VA WPB Cancer Center RTU-3 - AHU Performance reportR1.pdf

PDF 419 KB Posted

Attached to
N041--Cancer center RTU-3 temporary unit replacement with new unit (Amendment# 2)
Solicitation number
36C24826Q1106
Issued by

About this file

This document is a York Air Handling Unit (AHU) Performance Report for the VA WPB Cancer Center RTU-3 project. The report provides comprehensive technical specifications for a single outdoor-rated XTO-57x66 model unit with a 7,100 CFM airflow capacity and operating weight of 4,424 lbs at sea level altitude.

The unit features enhanced thermal performance construction with high humidity outdoor air (OA) capability and comprises seven segments in sequence: Mixing Box (MB), Rigid Filter (RF), Cooling Coil (CC), Fan Supply (FS), Access (XA), HEPA Filter (HF), and Discharge Plenum (DP). All major casing segments utilize 2-inch foam insulation with champagne urethane exterior paint (3,500-hour rating), 16-gauge G-90 galvanized steel exterior, and 20-gauge 304 stainless steel interior. The cooling coil operates at 112.5 gpm fluid flow with entering fluid temperature of 44°F and leaving temperature of 56°F, achieving air cooling from 93°F dry bulb to 52.5°F. The supply fan is a Lau DDPG2 direct-drive unit powered by a 15 HP Baldor premium efficiency motor operating at 1,800 RPM, delivering 7,100 CFM at 8.09 inches water gauge total static pressure. The unit includes a pre-filter (MERV 8) and primary filter (MERV 14) in the RF segment, an 11.5-inch HEPA filter (99.97% efficiency) in the HF segment, UV surface decontamination lighting in the CC segment, and a CD50 aluminum airfoil control damper in the MB segment. Electrical requirements include 460/3/60V service at 18.1 FLA for the main disconnect with 40 AMP maximum overcurrent protection, plus 120/1/60V circuits for UV and control components. The unit ships at 4,129 lbs and measures 187 inches length, 78 inches width, and 69 inches height on the shipping skid, with an overall cabinet footprint of 181 inches by 66 inches width and 57 inches height.

View the file

Other files

File Type Posted
36C24826Q1106_2.docx DOCX document
York Unit Description - VA WPB Cancer Center RTU-3 8.14.25.docx DOCX document
VA WPB Cancer Center RTU-3 DrawingREV08-15.pdf PDF
36C24826Q1106_1.docx DOCX document
ANSWERS TO CONTRACTOR QUESTIONS.pdf PDF
3- PAST PERFORMANCE QUESTIONNAIRE.docx DOCX document
3a- PAST PERFORMANCE QUESTIONNAIRE.pdf PDF
1- Combined Synopsis.pdf PDF
36C24826Q1106.docx DOCX document
2- Statement of Work RTU Replacement Unit.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Job Summary Project Name: VA WPB Cancer Center RTU-3 Unit Tag(s): RTU-3 Quantity: 1 Environment: Outdoor

Unit Overview Model Airflow (CFM) Altitude (ft) Operating Weight (lbs)

XTO-57x66 7,100 0 4,424

Segment Sequence

(DP HF XA FS CC RF MB)

Unit Construction Casing Details

Segment(s) Thickness

(in) Exterior Paint Exterior Gauge and Material Interior Gauge and

Material

Insulation Thickness and

Material

Mylar Lining

Thermal Break

Bulkhead Material

MB, XA, DP 2"

Champagne

Urethane 3,500 Hr

16 Ga. G-90 Galvanized

20 Ga. 304 Stainless 2" Foam - - None

RF, CC, FS 2"

Champagne

Urethane 3,500 Hr

16 Ga. G-90 Galvanized

20 Ga. 304 Stainless 2" Foam - - Galvanized

Steel

HF 2"

Champagne

Urethane 3,500 Hr

16 Ga. G-90 Galvanized

20 Ga. 304 Stainless 2" Foam - - Stainless

Steel, 304

Base Details Segment(s) Material Paint

MB, RF, CC, FS, XA, HF, DP 6" Formed Steel Champagne Urethane 3,500 Hr Floor Details

Segment(s) Gauge and Material Paint Insulation Thermal Break Attachment Sub-Floor Gauge and Material

MB, RF, CC, FS, XA, HF, DP 20 Ga. 304 Stainless None 2" - Screw Down None

Notes Enhanced Thermal Performance construction.

High Humidity OA construction.

A curb rest will be provided with the unit.

