Attch 3 Building 22 - Domiciliary - 2023.pdf
PDF 9 MB Posted
- Solicitation number
- 36C24825R0060
About this file
This document contains hydraulic sprinkler calculations for Building 22 (Domiciliary) at the West Palm Beach Veterans Medical Center. The comprehensive technical document includes detailed hydraulic analysis for both the first and second floor fire protection systems, with calculations performed on October 31, 2023 by Gulf States Engineering.
The first floor hydraulic calculations are for an Ordinary Hazard Group 1 area covering 1,500 square feet, with 20 sprinklers requiring 667.01 GPM at 37.86 psi, including a 250 GPM hose stream allowance. The second floor calculations cover a Light Hazard area of 900 square feet, with 7 sprinklers requiring 278.85 GPM at 84.03 psi, including a 100 GPM hose stream allowance. The calculations were conducted using AutoSPRINK RVT software and follow NFPA 13 (2016 Edition) standards, with the water supply providing sufficient pressure and flow for both floor systems.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FH 8
FH 4
INSTALL FIRE BOOSTER PUMP
NEW CONNECTION AND LINE
TO FEED MAIN BUILDINGS
OPEN IF WE NEED TO FEED LOOP FROM TOWER
DUE TO LOSS OF CITY SUPPLY.
VALVE WILL BE NORMALLY
OPEN TO MAINTAIN TRUE LOOP
NORMALLY CLOSED. OPEN ONLY IF WE
NEED TO FEED OFF CITY ONLY, NO TOWER
OPEN
FH 16
FIRE SP
FH 3
FH 6
FH 10
FH 15
FH 14
FH 11
FH 12
FH 13
OPEN. WE FEED OUR COOLING TOWERS
FROM THE LOOP.
NORMALLY CLOSED. THIS IS A
SECONDARY POINT TO SERVE MAIN BUILDING.
2 CLOSED
FH 1FH 2
FH 5
OPEN TO MAINTAIN TRUE LOOP.
PS
Covered Patio
Concrete
19FH 9
Pad
ER
PT
WEST PALM BEACH VAMC
CAMPUS DIRECTORY & WATER DISTRIBUTION
1. MAIN HOSPITAL
2. PARKING GARAGE
3. CLC COMMUNITY LIVING CENTER
4. FISHER HOUSE
5. EMERGENCY WELL (PUMP HOUSE)
6. MAS DRIVERS TRAILER
7. VA POLICE
8. MCCR (WOODBINE LEASE NOT
DEPICTED)
9. EMS SHREDDER
10. VBA/VSO BUILDING
11. TRANSPORTATION TRAILER
12. HUMAN RESOURCES
13. WAREHOUSE
14. ADMINISTRATIVE
15. CANCER CENTER
16. MENTAL HEALTH OUTPATIENT
17. DECON (IN TUNNEL)
18. PET/CT ADDITION
19. HOSPICE
20. MAINTENANCE BUILDING
21. MRI BUILDING
22. DOMICILIARY
W T
N.C.
W2 4" WM
6" FIRE 4" WM
12" WM
8" WM
12" WM
6" WM
12" WM
8" WM
BACKFLOW PREVENTER
STATION
INCOMING WATER
FROM MILITARY TR
12" WM
24 25
26 RBFP
M DOUBLE CHECK
RBFP
M
DOUBLE CHECK
12" WM
12" WM
8" WM
12" WM
INCOMING WATER FROM BLUE HERON BLVD
LIFT
M
M
INCO
M
ING W
ATER TO BLDG 1
M
W A T E R
T O
W E R
S
12" W M12" W
M
Gulf States Engineering, Inc.
GSEeng.com
600 Azalea Road, Mobile, AL 36609
(T) 251.460.4646 (F)251.460.4649
ENGINEER
CONTRACTOR
SEAL
DRAWN: CHECKED: APPROVED:
DATE: SCALE:
DWG NUMBER: REVISION:
T
IT
L E
PROJECT STATUS:
THIS DRAWING IS THE PROPERTY OF
GSE CONSULTING ENGINEERS &
VETERAN AFFAIRS. IT IS LOANED AND
SHALL BE RETURNED UPON REQUEST.
THE CONCEPTS HEREON SHALL NOT BE
USED, COPIED, OR DISCLOSED TO
OTHERS IN WHOLE OR PART WITHOUT
WRITTEN CONSENT.
(600 AZALEA ROAD, MOBLE, AL 36609)
Patriot Strategies, LLC 201 Union St. Ste 110 Alexandria, VA 22314
1/8" = 1'-0"
A
ZTW JCS JTW
10/31/23
FP-001
W E
S T
P A
LM
V
A S
P R
IN
K
LE
R
C A
LC
S
O V
E R
A L L
S
IT
E P
L A
N
ISSUED FOR
REVIEW
E n te r a d d re s s h e re
H Y
D R
A U
L
IC
C A
L C
U L
A T
IO
N
S
V E
T E
R A
N S
M E
D
IC
A L C
E N
T E
R
N.T.S.
1 OVERALL SITE PLAN
R E
V D
A T
E D
E S
C R
IP
T
IO
N
D R
A W
N B
Y
IS
S U
E D
B Y
A
/3
/2
IS
S U
E D
F O
R R
E V
IE
W
Z T
W J T
W
6'
/4
6.000ø
36' - 7"
6.000ø
6' - 10 1/8"
.0 ø
/4
4.000ø
5' - 2 3/4"
4.000ø
4' - 5"
.0 ø
/8
.0 ø
/2
.0 ø
/8
/4
2'
7'
" 2'
/8
4'
/8
2'
/4
1.250ø
3' - 10 3/4"
1.000ø
3 7/8" 1.000ø
5' - 9"
1.000ø
2' - 7 3/4"
.0 ø
/2
.0 ø
/4
1.000ø
9' - 10 1/4"
4.000ø
1' - 3"
3.000ø
62' - 11 1/8"
.0 ø
/8
1.250ø
3' - 11 1/4"
1.000ø
5' - 4 3/4"
1.000ø
11' - 2 1/8"
.0 ø
/8
1.500ø
4' - 0 1/2"
1.250ø
6' - 5 7/8"
1.000ø
3' - 9 7/8"
1.000ø
6' - 4 5/8"
.0 ø
/4
1.000ø
5 3/4"
.0 ø
/4
.0 ø
/4
.0 ø
/8
1.000ø
2' - 7 1/2"
.0 ø
/4
1.000ø
7' - 7 5/8"
1.000ø
11 7/8"
1.250ø
4' - 9 5/8"
1.500ø
4' - 5 3/4"
1.000ø
1' - 8 1/2"
1.000ø
10"
1.000ø
1' - 2 1/8"
1.250ø
3' - 10 1/2"
1.000ø
2' - 7 3/4"
1.000ø
9' - 3 1/2"
.0 ø
/8
12' - 2 5/8"
1.250ø
3' - 8"
1.000ø
6' - 10 1/8"
1.000ø
6' - 10"
.0 ø
/8
1.000ø
5 7/8"
.0 ø
/8
1.500ø
3' - 10 5/8"
1.500ø
8' - 3 1/2"
1.000ø
10' - 5"1 .0 ø
.0 ø
8.
0ø
4'
1/
2"
8.000ø
3' - 9 1/4"
8.000ø
4' - 11 1/2"
6.000ø
41' - 0 1/4"
6.
0ø
3"
2.500ø
7' - 2 5/8"
.0 ø
/8
3.000ø
27' - 10 1/4"
2'
/8
6' - 5 5/8" 10' - 0"
2.500ø
10' - 4"
3.000ø
27' - 10 1/4"
Occupancy Classification
Density
Total Hose Streams
Flowing Heads
K-Factor
Total Water Required
Total Pressure Required
Base of Riser
Base of Riser
Safety Margin
Hydraulic Information
Remote Area Name
Design Area (Actual)
Ordinary Hazard Group 1
0.15 GPM
250.00 GPM
20 @ 16.50 GPM
5.6
667.01 GPM
37.86 psi
667.01 GPM
37.86 psi
+0.59 (1.54%)
First Floor Remote Area
1600 SF
4.000ø
7 1/2"
1.000ø
4' - 7 1/2"
1.000ø
1' - 2 1/8"
1.000ø
1' - 2 1/8"
1.000ø
1' - 2 1/8"
1.000ø
1' - 7 1/8"
1.000ø
2 3/4"
1.000ø
1' - 2 1/8"
1.000ø
2 1/8"
1.000ø
1' - 7 1/8"
1.000ø
2 5/8" 1.000ø
1' - 2 1/8"
1.000ø
3' - 2 1/8"
.0 ø
/4
4.000ø
1' - 3 5/8"
1.000ø
1' - 2 1/8"
1.000ø
1' - 7 1/8"
1.000ø
3"
1.000ø
1' - 2 1/8"
1.000ø
1' - 2 1/8"
1.000ø
1' - 7 1/8"
1.000ø
2 3/4"
1.000ø
1' - 7 1/8"
1.000ø
1' - 2 1/8"
1.000ø
3"
1.000ø
2' - 6 1/4"
1.000ø
1 1/2" 1.000ø
5' - 9 1/8"
1.000ø
1 5/8"
1.000ø
1 5/8"
4.000ø
6 1/4"
8.000ø
4' - 3 1/8"
8.000ø
1/4"
8.000ø
1/4" 8.000ø
4' - 3 1/8"
6.000ø
3' - 5 7/8"
4.000ø
1/4"
2.500ø
1' - 0 5/8" 1.500ø
11"
2.500ø
5"
1.500ø
9 3/8"
10' - 7 1/2"
9' - 6"
9' - 4"
11' - 4"
-3' - 3 5/8"
FP-002
FP-003
FP-002
FP-003
FP-002
9' - 4"
9' - 4"
3/ 4"
Static Pressure
Residual Pressure
Flow
Outside Hose Flow
Conducted By
Witnessed By
Test Date
Test Time
Supply Information
62.00 psi
26.00 psi
839.00 GPM
0.00 GPM
Zachery Wilson
Justin Stewart
09/06/2023
10:00 A.M.
