36C24919R0128-0001006.pdf

PDF 2 MB Posted

Attached to
626-19-3-3303-0029 - 626-308 - USP 800 Pharmacy Compliance ACY
Solicitation number
36C24919R0128
Issued by

About this file

36C24919R0128 0001 Drawings 07-18-262_Elec_FCD.pdf

View the file

Other files

File Type Posted
36C24919R0128-0004001.pdf PDF
36C24919R0128-0004000.docx DOCX document
36C24919R0128-0003004.pdf PDF
36C24919R0128-0003005.pdf PDF
36C24919R0128-0003000.docx DOCX document
36C24919R0128-0003008.pdf PDF
36C24919R0128-0003001.pdf PDF
36C24919R0128-0003006.pdf PDF
36C24919R0128-0003003.pdf PDF
36C24919R0128-0003007.pdf PDF
36C24919R0128-0003002.pdf PDF
36C24919R0128-0003009.pdf PDF
36C24919R0128-0002000.docx DOCX document
36C24919R0128-0001005.pdf PDF
36C24919R0128-0001002.pdf PDF
36C24919R0128-0001008.pdf PDF
36C24919R0128-0001000.docx DOCX document
36C24919R0128-0001004.pdf PDF
36C24919R0128-0001007.pdf PDF
36C24919R0128-0001003.pdf PDF
36C24919R0128-0001001.pdf PDF
36C24919R0128-000.docx DOCX document
36C24919R0128-003.pdf PDF
36C24919R0128-005.xlsx XLSX spreadsheet
36C24919R0128-002.pdf PDF
36C24919R0128-001.docx DOCX document
36C24919R0128-004.docx DOCX document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

L L

ELECTRICAL ABBREVIATIONS LIST

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL

CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BYPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

W2 TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORDCOORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BDGYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

ELECTRICAL SYMBOL NOTES

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

GENERAL ELECTRICAL NOTES

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN

ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED

PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND

WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE

BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL

PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE

WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND

THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED

MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO

AVOID CONFLICT DURING CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR

SPARE, OR SPACE.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO

INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR

MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE

ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR

EQUIPMENT MANUFACTURER'S SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE

DEVICE'S SCREW TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT

UNLESS NOTED OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND

CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,

LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN

APPROVED THIRD PARTY TESTING AGENCY.

17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE

SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC

PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE

MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT

BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE

BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS

DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.

19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

SHORT CIRCUIT CURRENT CALCULATIONS WILL BE

PERFORMED ON THE ELECTRICAL SYSTEM USING A

BOLTED THREE PHASE FAULT CONDITION FOR

CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND

MECHANICAL STRESS TO THE SYSTEM FOR

CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT

VALUES WILL BE USED OUTSIDE THE WORK AREA, FOR

THE STARTING POINT OF THE CALCULATIONS.

METHOD OF SHORT CIRCUIT

CURRENT CALCULATIONS

USING OHM'S LAW AND THE KNOWN RESISTIVITY

CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM

PER FOOT) FOR COPPER CONDUCTORS, OUR INTENT IS

TO CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO

AS NOT TO EXCEED THE RECOMMENDED VOLTAGE DROP

OF 3% FOR BRANCH CIRCUIT CONDUCTORS.

METHOD OF VOLTAGE DROP

CALCULATIONS

ELECTRICAL SYMBOL LEGEND

120V DUPLEX RECEPTACLE

(NORMAL POWER CIRCUIT) SEE NOTE 1

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET AND

COVER PLATE SHALL BE RED IN COLOR

(CRITICAL POWER CIRCUIT) SEE NOTE 1

120V QUADRUPLEX RECEPTACLE SEE NOTE 1

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

SEE NOTE 1

JUNCTION BOX, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

NOTE 1: ALL RECEPTACLES AND DEVICES LOCATED ON PERIMETER WALLS

SHALL BE 20" AFF TO THE BOTTOM OF THE DEVICE (MINIMUM.)

SPECIAL RECEPTACLE SEE NOTE 1

EQUIPMENT CONNECTION

AS

NOTED

E

208V DUPLEX RECEPTACLE SEE NOTE 118"

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

PRESSURE MONITORPM

LIGHTNING PROTECTION AIR TERMINAL

LIGHTING SYMBOL LEGEND

2' X 2' RECESSED DIRECT/INDIRECT TROFFER

2' X 4' RECESSED DIRECT/INDIRECT TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER

WALL SCONCE

6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY

VS: VACANCY SENSOR

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

48"

CENTER

OCCUPANCY SENSOR, DUAL

TECHNOLOGY - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE

LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

4' LINEAR - WALL MOUNTED

7'-0"

CENTER

OS

OS

LS

--- 4' LINEAR LED STRIPLIGHT - CHAIN SUSPENDED

LIGHTING FIXTURE SCHEDULE

A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE

FOR MISMATCHED OR INACCURATE PART NUMBERS.

B. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.

C. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE

SUBMITTALS.

D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH

THE LIGHT FIXTURE SHOP DRAWINGS, FOR A COMPLETE REVIEW.

