Fire Alarm and Life Safety System
Inspection Certificate
For
Tampa VAMC Bldg 41
13000 Bruce B Downs Blvd
Tampa,FL 33637
Kinetix has performed this inspection and testing service in compliance with The Joint
Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Memorandum 23 Concurrence on EC &
LS Standards effective September 2017. This Inspection was performed in accordance with applicable
NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Inspection Completion Date
Jun 14, 2018
Building: Tampa VAMC Bldg 41 Company: Kinetix
Contact: Darren Matteson Contact: Michael Gill
Title: Biomedical Engineer Title: Field Supervisor/Technician
Kinetix 1 07/13/2018
Executive Summary Generated by: BuildingReports.com
Building Information
Building: Tampa VAMC Bldg 41 Contact: Darren Matteson
Address: 13000 Bruce B Downs Blvd Phone: 813-972-2000
Address: Fax:
City/State/Zip: Tampa, FL 33637 Mobile:
Country: United States of America Email:
Inspection Performed By
Company: Kinetix Inspector: Michael Gill
Address: 12 Creek Parkway Phone: 386-747-2294
Address: Fax: 3145020737
City/State/Zip: Boothwyn, PA 19061 Mobile:
Country: United States of America Email: michaelgill15@yahoo.com
Monitoring Company: Phone: Account #:
Central Station Signal Verification Type: Digital Communicator Mfg: Simplex Model #:
Test Time/Date: 6/14/18 8:27:53 AM Restore Time
Kinetix 2 07/13/2018
Inspection Completion Date: Jun 14, 2018
Building: Tampa VAMC Bldg 41
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Tamper Switch 0 0 0 8 0 8
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Heat Detector 2 2 0 2 0 2
Pull Station 5 5 0 5 0 5
Smoke Detector 40 40 0 40 0 40
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Speaker/Strobe 32 32 0 32 0 32
Strobe 5 5 0 5 0 5
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018)
Communicator 1 1 0 1 0 1
LS 02.01.34 EP 04
All other Life Safety Code fire alarm requirements related to NFPA 101-2018
18/19.3.4
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018)
Battery 0 0 0 0 2 2
LS 02.01.50 EP 04
Elevators are fully equipped and protected
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Elevator 1 1 0 1 0 1
Total Device Count: 96
Kinetix 3 07/13/2018
Certification
Company: Kinetix Building: Tampa VAMC Bldg 41
Inspector: Michael Gill Contact: Darren Matteson
Signed: Signed:
Kinetix 4 07/13/2018
Notes & Recommendations
Building: Tampa VAMC Bldg 41 Control Panel: n/a
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
40665800 1 Smoke Detector 1 ELEV. LOBBY Passed
Recalls To Alternate Floor
40665801 2 Smoke Detector 1 ELEV. MECH. RM 41-126 Passed
Recalls To Primary Floor
40665841 3 Smoke Detector 2 ELEV. LOBBY Passed
Recalls To Primary Floor
40665842 4 Smoke Detector 2 ELEV. TOP SHAFT Passed
Recalls To Primary Floor
Kinetix 5 07/13/2018
Inspection & Testing
The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72 Table 14.4.3.2 (17)(j)(1))
Devices Tested Q2/18 Pass Q2/18 Fail Q2/18 Tested YTD (2018) Total Quantity
Tamper Switch 0 0 0 8 8
Device Type Location ScanID Address Q2/17 Q1/18 Q2/18
Tamper Switch 1 East Exit 40665836 0-12:M1-03 01/12-P
Tamper Switch 1 RISER RM 41-101 OUTSIDE 40665837 0-12:M1-04 01/12-P
Tamper Switch 1 FL by stairwell 2 41858078 1-6:M1-31-0 01/12-P
Tamper Switch 1 FL East Exit 41858079 1-12:M1-3-0 01/12-P
Tamper Switch 2FL Stairwell 2 41858076 1-17:M1-170-
01/12-P
Tamper Switch BLDG Basement 41858075 1-6:M1-14-0 01/12-P
Tamper Switch BLDG Basement 41858074 1-6:M1-31-0 01/12-P
Tamper Switch BLG32 Tunnel 41858077 1-6:M1-31-0 01/12-P
Device Total: 8
Kinetix 6 07/13/2018
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-
Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72 Table 14.4.3.2 (17)(d))
Heat Detector 2 2 0 2 2
Heat Detector 1 ELEV MECH RM 41-126 40665795 0-12:M1-09 06/22-P 06/12-P
Heat Detector 2 ELEV. TOP SHAFT 40665838 0-12:M1-14 06/22-P 06/12-P
Device Total: 2
Kinetix 7 07/13/2018
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72 Table 14.4.3.2 (17e))
Pull Station 5 5 0 5 5
Pull Station 1 NORTH EXIT 40665797 0-12:M1-05 06/27-P 06/14-P
Pull Station 1 WEST EXIT 40665798 0-12:M1-07 06/30-P 06/14-P
Pull Station 1 EAST EXIT 40665796 0-12:M1-02 06/27-P 06/14-P
Pull Station 2 BY EAST STAIRWELL 40665839 0-12:M1-11 06/27-P 06/14-P
Pull Station 2 BY WEST STAIRWELL 40665840 0-12:M1-15 06/30-P 06/14-P
Device Total: 5
Kinetix 8 07/13/2018
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72 Table 14.4.3.2 (17)(g)(1))
Smoke Detector 40 40 0 40 40
Smoke Detector 1 ELEV. MECH. RM 41-126 40665801 0-12:M1-08 06/22-P 06/12-P
Smoke Detector 1 ELEV. LOBBY 40665800 0-12:M1-06 06/22-P 06/12-P
Smoke Detector 1 BY ROOM 127 40665804 0-12:M1-26 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 117 40665805 0-12:M1-29 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 105 40665808 0-12:M1-32 06/30-P 06/14-P
Smoke Detector 1 BY ROOM 103 40665810 0-12:M1-35 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 140 40665813 0-12:M1-39 06/30-P 06/14-P
