Tampa-VAMC-Bldgs-_1-30-32-38-68_-_June_2018.pdf

PDF 4 MB Posted

Attached to
QUARTERLY SIMPLEX FIRE ALARM TESTING & INSPECTION SERVICES
Solicitation number
36C24819Q0163
Issued by

About this file

36C24819Q0163 0003 Tampa-VAMC-Bldgs- 1-30-32-38-68 - June 2018.pdf

View the file

Other files

File Type Posted
Tampa-VAMC-Bldgs-_T33-T61-T62-T73-T74-T75-T76-T77-T78-T80-T81-T82-T83_-_June_2018.pdf PDF
Tampa-VAMC-Bldgs-_2-19-33-36-37-39-40-56_-_June_2018.pdf PDF
Tampa-VAMC-Bldgs-_41-42-53-54-55-63-64_-_June_2018.pdf PDF
36C24819Q0163_0003.docx DOCX document
RFQ_AMENDMENT_0003_-_Q_A's___SITE_VISIT_INFORMATION_-_12.26.18.docx DOCX document
36C24819Q0163_0003_1.docx DOCX document
36C24819Q0163_0002.docx DOCX document
36C24819Q0163_0002_1.docx DOCX document
Attachment_2_-_Statement_of_Work_-_FINAL.docx DOCX document
Attachment_6_-_Wage_Determination.docx DOCX document
Attachment_5_-_Basis_For_Award.docx DOCX document
Attachment_1_-_Price_and_Cost_Schedule.docx DOCX document
Attachment_4_-_Instruction_to_Quoters.docx DOCX document
36C24819Q0163_0001.docx DOCX document
Attachment_3_-_Delivery_Schedule.docx DOCX document
RFQ_AMENDMENT_-_Q_A's_-_12.20.18.docx DOCX document
36C24819Q0163_0001_1.docx DOCX document
36C24819Q0163.docx DOCX document
Attachment_4_-_Instruction_to_Quoters.docx DOCX document
Attachment_6_-_Wage_Determination.docx DOCX document
Attachment_5_-_Basis_For_Award.docx DOCX document
Attachment_1_-_Price_and_Cost_Schedule.docx DOCX document
Attachment_3_-_Delivery_Schedule.docx DOCX document
Attachment_2_-_Statement_of_Work_-_FINAL.docx DOCX document
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm and Life Safety System

Inspection Certificate

For

Tampa VAMC Bldg 1

13000 Bruce B Downs Blvd

Tampa,FL 33612

Kinetix has performed this inspection and testing service in compliance with The Joint

Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Memorandum 23 Concurrence on EC &

LS Standards effective September 2017. This Inspection was performed in accordance with applicable

NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Completion Date

Jun 20, 2018

Building: Tampa VAMC Bldg 1 Company: Kinetix

Contact: Harold Harrod Contact: Michael Gill

Title: Electronics Technician Title: Field Supervisor/Technician

Kinetix 1 07/13/2018

Executive Summary Generated by: BuildingReports.com

Building Information

Building: Tampa VAMC Bldg 1 Contact: Harold Harrod

Address: 13000 Bruce B Downs Blvd Phone: 813-972-2000 x3727

Address: Fax:

City/State/Zip: Tampa, FL 33612 Mobile:

Country: United States of America Email:

Inspection Performed By

Company: Kinetix Inspector: Michael Gill

Address: 12 Creek Parkway Phone: 386-747-2294

Address: Fax: 3145020737

City/State/Zip: Boothwyn, PA 19061 Mobile:

Country: United States of America Email: michaelgill15@yahoo.com

Monitoring Company: Phone: Account #:

Central Station Signal Verification Type: Digital Communicator Mfg: Simplex Model #:

Test Time/Date: 6/14/18 2:12:31 PM Restore Time

Kinetix 2 07/13/2018

Inspection Completion Date: Jun 20, 2018

Building: Tampa VAMC Bldg 1

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches

Devices Tested This

Quarter Pass Fail

Tested YTD

(2018)

Untested YTD

(2018) Total Quantity

Tamper Switch 0 0 0 104 0 104

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

Devices Tested This

Quarter Pass Fail

Tested YTD

(2018)

Untested YTD

(2018) Total Quantity

Duct Detector 74 74 0 74 0 74

Heat Detector 26 26 0 26 0 26

Pull Station 157 157 0 157 0 157

Smoke Detector 992 992 0 992 0 992

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices

Devices Tested This

Quarter Pass Fail

Tested YTD

(2018)

Untested YTD

(2018) Total Quantity

Releasing Device 191 187 4 191 0 191

Speaker/Strobe 243 241 2 243 0 243

Strobe 48 48 0 48 0 48

EC 02.03.05 EP 05

Annual test of fire alarm equipment for notifying off-site fire responders

Devices Tested This

Quarter Pass Fail

Tested YTD

(2018)

Untested YTD

(2018)

Communicator 1 1 0 1 0 1

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment per NFPA 90A-2018

Devices Tested This

Quarter Pass Fail

Tested YTD

(2018)

Untested YTD

(2018)

Duct Detector 74 74 0 74 0 74

LS 02.01.34 EP 04

All other Life Safety Code fire alarm requirements related to NFPA 101-2018

18/19.3.4

Devices Tested This

Quarter Pass Fail

Tested YTD

(2018)

Untested YTD

(2018) Total Quantity

Battery 66 51 15 66 0 66

Power Supply 15 15 0 15 0 15

LS 02.01.50 EP 04

Elevators are fully equipped and protected

Devices Tested This

Quarter Pass Fail

Tested YTD

(2018)

Untested YTD

(2018) Total Quantity

Elevator 11 11 0 11 0 11

Total Device Count: 1928

Kinetix 3 07/13/2018

Certification

Company: Kinetix Building: Tampa VAMC Bldg 1

Inspector: Michael Gill Contact: Harold Harrod

Signed: Signed:

Kinetix 4 07/13/2018

Discrepancy Report

Building: Tampa VAMC Bldg 1 Control Panel: n/a

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer

Product Safety Commission's website and is subject to a recall by the manufacturer is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall by Manufacturer

No recalled items found during this inspection.

ScanID Location Problem Address Reference

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices

Releasing Device

40663050 1 By 1B-156B Failed Operation 0 NFPA72 21.8.3

40663051 1 By 1B-156B Failed Operation 0 NFPA72 21.8.3

40663508 2 To Rooms 2B-209 to 2C-256 Failed Operation 0 NFPA72 21.8.3

40663509 2 To Rooms 2B-209 to 2C-256 Failed Operation 0 NFPA72 21.8.3

Speaker/Strobe

40664436 Penthouse Elevator 10 Equipment Room Failed Operation 0 NFPA72 14.2.2.2.2

40663990 3 Mechanical Room Failed Operation 0 NFPA72 14.2.2.2.2

LS 02.01.34 EP 04 All other Life Safety Code fire alarm requirements related to NFPA 101-2018 18/19.3.4

Battery

40662516 Basement In room GA016C Failed Test 0-12V/50Ah NFPA72 Table

14.4.2.2 (5)(b)

40663030 1 In room 1C-101C - NAC Extender 4009 Failed Test 0-12V/12Ah NFPA72 Table

14.4.2.2 (5)(b)

40663031 1 In room 1C-101C - NAC Extender 4009 Failed Test 0-12V/12Ah NFPA72 Table

14.4.2.2 (5)(b)

40663036 1 In rm 1A-113B-NAC Ext 4009 (Above

Panel)

Failed Test 0-12V/7Ah NFPA72 Table

14.4.2.2 (5)(b)

40663037 1 In rm 1A-113B-NAC Ext 4009 (Above

Panel)

Failed Test 0-12V/7Ah NFPA72 Table

14.4.2.2 (5)(b)

40663896 3 In Room 3B-304 - NAC Extender 4009

#28

Failed Test 0-12V/10Ah NFPA72 Table

14.4.2.2 (5)(b)

40664002 4 In Room 4B-402 - Control Panel 4100es Failed Test 0-12V/25Ah NFPA72 Table

14.4.2.2 (5)(b)

40664003 4 In Room 4B-402 - Control Panel 4100es Failed Test 0-12V/25Ah NFPA72 Table

14.4.2.2 (5)(b)

40662515 Ground In room GA-016C Failed Test 0-12V/50Ah NFPA72 Table

14.4.2.2 (5)(b)

40662678 Ground In room GA-23 Failed Test 0-12V/50Ah NFPA72 Table

14.4.2.2 (5)(b)

40662679 Ground In room GA-23 Failed Test 0-12V/55Ah NFPA72 Table

14.4.2.2 (5)(b)

Kinetix 5 07/13/2018

Code References NFPA72 21.8.3 All door hold-open release and integral door release and closure devices used for release service shall be monitored for integrity in accordance with Section 21.2

NFPA72 14.2.2.2.2 System deficiencies shall be corrected.

NFPA72 Table

14.4.2.2 (5)(b)

Batteries shall be replaced in accordance with the recommendations of the alarm equipment manufacturer or when the recharged battery voltage or current falls below the manufacturer's recommendations

Kinetix 6 07/13/2018

Building: Tampa VAMC Bldg 1 Control Panel: 1

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer

Product Safety Commission's website and is subject to a recall by the manufacturer is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall by Manufacturer

No recalled items found during this inspection.