GENERAL NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:1

:1

A

M

E-001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER

A1 1' X 4' CLEAN ROOM FIXTURE WITH

POLYCARBONATE LENS; IP65 RATED; FLUSH

INTEGRATION WITH 2" THICK CLEANROOM

WALKABLE CEILING SYSTEM;

RECESSED

FLANGE

LED; 4835 LUMENS;

82 CRI; 3500K

0-10V DIMMABLE

TO 5% DRIVER

120 V 50 W AES AES3ROL14 45L35K DCC DV 2F 2H SYM

A2 1' X 4' CLEAN ROOM FIXTURE WITH

POLYCARBONATE LENS; IP65 RATED; FLUSH

INTEGRATION WITH 2" THICK CLEANROOM

WALKABLE CEILING SYSTEM;

RECESSED

FLANGE

LED; 7191 LUMENS;

82 CRI; 3500K

0-10V DIMMABLE

TO 5% DRIVER

120 V 74 W AES AES3ROL14 67L35K DCC DV 2F 2H SYM

B 1' X 4' TROFFER; SEALED AND GASKETED RECESSED

GRID

LED; 5403 LUMENS;

82 CRI; 3500K

0-10V DIMMABLE

TO 5% DRIVER

120 V 49 W KENALL CSEDO14 45L35K DCC DV 5F 2H SYM

D EXTERIOR 15" DIAMETER X 4" HIGH ROUND

SURFACE MOUNT; WHITE POLYCARBONATE

DOME LENS; DAMP LOCATION RATED

SURFACE LED; 2109 LUMENS;

80 CRI; 3500K

ELECTRONIC LED

DRIVER

120 V 19 W KENALL RHR15 W PP 15L40K DV

E1 CONTEMPORARY LED SINGLE FACED EXIT

SIGN WITH BLACK POWDER PAINT ALUMINUM

HOUSING, BRUSHED ALUMINUM FACE, RED

LETTERS, AND CHEVRON ARROWS AS

SHOWN ON PLANS.

UNIVERSAL LED --- 120 V 5 W LITHONIA LES 1 R 120/277

F 4' LINEAR LED STRIPLIGHT WITH LENS CHAIN

SUSPEND

LED; 4585 LUMENS;

80 CRI; 4000K

ELECTRONIC LED

DRIVER

120 V 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 40K 80CRI

WH

F EM 4' LINEAR LED STRIPLIGHT WITH LENS AND

90 MINUTE NICKEL CADMIUM BATTERY BACK

UP.

CHAIN

SUSPEND

LED; 4585 LUMENS;

80 CRI; 4000K

ELECTRONIC LED

DRIVER

120 V 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 40K 80CRI

WH E15WLCP

DocuSign Envelope ID: CAB83445-0213-4068-9A58-FA45CCC7AD48

5/7/2019

GFI

VFDVFD

V F

D V

F D

27 302625.5 27 302625.5

3-HWP-11 3-HWP-10

3-CWP-11 3-CWP-10

'2N3P' - 5

'Q3P' - 20, 22, 24

'Q3P' - 14, 16, 18

'N3P' - 8, 10, 12

'N3P' - 2, 4, 6

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

/7

/2

:1

:1

A

M

EP101

BASEMENT POWER PLAN

2 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

Scale: 1/2" = 1'-0"

BASEMENT POWER PLAN

A. COORDINATE EXACT LOCATION OF DISCONNECTS

WITH PUMP INSTALLERS, TO MAINTAIN

CLEARNACE.

1 COORDINATE VFD LOCATION WITH PLUMBING

CONTRACTOR PRIOR TO ROUGH-IN.

A C

A C

CLNG

J

C

LN

G

J

CLNG

J

C

LN

G

J

GFI

AC

GFI

AC

GFI

AC

A C

A C

AC

48"

48"

CLNG

J

J

J

GFI

AC

A

IV BUFFER

G12CC

HD BUFFER

G12HH

HD ANTEROOM

G12GG

HD STAGING

G12X

DELIVERY/ RECYCLING

/WASTE PICKUP

G12U

RECEIVING TEARDOWN

G12V

OPEN STORAGE

G12Z

CORRIDOR

G12W

OFFICE

G12AA

'2N3P'-7

'2N3P'-1

'2N3P'-3

'2C3P'-3

'2C3P'-11

25.5 26 27 30 34 37 40

B

C

D

E

F

G

IV BUFFER

G12MM

IV ANTEROOM

G12DD

IV PREP

G12R

ANTE

G12S

CHEMO

G12T

'2C3P'-1

'2C3P'-5

'2C3P'-7

'2C3P'-9

OPEN STORAGE

G12Z

'2C3P'-13

'2C3P'-15

'2C3P'-17

'2C3P'-2

'2C3P'- 4

'2C3P'- 6 '2C3P'- 8

'2C3P'- 24

'2C3P'- 10 '2C3P'- 12

'2C3P'- 18

'2C3P'- 20

'2C3P'- 22

'2C3P'- 26

'2C3P'- 19

'2C3P'- 19

'2C3P'- 21

'2N3P'- 9

'2N3P'- 11

'2N3P'- 9

'2C3P'-25

'2C3P'-27

'2C3P'-29

'2C3P'- 28

25.5 26 27 30 34

'L3A'

'2L3A'

'Q3A'

'2Q3A'

'2C3A'

'C3A'

'2N3A'

'2N3A1'

'N3A'ELEC G23

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

/7

/2

:1

:2

A

M

EP102

GROUND FLOOR POWER PLAN

3 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

0 2 4 8

NORTH

PLAN

A. ALL GLOVE BOXES SHALL BE PROVIDED WITH

DEDICATED POWER CIRCUITS.

B. ALL REFRIGERATORS SHALL BE PROVIDED WITH

DEDICATED POWER CIRCUITS.

Scale: 1/4" = 1'-0"

GROUND FLOOR POWER PLAN

1 NOT A REQUIRED EGRESS.

Scale: 1/4" = 1'-0"

GROUND FLOOR POWER PLAN ELEC G23 0 2 4 8

NORTH

PLAN

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

ELEC

RM G23

M M

M

M

M M

M

CLNG

J

J

J

A

7 8 13 25.5 26 27 30 34 37 40

B

C

D

E

F

G

GG

57-TU-3

FFU-A

FFU-A

FFU-A

FFU-B

57-TU-2

FFU-A

2C3P-23

2C3P-31

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:1

:2

A

M

EP103

GROUND FLOOR MECHANICAL POWER

PLAN

4 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

GROUND FLOOR MECHANICAL POWER PLAN 0 4 8 16

NORTH

PLAN

01 01

01 PROVIDE MOTOR RATED SWITCH AT EACH

UNIT FOR LOCAL SERVICE DISCONNECT.