Air Handling Unit Performance Report

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004

Unit Electrical Circuit Details

# Component(s) V/Ph/Hz Full Load Amps (FLA) Minimum Current Ampacity (MCA)

Maximum Overcurrent Protection (MOP)

1 FS External Wired Disconnect-1 (on FS) 460/3/60 18.1 22.63 40

2 CC UV Light Panel 120/1/60 1.24 15 15 3 Light Switch (on FS) 120/1/60 - - 15

Electrical Details Minimum Unit SCCR 50 kA rms Symmetrical ETL Label (UL1995/NEC-2002) Yes

Unit Light Type Light Switch Enclosure LED Outdoor

Air Handling Unit Performance Report

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004

Supply Fan(s) Performance Details

Fan Manufacturer Model # Blades Class Size % Wheel

Width % Wheel Diameter Quantity Airflow per Fan

(CFM) Altitude (ft) TSP (in w.g)

ESP (in w.g)

Fan Speed

(RPM)

Fan Power

(BHP)

Lau DDPG2 12 II 245 80 100 1 7,100 0 8.09 3.00 2,100 13.96

Max RPM Wheel Type

Blade Type

Wheel Material Base Material Fan Flow

Isolation AirFlow

Monitoring Inverter Drive

Balancing Isolation Type Thrust Restraints

2,269 SWSI Airfoil Aluminum Galvanized Steel None Yes (K=3092.00) - 2" Spring Yes

Drive Type FEI FEP (KW) Inlet Screen Fan Cage Fan Stand Motor Removal Rail Seismic Snubber

Direct Drive 1.23 11.24 - - - - - Motor Details

Type / MFG Motor Power (HP) V/Ph/Hz Quantity Insulation Class RPM Frame Size FLA (Amps) Efficiency Location SGR

TEFC / Baldor 15.0 460/3/60 1 H 1,800 254T 18.10 Premium Right Yes At Motor Synchronous Details

TSP (in w.g.) Total Air Flow (CFM) Fan Speed (RPM) Fan Power (BHP)

5.71 5,967 1,765 8.29

Notes Certified by the AHRI Central Station Air-Handling Unit (AHU) Certification Program, based on AHRI Standard 430/431. AHRI certified units are subject to rigorous and continuous testing, have performance ratings independently measured and are third-party verified. Certified units may be found in the AHRI Directory at www.ahridirectory.org Per California Energy Code (C.E.C.), Title 20, the selected fan ratings are only approved for use in equipment outside the state of California. Buyer assumes all liability for non-compliance of the noted regulation.

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004

Water Coil(s)

Coil Information Segment[Index] Coil Tag Coil Duty Fluid Type Airflow (cfm) Flow Direction Density Altitude (ft)

CC[1] - Cooling Water 7100 Horizontal Standard 0 Coil Bank Configuration

Segment[Index] Tube Diameter

(in) Fin Type

Total Fin Height (in)

Fin Length per Coil (in)

Face Velocity (fpm)

Stacking Rack Material Coils High Coils

Wide Coil

Configuration

Coil Stagger

(in)

Coil Pull Panel

CC[1] 0.500

Corrugated 47.50 54.00 399 - 1 1 Standard 0 Right Side

Airside Performance Segment[Index] EAT-DB (°F) EAT-WB (°F) LAT-DB (°F) LAT-WB (°F) TMBH SMBH Air Pressure Drop (in w.g.)

CC[1] 93.0 80.0 52.5 52.2 675 314 0.58

Fluidside Performance

Segment[Index] EFT (°F) LFT (°F) Fluid Velocity (fps) Fluid Flow (gpm) Fluid Pressure

Drop (ft) Rows Tubes Per Circuit Reynolds Number

CC[1] 44.0 56.0 3.9 112.5 10.5 8 6 11322

Fin and Tube Configuration

Segment[Index] Fin Thickness (in) / Material Fin Spacing (fpi)

Tube Thickness

(in) Turbulators Return Bend

Thickness Casing Material Coil Coating Fouling Factor (hr.ft².°F/BTU)

CC[1] 0.008 Aluminum 9 0.016 No 0.016 Stainless Electro Fin UV - Header and Connection Configuration

Segment[Index] Header Material

Connection Material

Connection Diameter (in)

Connection Offset (in)

Connection Type Connection Location/Rotation

CC[1] Red Brass Red Brass 2.5 0 MPT Right Other Performance

Segment[Index] Dry Weight (lbs) Fluid Weight (lbs) Internal Volume (ft³)

CC[1] 369 135 2.2

Notes

● Performance is shown for the entire coil bank. Performance is not per coil.