Smoke Detector 1 LOUNGE 40665812 0-12:M1-37 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 146 40665814 0-12:M1-40 06/30-P 06/14-P
Smoke Detector 1 BY ROOM 137 40665811 0-12:M1-36 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 150 40665815 0-12:M1-42 06/30-P 06/14-P
Smoke Detector 1 BY ROOM 152 40665816 0-12:M1-43 06/30-P 06/14-P
Smoke Detector 1 BY ROOM 158 40665817 0-12:M1-44 06/30-P 06/14-P
Smoke Detector 1 BY REST ROOM 40665818 0-12:M1-75 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 120 40665819 0-12:M1-76 06/30-P 06/14-P
Smoke Detector 1 LOBBY RECEPTION 40665809 0-12:M1-33 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 115 40665806 0-12:M1-30 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 134 40665803 0-12:M1-25 06/27-P 06/14-P
Smoke Detector 1 BY ROOM 107 40665807 0-12:M1-31 06/27-P 06/14-P
Smoke Detector 1 FILE RM 41-118 40665802 0-12:M1-17 06/30-P 06/14-P
Smoke Detector 1 ABOVE FACP 40665799 0-12:M1-01 06/28-P 06/14-P
Smoke Detector 2 ELEV. TOP SHAFT 40665842 0-12:M1-13 06/22-P 06/12-P
Smoke Detector 2 ELEV. LOBBY 40665841 0-12:M1-12 06/22-P 06/12-P
Smoke Detector 2 BY ROOM 226 40665843 0-12:M1-48 06/27-P 06/14-P
Smoke Detector 2 BY ROOM 220 40665845 0-12:M1-50 06/27-P 06/14-P
Smoke Detector 2 BY ROOM 217 40665846 0-12:M1-53 06/30-P 06/14-P
Smoke Detector 2 BY ROOM 214 40665847 0-12:M1-54 06/30-P 06/14-P
Smoke Detector 2 BY ROOM 223 40665844 0-12:M1-49 06/27-P 06/14-P
Smoke Detector 2 BY ROOM 209 40665848 0-12:M1-56 06/30-P 06/14-P
Smoke Detector 2 BY ROOM 205 40665849 0-12:M1-57 06/27-P 06/14-P
Smoke Detector 2 BY ROOM 203 40665850 0-12:M1-59 06/27-P 06/14-P
Smoke Detector 2 BY ROOM 228 40665851 0-12:M1-61 06/27-P 06/14-P
Smoke Detector 2 LOUNGE 40665852 0-12:M1-62 06/27-P 06/14-P
Smoke Detector 2 BY REST ROOM 40665853 0-12:M1-63 06/27-P 06/14-P
Smoke Detector 2 BY ROOM 234 40665854 0-12:M1-67 06/30-P 06/14-P
Smoke Detector 2 BY ROOM 237 40665855 0-12:M1-68 06/30-P 06/14-P
Smoke Detector 2 BY ROOM 239 40665856 0-12:M1-69 06/30-P 06/14-P
Smoke Detector 2 BY ROOM 243 40665857 0-12:M1-71 06/30-P 06/14-P
Smoke Detector 2 BY ROOM 245 40665858 0-12:M1-72 06/30-P 06/14-P
Smoke Detector 2 BY ROOM 230 40665859 0-12:M1-73 06/30-P 06/14-P
Device Total: 40
Kinetix 9 07/13/2018
Annual test of visual and audible fire alarms, including speakers and door releasing devices
For periodic testing, verify the operation of the notification appliances. (NFPA 72 Table 14.4.3.2 (22)(b))
Speaker/Strobe 32 32 0 32 32
Speaker/Strobe 1 BY RM 41-129 40665826 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-120 40665825 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-135 40665827 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-151 40665829 0 06/30-P 06/14-P
Speaker/Strobe 1 INSIDE RM 41-118 40665832 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-158 40665831 0 06/30-P 06/14-P
Speaker/Strobe 1 INSIDE RM 41-158 40665833 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-154 40665830 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-140 40665828 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-118 40665824 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-111 40665823 0 06/30-P 06/14-P
Speaker/Strobe 1 BY RM 41-105 40665822 0 06/30-P 06/14-P
Speaker/Strobe 1 BY ELEV. LOBBY 40665821 0 06/30-P 06/14-P
Speaker/Strobe 1 BREAK RM 40665820 0 06/30-P 06/14-P
Speaker/Strobe 2 BREAK AREA 40665860 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-204 40665861 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-207 40665862 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-214 40665863 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-219 40665864 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-223 40665865 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-226 40665866 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-229 40665867 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-231 40665868 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-233 40665869 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-237 40665870 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-239 40665871 0 06/30-P 06/14-P
Speaker/Strobe 2 BY RM 41-245 40665872 0 06/30-P 06/14-P
Speaker/Strobe 2 CORNER BY RM 41-231 40665874 0 06/30-P 06/14-P
Speaker/Strobe 2 INSIDE RM 41-233 40665875 0 06/30-P 06/14-P
Speaker/Strobe 2 BY STAIRWELL EAST BY 41-219 40665873 0 06/30-P 06/14-P
Speaker/Strobe 2 INSIDE RM 41-237 40665876 0 06/30-P 06/14-P
Speaker/Strobe 2 MEETING RM 41-222 40665877 0 06/30-P 06/14-P
Device Total: 32
Kinetix 10 07/13/2018
Annual test of visual and audible fire alarms, including speakers and door releasing devices
For periodic testing, verify that each appliance flashes. (NFPA 72 Table 14.4.3.2 (22c))
Strobe 5 5 0 5 5
Strobe 1 WOMENS BATHROOM 40665835 0 06/30-P 06/14-P
Strobe 1 MENS BATHROOM 40665834 0 06/30-P 06/14-P
Strobe 2 RM 41-231 40665879 0 06/30-P 06/14-P