DN

G

FI

W P

J

VFD VFD VFD VFD VFD VFD

A

'Q3P'-1,3,5'Q3P'-7,9,11

'2N3P'-26

'2N3P' - 24

'N3P'

'2N3P'

'2C3P'

'Q3P'

7 8 13 25.5 26 27 30 34 37 40

B

C

D

E

F

G

GG

RTU

RTU

AHU-57

AHU-56

AHU-56-EF

'2C3P' - 41

'2C3P' - 39

6 6

'2C3P' - 14, 16

'Q3P' - 13, 15, 17

'Q3P' - 19, 21, 23

'Q3P' - 25, 27, 29

'Q3P-25,27,29'

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

/7

/2

:1

:2

A

M

EP104

FIRST FLOOR POWER PLAN

5 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

Scale: 1/4" = 1'-0"

FIRST FLOOR POWER PLAN

1 PROVIDE RACK CONSTRUCTED OF ANGLE

IRON WITH UNISTRUT CROSSBRACING, OF

LENGTH AND DURABILITY SUFFICIENT TO

SUPPORT VFD'S AS SHOWN. BOLT RACK TO

MECHANICAL PLATFORM AND SUPPORT

FROM MECHANICAL PLATFORM.

2 NEMA 3R RATED, 60A FUSIBLE DISCONNECT

FOR CONDENSING UNIT.

3 MOUNT RECEPTACLE TO EDGE OF CATWALK

SO AS NOT TO BE A TRIP HAZARD.

4 TRANSFORMER SUSPENDED FROM

STRUCTURE ON THREADED ROD.

5 CONTROL POWER JUNCTION BOX.

COORDINATE LOCATION WITH MECHANICAL

CONTRACTOR. CIRCUIT TO CIRCUITS 2C3P-14

AND 2C3P-16, TWO 120 VOLT CIRCUITS.

6 RECEPTACLE FOR HEAT TRACE.

COORDINATE WITH HVAC CONTRACTOR.

LABEL RECEPTACLE AS GFI PROTECTED.

7 ENCLOSED CIRCUIT BREAKER FEEDING

TRANSFORMER TC3P.

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

A. SEE SHEET E-602 FOR MECHANICAL EQUIPMENT

CONNECTION SCHEDULE.

DN

T

A

7 8 13 25.5 26 27 30 34 37 40

B

C

D

E

F

G

GG

(TYPICAL)

(TYPICAL)

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

/7

/2

:1

:2

A

M

EP105

LIGHTNING PROTECTION PLAN

6 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

0 4 8 16

NORTH

PLAN

01 PROVIDE MOTOR RATED SWITCH AT EACH

UNIT FOR LOCAL SERVICE DISCONNECT.

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

LIGHTNING PROTECTION PLAN

1. LIGHTNING PROTECTION SYSTEM SHALL BE

DESIGNED AND INSTALLED TO THE CRITERIA OF

A MASTER-LABEL LISTED SYSTEM, AND

CONNECTED INTO THE EXISTING LIGHTING

PROTECTION SYSTEM OF THE EXISTING

BUILDING. WHILE THE NEW ADDITION CANNOT BE

MASTER-LABEL LISTED AS IT IS BEING

CONNECTED INTO A NON-LISTED EXISTING

LIGHTNING PROTECTION SYSTEM, THE SYSTEM

SHALL BE INSPECTED AND A LETTER INDICATING

THAT NO ISSUES EXIST IN THE DESIGN OR

INSTALLATION OF THE NEW SYSTEM, WHICH

WOULD PREVENT IT FROM BEING LISTED IN THE

FUTURE.

2. THE LIGHTNING PROTECTION SYSTEM SHALL

CONFORM TO THE LATEST EDITION OF NFPA 70,

NFPA 780, AND UL96A. EXCEPT WHERE

REQUIREMENTS IN EXCESS ARE INDICATED OR

SPECIFIED.

3. SECURE AIR TERMINALS AND ROOF

CONDUCTORS WITH ADHESIVE BASES

COMPATIBLE WITH THE ROOF MATERIAL.

4. ISOLATED METAL BODIES THAT SHOW NO

CONDUCTANCE TO GROUND SHALL NOT

REQUIRE BONDING.

5. GROUNDED METAL BODIES THAT ARE WITHIN 6

FEET OF THE MAIN CONDUCTOR SHALL BE

BONDED TO THE SYSTEM.

6. ALL LIGHTNING CONDUCTORS ARE TO MAINTAIN

A HORIZONTAL OR DOWNWARD PATH. ALL

BENDS IN THE CONDUCTOR SHALL HAVE A

RADIUS OF 8 INCHES OR GREATER AND SHALL

HAVE AN ANGLE BEND OF 90 DEGREES OR

GREATER.

7. CONDUCTORS SHALL BE FASTENED A MAXIMUM

OF 3 FEET ON CENTER.