3'
3/ 8"
9'
/8
120 119
21 22
Level 1 Overall PLAN 0"
.0 ø
/8
.0 ø
/8
.0 ø
/8
4.000ø
4' - 5"
4.000ø
5' - 2 3/4"
.0 ø
/8
.0 ø
/4
4.000ø
7 1/2"
.0 ø
/8
.0 ø
.0 ø
/4
.0 ø
/8
6 7
Gulf States Engineering, Inc.
GSEeng.com
600 Azalea Road, Mobile, AL 36609
(T) 251.460.4646 (F)251.460.4649
ENGINEER
CONTRACTOR
SEAL
DRAWN: CHECKED: APPROVED:
DATE: SCALE:
DWG NUMBER: REVISION:
T
IT
L E
PROJECT STATUS:
THIS DRAWING IS THE PROPERTY OF
GSE CONSULTING ENGINEERS &
VETERAN AFFAIRS. IT IS LOANED AND
SHALL BE RETURNED UPON REQUEST.
THE CONCEPTS HEREON SHALL NOT BE
USED, COPIED, OR DISCLOSED TO
OTHERS IN WHOLE OR PART WITHOUT
WRITTEN CONSENT.
(600 AZALEA ROAD, MOBLE, AL 36609)
Patriot Strategies, LLC 201 Union St. Ste 110 Alexandria, VA 22314
As indicated
A
ZTW JCS JTW
09/26/23
FP-002
W E
S T
P A
LM
V
A S
P R
IN
K
LE
R
C A
LC
S
B U
L D
IN
G
D O
M
IC
IL
IA
R Y
ISSUED FOR
REVIEW
N
M ili ta ry
T rl W e s t P a lm
B e a c h F
L
H Y
D R
A U
L
IC
C A
L C
U L
A T
IO
N
S
V E
T E
R A
N S
M E
D
IC
A L C
E N
T E
R
3/16" = 1'-0"
LEVEL 1 FIRE PROTECTION PLAN 1 0F 3
Sprinkler Legend
Symbol Type Description Response K-Factor Count
1/2" Pendent R3516 F1RES49 4.9 (FR) Chrome 155°F Pendent Fast Response
4.9 7
1/2" Upright RA1425 F1FR56 5.6 (QR) Brass 155°F Upright Quick Response
5.6 3
1/2" Pendent TY-FRB Pendent Chrome 155°F/68°C 5.6K ½" NPT Quck Response
5.6 17
1/2" = 1'-0"
RISER DIAGRAM
KEY PLAN
1. NFPA 13 (2016 EDITION)
APPLICABLE CODES:
R E
V D
A T
E D
E S
C R
IP
T
IO
N
D R
A W
N B
Y
IS
S U
E D
B Y
A
/3
/2
IS
S U
E D
F O
R R
E V
IE
W
Z T
W J
.5 ø
/4
1.500ø
4' - 4 7/8"
.5 ø
/2
10' - 7"
9' - 6"
FP-002
FP-003
FP-002
FP-003
FP-002
FP-004
FP-003
FP-004
Gulf States Engineering, Inc.
GSEeng.com
600 Azalea Road, Mobile, AL 36609
(T) 251.460.4646 (F)251.460.4649
ENGINEER
CONTRACTOR
SEAL
DRAWN: CHECKED: APPROVED:
DATE: SCALE:
DWG NUMBER: REVISION:
T
IT
L E
PROJECT STATUS:
THIS DRAWING IS THE PROPERTY OF
GSE CONSULTING ENGINEERS &
VETERAN AFFAIRS. IT IS LOANED AND
SHALL BE RETURNED UPON REQUEST.
THE CONCEPTS HEREON SHALL NOT BE
USED, COPIED, OR DISCLOSED TO
OTHERS IN WHOLE OR PART WITHOUT
WRITTEN CONSENT.
(600 AZALEA ROAD, MOBLE, AL 36609)
Patriot Strategies, LLC 201 Union St. Ste 110 Alexandria, VA 22314
3/16" = 1'-0"
A
ZTW JCS JTW
09/26/23
FP-003
W E
S T
P A
LM
V
A S
P R
IN
K
LE
R
C A
LC
S
B U
IL
D
IN
G
D
O M
IC
IL
IA
R
Y
ISSUED FOR
REVIEW
N
M ili ta ry
T rl W e s t P a lm
B e a c h F
L
H Y
D R
A U
L
IC
C A
L C
U L
A T
IO
N
S
V E
T E
R A
N S
M E
D
IC
A L C
E N
T E
R
3/16" = 1'-0"
LEVEL 1 FIRE PROTECTION PLAN 2 OF 3
KEY PLAN
1. NFPA 13 (2016 EDITION)
APPLICABLE CODES:
R E
V D
A T
E D
E S
C R
IP
T
IO
N
D R
A W
N B
Y
IS
S U
E D
B Y
A
/3
/2
IS
S U
E D
F O
R R
E V
IE
W
Z T
W J
2.500ø
35' - 7 7/8"
10' - 5 5/8" 2.500ø
6' - 10 1/4"
9' - 7 1/2"
33' - 3 5/8" 6' - 11 3/4"
2' - 4 1/4" 2.500ø
6 7/8"
FP-002
FP-004
FP-003
FP-004
Gulf States Engineering, Inc.
GSEeng.com
600 Azalea Road, Mobile, AL 36609
(T) 251.460.4646 (F)251.460.4649
ENGINEER
CONTRACTOR
SEAL
DRAWN: CHECKED: APPROVED:
DATE: SCALE:
DWG NUMBER: REVISION:
T
IT
L E
PROJECT STATUS:
THIS DRAWING IS THE PROPERTY OF
GSE CONSULTING ENGINEERS &
VETERAN AFFAIRS. IT IS LOANED AND
SHALL BE RETURNED UPON REQUEST.
THE CONCEPTS HEREON SHALL NOT BE
USED, COPIED, OR DISCLOSED TO
OTHERS IN WHOLE OR PART WITHOUT
WRITTEN CONSENT.
(600 AZALEA ROAD, MOBLE, AL 36609)
Patriot Strategies, LLC 201 Union St. Ste 110 Alexandria, VA 22314
3/16" = 1'-0"
A
ZTW JCS JTW
09/26/23
FP-004
W E
S T
P A
LM
V
A S
P R
IN
K
LE
R
C A
LC
S
B U
IL
D
IN
G
D
O M
IC
IL
IA
R
Y
ISSUED FOR
REVIEW
N
M ili ta ry
T rl W e s t P a lm
B e a c h F
L
H Y
D R
A U
L
IC
C A
L C
U L
A T
IO
N
S
V E
T E
R A
N S
M E
D
IC
A L C
E N
T E
R
3/16" = 1'-0"
LEVEL 1 FIRE PROTECTION PLAN 3 OF 3
KEY PLAN
1. NFPA 13 (2016 EDITION)
APPLICABLE CODES:
R E
V D
A T
E D
E S
C R
IP
T
IO
N
D R
A W
N B
Y
IS
S U
E D
B Y
A
/3
/2
IS
S U
E D
F O
R R
E V
IE
W
Z T
W J
2.500ø
40' - 1 3/4"
.5 ø
/8
2.500ø
28' - 11 3/4"
.0 ø
/8
10' - 6 1/4"
.5 ø
/8
9' - 8"
3.000ø
12' - 8 3/8"
.0 ø
/2
1.500ø
7 1/8"
.5 ø
/4
39' - 6"
1.500ø
6 1/4"
9' - 8"
FP-005
FP-006
FP-005
FP-006
Gulf States Engineering, Inc.
GSEeng.com
600 Azalea Road, Mobile, AL 36609
(T) 251.460.4646 (F)251.460.4649
ENGINEER
CONTRACTOR
SEAL
DRAWN: CHECKED: APPROVED:
DATE: SCALE:
DWG NUMBER: REVISION:
T
IT
L E
PROJECT STATUS:
THIS DRAWING IS THE PROPERTY OF
GSE CONSULTING ENGINEERS &
VETERAN AFFAIRS. IT IS LOANED AND
SHALL BE RETURNED UPON REQUEST.