Strobe 2 MENS BATHROOM 40665878 0 06/30-P 06/14-P
Strobe 2 WOMENS BATHROOM 40665880 0 06/30-P 06/14-P
Device Total: 5
Kinetix 11 07/13/2018
Annual test of fire alarm equipment for notifying off-site fire responders
Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72 Table 14.4.3.2 (4))
Communicator 1 1 0 1 1
Communicator 1st In Bldg 39 40662943 1 06/28-P 06/14-P
Device Total: 1
Kinetix 12 07/13/2018
All other Life Safety Code fire alarm requirements related to NFPA 101-2018 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72 Table 14.4.3.2 (9))
Battery 0 0 0 0 2
Battery 42020001 1-12V-33Ah 06/28-P
Battery 42020000 1-12V-33Ah 06/28-P
Kinetix 13 07/13/2018
Elevators are fully equipped and protected
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72 Table 14.4.3.2 (20))
Elevator 1 1 0 1 1
Elevator Ground Elevator 23 Recall 40665794 0-MISC 06/22-P 06/14-P
Kinetix 14 07/13/2018
Service Summary
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Communicator Tested 1
Elevator Tested 1
Heat Detector Tested 2
Pull Station Tested 5
Smoke Detector Tested/Cleaned 40
Speaker/Strobe Tested 32
Strobe Tested 5
Total 86
Untested Battery 2
Tamper Switch 8
Total 10
Kinetix 15 07/13/2018
Auxiliary Functions Testing
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed
Heat Detector
Shunt Trip 1 ELEV MECH RM 41-126 Passed 40665795
Shunt Trip 2 ELEV. TOP SHAFT Passed 40665838
Smoke Detector
Elevator Recall 1 ELEV. LOBBY Passed 40665800
Elevator Recall 1 ELEV. MECH. RM 41-126 Passed 40665801
Elevator Recall 2 ELEV. LOBBY Passed 40665841
Elevator Recall 2 ELEV. TOP SHAFT Passed 40665842
Elevator
Primary Recall Ground Elevator 23 Recall Passed 40665794
Kinetix 16 07/13/2018
Inventory & Warranty Report
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Item Category % of Inventory Quantity
Tamper Switch Supervisory 8.33% 8
Battery Control 2.08% 2
Smoke Detector Initiating 41.67% 40
Heat Detector Initiating 2.08% 2
Elevator Auxiliary 1.04% 1
Communicator Control 1.04% 1
Pull Station Initiating 5.21% 5
Speaker/Strobe Indicating 33.33% 32
Strobe Indicating 5.21% 5
Type Qty Model # Description Install Date
In Service - 1 Year to 2 Years
Simplex
Tamper Switch 2 08/19/2016
In Service - 2 Years to 3 Years
Simplex
Pull Station 5 06/16/2016
Smoke Detector 36 Photoelectric 06/16/2016
Speaker/Strobe 31 06/16/2016
Strobe 5 06/16/2016
Elevator 1 Primary Recall 06/08/2016
Heat Detector 2 06/08/2016
Smoke Detector 3 Photoelectric 06/08/2016
Speaker/Strobe 1 06/08/2016
Smoke Detector 1 Photoelectric 06/07/2016
Kinetix 17 07/13/2018
Building: Tampa VAMC Bldg 41 Control Panel: 1
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date
In Service - 1 Year to 2 Years Battery 2 Sealed Lead Acid 06/28/2017
Tamper Switch 6 02/19/2017
Simplex
Communicator 1 Digital Communicator 08/19/2016
Kinetix 18 07/13/2018
Zone Address Report
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
12:M1-01 Smoke Detector 1 ABOVE FACP Photoelectric 40665799
12:M1-02 Pull Station 1 EAST EXIT 40665796
12:M1-05 Pull Station 1 NORTH EXIT 40665797
12:M1-06 Smoke Detector 1 ELEV. LOBBY Photoelectric 40665800
12:M1-07 Pull Station 1 WEST EXIT 40665798
12:M1-08 Smoke Detector 1 ELEV. MECH. RM 41-126 Photoelectric 40665801
12:M1-09 Heat Detector 1 ELEV MECH RM 41-126 40665795
12:M1-11 Pull Station 2 BY EAST STAIRWELL 40665839
12:M1-12 Smoke Detector 2 ELEV. LOBBY Photoelectric 40665841
12:M1-13 Smoke Detector 2 ELEV. TOP SHAFT Photoelectric 40665842
12:M1-14 Heat Detector 2 ELEV. TOP SHAFT 40665838
12:M1-15 Pull Station 2 BY WEST STAIRWELL 40665840
12:M1-17 Smoke Detector 1 FILE RM 41-118 Photoelectric 40665802
12:M1-25 Smoke Detector 1 BY ROOM 134 Photoelectric 40665803
12:M1-26 Smoke Detector 1 BY ROOM 127 Photoelectric 40665804
12:M1-29 Smoke Detector 1 BY ROOM 117 Photoelectric 40665805
12:M1-30 Smoke Detector 1 BY ROOM 115 Photoelectric 40665806
12:M1-31 Smoke Detector 1 BY ROOM 107 Photoelectric 40665807
12:M1-32 Smoke Detector 1 BY ROOM 105 Photoelectric 40665808
12:M1-33 Smoke Detector 1 LOBBY RECEPTION Photoelectric 40665809
12:M1-35 Smoke Detector 1 BY ROOM 103 Photoelectric 40665810
12:M1-36 Smoke Detector 1 BY ROOM 137 Photoelectric 40665811
12:M1-37 Smoke Detector 1 LOUNGE Photoelectric 40665812
12:M1-39 Smoke Detector 1 BY ROOM 140 Photoelectric 40665813
12:M1-40 Smoke Detector 1 BY ROOM 146 Photoelectric 40665814
12:M1-42 Smoke Detector 1 BY ROOM 150 Photoelectric 40665815
12:M1-43 Smoke Detector 1 BY ROOM 152 Photoelectric 40665816
12:M1-44 Smoke Detector 1 BY ROOM 158 Photoelectric 40665817
12:M1-48 Smoke Detector 2 BY ROOM 226 Photoelectric 40665843
12:M1-49 Smoke Detector 2 BY ROOM 223 Photoelectric 40665844
12:M1-50 Smoke Detector 2 BY ROOM 220 Photoelectric 40665845
12:M1-53 Smoke Detector 2 BY ROOM 217 Photoelectric 40665846
12:M1-54 Smoke Detector 2 BY ROOM 214 Photoelectric 40665847
12:M1-56 Smoke Detector 2 BY ROOM 209 Photoelectric 40665848
12:M1-57 Smoke Detector 2 BY ROOM 205 Photoelectric 40665849