● Coil index indicates position in segment. Example: CC-1, index 1; Spacer, index 2; CC-1, index 3

● Ratings are for coils manufactured by Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202.

● CC[1]: AHRI Certified:Yes.Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program, which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

● All Coils: BDW Tube Spacing: 1.25 x 1.08

● All Coils: Coil Dll Version: 8.11

● CC[1]: Note: When Conditions that produce condensate exist, coil face velocities above 467 fpm may result in condensate carryover.

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004

Drain(s) Details

Segment Drain Pan

Liner Material Connection Location Liner Coating

CC Stainless Steel, 304 Right None

UV

UV Surface Decontamination Details

Segment Manufacturer Total Watts Amps V/Ph/Hz Radiometer

CC V-Max 149 1.24 120/1/60 -

Filter(s)

Segment Type Depth Filter Loading Media/MERV # of Spares Spare Filter Media Frame Material

RF Pre Filter 2" Side Pleated 30% Efficiency

(MERV 8) - -

Galvanized Steel RF Primary Filter 4" Side Mini Pleat 90% Efficiency

(MERV 14) - -

HF Primary Filter 11.5 Upstream HEPA 99.97% Efficiency (Gasket Seal) - - Stainless Steel, 304

Sizes Filter Gauge Details Segment Filter 1st Filter Size H x W

(in) 1st Qty 2nd Filter Size H x W

(in) 2nd Qty Location Type Range

(in w.g) RF Pre Filter 24x12 6 24x20 2

Door Combined Minihelic 0 - 2.0 RF Primary Filter 24x12 6 24x20 2 HF Primary Filter 23.375x11.375 6 23.375x19.375 2 Door Minihelic 0 - 2.0

Notes HEPA filters are sized as listed above (actual). All other filter types shown are nominal size.

Damper(s)

Segment Air Path H x W (in) Qty Total Face Velocity (ft/min)

Face Area (ft²)

Airflow

(CFM)

Min Airflow Measurement

(CFM)

Type Config Model Material Blade

Orientation

MB Outside Air 26.75 x

32.00 1 1,194 5.9 7,100 - Control 100% CD50 Galvanized Parallel

Hood(s) Details

Segment Air Path Quantity H x W x D(in) Face Velocity (ft/min) Airflow (CFM) Moisture Eliminator Bird Screen Weight (lbs)

MB Outside Air 1 37.38 x 35.70 x

29.00 987 7,100 - Yes 87

Notes

Air Handling Unit Performance Report

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004

Hoods ship loose

Door(s) Details

Segment(s) Location Swing Hinge Location H x W x T (in) View Port ViewPort

Wire Test Port

Spare Gasket

Thermal Break Fastener Type Safety

Latch

Noncontact Safety

Interlock MB Right Outward Front 51 x 18 x 2 None - - - - Plated - Yes RF Right Outward Front 51 x 10 x 2 None - - - - Plated - Yes CC Right Outward Rear 51 x 18 x 2 None - - - Yes Plated - Yes FS Right Outward Rear 51 x 22 x 2 None - - - Yes Plated Yes Yes XA Right Outward Front 51 x 18 x 2 None - - - Yes Plated Yes Yes

Motor Control(s) External Wired Disconnect Details

Served Segment V/Ph/Hz Amps Enclosure Disconnect Type Fuse Size Auxiliary Contacts FS 460/3/60 18.1 NEMA 3R Non-Fused - -

Use Copper Conductors Only. Do not use aluminum wire.

Face Velocity and Static Pressure Summary

Segment Description Face Area (ft²) Airflow

(CFM)

Face Velocity (ft/min)

Supply Fan Static Pressure

(in w.g.)

Exhaust/Return Fan Static Pressure (in w.g.)

MB CD50 (Control Damper 50 - Aluminum Airfoil) 5.9 7,100 1,194 0.05 0.00 MB Outside Air Opening 5.9 7,100 1,194 0.24 0.00 MB Standard Hood 7.2 7,100 987 0.04 0.00 MB Bird Screen 7.2 7,100 987 0.10 0.00 RF 2" Pleated 30% Efficiency (MERV 8) 18.7 7,100 380 0.20 0.00 RF Dirty Filter Allowance - Pre Filter 0.0 0 0.50 0.00 RF 4" Mini Pleat 90% Efficiency (MERV 14) 18.7 7,100 380 0.45 0.00 RF Dirty Filter Allowance 0.0 0 0.50 0.00 CC Cooling - 8 Row - 9 Fins Per Inch 17.8 7,100 399 0.58 0.00 CC UV Lights 0.0 7,100 0 0.03 0.00 FS External Static - User Entered 0.0 0 3.00 0.00 HF 12" HEPA 99.97% Efficiency (MERV 17) 17.4 7,100 409 1.11 0.00 HF Dirty Filter Allowance 0.0 0 0.50 0.00 DP Safety Cover 4.2 7,100 1,690 0.31 0.00 DP Supply Air Opening 4.2 7,100 1,690 0.48 0.00