THE CONCEPTS HEREON SHALL NOT BE
USED, COPIED, OR DISCLOSED TO
OTHERS IN WHOLE OR PART WITHOUT
WRITTEN CONSENT.
(600 AZALEA ROAD, MOBLE, AL 36609)
Patriot Strategies, LLC 201 Union St. Ste 110 Alexandria, VA 22314
3/16" = 1'-0"
A
ZTW JCS JTW
09/26/23
FP-005
W E
S T
P A
LM
V
A S
P R
IN
K
LE
R
C A
LC
S
B U
IL
D
IN
G
D
O M
IC
IL
IA
R
Y
ISSUED FOR
REVIEW
N
M ili ta ry
T rl W e s t P a lm
B e a c h F
L
H Y
D R
A U
L
IC
C A
L C
U L
A T
IO
N
S
V E
T E
R A
N S
M E
D
IC
A L C
E N
T E
R
3/16" = 1'-0"
LEVEL 2 FIRE PROTECTION PLAN 1 OF 2
KEY PLAN
1. NFPA 13 (2016 EDITION)
APPLICABLE CODES:
R E
V D
A T
E D
E S
C R
IP
T
IO
N
D R
A W
N B
Y
IS
S U
E D
B Y
A
/3
/2
IS
S U
E D
F O
R R
E V
IE
W
Z T
W J
5'
1.000ø
9' - 10 3/8"
1.000ø
10 3/4"
.5 ø
/2
.5 ø
/4
2.000ø
39' - 3 1/8"
1.000ø
3' - 9 1/4"
.0 ø
/4
.5 ø
/4
.5 ø
/8
.5 ø
1.000ø
1' - 0 3/8"
1.000ø
8' - 1 3/4"
1.000ø
3' - 9 5/8"
9' - 7"
Occupancy Classification
Density
Total Hose Streams
Flowing Heads
K-Factor
Total Water Required
Total Pressure Required
Base of Riser
Base of Riser
Safety Margin
Hydraulic Information
Remote Area Name
Design Area (Actual)
Light Hazard
0.10 GPM
100.00 GPM
7 @ 23.85 GPM
4.9
278.85 GPM
84.03 psi
278.85 GPM
84.03 psi
-26.73 (-46.63%)
Second Floor Remote Area
1037 SF
.5 ø
1.000ø
1' - 3 7/8"
1.000ø
2' - 1 7/8"
1.000ø
7 5/8"
1.000ø
1' - 3 7/8"
.5 ø
/8
1.000ø
2' - 1 7/8"
1.000ø
7 3/4"
1.000ø
2' - 1 7/8"
.5 ø
/8
1.000ø
1' - 3 7/8"
.5 ø
/8
9' - 8"
9' - 8"
8' - 11 3/4"
4'
/4
/8
.5 ø
.5 ø
/4
.5 ø
.5 ø
/4
.5 ø
.5 ø
/4
.5 ø
.5 ø
/4
6'
/2
.5 ø
.5 ø
1.000ø
1' - 3 7/8"
1.000ø
3' - 8 7/8"
FP-005
FP-006
FP-005
FP-006
Gulf States Engineering, Inc.
GSEeng.com
600 Azalea Road, Mobile, AL 36609
(T) 251.460.4646 (F)251.460.4649
ENGINEER
CONTRACTOR
SEAL
DRAWN: CHECKED: APPROVED:
DATE: SCALE:
DWG NUMBER: REVISION:
T
IT
L E
PROJECT STATUS:
THIS DRAWING IS THE PROPERTY OF
GSE CONSULTING ENGINEERS &
VETERAN AFFAIRS. IT IS LOANED AND
SHALL BE RETURNED UPON REQUEST.
THE CONCEPTS HEREON SHALL NOT BE
USED, COPIED, OR DISCLOSED TO
OTHERS IN WHOLE OR PART WITHOUT
WRITTEN CONSENT.
(600 AZALEA ROAD, MOBLE, AL 36609)
Patriot Strategies, LLC 201 Union St. Ste 110 Alexandria, VA 22314
As indicated
A
ZTW JCS JTW
09/26/23
FP-006
W E
S T
P A
LM
V
A S
P R
IN
K
LE
R
C A
LC
S
B U
IL
D
IN
G
D
O M
IC
IL
IA
R
Y
ISSUED FOR
REVIEW
N
M ili ta ry
T rl W e s t P a lm
B e a c h F
L
H Y
D R
A U
L
IC
C A
L C
U L
A T
IO
N
S
V E
T E
R A
N S
M E
D
IC
A L C
E N
T E
R
3/16" = 1'-0"
LEVEL 2 FIRE PROTECTION PLAN 2 OF 2
Sprinkler Legend
Symbol Type Description Response K-Factor Count
1/2" Pendent R3516 F1RES49 4.9 (FR) Chrome 155°F Pendent Fast Response
4.9 7
1/2" Upright RA1425 F1FR56 5.6 (QR) Brass 155°F Upright Quick Response
5.6 3
1/2" Pendent TY-FRB Pendent Chrome 155°F/68°C 5.6K ½" NPT Quck Response
5.6 17
KEY PLAN
1. NFPA 13 (2016 EDITION)
APPLICABLE CODES:
R E
V D
A T
E D
E S
C R
IP
T
IO
N
D R
A W
N B
Y
IS
S U
E D
B Y
A
/3
/2
IS
S U
E D
F O
R R
E V
IE
W
Z T
W J
Location: 7305 N Military Trl, West Palm Beach, FL 33410, , Project Name: West Palm VA Sprinkler Hydraulic Calculations
Drawing Name: 22 - Domiciliary Calculation Date:10/31/2023
Hydraulic Calculations Summary for
Design
Ordinary Hazard Group 1
1500 SF
110 SF (typical)
First Floor Remote Area
0.15 GPM/SF
Remote Area Name:
Occupancy Classification:
Density
Area of Application:
Coverage per Sprinkler:
Type of Sprinklers Calculated:
No. of Sprinklers Calculated:
at Node:
Fire Protection Wet
N/AN/A
1250.00 GPM
0.0 galType of System:
In-rack Demand:
Hose Streams:
Volume of Dry or PreAction System:
at Node:
Type Allowance at Source
Total Water Required (including Hose Streams where applicable)
37.86 psi@667.01 GPMFROM: Water Supply at Node 1:
0.59 psiSafety Margin:
Gulf States Engineering
Veterans Medical Center
600 Azalea Rd, Mobile, AL 36609, 251-460-4646 Zachery Wilson
Contact Name
Address:
Phone Number:
Authority Having Jurisdiction:
Name of Designer:
Automatic Peaking Results
Notes:
10/31/2023 Page 1AutoSPRINK RVT v7.1.23.0 2:47:00PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Hydraulic Graph
Water Supply
Node: 1
Job Name: West Palm VA Sprinkler Hydraulic Calculations
Remote Area Name: First Floor Remote Area Date: 10/31/2023 N 1.85
Summary Sheet
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
10/31/2023 Page 1AutoSPRINK RVT v7.1.23.0 2:47:00PM@ M.E.P.CAD, Inc.
(GPM) (GPM) (K) (psi)
Outflowing Devices Report Description: Ordinary Hazard Group 1
Job Number: A23040
Device
Actual Flow Minimum Flow K-Factor Pressure
Sprinkler 102 20.51 GPM 16.50 GPM 5.6 13.41 psi
Sprinkler 107 19.65 GPM 16.50 GPM 5.6 12.31 psi
Sprinkler 112 22.05 GPM 16.50 GPM 5.6 15.50 psi
Sprinkler 114 22.71 GPM 16.50 GPM 5.6 16.45 psi
Sprinkler 108 23.67 GPM 16.50 GPM 5.6 17.87 psi
Sprinkler 113 22.48 GPM 16.50 GPM 5.6 16.11 psi
Sprinkler 115 22.39 GPM 16.50 GPM 5.6 15.99 psi
Sprinkler 116 22.14 GPM 16.50 GPM 5.6 15.63 psi
Sprinkler 106 22.31 GPM 16.50 GPM 5.6 15.87 psi
Sprinkler 104 19.66 GPM 16.50 GPM 5.6 12.32 psi
Sprinkler 103 19.36 GPM 16.50 GPM 5.6 11.95 psi
Sprinkler 105 21.16 GPM 16.50 GPM 5.6 14.28 psi
Sprinkler 111 22.11 GPM 16.50 GPM 5.6 15.59 psi
Sprinkler 110 19.93 GPM 16.50 GPM 5.6 12.67 psi
Sprinkler 109 19.83 GPM 16.50 GPM 5.6 12.54 psi
Sprinkler 118 17.08 GPM 16.50 GPM 5.6 9.30 psi
Sprinkler 119 16.50 GPM 16.50 GPM 5.6 8.68 psi
Sprinkler 120 18.75 GPM 16.50 GPM 5.6 11.21 psi
Sprinkler 101 22.37 GPM 16.50 GPM 5.6 15.96 psi
Sprinkler 117 22.34 GPM 16.50 GPM 5.6 15.92 psi
Most Demanding Sprinkler Data
10/31/2023 Page 1AutoSPRINK RVT v7.1.23.0 2:47:01PM@ M.E.P.CAD, Inc.