OS

OS

OS

OS

OS

OS

OS

OS

OS

LVD

LVD

LV

D

LVD

LVD

LVD

PC

LV

D

LVD

LV

D

LVD

LV

D

OS

OS

OS

OS

A

B

B B

B

B

B

A1

B

HD BUFFER

G12HH HD ANTEROOM

G12GG

DELIVERY/ RECYCLING

/WASTE PICKUP

G12U

RECEIVING TEARDOWN

G12V

OPEN STORAGE

G12Z

CORRIDOR

G12W

IV ANTEROOM

G12DD

B

A2

A2 A2

A2

A2

B

B B

A1

B B

A1 A1

EM

EM

EM

EM

EM

PAT ED BOOTHS

G13

IV PREP

G12R

ANTE

G12S

CHEMO

G12T

D D

E1

E1

E1

E1

RCD

RCD2

RCD

RCD

RCD

RCD

RCD

RCD

RCD

B

B

'2N3P - 24

'2N3P - 28

'2L3A - 34

'2L3A' - 36

7 8 13 25.5 26 27 30 34 37 40

B

C

D

E

F

G

GG

IV BUFFER

G12MM

HD STAGING

G12X

OFFICE

G12AA

B

B B

A2

IV BUFFER

G12CC

B EM

OPEN STORAGE

G12Z

EM

EM

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

/7

/2

:1

:1

A

M

EL101

GROUND FLOOR LIGHTING PLAN

7 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

0 4 8 16

NORTH

PLAN

1 CLEAN ROOM LED FIXTURE MANUAL AND

AUTOMATIC SWITCHES PROVIDED WITH

MODULAR CLEANROOM PACKAGE

CONTACTOR SHALL PROVIDE HOMERUN

CIRCUIT WIRING.

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

Scale: 1/4" = 1'-0"

GROUND FLOOR LIGHTING PLAN

A. ALL FIXTURES SHALL BE RECESSED SEALED AND

GASKETED LED LIGHTING FIXTURES.

B. FOR FIXTURE TYPE REFER TO LIGHTING FIXTURE

SCHEDULE SHEET E-001.

C. ALL LIGHTING CONDUCTORS SHALL BE 2-12 AWG,

1-12 AWG EG IN 3/4" EMT UNLESS NOTED

OTHERWISE.

D. ALL EXIT SIGNS SHALL BE CIRCUITED FROM

EMERGENCY LIGHTING CIRCUIT INDICATED BUT

AHEAD OF ANY SWITCHING.

E. CONTRACTOR MUST VERIFY COMPATIBILITY OF

ALL LIGHTING CONTROLS WITH THE LED DRIVERS

TO BE CONTROLLED. COORDINATE ALL TIME

DELAY, AUTO DIM, PRESET DIMMING LEVELS,

PHOTO SENSOR CALIBRATION, SENSOR

SENSITIVITY AND CONFIGURATIONS WITH THE VA.

T

A

F

F EM

F

F EM F

F F

F F EM

F EM F F

F F EM F

F F F

'2N3P' - 25

7 8 13 25.5 26 27 30 34 37 40

B

C

D

E

F

G

GG

F

F

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

/7

/2

:1

:1

A

M

EL102

FIRST FLOOR LIGHTING PLAN

8 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

0 4 8 16

NORTH

PLAN

Scale: 1/4" = 1'-0"

FIRST FLOOR LIGHTING PLAN

1 CHAIN HANG FIXTURES FROM STRUCTURE.

COORDINATE EXACT LOCATION WITH OTHER

DISCIPLINES SO AS NOT TO CONFLICT WITH

EQUIPMENT.

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

A. FOR FIXTURE TYPE REFER TO LIGHTING FIXTURE

SCHEDULE SHEET E-001.

B. ALL LIGHTING CONDUCTORS SHALL BE 2-12 AWG,

1-12 AWG EG IN 3/4" EMT UNLESS NOTED

OTHERWISE.

C. ALL EXIT SIGNS SHALL BE CIRCUITED FROM

EMERGENCY LIGHTING CIRCUIT INDICATED BUT

AHEAD OF ANY SWITCHING.

D. CONTRACTOR MUST VERIFY COMPATIBILITY OF

ALL LIGHTING CONTROLS WITH THE LED DRIVERS

TO BE CONTROLLED. COORDINATE ALL TIME

DELAY, AUTO DIM, PRESET DIMMING LEVELS,

PHOTO SENSOR CALIBRATION, SENSOR

SENSITIVITY AND CONFIGURATIONS WITH THE VA.

E. EMERGENCY LIGHTS ARE CIRCUITED TO 2L3A-32

USING 2-12 AWG, 1-12 AWG EG, IN 3/4" CONDUIT.

PROVIDE NEW 1 POLE 20 AMP BREAKER IN

EXISTING SQUARD D TYPE NQ PANEL.

1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE

BLOCKS*. MAX DIAM OF CIRCULAR THROUGH OPENING IS 32-1/2 IN. (826 MM).

SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF

MANUFACTURERS.

1A. STEEL SLEEVE (OPTIONAL, NOT SHOWN) - NOM 12 IN. (305 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE SLEEVE CAST INTO CONCRETE FLOOR OR WALL. SLEEVE TO BE FLUSH WITH OR PROJECT MAX 2 IN. (51MM) FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL.

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM)(POINT CONTACT) TO MAX 1-3/8 IN. (35 MM).

PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING

TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

A1. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

B. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.

C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.

3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED CERAMIC (ALUMINA SILICA) FIBER BLANKET, MINERAL WOOL BATT OR GLASS FIBER INSULATION MATERIAL USED AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF SOLID CONCRETE OR CONCRETE BLOCK WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4). AS AN ALTERNATE WHEN MAX PIPE SIZE IS 10 IN. (254 MM) DIAM AND WHEN MAX ANNULAR SPACE IS 1 IN. (25 MM), A MIN 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED CERAMIC FIBER BLANKET OR MINERAL WOOL BATT PACKING MATERIAL MAY BE RECESSED MIN 1/2 IN. (13 MM) FROM BOTTOM SURFACE OF FLOOR OR FROM EITHER SIDE OF SOLID CONCRETE WALL.

4. FILL,VOID OR CAVITY MATERIALS* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR SPACE TO THE

MIN THICKNESS SHOWN IN THE FOLLOWING TABLE:

(A) BR = POLYETHYLENE BACKER ROD.