ScanID Location Problem Address Reference

LS 02.01.34 EP 04 All other Life Safety Code fire alarm requirements related to NFPA 101-2018 18/19.3.4

Battery

43020006 Basement Red Panel By Exit 1-12V-20Ah

43020007 Basement Red Panel By Exit Failed Test 1-12V-20Ah NFPA72 Table

14.4.2.2 (5)(b)

42020000 2nd In Room 2C-201C NAC Extender 4009

#28

Failed Test 1-12V/10Ah NFPA72 Table

14.4.2.2 (5)(b)

42020001 2nd In Room 2C-201C - NAC Extender

4009 #28

Failed Test 1-12V/10Ah NFPA72 Table

14.4.2.2 (5)(b)

Code References NFPA72 Table

14.4.2.2 (5)(b)

Batteries shall be replaced in accordance with the recommendations of the alarm equipment manufacturer or when the recharged battery voltage or current falls below the manufacturer's recommendations

Kinetix 7 07/13/2018

Proposed Solutions Report

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a

Time and Materials basis.

ScanID Location Solution Model # Cost Fix

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices

Releasing Device

40663050 1 By 1B-156B Investigate T/M

40663051 1 By 1B-156B Investigate T/M

40663508 2 To Rooms 2B-209 to 2C-256 Investigate T/M

40663509 2 To Rooms 2B-209 to 2C-256 Investigate T/M

Speaker/Strobe

40664436 Penthouse Elevator 10 Equipment Room Replace T/M

40663990 3 Mechanical Room Investigate T/M

LS 02.01.34 EP 04 All other Life Safety Code fire alarm requirements related to NFPA 101-2018 18/19.3.4

Battery

40662516 Basement In room GA016C Replace T/M

40663030 1 In room 1C-101C - NAC Extender 4009 Replace T/M

40663031 1 In room 1C-101C - NAC Extender 4009 Replace T/M

40663036 1 In rm 1A-113B-NAC Ext 4009 (Above

Panel)

Replace T/M

40663037 1 In rm 1A-113B-NAC Ext 4009 (Above

Panel)

Replace T/M

40663896 3 In Room 3B-304 - NAC Extender 4009

#28

Replace T/M

40664002 4 In Room 4B-402 - Control Panel 4100es Replace T/M

40664003 4 In Room 4B-402 - Control Panel 4100es Replace T/M

40662515 Ground In room GA-016C Replace T/M

40662678 Ground In room GA-23 Replace T/M

40662679 Ground In room GA-23 Replace T/M

Kinetix 8 07/13/2018

Building: Tampa VAMC Bldg 1 Control Panel: 1

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a

Time and Materials basis.

ScanID Location Solution Model # Cost Fix

LS 02.01.34 EP 04 All other Life Safety Code fire alarm requirements related to NFPA 101-2018 18/19.3.4

Battery

43020006 Basement Red Panel By Exit T/M

43020007 Basement Red Panel By Exit Replace T/M

42020000 2nd In Room 2C-201C NAC Extender 4009

#28

Replace T/M

42020001 2nd In Room 2C-201C - NAC Extender

4009 #28

Replace T/M

Kinetix 9 07/13/2018

Notes & Recommendations

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.