Job Name: West Palm VA Sprinkler Hydraulic Calculations
Remote Area Name: First Floor Remote Area Date: 10/31/2023
(psi) (psi)(GPM)(psi)(GPM)(psi)
Supply Analysis
Node Name Static Residual Flow Available Total Demand Required Pressure
26.00 psi1 37.86 psi667.01 GPM839.00 GPM 38.45 psi62.00 psiWater Supply
Node Analysis
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
-3' - 3 5/8" 417.01 GPM37.86 psi Supply
8' - 0 3/8" 22.37 GPM15.96 psi Sprinklers
8' - 0 3/8" 20.51 GPM13.41 psi Sprinklers
8' - 0 3/8" 19.36 GPM11.95 psi Sprinklers
8' - 0 3/8" 19.66 GPM12.32 psi Sprinklers
8' - 0 3/8" 21.16 GPM14.28 psi Sprinklers
8' - 0 3/8" 22.31 GPM15.87 psi Sprinklers
8' - 0 3/8" 19.65 GPM12.31 psi Sprinklers
8' - 0 3/8" 23.67 GPM17.87 psi Sprinklers
8' - 0 3/8" 19.83 GPM12.54 psi Sprinklers
8' - 0 3/8" 19.93 GPM12.67 psi Sprinklers
8' - 0 3/8" 22.11 GPM15.59 psi Sprinklers
8' - 0 3/8" 22.05 GPM15.50 psi Sprinklers
8' - 0 3/8" 22.48 GPM16.11 psi Sprinklers
8' - 0 3/8" 22.71 GPM16.45 psi Sprinklers
8' - 0 3/8" 22.39 GPM15.99 psi Sprinklers
8' - 0 3/8" 22.14 GPM15.63 psi Sprinklers
8' - 0 3/8" 22.34 GPM15.92 psi Sprinklers
12' - 4 7/8" 17.08 GPM9.30 psi Sprinklers
10/31/2023 Page 1AutoSPRINK RVT v7.1.23.0 2:47:01PM@ M.E.P.CAD, Inc.
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
12' - 5 1/8" 16.50 GPM8.68 psi Sprinklers
12' - 5 1/8" 18.75 GPM11.21 psi Sprinklers
-3' - 3 5/8" 37.71 psi2
-3' - 3 5/8" 32.53 psi3
-3' - 3 5/8" 30.38 psi4
1' - 0 3/8" 28.30 psi5
2' - 1" 27.80 psi6
2' - 1" 27.21 psi7
2' - 5 1/2" 35.15 psi8
3' - 2 1/8" 26.18 psi9
4' - 3" 24.54 psi11
9' - 4" 21.53 psi14
9' - 4" 20.12 psi15
9' - 4" 19.84 psi16
9' - 4" 19.84 psi17
9' - 4" 16.88 psi18
9' - 4" 14.09 psi19
9' - 4" 19.77 psi20
9' - 4" 13.43 psi21
9' - 4" 15.21 psi22
9' - 4" 16.96 psi23
9' - 4" 19.72 psi24
9' - 4" 19.66 psi25
10/31/2023 Page 2AutoSPRINK RVT v7.1.23.0 2:47:01PM@ M.E.P.CAD, Inc.
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
9' - 4" 13.63 psi26
9' - 4" 16.88 psi27
9' - 4" 19.65 psi28
9' - 4" 19.61 psi29
9' - 4" 17.92 psi30
9' - 4" 18.51 psi31
9' - 4" 18.68 psi32
9' - 4" 19.61 psi33
9' - 4" 19.61 psi34
9' - 4" 19.84 psi35
9' - 4" 19.84 psi36
9' - 4" 19.84 psi37
9' - 6" 19.65 psi38
9' - 6" 19.65 psi39
10' - 7" 19.18 psi44
10' - 7" 19.18 psi45
10' - 7 1/2" 19.03 psi46
10' - 7 1/2" 19.03 psi47
10' - 7 1/2" 19.03 psi48
11' - 4" 18.73 psi49
11' - 4" 18.30 psi50
11' - 4" 18.72 psi51
11' - 4" 18.31 psi52
10/31/2023 Page 3AutoSPRINK RVT v7.1.23.0 2:47:01PM@ M.E.P.CAD, Inc.
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
11' - 4" 18.72 psi53
11' - 4" 18.72 psi54
12' - 2" 12.85 psi55
12' - 2" 9.91 psi56
10/31/2023 Page 4AutoSPRINK RVT v7.1.23.0 2:47:01PM@ M.E.P.CAD, Inc.
Date: 10/31/2023
Remote Area Name: First Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
2' - 0"
12' - 2" 12' - 3 3/8"
0.11 psi
1.12 psi
12' - 5 1/8" 10' - 3 3/8"
1.000
• • • • • Route 1 • • • • •
(See
Notes)
1.049
8.68 psi16.50 GPM
0.09 psi
Sprinkler,
16.50 GPM
5.6
E(2' - 0"), Tr
6 FPS
5' - 0"
12' - 2" 8' - 7 7/8" 2.94 psi
12' - 2" 3' - 7 7/8"
1.000 (See
Notes)
1.049
9.91 psi17.08 GPM
0.34 psi
Flow (q) from Route 2
33.58 GPM T(5' - 0")
12 FPS
5' - 0"
9' - 4" 7' - 10"
1.23 psi
6.04 psi
12' - 2" 2' - 10"
1.000 (See
Notes)
1.049
12.85 psi18.75 GPM
0.77 psi
Flow (q) from Route 3
52.33 GPM PO(5' - 0")
19 FPS
26' - 4"
9' - 4" 36' - 1 1/2" 1.41 psi
9' - 4" 9' - 9 1/2"
4.000 (See
Notes)
4.260
20.12 psi364.68 GPM
0.04 psi
Flow (q) from Route 4
417.01 GPM 2E(13' - 2")
9 FPS
15' - 9 5/8"
4' - 3" 20' - 10 5/8"
2.20 psi
0.81 psi
9' - 4" 5' - 1"
4.000 (See
Notes)
4.260
21.53 psi
0.04 psi417.01 GPM BV(15' - 9 5/8"), Tr
9 FPS
28' - 11 5/8"
3' - 2 1/8" 30' - 0 1/2"
0.47 psi
1.17 psi
4' - 3" 1' - 0 7/8"
4.000 (See
Notes)
4.260
24.54 psi
0.04 psi417.01 GPM CV(28' - 11 5/8")
9 FPS
13' - 2"
2' - 1" 14' - 3 1/8"
0.48 psi
0.56 psi
3' - 2 1/8" 1' - 1 1/8"
4.000 (See
Notes)
4.260
26.18 psi
0.04 psi417.01 GPM E(13' - 2")
9 FPS
13' - 2"
2' - 1" 15' - 1 3/8" 0.59 psi
2' - 1" 1' - 11 3/8"
4.000 (See
Notes)
4.260
27.21 psi
0.04 psi417.01 GPM E(13' - 2")
9 FPS
1' - 0 3/8" 1' - 0 5/8"
0.46 psi
0.04 psi
2' - 1" 1' - 0 5/8"
4.000 (See
Notes)
4.260
27.80 psi
0.04 psi417.01 GPM red
9 FPS
14' - 0"
-3' - 3 5/8" 18' - 4"
1.88 psi
0.21 psi
1' - 0 3/8" 4' - 4"
6.000 (See
Notes)
5.500
28.30 psi
0.01 psi417.01 GPM E(14' - 0")
6 FPS
29' - 11 3/8"
-3' - 3 5/8" 136' - 6 1/2" 2.15 psi
-3' - 3 5/8" 106' - 7 1/8"
6.000 (See
Notes)
5.500
30.38 psi
0.02 psi417.01 GPM 4EE(4' - 11 7/8"), E(9' - 11 3/4")
6 FPS
10/31/2023 Page 1AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: First Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
25' - 8"
2' - 5 1/2" 37' - 1 3/8"
-2.50 psi
5.12 psi
-3' - 3 5/8" 11' - 5 3/8"
8.000 (See
Notes)
7.570
32.53 psi
0.00 psi417.01 GPM 2E(12' - 10"), BFP(-5.00 psi)
3 FPS
12' - 10"
-3' - 3 5/8" 18' - 7 1/8"
2.50 psi
0.06 psi
2' - 5 1/2" 5' - 9 1/8"
8.000 (See
Notes)
7.570
35.15 psi
0.00 psi417.01 GPM E(12' - 10")
3 FPS
25' - 8"
-3' - 3 5/8" 43' - 9 3/8" 0.15 psi
-3' - 3 5/8" 18' - 1 3/8"
8.000 (See
Notes)
7.570
37.71 psi
0.00 psi417.01 GPM E(12' - 10"), 2EE(6' - 5"), S
3 FPS
250.00 GPM Hose Allowance At Source
667.01 GPM
Route 1
37.86 psi
Total(Pt)
5' - 0"
12' - 2" 5' - 2 7/8"
0.10 psi
0.51 psi
12' - 4 7/8" 2 7/8"
1.000