CF = CERAMIC FIBER BLANKET.

GF = GLASS FIBER INSULATION.

MW = MINERAL-WOOL BATT.

(B) CAULK INSTALLED FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL.

(C) CAULK INSTALLED FLUSH WITH BOTTOM SURFACE OF FLOOR OR ONE SURFACE OF SOLID (NON-

CONCRETE BLOCK) WALL.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT.

(NOTE: W RATING APPLIES ONLY WHEN FB-3000 WT SEALANT IS USED.)

*BEARING THE UL CLASSIFICATION MARKING

MAX PIPE DIAM

IN. (MM)

10 (254)

10 (254)

30 (762)

MAX ANNULAR

SPACE IN. (MM)

1 (25)

1 (25)

2-1/2 (64)

PACKING MATL

TYPE (a)

BR, CF, GF OR MW

CF OR MW

BR, CF, GF OR MW

MIN. CAULK THKNS

IN. (MM)

1/2 (13) (b)

1/2 (13) (c)

1 (25) (b)

System No. C-AJ-1001 June 15, 2005 F Rating - 3 Hr T Rating - 0 Hr

W Rating - Class I (See Item 4)

SECTION A-A

4 4 1

A

A

1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE

CONSTRUCTED

OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION

DESIGNS

IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC

WITH

NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)

WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES.

THE

GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE

AS

SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF

OPENING IS 26 IN. (660 MM).

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND

PERIPHERY

OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12

IN.

(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.

C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL

ELECTRICAL METALLIC TUBING

D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL

GAS

PIPING MAY BE USED:

1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

OMEGA FLEX INC

2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

TITEFLEX CORP

A BUNDY CO

3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

WARD MFG INC

3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM)

THICKNESS

OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH

SURFACES

OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT

CONTACT

LOCATION ON BOTH SIDES OF WALL.

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL

ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.

THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT

AND

THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:

+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,

*BEARING THE UL CLASSIFICATION MARKING

SYSTEM NO.W-L-1001

JUNE 15, 2005

F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)

T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT

L RATING AT 400 F - LESS THAN 1 CFM/SQ FT

MAX PIPE OR

CONDUIT DIAM

IN. (mm)

1 (25)

1 (25)

4 (102)

6 (152)

12 (305)

F RATING

HR

1 OR 2

3 OR 4

1 OR 2

3 OR 4

1 OR 2

T RATING

HR

0+, 1 OR 2

3 OR 4

SECTION A-A

1B

1A

3A

A

AIR TERMINAL

NOTES:

1. SEE PLATE E-001 FOR LEGEND.

2. ALL SPLICES BELOW GRADE SHALL BE THE

EXOTHERMIC WELD TYPE.

3. AIR TERMINALS SHALL EXTEND NO LESS THAN 24

INCHES ABOVE THE ROOF.

4. ALL METAL EQUIPMENT ON THE ROOF SHALL BE

BONDED TO THE LIGHTNING PROTECTION SYSTEM.

5. THRU ROOF FLASHING SHALL BE COPPER WITH 8 INCH

ROUND BASE AND VERTICAL TUBE WITH NEOPRENE

SEAL. FLASHING SHALL BE THE PRODUCT OF THE

MANUFACTURER OF THE LIGHTNING PROTECTION

SYSTEM. A MEMBRANE FLASHING SHALL BE PROVIDED

OVER THE THRU ROOF FLASHING.

MAIN CONDUCTOR

CLIP CABLE SUPPORT

SEALING WASHER

(M

IN

LIGHTING

ZONE (a)

LIGHTING

ZONE (b)

RCD2

(AS NEEDED)

SEQUENCE OF OPERATION:

• OCCUPANCY SENSOR CONTROLS ALL LUMINAIRES WITHIN

ROOM

• LIGHT LEVEL SENSOR CONTROLS DIMMING OF LIGHTING ZONE

CLOSEST TO WINDOWS

• ALL ZONES SET TO MANUAL ON-AUTO OFF UNLESS DIRECTED

OTHERWISE BY THE VA

• LIGHTING CONTROL DEVICE MUST COMPLY WITH NEC 700.23

LINE VOLTAGE CIRCUIT

b1 a,b b

LVDS S

a

LVD

OS OS

LS

LOW VOLTAGE

OCCUPANCY

SENSOR

LOW VOLTAGE LIGHT LEVEL

SENSOR (AS NEEDED)

LIGHTING

CONTROLLER WITH 2

RELAYS AND

2 CHANNELS OF

0-10V DIMMING

LOW VOLTAGE

DIMMER SWITCHES

(AS NEEDED)

DAYLIGHTING

ZONE (b1)

LIGHTING

ZONE (a)

DAYLIGHTING

ZONE

RCD

(AS NEEDED)

SEQUENCE OF OPERATION:

• OCCUPANCY SENSOR CONTROLS ALL LUMINAIRES WITHIN

ROOM

• LIGHT LEVEL SENSOR CONTROLS DIMMING OF LIGHTING ZONE

CLOSEST TO WINDOWS

• ALL ZONES SET TO MANUAL ON-AUTO OFF UNLESS DIRECTED

OTHERWISE BY THE VA

• LIGHTING CONTROL DEVICE MUST COMPLY WITH NEC 700.23

LINE VOLTAGE CIRCUIT

LVDS

OS OS

LS

LOW VOLTAGE

OCCUPANCY

SENSOR

LOW VOLTAGE LIGHT LEVEL

SENSOR (AS NEEDED)

LIGHTING CONTROLLER

WITH 1 RELAYS AND 1

CHANNEL OF 0-10V

DIMMING

LOW VOLTAGE

DIMMER SWITCHES

(AS NEEDED)

STEP 1. FILE STRUCTURE CONNECTION AREA (3 IN. X 3. IN.

