
PASSTHRUS - G12HH --- --- 1.90 1P-20 17 18 1P-20 --- --- 0.90 DOOR - G12MM
MINIHOOD - G12HH --- 1.00 --- 1P-20 15 16 1P-20 --- 1.00 --- TERMINAL UNITS
MINIHOOD - G12Z 1.00 --- --- 1P-20 13 14 1P-20 1.00 --- --- TERMINAL UNITS
MINIHOOD - G12Z --- --- 1.00 1P-20 11 12 1P-20 --- --- 1.30 HOOD 2 - G12CC
MINIHOOD - G12Z --- 1.00 --- 1P-20 9 10 1P-20 --- 1.30 --- HOOD 1 - G12CC
MINIHOOD - G12X 1.00 --- --- 1P-20 7 8 1P-20 1.30 --- --- HOOD 2 - G12MM
COMPUTER - G12X --- --- 0.40 1P-20 5 6 1P-20 --- --- 1.30 HOOD 1 - G12MM
RCPT - SINKS G12W,Z,GG --- 0.60 --- 1P-20 3 4 1P-20 --- 1.30 --- HOOD - G12HH
REFRIDGE - G12X 1.30 --- --- 1P-20 1 2 1P-20 0.60 --- --- RCPT - G12 CC,DD,MM
A B C A B C
LOAD SERVED
KVA / Phase CKT
BRKR
CKT
NO
NEUTRAL
A B C
CKT
NO
CKT
BRKR
KVA / Phase
LOAD SERVED
PANEL '2N3P'
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 22
PANEL / FEEDER (TOTAL KVA) 7.95
TOTAL DEMAND AMPERES PER PHASE 24 23 19
NOTE: ALL MOTOR CIRCUIT BREAKERS SHALL BE HACR RATED. TOTAL... 2.66 2.64 2.16 2.83 2.80 2.32
NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 200A DEDICATED RECEPT 0.18 1.00 0.00 100% 0.18 1.00 0.00
MCB RATING 125A ALL OTHERS 0.00 0.00 0.00 100% 0.00 0.00 0.00
MINIMUM AIC (K AMPS) 10 MOTORS AND
EQUIPMENT
LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00
SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00
MAIN CIRCUIT BREAKER X YES NO GENERAL USE
RECEPT
1.80 1.00 1.52
<=10 KVA@100% 1.80 1.00 1.52
ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.68 0.64 0.64 125% 0.85 0.80 0.80
MOUNTING SURFACE A B C A B C
C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE
LOAD TYPE
CONNECTED KVA
NEC DEM...
DEMAND KVA
2.66 2.64 2.16 TOTAL
SUB TOTAL 2.48 2.00 0.98 0.18 0.64 1.18 SUB TOTAL
SPARE --- --- 0.00 1P-20 41 42 1P-20 --- --- 0.00 SPARE
SPARE --- 0.00 --- 1P-20 39 40 1P-20 --- 0.00 --- SPARE
SPARE 0.00 --- --- 1P-20 37 38 1P-20 0.00 --- --- SPARE
SPARE --- --- 0.00 1P-20 35 36 1P-20 --- --- 0.00 SPARE
SPARE --- 0.00 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE
SPARE 0.00 --- --- 1P-20 31 32 1P-20 0.00 --- --- SPARE
SPARE --- --- 0.00 1P-20 29 30 1P-20 --- --- 0.54 RECEPTACLES - FIRST FLOOR
SPARE --- 0.00 --- 1P-20 27 28 1P-20 --- 0.64 --- LIGHTING
FIRST FLOOR LIGHTING 0.68 --- --- 1P-20 25 26 1P-20 0.18 --- --- SERVICE RECEPTACLE
SPARE --- --- 0.00 1P-20 23 24 1P-20 --- --- 0.64 LIGHTING
SPARE --- 0.00 --- 1P-20 21 22 1P-20 --- 0.00 --- SPARE
SPARE 0.00 --- --- 1P-20 19 20 1P-20 0.00 --- --- SPARE
SPARE --- --- 0.00 1P-20 17 18 1P-20 --- --- 0.00 SPARE
SPARE --- 0.00 --- 1P-20 15 16 1P-20 --- 0.00 --- SPARE
PRINTER - G12AA 0.40 --- --- 1P-20 13 14 1P-20 0.00 --- --- SPARE
COMPUTERS - G12Z, G12AA --- --- 0.80 1P-20 11 12 1P-20 --- --- 0.00 SPARE
RCPT - G12Z, G12AA --- 1.00 --- 1P-20 9 10 1P-20 --- 0.00 --- SPARE