• • • • • Route 2 • • • • •
(See
Notes)
1.049
9.30 psi17.08 GPM
0.10 psi
Sprinkler,
17.08 GPM
5.6
T(5' - 0")
6 FPS
9.91 psi Route 2Total(Pt)
7' - 0"
12' - 2" 13' - 2 3/8"
0.11 psi
1.52 psi
12' - 5 1/8" 6' - 2 3/8"
1.000
• • • • • Route 3 • • • • •
(See
Notes)
1.049
11.21 psi18.75 GPM
0.12 psi
Sprinkler,
18.75 GPM
5.6
E(2' - 0"), T(5' - 0")
7 FPS
12.85 psi Route 3Total(Pt)
6' - 0"
9' - 4" 16' - 7 1/4"
-0.56 psi
2.04 psi
8' - 0 3/8" 10' - 7 1/4"
1.000
• • • • • Route 4 • • • • •
(See
Notes)
1.049
11.95 psi19.36 GPM
0.12 psi
Sprinkler,
19.36 GPM
5.6
3E(2' - 0"), Tr
7 FPS
9' - 4" 3' - 11 3/4" 1.79 psi
9' - 4" 3' - 11 3/4"
1.000 (See
Notes)
1.049
13.43 psi19.66 GPM
0.45 psi
Flow (q) from Route 6
39.02 GPM Tr
14 FPS
9' - 4" 6' - 8" 1.75 psi
9' - 4" 6' - 8"
1.250 (See
Notes)
1.380
15.21 psi21.16 GPM
0.26 psi
Flow (q) from Route 10
60.18 GPM Tr
13 FPS
8' - 0"
9' - 4" 12' - 4 7/8" 2.76 psi
9' - 4" 4' - 4 7/8"
1.500 (See
Notes)
1.610
16.96 psi22.31 GPM
0.22 psi
Flow (q) from Route 14
82.49 GPM PO(8' - 0")
13 FPS
10/31/2023 Page 2AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: First Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
9' - 4" 2' - 2 3/4" 0.05 psi
9' - 4" 2' - 2 3/4"
4.000 (See
Notes)
4.260
19.72 psi215.53 GPM
0.02 psi
Flow (q) from Route 7
298.02 GPM Tr
7 FPS
9' - 4" 2' - 7 1/8" 0.08 psi
9' - 4" 2' - 7 1/8"
4.000 (See
Notes)
4.260
19.77 psi62.53 GPM
0.03 psi
Flow (q) from Route 5
360.55 GPM Tr
8 FPS
9' - 4" 9' - 0 3/8" 0.27 psi
9' - 4" 9' - 0 3/8"
4.000 (See
Notes)
4.260
19.84 psi4.13 GPM
0.03 psi
Flow (q) from Route 21
364.68 GPM Tr
8 FPS
20.12 psi Route 4Total(Pt)
9' - 0"
9' - 4" 18' - 7 1/4"
-0.56 psi
2.34 psi
8' - 0 3/8" 9' - 7 1/4"
1.000
• • • • • Route 5 • • • • •
(See
Notes)
1.049
12.31 psi19.65 GPM
0.13 psi
Sprinkler,
19.65 GPM
5.6
2E(2' - 0"), T(5' - 0")
7 FPS
9' - 4" 5' - 11" 2.79 psi
9' - 4" 5' - 11"
1.000 (See
Notes)
1.049
14.09 psi20.51 GPM
0.47 psi
Flow (q) from Route 9
40.16 GPM Tr
15 FPS
6' - 0"
9' - 4" 10' - 2 3/4" 2.88 psi
9' - 4" 4' - 2 3/4"
1.250 (See
Notes)
1.380
16.88 psi22.37 GPM
0.28 psi
Flow (q) from Route 16
62.53 GPM PO(6' - 0")
13 FPS
19.77 psi Route 5Total(Pt)
9' - 0"
9' - 4" 13' - 2 5/8"
-0.56 psi
1.67 psi
8' - 0 3/8" 4' - 2 5/8"
1.000
• • • • • Route 6 • • • • •
(See
Notes)
1.049
12.32 psi19.66 GPM
0.13 psi
Sprinkler,
19.66 GPM
5.6
2E(2' - 0"), T(5' - 0")
7 FPS
13.43 psi Route 6Total(Pt)
4' - 0"
9' - 4" 12' - 11 5/8"
-0.56 psi
1.66 psi
8' - 0 3/8" 8' - 11 5/8"
1.000
• • • • • Route 7 • • • • •
(See
Notes)
1.049
12.54 psi19.83 GPM
0.13 psi
Sprinkler,
19.83 GPM
5.6
2E(2' - 0"), Tr
7 FPS
9' - 4" 7' - 0" 3.25 psi
9' - 4" 7' - 0"
1.000 (See
Notes)
1.049
13.63 psi19.93 GPM
0.46 psi
Flow (q) from Route 8
39.76 GPM Tr
15 FPS
6' - 0"
9' - 4" 10' - 0" 2.77 psi
9' - 4" 4' - 0"
1.250 (See
Notes)
1.380
16.88 psi22.11 GPM
0.28 psi
Flow (q) from Route 12
61.87 GPM PO(6' - 0")
13 FPS
10/31/2023 Page 3AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: First Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
9' - 4" 2' - 0 3/8" 0.02 psi
9' - 4" 2' - 0 3/8"
4.000 (See
Notes)
4.260
19.65 psi129.99 GPM
0.01 psi
Flow (q) from Route 11
191.86 GPM Tr
4 FPS
9' - 4" 4' - 9 5/8" 0.06 psi
9' - 4" 4' - 9 5/8"
4.000 (See
Notes)
4.260
19.66 psi23.67 GPM
0.01 psi
Flow (q) from Route 20
215.53 GPM Tr
5 FPS
19.72 psi Route 7Total(Pt)
9' - 0"
9' - 4" 11' - 9 5/8"
-0.56 psi
1.53 psi
8' - 0 3/8" 2' - 9 5/8"
1.000
• • • • • Route 8 • • • • •
(See
Notes)
1.049
12.67 psi19.93 GPM
0.13 psi
Sprinkler,
19.93 GPM
5.6
2E(2' - 0"), T(5' - 0")
7 FPS
13.63 psi Route 8Total(Pt)
4' - 0"
9' - 4" 9' - 1"
-0.56 psi
1.24 psi
8' - 0 3/8" 5' - 1"
1.000
• • • • • Route 9 • • • • •
(See
Notes)
1.049
13.41 psi20.51 GPM
0.14 psi
Sprinkler,
20.51 GPM
5.6
2E(2' - 0"), Tr
8 FPS
14.09 psi Route 9Total(Pt)
7' - 0"
9' - 4" 10' - 4 5/8"
-0.56 psi
1.50 psi
8' - 0 3/8" 3' - 4 5/8"
1.000
• • • • • Route 10 • • • • •
(See
Notes)
1.049
14.28 psi21.16 GPM
0.14 psi
Sprinkler,
21.16 GPM
5.6
E(2' - 0"), T(5' - 0")
8 FPS
15.21 psi Route 10Total(Pt)
7' - 0"
9' - 4" 19' - 1 1/2"
-0.56 psi
2.98 psi
8' - 0 3/8" 12' - 1 1/2"
1.000
• • • • • Route 11 • • • • •
(See
Notes)
1.049
15.50 psi22.05 GPM
0.16 psi
Sprinkler,
22.05 GPM
5.6
E(2' - 0"), T(5' - 0"), Tr
8 FPS
6' - 0"
9' - 4" 11' - 2" 1.70 psi
9' - 4" 5' - 2"
1.250 (See
Notes)
1.380
17.92 psi22.71 GPM
0.15 psi
Flow (q) from Route 19
44.76 GPM PO(6' - 0")
10 FPS
9' - 4" 7' - 1" 0.03 psi
9' - 4" 7' - 1"
4.000 (See
Notes)
4.260
19.61 psi85.22 GPM
0.00 psi
Flow (q) from Route 13
129.99 GPM Tr
3 FPS
19.65 psi Route 11Total(Pt)
9' - 0"
9' - 4" 11' - 9 5/8"
-0.56 psi
1.85 psi
8' - 0 3/8" 2' - 9 5/8"
1.000
• • • • • Route 12 • • • • •
(See
Notes)
1.049
15.59 psi22.11 GPM
0.16 psi
Sprinkler,
22.11 GPM
5.6
2E(2' - 0"), T(5' - 0")
8 FPS
16.88 psi Route 12Total(Pt)
10/31/2023 Page 4AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: First Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
4' - 0"
11' - 4" 26' - 1"
-1.43 psi
4.10 psi
8' - 0 3/8" 22' - 1"
1.000
• • • • • Route 13 • • • • •
(See
Notes)
1.049
15.63 psi22.14 GPM
0.16 psi
Sprinkler,
22.14 GPM
5.6
2E(2' - 0"), 2Tr
8 FPS
6' - 0"
11' - 4" 10' - 3 1/2" 0.43 psi
11' - 4" 4' - 3 1/2"
1.250 (See
Notes)
1.380
18.30 psi
0.04 psi22.14 GPM PO(6' - 0")
5 FPS
13' - 2"
11' - 4" 20' - 1 1/8" 0.01 psi
