List AP and remarks clarification.pdf

PDF 110 KB Posted

Attached to
Y1DA--FY25: NRM (PROJ: 673-25-704) EHRM Installation of Next-Gen Wi-fi – Tampa, FL
Solicitation number
36C24825R0009
Issued by

About this file

This is an AP (Access Point) installation status document detailing why various wireless access points could not be installed across multiple buildings and floors. The document lists justifications for non-installed APs across Building 1 (basement through fifth floor) and Buildings 30, 32, 38, T49, and T78.

The main reasons for non-installation include: areas with known asbestos above ceilings, requiring conduit installation, unavailable ECUs (Environmental Control Units), lack of safety director approval for specific areas, and one case of a patient room that could not be accessed. The majority of issues were related to asbestos presence, particularly on the ground and first floors of Building 1. In these cases, the APs were left for site personnel to install later. For locations requiring conduit, cables were typically pulled, terminated, tested, and left coiled above ceilings for future installation. The document appears to be part of a larger federal contract related to EHRM (Electronic Health Record Modernization) NextGen Wi-Fi upgrades at a VA facility.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Building Floor AP Name Justifications/ Remarks

1 Basement AP36 The APs were not installed due to requiring conduit, left for site to install.

1 Basement AP37 The APs were not installed due to requiring conduit, left for site to install.

1 Basement AP38 The APs were not installed due to requiring conduit, left for site to install.

1 Ground AP63 The AP was not swapped due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP76 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP85 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP86 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP87 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP88 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP89 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP90 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP91 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP92 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP89 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP98 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP101 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP102 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP103 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP104 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP105 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP107 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP108 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP109 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP110 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP111 The APs were not installed due to being located in an area with known asbestos above the ceiling, left for site to install.

1 Ground AP80 The APs were not installed due to ECU not being available, left for site to install.

1 Ground AP81 The APs were not installed due to ECU not being available, left for site to install.

1 Ground AP82 The APs were not installed due to ECU not being available, left for site to install.

1 Ground AP83 The APs were not installed due to ECU not being available, left for site to install.

1 Ground AP84 The APs were not installed due to ECU not being available, left for site to install.

1 Ground AP93 The APs were not installed due to requiring conduit, left for the site to install.

1 Ground AP94 The APs were not installed due to requiring conduit, left for the site to install.

1 Ground AP95 The APs were not installed due to requiring conduit, left for the site to install.

1 Ground AP96 The APs were not installed due to requiring conduit, left for the site to install.

1 Ground AP97 The APs were not installed due to requiring conduit, left for the site to install.

1 Ground AP106 The APs were not installed due to requiring conduit, left for the site to install.

1 Ground AP112

1 First AP37 The AP was not swapped due to being in an active construction /asbestos area, left for site to install.

1 First AP13 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP40 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP91 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP94 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP95 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP96 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP97 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP98 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP99 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP100 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP102 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP108 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP109 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP110 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP111 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP112 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP113 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP114 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP115 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP116 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP117 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP118 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP119 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP120 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP121 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP130 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP131 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP133 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP134 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP135 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP137 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP139 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP141 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP142 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 First AP136 The AP was not installed due to being located in an area with known asbestos above the ceiling and requiring conduit, left for site to install.

1 First AP101 The APs were not installed due to ECU not being available, left for site to install.

1 First AP105 The APs were not installed due to ECU not being available, left for site to install.

1 First AP106 The APs were not installed due to ECU not being available, left for site to install.

1 First AP107 The APs were not installed due to ECU not being available, left for site to install.

1 First AP128 The APs were not installed due to ECU not being available, left for site to install.

1 First AP129 The APs were not installed due to ECU not being available, left for site to install.

1 First AP138 The APs were not installed due to ECU not being available, left for site to install.

1 First AP140 The APs were not installed due to ECU not being available, left for site to install.

1 Second AP88 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP89 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP94 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP95 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP98 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP100 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP101 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP102 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP103 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP105 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Second AP62 The APs were not installed due to ECU not being available, left for site to install.

1 Second AP92 The APs were not installed due to ECU not being available, left for site to install.

1 Second AP107 The APs were not installed due to ECU not being available, left for site to install.

1 Second AP108 The APs were not installed due to ECU not being available, left for site to install.

1 Second AP110 The APs were not installed due to ECU not being available, left for site to install.

1 Second AP111 The APs were not installed due to ECU not being available, left for site to install.

1 Second AP114 The APs were not installed due to ECU not being available, left for site to install.

1 Second AP90 The APs were not installed due to requiring conduit, left for the site to install.

1 Second AP91 The APs were not installed due to requiring conduit, left for the site to install.

1 Second AP97 The APs were not installed due to requiring conduit, left for the site to install.

1 Second AP112 The APs were not installed due to requiring conduit, left for the site to install.

1 Second AP93 The APs were not installed due to not receiving approval from safety director to work in these specific areas, left for site to install.

1 Second AP96 The APs were not installed due to not receiving approval from safety director to work in these specific areas, left for site to install.

1 Second AP99 The APs were not installed due to not receiving approval from safety director to work in these specific areas, left for site to install.

1 third AP19 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 third AP20 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 third AP21 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 third AP29 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 third AP30 The APs were not installed due to being in areas with known unabated asbestos above ceiling, left for site to install.

1 Fifth AP27

The AP was not installed due to a patient in room unable to be moved; cable is coiled up in ceiling outside room 5A‐547, terminated, tested and to be pulled into room at a later date, left for site to install.

30 Ground AP38 The AP was not installed due to requiring conduit, left with site to install.

32 Basement AP12 The APs were not installed due to requiring conduit, left with site to install.

32 Basement AP13 The APs were not installed due to requiring conduit, left with site to install.

38 Ground AP102 The AP was not installed due to requiring conduit, left with site to install.

38 Second AP44 The APs were not installed due to requiring conduit, left with site to install.

38 Second AP45 The APs were not installed due to requiring conduit, left with site to install.

38 Second AP48 The APs were not installed due to requiring conduit, left with site to install.

38 Third AP40

The APs were not installed due to requiring conduit. Cables pulled, terminated, tested, and left coiled above the ceiling in corridor outside of room A310‐38 and in corridor outside of room A319‐38 for site to install.

38 Third AP42

The APs were not installed due to requiring conduit. Cables pulled, terminated, tested, and left coiled above the ceiling in corridor outside of room A310‐38 and in corridor outside of room A319‐38 for site to install.

38 Third AP43 The AP was not installed due to requiring conduit, left with site to install.

T49 First AP The AP was not installed due to requiring conduit, left with site to install.

T78 First AP03 The AP was not installed due to requiring conduit, left with site to install.