ScanID Note Device Type Location Comment

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

40662517 1 Duct Detector Basement BASE A SEC AH13 Passed

Shuts Down Unit

40662518 2 Duct Detector Basement BASE A SEC AH13 Passed

Shuts Down Unit

40662519 3 Duct Detector Basement BSMT D WING FCU-4 RM BD-102 Passed

Shuts Down Unit

40662520 4 Duct Detector Basement BSMT D WING AHU-232 Passed

Shuts Down Unit

40662521 5 Duct Detector Basement BSMT D WING FCU-3 RM BD-102 Passed

Shuts Down Unit

40662522 6 Duct Detector Basement BSMT D WING AHU-203 Passed

Shuts Down Unit

40662523 7 Duct Detector Basement BSMT D WING AHU-204 Passed

Shuts Down Unit

40662524 8 Duct Detector Basement BASE D SEC AHU 6 Passed

Shuts Down Unit

40662525 9 Duct Detector Basement BASE D SEC AHU 11 Passed

Recalls To Primary Floor

40662526 10 Duct Detector Basement BASE D SEC AHU 18 Passed

Shuts Down Unit

40662527 11 Duct Detector Basement BASE D SEC AHU 38 Passed

Shuts Down Unit

40662528 12 Duct Detector Basement BASE D SEC AHU 6A Passed

Shuts Down Unit

40662529 13 Duct Detector Basement B D AHU-231 ROOM GD-036 Passed

Shuts Down Unit

40662530 14 Duct Detector Basement BASE C AHU 17 SUPPLY Passed

Shuts Down Unit

40662531 15 Duct Detector Basement BASE C AHU 17 RETURN Passed

Shuts Down Unit

40662532 16 Duct Detector Basement BASE B SEC AC 20 Passed

Shuts Down Unit

40662533 17 Duct Detector Basement BASE B SEC AC 20 Passed

Shuts Down Unit

40662534 18 Duct Detector Basement BASE B SEC AC 19 Passed

Shuts Down Unit

Kinetix 10 07/13/2018

40662535 19 Duct Detector Basement BASE B SEC AC 19 Passed

40662536 20 Duct Detector Basement GND FL B WING AC/14 Passed

Shuts Down Unit

40662537 21 Duct Detector Basement B Wing IRMS AC1 Return Passed

Shuts Down Unit

40662538 22 Duct Detector Basement G B AC12 SUPPLY Passed

Shuts Down Unit

40662539 23 Duct Detector Basement G B AC12 RETURN Passed

Shuts Down Unit

40662605 24 Smoke Detector Basement B C MRI ELEV LOBBY Passed

Recalls To Primary Floor

40662606 25 Smoke Detector Basement B C MRI ELEV MECH ROOM Passed

Recalls To Primary Floor

40662737 26 Duct Detector Ground G Fl E Mechanical Room GE001 Passed

Shuts Down Unit

40662738 27 Duct Detector Ground Mechanical Room 1E-101 Passed

Shuts Down Unit

40662739 28 Duct Detector Ground GFL D WING FCU-5 GD-100 Passed

Shuts Down Unit

40662740 29 Duct Detector Ground GFL D WING FCU-6 GD-100 Passed

Shuts Down Unit

40662741 30 Duct Detector Ground G C MRI GC021 AHU RETURN Passed

Shuts Down Unit

40662742 31 Duct Detector Ground G C MRI GC028 AC3 AND 4 SUPPLY

DUCT

Passed

Shuts Down Unit

40662743 32 Duct Detector Ground G C MRI GC028 AC3 AND 4 RETURN

DUCT

Passed

Shuts Down Unit

40662744 33 Duct Detector Ground G C MRI GC021 AHU SUPPLY Passed

Shuts Down Unit

40662745 34 Duct Detector Ground G C MRI GC050 AC1 SUPPLY DUCT Passed

Shuts Down Unit

40662746 35 Duct Detector Ground G C MRI GC050 AC1 RETURN DUCT Passed

Shuts Down Unit

40662747 36 Duct Detector Ground G C MRI GC021 AHU RETURN Passed

Shuts Down Unit

40662748 37 Duct Detector Ground G C MRI GC021 AHU SUPPLY Passed

Shuts Down Unit

40662901 38 Smoke Detector Ground G C RTU ELEV LOBBY Passed

Recalls To Primary Floor

40662902 39 Smoke Detector Ground G C MRI ELEV LOBBY Passed

Recalls To Primary Floor

40662936 40 Smoke Detector Ground GNDFL D SEC BY ELEV 2 Passed

Recalls To Primary Floor

40662937 41 Smoke Detector Ground GNDFL D SEC BY ELEV 5 Passed

Recalls To Primary Floor

Kinetix 11 07/13/2018

40662938 42 Smoke Detector Ground GNDFL D SEC BY ELEV 10 Passed

40662939 43 Smoke Detector Ground GNDFL C SEC BY ELEV 6 Passed

Recalls To Primary Floor

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices

40663050 44 Releasing Device 1 By 1B-156B Failed Operation

Door did not close

40663051 45 Releasing Device 1 By 1B-156B Failed Operation

Door did not close

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

40663081 46 Duct Detector 1 1 Fl E By Room 1E-123 Passed

Shuts Down Unit

40663082 47 Duct Detector 1 1 Fl E By Room 1E-110 Passed

Shuts Down Unit

40663083 48 Duct Detector 1 1 C MRI C182 AHU RETURN Passed

Shuts Down Unit

40663084 49 Duct Detector 1 1 C MRI C182 AHU SUPPLY Passed

Shuts Down Unit

40663085 50 Duct Detector 1 1ST FL D WING AC/65 Passed

Shuts Down Unit

40663160 51 Smoke Detector 1 1FL A SEC ELEV 9 SHAFT Passed

Recalls To Primary Floor

40663269 52 Smoke Detector 1 1 C MRI ELEV LOBBY Passed

Recalls To Primary Floor

40663270 53 Smoke Detector 1 1 C MRI ELEV SHAFT Passed

Recalls To Alternate Floor

40663278 54 Smoke Detector 1 1 C MRI HALL BY C-173 Passed

Recalls To Primary Floor

40663309 55 Smoke Detector 1 1FL D SEC BY ELEV 2 Passed

Recalls To Alternate Floor

40663310 56 Smoke Detector 1 1FL D SEC BY ELEV 5 Passed

Recalls To Alternate Floor

40663311 57 Smoke Detector 1 1FL D SEC BY ELEV 10 Passed

Recalls To Alternate Floor

40663312 58 Smoke Detector 1 1FL C SEC BY ELEV 6 Passed

Recalls To Alternate Floor

40663515 59 Duct Detector 2 2 D SICU AHU 40 RETURN Passed

Shuts Down Unit

40663516 60 Duct Detector 2 2 D SICU AHU 40 RETURN Passed

Shuts Down Unit

40663517 61 Duct Detector 2 2 D SICU AHU 40 SUPPLY Passed

Shuts Down Unit

40663518 62 Duct Detector 2 2 D SICU AHU 40 SUPPLY Passed

Shuts Down Unit

40663519 63 Duct Detector 2 2 D SICU AHU 40 SUPPLY Passed

40663520 64 Duct Detector 2 2FL ROOF D PACU Passed

Kinetix 12 07/13/2018

40663521 65 Duct Detector 2 2FL D SEC RM 2D-215 Passed

Shuts Down Unit

40663680 66 Smoke Detector 2 2FL D SEC BY ELEV 2 Passed

Recalls To Primary Floor

40663681 67 Smoke Detector 2 2FL D SEC BY ELEV 4 Passed

Recalls To Primary Floor

40663682 68 Smoke Detector 2 2FL D SEC BY ELEV 10 Passed

Recalls To Primary Floor

40663683 69 Smoke Detector 2 2FL C SEC BY ELEV 6 Passed

Recalls To Primary Floor

40663907 70 Duct Detector 3 3FL 3S ROOM 326 Passed

Shuts Down Unit

40663908 71 Duct Detector 3 3FL 3S ROOM 326 Passed

Shuts Down Unit

40663909 72 Duct Detector 3 3 A BY 3A-348 Passed

Shuts Down Unit

40663910 73 Duct Detector 3 3 B AC5 SUPPLY Passed

Shuts Down Unit

40663911 74 Duct Detector 3 3 B AC5 RETURN Passed

Shuts Down Unit

40663912 75 Duct Detector 3 3FL B SEC AC9 Passed

Shuts Down Unit

40663913 76 Duct Detector 3 3FL B SEC AC9 Passed

Shuts Down Unit

40663914 77 Duct Detector 3 3FL B SEC AC10A Passed

Shuts Down Unit

40663915 78 Duct Detector 3 3FL B SEC AC10A Passed

Shuts Down Unit

40663916 79 Duct Detector 3 3FL B SEC AC10B Passed

Shuts Down Unit

40663917 80 Duct Detector 3 3FL B SEC AC10B Passed

Shuts Down Unit

40663918 81 Duct Detector 3 3FL B SEC AC8 SUPPLY Passed

Shuts Down Unit

40663920 82 Duct Detector 3 3FL B SEC AC7 SUPPLY Passed

Shuts Down Unit

40663921 83 Duct Detector 3 3RD FL WING B AC/39 Passed

Shuts Down Unit

40663922 84 Duct Detector 3 3RD FL WING B AC/39 Passed

Shuts Down Unit

40663949 85 Smoke Detector 3 ELEVATOR 6 EQUIP ROOM Passed

Recalls To Primary Floor

40663950 86 Smoke Detector 3 3W A SEC BY ELEV 5 Passed

Recalls To Primary Floor

40663952 87 Smoke Detector 3 3W A SEC BY ELEV 10 Passed

40663958 88 Smoke Detector 3 3FL A SEC BY ELEV 2 Passed

Kinetix 13 07/13/2018

40663981 89 Smoke Detector 3 3FL B SEC ELEV 6 SHAFT Passed

Recalls To Primary Floor

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices

40663990 90 Speaker/Strobe 3 Mechanical Room Failed Operation

All speakers and Strobe are inop in Mechanical Room

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

40664009 91 Duct Detector 4 4W B SEC MICU RM 4B410 Passed

Shuts Down Unit

40664036 92 Smoke Detector 4 4W A SEC BY ELEV 5 Passed

Recalls To Primary Floor

40664038 93 Smoke Detector 4 4W A SEC BY ELEV 10 Passed

Recalls To Primary Floor

40664053 94 Smoke Detector 4 4FL A SEC BY ELEV 2 Passed

Recalls To Primary Floor

40664110 95 Duct Detector 5 5TH FL B WEST RM 5B-509 AHU Passed

Shuts Down Unit

40664111 96 Duct Detector 5 5N BY ROOM 5A-541 Passed

Shuts Down Unit

40664138 97 Smoke Detector 5 5FL A SEC BY ELEV 2 Passed

Recalls To Primary Floor

40664139 98 Smoke Detector 5 5W A SEC BY ELEV 5 Passed

Recalls To Primary Floor

40664141 99 Smoke Detector 5 5W A SEC BY ELEV 10 Passed

Recalls To Primary Floor

40664219 100 Duct Detector 6 6W B SEC RM CCU 6B610 S Passed

Shuts Down Unit

40664268 101 Smoke Detector 6 6W A SEC BY ELEV 5 Passed

Recalls To Primary Floor

40664270 102 Smoke Detector 6 6W A SEC BY ELEV 10 Passed

Recalls To Primary Floor

40664275 103 Smoke Detector 6 6FL A SEC BY ELEV 2 Passed

Recalls To Primary Floor

40664353 104 Smoke Detector 7 7W A SEC BY ELEV 5 Passed

Recalls To Primary Floor

40664355 105 Smoke Detector 7 7W A SEC BY ELEV 10 Passed

Recalls To Primary Floor

40664364 106 Smoke Detector 7 7FL A SEC BY ELEV 2 Passed

Recalls To Primary Floor

40664410 107 Duct Detector Penthouse B WING PENTHOUSE AC/2 Passed

Shuts Down Unit

40664411 108 Duct Detector Penthouse B WING PENTHOUSE AC/2 Passed

Shuts Down Unit

40664412 109 Duct Detector Penthouse B WING PENTHOUSE AC/3 Passed

Shuts Down Unit

40664413 110 Duct Detector Penthouse B WING PENTHOUSE AC/3 Passed

Kinetix 14 07/13/2018

40664414 111 Duct Detector Penthouse PENT AC 1 Passed

40664415 112 Duct Detector Penthouse PENT AC 4 Passed

Shuts Down Unit

40664424 113 Smoke Detector Penthouse PENT ELEV MACH RM Passed

Recalls To Primary Floor

40664425 114 Smoke Detector Penthouse PENT ELEV MACH RM Passed

Recalls To Primary Floor

40664426 115 Smoke Detector Penthouse PENT ELEV MACH RM Passed

Recalls To Primary Floor

40664429 116 Smoke Detector Penthouse PENT ELEV 1,2,3 SHAFT Passed

Recalls To Primary Floor

40664430 117 Smoke Detector Penthouse PENT ELEV 4,5 SHAFT Passed

Recalls To Primary Floor

40664433 118 Smoke Detector Penthouse PENT ELEV 10,11 SHAFT Passed

Recalls To Primary Floor

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices

40664436 119 Speaker/Strobe Penthouse Elevator 10 Equipment Room Failed Operation

Old device

Kinetix 15 07/13/2018

Inspection & Testing

Building: Tampa VAMC Bldg 1 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72 Table 14.4.3.2 (17)(j)(1))

Devices Tested Q2/18 Pass Q2/18 Fail Q2/18 Tested YTD (2018) Total Quantity

Tamper Switch 0 0 0 104 104

Device Type Location ScanID Address Q2/17 Q3/17 Q1/18 Q2/18

Tamper Switch Basement A Generator Rm 40662641 0-9:M1-64 07/21-P 01/18-P

Tamper Switch Basement A NORTH TOWER

RISER

40662631 0-20:M1-54 07/21-P 01/18-P

Tamper Switch Basement A SOUTH TOWER

RISER (By Stair 2)

40662629 0-16:M1-12 07/21-P 01/18-P

Tamper Switch Basement A Wing Below

GA-023

40663883 0-16:M3-25 07/21-P 01/18-P

Tamper Switch Basement B A GENERATOR

ROOM

40663025 0-9:M1-64 07/21-P 01/18-P

Tamper Switch Basement B A GENERATOR

ROOM

40662656 0-9:M1-64 07/21-P 01/18-P

Tamper Switch Basement B B PIPE SHOP 40662635 0-8:M1-30 07/21-P 01/18-P

Tamper Switch Basement B By Stair 1 TS (In

Basement)

40662634 0-20:M4-06 07/21-P 01/18-P

Tamper Switch Basement B C BASEMENT

STORAGE

40662636 0-8:M1-31 07/21-P 01/18-P

Tamper Switch Basement B C ELECTICAL

SHOP

40662654 0-8:M1-36 07/21-P 01/18-P

Tamper Switch Basement B C RTU and MRI 40662638 0-8:M1-35 07/21-P 01/18-P

Tamper Switch Basement B D BOILER ROOM

(By Stair 1)