12:M1-59 Smoke Detector 2 BY ROOM 203 Photoelectric 40665850
12:M1-61 Smoke Detector 2 BY ROOM 228 Photoelectric 40665851
12:M1-62 Smoke Detector 2 LOUNGE Photoelectric 40665852
12:M1-63 Smoke Detector 2 BY REST ROOM Photoelectric 40665853
12:M1-67 Smoke Detector 2 BY ROOM 234 Photoelectric 40665854
12:M1-68 Smoke Detector 2 BY ROOM 237 Photoelectric 40665855
12:M1-69 Smoke Detector 2 BY ROOM 239 Photoelectric 40665856
Kinetix 19 07/13/2018
12:M1-71 Smoke Detector 2 BY ROOM 243 Photoelectric 40665857
12:M1-72 Smoke Detector 2 BY ROOM 245 Photoelectric 40665858
12:M1-73 Smoke Detector 2 BY ROOM 230 Photoelectric 40665859
12:M1-75 Smoke Detector 1 BY REST ROOM Photoelectric 40665818
12:M1-76 Smoke Detector 1 BY ROOM 120 Photoelectric 40665819
MISC Elevator Ground Elevator 23 Recall Primary Recall 40665794
12:M1-03 Tamper Switch 1 East Exit 40665836
12:M1-04 Tamper Switch 1 RISER RM 41-101 OUTSIDE 40665837
Kinetix 20 07/13/2018
Building: Tampa VAMC Bldg 41 Control Panel: 1
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
12:M1-3-0 Tamper Switch 1 FL East Exit 41858079
17:M1-170-0 Tamper Switch 2FL Stairwell 2 41858076
6:M1-14-0 Tamper Switch BLDG Basement 41858075
6:M1-31-0 Tamper Switch 1 FL by stairwell 2 41858078
6:M1-31-0 Tamper Switch BLDG Basement 41858074
6:M1-31-0 Tamper Switch BLG32 Tunnel 41858077
12V-33Ah Battery Sealed Lead Acid 42020000
12V-33Ah Battery Sealed Lead Acid 42020001
For
Tampa VAMC Bldg 42
13000 Bruce B Downs Blvd
Tampa,FL 33637
Kinetix has performed this inspection and testing service in compliance with The Joint
Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Memorandum 23 Concurrence on EC &
LS Standards effective September 2017. This Inspection was performed in accordance with applicable
NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Inspection Completion Date
Jun 13, 2018
Building: Tampa VAMC Bldg 42 Company: Kinetix
Building: Tampa VAMC Bldg 42 Contact: Darren Matteson
Address: 13000 Bruce B Downs Blvd Phone: 813-972-2000
Address: Fax:
City/State/Zip: Tampa, FL 33637 Mobile:
Country: United States of America Email:
Inspection Performed By
Company: Kinetix Inspector: Michael Gill
Address: 12 Creek Parkway Phone: 386-747-2294
Address: Fax: 3145020737
City/State/Zip: Boothwyn, PA 19061 Mobile:
Country: United States of America Email: michaelgill15@yahoo.com
Monitoring Company: Phone: Account #:
Central Station Signal Verification Type: Mfg: Model #:
Test Time/Date: Restore Time
Inspection Completion Date: Jun 13, 2018
Building: Tampa VAMC Bldg 42 and smoke detectors
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Duct Detector 6 6 0 6 0 6
Heat Detector 2 2 0 2 0 2
Pull Station 15 15 0 15 0 15
Smoke Detector 43 43 0 43 0 43 releasing devices
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Releasing Device 1 1 0 1 0 1
Speaker/Strobe 17 17 0 17 0 17
Strobe 2 2 0 2 0 2
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2018
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018)
Duct Detector 6 6 0 6 0 6
All other Life Safety Code fire alarm requirements related to NFPA 101-2018
18/19.3.4
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Battery 0 0 0 0 4 4
Total Device Count: 90
Company: Kinetix Building: Tampa VAMC Bldg 42
Building: Tampa VAMC Bldg 42 Control Panel: n/a
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
40665893 1 Duct Detector 1 1 FL By Room 42B-102 Passed
Shuts Down Unit
40665894 2 Duct Detector 1 Room 102 -42A (AHU Supply) Passed
Shuts Down Unit
40665917 3 Smoke Detector 1 1 FL Elevator Control Room Passed
Recalls To Primary Floor
40665939 4 Duct Detector 2 2 FL Room 42-218 ( AHU 92 Supply) Passed
Shuts Down Unit
40665940 5 Duct Detector 2 2 FL Room 42-215 ( AHU 94 Supply) Passed
Shuts Down Unit
40665941 6 Duct Detector 2 2 FL Room 202 ( AHU 98 Supply) Passed
Shuts Down Unit
40665942 7 Duct Detector 2 2 FLRoom 42-206 (AHU 97 Supply) Passed
Shuts Down Unit
40665950 8 Smoke Detector 2 2 FL Corridor By Elevator Passed
Recalls To Primary Floor
The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72 Table 14.4.3.2 (17)(g)(5))
Duct Detector 6 6 0 6 6
Device Type Location ScanID Address Q2/17 Q2/18
Duct Detector 1 Room 102 -42A (AHU Supply) 40665894 0-21:M1-39 06/27-P 06/13-P
Duct Detector 1 1 FL By Room 42B-102 40665893 0-21:M1-32 06/27-P 06/13-P
Duct Detector 2 2 FLRoom 42-206 (AHU 97 Supply) 40665942 0-21:M1-12 06/27-P 06/13-P
Duct Detector 2 2 FL Room 42-218 ( AHU 92 Supply) 40665939 0-21:M1-04 06/30-P 06/13-P
Duct Detector 2 2 FL Room 42-215 ( AHU 94 Supply) 40665940 0-21:M1-08 06/27-P 06/13-P
Duct Detector 2 2 FL Room 202 ( AHU 98 Supply) 40665941 0-21:M1-11 06/27-P 06/13-P
Device Total: 6
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-
Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72 Table 14.4.3.2 (17)(d))
Heat Detector 2 2 0 2 2
Heat Detector 1 1FL ELEVATOR LOBBY 40665895 0-21:M1-71 06/27-P 06/13-P
Heat Detector 2 2FL ELEVATOR LOBBY 40665943 0-21:M1-57 06/27-P 06/13-P
