2010 Lakemont Campus Asbestos Report .pdf

PDF 3 MB Posted

Attached to
F107--FY24 Re-Baseline Asbestos Survey for Lake Baldwin
Solicitation number
36C24824Q1221
Issued by

About this file

This document is an Asbestos Survey Report for the third floor of the Orlando Veterans Administration Lakemont Campus facility. Air Analytics conducted an inspection and assessment of asbestos-containing building materials (ACBM) at the facility on May 13, 2010. Twenty samples were collected and analyzed, and none of the materials were found to contain asbestos. Therefore, no asbestos abatement action is required. The report includes details on the methodology used, sample results, and photographic documentation. It is intended to provide information to the building owner, construction managers, and potential asbestos abatement contractors.

The related federal contract opportunity is for a Fiscal Year 2024 Re-Baseline Asbestos Survey for the Lake Baldwin facility. The solicitation is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8. No additional details about the specific requirements, response dates, pricing terms, or set asides are provided in the information given.

View the file

Other files

File Type Posted
S02 36C24824Q1221 0004.docx DOCX document
36C24824Q1221 0002.docx DOCX document
36C24824Q1221 0003.docx DOCX document
36C24824Q1221 0002.docx DOCX document
36C24824Q1221 0002.docx DOCX document
52.212-1 ADDENDUM to FAR 52.docx DOCX document
Revised STATEMENT OF WORK Asbestos .docx DOCX document
S06 GOVERNMENT RESPONSE TO CONTRACTORS QUESTIONS.docx DOCX document
36C24824Q1221 0002.docx DOCX document
S02 36C24824Q1221 0001.docx DOCX document
36C24824Q1221.docx DOCX document
ATTACHMENT B 2014 LAKE BALDWIN BLDG 502 ASBESTOS SURVEY.pdf PDF
ATTACHMENT D VHA DIRECTIVE 7714 ASBESTOS MANAGEMENT PROGRAM.pdf PDF
ATTACHMENT C RE BASELINE ASBESTOS ASSESSMENT SURVEY BUILDING PLANS.docx DOCX document
36C24824Q1221.docx DOCX document
ATTACHMENT A 2014 LAKE BALDWIN BLDG 500 ASBESTOS SURVEY.pdf PDF
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2582 Connection Point, Suite 1000, Oviedo, Florida, 32765

Tel. (407) 359-1974 www.airanalytics.com Fax (407) 366-9895

AIR ANALYTICS

Orlando Veterans Administration - Lakemont Campus

3rd Floor Asbestos Inspection & Assessment Report

Air Analytics Project No. 10-10124.

To: Orlando VA Medical Center May 14, 2010

5201 Raymond Street

Building 3130

Orlando, Florida 32803

Attn: Maria Escobales, CSHO

Industrial Hygienist / GEMS Coordinator

To: Orlando VA Medical Center May 14, 2010

5201 Raymond Street

Building 3130

Orlando, Florida 32803

Attn: Maria Escobales, CSHO

Industrial Hygienist / GEMS Coordinator

Re: Orlando Veterans Administration - Lakemont Campus 3rd Floor Asbestos Inspection &

Assessment Report. Air Analytics Project No. 10-10124.

Dear Mrs. Escobales:

Air Analytics (AA) is pleased to submit this asbestos survey report conducted at the Orlando Veterans

Administration Lakemont Campus, located at 2500 S. Lakemont Ave., Winter Park, Florida 32814.

Edward A. Nunez, a Florida Licensed Asbestos Consultant (LAC AX0000048) and Asbestos Inspector

(Certification number AA101409IR04), completed the field investigation conducted on May 13, 2010, encompassing the physical assessment, sampling and analysis for suspect Asbestos Containing Building

Materials (ACBM) at the subject facility.

Twenty samples were collected from nine distinct homogenous sampling areas. These samples yielded twenty-six distinct materials, when each layer was identified by the laboratory, in accordance with EPA requirements. Laboratory results determined that none of the materials were found to be asbestos-containing. Therefore, no action is required.

All of the information collected as a result of this survey will be treated with the utmost confidentiality and will not be released to any unauthorized person(s) for any reason without your prior written consent.

Air Analytics appreciates the opportunity to be of service to you on this project and looks forward to our continued relationship. If you should have any questions concerning the content of this report, please do not hesitate to contact us.

Very truly yours, Edward A. Nuñez, CIH, LAC

3rd Floor Asbestos Inspection & Assessment Report.