MIN)

TO BARE SHINY METAL AND CLEAN.

NOTES:

1. ALL CABLES AND WELDS SHALL BE MINIMUM 3 INCHES APART.

2. STANDARD WELD CARTRIDGES SHALL BE USED FOR STEEL

SURFACES. FOR DIP USE XF-19 WELD CARTRIDGES.

STEP 2. STRIP INSULATION FROM WIRE. ATTACH

SLEEVE

(REQUIRED ON NO.4 AWG WIRE AND

SMALLER).

STEP 3. HOLD MOLD FIRMLY WITH OPENING AWAY FROM

OPERATOR AND IGNITE WITH FLINT GUN.

STEP 4. REMOVE SLAG FROM CONNECTION AND

PEEN

WELD FOR SOUNDNESS.

STEP 5. COVER CONNECTION AND EXPOSED STRUCTURE

SURFACE WITH AN EPOXY COATING.

HANDLE

GRAPHITE COVER

STARTING POWDER

METAL WELDING POWDER

GRAPHITE MOLD

WIRE

PIPE WALL

METAL DISC

ECLEUL

SPRING NUT

CONDUIT FITTING

JUNCTION BOX

(SIZE AS

REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

BEAM

CLAMP,

TYP.

CONDUIT

TRAPEZE PER

SD260533-03, TYP. CONDUIT,

TYP.

STEEL

EXPANSION

ANCHOR

STRUCTURAL MEMBER

(BEAM , JOIST, ETC.), TYP.

SEISMIC OR

EXPANSION

JOINT. FIELD

VERIFY

ACTUAL

CONDITIONS &

LOCATIONS.

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

PROVIDE 127MM (5") OF SLACK AT

MIDPOINT BETWEEN TWO END OF

FLEXIBLE GALVANIZED STEEL

CONDUIT. PROVIDE GREEN INSULATED

COPPER EQUIPMENT GROUNDING

CONDUCTOR WITH FLEXIBLE CONDUIT.

914mm

(3'-0") MAX

PROVIDE EXTRA

CABLE TO MAKE

COMPLETE LOOP

AROUND BOX

PERIMETER

GENERAL NOTE:

1. DETAIL IS APPLICABLE ONLY FOR CONDUITS SMALLER THAN 76MM (3").

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:1

:1

A

M

E-501

ELECTRICAL DETAILS

9 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

Scale: N.T.S.

UL PENETRATION DETAIL C-AJ-1001

Scale: N.T.S.

UL PENETRATION DETAIL W-L-1001

Scale: N.T.S.

LIGHTNING PROTECTION AIR TERMINAL

Scale: N.T.S.

DUAL RELAY ROOM CONTROLLER DIAGRAM

Scale: N.T.S.

SINGLE RELAY ROOM CONTROLLER DIAGRAM

Scale: N.T.S.

EXOTHERMIC WELD - WIRE TO PIPE

Scale: N.T.S.

GROUNDING MECHANICAL BOND

Scale: N.T.S.

CONDUIT EXPANSION JOINT CROSSING - FLEXIBLE

CONDUIT

NEW 'N3A'

480Y/277V

NEW 'N3P'

480Y/277V

200A MLO

45 KVA

480V-208Y/120V

'TN3P'

BOND TO BUILDING

STEEL AND COLD

WATER PIPE

6 AWG GEC

NEW '2N3P'

208Y/120V

125A MCB

45 KVA

480V-208Y/120V

'TC3P'

BOND TO BUILDING

STEEL AND COLD

WATER PIPE

NEW '2C3P'

208Y/120V

125A MCB

NEW 'Q3P'

480Y/277V

150A MLO

200A

6 AWG GEC

60A

125A

INTERSTITIAL

SPACE

ELEC

ROOM

G23

125A

150A MTS

100A MTS

60A

150A

150A

EXISTING 'C3A'

480Y/277V

EXISTING 'Q3A'

480Y/277V

60A

150A

4-3/0 AWG, 1-4 AWG EG

IN 2" CONDUIT

4-6 AWG, 1-10 AWG EG

IN 1 1/4" CONDUIT

4-1/0 AWG, 1-6 AWG EG

IN 2" CONDUIT

3-6 AWG, 1-10 AWG EG

IN 1" CONDUIT

3-6 AWG, 1-10 AWG EG

IN 1" CONDUIT

4-1 AWG, 1-6 AWG EG

IN 1 1/2" CONDUIT

4-1 AWG, 1-6 AWG EG

IN 1 1/2" CONDUIT

EXISTING

INCOMING

FEEDER

4-1/0 AWG, 1-6 AWG EG

IN 2" CONDUIT

N E

L

N E

L

4-6 AWG, 1-10 AWG EG

IN 1 1/4" CONDUIT

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:1

:1

A

M

E-601

ONE-LINE DIAGRAM

10 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

Scale: No Scale

ONE-LINE DIAGRAM

1 EXISTING 600A SQUARE D TYPE HCM PANEL.

INSTALL ONE 3 POLE, 150A BREAKER AS

SHOWN TO SERVE NEW PANEL Q3P.

2 REPLACE EXISTING 400A GE TYPE NHB

PANEL WITH NEW PANEL AS SHOWN.

RECONNECT EXISTING FEEDERS TO NEW

PANEL.

3 EXISTING 400A 480V PANEL. INSTALL ONE 3

POLE, 60A BREAKER AS SHOWN TO SERVE

ENCLOSED CIRCUIT BREAKER.

