36C24919R0128-0001005.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24919R0128
About this file
36C24919R0128 0001 Drawings 07-18-262 Mech FCD.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24919R0128-0004001.pdf | ||
| 36C24919R0128-0004000.docx | DOCX document | |
| 36C24919R0128-0003004.pdf | ||
| 36C24919R0128-0003005.pdf | ||
| 36C24919R0128-0003000.docx | DOCX document | |
| 36C24919R0128-0003008.pdf | ||
| 36C24919R0128-0003001.pdf | ||
| 36C24919R0128-0003006.pdf | ||
| 36C24919R0128-0003003.pdf | ||
| 36C24919R0128-0003007.pdf | ||
| 36C24919R0128-0003002.pdf | ||
| 36C24919R0128-0003009.pdf | ||
| 36C24919R0128-0002000.docx | DOCX document | |
| 36C24919R0128-0001002.pdf | ||
| 36C24919R0128-0001008.pdf | ||
| 36C24919R0128-0001000.docx | DOCX document | |
| 36C24919R0128-0001006.pdf | ||
| 36C24919R0128-0001004.pdf | ||
| 36C24919R0128-0001007.pdf | ||
| 36C24919R0128-0001003.pdf | ||
| 36C24919R0128-0001001.pdf | ||
| 36C24919R0128-000.docx | DOCX document | |
| 36C24919R0128-003.pdf | ||
| 36C24919R0128-005.xlsx | XLSX spreadsheet | |
| 36C24919R0128-002.pdf | ||
| 36C24919R0128-001.docx | DOCX document | |
| 36C24919R0128-004.docx | DOCX document |
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR-COOLED CONDENSER
ACCH AIR-COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
ACD AUTOMATIC CONTROL DAMPER,
MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER,TWO
POSITION
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BUFFER TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CENTIGRADE (CELCIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CH CHILLER
CHWP CHILLED WATER PUMP
CHW CHILLER WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CHWCC CHILLED WATER COOLING COIL
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
D-4 ECONOMIZER OUTDOOR AIR DAMPER
dB DECIBELS Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECC ENGINEERING CONTROL CENTER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FM FLOW METER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GS GALVANIZED STEEL
H HUMIDIFER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HHW HEATING HOT WATER
HHWC HEATING HOT WATER COIL
HHWP HEATING HOT WATER PUMP
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM
CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
Hz HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTERGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IV INLET VANES
kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
L LITER
L/s LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LH LATENT HEAT
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPS LOW PRESSURE SUPPLY (STEAM)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL
PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/s METERS PER SECOND (OR
METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM
CONDENSATE)
MPS MEDIUM PRESSURE SUPPLY (STEAM)
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OR OPERATING ROOM
OSA OUTSIDE SUPPLY AIR (CONDITIONED)
P PUMP
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PHC PREHEAT COIL
PHCP PREHEAT COIL PUMP
PPM PARTS PER MILLION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH –
ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
R/E RETURN OR EXHAUST
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSR SOLID SEPARATOR
ST STEAM TRAP
SV STEAM SAFETY VALVE
SVS STEAM VENT SILENCER
T & PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED
BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE)
RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
Wb WET-BULB (TEMPERATURE)
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
XT EXPANSION TANK
YR YEAR
MECHANICAL ABBREVIATIONS
1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.
4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE PURPOSES INTENDED.
5. WHERE POSSIBLE, PROVIDE STANDARD PRODUCTS OF THE VARIOUS MANUFACTURERS EXCEPT WHERE SPECIAL CONSTRUCTION OR PERFORMANCE FEATURES ARE
REQUIRED.
6. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS SHALL BE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
7. PROVIDE MECHANICAL EQUIPMENT THAT IS LISTED AND LABELED BY UNDERWRITERS LABORATORIES (U.L.).
8. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT MAINTENANCE, REPAIRS, AND REPLACEMENT.
9. INSTALL EQUIPMENT WITH PROPER CLEARANCES FOR REQUIRED PIPING AND ELECTRICAL SERVICES AND CONNECTIONS. INSTALL EQUIPMENT WITH REQUIRED ACCESS AND CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS AND APPLICABLE CODES AND STANDARDS.
10. COORDINATE LOCATION, INSTALLATION, AND ROUTING OF DUCTWORK, PIPING, AND EQUIPMENT WITH WORK OF ALL OTHER TRADES.
11. PROVIDE SUPPORT FOR MECHANICAL EQUIPMENT. COORDINATE SUPPORT LOCATIONS WITH ALL CONTRACTORS PRIOR TO INSTALLATION.
12. PROVIDE POWER CONNECTIONS TO EQUIPMENT PROVIDED UNDER THIS CONTRACT AS WORK OF DIVISION 26.
13. PROVIDE CONTROL WIRING FOR MECHANICAL EQUIPMENT AS WORK OF DIVISION 23.
14. DUCTWORK AND PIPING LAYOUTS AND LOCATIONS ARE SCHEMATIC. DO NOT SCALE THESE DRAWINGS. COORDINATE AND DETERMINE EXACT ROUTING OF DUCTWORK AND
PIPING IN THE FIELD.
15. FIELD VERIFY DIMENSIONS BY ACTUAL MEASUREMENT AND OBSERVATION BEFORE ORDERING OR FABRICATING DUCTWORK, PIPING OR EQUIPMENT.
16. NOTIFY COR REGARDING DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND EXISTING CONDITIONS OR DIMENSIONS BEFORE PERFORMING WORK. FAILURE TO VERIFY AND REPORT SHALL CONSTITUTE CONTRACTOR'S ACCEPTANCE OF EXISTING CONDITIONS AS FIT FOR THE PROPER EXECUTION OF THE WORK.
17. SEE ARCHITECTURAL DRAWINGS FOR FINAL LOCATION OF CEILING INSTALLED EQUIPMENT.
18. INSTALL DUCTWORK AND PIPING AS HIGH AS POSSIBLE AND AS CLOSE AS POSSIBLE TO BUILDING WALLS, CEILING AND FLOOR AND ROOF STRUCTURE. PROVIDE OFFSETS, FITTINGS, AND DIMENSIONAL TRANSITIONS NOT SHOWN BUT REQUIRED TO MAINTAIN MINIMUM CLEAR SPACE TO BUILDING SURFACES AT NO ADDITIONAL COST.
19. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH MECHANICAL WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.
20. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF PROJECT.
21. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.
22. MAKE A COMPLETE REVIEW OF DRAWINGS, INCLUDING SCHEDULES AND DETAILS, PRIOR TO BEGINNING MECHANICAL SYSTEM INSTALLATION. RESOLVE CONFLICTS WITH
COR.
23. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING SYSTEMS.
24. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS
ARE NOT ACCEPTABLE UNLESS SPECIFICALLY INDICATED OTHERWISE.
25. INSTALL PIPING FREE OF SAGS AND BENDS.
26. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION.
27. PIPING SHALL NOT BE ROUTED OVER TELECOM OR ELECTRICAL CLOSETS/ROOMS.
28. PREPARE DRAWINGS SHOWING MECHANICAL SYSTEMS AND EQUIPMENT FOR COORDINATION WITH WORK OF OTHER DIVISIONS AND WORK BY THE GOVERNMENT.