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72 Table 14.4.3.2 (17e))
Pull Station 15 15 0 15 15
Pull Station 1 1 FL Room 42-119 40665901 0-21:M1-30 06/27-P 06/13-P
Pull Station 1 1 FL Room 42-117 40665902 0-21:M1-35 06/27-P 06/13-P
Pull Station 1 1 FL Room 42-123 40665900 0-21:M1-27 06/27-P 06/13-P
Pull Station 1 1 FL Room 42-112 40665904 0-21:M1-41 06/27-P 06/13-P
Pull Station 1 1 FL By Room 42-103 40665905 0-21:M1-42 06/27-P 06/13-P
Pull Station 1 1 FL Room 42-114 40665903 0-21:M1-38 06/27-P 06/13-P
Pull Station 1 1 FL By Room 42A-101 40665906 0-21:M1-46 06/27-P 06/13-P
Pull Station 1 1 FL Room 42A-105 40665907 0-21:M1-48 06/30-P 06/13-P
Pull Station 1 1 FL Room 42-127 40665899 0-21:M1-26 06/27-P 06/13-P
Pull Station 1 1 FL Room 42-130 40665898 0-21:M1-25 06/27-P 06/13-P
Pull Station 1 1 Fl Exitt By Room 42B-110 40665896 0-21:M1-18 06/27-P 06/13-P
Pull Station 1 1 FL Exit By Room 42B-101 40665897 0-21:M1-20 06/27-P 06/13-P
Pull Station 2 2 FL By East Stairwell 40665944 0-21:M1-02 06/27-P 06/13-P
Pull Station 2 2 FL Exit By Elevator 40665945 0-21:M1-06 06/27-P 06/13-P
Pull Station 2 2 FL By West Stairwell 40665946 0-21:M1-15 06/27-P 06/13-P
Device Total: 15
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72 Table 14.4.3.2 (17)(g)(1))
Smoke Detector 43 43 0 43 43
Smoke Detector 1 1 FL Elevator Control Room 40665917 0-21:M1-36 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42B-103 40665909 0-21:M1-21 06/27-P 06/13-P
Smoke Detector 1 1 FL Room 42-133 40665911 0-21:M1-23 06/27-P 06/13-P
Smoke Detector 1 1 FLRoom 42-123 40665912 0-21:M1-28 06/27-P 06/13-P
Smoke Detector 1 1 FL Room 42-124 40665913 0-21:M1-29 06/27-P 06/13-P
Smoke Detector 1 1 FL Room 42-119 40665914 0-21:M1-31 06/27-P 06/13-P
Smoke Detector 1 1 FL Room 42-117A 40665916 0-21:M1-34 06/27-P 06/13-P
Smoke Detector 1 1 FL Rear Electrical Room 40665915 0-21:M1-33 06/27-P 06/13-P
Smoke Detector 1 1 FL Room 42B-102 40665910 0-21:M1-22 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42A-102 40665921 0-21:M1-52 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42-102 40665922 0-21:M1-53 06/27-P 06/13-P
Smoke Detector 1 1 FL Room 42A-105 40665920 0-21:M1-47 06/30-P 06/13-P
Smoke Detector 1 1 FL Room 42-110 40665918 0-21:M1-40 06/27-P 06/13-P
Smoke Detector 1 1 FL Room 42-127 40665928 0-21:M1-66 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42-106 40665925 0-21:M1-63 06/27-P 06/13-P
Smoke Detector 1 1 FLBy Room 42-109 40665923 0-21:M1-54 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42-116 40665930 0-21:M1-68 06/27-P 06/13-P
Smoke Detector 1 ROOM 42B-102 40665924 0-21:M1-62 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42-109 40665926 0-21:M1-64 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42-123 40665929 0-21:M1-67 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42-111 40665931 0-21:M1-69 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42-110 40665932 0-21:M1-74 06/27-P 06/13-P
Smoke Detector 1 1 FL Room 42-105 40665919 0-21:M1-44 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42-128 40665927 0-21:M1-65 06/27-P 06/13-P
Smoke Detector 1 1 FL By Room 42B-110 40665908 0-21:M1-19 06/27-P 06/13-P
Smoke Detector 2 2 FL Fire Panel Room 42-218A 40665947 0-21:M1-01 06/28-P 06/13-P
Smoke Detector 2 2 FL Room 42-218 40665948 0-21:M1-03 06/27-P 06/13-P
Smoke Detector 2 2 FL Corridor By Elevator 40665950 0-21:M1-07 06/27-P 06/13-P
Smoke Detector 2 2 FLBy Room 42-211 40665951 0-21:M1-09 06/27-P 06/13-P
Smoke Detector 2 2 FLRoom 42-202 40665953 0-21:M1-13 06/27-P 06/13-P
Smoke Detector 2 2 FL By Room 42-202 40665952 0-21:M1-10 06/27-P 06/13-P
Smoke Detector 2 2 FLBy Room 42-205 40665954 0-21:M1-14 06/27-P 06/13-P
Smoke Detector 2 2 FL Storage Room 42-203 40665955 0-21:M1-16 06/30-P 06/13-P
Smoke Detector 2 2 FL Telephone Room 42-202E 40665956 0-21:M1-17 06/30-P 06/13-P
Smoke Detector 2 2 FL Storage Room 42-200 40665957 0-21:M1-24 06/27-P 06/13-P
Smoke Detector 2 2 FL By Room 42-221 40665949 0-21:M1-05 06/27-P 06/13-P
Smoke Detector 2 2 FL By Room 42-215 40665958 0-21:M1-50 06/30-P 06/13-P
Smoke Detector 2 2 FL By Room 42-205 40665959 0-21:M1-51 06/27-P 06/13-P
Smoke Detector 2 1 FL By Room 42-210 40665961 0-21:M1-58 06/27-P 06/13-P
Smoke Detector 2 1 FL Room 42-221 40665960 0-21:M1-56 06/30-P 06/13-P
Smoke Detector 2 ROOM 42-202 40665962 0-21:M1-59 06/27-P 06/13-P
Smoke Detector 2 1 FL Room 42-221 40665963 0-21:M1-60 06/27-P 06/13-P
Smoke Detector 2 1 FL Room 42-221 40665964 0-21:M1-78 06/27-P 06/13-P
Device Total: 43
Annual test of visual and audible fire alarms, including speakers and door releasing devices
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72 Table 14.4.3.2 (20))
Releasing Device 1 1 0 1 1
Releasing Device 1 AHU Shutdown AC 98 40665892 0 06/30-P 06/13-P
Annual test of visual and audible fire alarms, including speakers and door releasing devices
For periodic testing, verify the operation of the notification appliances. (NFPA 72 Table 14.4.3.2 (22)(b))