40662632 0-20:M1-55 07/21-P 01/18-P

Tamper Switch Basement B D BY AHU 18 40662658 0-20:M2-11

07/21-P 01/18-P

Tamper Switch Basement B WEST TOWER

RISER

40662637 0-8:M1-33 07/21-P 01/18-P

Tamper Switch Basement B WING PIPE SHOP 40662643 0-9:M2-26 07/21-P 01/18-P

Tamper Switch Basement BASEMENT BY ELEV

1 2 3

40662659 0-9:M2-41 07/21-P 01/18-P

Tamper Switch Basement BASEMENT BY ELEV

4 5

40662660 0-9:M2-42 07/21-P 01/18-P

Tamper Switch Basement BASEMENT BY

STAIR 3

40662649 0-9:M2-43 07/21-P 01/18-P

Tamper Switch Basement BASEMENT BY

STAIRWELL 3

40662646 0-9:M2-31 07/21-P 01/18-P

Tamper Switch Basement BASEMENT BY

STAIRWELL 3

40662647 0-9:M2-33 07/21-P 01/18-P

Tamper Switch Basement BASEMENT WING C

ELEC SHOP

40662657 0-9:M2-03 07/21-P 01/18-P

Tamper Switch Basement BASEMENT WING D

X-RAY FILE

40662640 0-9:M2-07 07/21-P 01/18-P

Tamper Switch Basement BLDG 1 BASEMENT 40662630 0-16:M1-13 07/21-P 01/18-P

Kinetix 16 07/13/2018

BELOW GA-023

Tamper Switch Basement BLDG 32 RTU ( By

Stair 3)

40662639 0-8:M1-38 07/21-P 01/18-P

Tamper Switch Basement BSMT D WING BY

STAIR 1

40662648 0-9:M2-35 07/21-P 01/18-P

Tamper Switch Basement BSMT D WING RM

BD-102

40662651 0-M1-14 07/21-P 01/18-P

Tamper Switch Basement BSMT WING D

STAIR BD-STR 22

40662650 0-19:M1-09 07/21-P 01/18-P

Tamper Switch Basement By Stair 3 40662642 0-8:M1-35 07/21-P 01/18-P

Tamper Switch Basement C Electric Shop

Cage

40663464 0-9:M2-3 07/21-P 01/18-P

Tamper Switch Basement C Stair 6 Riser 40663461 0-8:M1-34 07/21-P 01/18-P

Tamper Switch Basement D Wing AC Mech

Rm

40663876 0-20:M2-12

07/21-P 01/18-P

Tamper Switch Basement D Wing By Stair 1 40662655 0-20:M1-55 07/21-P 01/18-P

Tamper Switch Basement D Wing Stair

BD-STR

40664312 0-19:M1-9 07/21-P 01/18-P

Tamper Switch Basement D Wing Stair

BD-STR

40662633 0-19:M1-1 07/21-P 01/18-P

Tamper Switch Basement Electrical Shop

Cage

40662652 0-8:M1-32 07/21-P 01/18-P

Tamper Switch Basement GFL B WING 40662645 0-9:M2-29 07/21-P 01/18-P

Tamper Switch Basement GFL B WING RM

BB6

40662644 0-9:M2-28 07/21-P 01/18-P

Tamper Switch Basement MRI By Elevator 18 40663878 0-9:M2-5 07/21-P 01/18-P

Tamper Switch Basement MRI Rm CB-6F 40663884 0-9:M2-6 07/21-P 01/18-P

Tamper Switch Basement PB A WING FIRE

PUMP ROOM TS

40662661 0-16:M3-22 07/21-P 01/18-P

Tamper Switch Basement PB A WING FIRE

PUMP ROOM TS

40662664 0-16:M3-28 07/21-P 01/18-P

Tamper Switch Basement PB A WING FIRE

PUMP ROOM TS

40662665 0-16:M3-29 07/21-P 01/18-P

Tamper Switch Basement PB A WING FIRE

PUMP ROOM TS

40662662 0-16:M3-26 07/21-P 01/18-P

Tamper Switch Basement PB A WING FIRE

PUMP ROOM TS

40662663 0-16:M3-27 07/21-P 01/18-P

Tamper Switch Basement PB A WING FIRE

PUMP ROOM TS

40662666 0-16:M3-30 07/21-P 01/18-P

Tamper Switch Basement PB A WING FIRE

PUMP ROOM TS

40662667 0-16:M3-31 07/21-P 01/18-P

Tamper Switch 1st 1 B C MRI Tamper Switch 40663460 0-7:M1-48 07/21-P 01/18-P

Tamper Switch 1st 1 C COR THERAPY TS

(Stair 3)

40663467 0-8:M4-34 07/21-P 01/18-P

Tamper Switch 1st 1 C THERAPY 40663459 0-8:M1-39 07/21-P 01/18-F

Tamper Switch 1st 1CN Stair 7 40663877 0-8:M4-5 07/21-P 01/18-P

Tamper Switch 1st 1CW Stair 6 40663023 0-8:M4-4 07/21-P 01/18-P

Tamper Switch 1st 1FL B WING WEST STAIR 5 40663463 0-9:M2-21 07/21-P 01/18-P

Tamper Switch 1st A Wing Stair 9 40663465 0-15:M1-44 07/21-P 01/18-P

Tamper Switch 1st D Wing Stair 1 40663022 0-20:M4-2 07/21-P 01/18-P

Tamper Switch 1st D Wing Stair 1 40663019 0-20:M4-5 07/21-P 01/18-P

Tamper Switch 1st G C MRI Tamper Switch 40663024 0-7:M1-46 07/21-P 01/18-P

Tamper Switch 1st IN STAIR 2 40663458 0-16:M3-2 07/21-P 01/18-P

Tamper Switch 1st IN STAIR 3 40663456 0-8:M4-30 07/21-P 01/18-P

Tamper Switch 2nd 2FL 2BW STAIRWELL 5 40663885 0-8:M4-105 07/21-P 01/18-P

Tamper Switch 2nd 2ND FL 2CW TS M4-12 40663886 0-8:M4-12 07/21-P 01/18-P

Tamper Switch 2nd 2ND FL B WING Stair 4 40663880 0-9:M2-17 07/21-P 01/18-P

Tamper Switch 2nd A Retail Store Stair 2 40663881 0-16:M3-6 07/21-P 01/18-P

Kinetix 17 07/13/2018

Tamper Switch 2nd C Wing By Rm 201A 40663457 0-8:M4-8 07/21-P 01/18-P

Tamper Switch 2nd D Wing SPS Elevator

Lobby

40663888 0-19:M1-17

07/21-P 01/18-P

Tamper Switch 2nd IN STAIR 1 40663874 0-20:M5-48 07/21-P 01/18-P

Tamper Switch 2nd IN STAIR 1 40663875 0-20:M5-46 07/21-P 01/18-P

Tamper Switch 2nd IN STAIR 3 40663873 0-8:M5-35 07/21-P 01/18-P

Tamper Switch 3rd 3RD FL A NORTH TS

(Stair1)

40663995 0-20:M4-12 07/21-P 01/18-P

Tamper Switch 3rd 3RD FL B WING TS (Stair

3)

40663996 0-8:M4-14 07/21-P 01/18-P

Tamper Switch 3rd 3RD FLOOR A WING SO

TS (Stair 2)

40663994 0-16:M3-10 07/21-P 01/18-P

Tamper Switch 3rd IN STAIR 3 - West Side 40663993 0-8:M4-35 07/21-P 01/18-P

Tamper Switch 4th 4TH FL A NORTH TS

(Stair1)

40664101 0-20:M4-14 07/21-P 01/18-P

Tamper Switch 4th 4TH FL B WEST TS (Stair

3)

40664102 0-8:M4-18 07/21-P 01/18-P

Tamper Switch 4th 4TH FLOOR A WING SO

TS (Stair 2)

40664100 0-16:M3-12 07/21-P 01/18-P

Tamper Switch 4th IN STAIR 3 - West Side 40664099 0-8:M4-62 07/21-P 01/18-P

Tamper Switch 6th 6TH FL A NORTH TS

(Stair1)

40664314 0-20:M4-18 07/21-P 01/18-P

Tamper Switch 6th 6TH FL B WEST TS (Stair

3)

40664315 0-8:M4-22 07/21-P 01/18-P

Tamper Switch 6th 6TH FLOOR A WING SO

TS (Stair 2)

40664313 0-16:M3-16 07/21-P 01/18-P

Tamper Switch 7th 7TH FL A WING NORTH

TS (Stair1)

40664404 0-20:M4-20 07/21-P 01/18-P

Tamper Switch 7th 7TH FL B WEST TS (Stair

3)

40664405 0-8:M4-24 07/21-P 01/18-P

Tamper Switch 7th 7TH FLOOR A WING SO

TS (Stair 2)