A. INCLUDE PLAN VIEWS, SECTIONS, AND ELEVATIONS, AS REQUIRED, TO FULLY COORDINATE ALL NEW WORK WITH ITSELF AND EXISTING CONDITIONS.
B. DRAWINGS SHALL SHOW, BUT NOT BE LIMITED TO, ALL DUCTWORK, AIR DISTRIBUTION, MECHANICAL EQUIPMENT, MECHANICAL PIPING, FIRE PROTECTION PIPING, PLUMBING PIPING, CABLE TRAYS, LIGHTING FIXTURES, CEILING GRID AND HEIGHT, BEAMS AND JOISTS (WITH ELEVATIONS MARKED), ELECTRICAL CONDUIT LARGER THAN 2 INCHES IN DIAMETER AND OTHER CEILING MOUNT DEVICES OR EQUIPMENT THAT PROTRUDE INTO THE CEILING CAVITY.
C. IF THERE ARE OUTSTANDING ISSUES THAT CANNOT BE RESOLVED, CONSULT WITH COR FOR GUIDANCE AND MAKE CORRECTIONS IN ACCORDANCE WITH DIRECTIONS
GIVEN.
D. DO NOT BEGIN FABRICATION OR PLACE EQUIPMENT ORDERS UNTIL COORDINATION DRAWINGS HAVE BEEN APPROVED.
29. INSTALLATION COMMENCED PRIOR TO COORDINATION DRAWING APPROVAL IS TAKEN AT THE CONTRACTORS OWN RISK. MODIFY, MOVE OR RECONFIGURE WORK LACKING
COORDINATION AT NO ADDITIONAL COST
MECHANICAL GENERAL NOTES
T
CO2 CARBON DIOXIDE
THERMOSTAT
SUPPLY DIFFUSER
RETURN DIFFUSER/GRILLE
EXHAUST GRILLE
ROUND FLEX DUCT
EG-88 2000 DIFFUSER TAG | DIFFUSER CFM
LINEAR SLOT DIFFUSER
BALANCING DAMPER
(RECTANGULAR)
BALANCING DAMPER
(ROUND)
FIRE DAMPER
SMOKE DAMPER
D
R INCLINED RISE, IN
DIRECTION OF AIRFLOW
INCLINED DROP, IN DIRECTION
OF AIRFLOW
CONNECT NEW DUCT
TO EXISTING
LIMIT OF DEMOLITION
VANED ELBOW (PROVIDE ALL
SQUARE OR RECTANGULAR
ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
STANDARD RADIUS ELBOW
(LONG RADIUS)
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
DUCT TRANSITION
SIDE MOUNTED GRILLE
SUPPLY
RETURN45°
45°
DN
DN
UP
UP
DNUP
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
MECHANICAL LEGEND
HPS
LPS
LPR
CHS
CHR
HIGH PRESSURE STEAM
PIPING (60 PSI)
LOW PRESSURE STEAM PIPING
(15 PSI AND BELOW)
LOW PRESSURE STEAM
CONDENSATE RETURN
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
PIPE UP
PIPE DOWN
BOTTOM CONNECTION
TOP CONNECTION
CAPPED OUTLET
GLOBE VALVE
GATE VALVE
BALL VALVE
STEAM SAFETY VALVE
PRESSURE REGULATING VALVE
WYE STRAINER VALVE
BALANCING VALVE
MOTORIZED CONTROL VALVE
STEAM TRAPCOND CONDENSATE DRAIN LINE
HPR HIGH PRESSURE STEAM
CONDENSATE RETURN
HWS
HWR
HEATING HOT WATER SUPPLY
PIPING
HEATING HOT WATER RETURN PIPING
RLS REFRIGERANT LINE SET (LIQUID
AND SUCTION)
CONNECT TO EXISTING PIPE
LIMITS OF DEMOLITION
INLINE CENTRIFUGAL PUMP
TANGENTIAL AIR SEPARATOR
EXPANSION TANK
WALL-MOUNTED INDOOR
SPLIT-SYSTEM
SPLIT-SYSTEM CONDENSING UNIT
UTILITY SET EXHAUST FAN
STEAM PRESSURE
REDUCING STATION
DRAIN VALVE
TEST PLUG
SUPPLY
TERMINAL UNIT SUPPLY
DUCT BRANCH (CONICAL
TAP)
TERMINAL UNIT
CHECK VALVE
AGRICULTURE
S
IL
AS
P. GEORG
E
R E G
IS
T E
RED ENG
IN
E E R
C O M M E R C E
N o . 12 0 6 3 4
S T A
T E
OF T ENNE
S
S E E
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:3
P M
M-001
MECHANICAL GENERAL INFORMATION
1 13SPG PA
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
ENERGY REVIEW INFORMATION
ENERGY ENGINEER REVIEW ACTURAL: 4-3-19
ENERGY ENGINEER NAME: MIKE HATCHER/ER#19-11/DESIGN
ENERGY ENGINEER PHONE: 615-489-2398
RECEIVING
TEARDOWN
G12V
DELIVERY/
RECYCLING
/WASTE
PICKUP
G12U
IV
BUFFER
G12CC
HD
BUFFER
G12HH
HD
ANTEROOM
G12GG
OPEN
STORAGE
G12Z
HD
STAGING
G12X
CORRIDOR
G12W
IV
ANTEROOM
G12DD
x x x ø 1 x x
24x12 x
10x10
6ø
10ø
8ø x
32x14 36x18 x x
16x14
16x10 x
14x8
12x10 ø
12ø ø x
14x12 20x12
10ø
20x14 x x
57-TU-2
57-TU-1
57-AFCV-2
57-HC-3
AHU-56
57-TU-3
56-AFCV-3
56-HC-3
57-HC-2
57-AFCV-3
56-HC-1
56-HC-2
56-EV-3
56-AFCV-1
x
16x6
57-RV-3
57-RV-1
24x12
AHU-56-EF
56-EV-2
56-EV-1
AHU-57
IV PREP
G12R
ANTE
G12S
CHEMO
G12T ø
20x12 ø x x x
8ø
8x8
2 2 x
56-AFCV-2
6ø
14x6
10x10
6x6
8x12
OFFICE
G12AA
ø x
RTU 3 RTU 2
20x14
57-AFCV-1
57-HC-1
IV
BUFFER
G12MM
57-RV-2
16x12
12ø 10ø12x10
12x8
12x10
12x8 12x8
4ø
10ø 10x10
10ø 10x10
8x8
8x8 x
12x10
8x8
A
C
D
E
F
G
GG
30 34 37 40
2625.5
B
COORDINATE WORK WITH OTHER
TRADES AND THE COR TO
MINIMIZE DISRUPTION OF AREAS.
A.
NEW DUCT SHOWN IS IN
INTERSTITIAL SPACE.
B.
AGRICULTURE
S
IL
AS
P. GEORG
E
R E G
IS
T E
RED ENG
IN
E E R
C O M M E R C E
N o . 12 0 6 3 4
S T A
T E
OF T ENNE
S
S E E
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
WALL RATING LEGEND
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREAS S S S
/7
/2
:1
:0
P M
MH101
GROUND FLOOR HVAC PLAN
2 13SPG PA
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
Scale: 1/4" = 1'-0"
GROUND FLOOR HVAC PLAN 0 4 8 16
NORTH
PLAN
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
1 PROVIDE 4" DIA. DUCT CONNECTION FOR
HOUSEKEEPING CABINET.
