36C24818R0737-029.pdf
PDF 24 MB Posted
- Attached to
- Project 546-16-104 Renovate Ambulatory Surgery
- Solicitation number
- 36C24818R0737
About this file
36C24818R0737 546-16-104 Final Submittal Drawings_Part6.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24818R0737-0003000.docx | DOCX document | |
| 36C24818R0737-0002000.docx | DOCX document | |
| 36C24818R0737-0002003.pdf | ||
| 36C24818R0737-0002001.pdf | ||
| 36C24818R0737-0002002.pdf | ||
| 36C24818R0737-0001001.pdf | ||
| 36C24818R0737-0001000.docx | DOCX document | |
| 36C24818R0737-026.pdf | ||
| 36C24818R0737-024.pdf | ||
| 36C24818R0737-021.pdf | ||
| 36C24818R0737-023.pdf | ||
| 36C24818R0737-019.docx | DOCX document | |
| 36C24818R0737-020.pdf | ||
| 36C24818R0737-022.pdf | ||
| 36C24818R0737-027.pdf | ||
| 36C24818R0737-025.pdf | ||
| 36C24818R0737-028.pdf | ||
| 36C24818R0737-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Dale A Bacik, PE COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
36564
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
NEW PANEL: RN-7MH-2C PANELBOARD SCHEDULE
Description Circuit Breakers Wire and
Condiut Load (VA)
P ha se Load (VA) Wire and Condiut
Circuit Breakers Description # Trip (A) Poles Options A B C A B C Options Poles Trip (A) #
1 * LIGHTING 20 1 C2-20 1,294 A 400 C2-20 1 20 ** VAV 2
3 * LIGHTING 20 1 C2-20 567 B 400 C2-20 1 20 ** VAV 4
5 *** SPARE 20 1 - C 400 C2-20 1 20 *** VAV 6
7 *** DEHUMIDIFIER 20 1 C2-20 750 A 400 C2-20 1 20 *** VAV 8
9 HEADWALL C702A 20 1 C2-20 720 B 720 C2-20 1 20 HEADWALL C702J 10
11 HEADWALL C702B 20 1 C2-20 720 C 720 C2-20 1 20 HEADWALL C702K 12
13 HEADWALL C702C 20 1 C2-20 720 A 720 C2-20 1 20 HEADWALL C702L 14
15 HEADWALL C702D 20 1 C2-20 720 B 720 C2-20 1 20 HEADWALL C702M 16
17 HEADWALL C702E 20 1 C2-20 720 C 720 C2-20 1 20 HEADWALL C702N 18
19 HEADWALL C702F 20 1 C2-20 720 A 500 C2-20 1 20 AUTO FLUSH/FAUCET B732,C702A 20
21 HEADWALL C702G 20 1 C2-20 720 B 500 C2-20 1 20 AUTO FLUSH/FAUCET C702 22
23 HEADWALL C702H 20 1 C2-20 720 C 500 C2-20 1 20 AUTO FLUSH/FAUCET C704, C705 24
25 HEADWALL C702I 20 1 C2-20 720 A 360 C2-20 1 20 RECEPT STORAGE C712 26
27 NUTRITION 20 1 C2-20 1,200 B 720 C2-20 1 20 RECEPT STORAGE C712 28
29 NUTRITION 20 1 C2-20 800 C 540 C2-20 1 20 NURSE STATION C708 30
31 ** RECEPT C702, C703, B732 20 1 C2-20 900 A 180 C2-20 1 20 NURSE MANAGER C707 32
33 ** RECEPT C702 20 1 C2-20 900 B 720 C2-20 1 20 NURSE MANAGER C707 34
35 STAFF LOUNGE 20 1 C2-20 1,200 C 1,500 C2-20 1 20 ICE MACHINE 36
37 STAFF LOUNGE 20 1 C2-20 800 A - 1 20 RECEPT C706, C705, C704 38
39 ** ISO RM EXHAUST FAN 20 1 C2-20 240 B - ETR 2 20 2-POLE SPARE 40
41 ** SPARE 1 - C - - 42
43 SPARE 20 1 - A - 1 20 SPARE 44
45 SPARE 20 1 - B - 1 20 SPARE 46
47 SPARE 20 1 - C - 1 20 SPARE 48
49 SPARE 20 1 - A - 1 20 SPARE 50
51 SPARE 20 1 - B - 1 20 SPARE 52