RCPT - G12Z 0.40 --- --- 1P-20 7 8 1P-20 0.00 --- --- SPARE
SERVICE RECEPTACLE - BASEMENT --- --- 0.18 1P-20 5 6 1P-20 --- --- 0.00 SPARE
RCPT - G12V --- 1.00 --- 1P-20 3 4 1P-20 --- 0.00 --- SPARE
RCPT - G12X, G12W 1.00 --- --- 1P-20 1 2 1P-20 0.00 --- --- SPARE
A B C A B C
LOAD SERVED
KVA / Phase CKT
BRKR
CKT
NO
NEUTRAL
A B C
CKT
NO
CKT
BRKR
KVA / Phase
LOAD SERVED
PANEL N3A
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 0
PANEL / FEEDER (TOTAL KVA) 0.00
TOTAL DEMAND AMPERES PER PHASE 0 0 0
NOTE: ALL MOTOR CIRCUIT BREAKERS MUST BE HACR RATED. TOTAL... 0.00 0.00 0.00 0.00 0.00 0.00
WATER HEATER 0.00 0.00 0.00 125% 0.00 0.00 0.00
SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00
NEUTRAL RATING 100% DEDICATED RECEPT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 400A FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
MCB RATING MLO ALL OTHERS 0.00 0.00 0.00 100% 0.00 0.00 0.00
MINIMUM AIC (K AMPS) 22 MOTORS AND
EQUIPMENT
LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00
SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00
MAIN CIRCUIT BREAKER YES X NO GENERAL USE
RECEPT
0.00 0.00 0.00
<=10 KVA@100% 0.00 0.00 0.00
ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00
MOUNTING SURFACE A B C A B C
C/B TEMP. 75 C. RATING 277 480 V 3 PH 4 WIRE
LOAD TYPE
CONNECTED KVA
NEC DEM...
DEMAND KVA
38.16 37.62 37.70 TOTAL
SUB TOTAL 38.16 37.62 37.70 0.00 0.00 0.00 SUB TOTAL
--- --- EX 29 30 1P-20 --- --- 0.00 SPACE
--- EX --- 27 28 1P-20 --- 0.00 --- SPACEFEED FOR TRANSFORMER T-N3A
EX --- ---
3P-225
25 26 1P-20 0.00 --- --- SPACE
--- --- 37.70 23 24 1P-20 --- --- 0.00 SPACE
--- 37.62 --- 21 22 1P-20 --- 0.00 --- SPACEFEED FOR NEW PANEL N3P
38.16 --- ---
3P-200
19 20 1P-20 0.00 --- --- SPARE
SPARE --- --- 0.00 1P-20 17 18 1P-20 --- --- 0.00 SPARE
SPARE --- 0.00 --- 1P-20 15 16 1P-20 --- 0.00 --- SPARE
SPARE 0.00 --- --- 1P-20 13 14 1P-20 0.00 --- --- SPARE
--- --- EX 11 12 1P-20 --- --- 0.00 SPARE
--- EX --- 9 10 1P-20 --- 0.00 --- SPAREPANEL N3B, ROOM 113
EX --- ---
3P-80
7 8 1P-20 0.00 --- --- SPARE
LIGHTS - SOUTH WING, G18 LIGHTS --- --- EX 1P-20 5 6 1P-20 --- --- EX 9G,9I
LIGHTS - SOUTH WING --- EX --- 1P-20 3 4 1P-20 --- EX --- 9
LIGHTS - SOUTH WING EX --- --- 1P-20 1 2 1P-20 EX --- --- 9B,C,D,F
A B C A B C
LOAD SERVED
KVA / Phase CKT
BRKR
CKT
NO
NEUTRAL
A B C
CKT
NO
CKT
BRKR
KVA / Phase
LOAD SERVED
PANEL 'N3P'
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 146
PANEL / FEEDER (TOTAL KVA) 121.59
TOTAL DEMAND AMPERES PER PHASE 147 146 146
NOTE: ALL MOTOR CIRCUIT BREAKERS MUST BE HACR RATED. TOTAL... 38.16 37.62 37.70 40.86 40.38 40.35
SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00
DEDICATED RECEPT 0.00 0.00 0.00 100% 0.00 0.00 0.00
NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 200A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.