Questions Received During Site Visit.pdf

PDF 102 KB Posted

Attached to
J041--Cooling Towers Maintenance and Repairs Tiered Evaluations
Solicitation number
36C24824Q1291
Issued by

About this file

This document is a set of questions and answers related to a solicitation for Cooling Towers Maintenance and Repairs Services issued by the Department of Veterans Affairs, Network Contracting Office - 8. The key details are:

The solicitation is for a contract to perform repair and maintenance services on twelve (12) cooling towers. It will be awarded as a tiered evaluation, with Service-Disabled Veteran-Owned Small Businesses (SDVOSBs) evaluated first, followed by Small Businesses (SBs) if no acceptable SDVOSB offer is received. The period of performance is expected to be from November 1, 2024 to October 31, 2025, with four one-year option periods.

The questions addressed during a site visit cover topics such as responsibility for major repairs, cleaning of cooling tower fill media, potential contract price increases, maintenance of structural supports, water quality reporting, and controls responsibility. The answers provided clarify the contract requirements in these areas.

View the file

Other files

File Type Posted
36C24824Q1291_4.docx DOCX document
Cooling Towers Maintenance and Repair PWS - Final.docx DOCX document
Combined Synopsis Amendment 2 SF-30.pdf PDF
36C24824Q1291_3.docx DOCX document
Evaluation Factors - Revised.pdf PDF
Questions in Response to RFQ - Answered.pdf PDF
Combined Synopsis Amendment SF-30.pdf PDF
Contract Documents Exhibits or Attachments.pdf PDF
Schedule of Prices.pdf PDF
Performance Work Statement.pdf PDF
36C24824Q1291_2.docx DOCX document
Clauses and Provisions.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

The questions made in response to the aforementioned solicitation during the September 12 site visit, and their answers as follows:

1- Question: Shall the Contractor to whom this contract is awarded be responsible for mayor repairs?

Answer: Yes. The resultant contract is for preventive maintenance services and repairs. This is to include minor and mayor repairs.

2- Question: Can the fill media of the cooling towers be cleaned without removing it from its respective cooling tower?

Answer: No. The only exception for this being the fill media for the Marley cooling towers, which can be cleaned without removing them. The reason for this exception is because the fill media from the Marley cooling towers has a high probability of breakage while being removed. The fill media for all other cooling towers shall be removed before cleaning. This exception has been added to section 4.6 of the revised Performance Work Statement (PWS), which can be seen attached to this amendment.

3- Question: Can there be increases in the contract once awarded, due to changes in market conditions?

Answer: No. The only authorized increases will be those that result from changes in the applicable Wage Rates, since this contract will be subject to the Service Contract Labor Standards (Wage Determination No. 2015-5707). Therefore, in the event of any changes or increases in wage rates the Contractor shall submit a quote that reflects the impact this wage rate increase had on the pre-established contract prices. After the Contracting Officer determines that the quote is fair and reasonable to the Government, and funding is confirmed, the wage rate change shall be implanted into the contract via supplemental agreement (see FAR 52.222-43).

4 - Question: Shall the Contractor also maintain the structural support from each cooling tower?

Answer: Yes. This structural support is considered to be part of the cooling tower system. Section 3.6 has been added to the revised PWS, to state this accordingly.

5 - Question: Will the Contractor receive a water quality report, respective to the quality of water entering each cooling tower?

Answer: Yes, those reports can be provided upon request, once the contract is awarded. Additionally, section 15 of the PWS has been added, to provide water quality information.

6- Question: Is the Contractor responsible of maintaining the Variable Frequency Drives (VFD) associated with these cooling towers?

Answer: No. These VFDs are maintained under another contract. Sections 3.5 and 4.1 have been revised to remove the mention of these VFDs.

7- Question: Will the Contractor to whom this contract is awarded be responsible for the controls?

Answer: The Contractor shall only be responsible for the controls that are part of the cooling towers components. Not the facility controls.

8- Question: Can the tonnage capacity for each cooling tower be provided?

Answer: Yes. The tonnage capacity has been added to section 14 of the PWS.