2 CONDENSING UNITS LOCATED ON ROOF OF
EXISTING PHARMACY.
3 EXTEND WELDED EXHUAST DUCT TO BE
MINIMUM 25 FEET FROM PHARMACY AHU
INTAKE. PROVIDE WITH HIGH VELOCITY
DISCHARGE.
4 PROVIDE 24" DEEP INSULATED PLEMUM THE
FULL SIZE OF THE 5'-0" x 6'-0" LOUVER. DIVIDE
PLENUM DOWN THE MIDDLE WITH 2.5' ON
EACH SIDE.
5 PROVIDE STATIC PRESSURE SENSOR AT END
OF DUCT. CONTRACTOR TO COORDINATE
EXACT LOCATION DURING THE SUBMITTAL
PROCESS.
G12Z OPEN STORAGE NONE REQUIRED
G12CC IV BUFFER 7
G12MM IV BUFFER 7
G12FF BCG 7
G12DD IV ANTEROOM 7
G12X HD STORAGE NONE REQUIRED
G12GG HD ANTEROOM 7
G12HH HD BUFFER 7
ROOM # ROOM NAME ISO CLASS
ROOM ISO CLASSIFICATIONS
PAT ED
BOOTHS
G13
IV
BUFFER
G12CC
HD
BUFFER
G12HH
HD
ANTEROOM
G12GG
HD
STAGING
G12X
DELIVERY/
RECYCLING
/WASTE
PICKUP
G12U
RECEIVING
TEARDOWN
G12V
OPEN
STORAGE
G12Z
CORRIDOR
G12W
OFFICE
G12AA
IV
ANTEROOM
G12DD
100SD-12
100SD-11
200SD-12
200SD-12
150SD-12
200SD-12
380SD-14
IV PREP
G12R
ANTE
G12S
CHEMO
G12T
325EG-24
90EG-21
FFU-A
FFU-B
FFU-A
FFU-A FFU-A
445460
A
C
D
E
F
G
GG
30 34 37 40
2625.5
B
170RG-22
170RG-22
COORDINATE WORK WITH OTHER
TRADES AND THE COR TO
MINIMIZE DISRUPTION OF AREAS.
A.
AGRICULTURE
S
IL
AS
P. GEORG
E
R E G
IS
T E
RED ENG
IN
E E R
C O M M E R C E
N o . 12 0 6 3 4
S T A
T E
OF T ENNE
S
S E E
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:0
P M
MH102
AIR TERMINAL PLAN
3 13SPG PA
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
AIR TERMINAL PLAN 0 4 8 16
NORTH
PLAN
1 BALANCE EXHUAST TO AIRFLOW IN.
PAT ED
BOOTHS
G13
IV
BUFFER
G12CC
HD
BUFFER
G12HH
HD
ANTEROOM
G12GG
HD
STAGING
G12X
DELIVERY/
RECYCLING
/WASTE
PICKUP
G12U
RECEIVING
TEARDOWN
G12V
OPEN
STORAGE
G12Z
CORRIDOR
G12W
OFFICE
G12AA
56-HC-1
56-HC-2
56-HC-3
57-TU-2
57-TU-1
57-HC-3
57-HC-2
AHU-56
RTU 3 RTU 2
L/S
L/S
L /S
1 1/4" HWS
S -3
C H
R2
C H
S
H W
R
H W
S
1 1/4" HWR
T
T
1 1/4"1 1/4"
3/4"3/4"
1" HWS
1" HWR
H W
R
H W
S 1
/2
H W
S
/2
H W
R
IV PREP
G12R
88 SF
ANTE
G12S
63 SF
CHEMO
G12T
58 SF
AHU-57
C R
-3
S -3
/2
C H
S
H W
R
/2
C H
R
IV
ANTEROOM
G12DD
IV
BUFFER
G12MM
57-HC-1
/4
H
W R
/4
H
W S
3/4" HWS
3/4" HWR
1" HWS
1" HWR
3/4"3/4"
3/4"3/4"
3/4" 3/4"
3/4" 3/4"
T
T
T
T
T
T
T
H W
S
A
C
D
E
F
G
GG
30 34 37 40
2625.5
B
57-TU-3
AGRICULTURE
S
IL
AS
P. GEORG
E
R E G
IS
T E
RED ENG
IN
E E R
C O M M E R C E
N o . 12 0 6 3 4
S T A
T E
OF T ENNE
S
S E E
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:0
P M
MP101
GROUND FLOOR MECHANICAL PIPING
PLAN
4 13SPG PA
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
Scale: 1/4" = 1'-0"
GROUND FLOOR MECHANICAL PIPING PLAN 0 4 8 16
NORTH
PLAN
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
A COORDINATE ALL WORK WITH THE GENERAL CONTRACTOR,
OTHER TRADES AND THE COR TO MINIMIZE DISRUPTION OF
AREAS OUTSIDE OF THE PROJECT LIMITS OF WORK.
MPS
MPS
LPS
M P S
STM
COND STM
COND
STM
COND
STM
COND
STM
COND
MPS
LPS
LPS
MPS
STM
COND
HWHS
A
B
C
D
E
F
G
30 34 37 402625.5
2 1/2" CHS
2 1/2" CHR
H W
S
H
W R
C H
R
C H
S
3-HWP-11
3-HX-10
3-HWP-10
3-CWP-11
3-AS-10
3-CWP-10
3-XT-10
A
C
D
E
F
G
30 34 37 402625.5
B
AGRICULTURE
S
IL
AS
P. GEORG
E
R E G
IS
T E
RED ENG
IN
E E R
C O M M E R C E
N o . 12 0 6 3 4
S T A
T E
OF T ENNE
S
S E E
## KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:0
P M
MP102
BASEMENT MECHANICAL PIPING PLAN
5 13SPG PA
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
BASEMENT MECHANICAL PIPING - PLAN 0 4 8 16
NORTH
PLAN
1 CONNECT TO EXISTING CHILLED WATER
PIPING.
2 NEW HOT WATER SUPPLY, HOT WATER
RETURN, CHILLED WATER SUPPLY, CHILLED
WATER RETURN, AND STEAM PIPING.
3 BURIED PIPE.
4 PIPE ENTERS CRAWLSPACE.
A COORDINATE ALL WORK WITH THE GENERAL CONTRACTOR,
OTHER TRADES AND THE COR TO MINIMIZE DISRUPTION OF
AREAS OUTSIDE OF THE PROJECT LIMITS OF WORK.
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS THE
NIPPLE ON THE DRAIN PAN. PIPING SHALL BE RIGIND
COPPER TYPE L OR TYPE M UNLESS NOTE BELOW IS
MET
PITCH DOWN TOWARD DRAIN
CLAEANOUT
FLOOR SINK
DRAIN PAN
DIALECTRIC FITTING
NOTES:
1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS INDOORS AND DOES
NOT PASS THROUHG RATED BARRIERS.
2. DIALECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE TO BE CONNECTED.
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAW THRU 2" PLUS X X
B A
ABOVE 2" [50mm] DIA. PIPE 2" [50mm] DIA. & SMALLER
VERTICAL
2 1/2" [65mm] DIA.
