VA WPB Cancer Center RTU-3 DrawingREV08-15.pdf

PDF 783 KB Posted

Attached to
N041--Cancer center RTU-3 temporary unit replacement with new unit (Amendment# 2)
Solicitation number
36C24826Q1106
Issued by

About this file

This is a technical unit drawing for a York Solution RTU-3 (Rooftop Unit) designated for the VA WPB Cancer Center. The drawing package, consisting of 6 sheets, provides comprehensive dimensional and operational specifications for the heating, ventilation, and air conditioning unit dated August 14, 2025, with drawing designation XTO-57x66.

The unit has an overall length of 242.01 inches, width of 73.89 inches, and height of 64.19 inches, with an estimated shipping weight of 4,940 pounds (±10%). The drawing includes detailed specifications for piping connections with four coil connection points: two supply connections (S1 at 2.5" MPT and S2 at 1.5" MPT) and two return connections (R1 at 2.5" MPT and R2 at 1.5" MPT), plus one drain connection (D1 at 1.25"). The unit accommodates various filter sizes (24H x 12W in 2D, 4D, and 12D configurations, with optional 24H x 20W variants) and contains multiple internal components including dampers, fans, and heating/cooling coils across designated segments (DP, HF, XA-2, FS, CC, XA-1, HC, RF, MB). The drawing specifies dimension tolerances of ±1/2" for the unit and ±2" for piping, and includes a roof curb installation detail with Type A, B, and C mounting configurations. All dimensions are shown in inches, and the drawing explicitly states it is "NOT TO BE USED FOR CONSTRUCTION" and is presented at NTS (Not To Scale).

View the file

Other files

File Type Posted
36C24826Q1106_2.docx DOCX document
York Unit Description - VA WPB Cancer Center RTU-3 8.14.25.docx DOCX document
VA WPB Cancer Center RTU-3 - AHU Performance reportR1.pdf PDF
36C24826Q1106_1.docx DOCX document
ANSWERS TO CONTRACTOR QUESTIONS.pdf PDF
3- PAST PERFORMANCE QUESTIONNAIRE.docx DOCX document
3a- PAST PERFORMANCE QUESTIONNAIRE.pdf PDF
1- Combined Synopsis.pdf PDF
36C24826Q1106.docx DOCX document
2- Statement of Work RTU Replacement Unit.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

XTO-57x66

PROJECT NAME:

YORK SOLUTION UNIT DRAWING

MODEL:

VA WPB CANCER CENTER RTU-3

CONTRACT#:

UNIT

TAG:

RTU-3

ALL DIMENSIONS SHOWN IN:

DIMENSION TOLERANCES: UNIT (+/- 1/2"); PIPING (+/- 2")

08/14/2025 11:47:31 PM UTC

INCHES

Front

(Return)

Left

Right

Rear

(Supply)

AIRFLOW

DRAWING NOT TO BE USED FOR CONSTRUCTION

DRAWING SCALE: NTS

DESIGNATION: RTU-3

PLAN VIEW

REV DATE REVISION CHANGE REV BY

EaS Version: 1.23.6.2

SHEET 1 OF 6

ISOMETRIC VIEW

WEIGHT: 4940 (+/- 10%)

LEFT [ELEVATION] VIEWREAR VIEW FRONT VIEW

TOP [PLAN] VIEW

XTO-57x66

PROJECT NAME:

YORK SOLUTION UNIT DRAWING

MODEL:

VA WPB CANCER CENTER RTU-3

CONTRACT#:

UNIT

TAG:

RTU-3

ALL DIMENSIONS SHOWN IN:

DIMENSION TOLERANCES: UNIT (+/- 1/2"); PIPING (+/- 2")

08/14/2025 11:47:31 PM UTC

INCHES

Front

(Return)

Left

Right

Rear

(Supply)

AIRFLOW

DRAWING NOT TO BE USED FOR CONSTRUCTION

DRAWING SCALE: NTS

DESIGNATION: RTU-3

PLAN VIEW

REV DATE REVISION CHANGE REV BY

EaS Version: 1.23.6.2

SHEET 2 OF 6

EXTENTS VIEW

NOTES:

UNITS WITH A BASERAIL AND A BOTTOM OPENING: DUCT CONNECTION

FLUSH WITH THE BOTTOM OF UNIT, NOT FLUSH WITH BOTTOM OF BASERAIL.