Speaker/Strobe 17 17 0 17 17
Speaker/Strobe 1 RM 124 BREAKROOM 40665890 0 06/30-P 06/13-P
Speaker/Strobe 1 RM 113 40665887 0 06/30-P 06/13-P
Speaker/Strobe 1 RM 102 40665886 0 06/30-P 06/13-P
Speaker/Strobe 1 BY RESTROOMS 40665885 0 06/30-P 06/13-P
Speaker/Strobe 1 BY B101 40665883 0 06/30-P 06/13-P
Speaker/Strobe 1 BY B110 40665884 0 06/30-P 06/13-P
Speaker/Strobe 1 RM A-105 40665891 0 06/30-P 06/13-P
Speaker/Strobe 1 RM 123 EAST 40665889 0 06/30-P 06/13-P
Speaker/Strobe 1 RM 119 40665888 0 06/30-P 06/13-P
Speaker/Strobe 1 BY A101 40665882 0 06/30-P 06/13-P
Speaker/Strobe 1 BY 109 40665881 0 06/30-P 06/13-P
Speaker/Strobe 2 BY 212 40665935 0 06/30-P 06/13-P
Speaker/Strobe 2 BY 215 40665936 0 06/30-P 06/13-P
Speaker/Strobe 2 BY 209 40665934 0 06/30-P 06/13-P
Speaker/Strobe 2 BY 220 40665937 0 06/30-P 06/13-P
Speaker/Strobe 2 By Room 205 40665938 0 06/30-P 06/13-P
Speaker/Strobe 2 Room 218 Exit 40665965 0 06/30-P 06/13-P
Device Total: 17
Annual test of visual and audible fire alarms, including speakers and door releasing devices
For periodic testing, verify that each appliance flashes. (NFPA 72 Table 14.4.3.2 (22c))
Strobe 2 2 0 2 2
Strobe 1 MENS 116 40665933 0 06/30-P 06/13-P
Strobe 2 WOMENS 115 40665966 0 06/30-P 06/13-P
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72 Table 14.4.3.2 (17)(g)(5))
Duct Detector 6 6 0 6 6
Duct Detector 1 Room 102 -42A (AHU Supply) 40665894 0-21:M1-39 06/27-P 06/13-P
Duct Detector 1 1 FL By Room 42B-102 40665893 0-21:M1-32 06/27-P 06/13-P
Duct Detector 2 2 FLRoom 42-206 (AHU 97 Supply) 40665942 0-21:M1-12 06/27-P 06/13-P
Duct Detector 2 2 FL Room 42-218 ( AHU 92 Supply) 40665939 0-21:M1-04 06/30-P 06/13-P
Duct Detector 2 2 FL Room 42-215 ( AHU 94 Supply) 40665940 0-21:M1-08 06/27-P 06/13-P
Duct Detector 2 2 FL Room 202 ( AHU 98 Supply) 40665941 0-21:M1-11 06/27-P 06/13-P
Device Total: 6
All other Life Safety Code fire alarm requirements related to NFPA 101-2018 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72 Table 14.4.3.2 (9))
Battery 0 0 0 0 4
Battery 2 Fire Alarm Panel 42020006 1-12V-12Ah 06/28-P
Battery 2 Fire Alarm Panel 42020007 1-12V-12Ah 06/28-P
Battery 2 Fire Alarm Panel 42020008 1-12V-33Ah 06/28-P
Battery 2 Fire Alarm Panel 42020009 1-12-33Ah 06/28-P
Device Total: 4
Duct Detector Tested 6
Heat Detector Tested 2
Pull Station Tested 15
Releasing Device Tested 1
Smoke Detector Tested/Cleaned 43
Speaker/Strobe Tested 17
Strobe Tested 2
Total 86
Untested Battery 4
Total 4
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed
Duct Detector
Fan Shut Down 1 1 FL By Room 42B-102 Passed 40665893
Fan Shut Down 1 Room 102 -42A (AHU Supply) Passed 40665894
Fan Shut Down 2 2 FL Room 202 ( AHU 98 Supply) Passed 40665941
Fan Shut Down 2 2 FL Room 42-215 ( AHU 94 Supply) Passed 40665940
Fan Shut Down 2 2 FL Room 42-218 ( AHU 92 Supply) Passed 40665939
Fan Shut Down 2 2 FLRoom 42-206 (AHU 97 Supply) Passed 40665942
Heat Detector
Shunt Trip 1 1FL ELEVATOR LOBBY Passed 40665895
Shunt Trip 2 2FL ELEVATOR LOBBY Passed 40665943
Smoke Detector
Elevator Recall 1 1 FL Elevator Control Room Passed 40665917
Elevator Recall 2 2 FL Corridor By Elevator Passed 40665950
Releasing Device
1 AHU Shutdown AC 98 Passed 40665892
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Item Category % of Inventory Quantity
Battery Control 4.44% 4
Pull Station Initiating 16.67% 15
Heat Detector Initiating 2.22% 2
Releasing Device Auxiliary 1.11% 1
Smoke Detector Initiating 47.78% 43
Strobe Indicating 2.22% 2
Speaker/Strobe Indicating 18.89% 17
Duct Detector Initiating 6.67% 6
Type Qty Model # Description Install Date
In Service - 2 Years to 3 Years
Simplex
Duct Detector 6 Photoelectric 06/29/2016
Pull Station 10 06/29/2016
Smoke Detector 1 06/29/2016
Smoke Detector 37 Photoelectric 06/29/2016
Pull Station 4 06/16/2016
Releasing Device 1 06/16/2016
Smoke Detector 3 Photoelectric 06/16/2016
Speaker/Strobe 17 06/16/2016
Strobe 2 06/16/2016
Heat Detector 2 06/08/2016
Pull Station 1 06/08/2016
Smoke Detector 2 Photoelectric 06/08/2016
Building: Tampa VAMC Bldg 42 Control Panel: 1
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date
In Service - 2 Years to 3 Years
Battery 4 Sealed Lead Acid 06/29/2016
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
21:M1-01 Smoke Detector 2 2 FL Fire Panel Room 42-218A Photoelectric 40665947
21:M1-02 Pull Station 2 2 FL By East Stairwell 40665944
21:M1-03 Smoke Detector 2 2 FL Room 42-218 Photoelectric 40665948
21:M1-04 Duct Detector 2 2 FL Room 42-218 ( AHU 92 Supply) Photoelectric 40665939
21:M1-05 Smoke Detector 2 2 FL By Room 42-221 Photoelectric 40665949
21:M1-06 Pull Station 2 2 FL Exit By Elevator 40665945
21:M1-07 Smoke Detector 2 2 FL Corridor By Elevator Photoelectric 40665950
21:M1-08 Duct Detector 2 2 FL Room 42-215 ( AHU 94 Supply) Photoelectric 40665940
21:M1-09 Smoke Detector 2 2 FLBy Room 42-211 Photoelectric 40665951