ABOVE 2" [50mm] DIA. PIPE 2" [50mm] DIA. & SMALLER
HORIZONTAL
2 1/2" [65mm] DIA.
NOM. SIZE (IN.)
PIPE (FT.)
TUBING (FT.)
5 FT
THRU 3/4
1 1 1/4
1 1/2
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR
LOW TEMPERATURE
PIPE)
PROVIDE HIGH
COMPRESSIVE
STRENGHT
INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD AT
HANGER
WELD
SADDLE
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE
SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE
SPECIFICATIONS
1/2" DIA. HANGER RODS WITH 36"
MAX. SPACING ON EACH CHANNEL
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2" x 2" x 1/4" ANGLE
NOTES:
SEE SPECIFICATIONS FOR
DETAILED HANGER
REQUIREMENTS. SIDE VIEW TRAPEZE HANGER
FOR UP TO 1000 LB. UNIFORM
LOAD
1" MAX.
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8" MIN.)
2 2 1/2 3 4 5 6 8 10 12
11 12 14 16 17 19 22 23
9 10 12 13 14 16 - -
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE
MAXIMUM PIPE/TUBING SUPPORT SPACING
SEE MANUFACTURER'S
PIPING RECOMMENDATIONS
FOR FINAL LAYOUT
AHU CROSS SECTION1/3 MODULATING CONTROL VALVE
STEAM SUPPLY
MANIFOLD PIPE ADAPTERS
TO HUMIDISTAT
HUMIDIFIER CONTROL VALVE
F & T TRAP ASSEMBLY
SCALE POCKET
TEMPERATURE SWITCH
STEAM
CONDENSATE
RETURN
A H
U H
E
IG
H T
H
/3
H
M
IN
2/3 MODULATING CONTROL VALVE
3-WAY PRESSURE
INDEPENDENT CONTROL
VALVE
AIR VENT
STRAINER WITH
DRAIN VALVE
COIL
BUTTERFLY VALVE
(TYP.)
NOTES:
1. CONTROL VALVE TO BE NORMALLY CLOSED (NC) FOR CHILLED WATER COILS.
2. ARRANGE PIPING TO ALLOW FOR COIL REMOVAL AND ACCESS FOR MAINTENANCE.
PRESSURE GAUGE
RETURN
SUPPLY
THERMOMETER
(TYP.)
DIRT LEG
BALL VALVE
(TYP.)
STEAM PIPE
RISER
INVERTED BUCKET
TRAP ASSEMBLYMV
MANUAL AIR
VENT
TO BUILDING LOAD
GATE VALVE
CONDENSATE
UNION
STRAINER
SCHEDULE 80
STEEL PIPE
TO
BUILDING
LOAD
1" GATE VALVE
SCALE POCKET/
DRIP LEG
" [3
0 M
M
" [150
M M
NOTE:
ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6" SCALE POCKET BELOW TRAP INLET.
DIELECTRIC FITTING WHERE
RETURN IS COPPER PIPE
TO RETURN MAIN
FLOAT AND THERMOSTATIC TRAP.
SEE PLANS, AND SCHEDULES
1" GATE
VALVE
SCHEDULE 80 STEEL PIPE
PIPE SIZE SHALL BE
SAME SIZE AS TRAP
BYPASS - INSTALL IN HORIZONTAL
PLANE LEVEL WITH TRAP OR IN
VERTICAL PLANE & BELOW TRAP
DRIP LEG OR EQUIPMENT CONNECTION.
MAKE THE SAME SIZE AS THE SUPPLY
MAIN OR EQUIPMENT CONNECTION. SEE
NOTE 1
M
IN
M
IN
FLOW
SEE DRAWINGS
FOR PIPE SIZES
SCALE
POCKET/ DRIP
LEG
SCHEDULE
80 STEEL
PIPE
PRESSURE GAUGE
STRAINER
1/2"
FLEXIBLE
CONNECTION (TYP.)
BALANCING DEVICE
BALL OR BUTTERFLY
VALVE (TYP.)
PIPE HANGERS: PROVIDE DOUBLE
DEFLECTION NEOPRENE (TYPE HN)
FOR FIRST TWO ON EACH SIDE OF
PUMP (SEE NOTE)
NOTE:
SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
NOTE:
1. SIZE AND SELECT COIL FOR
PARALLEL FLOW AND MINIMUM TUBE
WATER VELOCITY OF 3.0 FEET PER
SECOND.
MODULATING CONTROL
VALVE
HHWS
HHWR
INLINE PUMP
AV
AUTO. AIR VENT
TO DRAIN, TYP.
AV
SHUTOFF VALVE
FULL SIZE
CONNECTIONS
TO ALL COIL HEADER
TAPPINGS
BALANCING
DEVICE
MANUAL
BYPASS
VALVE
PREHEAT
COIL
AIR
MANUAL BYPASS VALVE
3-WAY MODULATING
CONTROL VALVE
COIL
3-WAY VAV COIL PIPING
RETURN
SUPPLY
COIL
2-WAY VAV COIL PIPING
DRAIN VALVE WITH HOSE
CONNECTION
MANUAL AIR VENT
UNION (TYPICAL)
2-WAY MODULATING
CONTROL VALVE
STRAINER WITH
DRAIN VALVE AND
HOSE CONNECTION
TEMPERATURE/PRESSURE TEST PORT
ISOLATION VALVE
RETURN
SUPPLY
ISOLATION VALVE
(TYP.)
UNION (TYPICAL)
MANUAL AIR VENT
DRAIN VALVE WITH HOSE
CONNECTION
STRAINER WITH
DRAIN VALVE AND
HOSE CONNECTION
CONCENTRIC REDUCERS,
IF REQUIRED (TYP.)
CONCENTRIC REDUCERS,
IF REQUIRED (TYP.) TEMPERATURE/PRESSURE TEST PORT
M V
M V
M V
WATER COIL
TI
FE
TEMPERATURE
INDICATION TO ECC.
SEE CONTROL DIAGRAM
(TYP.)
DRAIN
AIR VENT WHEN COIL IS
NOT SELF-VENTING
(TYP.)
DRAIN WHEN COIL IS
NOT SELF-DRAINING
(TYP.)
PIPE HANGERS SHALL SUPPORT
PIPING INDEPENDENT OF COIL
(TYP.)
REDUCER, IF REQUIRED (TYP.)
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST TWO HANGERS FOR EACH PIPE
SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" 4" DIA. PIPE & SMALLER. TYPE "H-P" FOR 5" DIA. PIPE & LARGER.
2. PIPING SHALL BE INSTALLED IN SUCH A MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS
OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALVES, OR EQUIPMENT.
3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM UPSTREAM AND
DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE RETURN PIPING.
SEE SCHEDULES FOR RELIEF
VALVESETTING
RUN DRAIN LINE FROM
RELIEF VALVE TO NEAREST
FLOOR DRAIN. (TYP.)
1/2" [15mm]
CHECK VALVE
VACUUM
BREAKER (TYP.)
DDC
TEMPERATURE
SENSORS
THERMOMETER
(TYP.)
HWR
HWS
TT
TT--
D
PI
CONTROL V
ALVES IN
2/3 & 1/3
SIZE A
RRANGEMENT, T
YP.
MPR T
O F
LASH
TANK (T
YP.)
THERMOSTATIS AIR
VENT (T
YP.)