TABLE OF CONTENTS

1.0 INTRODUCTION AND BACKGROUND................................. Page 1

2.0 METHODOLOGY ............................................................. Page 1

3.0 RESULTS ................................................................................ Page 2

APPENDICES

APPENDIX A PLM LABORATORY RESULTS

ASBESTOS BUILDING SURVEY FORM

APPENDIX B PHOTOGRAPHIC DOCUMENTATION

Orlando Veterans Administration - Lakemont Campus Page 1 of 4

1.0 INTRODUCTION & BACKGROUND

An asbestos-containing building materials inspection & physical assessment survey was conducted at the Orlando Veterans Administration Lakemont Campus (third floor only), located at 2500 S. Lakemont Ave., Winter Park, Florida 32814. The evaluation was performed on May

13, 2010. Air Analytics’ Edward A. Nunez, a Florida Licensed Asbestos Consultant (LAC

AX0000048) and Asbestos Inspector (Certification number AA101409IR04), conducted the subject evaluation.

Briefly, the services included:

• Inspection and sample collection for suspected asbestos-containing building materials, by an

EPA-accredited asbestos surveyor according to federal guidelines, to provide information on material condition, approximate locations, and estimated quantities of ACBM, according to a generally representative sampling protocol.

• Analysis of all bulk samples utilizing Polarized Light Microscopy and Dispersion Staining

Techniques performed in accordance with EPA Bulk Analysis Method EPA 600/R-93/116, incorporating visual estimates of identified material percentages.

• Compilation of a report with collected samples, assessment forms, and photographic documentation.

• Data Evaluation And Interpretation

• Final Report

2.0 METHODOLOGY

The asbestos inspection was limited to the third floor of the Orlando Veterans Administration -

Lakemont Campus facility. The asbestos facility inspection was conducted in general accordance with AHERA guidelines, by identifying Homogeneous Sampling Areas (HSA), and collecting a minimum number of samples required by the standard. A homogeneous sampling area can be described as any suspect asbestos material that is similar in appearance and texture, having the same installation date, use, and function. Sample collection depends on the category that the

HSA falls into and the professional judgment of the field inspector/surveyor.

If the analytical results indicated that all the samples collected per HSA did not contain asbestos, then the HSA (material) would be considered a non-ACM. However, if the analytical results indicate one or more of the samples collected per HSA contains asbestos in quantities of greater than 1 percent asbestos by weight (as defined by EPA), all of the HSA (material) shall be treated as an ACM Material.

Friable materials and Category I and II non-friable materials, which have become friable are classified by EPA NESHAPs (40 CFR 61 M) as Regulated Asbestos Containing Materials

Orlando Veterans Administration - Lakemont Campus Page 2 of 4

(RACM), and must be removed by a State of Florida-licensed asbestos abatement contractor prior to building demolition. Category I non-friable ACMs shall not be subjected to abrasion, grinding, sanding or any other processes during demolition, which will render these non-friable materials friable. A ten-day notification must be submitted to the FDEP prior to the initiation of the abatement of more than 160 square feet or 260 linear feet of an RACM. Air monitoring to ensure that other areas of the building are not being contaminated with asbestos fibers should be performed by a licensed asbestos business organization during the abatement project. Final clearance air sampling should be performed to document that the consensus clean air standard of

0.01 fibers per cubic centimeter of air has been met.

3.0 RESULTS

A thorough walkthrough of the facility’s third floor was conducted, to identify suspect ACBM materials prior to sampling. Nine homogeneous sampling areas were identified, and twenty samples were collected. These samples yielded twenty-six distinct materials, when each layer was identified by the laboratory, in accordance with EPA requirements.

3rd Floor Asbestos Inspection

SUSPECT MATERIAL

SAMPLE

I.D.

ASBESTOS

LOCATION

FRIABLE

Y/N

Drywall DFAS-1 NAD Room 320 N

Blue Baseboard DFAS-2B NAD Room 320 N

Blue Baseboard Mastic DFAS-2M NAD Room 320 N

2’ x 4’ White Ceiling Tile DFAS-3 NAD Room 326 Y

Drywall Joint Compound DFAS-4J NAD Room 323 Y

Drywall DFAS-4D NAD Room 323 N

Blue Baseboard DFAS-5B NAD Room 323 N

Blue Baseboard Mastic DFAS-5M NAD Room 323 N

White Duct Mastic DFAS-6 NAD Room 323 N

White Duct Mastic DFAS-7 NAD Room 314 N

Beige Duct Mastic DFAS-8 NAD Room 314 N

Orlando Veterans Administration - Lakemont Campus Page 3 of 4

3rd Floor Asbestos Inspection

SUSPECT MATERIAL

SAMPLE

I.D.