40664403 0-16:M3-18 07/21-P 01/18-P

Tamper Switch 7th IN STAIR 3 - Elevator

Machine Room

40664400 0-8:M4-110 07/21-P 01/18-P

Tamper Switch 7th IN STAIR 3 - West Side 40664401 0-8:M4-112 07/21-P 01/18-P

Tamper Switch 1 1ST FL B WING Stair 4 40663462 0-9:M2-13 07/21-P 01/18-P

Tamper Switch 5 5 A NORTH TS (Stair1) 40664203 0-20:M4-16 07/21-P 01/18-P

Tamper Switch 5 5TH FL B WEST TS (Stair 3) 40664204 0-8:M4-20 07/21-P 01/18-P

Tamper Switch 5 5TH FLOOR A WING SO TS

(Stair 2)

40664202 0-16:M3-14 07/21-P 01/18-P

Tamper Switch 5 IN STAIR 1 40664201 0 07/10-P 01/18-P

Tamper Switch 5 IN STAIR 3 - West Side 40664200 0-8:M4-84 07/21-P 01/18-P

Tamper Switch Ground A Wing By Stair 9 40663466 0-15:M1-41 07/21-P 01/18-P

Tamper Switch Ground A Wing Stair 9 40663879 0-15:M1-42 07/21-P 01/18-P

Tamper Switch Ground B Wing Stair 5 40662653 0-9:M1-34 07/21-P 01/18-P

Tamper Switch Ground C Wing MRI Above

GC-051

40664402 0-7:M1-64 07/21-P 01/18-P

Tamper Switch Ground C Wing Stair 3 40663020 0-8:M4-28 07/21-P 01/18-P

Tamper Switch Ground C Wing Stair 3 40664440 0-8:M4-25 07/21-P 01/18-P

Tamper Switch Ground C Wing Stair 4 40663882 0-9:M2-18 07/21-P 01/18-P

Tamper Switch Ground C Wing Stair 6 40663889 0-20:M1-44 07/21-P 01/18-P

Tamper Switch Ground D Wing SPS Elevator

Lobby

40663887 0-19:M1-16

07/21-P 01/18-P

Tamper Switch Ground GFL A Wing TS (By

Stair 2)

40663021 0-16:M3-20 07/21-P 01/18-P

Tamper Switch Ground IN STAIR 1 40663018 0-19:M1-77 07/21-P 01/18-P

Tamper Switch Ground IN STAIR 1 40663017 0-19:M1-75 07/21-P 01/18-P

Tamper Switch Ground IN STAIR 1 40663016 0-19:M1-73 07/21-P 01/18-P

Kinetix 18 07/13/2018

Tamper Switch Ground PIV BY BLDG 29 NW

M1-16

40662756 0-16:M1-16 07/21-P 01/18-P

Tamper Switch Ground PIV BY BLDG 30 NW

Rm D8-7

40662755 0-16:M1-15 07/21-P 01/18-P

Device Total: 104

Kinetix 19 07/13/2018

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72 Table 14.4.3.2 (17)(g)(5))