REFER TO PERFORMANCE REPORT FOR SHIPPING SPLIT DETAILS.

ALLOW SUFFICIENT SPACE AROUND THE UNIT FOR REMOVING THE ACCESS

PANELS AND VARIOUS PARTS OF THE UNIT. A MINIMUM CLEARANCE EQUAL

TO THE WIDTH OF THE UNIT MUST BE PROVIDED ON ONE SIDE OF THE UNIT

FOR REMOVING THE COIL OR FAN ASSEMBLY.

CONTRACTOR RESPONSIBLE FOR PENETRATIONS AND CONNECTIONS OF

ALL ELECTRICAL BOXES AND INTERNAL COIL CONNECTIONS (IF PRESENT).

OVERALL DIMENSIONS ACCOUNT FOR COMPONENTS EXTENDING BEYOND

UNIT CABINET IN ORDER TO CONVEY THE TRUE SPACE REQUIREMENTS FOR

THE UNIT. THESE ITEMS MAY INCLUDE OUTDOOR ROOF PEAK, MOTOR

CONTROL AND/OR FACTORY PACKAGE CONTROL BOXES, WEATHER HOODS,

PIPE CHASES, DAMPER/LOUVER ASSEMBLIES, AND/OR UNIT BASE RAIL.

CERTAIN ITEMS MAY EXTEND BEYOND CABINET DIMENSIONS INCLUDING:

COIL CONNECTIONS, ROOF TRIM, DOOR HANDLES, LIGHT SWITCHES,

ELECTRICAL PANEL HANDLES, LIFTING LUGS, GAS FUEL SYSTEM, ETC.

THE OVERALL UNIT LENGTH MAY INCLUDE ADDITIONAL 1/4" PER SHIPPING

SPLIT (IF APPLICABLE) FOR GASKET AND CONNECTION HARDWARE.

FILTER DIMENSIONS ARE NOMINAL SIZES.

ELECTRICAL DEVICES (LIGHTS, SWITCHES, PANELS, ETC.) INDICATE

GENERAL AREA OF UNIT (E.G., SEGMENT); FINAL PLACEMENT DETERMINED

DURING MANUFACTURING.

SL

242.01 OVERALL LENGTH

O

V E

R A

L L

W

I D

T H

O

V E

R A

L L

H

E I G

H T

73.89

OVERALL WIDTH

29.06

MB

RF

HC

XA-1

CC

FS

XA-2

HF

DP

242.01 OVERALL LENGTH

SL

YORK SOLUTION UNIT DRAWING

MODEL:

VA WPB CANCER CENTER RTU-3

CONTRACT#:

UNIT

TAG:

RTU-3

ALL DIMENSIONS SHOWN IN:

DIMENSION TOLERANCES: UNIT (+/- 1/2"); PIPING (+/- 2")

08/14/2025 11:47:31 PM UTC

INCHES

Front

(Return)

Left

Right

Rear

(Supply)

AIRFLOW

DRAWING NOT TO BE USED FOR CONSTRUCTION

DRAWING SCALE: NTS

DESIGNATION: RTU-3

PLAN VIEW

REV DATE REVISION CHANGE REV BY

EaS Version: 1.23.6.2

SHEET 3 OF 6

ELEVATION VIEW

NOTE:

SKID WEIGHTS REPRESENT ESTIMATED SHIPPING WEIGHTS INCLUDING SHIPPING MATERIALS

AND/OR OPENING COVERS BUT DO NOT INCLUDE SHIP LOOSE AND/OR FIELD-INSTALLED ITEMS.

29.81

DP HF XA-2 FS CC XA-1 HC RF MB

4632 lbs

209 Unit Length (not including 0.25" gasket per End-channel split)

OA

SA

D1

UV

H x x

D

H

D

H x

D

D

H x

D

H x

D

SL

YORK SOLUTION UNIT DRAWING

MODEL:

VA WPB CANCER CENTER RTU-3

CONTRACT#:

UNIT

TAG:

RTU-3

ALL DIMENSIONS SHOWN IN:

DIMENSION TOLERANCES: UNIT (+/- 1/2"); PIPING (+/- 2")

08/14/2025 11:47:31 PM UTC

INCHES

Front

(Return)

Left

Right

Rear

(Supply)