11' - 4" 6' - 11 1/8"
4.000 (See
Notes)
4.260
18.72 psi18.21 GPM
0.00 psi
Flow (q) from Route 15
40.35 GPM E(13' - 2")
1 FPS
13' - 2"
9' - 4" 15' - 2"
0.87 psi
0.01 psi
11' - 4" 2' - 0"
4.000 (See
Notes)
4.260
18.73 psi
0.00 psi40.35 GPM E(13' - 2")
1 FPS
9' - 4" 2' - 4 1/4" 0.00 psi
9' - 4" 2' - 4 1/4"
4.000 (See
Notes)
4.260
19.61 psi
0.00 psi40.35 GPM Tr
1 FPS
9' - 4" 2' - 1" 0.00 psi
9' - 4" 2' - 1"
4.000 (See
Notes)
4.260
19.61 psi44.87 GPM
0.00 psi
Flow (q) from Route 17
85.22 GPM Tr
2 FPS
19.61 psi Route 13Total(Pt)
7' - 0"
9' - 4" 10' - 4 5/8"
-0.56 psi
1.65 psi
8' - 0 3/8" 3' - 4 5/8"
1.000
• • • • • Route 14 • • • • •
(See
Notes)
1.049
15.87 psi22.31 GPM
0.16 psi
Sprinkler,
22.31 GPM
5.6
E(2' - 0"), T(5' - 0")
8 FPS
16.96 psi Route 14Total(Pt)
4' - 0"
11' - 4" 23' - 11"
-1.43 psi
3.82 psi
8' - 0 3/8" 19' - 11"
1.000
• • • • • Route 15 • • • • •
(See
Notes)
1.049
15.92 psi22.34 GPM
0.16 psi
Sprinkler,
22.34 GPM
5.6
2E(2' - 0"), Tr
8 FPS
8' - 0"
11' - 4" 20' - 8 3/4" 0.41 psi
11' - 4" 12' - 8 3/4"
1.500 (See
Notes)
1.610
18.31 psi
0.02 psi22.34 GPM Tr, PO(8' - 0")
4 FPS
11' - 4" 14' - 3 3/4" 0.00 psi
11' - 4" 14' - 3 3/4"
4.000 (See
Notes)
4.260
18.72 psi
0.00 psi18.21 GPM Tr
0 FPS
18.72 psi Route 15Total(Pt)
10/31/2023 Page 5AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: First Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
7' - 0"
9' - 4" 9' - 3 1/4"
-0.56 psi
1.48 psi
8' - 0 3/8" 2' - 3 1/4"
1.000
• • • • • Route 16 • • • • •
(See
Notes)
1.049
15.96 psi22.37 GPM
0.16 psi
Sprinkler,
22.37 GPM
5.6
E(2' - 0"), T(5' - 0")
8 FPS
16.88 psi Route 16Total(Pt)
4' - 0"
9' - 4" 19' - 3"
-0.56 psi
3.09 psi
8' - 0 3/8" 15' - 3"
1.000
• • • • • Route 17 • • • • •
(See
Notes)
1.049
15.99 psi22.39 GPM
0.16 psi
Sprinkler,
22.39 GPM
5.6
2E(2' - 0"), 2Tr
8 FPS
9' - 4" 4' - 0 3/4" 0.17 psi
9' - 4" 4' - 0 3/4"
1.250 (See
Notes)
1.380
18.51 psi
0.04 psi22.39 GPM Tr
5 FPS
8' - 0"
9' - 4" 12' - 10 1/8" 0.92 psi
9' - 4" 4' - 10 1/8"
1.500 (See
Notes)
1.610
18.68 psi22.48 GPM
0.07 psi
Flow (q) from Route 18
44.87 GPM PO(8' - 0")
7 FPS
19.61 psi Route 17Total(Pt)
13' - 0"
9' - 4" 19' - 5"
-0.56 psi
3.14 psi
8' - 0 3/8" 6' - 5"
1.000
• • • • • Route 18 • • • • •
(See
Notes)
1.049
16.11 psi22.48 GPM
0.16 psi
Sprinkler,
22.48 GPM
5.6
4E(2' - 0"), T(5' - 0")
8 FPS
18.68 psi Route 18Total(Pt)
9' - 0"
9' - 4" 12' - 3 3/4"
-0.56 psi
2.03 psi
8' - 0 3/8" 3' - 3 3/4"
1.000
• • • • • Route 19 • • • • •
(See
Notes)
1.049
16.45 psi22.71 GPM
0.16 psi
Sprinkler,
22.71 GPM
5.6
2E(2' - 0"), T(5' - 0")
8 FPS
17.92 psi Route 19Total(Pt)
7' - 0"
9' - 4" 13' - 3 1/2"
-0.56 psi
2.36 psi
8' - 0 3/8" 6' - 3 1/2"
1.000
• • • • • Route 20 • • • • •
(See
Notes)
1.049
17.87 psi23.67 GPM
0.18 psi
Sprinkler,
23.67 GPM
5.6
E(2' - 0"), PO(5' - 0")
9 FPS
19.66 psi Route 20Total(Pt)
13' - 2"
11' - 4" 25' - 6" 0.00 psi
11' - 4" 12' - 3 7/8"
4.000
• • • • • Route 21 • • • • •
(See
Notes)
4.260
18.72 psi18.21 GPM
0.00 psi
Flow (q) from Route 15
4.13 GPM E(13' - 2")
0 FPS
26' - 4"
10' - 7 1/2" 27' - 0 5/8"
0.31 psi
0.00 psi
11' - 4" 8 5/8"
4.000 (See
Notes)
4.260
18.72 psi
0.00 psi4.13 GPM T(26' - 4")
0 FPS
10/31/2023 Page 6AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: First Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
10' - 7 1/2" 0" 0.00 psi
10' - 7 1/2" 0"
4.000 (See
Notes)
4.260
19.03 psi
0.00 psi4.13 GPM red
0 FPS
10' - 7 1/2" 9' - 8" 0.00 psi
10' - 7 1/2" 9' - 8"
2.500
2.635
19.03 psi
0.00 psi4.13 GPM
0 FPS
28' - 0"
9' - 6" 147' - 6"
0.49 psi
0.13 psi
10' - 7 1/2" 119' - 6"
1.500 (See
Notes)
1.610
19.03 psi
0.00 psi
PO(8' - 0")
4.13 GPM 3E(4' - 0"), PO(8' - 0")
1 FPS
8' - 2 7/8"
9' - 6" 14' - 11 5/8" 0.00 psi
9' - 6" 6' - 8 3/4"
2.500 (See
Notes)
2.635
19.65 psi
0.00 psi4.13 GPM E(8' - 2 7/8")
0 FPS
8' - 2 7/8"
10' - 7" 9' - 3 7/8"
-0.47 psi
0.00 psi
9' - 6" 1' - 1"
2.500 (See
Notes)
2.635
19.65 psi
0.00 psi4.13 GPM E(8' - 2 7/8")
0 FPS
10' - 7" 33' - 6 3/4" 0.00 psi
10' - 7" 33' - 6 3/4"
2.500
2.635
19.18 psi
0.00 psi4.13 GPM
0 FPS
20' - 0"
9' - 4" 133' - 8 1/2"
0.54 psi
0.12 psi
10' - 7" 113' - 8 1/2"
1.500 (See
Notes)
1.610
19.18 psi
0.00 psi
PO(8' - 0")
4.13 GPM E(4' - 0"), PO(8' - 0")
1 FPS
9' - 4" 6' - 2 1/4" 0.00 psi
9' - 4" 6' - 2 1/4"
2.500 (See
Notes)
2.635
19.84 psi
0.00 psi4.13 GPM red
0 FPS
20' - 1 7/8"
9' - 4" 20' - 1 7/8" 0.00 psi
9' - 4" 0"
3.000 (See
Notes)
3.260
19.84 psi
0.00 psi4.13 GPM T(20' - 1 7/8")
0 FPS
9' - 4 7/8"
9' - 4" 95' - 6 3/4" 0.00 psi
9' - 4" 86' - 1 3/4"
3.000 (See
Notes)
3.260
19.84 psi
0.00 psi4.13 GPM E(9' - 4 7/8"), red
0 FPS
26' - 4"
9' - 4" 26' - 4" 0.00 psi
9' - 4" 0"
4.000 (See
Notes)
4.260
19.84 psi
0.00 psi4.13 GPM T(26' - 4")
0 FPS
10/31/2023 Page 7AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: First Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
19.84 psi Route 21Total(Pt)
10/31/2023 Page 8AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: First Floor Remote Area
1.51
Fittings Legend
BFP Backflow Preventer BV Butterfly Valve CV Check Valve
E 90° Elbow EE 45° Elbow PO Pipe Outlet red Reducer/Adapter S Supply Spr Sprinkler
T Tee Flow Turn 90° Tr Tee run
4.87
1.33
1.16
0.713
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
10/31/2023 Page 9AutoSPRINK RVT v7.1.23.0 2:47:01PMFirst Floor Remote Area@ M.E.P.CAD, Inc.