SCALE P
OCKET
(T
YP.)
MPS
STEAM
SUPPLY
HEAT
EXCHANGER
(TYP.)
TEST
PLUG
(TYP.)
M
IN
[3 m m
(T Y
P
M
IN
[1 m m
(T Y
P
NOTE:
1. THE ABOVE DETAIL SHOWS REQUIRED PIPING FOR TWO HEAT EXCHANGERS IN PARALLEL.
2. PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR HEAT EXCHANGER. MOUNTING HEIGHT SHALL
BE ADJUSTED TO FACILITATE GRAVITY RETURN OF STEAM CONDENSATE.
3. CONTROL VALVES SHALL BE IN A 1/3 AND 2/3 SIZE ARRANGEMENT.
CONNECT TO SIDE OF PIPE
MAIN. AVOID TOP OR BOTTOM
CONNECTIONS TO PREVENT
AIR OR DEBRIS FROM
ENTERING PIPE TO THE TANK.
LOCK-SHIELD TYPE SHUTOFF
VALVE.
TANK CONNECTION LOCATIONS
MAY VARY DEPENDING ON
TANK SIZE AND
MANUFACTURER.
NOTES:
TO FLOOR DRAIN
HOUSEKEEPING PAD
RELIEF PLUG
PRE-CHARGING
AIR
CONNECTION
PRESSURE GUAGE
AUTOMATIC AIR VENT
SAFETY RELIEF VALVE
1FROM SYSTEM
AIR VENT (HIGH CAPACITY FLOAT TYPE)
DOMESTIC COLD WATER MAKE-UP
WITH RPBP AND PRV, SEE PLUMBING
PLANS
AIR SEPARATOR
(WITHOUT STRAINER)
ROUT FULL SIZE DRAIN LINE
TO NEAREST FLOOR DRAIN.
REFER TO PLUMBING
DRAWINGS FOR FLOOR DRAIN
LOCATION.
TO PUMP SUCTION
FLOOR
PRESSURIZED
EXPANSION TANK
AIR SEPARATOR AND EXPANSION TANK PIPING DETAIL (WITH FLOOR MOUNTED EXPANSION TANK)
AGRICULTURE
S
IL
AS
P. GEORG
E
R E G
IS
T E
RED ENG
IN
E E R
C O M M E R C E
N o . 12 0 6 3 4
S T A
T E
OF T ENNE
S
S E E
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:3
P M
M-501
MECHANICAL DETAILS
6 13SPG PA
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
SCALE: N.T.S.4
AIR HANDLING UNIT DRAIN TRAP DETAIL
SCALE: N.T.S.6 INSTALLATION OF THERMOMETER WELLS
Scale: N.T.S.
PIPE HANGER
Scale: N.T.S.
STEAM HUMIDIFIER - PIPING CONNECTIONS
Scale: N.T.S.
AHU 3-WAY CHW COIL PIPING DETAIL
Scale: N.T.S.
END OF STEAM LINE DRIP TRAP
Scale: N.T.S.
FLOAT AND THERMOSTATIC STEAM TRAP ASSEMBLY
Scale: N.T.S.
INLINE PUMP CONNECTIONS
Scale: N.T.S.
PREHEAT COIL (HOT WATER) - PIPING CONNECTIONS
Scale: N.T.S.
VAV COIL PIPING DETAIL
Scale: N.T.S.
WATER COILS - PIPING CONNECTIONS
Scale: N.T.S.
HEAT EXCHANGER - STEAM TO HOT WATER
Scale: 1/8" = 1'-0"
AIR SEPARATOR AND EXPANSION TANK PIPING DETAIL
NOTES:
1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1-1/2" MAXIMUM SPACE BETWEEN
VANES AND A 3/4" TRAILING EDGE.
4. WHEN W EQUAL W2 AND W1 IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE TYPE.
W1
W
MAIN SUPPLY
DUCT
PROVIDE VOLUME
DAMPER
PROVIDE
VOLUME
DAMPER
1/4 W OR
4" MIN.
SUPPLY REGISTER OR
BRANCH DUCT
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN
FOR SPLIT
DIMENSION
TURNING VANES
AIR FLOW
AIR FLOW
A
IR
F L O
W
AIR SPLIT DUCT TAKE-
OFF PLAN VIEW
BRANCH DUCT TAKE-OFF
PLAN VIEW
AIR FLOW
A
IR
F
LO
W
W
MAIN SUPPLY
DUCT
CONICAL TAP
TERMINAL UNIT DUCT TAKE-
OFF PLAN VIEW
AIR FLOW
A
IR
F
LO
W
W
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS THIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-16
INSULATION
DUCT
GASKET
INSULATION
SECTION "A-A"
ACCESS PANEL
CASING
GASKET HANDLE INSIDE
FLEXIBLE WASHER
FACTORY
FABRICATED LATCH
SECTION "B-B"
ACCESS DOOR
INSULATION
"B" "B"
"A"
"A"
NOTES:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
2. ALL STANDARD ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED , SUPPORTED AND FASTENED AS RECOMMENDED BY
SMACNA.
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
R
SHALL
EQUAL OR
BE
GREATER
THAN 1/6 W
R
SHALL
EQUAL OR
BE
GREATER
THAN 1/3 W
R
SHALL
EQUAL OR
BE
GREATER
THAN W
R
W
W
2/3W
R
/3
W
/3
W
1/2W
VAN
E
VAN
E R
W
1/6W
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
1-1/2" POCKET SLIP
DUCT
1-1/2" MIN. TO 3" MAX.
INSTALLED. 6" NOMINAL
WITH MATERIAL TAUT
1" FLANGE & HEM
BOLT ON 4" CENTERALTERNATE
POSITION OF
BOLT 1" x 1/8" BAND IRON
WASHER
FLANGED
CONNECTION ON FAN
SIDE
FLEXIBLE MATERIAL
AS SPECIFIED
5/16" FLANGE
BOLT ON 4" CENTERS
1" x 1/8" BAND IRON
WASHER
FALNGED
CONNECTION ON FAN
SIDE
1" x 1/8" DRAW BAND
FLEXIBLE
MATERIAL AS
SPECIFIED
SHEET
METAL
SCREWS ON
12" CENTERS
RIVET ON 4" CENTERS
DUCT
1-1/2" MIN. TO 3" MAX.
