This document is a unit description specification for a rooftop chilled water air handling unit (RTU-3) required for the Department of Veterans Affairs West Palm Beach VA Medical Center Cancer Center. The specification details a single JCI/York Model XTO-84x132 air handling unit with a capacity of 7,100 CFM, featuring 2-inch double wall foam insulated panels, heavy gauge galvanized exterior with stainless steel interior liners, and a 6-inch base rail with curb rest. The unit includes electrical components rated for 460/3/60 volts for the supply air fan disconnect and 120/1/60 volts for lights and UV lights, with exterior paint and NOA rating specified, access doors on all segments, and includes a base rail system.
Per the associated solicitation (36C24826Q1106, Amendment #2), the Department of Veterans Affairs is requesting quotes for the temporary replacement of the Cancer Center RTU-3 unit. Contractors are responsible for crane and safety lift plans, verifying VFD location, performing the crane lift of the new replacement unit, connecting chilled water and heating valve systems, and conducting testing, adjusting, and balance (TAB) services to ensure unit performance. The existing rental unit contractor handles removal of the current unit. Interested contractors must submit three Past Performance Questionnaires as part of their proposal response.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24826Q1106_2.docx | DOCX document | |
| VA WPB Cancer Center RTU-3 DrawingREV08-15.pdf | ||
| VA WPB Cancer Center RTU-3 - AHU Performance reportR1.pdf | ||
| 36C24826Q1106_1.docx | DOCX document | |
| ANSWERS TO CONTRACTOR QUESTIONS.pdf | ||
| 3- PAST PERFORMANCE QUESTIONNAIRE.docx | DOCX document | |
| 3a- PAST PERFORMANCE QUESTIONNAIRE.pdf | ||
| 1- Combined Synopsis.pdf | ||
| 36C24826Q1106.docx | DOCX document | |
| 2- Statement of Work RTU Replacement Unit.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Based on Existing Drawings by TLC Engineering Dated - 9/14/2009
ITEM A: (1) JCI/York Rooftop Chilled Water Air Handling Unit(s)
| QTY |
| Tag(s) |
| Description |
| 1 |
| RTU-3 |
| 7,100 CFM Model XTO-84x132 Air Handling Unit |
Equipment Summary
· 2” Double Wall Foam Insulated Panels
· Heavy Gauge Galvanized exterior and floors liner
· Stainless Steel Interior Liners
· Electrical – 2 circuits
· 460/3/60 – Disconnect for supply air fan
· 120/1/60 – Lights, UV Lights
· Exterior Paint
· NOA Rated
· 6” Base Rail
· Curb Rest
· Access Doors on Every Segment
· Total Weight <4500 LBS Mixing Box / Filter Segment
· 100% OA Hood w/ Galvanize Damper(s)
· 2” MERV 8 Pleated Filter
· 4” MERV 14 Mini Pleat Filter Heating Coil Segment
· Stainless Steel Drain Pan
· Stainless Steel Coil Casing
· Electrofin Coil Coating
· Hot Water Coil with Copper Tube / Aluminum Fins Cooling Coil Segment
· Stainless Steel Drain Pan
· Stainless Steel Coil Casing
· Electrofin Coil Coating with UV Protection
· Chilled Water-Cooling Coil with Copper Tube / Aluminum Fins
· Red Brass Connections Supply Fan Segment
· Direct Drive Fan
· 460V / 3Ph / 60Hz
· External Disconnect Access Segment
· Access Door for Upstream Filter Loading HEPA Filter Segment
· 11.5” 99.97% Efficiency HEPA Filter (Gasket Seal)
· Bottom Discharge
NOT INCLUDED: Wiring, Spare Filters, OA Monitoring, Temperature Controls, Disassembly and Reassembly of Unit, Control, Shut Off and Balancing Valves, Auxiliary Drain Pan, Smoke Detectors And Fire stats, CO2 Sensors, Freeze Stat And Alarm, External Vibration Isolation, Start Up and any material or labor not specifically described above.
Note(s)
1. Installing contractor to confirm the following:
a. Electrical Requirements
b. Dimensions/Clearances
c. Control Requirements
d. Weights
e. Piping Requirements