Total 8.09 0.00

Air Handling Unit Performance Report

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004

Dimensions and Weight

Segment Description Length1 (in) Height (in) Width2 (in) Weight3 (lbs) MB Mixing Box 24 57 66 644 RF Rigid Filter 10 57 66 227 CC Cooling Coil 49 57 66 1,267 FS Fan (Supply) 40 57 66 1,122 XA Access 18 57 66 241 HF HEPA Filter 22 57 66 475 DP Discharge Plenum 18 57 66 448

Overall 181

Notes ¹The length includes bottom tier segments only.

²The width does not include coil connection extensions or door latches that extend beyond the unit casing. The width does not include the depth of any pipe chases.

³See Shipping Summary for notes on weights.

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004

Recommended Trap Height

Segment Applicable Fan Fan TSP (in w.g.) Positive or Negative Calculated Dimensions (in) Recommended Dimensions (in) Base Rail

Height (in) H X H + X H H + X

CC Supply Fan 8.09 Negative 7.19 3.60 10.78 7.25 10.75 6

Formulas and calculations are recommendations only. Contractor shall determine actual dimensions required for each trap based on jobsite conditions, and application requirements.

Refer to the Installation Manual of the IOM for more information.

Statement of Compliance

Air Handling Unit AHU's meet IBC seismic requirements for non-critical equipment (Ip = 1.0) for locations with design spectral response Sds <= 0.43.

Units must be rigid mounted.

The anchorage of the unit to the ground or building structure needs to be evaluated by and is the responsibility of the engineer of record.

Specification of seismic requirements is the responsibility of the project design engineer. If formal certification is required, please contact your sales representative and/or application engineer for review. Certain application and site requirements may require additional cost and/or lead time.

Component locations are listed as Segment Hand (Unit Hand): ex. Left (Right). See Submittal Drawing for additional details.

Air handling unit parameters vary depending on conditions. Parameters such as airflows, air pressure drops, and coil capacities are shown for design conditions.

Air Handling Unit Performance Report

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004

Shipping Summary

Skid Skid Length (in) Skid Height (in) Skid Width (in) Shipping Weight (lbs) Operating Weight (lbs)

DP HF XA FS CC RF MB 187 69 78 4,129 4,424

Weather Hood(s) N/A N/A N/A 87 N/A

Overall 4,424

Notes Skid Width: Total width of the shipping skid, including any items that may extend beyond the cabinet (this includes any door handles, coil connections, drain connections, lifting lugs, mounted pipe-chases, electrical/control components, tie-down brackets, side dampers).

Skid Height: Total height of the shipping skid, including any items that may extend beyond the cabinet (this includes any base-rails, shipping wood-blocks, roof peak, discharge flanges, mounted gas-furnace flue pipes).

Skid Length: Total length of the shipping skid, including any items that may extend beyond the cabinet (this includes any mounted rain-hoods, discharge flanges, tie-down brackets, shipping wood-blocks, front dampers, split connectors, electrical/control components, outrigging extensions, isolation dampers, inlet baskets).

Shipping Weight: Represents the estimated shipping weight with a tolerance of +/- 10% for values greater than 5,000 lbs. Values less than 5,000 lbs. may have higher percentage variation but not any consequential shipping impact. Shipping weight does not include ship loose and/or field-installed items but does include estimate for shipping materials and/or opening covers.

Operating Weight: Represents the estimated operational weight with a tolerance of +/- 10% for values greater than 5,000 lbs. Values less than 5,000 lbs. may have higher percentage variation. Operational weight estimate includes unit shell, internal components and structure, and known ship loose and/or field-installed items (weather hoods, pipe chases, factory-provided filter media and estimated fluid weight in coils). Actual operating weight will be heaver due to additional field installed materials including but not limited to field-provided filter media, piping, control devices, and/or inertia base concrete.

Project Name: VA WPB Cancer Center RTU-3 Last Saved: 07/24/2025-01:59:36 PM (UTC) Estimate Name: Unknown Software Version: 2025.06.25.004