INSTALLED. 6" NOMINAL
WITH MATERIAL TAUT
RECTANGULAR FLEXIBLE CONNECTION
ROUND FLEXIBLE CONNECTION
1-1/2"1/2" 1/2"
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
NOTES:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
SECTIONSIDE ELEVATION
1/2" ROUND ROD PIN
1/8" CLEARANCE
ALL AROUND
INSIDE END
BEARING
INSULATION
STAND-OFF
DAMPER BLADE
HANDLE
WITH
LOCKING
QUADRANT
STIFFEN BLADE
AS REQUIRED
INSULATION SEE
SPECIFICATION
DUCT
OUTSIDE END BEARING
100 CFM
RECEIVING TEARDOWN
G12V
IV ANTEROOM
G12DD
CORRIDOR
G12W
HD STAGING
G12X
HD BUFFER
G12HH
IV BUFFER
G12MM
HD ANTEROOM
G12GG
IV BUFFER
G12CC
+445 CFM
65 CFM
-400 CFM
70 CFM
150 CFM
+100 CFM
50 CFM
+150 CFM
-90 CFM
60 CFM
+380 CFM -40 CFM
-390 CFM
-130 CFM
-400 CFM
70 CFM
-270 CFM
-335 CFM
-40 CFM
-40 CFM
70 CFM
-575 CFM
-390 CFM
+460 CFM
-40 CFM
+560 CFM
85 CFM
+100 CFM
100 CFM
150 CFM
-325 CFM
+600 CFM
+460 CFM
+460 CFM
OFFICE
G12AA
AGRICULTURE
S
IL
AS
P. GEORG
E
R E G
IS
T E
RED ENG
IN
E E R
C O M M E R C E
N o . 12 0 6 3 4
S T A
T E
OF T ENNE
S
S E E
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:3
P M
M-502
MECHANICAL DETAILS
7 13SPG PA
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
SCALE: N.T.S.5 DUCTWORK SQUARE VANE ELBOWS
SCALE: N.T.S.3 SUPPLY DUCT TAKE-OFFS
SCALE: N.T.S.1 ACCESS PANEL AND DOOR DETAIL
SCALE: N.T.S.4 DUCTWORK RADIUS ELBOW
SCALE: N.T.S.6
FLEXIBLE DUCT CONNECTIONS
SCALE: N.T.S.2 VOLUME DAMPER DETAIL
Scale: N.T.S.
GROUND FLOOR ROOM PRESSURIZATION PLAN
G12Z OPEN STORAGE NONE REQUIRED
G12CC IV BUFFER 7
G12MM IV BUFFER 7
G12FF BCG 7
G12DD IV ANTEROOM 7
G12X HD STORAGE NONE REQUIRED
G12GG HD ANTEROOM 7
G12HH HD BUFFER 7
ROOM # ROOM NAME ISO CLASS
ROOM ISO CLASSIFICATIONS
M
CT
VFD
BO - Supply Fan Start/Stop
BI - Supply Fan Status
AO - Supply Fan VFD Speed
BI - Supply Fan VFD Fault
Locate ¾ distance down longest duct
H
L
AI - Supply Air Static Pressure
SA
BI - High Static Shutdown
H L
BI - UV Light
AI - Supply Air Humidity AO - Humidifier
BO - Humidifier Enable
H
STM
M
L s
DX
AO - Cooling Valve
CHWS
CHWR
M
CHW
H L
AI - Prefilter Differential Pressure
M
N.C.
AI - Mixed Air Temp
T
BI - Freezestat
T
H
AI - Space Humidity
T
AI - Space Temp
H L
AI - Final Filter Differential Pressure
AO - Preheating Valve
HWS
HWR
M
HW
OA
T
AI - Supply Air Temp
SF
M
CT
VFD
BO - Supply Fan Start/Stop
BI - Supply Fan Status
AO - Supply Fan VFD Speed
BI - Supply Fan VFD Fault
Locate ¾ distance down longest duct
H
L
AI - Supply Air Static Pressure
SA
BI - High Static Shutdown
H L
BI - UV Light
H
STM
M
AI - Supply Air Humidity AO - Humidifier
BO - Humidifier Enable
L s
DX
AO - Cooling Valve
CHWS
CHWR
M
CHW
H L
AI - Prefilter Differential Pressure
M
M AO - Mixed Air Dampers
N.O.
N.C.
AI - Mixed Air Temp
T
BI - Freezestat
T
H
AI - Return Air Humidity
T
AI - Return Air Temp
H L
AI - Final Filter Differential Pressure
AO - Preheating Valve
HWS
HWR
M
HW
OA
RA
T
AI - Supply Air Temp
SF
RUN CONDITIONS - CONTINUOUS:
THE UNIT SHALL RUN CONTINUOUSLY.
EMERGENCY SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL.
FREEZE PROTECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A FREEZESTAT STATUS.
HIGH STATIC SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN HIGH STATIC SHUTDOWN SIGNAL.
SUPPLY FAN:
THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
SUPPLY AIR DUCT STATIC PRESSURE CONTROL:
THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT OF 1.5IN H2O (ADJ.). THE SUPPLY FAN VFD SPEED SHALL NOT DROP
BELOW 30% (ADJ.).
PREHEATING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE THE PREHEATING COIL VALVE TO
MAINTAIN ITS SETPOINT 5°F (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT.
THE PREHEATING SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS LESS THAN 60°F (ADJ.).
• AND THE ECONOMIZER (IF PRESENT) IS DISABLED.
• AND THE SUPPLY FAN STATUS IS ON.
THE PREHEATING COIL VALVE SHALL OPEN FOR FREEZE PROTECTION WHENEVER:
• MIXED AIR TEMPERATURE DROPS FROM 40°F TO 35°F (ADJ.).
• OR THE FREEZESTAT (IF PRESENT) IS ON.
SUPPLY AIR TEMPERATURE SETPOINT - OPTIMIZED:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN A SUPPLY AIR
TEMPERATURE SETPOINT RESET BASED ON ZONE COOLING AND HEATING REQUIREMENTS
THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR COOLING BASED ON ZONE COOLING REQUIREMENTS
AS FOLLOWS:
• THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F (ADJ.).
• AS COOLING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 50°
F (ADJ.).
• AS COOLING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 65°
F (ADJ.) .
IF MORE ZONES NEED HEATING THAN COOLING, THEN THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET
FOR HEATING AS FOLLOWS:
• THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 62°F (ADJ.).
• AS HEATING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 55°
F (ADJ.).
• AS HEATING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 60°
F (ADJ.).
COOLING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE COOLING COIL VALVE TO
MAINTAIN ITS COOLING SETPOINT.
THE COOLING SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).
• AND THE ECONOMIZER (IF PRESENT) IS DISABLED OR FULLY OPEN.
• AND THE SUPPLY FAN STATUS IS ON.
• AND THE HEATING (IF PRESENT) IS NOT ACTIVE.
THE COOLING COIL VALVE SHALL OPEN TO 50% (ADJ.) WHENEVER THE FREEZESTAT (IF PRESENT) IS ON.
DEHUMIDIFICATION:
THE CONTROLLER SHALL MEASURE THE SPACE HUMIDITY AND OVERRIDE THE COOLING SEQUENCE BY REDUCING THE COOLING COIL DISCHARGE TEMPERATURE INCREMENTALLY TO A MINIMUM OF 50ºF (ADJ.) TO MAINTAIN SPACE HUMIDITY AT OR BELOW 60% RH (ADJ.). DEHUMIDIFICATION SHALL BE ENABLED WHENEVER THE SUPPLY FAN STATUS
IS ON.
HUMIDIFIER CONTROL:
THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND MODULATE THE HUMIDIFIER TO MAINTAIN A SETPOINT OF 50% RH (ADJ.). THE HUMIDIFIER SHALL BE ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON.
THE HUMIDIFIER SHALL TURN OFF WHENEVER:
• SUPPLY AIR HUMIDITY RISES FROM 90% RH TO 95% RH (ADJ.).
• OR ON LOSS OF SUPPLY FAN STATUS.
PREFILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE PREFILTER.
FINAL FILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FINAL FILTER.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• MIT (ADJ.).