EQUIPMENT CONDUCTOR SCHEDULE

TAG DESCRIPTION VOLTS PHASE LOAD MOCP CONDUCTORS NEUTRAL GROUND CONDUIT PLUG DISCONNECT TYPE

3-SF-10 AIR HANDLING UNIT 480 3 3 HP 3 12 12 3/4" 30A FUSIBLE DISC

3-SF-11 AIR HANDLING UNIT 480 3 3 HP 3 12 12 3/4" 30A FUSIBLE DISC

AHU-56-EF EXHAUST FAN 480 3 1 1/2 HP 3 12 12 3/4" 30A FUSIBLE DISC

3-CU-10 CONDENSING UNIT 480 3 32 MCA 40A 3 8 10 1" 60A FUSIBLE DISC

3-CU-11 CONDENSING UNIT 480 3 32 MCA 40A 3 8 10 1" 60A FUSIBLE DISC

3-HWP-10 HOT WATER PUMP 480 3 3/4 HP 3 12 12 3/4" 30A FUSIBLE DISC

3-HWP-11 HOT WATER PUMP 480 3 3/4 HP 3 12 12 3/4" 30A FUSIBLE DISC

3-CHWP-10 CHILLED WATER PUMP 480 3 1 HP 3 12 12 3/4" 30A FUSIBLE DISC

3-CHWP-11 CHILLED WATER PUMP 480 3 1 HP 3 12 12 3/4" 30A FUSIBLE DISC

20A

20A

20A

20A

20A

20A

20A

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/7

/2

:1

:1

A

M

E-602

ELECTRICAL SCHEDULES

11 11KM CR

USP 800 PHARMACY

COMPLIANCE FOR YORK

VAMC - TVHS

3400 LEBANON RD, MURFREESBORO,

TN 37129

05/07/2019

FINAL CONSTRUCTION DOCUMENTS

626-30818-262

PANEL '2C3P'

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 75

PANEL / FEEDER (TOTAL KVA) 27.05

TOTAL DEMAND AMPERES PER PHASE 82 76 67

NOTE: ALL MOTOR CIRCUIT BREAKERS SHALL BE HACR RATED.

NOTE 1: THIS BREAKER SHALL BE A 30mA GFI TYPE BREAKER FOR HEAT TRACE.

TOTAL... 11.10 10.40 10.10 9.82 9.17 8.07

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED RECEPT 4.20 3.60 2.70 100% 4.20 3.60 2.70

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 200A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00

MCB RATING 125A ALL OTHERS 1.00 1.00 0.00 100% 1.00 1.00 0.00

MINIMUM AIC (K AMPS) 10 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED YES X NO >10KVA@50% 1.29 1.24 2.04

MAIN CIRCUIT BREAKER X YES NO GENERAL USE

RECEPT

5.90 5.80 7.40

<=10 KVA@100% 3.33 3.33 3.33

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA

NEC DEM...

DEMAND KVA

11.10 10.40 10.10 TOTAL

SUB TOTAL 6.40 5.50 5.70 4.70 4.90 4.40 SUB TOTAL

HEAT TRACE RECEP (NOTE 1) --- --- 1.00 1P-20 41 42 1P-20 --- --- 0.00 SPARE

HEAT TRACE RECEP (NOTE 1) --- 1.00 --- 1P-20 39 40 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 37 38 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 35 36 1P-20 --- --- 0.00 SPARE

SPARE --- 0.00 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE

FAN HEPA FILTERS 1.00 --- --- 1P-20 31 32 1P-20 0.00 --- --- SPARE

RCPT - G12DD --- --- 0.40 1P-20 29 30 1P-20 --- --- 0.00 SPARE

REFRIDGE - G12Z --- 1.30 --- 1P-20 27 28 1P-20 --- 0.40 --- RCPT - G12GG

REFRIDGE - G12Z 1.30 --- --- 1P-20 25 26 1P-20 0.90 --- --- DOOR - G12GG

FAN HEPA FILTERS --- --- 1.00 1P-20 23 24 1P-20 --- --- 0.90 DOOR - G12HH

COMPUTER - G12Z --- 0.60 --- 1P-20 21 22 1P-20 --- 0.90 --- DOOR - G12DD

HAC CABINETS - G12GG, G12DD 0.80 --- --- 1P-20 19 20 1P-20 0.90 --- --- DOOR - G12CC

PASSTHRUS - G12HH --- --- 1.90 1P-20 17 18 1P-20 --- --- 0.90 DOOR - G12MM

MINIHOOD - G12HH --- 1.00 --- 1P-20 15 16 1P-20 --- 1.00 --- TERMINAL UNITS

MINIHOOD - G12Z 1.00 --- --- 1P-20 13 14 1P-20 1.00 --- --- TERMINAL UNITS

MINIHOOD - G12Z --- --- 1.00 1P-20 11 12 1P-20 --- --- 1.30 HOOD 2 - G12CC

MINIHOOD - G12Z --- 1.00 --- 1P-20 9 10 1P-20 --- 1.30 --- HOOD 1 - G12CC

MINIHOOD - G12X 1.00 --- --- 1P-20 7 8 1P-20 1.30 --- --- HOOD 2 - G12MM

COMPUTER - G12X --- --- 0.40 1P-20 5 6 1P-20 --- --- 1.30 HOOD 1 - G12MM

RCPT - SINKS G12W,Z,GG --- 0.60 --- 1P-20 3 4 1P-20 --- 1.30 --- HOOD - G12HH

REFRIDGE - G12X 1.30 --- --- 1P-20 1 2 1P-20 0.60 --- --- RCPT - G12 CC,DD,MM

A B C A B C

LOAD SERVED

KVA / Phase CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase

LOAD SERVED

PANEL '2N3P'

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 22

PANEL / FEEDER (TOTAL KVA) 7.95

TOTAL DEMAND AMPERES PER PHASE 24 23 19

NOTE: ALL MOTOR CIRCUIT BREAKERS SHALL BE HACR RATED. TOTAL... 2.66 2.64 2.16 2.83 2.80 2.32

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 200A DEDICATED RECEPT 0.18 1.00 0.00 100% 0.18 1.00 0.00

MCB RATING 125A ALL OTHERS 0.00 0.00 0.00 100% 0.00 0.00 0.00

MINIMUM AIC (K AMPS) 10 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00

MAIN CIRCUIT BREAKER X YES NO GENERAL USE

RECEPT

1.80 1.00 1.52

<=10 KVA@100% 1.80 1.00 1.52

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.68 0.64 0.64 125% 0.85 0.80 0.80

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA

NEC DEM...