Duct Detector 74 74 0 74 74

Duct Detector Basement BASE D SEC AHU 6 40662524 0-20:M2-10

06/23-P 06/14-P

Duct Detector Basement BASE D SEC AHU

40662525 0-20:M2-11

06/23-P 06/14-P

Duct Detector Basement B D AHU-231

ROOM GD-036

40662529 0-20:M4-59 06/23-P 06/14-P

Duct Detector Basement BASE C AHU 17

SUPPLY

40662530 0-8:M3-69 06/23-P 06/14-P

Duct Detector Basement BASE B SEC AC 19 40662535 0-9:M1-127 06/30-P 06/14-P

Duct Detector Basement BASE B SEC AC 19 40662534 0-9:M1-126 06/30-P 06/14-P

Duct Detector Basement GND FL B WING

AC/14

40662536 0-9:M2-01 06/30-P 06/14-P

Duct Detector Basement B Wing IRMS AC1

Return

40662537 0-9:M2-23 06/23-P 06/14-P

Duct Detector Basement BSMT D WING

FCU-3 RM BD-102

40662521 0-19:M1-30 06/30-P 06/14-P

Duct Detector Basement BSMT D WING

AHU-203

40662522 0-19:M1-32 06/23-P 06/14-P

Duct Detector Basement BASE B SEC AC 20 40662532 0-9:M1-124 06/30-P 06/14-P

Duct Detector Basement BASE B SEC AC 20 40662533 0-9:M1-125 06/30-P 06/14-P

Duct Detector Basement BASE D SEC AHU

6A

40662528 0-20:M2-11

06/30-P 06/14-P

Duct Detector Basement BASE D SEC AHU

40662526 0-20:M2-11

06/30-P 06/14-P

Duct Detector Basement G B AC12 SUPPLY 40662538 0-9:M2-29 06/30-P 06/14-P

Duct Detector Basement BASE C AHU 17

RETURN

40662531 0-8:M3-74 06/23-P 06/14-P

Duct Detector Basement BASE D SEC AHU

40662527 0-20:M2-11

06/23-P 06/14-P

Duct Detector Basement BSMT D WING

AHU-232

40662520 0-19:M1-12

06/23-P 06/14-P

Duct Detector Basement G B AC12 RETURN 40662539 0-9:M2-30 06/30-P 06/14-P

Duct Detector Basement BSMT D WING

AHU-204

40662523 0-19:M1-35 06/23-P 06/14-P

Duct Detector Basement BSMT D WING

FCU-4 RM BD-102

40662519 0-19:M1-10 06/23-P 06/14-P

Duct Detector Basement BASE A SEC AH13 40662518 0-16:M2-11

06/30-P 06/14-P

Duct Detector Basement BASE A SEC AH13 40662517 0-16:M2-11

06/30-P 06/14-P

Duct Detector Penthouse B WING

PENTHOUSE AC/3

40664412 0-8:M1-44 06/23-P 06/04-P

Duct Detector Penthouse B WING

PENTHOUSE AC/3

40664413 0-8:M1-45 06/23-P 06/04-P

Duct Detector Penthouse PENT AC 4 40664415 0-8:M1-81 06/23-P 06/04-P

Duct Detector Penthouse PENT AC 1 40664414 0-8:M1-80 06/23-P 06/04-P

Duct Detector Penthouse B WING

PENTHOUSE AC/2

40664410 0-8:M1-42 06/23-P 06/04-P

Duct Detector Penthouse B WING

PENTHOUSE AC/2

40664411 0-8:M1-43 06/23-P 06/04-P

Duct Detector Penthouse B WING

PENTHOUSE AC/1

40664416 0-8:M4-25 06/30-P 06/12-P

Kinetix 20 07/13/2018

Duct Detector 1 1ST FL D WING AC/65 40663085 0-9:M2-10 06/21-P 06/14-P

Duct Detector 1 1 C MRI C182 AHU SUPPLY 40663084 0-7:M1-52 06/21-P 06/14-P

Duct Detector 1 1 C MRI C182 AHU RETURN 40663083 0-7:M1-51 06/21-P 06/14-P

Duct Detector 1 1 Fl E By Room 1E-110 40663082 0-15:M1-17 06/21-P 06/14-P

Duct Detector 1 1 Fl E By Room 1E-123 40663081 0-15:M1-16 06/21-P 06/14-P

Duct Detector 2 2FL D SEC RM 2D-215 40663521 0-8:M2-102 06/30-P 06/14-P

Duct Detector 2 2 D SICU AHU 40 SUPPLY 40663518 0-20:M3-42 06/21-F 06/14-P

Duct Detector 2 2FL ROOF D PACU 40663520 0-20:M4-38 06/30-P 06/14-P

Duct Detector 2 2 D SICU AHU 40 SUPPLY 40663519 0-20:M3-43 06/21-P 06/14-P

Duct Detector 2 2 D SICU AHU 40 SUPPLY 40663517 0-20:M3-41 06/21-P 06/14-P

Duct Detector 2 2 D SICU AHU 40 RETURN 40663516 0-20:M3-27 06/21-P 06/14-P

Duct Detector 2 2 D SICU AHU 40 RETURN 40663515 0-20:M3-26 06/21-P 06/14-P

Duct Detector 3 3FL B SEC AC9 40663913 0-8:M2-121 06/20-P 06/04-P

Duct Detector 3 3FL B SEC AC9 40663912 0-8:M2-116 06/20-P 06/04-P

Duct Detector 3 3FL B SEC AC8 SUPPLY 40663918 0-8:M2-19 06/20-P 06/04-P

Duct Detector 3 3FL B SEC ROOF AC8

RETURN

40663919 0-8:M2-20 06/20-P 06/04-P

Duct Detector 3 3FL B SEC AC7 SUPPLY 40663920 0-8:M2-23 06/20-P 06/04-P

Duct Detector 3 3 B AC5 SUPPLY 40663910 0-8:M1-40 06/20-P 06/04-P

Duct Detector 3 3 B AC5 RETURN 40663911 0-8:M1-41 06/20-P 06/04-P

Duct Detector 3 3FL B SEC AC10A 40663914 0-8:M2-124 06/20-P 06/04-P

Duct Detector 3 3FL B SEC AC10A 40663915 0-8:M2-125 06/20-P 06/04-P

Duct Detector 3 3FL B SEC AC10B 40663917 0-8:M2-127 06/20-P 06/04-P

Duct Detector 3 3FL B SEC AC10B 40663916 0-8:M2-126 06/20-P 06/04-P

Duct Detector 3 3 A BY 3A-348 40663909 0-20:M1-60 06/20-P 06/04-P

Duct Detector 3 3FL 3S ROOM 326 40663908 0-16:M3-10

06/20-P 06/04-P

Duct Detector 3 3FL 3S ROOM 326 40663907 0-16:M3-10

06/20-P 06/12-P

Duct Detector 3 3RD FL WING B AC/39 40663922 0-9:M2-40 06/30-P 06/14-P

Duct Detector 3 3RD FL WING B AC/39 40663921 0-9:M2-24 06/30-P 06/14-P

Duct Detector 4 4W B SEC MICU RM 4B410 40664009 0-8:M2-103 06/20-P 06/12-P

Duct Detector 5 5TH FL B WEST RM 5B-509

AHU

40664110 0-8:M4-45 06/20-P 06/04-P

Duct Detector 5 5N BY ROOM 5A-541 40664111 0-8:M7-94 06/20-P 06/04-P

Duct Detector 6 6W B SEC RM CCU 6B610 S 40664219 0-8:M2-18 06/20-P 06/04-P

Duct Detector Ground G Fl E Mechanical

Room GE001

40662737 0-15:M1-26 06/23-P 06/12-P

Duct Detector Ground Mechanical Room

1E-101

40662738 0-15:M1-27 06/23-P 06/12-P

Duct Detector Ground GFL D WING FCU-5

GD-100

40662739 0-19:M1-45 06/30-P 06/14-P

Duct Detector Ground G C MRI GC021 AHU

RETURN

40662741 0-7:M1-18 06/23-P 06/14-P

Duct Detector Ground GFL D WING FCU-6

GD-100

40662740 0-19:M1-71 06/30-P 06/14-P

Duct Detector Ground G C MRI GC021 AHU

SUPPLY

40662744 0-7:M1-22 06/30-P 06/14-P

Duct Detector Ground G C MRI GC028 AC3

AND 4 SUPPLY DUCT

40662742 0-7:M1-20 06/23-P 06/14-P

Duct Detector Ground G C MRI GC050 AC1

RETURN DUCT

40662746 0-7:M1-25 06/30-P 06/14-P

Duct Detector Ground G C MRI GC028 AC3

AND 4 RETURN DUCT

40662743 0-7:M1-21 06/30-P 06/14-P

Duct Detector Ground G C MRI GC050 AC1

SUPPLY DUCT

40662745 0-7:M1-24 06/30-P 06/14-P

Duct Detector Ground G C MRI GC021 AHU

RETURN

40662747 0-7:M1-49 06/23-P 06/14-P

Kinetix 21 07/13/2018

Duct Detector Ground G C MRI GC021 AHU

SUPPLY

40662748 0-7:M1-50 06/23-P 06/14-P

Device Total: 74

Kinetix 22 07/13/2018

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.

Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72 Table 14.4.3.2 (17)(d))

Heat Detector 26 26 0 26 26

Heat Detector Basement B A GENERATOR

ROOM Pre Action

40662543 0-9:M1-62 07/21-P 06/14-P

Heat Detector Basement B A GENERATOR

ROOM Pre Action

40662542 0-9:M1-61 07/21-P 06/14-P

Heat Detector Basement B A GENERATOR

ROOM Pre Action

40662541 0-9:M1-59 07/21-P 06/14-P

Heat Detector Basement B A ATS ROOM 40662540 0-9:M1-56 06/30-P 06/14-P

Heat Detector 1 1 Fl E Decon Room 1E-122 40663086 0-15:M1-09 06/21-P 06/14-P

Heat Detector 1 1 Fl E AMB Storage Room

1E-123

40663087 0-15:M1-10 06/21-P 06/14-P

Heat Detector 1 1 Fl E HAC Room 1E-118 40663088 0-15:M1-11 06/30-P 06/14-P

Heat Detector 1 1 Fl E Room 1E-138 40663089 0-15:M1-21 06/21-P 06/14-P

Heat Detector 1 1 Fl E Room 1E-136 40663090 0-15:M1-22 06/21-P 06/14-P

Heat Detector 1 1FL D WING ROOM

1D-196D

40663092 0-19:M1-85 06/30-P 06/14-P

Heat Detector 1 1 C STAIR 20 STORAGE

ROOM

40663093 0-7:M1-07 06/30-P 06/14-P

Heat Detector 1 1 Fl E Storage Closet

1E-114

40663091 0-15:M1-28 06/30-P 06/14-P

Heat Detector 2 2FL ROOM 2A-205 (Fixed

Temp Heat) Pre Action

40663522 0-20:M5-12 07/21-P 06/14-P

Heat Detector 2 2FL ROOM 2A-205 (Fixed

Temp Heat) Pre Action

40663523 0-20:M5-13 07/21-P 06/14-P

Heat Detector 2 2FL ROOM 2A-205 (Fixed

Temp Heat) Pre Action

40663524 0-20:M5-14 07/21-P 06/14-P

Heat Detector 2 2FL ROOM 2A-237 40663526 0-20:M5-25 06/21-P 06/14-P

Heat Detector 2 2FL ROOM 2A-237A 40663525 0-20:M5-24 06/21-P 06/14-P

Heat Detector 2 2FL ROOM 2A-239 40663527 0-20:M5-26 06/21-P 06/14-P

Heat Detector 2 2FL ROOM 2A-238A 40663528 0-20:M5-27 06/21-P 06/14-P

Heat Detector 2 2FL ROOM 2A-239 40663529 0-20:M5-28 06/21-P 06/14-P

Heat Detector Ground G C MRI GC049 40662752 0-7:M1-08 06/30-P 06/14-P

Heat Detector Ground G C MRI GC040 40662753 0-7:M1-10 06/30-P 06/14-P

Heat Detector Ground GNDFL D SEC RM

GD-038A

40662751 0-20:M2-85 06/23-P 06/14-P

Heat Detector Ground G C MRI GC042 40662754 0-7:M1-11 06/30-P 06/14-P

Heat Detector Ground G Fl E Mechanical

Room

40662750 0-15:M1-06 06/30-P 06/14-P

Heat Detector Ground G Fl E Electrical

Room GE001

40662749 0-15:M1-05 06/30-P 06/14-P

Device Total: 26

Kinetix 23 07/13/2018

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72 Table 14.4.3.2 (17e))