SPACE HUMIDITY:
THE CONTROLLER SHALL MONITOR THE SPACE HUMIDITY AND USE AS REQUIRED FOR HUMIDITY CONTROL.
SPACE TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE SPACE TEMPERATURE AND USE AS REQUIRED FOR SETPOINT CONTROL OR
ECONOMIZER CONTROL (IF PRESENT).
SUPPLY AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
• HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) GREATER THAN
SETPOINT.
• LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) LESS THAN
SETPOINT.
• SUPPLY FAN VFD FAULT.
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) GREATER THAN SETPOINT.
• HIGH SUPPLY AIR HUMIDITY: IF THE SUPPLY AIR HUMIDITY IS GREATER THAN 90% RH (ADJ.).
• LOW SUPPLY AIR HUMIDITY: IF THE SUPPLY AIR HUMIDITY IS LESS THAN 30% RH (ADJ.).
• PREFILTER CHANGE REQUIRED: PREFILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT
(ADJ.).
• FINAL FILTER CHANGE REQUIRED: FINAL FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE
LIHIGH SPACE HUMIDITY: IF THE RETURN AIR HUMIDITY IS GREATER THAN 60% (ADJ.).
• LOW SPACE HUMIDITY: IF THE RETURN AIR HUMIDITY IS LESS THAN 30% (ADJ.).
• HIGH SPACE TEMP: IF THE SPACE TEMPERATURE IS GREATER THAN 75°F (ADJ.).
• LOW RETURN AIR TEMP: IF THE SPACE TEMPERATURE IS LESS THAN 65°F (ADJ.).
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 75°F (ADJ.).
• LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
FINAL FILTER DIFFERENTIAL PRESSURE X X
MIXED AIR TEMP X X X
PREFILTER DIFFERENTIAL PRESSURE X X
SPACE HUMIDITY X X X
SPACE TEMP X X X
SUPPLY AIR HUMIDITY X X X
SUPPLY AIR STATIC PRESSURE X X X X
SUPPLY AIR TEMP X X X
COOLING VALVE X X X
HUMIDIFIER X X X
MIXED AIR DAMPERS X X X
PREHEATING VALVE X X X
SUPPLY FAN VFD SPEED X X X
FREEZESTAT X X X X
HIGH STATIC SHUTDOWN X X X X
SUPPLY FAN STATUS X X X
SUPPLY FAN VFD FAULT X X X
HUMIDIFIER ENABLE X X
SUPPLY FAN START/STOP X X X
DEHUMIDIFICATION SETPOINT X X X
HUMIDIFIER SETPOINT X X
PREHEATING ENTERING AIR TEMP SETPOINT X X X
SUPPLY AIR STATIC PRESSURE SETPOINT X X X
SUPPLY AIR TEMP SETPOINT X X X
EMERGENCY SHUTDOWN X X X X
PREFILTER CHANGE REQUIRED X X
FINAL FILTER CHANGE REQUIRED X X
HIGH ENTERING AIR TEMP X
HIGH SPACE HUMIDITY X
HIGH SPACE TEMP X
HIGH SUPPLY AIR HUMIDITY X
HIGH SUPPLY AIR STATIC PRESSURE X
HIGH SUPPLY AIR TEMP X
LOW ENTERING AIR TEMP X
LOW SPACE HUMIDITY X
LOW SPACE TEMP X
LOW SUPPLY AIR HUMIDITY X
LOW SUPPLY AIR STATIC PRESSURE X
LOW SUPPLY AIR TEMP X
LOW SUPPLY AIR TEMP X
SUPPLY FAN FAILURE X
SUPPLY FAN IN HAND X
SUPPLY FAN RUNTIME EXCEEDED X
POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM
SHOW ON
GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
RUN CONDITIONS - CONTINUOUS:
THE UNIT SHALL RUN CONTINUOUSLY.
EMERGENCY SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL.
FREEZE PROTECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A FREEZESTAT STATUS.
HIGH STATIC SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN HIGH STATIC SHUTDOWN SIGNAL.
SUPPLY FAN:
THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
SUPPLY AIR DUCT STATIC PRESSURE CONTROL:
THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT OF 1.5IN H2O (ADJ.). THE SUPPLY FAN VFD SPEED SHALL NOT DROP
BELOW 30% (ADJ.).
PREHEATING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE THE PREHEATING COIL VALVE TO
MAINTAIN ITS SETPOINT 5°F (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT.
THE PREHEATING SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS LESS THAN 60°F (ADJ.).
• AND THE ECONOMIZER (IF PRESENT) IS DISABLED.
• AND THE SUPPLY FAN STATUS IS ON.
THE PREHEATING COIL VALVE SHALL OPEN FOR FREEZE PROTECTION WHENEVER:
• MIXED AIR TEMPERATURE DROPS FROM 40°F TO 35°F (ADJ.).
• OR THE FREEZESTAT (IF PRESENT) IS ON.
SUPPLY AIR TEMPERATURE SETPOINT - OPTIMIZED:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN A SUPPLY AIR
TEMPERATURE SETPOINT RESET BASED ON ZONE COOLING AND HEATING REQUIREMENTS
THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FOR COOLING BASED ON ZONE COOLING REQUIREMENTS
AS FOLLOWS:
• THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F (ADJ.).
• AS COOLING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 52°
F (ADJ.).
• AS COOLING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 65°
F (ADJ.) .
IF MORE ZONES NEED HEATING THAN COOLING, THEN THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET
FOR HEATING AS FOLLOWS:
• THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 82°F (ADJ.).
• AS HEATING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 85°
F (ADJ.).
• AS HEATING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 72°
F (ADJ.).
COOLING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE COOLING COIL VALVE TO
MAINTAIN ITS COOLING SETPOINT.
THE COOLING SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).
• AND THE ECONOMIZER (IF PRESENT) IS DISABLED OR FULLY OPEN.
• AND THE SUPPLY FAN STATUS IS ON.
• AND THE HEATING (IF PRESENT) IS NOT ACTIVE.
THE COOLING COIL VALVE SHALL OPEN TO 50% (ADJ.) WHENEVER THE FREEZESTAT (IF PRESENT) IS ON.
ECONOMIZER:
THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE THE ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN A SETPOINT 2°F (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT. THE OUTSIDE AIR DAMPERS SHALL MAINTAIN A MINIMUM ADJUSTABLE POSITION OF 20% (ADJ.) OPEN WHENEVER OCCUPIED.
THE ECONOMIZER SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).
• AND THE OUTSIDE AIR ENTHALPY IS LESS THAN 22BTU/LB (ADJ.)
• AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE.
• AND THE OUTSIDE AIR ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY.
• AND THE SUPPLY FAN STATUS IS ON.
THE ECONOMIZER SHALL CLOSE WHENEVER:
• MIXED AIR TEMPERATURE DROPS FROM 40°F TO 35°F (ADJ.)
• OR THE FREEZESTAT (IF PRESENT) IS ON.
• OR ON LOSS OF SUPPLY FAN STATUS.
THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN WHEN THE UNIT IS OFF. IF OPTIMAL START UP IS AVAILABLE THE MIXED AIR DAMPER SHALL OPERATE AS DESCRIBED IN THE OCCUPIED
MODE EXCEPT THAT THE OUTSIDE AIR DAMPER SHALL MODULATE TO FULLY CLOSED.