53 SPARE 20 1 - C - 1 20 SPARE 54
Connected Demand Demand Connected Load (VA) Panel Options Circuit Breaker Options Load Description Load (VA) Factor Load (VA) Phase A: 8,464 Voltage: 208Y/120V, 3Ø , 4W AFCI Arc Fault Circuit Interrupter Lighting: 1,861 1.25 2,326 Phase B: 8,847 Mains: 150 MCB GFCI GFCI-Personnel (4-6 mA) Receptacles - First 10 kVA: 10,000 1.00 10,000 Phase C: 8,540 Rating: 10K AIC GF-E GFCI-Equipment (30 mA) Receptacles - Over 10 kVA: 8,400 0.50 4,200 Total (VA): 25,851 Minimum Bus Rating: 150A GFP Ground Fault Protection Motors: - 1.00 - Mounting: Surface ST Shunt Trip Largest Motor: - 0.25 - Enclosure Type: NEMA 1 L-ON CB Lock in Closed Position Air Conditioning: 2,590 1.00 2,590 Panel Service Isolated Ground: No L-OFF CB Lock in Open Position Heat Pumps: - 1.00 - Fed From: See Riser Sub-feed Lugs: No TC/TC Timeclock On/Timeclock Off Electric Space Heating: - - - Feeder: See Riser Feed-thru Lugs: No PC/TC Photocell On/Timeclock Off Kitchen: - 1.00 - PC/PC Photocell On/Photocell Off Elevators: - 1.00 - Notes:
Continuous Loads: 1,500 1.25 1,875 * Remove existing 50A, 2P circuit breaker.. See Wire and Conduit Schedule Non-continuous Loads: 1,500 1.00 1,500 ** Remove existing 20A, 2P circuit breaker. for wire and conduit sizes.
Totals (VA): 25,851 22,491 *** Remove existing 30A, 2P circuit breaker.
Total (A): 62 Existing Square D NQOD panelboard.
EXISTING PANEL: RN-7MH-2B PANELBOARD SCHEDULE
Description Circuit Breakers Wire and
Condiut Load (VA)
P ha se Load (VA) Wire and Condiut
Circuit Breakers Description # Trip (A) Poles Options A B C A B C Options Poles Trip (A) #
43 RECEPT C702N 20 1 C2-20 540 A - ETR 20 C708--REPT1 44
45 RECEPT C702M 20 1 C2-20 540 B - ETR 1 20 C707/C708--REPT 46
47 C711--REPT/S 20 1 ETR - C 540 C2-20 1 20 RECEPT C702J 48
49 D707--REPT/S 20 1 ETR - A - ETR 1 20 D710--REPT 50
51 D706/D707--REPT/S 20 1 ETR - B - ETR 20 D711--REPT1 52
53 D706--REPT 20 1 ETR - C - ETR 20 D710--REPT1 54
55 D705--REPT/S 20 1 ETR - A 540 C2-20 1 20 RECEPT C702C 56
57 D711--REPT 20 1 ETR - B 540 C2-20 1 20 RECEPT C702B 58
59 CORRIDOR DOORBELL 20 1 ETR - C - ETR 1 20 D707/D710--REPT 60
61 C703--REPT/Q 20 1 ETR - A - ETR 1 20 C701/C709--REPT, C709--L 62
63 B739--REPT/Q 20 1 ETR - B - ETR 20 D707--REPT1 64
65 D711--REPT 20 1 ETR - C - ETR 1 20 C-WING HALL--REPT 66
67 D712-208V REPT 30 3 ETR - A - ETR 1 20 D710--REPT 68
69 - - B - ETR 1 20 D-WING HALL 70
71 - - C - ETR 1 20 D-WING HALL/D-WING STAIR 72
73 CORRIDOR D & C2-208V REPT 30 2 ETR - A - ETR 20 CORRIDOR C3-208V REPT 742
75 - - B - - 76
77 CORRIDOR C3-208V REPT 30 2 ETR - C - ETR 2 30 EXISTING CIRCUIT 78
79 - - A - - 80
81 RECEPT C702L 20 1 C2-20 540 B - ETR 1 20 EXISTING CIRCUIT 82
83 RECEPT C702K 20 1 C2-20 540 C 540 C2-20 1 20 RECEPT C702A 84