21:M1-10 Smoke Detector 2 2 FL By Room 42-202 Photoelectric 40665952
21:M1-11 Duct Detector 2 2 FL Room 202 ( AHU 98 Supply) Photoelectric 40665941
21:M1-12 Duct Detector 2 2 FLRoom 42-206 (AHU 97 Supply) Photoelectric 40665942
21:M1-13 Smoke Detector 2 2 FLRoom 42-202 Photoelectric 40665953
21:M1-14 Smoke Detector 2 2 FLBy Room 42-205 Photoelectric 40665954
21:M1-15 Pull Station 2 2 FL By West Stairwell 40665946
21:M1-16 Smoke Detector 2 2 FL Storage Room 42-203 Photoelectric 40665955
21:M1-17 Smoke Detector 2 2 FL Telephone Room 42-202E Photoelectric 40665956
21:M1-18 Pull Station 1 1 Fl Exitt By Room 42B-110 40665896
21:M1-19 Smoke Detector 1 1 FL By Room 42B-110 Photoelectric 40665908
21:M1-20 Pull Station 1 1 FL Exit By Room 42B-101 40665897
21:M1-21 Smoke Detector 1 1 FL By Room 42B-103 Photoelectric 40665909
21:M1-22 Smoke Detector 1 1 FL Room 42B-102 Photoelectric 40665910
21:M1-23 Smoke Detector 1 1 FL Room 42-133 Photoelectric 40665911
21:M1-24 Smoke Detector 2 2 FL Storage Room 42-200 Photoelectric 40665957
21:M1-25 Pull Station 1 1 FL Room 42-130 40665898
21:M1-26 Pull Station 1 1 FL Room 42-127 40665899
21:M1-27 Pull Station 1 1 FL Room 42-123 40665900
21:M1-28 Smoke Detector 1 1 FLRoom 42-123 Photoelectric 40665912
21:M1-29 Smoke Detector 1 1 FL Room 42-124 Photoelectric 40665913
21:M1-30 Pull Station 1 1 FL Room 42-119 40665901
21:M1-31 Smoke Detector 1 1 FL Room 42-119 Photoelectric 40665914
21:M1-32 Duct Detector 1 1 FL By Room 42B-102 Photoelectric 40665893
21:M1-33 Smoke Detector 1 1 FL Rear Electrical Room Photoelectric 40665915
21:M1-34 Smoke Detector 1 1 FL Room 42-117A 40665916
21:M1-35 Pull Station 1 1 FL Room 42-117 40665902
21:M1-36 Smoke Detector 1 1 FL Elevator Control Room Photoelectric 40665917
21:M1-38 Pull Station 1 1 FL Room 42-114 40665903
21:M1-39 Duct Detector 1 Room 102 -42A (AHU Supply) Photoelectric 40665894
21:M1-40 Smoke Detector 1 1 FL Room 42-110 Photoelectric 40665918
21:M1-41 Pull Station 1 1 FL Room 42-112 40665904
21:M1-42 Pull Station 1 1 FL By Room 42-103 40665905
21:M1-44 Smoke Detector 1 1 FL Room 42-105 Photoelectric 40665919
21:M1-46 Pull Station 1 1 FL By Room 42A-101 40665906
21:M1-47 Smoke Detector 1 1 FL Room 42A-105 Photoelectric 40665920
21:M1-48 Pull Station 1 1 FL Room 42A-105 40665907
21:M1-50 Smoke Detector 2 2 FL By Room 42-215 Photoelectric 40665958
21:M1-51 Smoke Detector 2 2 FL By Room 42-205 Photoelectric 40665959
21:M1-52 Smoke Detector 1 1 FL By Room 42A-102 Photoelectric 40665921
21:M1-53 Smoke Detector 1 1 FL By Room 42-102 Photoelectric 40665922
21:M1-54 Smoke Detector 1 1 FLBy Room 42-109 Photoelectric 40665923
21:M1-56 Smoke Detector 2 1 FL Room 42-221 Photoelectric 40665960
21:M1-57 Heat Detector 2 2FL ELEVATOR LOBBY 40665943
21:M1-58 Smoke Detector 2 1 FL By Room 42-210 Photoelectric 40665961
21:M1-59 Smoke Detector 2 ROOM 42-202 Photoelectric 40665962
21:M1-60 Smoke Detector 2 1 FL Room 42-221 Photoelectric 40665963
21:M1-62 Smoke Detector 1 ROOM 42B-102 Photoelectric 40665924
21:M1-63 Smoke Detector 1 1 FL By Room 42-106 Photoelectric 40665925
21:M1-64 Smoke Detector 1 1 FL By Room 42-109 Photoelectric 40665926
21:M1-65 Smoke Detector 1 1 FL By Room 42-128 Photoelectric 40665927
21:M1-66 Smoke Detector 1 1 FL Room 42-127 Photoelectric 40665928
21:M1-67 Smoke Detector 1 1 FL By Room 42-123 Photoelectric 40665929
21:M1-68 Smoke Detector 1 1 FL By Room 42-116 Photoelectric 40665930
21:M1-69 Smoke Detector 1 1 FL By Room 42-111 Photoelectric 40665931
21:M1-71 Heat Detector 1 1FL ELEVATOR LOBBY 40665895
21:M1-74 Smoke Detector 1 1 FL By Room 42-110 Photoelectric 40665932
21:M1-78 Smoke Detector 2 1 FL Room 42-221 Photoelectric 40665964
Building: Tampa VAMC Bldg 42 Control Panel: 1
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
12-33Ah Battery 2 Fire Alarm Panel Sealed Lead Acid 42020009
12V-12Ah Battery 2 Fire Alarm Panel Sealed Lead Acid 42020006
12V-12Ah Battery 2 Fire Alarm Panel Sealed Lead Acid 42020007
12V-33Ah Battery 2 Fire Alarm Panel Sealed Lead Acid 42020008
For
Tampa VAMC Bldg 53
13000 Bruce B Downs Blvd
Tampa,FL 33637
Kinetix has performed this inspection and testing service in compliance with The Joint
Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Memorandum 23 Concurrence on EC &
LS Standards effective September 2017. This Inspection was performed in accordance with applicable
NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Inspection Completion Date
Jun 14, 2018
Building: Tampa VAMC Bldg 53 Company: Kinetix
Building: Tampa VAMC Bldg 53 Contact: Darren Matteson
Address: 13000 Bruce B Downs Blvd Phone: 813-972-2000
Address: Fax:
City/State/Zip: Tampa, FL 33637 Mobile:
Country: United States of America Email:
Inspection Performed By
Company: Kinetix Inspector: Michael Gill
Address: 12 Creek Parkway Phone: 386-747-2294
Address: Fax: 3145020737
City/State/Zip: Boothwyn, PA 19061 Mobile:
Country: United States of America Email: michaelgill15@yahoo.com
Monitoring Company: Phone: Account #:
Central Station Signal Verification Type: Mfg: Model #:
Test Time/Date: Restore Time
Inspection Completion Date: Jun 14, 2018
Building: Tampa VAMC Bldg 53
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018)
Tamper Switch 0 0 0 2 0 2 and smoke detectors
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Duct Detector 4 4 0 4 0 4
Heat Detector 2 1 1 2 0 2
Pull Station 9 9 0 9 0 9
Smoke Detector 26 23 3 26 0 26 releasing devices
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Horn 20 20 0 20 0 20
Releasing Device 16 16 0 16 0 16
Speaker/Strobe 23 23 0 23 0 23
Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2018
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018)
Duct Detector 4 4 0 4 0 4
Elevators are fully equipped and protected
Devices Tested This
Quarter Pass Fail
Tested YTD
(2018)
Untested YTD
(2018) Total Quantity
Elevator 1 1 0 1 0 1
Total Device Count: 103
Company: Kinetix Building: Tampa VAMC Bldg 53
Discrepancy Report
Building: Tampa VAMC Bldg 53 Control Panel: n/a
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer
Product Safety Commission's website and is subject to a recall by the manufacturer is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall by Manufacturer
No recalled items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Heat Detector
40666004 1 1 FL Elevator Equipment Room Failed Operation 0-14:M1-05 NFPA72 14.2.2.2.2
Smoke Detector
40666027 1 1 FL Elevator Equipment Room Failed Operation 0-14:M1-06 NFPA72 14.2.2.2.2
40666039 1 1 FL Elevator Lobby Failed Operation 0-14:M1-25 NFPA72 14.2.2.2.2
40666068 2 2 FL Elevator Lobby Failed Operation 0-14:M1-42 NFPA72 14.2.2.2.2
Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Proposed Solutions Report
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a
Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Heat Detector
40666004 1 1 FL Elevator Equipment Room Investigate T/M
Smoke Detector
40666027 1 1 FL Elevator Equipment Room Investigate T/M
40666039 1 1 FL Elevator Lobby Investigate T/M
40666068 2 2 FL Elevator Lobby Investigate T/M
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
40666002 1 Duct Detector 1 1 FL Outside Mech. South Mech RM AHU Passed
Shuts Down Unit
40666003 2 Duct Detector 1 1 FL Outside Mech. North/ AHU 2 Passed
Shuts Down Unit
40666004 3 Heat Detector 1 1 FL Elevator Equipment Room Failed Operation
Did Not Shunt
40666027 4 Smoke Detector 1 1 FL Elevator Equipment Room Failed Operation
Did Not Recall
40666039 5 Smoke Detector 1 1 FL Elevator Lobby Failed Operation
Did Not Recall
40666053 6 Duct Detector 2 2 FL Mech. Rm AHU 3 Supply Passed
Shuts Down Unit
40666054 7 Duct Detector 2 2 FL Mech. Rm AHU 3 Return Passed
Shuts Down Unit
40666068 8 Smoke Detector 2 2 FL Elevator Lobby Failed Operation
Did Not Recall
The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72 Table 14.4.3.2 (17)(j)(1))
Tamper Switch 0 0 0 2 2
Tamper Switch 1 1 FL Elevator Equipment Room 40666048 0-14:M1-04 01/12-P
Tamper Switch 1 1 FL Riser by FACP 40666047 0-14:M1-02 01/12-P
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72 Table 14.4.3.2 (17)(g)(5))
Duct Detector 4 4 0 4 4
Duct Detector 1 1 FL Outside Mech. South Mech
RM AHU
40666002 0-14:M1-48 06/29-P 06/13-P
Duct Detector 1 1 FL Outside Mech. North/ AHU
40666003 0-14:M1-49 06/29-P 06/13-P
Duct Detector 2 2 FL Mech. Rm AHU 3 Supply 40666053 0-14:M1-46 06/29-P 06/13-P
Duct Detector 2 2 FL Mech. Rm AHU 3 Return 40666054 0-14:M1-47 06/29-P 06/13-P
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-
Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72 Table 14.4.3.2 (17)(d))
Heat Detector 2 1 1 2 2
Heat Detector 1 1 FL Kitchen 40666005 0-14:M1-18 06/29-P 06/13-P
Heat Detector 1 1 FL Elevator Equipment Room 40666004 0-14:M1-05 06/22-F 06/12-F
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72 Table 14.4.3.2 (17e))
Pull Station 9 9 0 9 9
Pull Station 1 1 FL Northwet Entrance 40666022 0-14:M1-37 06/29-P 06/13-P
Pull Station 1 1 FL Northeast Entrance 40666021 0-14:M1-36 06/29-P 06/13-P
Pull Station 1 1 FL Office @ Northwest
Entrance
40666023 0-14:M1-38 06/29-P 06/13-P
Pull Station 1 1 FL East Double Door Entrance 40666020 0-14:M1-35 06/29-P 06/13-P
Pull Station 1 1 FL Southeast Entrance 40666019 0-14:M1-34 06/29-P 06/13-P
Pull Station 1 1 FL Family Room 116 40666024 0-14:M1-39 06/29-P 06/13-P
Pull Station 1 1 FL Southwest Entrance 40666018 0-14:M1-33 06/29-P 06/13-P
Pull Station 2 2 FL Center Stairwell 40666064 0-14:M1-44 06/29-P 06/13-P
Pull Station 2 2 FL Attic Access 40666065 0-14:M1-45 06/29-P 06/13-P
Device Total: 9
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72 Table 14.4.3.2 (17)(g)(1))
Smoke Detector 26 23 3 26 26
Smoke Detector 1 1 FL Dining Room 114 40666034 0-14:M1-20 06/29-P 06/13-P
Smoke Detector 1 1 FL Corridor By Kitchen 40666033 0-14:M1-17 06/29-P 06/13-P
Smoke Detector 1 1 FL Southeast Entrance 40666032 0-14:M1-16 06/29-P 06/13-P
Smoke Detector 1 1 FL Dining Room 114 40666035…