MINIMUM OUTSIDE AIR VENTILATION - FIXED PERCENTAGE:
THE OUTSIDE AIR DAMPERS SHALL MAINTAIN A MINIMUM ADJUSTABLE POSITION DURING BUILDING OCCUPIED HOURS
AND BE CLOSED DURING UNOCCUPIED HOURS.
DEHUMIDIFICATION:
THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND OVERRIDE THE COOLING SEQUENCE BY REDUCING THE COOLING COIL DISCHARGE TEMPERATURE INCREMENTALLY TO A MINIMUM OF 50ºF (ADJ.) TO MAINTAIN RETURN AIR HUMIDITY AT OR BELOW 60% RH (ADJ.). DEHUMIDIFICATION SHALL BE ENABLED WHENEVER
THE SUPPLY FAN STATUS IS ON.
HUMIDIFIER CONTROL:
THE CONTROLLER SHALL MEASURE THE RETURN AIR HUMIDITY AND MODULATE THE HUMIDIFIER TO MAINTAIN A SETPOINT OF 50% RH (ADJ.). THE HUMIDIFIER SHALL BE ENABLED WHENEVER THE SUPPLY FAN STATUS IS ON.
THE HUMIDIFIER SHALL TURN OFF WHENEVER:
• SUPPLY AIR HUMIDITY RISES FROM 90% RH TO 95% RH (ADJ.).
• OR ON LOSS OF SUPPLY FAN STATUS.
PREFILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE PREFILTER.
FINAL FILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FINAL FILTER.
MIXED AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE MIXED AIR TEMPERATURE AND USE AS REQUIRED FOR ECONOMIZER
CONTROL (IF PRESENT) OR PREHEATING CONTROL (IF PRESENT).
RETURN AIR HUMIDITY:
THE CONTROLLER SHALL MONITOR THE RETURN AIR HUMIDITY AND USE AS REQUIRED FOR ECONOMIZER CONTROL
(IF PRESENT) OR HUMIDITY CONTROL (IF PRESENT).
RETURN AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE RETURN AIR TEMPERATURE AND USE AS REQUIRED FOR SETPOINT CONTROL
OR ECONOMIZER CONTROL (IF PRESENT).
SUPPLY AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
• HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) GREATER THAN
SETPOINT.
• LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) LESS THAN
SETPOINT.
• SUPPLY FAN VFD FAULT.
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) GREATER THAN SETPOINT.
• LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) LESS THAN SETPOINT.
• HIGH SUPPLY AIR HUMIDITY: IF THE SUPPLY AIR HUMIDITY IS GREATER THAN 90% RH (ADJ.).
• LOW SUPPLY AIR HUMIDITY: IF THE SUPPLY AIR HUMIDITY IS LESS THAN 30% RH (ADJ.).
• PREFILTER CHANGE REQUIRED: PREFILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT
(ADJ.).
• FINAL FILTER CHANGE REQUIRED: FINAL FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT
(ADJ.).
• HIGH MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
• LOW MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
• HIGH RETURN AIR HUMIDITY: IF THE RETURN AIR HUMIDITY IS GREATER THAN 70% (ADJ.).
• LOW RETURN AIR HUMIDITY: IF THE RETURN AIR HUMIDITY IS LESS THAN 35% (ADJ.).
• HIGH RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
• LOW RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
• LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
FINAL FILTER DIFFERENTIAL PRESSURE X X
MIXED AIR TEMP X X X
PREFILTER DIFFERENTIAL PRESSURE X X
RETURN AIR HUMIDITY X X X
RETURN AIR TEMP X X X
SUPPLY AIR HUMIDITY X X X
SUPPLY AIR STATIC PRESSURE X X X X
SUPPLY AIR TEMP X X X
COOLING VALVE X X X
HEATING VALVE X X X
HUMIDIFIER X X X
MIXED AIR DAMPERS X X X
PREHEATING VALVE X X X
SUPPLY FAN VFD SPEED X X X
FREEZESTAT X X X X
HIGH STATIC SHUTDOWN X X X X
SUPPLY FAN STATUS X X X
SUPPLY FAN VFD FAULT X X X
HUMIDIFIER ENABLE X X
SUPPLY FAN START/STOP X X X
DEHUMIDIFICATION SETPOINT X X X
ECONOMIZER MIXED AIR TEMP SETPOINT X X X
HUMIDIFIER SETPOINT X X
PREHEATING MIXED AIR TEMP SETPOINT X X X
SUPPLY AIR STATIC PRESSURE SETPOINT X X X
SUPPLY AIR TEMP SETPOINT X X X
EMERGENCY SHUTDOWN X X X X
FINAL FILTER CHANGE REQUIRED X X
HIGH MIXED AIR TEMP X
HIGH RETURN AIR HUMIDITY X
HIGH RETURN AIR TEMP X
HIGH SUPPLY AIR HUMIDITY X
HIGH SUPPLY AIR STATIC PRESSURE X
HIGH SUPPLY AIR TEMP X
LOW MIXED AIR TEMP X
LOW RETURN AIR HUMIDITY X
LOW RETURN AIR TEMP X
LOW SUPPLY AIR HUMIDITY X
LOW SUPPLY AIR STATIC PRESSURE X
LOW SUPPLY AIR TEMP X
LOW SUPPLY AIR TEMP X
PREFILTER CHANGE REQUIRED X X
SUPPLY FAN FAILURE X
SUPPLY FAN IN HAND X
SUPPLY FAN RUNTIME EXCEEDED X
POINT NAME AI AO BI BO AV BV LOOP SCHED TREND ALARM
SHOW ON
GRAPHIC
HARDWARE POINTS SOFTWARE POINTS
AGRICULTURE
S
IL
AS
P. GEORG
E
R E G
IS
T E
RED ENG
IN
E E R
C O M M E R C E
N o . 12 0 6 3 4
S T A
T E
OF T ENNE
S
S E E
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7
/2
:1
:4
P M
M-503
MECHANICAL CONTROLS
8 13SPG PA
USP 800 PHARMACY
COMPLIANCE FOR YORK
VAMC - TVHS
3400 LEBANON RD, MURFREESBORO,
TN 37129
05/07/2019
FINAL CONSTRUCTION DOCUMENTS
626-30818-262
Scale: N.T.S.
AHU-56 SEQUENCE OF OPERATION
Scale: N.T.S.
AHU-56 POINTS LIST
Scale: N.T.S.
AHU-56 CONTROL DIAGRAM
Scale: N.T.S.
AHU-57 CONTROL DIAGRAM
Scale: N.T.S.
AHU-57 SEQUENCE OF OPERATION
Scale: N.T.S.
AHU-57 POINTS LIST
POINT NAME:
ZONE TEMPERATURE
ZONE TEMPERATURE SETPOINT
AIRFLOW
DISCHARGE AIR TEMPERATURE
ZONE DAMPER
REHEATING VALVE
MAXIMUM OCCUPIED AIRFLOW SETPOINT
HEATING MODE
HEATING SETPOINT
COOLING SETPOINT
HIGH ZONE TEMPERATURE
LOW ZONE TEMPERATURE
HIGH DISCHARGE TEMPERATURE
LOW DISCHARGE TEMPERATURE
HARDWARE POINTS
AI AO
X
X
X
X
BI BO
SOFTWAR…