Pull Station 157 157 0 157 157

Pull Station Basement BASEMENT A SEC

RM GA-024

40662577 0-9:M2-49 06/30-P 06/14-P

Pull Station Basement BASEMENT A SEC

RM GA-023D

40662578 0-9:M2-50 06/30-P 06/14-P

Pull Station Basement B A GENERATOR

ROOM Pre Action

40662574 0-9:M1-60 07/21-P 06/14-P

Pull Station Basement BASEMENT STAIR 9

SOUTH A WING

40662571 0-9:M1-14 06/30-P 06/14-P

Pull Station Basement B A ATS ROOM

AB-06B Pre Action

40662572 0-9:M1-57 07/21-P 06/14-P

Pull Station Basement B A GENERATOR

ROOM Pre Action

40662573 0-9:M1-58 07/21-P 06/14-P

Pull Station Basement B A GENERATOR

ROOM Pre Action

40662575 0-9:M1-63 07/21-P 06/14-P

Pull Station Basement BASEMENT PIPE

AND METAL EX B WING

40662570 0-9:M1-13 06/23-P 06/14-P

Pull Station Basement BASEMENT AC

SHOP EXIT B WING

40662569 0-9:M1-12 06/23-P 06/14-P

Pull Station Basement BASEMENT D WING

FIRE PUMP RM Pre Action

40662567 0-9:M1-10 07/21-P 06/14-P

Pull Station Basement BASEMENT A WING

CHILLER ROOM Pre Action

40662565 0-9:M1-08 07/21-P 06/14-P

Pull Station Basement BASEMENT A WING

SWITCH GEAR ROOM Pre

Action

40662564 0-9:M1-07 07/21-P 06/14-P

Pull Station Basement BASEMENT A WING

X-RAY STORAGE

40662563 0-9:M1-05 06/23-P 06/14-P

Pull Station Basement BASEMENT B WING

CHILLER ROOM Pre Action

40662566 0-9:M1-09 07/21-P 06/14-P

Pull Station Basement BASEMENT C WING

STAIR 3

40662561 0-9:M1-03 06/30-P 06/14-P

Pull Station Basement B D ROOM GD-036 40662558 0-20:M4-58 06/23-P 06/14-P

Pull Station Basement B D ROOM GD-036 40662557 0-20:M4-56 06/23-P 06/14-P

Pull Station Basement BASEMENT D WING

STAIR 1

40662559 0-9:M1-01 06/23-P 06/14-P

Pull Station Basement BSMT C SEC AC 17

STORAGE RM

40662556 0-20:M1-42 06/23-P 06/14-P

Pull Station Basement BASEMENT A WING

STAIR 2

40662560 0-9:M1-02 06/30-P 06/14-P

Pull Station Basement BASEMENT

OUTSIDE ROOM DB-06

40662562 0-9:M1-04 06/23-P 06/14-P

Pull Station Basement BASEMENT B WING

HYDRA LIFT EXIT

40662568 0-9:M1-11 06/30-P 06/14-P

Pull Station Basement B C CARP SHOP

EXIT

40662555 0-20:M1-41 06/23-P 06/14-P

Pull Station Basement BSMT D WING BY

STAIR BD-STR

40662554 0-19:M1-27 06/23-P 06/14-P

Pull Station Basement BASEMENT A SEC

RM GA-024

40662576 0-9:M2-48 06/30-P 06/14-P

Pull Station Basement BSMT D WING

MECH RM BD-10

40662553 0-19:M1-12

06/23-P 06/14-P

Pull Station Penthouse PENTHOUSE STAIR 40664422 0-8:M1-21 06/22-P 06/04-P

Kinetix 24 07/13/2018

Pull Station Penthouse 7TH FL PENT ELEV

1-5 MACH RM

40664421 0-20:M1-22 06/22-P 06/04-P

Pull Station Penthouse 7TH FL PENT ELEV

10and11 MACH RM

40664420 0-20:M1-21 06/22-P 06/04-P

Pull Station 1 1ST FL EMERG. ENTRANCE

A WING

40663130 0-9:M1-18 06/21-P 06/14-P

Pull Station 1 1 C CORRIDOR BY 1C-133 40663128 0-8:M1-62 06/21-P 06/14-P

Pull Station 1 1 C 1CN ENTRANCE/NURSE

STATION

40663127 0-8:M1-61 06/21-P 06/14-P

Pull Station 1 1ST FL STAIR 9 SOUTH A

WING

40663129 0-9:M1-16 06/21-P 06/14-P

Pull Station 1 1 1ST FL 1CW STAIR 6 40663125 0-8:M1-11 06/21-P 06/14-P

Pull Station 1 1ST FL ELEV 6 LOBBY 40663121 0-8:M1-04 06/21-P 06/14-P

Pull Station 1 1ST FL 1BS STAIR 4 40663123 0-8:M1-07 06/21-P 06/14-P

Pull Station 1 1ST FL C STAIR 3 40663120 0-8:M1-01 06/21-P 06/14-P

Pull Station 1 1ST FL 1CN STAIR 7 40663126 0-8:M1-13 06/21-P 06/14-P

Pull Station 1 1FL D BY ROOM 1D-101D 40663119 0-20:M4-87 06/21-P 06/14-P

Pull Station 1 1ST FL 1BW STAIR 5 40663124 0-8:M1-09 06/21-P 06/14-P

Pull Station 1 1ST FL D SEC LAB 40663118 0-20:M1-30 06/30-P 06/14-P

Pull Station 1 1ST FL STAIR 1 40663117 0-20:M1-23 06/21-P 06/14-P

Pull Station 1 1ST FL ELEV 4and5 LOBBY 40663115 0-20:M1-07 06/21-P 06/14-P

Pull Station 1 1ST FL MAIN LOBBY SOUTH 40663113 0-20:M1-05 06/21-P 06/14-P

Pull Station 1 1ST FL MAIN LOBBY EAST 40663112 0-20:M1-04 06/21-P 06/14-P

Pull Station 1 1ST FL ELEV 1,2and3

LOBBY

40663116 0-20:M1-08 06/21-P 06/14-P

Pull Station 1 1ST FL MAIN LOBBY 40663111 0-20:M1-03 06/21-P 06/14-P

Pull Station 1 1ST FL A SEC BY RM

1A-104H

40663109 0-16:M1-18 06/21-P 06/14-P

Pull Station 1 1FL D WING BY STAIR

1D-STR

40663110 0-19:M1-82 06/21-P 06/14-P

Pull Station 1 1ST FL ALPHA TEAM LOBBY 40663114 0-20:M1-06 06/21-P 06/14-P

Pull Station 1 1ST FL STAIR 2 S 40663108 0-16:M1-02 06/21-P 06/14-P

Pull Station 1 1 FL E Ambulance Entrance 40663106 0-15:M1-25 06/30-P 06/14-P

Pull Station 1 1 FL E Waiting Room

1E-101

40663105 0-15:M1-14 06/21-P 06/14-P

Pull Station 1 1FL E WAITING ROOM

1E-101

40663107 0-15:M1-31 06/21-P 06/14-P

Pull Station 2 2ND FL STAIR 2 40663532 0-16:M1-03 06/20-P 06/12-P

Pull Station 2 2FL BY WALKWAY TO USF 40663548 0-20:M5-15 06/20-P 06/12-P

Pull Station 2 USF WALKWAY #1 40663533 0-16:M1-04 06/20-P 06/12-P

Pull Station 2 USF WALKWAY #2 40663534 0-16:M1-05 06/20-P 06/12-P

Pull Station 2 2ND FL STAIR 9 SOUTH A

WING

40663556 0-9:M1-17 06/20-P 06/12-P

Pull Station 2 2ND FL ELEV 4and5 LOBBY 40663536 0-20:M1-09 06/20-P 06/12-P

Pull Station 2 2ND FL ELEV 1,2and3

LOBBY

40663537 0-20:M1-10 06/20-P 06/12-P

Pull Station 2 2ND FL ELEV 6 LOBBY 40663549 0-8:M1-06 06/20-P 06/12-P

Pull Station 2 2FL 2BW BY STAIRWELL 5 40663555 0-8:M4-83 06/20-P 06/14-P

Pull Station 2 2ND FL 2CW STAIR 6 40663551 0-8:M1-12 06/21-P 06/14-P

Pull Station 2 2ND FL 2CN STAIR 7 40663552 0-8:M1-14 06/21-P 06/14-P

Pull Station 2 2ND FL 2W STAIR 3 40663553 0-8:M1-15 06/20-P 06/14-P

Pull Station 2 2ND FL 2BS STAIR 4 40663550 0-8:M1-08 06/20-P 06/14-P

Pull Station 2 2FL D PACU NURSE

STATION 1

40663545 0-20:M4-39 06/20-P 06/14-P

Pull Station 2 2FL D PACU NURSE

STATION 2

40663546 0-20:M4-41 06/20-P 06/14-P

Pull Station 2 2FL PACU CORRIDOR 40663547 0-20:M4-48 06/20-P 06/14-P

Kinetix 25 07/13/2018

Pull Station 2 2 D SICU RM 2D-252N 40663544 0-20:M3-46 06/21-P 06/14-P

Pull Station 2 2 D SICU BY 2D-252A 40663543 0-20:M3-30 06/21-P 06/14-P

Pull Station 2 2FL 2BW NURSE STATION 40663554 0-8:M4-107 06/20-P 06/14-P

Pull Station 2 2 D SICU BY 2D-252W 40663542 0-20:M3-21 06/21-P 06/14-P

Pull Station 2 2ND FL RECOVERY RM.