Location: 7305 N Military Trl, West Palm Beach, FL 33410, , Project Name: West Palm VA Sprinkler Hydraulic Calculations
Drawing Name: 22 - Domiciliary Calculation Date:10/31/2023
Hydraulic Calculations Summary for
Design
Light Hazard
900 SF
239 SF (typical)
Second Floor Remote Area
0.10 GPM/SF
Remote Area Name:
Occupancy Classification:
Density
Area of Application:
Coverage per Sprinkler:
Type of Sprinklers Calculated:
No. of Sprinklers Calculated:
at Node:
Fire Protection Wet
N/AN/A
1100.00 GPM
0.0 galType of System:
In-rack Demand:
Hose Streams:
Volume of Dry or PreAction System:
at Node:
Type Allowance at Source
Total Water Required (including Hose Streams where applicable)
84.03 psi@278.85 GPMFROM: Water Supply at Node 1:
-26.73 psiSafety Margin:
Gulf States Engineering
Veterans Medical Center
600 Azalea Rd, Mobile, AL 36609, 251-460-4646 Zachery Wilson
Contact Name
Address:
Phone Number:
Authority Having Jurisdiction:
Name of Designer:
Automatic Peaking Results
Notes:
10/31/2023 Page 1AutoSPRINK RVT v7.1.23.0 2:47:44PMSecond Floor Remote Area@ M.E.P.CAD, Inc.
Hydraulic Graph
Water Supply
Node: 1
Job Name: West Palm VA Sprinkler Hydraulic Calculations
Remote Area Name: Second Floor Remote Area Date: 10/31/2023 N 1.85
Summary Sheet
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
10/31/2023 Page 1AutoSPRINK RVT v7.1.23.0 2:47:45PM@ M.E.P.CAD, Inc.
(GPM) (GPM) (K) (psi)
Outflowing Devices Report Description: Light Hazard
Job Number: A23040
Device
Actual Flow Minimum Flow K-Factor Pressure
Sprinkler 207 25.88 GPM 23.85 GPM 4.9 27.89 psi
Sprinkler 206 25.96 GPM 23.85 GPM 4.9 28.08 psi
Sprinkler 205 25.62 GPM 23.85 GPM 4.9 27.35 psi
Sprinkler 202 24.60 GPM 23.85 GPM 4.9 25.20 psi
Sprinkler 204 26.00 GPM 23.85 GPM 4.9 28.17 psi
Sprinkler 203 23.85 GPM 23.85 GPM 4.9 23.69 psi
Sprinkler 201 26.94 GPM 23.85 GPM 4.9 30.22 psi
Most Demanding Sprinkler Data
Remote Area Name: Second Floor Remote Area Date: 10/31/2023
(psi) (psi)(GPM)(psi)(GPM)(psi)
Supply Analysis
Node Name Static Residual Flow Available Total Demand Required Pressure
26.00 psi1 84.03 psi278.85 GPM839.00 GPM 57.31 psi62.00 psiWater Supply
Node Analysis
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
-3' - 3 5/8" 178.85 GPM84.03 psi Supply
20' - 10 5/8" 26.94 GPM30.22 psi Sprinklers
20' - 10 5/8" 24.60 GPM25.20 psi Sprinklers
20' - 10 5/8" 23.85 GPM23.69 psi Sprinklers
20' - 10 5/8" 26.00 GPM28.17 psi Sprinklers
20' - 10 5/8" 25.62 GPM27.35 psi Sprinklers
20' - 10 5/8" 25.96 GPM28.08 psi Sprinklers
20' - 10 5/8" 25.88 GPM27.89 psi Sprinklers
-3' - 3 5/8" 84.00 psi2
-3' - 3 5/8" 78.96 psi3
-3' - 3 5/8" 78.52 psi4
1' - 0 3/8" 76.60 psi5
2' - 1" 76.13 psi6
2' - 1" 76.01 psi7
2' - 5 1/2" 81.49 psi8
3' - 2 1/8" 75.42 psi9
4' - 3" 74.48 psi10
8' - 0" 72.59 psi12
8' - 0" 72.48 psi13
Remote Area Name: Second Floor Remote Area Date: 10/31/2023
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
9' - 11" 71.52 psi40
9' - 11" 71.19 psi41
9' - 11" 71.19 psi42
9' - 11" 66.50 psi43
22' - 4" 32.39 psi57
22' - 4" 30.45 psi58
22' - 4" 30.17 psi59
22' - 4" 30.17 psi60
22' - 4" 30.26 psi61
22' - 4" 33.69 psi62
22' - 4" 30.60 psi63
22' - 4" 30.45 psi64
23' - 2" 26.18 psi65
23' - 2 1/4" 59.48 psi66
23' - 2 1/4" 58.87 psi67
23' - 2 1/4" 60.07 psi68
23' - 2 1/4" 53.80 psi69
23' - 2 1/4" 52.21 psi70
23' - 2 1/4" 53.79 psi71
10/31/2023 Page 2AutoSPRINK RVT v7.1.23.0 2:47:45PM@ M.E.P.CAD, Inc.
Remote Area Name: Second Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
7' - 0"
23' - 2" 19' - 3 3/4"
-0.99 psi
3.48 psi
20' - 10 5/8" 12' - 3 3/4"
1.000
• • • • • Route 1 • • • • •
(See
Notes)
1.049
23.69 psi23.85 GPM
0.18 psi
Sprinkler,
23.85 GPM
4.9
E(2' - 0"), T(5' - 0")
9 FPS
5' - 0"
22' - 4" 5' - 10"
0.36 psi
3.90 psi
23' - 2" 10"
1.000 (See
Notes)
1.049
26.18 psi24.60 GPM
0.67 psi
Flow (q) from Route 2
48.45 GPM T(5' - 0")
18 FPS
22' - 4" 11' - 1 3/4" 1.94 psi
22' - 4" 11' - 1 3/4"
1.500 (See
Notes)
1.610
30.45 psi23.86 GPM
0.17 psi
Flow (q) from Route 6
72.31 GPM Tr
11 FPS
12' - 0"
23' - 2 1/4" 64' - 6 3/4"
-0.37 psi
20.20 psi
22' - 4" 52' - 6 3/4"
1.500 (See
Notes)
1.610
32.39 psi26.94 GPM
0.31 psi
Flow (q) from Route 7
99.24 GPM E(4' - 0"), PO(8' - 0")
16 FPS
16' - 5 3/4"
23' - 2 1/4" 55' - 11 3/4" 1.59 psi
23' - 2 1/4" 39' - 6"
2.500 (See
Notes)
2.635
52.21 psi
0.03 psi99.24 GPM T(16' - 5 3/4")
6 FPS
8' - 2 7/8"
23' - 2 1/4" 60' - 0 7/8" 5.07 psi
23' - 2 1/4" 51' - 10"
2.500 (See
Notes)
2.635
53.80 psi79.61 GPM
0.08 psi
Flow (q) from Route 3
178.85 GPM E(8' - 2 7/8"), red
11 FPS
20' - 1 7/8"
23' - 2 1/4" 20' - 1 7/8" 0.60 psi
23' - 2 1/4" 0"
3.000 (See
Notes)
3.260
58.87 psi
0.03 psi178.85 GPM T(20' - 1 7/8")
7 FPS
9' - 4 7/8"
23' - 2 1/4" 19' - 8 7/8" 0.59 psi
23' - 2 1/4" 10' - 4"
3.000 (See
Notes)
3.260
59.48 psi
0.03 psi178.85 GPM E(9' - 4 7/8")
7 FPS
9' - 4 7/8"
9' - 11" 22' - 8 1/8"
5.75 psi
0.68 psi
23' - 2 1/4" 13' - 3 1/4"
3.000 (See
Notes)
3.260
60.07 psi
0.03 psi178.85 GPM E(9' - 4 7/8")
7 FPS
18' - 9 3/4"
9' - 11" 156' - 4 3/4" 4.68 psi
9' - 11" 137' - 7"
3.000 (See
Notes)
3.260
66.50 psi
0.03 psi178.85 GPM 2E(9' - 4 7/8")
7 FPS
9' - 11" 0" 0.00 psi
9' - 11" 0"
3.000 (See
Notes)
3.260
71.19 psi
0.03 psi178.85 GPM red
7 FPS
10/31/2023 Page 1AutoSPRINK RVT v7.1.23.0 2:47:46PMSecond Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: Second Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
26' - 4"
9' - 11" 41' - 4 5/8" 0.34 psi
9' - 11" 15' - 0 5/8"
4.000 (See
Notes)
4.260
71.19 psi
0.01 psi178.85 GPM 2E(13' - 2")
4 FPS
13' - 2"
8' - 0" 15' - 1"
0.83 psi
0.12 psi
9' - 11" 1' - 11"
4.000 (See
Notes)
4.260
71.52 psi