DEMAND KVA

2.66 2.64 2.16 TOTAL

SUB TOTAL 2.48 2.00 0.98 0.18 0.64 1.18 SUB TOTAL

SPARE --- --- 0.00 1P-20 41 42 1P-20 --- --- 0.00 SPARE

SPARE --- 0.00 --- 1P-20 39 40 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 37 38 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 35 36 1P-20 --- --- 0.00 SPARE

SPARE --- 0.00 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 31 32 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 29 30 1P-20 --- --- 0.54 RECEPTACLES - FIRST FLOOR

SPARE --- 0.00 --- 1P-20 27 28 1P-20 --- 0.64 --- LIGHTING

FIRST FLOOR LIGHTING 0.68 --- --- 1P-20 25 26 1P-20 0.18 --- --- SERVICE RECEPTACLE

SPARE --- --- 0.00 1P-20 23 24 1P-20 --- --- 0.64 LIGHTING

SPARE --- 0.00 --- 1P-20 21 22 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 19 20 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 17 18 1P-20 --- --- 0.00 SPARE

SPARE --- 0.00 --- 1P-20 15 16 1P-20 --- 0.00 --- SPARE

PRINTER - G12AA 0.40 --- --- 1P-20 13 14 1P-20 0.00 --- --- SPARE

COMPUTERS - G12Z, G12AA --- --- 0.80 1P-20 11 12 1P-20 --- --- 0.00 SPARE

RCPT - G12Z, G12AA --- 1.00 --- 1P-20 9 10 1P-20 --- 0.00 --- SPARE

RCPT - G12Z 0.40 --- --- 1P-20 7 8 1P-20 0.00 --- --- SPARE

SERVICE RECEPTACLE - BASEMENT --- --- 0.18 1P-20 5 6 1P-20 --- --- 0.00 SPARE

RCPT - G12V --- 1.00 --- 1P-20 3 4 1P-20 --- 0.00 --- SPARE

RCPT - G12X, G12W 1.00 --- --- 1P-20 1 2 1P-20 0.00 --- --- SPARE

A B C A B C

LOAD SERVED

KVA / Phase CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase

LOAD SERVED

PANEL N3A

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 0

PANEL / FEEDER (TOTAL KVA) 0.00

TOTAL DEMAND AMPERES PER PHASE 0 0 0

NOTE: ALL MOTOR CIRCUIT BREAKERS MUST BE HACR RATED. TOTAL... 0.00 0.00 0.00 0.00 0.00 0.00

WATER HEATER 0.00 0.00 0.00 125% 0.00 0.00 0.00

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

NEUTRAL RATING 100% DEDICATED RECEPT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 400A FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

MCB RATING MLO ALL OTHERS 0.00 0.00 0.00 100% 0.00 0.00 0.00

MINIMUM AIC (K AMPS) 22 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00

MAIN CIRCUIT BREAKER YES X NO GENERAL USE

RECEPT

0.00 0.00 0.00

<=10 KVA@100% 0.00 0.00 0.00

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 277 480 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA

NEC DEM...

DEMAND KVA

38.16 37.62 37.70 TOTAL

SUB TOTAL 38.16 37.62 37.70 0.00 0.00 0.00 SUB TOTAL

--- --- EX 29 30 1P-20 --- --- 0.00 SPACE

--- EX --- 27 28 1P-20 --- 0.00 --- SPACEFEED FOR TRANSFORMER T-N3A

EX --- ---

3P-225

25 26 1P-20 0.00 --- --- SPACE

--- --- 37.70 23 24 1P-20 --- --- 0.00 SPACE

--- 37.62 --- 21 22 1P-20 --- 0.00 --- SPACEFEED FOR NEW PANEL N3P

38.16 --- ---

3P-200

19 20 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 17 18 1P-20 --- --- 0.00 SPARE

SPARE --- 0.00 --- 1P-20 15 16 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 13 14 1P-20 0.00 --- --- SPARE

--- --- EX 11 12 1P-20 --- --- 0.00 SPARE

--- EX --- 9 10 1P-20 --- 0.00 --- SPAREPANEL N3B, ROOM 113

EX --- ---

3P-80

7 8 1P-20 0.00 --- --- SPARE

LIGHTS - SOUTH WING, G18 LIGHTS --- --- EX 1P-20 5 6 1P-20 --- --- EX 9G,9I

LIGHTS - SOUTH WING --- EX --- 1P-20 3 4 1P-20 --- EX --- 9

LIGHTS - SOUTH WING EX --- --- 1P-20 1 2 1P-20 EX --- --- 9B,C,D,F

A B C A B C

LOAD SERVED

KVA / Phase CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase

LOAD SERVED

PANEL 'N3P'

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 146

PANEL / FEEDER (TOTAL KVA) 121.59

TOTAL DEMAND AMPERES PER PHASE 147 146 146

NOTE: ALL MOTOR CIRCUIT BREAKERS MUST BE HACR RATED. TOTAL... 38.16 37.62 37.70 40.86 40.38 40.35

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED RECEPT 0.00 0.00 0.00 100% 0.00 0.00 0.00

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 200A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.