ASBESTOS

LOCATION

FRIABLE

Y/N

2’ x 2’ Tan Raised Floor Tile DFAS-9 NAD Room 314 N

12” x 12” Beige Floor Tile DFAS-10F NAD Room 312 N

12” x 12” Beige Floor Tile Mastic DFAS-10M NAD Room 312 N

Beige Duct Mastic DFAS-11 NAD Room 319 N

2’ x 4’ White Ceiling Tile DFAS-12 NAD Room 319 Y

White Drywall Joint Compound DFAS-13J NAD Room 319 Y

Drywall DFAS-13D NAD Room 319 N

Blue Baseboard DFAS-14B NAD Room 319 N

Blue Baseboard Mastic DFAS-14M NAD Room 319 N

White Duct Mastic DFAS-15 NAD Room 317 N

12” x 12” Beige Floor Tile DFAS-16 NAD Room 306 N

Drywall DFAS-17 NAD Room 325 N

2’ x 4’ White Ceiling Tile DFAS-18 NAD Room 302B Y

White Drywall Joint Compound DFAS-19 NAD Room 313 Y

Gray Duct Mastic DFAS-20 NAD Room 341 N

NAD – No Asbestos Detected

Laboratory results determined that none of the materials were found to be asbestos-containing.

Therefore, no action is required.

All ACM physical assessments were documented in the “Asbestos Building Survey Form” found in Appendix A of this report. Photographic documentation is included in Appendix B.

This report is designed to aid the building owner, construction manager, general contractors, and potential asbestos abatement contractors in identifying and locating ACM. Under NO circumstances is this report to be utilized as a bidding document or as a project specification document, as it does not have any of the components required to serve as an Asbestos Project

Design document or an Abatement Work plan.

Orlando Veterans Administration - Lakemont Campus Page 4 of 4

A copy of this report should be integrated into the facility’s Asbestos Operations and

Maintenance Plan.

We appreciate the opportunity to be of service to you on this project. If you should have any questions concerning this report or our investigation, please do not hesitate to contact me, at

(407) 359-1974 or (407) 760-3058

Very truly yours, Edward A. Nunez, CIH, LAC

Florida Licensed Asbestos Consultant

AX-0000048

These results are to be used by the client, Veterans Administration, its representatives, and Air Analytics. All other use without prior consent by Veterans

Administration is strictly prohibited. These results may not be copied, except in full, without the written consent of Veterans Administration and Air Analytics.

These results present the conditions of the subject study, at the time of the study, and are not reflective of conditions present prior to or after the study. No representations are made, except for those specifically addressed by this report.

Air Analytics follows and abides by the Code of Ethics of the American Industrial

Hygiene Association

• Practice their profession following recognized scientific principles with the realization that the lives, health and well-being of people may depend upon their professional judgment and that they are obligated to protect the health and well-being of people.

• Counsel affected parties factually regarding potential health risks and precautions necessary to avoid adverse health effects.

• Keep confidential personal and business information obtained during the exercise of industrial hygiene activities, except when required by law or overriding health and safety considerations.

• Avoid circumstances where a compromise of professional judgment or conflict of interest may arise.

• Perform services only in the areas of their competence.

• Act responsibly to uphold the integrity of the profession.

APPENDIX A

PLM LABORATORY RESULTS

ASBESTOS BUILDING SURVEY FORM

APPENDIX B

PHOTOGRAPHIC DOCUMENTATION

Photo #2; Representative Raised Floor & Suspended Ceiling View in Typical Office Suite

Photo #1; Orlando Veterans Administration Lakemont Campus – Facility Front View

Photo #4; Representative Blue Vinyl Baseboard & Mastic Sampling Area View

Photo #3; Representative 2’ x 4’ White Ceiling Tile Sampling Area View

Photo #6; Representative Drywall Sampling Area View

Photo #5; Representative Drywall Sampling Area View

Photo #8; Representative Beige Ductwork Mastic Sampling Area View

Photo #7; Representative White Ductwork Mastic Sampling Area View

Photo #10; Representative Drywall Joint Compound Sampling Area View

Photo #9; Representative 2’ x 2’ Raised Floor Tile Board Sampling Area View

Photo #12; Representative Drywall Sampling Area View

Photo #11; Representative 12” x 12” Tan Vinyl Floor Tile w/ Brown Specs Sampling Area View

Photo #14; Representative Men/Women Restroom Hard (Drywall) Ceiling View

Photo #13; Representative Drywall Joint Compound Sampling Area View

Lakemont Campus Asbestos Survey Report 3RD FLOOR
Lakemont first floor Asbestos Survey 2010
Page 1
Page 2
Page 3
Page 4
Page 5
Page 6