AIRFLOW

DRAWING NOT TO BE USED FOR CONSTRUCTION

DRAWING SCALE: NTS

DESIGNATION: RTU-3

PLAN VIEW

REV DATE REVISION CHANGE REV BY

EaS Version: 1.23.6.2

SHEET 4 OF 6

PLAN VIEW

WEIGHT: 4940 (+/- 10%)

209 Unit Length (not including 0.25" gasket per End-channel split)

U n i t

W i d t h

UV

H x

D

D

D

W x

D

H x

D

D

D

W x

D

D

H x

W x

D

H x

W x

D

W x

D

SL

MB

RF

HC

XA-1

CC

FS

XA-2

HF

DP

YORK SOLUTION UNIT DRAWING

MODEL:

VA WPB CANCER CENTER RTU-3

CONTRACT#:

UNIT

TAG:

RTU-3

ALL DIMENSIONS SHOWN IN:

DIMENSION TOLERANCES: UNIT (+/- 1/2"); PIPING (+/- 2")

08/14/2025 11:47:31 PM UTC

INCHES

Front

(Return)

Left

Right

Rear

(Supply)

AIRFLOW

DRAWING NOT TO BE USED FOR CONSTRUCTION

DRAWING SCALE: NTS

DESIGNATION: RTU-3

PLAN VIEW

REV DATE REVISION CHANGE REV BY

EaS Version: 1.23.6.2

SHEET 5 OF 6

PIPING CONNECTIONS

WEIGHT: 4940 (+/- 10%)

COIL CONNECTIONS

CNCT XDIM YDIM SEG HAND TYPE SIZE SRVC

S2 168.1 10.7 HC RIGHT MPT 1.5 SPLY

S1 133.9 11.2 CC RIGHT MPT 2.5 SPLY

R1 143.5 56.0 CC RIGHT MPT 2.5 RTRN

R2 172.5 56.5 HC RIGHT MPT 1.5 RTRN

S1

R1

S2

R2

DRAIN CONNECTIONS

CNCT XDIM YDIM SEG HAND TYPE SIZE SRVC

D1 119.2 7.7 CC RIGHT

1.25 DRAIN

YORK SOLUTION UNIT DRAWING

MODEL:

VA WPB CANCER CENTER RTU-3

CONTRACT#:

UNIT

TAG:

RTU-3

ALL DIMENSIONS SHOWN IN:

DIMENSION TOLERANCES: UNIT (+/- 1/2"); PIPING (+/- 2")

08/14/2025 11:47:31 PM UTC

INCHES

Front

(Return)

Left

Right

Rear

(Supply)

AIRFLOW

DRAWING NOT TO BE USED FOR CONSTRUCTION

DRAWING SCALE: NTS

DESIGNATION: RTU-3

PLAN VIEW

REV DATE REVISION CHANGE REV BY

EaS Version: 1.23.6.2

SHEET 6 OF 6

CURB SHEET

WEIGHT: 4940 (+/- 10%)

11.00

1. CERTAIN ITEMS MAY EXTEND BYOND CABINET DIMENSIONS.

(ex. COIL CONNECTIONS, DOOR Handles, MOUNTING FEET, ETC.)

2. ROOF CURB MUST BE INSTALLED SQUARE And LEVEL.

3. CROSS BRACES As REQ'D: NO SPLICES OR CROSS BRACES WITHIN 10.00" OF

EITHER END OF PIPE CHASE. CROSS BRACING CAN BE LOCATED BETWEEN

PIPE CHASE ENDS.

NOTES:

HARDWOOD OR STEEL

SHIMS BETWEEN

ROOF DECKING AND

SUPPORT STRUCTURE

TYPE "C"

ROOF

DECKING

ROOF

INSULATION

CANT

STRIP

ROOFING

FELT

ROOF

STRUCTURE

3/16" THICK

BEARING

PLATE

ROOF

CURB

2" X 4"

NAILER

HARDWOOD OR STEEL

SHIMS BETWEEN

ROOF DECKING AND

SUPPORT STRUCTURE

TYPE "B"

ROOF

CURB

2" X 4"

NAILER

ROOF

DECKING

ROOF

INSULATION

CANT

STRIP

ROOFING

FELT

TYPE "A"

ROOF

DECKING

ROOF

INSULATION

CANT

STRIP

ROOFING

FELT

ROOF

CURB

2" X 4"

NAILER

CURB

INSULATION

DETAIL A

SCALE 1/2

TYPICAL

ROOF

STRUCTURE

ROOF

STRUCTURE

A

192.56