0.01 psi178.85 GPM E(13' - 2")
4 FPS
13' - 2"
8' - 0" 13' - 11 3/4" 0.11 psi
8' - 0" 9 3/4"
4.000 (See
Notes)
4.260
72.48 psi
0.01 psi178.85 GPM E(13' - 2")
4 FPS
28' - 11 5/8"
4' - 3" 32' - 8 5/8"
1.63 psi
0.27 psi
8' - 0" 3' - 9"
4.000 (See
Notes)
4.260
72.59 psi
0.01 psi178.85 GPM BV(15' - 9 5/8"), E(13' - 2")
4 FPS
55' - 3 5/8"
3' - 2 1/8" 57' - 8 1/4"
0.47 psi
0.47 psi
4' - 3" 2' - 4 5/8"
4.000 (See
Notes)
4.260
74.48 psi
0.01 psi178.85 GPM T(26' - 4"), CV(28' - 11 5/8")
4 FPS
13' - 2"
2' - 1" 14' - 3 1/8"
0.48 psi
0.12 psi
3' - 2 1/8" 1' - 1 1/8"
4.000 (See
Notes)
4.260
75.42 psi
0.01 psi178.85 GPM E(13' - 2")
4 FPS
13' - 2"
2' - 1" 15' - 1 3/8" 0.12 psi
2' - 1" 1' - 11 3/8"
4.000 (See
Notes)
4.260
76.01 psi
0.01 psi178.85 GPM E(13' - 2")
4 FPS
1' - 0 3/8" 1' - 0 5/8"
0.46 psi
0.01 psi
2' - 1" 1' - 0 5/8"
4.000 (See
Notes)
4.260
76.13 psi
0.01 psi178.85 GPM red
4 FPS
14' - 0"
-3' - 3 5/8" 18' - 4"
1.88 psi
0.04 psi
1' - 0 3/8" 4' - 4"
6.000 (See
Notes)
5.500
76.60 psi
0.00 psi178.85 GPM E(14' - 0")
2 FPS
29' - 11 3/8"
-3' - 3 5/8" 136' - 6 1/2" 0.45 psi
-3' - 3 5/8" 106' - 7 1/8"
6.000 (See
Notes)
5.500
78.52 psi
0.00 psi178.85 GPM 4EE(4' - 11 7/8"), E(9' - 11 3/4")
2 FPS
25' - 8"
2' - 5 1/2" 37' - 1 3/8"
-2.50 psi
5.03 psi
-3' - 3 5/8" 11' - 5 3/8"
8.000 (See
Notes)
7.570
78.96 psi
0.00 psi178.85 GPM 2E(12' - 10"), BFP(-5.00 psi)
1 FPS
10/31/2023 Page 2AutoSPRINK RVT v7.1.23.0 2:47:46PMSecond Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: Second Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
12' - 10"
-3' - 3 5/8" 18' - 7 1/8"
2.50 psi
0.01 psi
2' - 5 1/2" 5' - 9 1/8"
8.000 (See
Notes)
7.570
81.49 psi
0.00 psi178.85 GPM E(12' - 10")
1 FPS
25' - 8"
-3' - 3 5/8" 43' - 9 3/8" 0.03 psi
-3' - 3 5/8" 18' - 1 3/8"
8.000 (See
Notes)
7.570
84.00 psi
0.00 psi178.85 GPM E(12' - 10"), 2EE(6' - 5"), S
1 FPS
100.00 GPM Hose Allowance At Source
278.85 GPM
Route 1
84.03 psi
Total(Pt)
7' - 0"
23' - 2" 10' - 4 1/8"
-0.99 psi
1.97 psi
20' - 10 5/8" 3' - 4 1/8"
1.000
• • • • • Route 2 • • • • •
(See
Notes)
1.049
25.20 psi24.60 GPM
0.19 psi
Sprinkler,
24.60 GPM
4.9
E(2' - 0"), T(5' - 0")
9 FPS
26.18 psi Route 2Total(Pt)
7' - 0"
22' - 4" 16' - 9 1/2"
-0.63 psi
3.46 psi
20' - 10 5/8" 9' - 9 1/2"
1.000
• • • • • Route 3 • • • • •
(See
Notes)
1.049
27.35 psi25.62 GPM
0.21 psi
Sprinkler,
25.62 GPM
4.9
E(2' - 0"), T(5' - 0")
10 FPS
22' - 4" 2' - 11 1/8" 0.09 psi
22' - 4" 2' - 11 1/8"
1.500 (See
Notes)
1.610
30.17 psi2.15 GPM
0.03 psi
Flow (q) from Route 8
27.77 GPM Tr
4 FPS
22' - 4" 3' - 4 3/4" 0.34 psi
22' - 4" 3' - 4 3/4"
1.500
1.610
30.26 psi25.96 GPM
0.10 psi
Flow (q) from Route 5
53.73 GPM
8 FPS
24' - 7 3/8"
22' - 4" 64' - 1 3/8" 3.08 psi
22' - 4" 39' - 6"
2.000 (See
Notes)
2.175
30.60 psi25.88 GPM
0.05 psi
T(12' - 3 5/8"), Flow (q) from
Route 4
79.61 GPM T(12' - 3 5/8")
7 FPS
8' - 0"
23' - 2 1/4" 98' - 4 3/4"
-0.37 psi
20.47 psi
22' - 4" 90' - 4 3/4"
1.500 (See
Notes)
1.610
33.69 psi
0.21 psi79.61 GPM 2E(4' - 0"), red
13 FPS
23' - 2 1/4" 8 1/4" 0.01 psi
23' - 2 1/4" 8 1/4"
2.500 (See
Notes)
2.635
53.79 psi
0.02 psi79.61 GPM Tr
5 FPS
53.80 psi Route 3Total(Pt)
10/31/2023 Page 3AutoSPRINK RVT v7.1.23.0 2:47:46PMSecond Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: Second Floor Remote Area
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction
Loss Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
9' - 0"
22' - 4" 15' - 2"
-0.63 psi
3.18 psi
20' - 10 5/8" 6' - 2"
1.000
• • • • • Route 4 • • • • •
(See
Notes)
1.049
27.89 psi25.88 GPM
0.21 psi
Sprinkler,
25.88 GPM
4.9
2E(2' - 0"), T(5' - 0")
10 FPS
22' - 4" 6' - 0" 0.16 psi
22' - 4" 6' - 0"
1.500 (See
Notes)
1.610
30.45 psi
0.03 psi25.88 GPM Tr
4 FPS
30.60 psi Route 4Total(Pt)
9' - 0"
22' - 4" 13' - 4"
-0.63 psi
2.81 psi
20' - 10 5/8" 4' - 4"
1.000
• • • • • Route 5 • • • • •
(See
Notes)
1.049
28.08 psi25.96 GPM
0.21 psi
Sprinkler,
25.96 GPM
4.9
2E(2' - 0"), T(5' - 0")
10 FPS
30.26 psi Route 5Total(Pt)
7' - 0"
22' - 4" 12' - 5 3/8"
-0.63 psi
2.63 psi
20' - 10 5/8" 5' - 5 3/8"
1.000
• • • • • Route 6 • • • • •
(See
Notes)
1.049
28.17 psi26.00 GPM
0.21 psi
Sprinkler,
26.00 GPM
4.9
E(2' - 0"), T(5' - 0")
10 FPS
22' - 4" 12' - 3" 0.27 psi
22' - 4" 12' - 3"
1.500 (See
Notes)
1.610
30.17 psi
0.02 psi23.86 GPM Tr
4 FPS
30.45 psi Route 6Total(Pt)
7' - 0"
22' - 4" 12' - 4 5/8"
-0.63 psi
2.80 psi
20' - 10 5/8" 5' - 4 5/8"
1.000
• • • • • Route 7 • • • • •
(See
Notes)
1.049
30.22 psi26.94 GPM
0.23 psi
Sprinkler,
26.94 GPM
4.9
E(2' - 0"), T(5' - 0")
10 FPS
32.39 psi Route 7Total(Pt)
22' - 4" 8' - 9 5/8" 0.00 psi
22' - 4" 8' - 9 5/8"
1.500
• • • • • Route 8 • • • • •
(See
Notes)
1.610
30.17 psi23.86 GPM
0.00 psi
Flow (q) from Route 6
2.15 GPM Tr
0 FPS
30.17 psi Route 8Total(Pt)
10/31/2023 Page 4AutoSPRINK RVT v7.1.23.0 2:47:46PMSecond Floor Remote Area@ M.E.P.CAD, Inc.
Remote Area Name: Second Floor Remote Area
1.51
Fittings Legend
BFP Backflow Preventer BV Butterfly Valve CV Check Valve
E 90° Elbow EE 45° Elbow PO Pipe Outlet red Reducer/Adapter S Supply Spr Sprinkler
T Tee Flow Turn 90° Tr Tee run
4.87
1.33
1.16
0.713
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
10/31/2023 Page 5AutoSPRINK RVT v7.1.23.0 2:47:46PMSecond Floor Remote Area@ M.E.P.CAD, Inc.
| FP-001 - OVERALL SITE PLAN |
| FP-002 - BULDING 22 - DOMICILIARY |
| FP-003 - BUILDING 22 - DOMICILIARY |
| FP-004 - BUILDING 22 - DOMICILIARY |
| FP-005 - BUILDING 22 - DOMICILIARY |
| FP-006 - BUILDING 22 - DOMICILIARY |
| First Floor Remote Area Hydraulic Data |
| Second Floor Remote Area Hydraulic Data |
File details come from the government source that posted it. Updated .