EXIT

40663540 0-20:M1-66 06/30-P 06/14-P

Pull Station 2 2 D SICU BY 2D-260 40663541 0-20:M3-09 06/21-P 06/14-P

Pull Station 2 2FL D BY STAIR 2D-STR 40663535 0-19:M1-10

06/30-P 06/14-P

Pull Station 2 2ND FL STAIR 1 40663538 0-20:M1-24 06/20-P 06/14-P

Pull Station 2 2ND FL O.R. CENTER CORE 40663539 0-20:M1-65 06/30-P 06/14-P

Pull Station 3 3RD FL ELEV 4and5 LOBBY 40663925 0-20:M1-11 06/20-P 06/04-P

Pull Station 3 3RD FL 3W STAIR 3 40663928 0-8:M1-16 06/20-P 06/04-P

Pull Station 3 3RD FL 3N STAIR 1 40663927 0-20:M1-25 06/20-P 06/04-P

Pull Station 3 3N BY ROOM 3A-344B 40663929 0-8:M7-21 06/20-P 06/04-P

Pull Station 3 3RD FL 3S STAIR 2 40663924 0-16:M1-06 06/20-P 06/04-P

Pull Station 3 3RD FL ELEV 1,2and3

LOBBY

40663926 0-20:M1-12 06/30-P 06/12-P

Pull Station 4 4TH FL ELEV 4and5 LOBBY 40664011 0-20:M1-13 06/20-P 06/04-P

Pull Station 4 4W B SEC MICU BY 4B406 40664016 0-8:M2-49 06/20-P 06/04-P

Pull Station 4 4TH FL 4W STAIR 3 40664014 0-8:M1-17 06/30-P 06/04-P

Pull Station 4 4W BY ROOM 4B-416 40664017 0-8:M7-43 06/20-P 06/04-P

Pull Station 4 4W B SEC MICU BY 4B417 40664015 0-8:M2-40 06/20-P 06/04-P

Pull Station 4 4TH FL ELEV 1,2and3

LOBBY

40664012 0-20:M1-14 06/20-P 06/04-P

Pull Station 4 4TH FL 4N STAIR 1 40664013 0-20:M1-26 06/30-P 06/04-P

Pull Station 4 4N NURSE STATION 4A-4 40664019 0-8:M7-70 06/20-P 06/04-P

Pull Station 4 4S NURSE STATION 4A-408 40664018 0-8:M7-59 06/20-P 06/04-P

Pull Station 4 4TH FL 4S STAIR 2 40664010 0-16:M1-07 06/20-P 06/04-P

Pull Station 5 5TH FL ELEV 4and5 LOBBY 40664113 0-20:M1-15 06/20-P 06/04-P

Pull Station 5 5TH FL B WEST BY STAIR 3 40664116 0-8:M4-46 06/20-P 06/04-P

Pull Station 5 5W BY NURSE STATION

5B-506

40664118 0-8:M7-75 06/30-P 06/04-P

Pull Station 5 5N BY STAIRWELL 1 40664117 0-8:M7-101 06/20-P 06/04-P

Pull Station 5 5TH FL ELEV 1,2and3

LOBBY

40664114 0-20:M1-16 06/20-P 06/04-P

Pull Station 5 5TH FL 5N STAIR 1 40664115 0-20:M1-27 06/20-P 06/04-P

Pull Station 5 5S NURSE STATION

5A-508A

40664119 0-8:M7-89 06/20-P 06/04-P

Pull Station 5 5TH FL 5S STAIR 2 40664112 0-16:M1-08 06/20-P 06/04-P

Pull Station 6 6TH FL ELEV 4and5 LOBBY 40664221 0-20:M1-17 06/19-P 06/04-P

Pull Station 6 6W B SEC CCU BY 6B604 40664226 0-8:M1-84 06/19-P 06/04-P

Pull Station 6 6W B SEC CCU BY STAIR 3 40664227 0-8:M1-95 06/19-P 06/04-P

Pull Station 6 6W B SEC CCU BY 6B620 40664224 0-8:M1-109 06/19-P 06/04-P

Pull Station 6 6TH FL ELEV 1,2and3

LOBBY

40664222 0-20:M1-18 06/30-P 06/04-P

Pull Station 6 6TH FL 6N STAIR 1 40664223 0-20:M1-28 06/19-P 06/04-P

Pull Station 6 6S NURSE STATION 6A-608 40664228 0-8:M6-118 06/20-P 06/04-P

Pull Station 6 6TH FL 6S STAIR 2 40664220 0-16:M1-09 06/20-P 06/04-P

Pull Station 6 6N NURSE STATION

6A-644

40664229 0-8:M6-129 06/19-P 06/12-P

Pull Station 6 6TH FL 6W STAIR 3 40664225 0-8:M1-19 06/19-P 06/12-P

Pull Station 7 7N ROOM 7A-737 40664335 0-8:M6-160 06/19-P 06/04-P

Pull Station 7 7TH FL ELEV 4and5 LOBBY 40664330 0-20:M1-19 06/19-P 06/04-P

Pull Station 7 7TH FL ELEV 1,2and3

LOBBY

40664331 0-20:M1-20 06/19-P 06/04-P

Pull Station 7 7TH FL 7N STAIR 1 40664332 0-20:M1-29 06/19-P 06/04-P

Kinetix 26 07/13/2018

Pull Station 7 7S ROOM 7A-708 40664334 0-8:M6-151 06/30-P 06/04-P

Pull Station 7 7TH FL 7W STAIR 3 40664333 0-8:M1-20 06/19-P 06/04-P

Pull Station 7 7TH FL 7S STAIR 2 40664329 0-16:M1-10 06/19-P 06/04-P

Pull Station Ground GRD FL B WING

STAIR-4

40662799 0-9:M1-24 06/23-P 06/14-P

Pull Station Ground GRD FL COMPUTER

ROOM B WING

40662798 0-9:M1-23 06/23-P 06/14-P

Pull Station Ground GRD FL B WING

LINEN ROOM

40662800 0-9:M1-25 06/23-P 06/14-P

Pull Station Ground GRD FL B RM GB027 40662796 0-9:M1-21 06/23-P 06/14-P

Pull Station Ground GRD FL B WING

STAIRWELL 5

40662797 0-9:M1-22 06/23-P 06/14-P

Pull Station Ground GRD FL B WING

NORTH DOOR

40662795 0-9:M1-20 06/23-P 06/14-P

Pull Station Ground GRD FL A WING 40662794 0-9:M1-19 06/30-P 06/14-P

Pull Station Ground GRD STAIR 9 SOUTH

A WING

40662793 0-9:M1-15 06/23-P 06/14-P

Pull Station Ground GFL C BY STAIRWELL

40662789 0-7:M2-35 06/30-P 06/14-P

Pull Station Ground GFL C Stairwell 6 40662790 0-7:M2-36 06/30-P 06/14-P

Pull Station Ground GRD FL ELEV 6 LOBBY 40662792 0-8:M1-03 06/23-P 06/14-P

Pull Station Ground MRI BY ROOM

GC-028

40662788 0-7:M2-20 06/30-P 06/14-P

Pull Station Ground G D ENGR AREA 40662784 0-20:M1-40 06/23-P 06/14-P

Pull Station Ground G C MRI 40662787 0-7:M1-01 06/23-P 06/14-P

Pull Station Ground G C WAREHOUSE BY

N ROLL DOOR

40662791 0-7:M2-37 06/23-P 06/14-P

Pull Station Ground G D MORGUE 40662783 0-20:M1-39 06/30-P 06/14-P

Pull Station Ground G C COMPRESSOR RM 40662782 0-20:M1-38 06/23-P 06/14-P

Pull Station Ground G C WAREHOUSE BY

STAIR 7

40662781 0-20:M1-37 06/23-P 06/14-P

Pull Station Ground G D BOILER RM Pre

Action

40662785 0-20:M1-43 07/21-P 06/14-P

Pull Station Ground G C WAREHOUSE

AREA BY GD-007

40662778 0-20:M1-34 06/23-P 06/14-P

Pull Station Ground GRD FL ENGR AREA 40662775 0-20:M1-31 06/23-P 06/14-P

Pull Station Ground GRD FL LOADING

DOCK EAST

40662776 0-20:M1-32 06/23-P 06/14-P

Pull Station Ground GRD FL MAIN

KITCHEN

40662777 0-20:M1-33 06/23-P 06/14-P

Pull Station Ground G C WAREHOUSE

AREA ENTRANCE

40662779 0-20:M1-35 06/23-P 06/14-P

Pull Station Ground 1 GRD FL ELEV 1,2 and 3 LOBBY

40662774 0-20:M1-02 06/30-P 06/14-P

Pull Station Ground G C WAREHOUSE BY

STAIR 6

40662780 0-20:M1-36 06/23-P 06/14-P

Pull Station Ground GRD FL ELEV 4and5

LOBBY

40662773 0-20:M1-01 06/23-P 06/14-P

Pull Station Ground GFL D WING BY STAIR

GD-STR

40662769 0-19:M1-42 06/30-P 06/14-P

Pull Station Ground GFL D WING GD-100 40662771 0-19:M1-60 06/23-P 06/14-P

Pull Station Ground GFL D WING STAIR

GD-STR

40662768 0-19:M1-41 06/30-P 06/14-P

Pull Station Ground GFL D WING ROOM

GD-036N3

40662767 0-19:M1-11

06/23-P 06/14-P

Pull Station Ground GFL A BY SOUTH EXIT 40662766 0-16:M3-63 06/23-P 06/14-P

Pull Station Ground GFL D WING GD-100 40662770 0-19:M1-58 06/30-P 06/14-P

Pull Station Ground GFL A BY SOUTH EXIT 40662765 0-16:M3-61 06/23-P 06/14-P

Kinetix 27 07/13/2018

Pull Station Ground GRD FL STAIR 2 S 40662763 0-16:M1-01 06/23-P 06/14-P

Pull Station Ground GFL A BY T33 EXIT 40662764 0-16:M3-60 06/23-P 06/14-P

Pull Station Ground GFL D WING GD-100 40662772 0-19:M1-70 06/30-P 06/14-P

Device Total: 157

Kinetix 28 07/13/2018

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72 Table 14.4.3.2 (17)(g)(1))

Smoke Detector 992 992 0 992 992

Smoke Detector Basement B C MRI ELEV

MECH ROOM

40662606 0-7:M1-06 06/22-P 06/12-P

Smoke Detector Basement B C MRI ELEV

LOBBY

40662605 0-7:M1-05 06/22-P 06/12-P

Smoke Detector Basement B B ROOM BB2-I 40662614 0-9:M1-52 06/30-P 06/12-P

Smoke Detector Basement BSMT D WING RM

BD-102

40662601 0-19:M1-31 06/23-P 06/14-P

Smoke Detector Basement BSMT D WING RM

BD-102

40662600 0-19:M1-28 06/23-P 06/14-P

Smoke Detector Basement BSMT D WING RM

BD-102

40662599 0-19:M1-26 06/23-P 06/14-P

Smoke Detector Basement BASE A SEC BY

ELEV 9

40662607 0-9:M1-113 06/30-P 06/14-P

Smoke Detector Basement BSMT D WING RM

BD-102

40662603 0-19:M1-34 06/23-P 06/14-P

Smoke Detector Basement BSMT D WING RM

BD-103

40662604 0-19:M1-37 06/23-P 06/14-P

Smoke Detector Basement BASE A SEC RM

A027B

40662610 0-9:M1-116 06/30-P 06/14-P

Smoke Detector Basement BASE A SEC ELEV 9

M…