Connected Demand Demand Connected Load (VA) Panel Options Circuit Breaker Options Load Description Load (VA) Factor Load (VA) Phase A: 1,080 Voltage: 208Y/120V, 3Ø , 4W AFCI Arc Fault Circuit Interrupter Lighting: - 1.25 - Phase B: 1,620 Mains: 150A MCB GFCI GFCI-Personnel (4-6 mA) Receptacles - First 10 kVA: 4,320 1.00 4,320 Phase C: 1,620 Rating: 10K AIC GF-E GFCI-Equipment (30 mA) Receptacles - Over 10 kVA: - 0.50 - Total (VA): 4,320 Minimum Bus Rating: 150A GFP Ground Fault Protection Motors: - 1.00 - Mounting: Surface ST Shunt Trip Largest Motor: - 0.25 - Enclosure Type: NEMA 1 L-ON CB Lock in Closed Position Air Conditioning: - - - Panel Service Isolated Ground: No L-OFF CB Lock in Open Position Heat Pumps: - 1.00 - Fed From: See Riser Sub-feed Lugs: No TC/TC Timeclock On/Timeclock Off Electric Space Heating: - 1.00 - Feeder: See Riser Feed-thru Lugs: No PC/TC Photocell On/Timeclock Off Kitchen: - 1.00 - PC/PC Photocell On/Photocell Off Elevators: - 1.00 - Notes:
Continuous Loads: - 1.25 - Existing Square D NQOD panelboard. See Wire and Conduit Schedule Non-continuous Loads: - 1.00 - for wire and conduit sizes.
Totals (VA): 4,320 4,320
Total (A): 12
EXISTING PANEL: RN-7MH-2A PANELBOARD SCHEDULE
Description Circuit Breakers Wire and
Condiut Load (VA)
P ha se Load (VA) Wire and Condiut
Circuit Breakers Description # Trip (A) Poles Options A B C A B C Options Poles Trip (A) #
1 RECEPT C711 20 1 - A 900 C2-20 1 20 RECEPT C710, C709 2
3 RECEPT C711, 710 20 1 - B 500 C2-20 1 20 AUTO FLUSH/FAUCET C702 4
5 D709--REPT/G--L 20 1 ETR - C - ETR 1 20 D703--L, D702/D712--REPT/Q 6
7 D710--REPT/G--L 20 1 ETR - A - ETR 1 20 D705--REPT/G--L 8
9 D711--REPT/G--L 20 1 ETR - B 540 C2-20 1 20 RECEPT C702G, 702H, 702I 10
11 D712--REPT/G--L 20 1 ETR - C - ETR 1 20 D705/D707-REPT/G, D707--L 12
13 D707--REPT/S 20 1 ETR - A 540 C2-20 1 20 RECEPT C702G 14
15 D705--REPT 20 1 ETR - B - ETR 1 20 D709--REPT 16
17 D706--REPT/S 20 1 ETR - C - ETR 1 20 D708--REPT 18
19 D709/D711--REPT/S 20 1 ETR - A 540 C2-20 20 RECEPT C702F1 20
21 D710/D711--REPT/S 20 1 ETR - B 540 C2-20 1 20 RECEPT C702E 22
23 D703--REPT/G 20 1 ETR - C - ETR 1 20 AUTO DOOR 24
25 C715/C717--REPT/G--L 20 1 ETR - A - ETR 1 20 E7.2--REPT 26
27 C717/C713--REPT 20 1 ETR - B - ETR 1 20 C701/C701C--REPT 28
29 C712/C713--REPT 20 1 ETR - C - ETR 1 20 C701B--REPT 30
31 C716/C717--REPT/Q 20 1 ETR - A - ETR 20 C702--REPT/G1 32
33 RECEPT C702I 20 1 C2-20 540 B 540 C2-20 1 20 RECEPT C702D 34
35 D707/D708--REPT/S 20 1 ETR - C - ETR 1 20 C707--REPT 36
37 RECEPT C702H 20 1 C2-20 540 A - ETR 1 20 C712--REPT 38
39 C713--REPT/S 20 1 ETR - B - ETR 1 20 C713--REPT 40
41 C713--REPT/S 20 1 ETR - C - ETR 20 C713--REPT1 42
Connected Demand Demand Connected Load (VA) Panel Options Circuit Breaker Options Load Description Load (VA) Factor Load (VA) Phase A: 2,520 Voltage: 208Y/120V, 3Ø , 4W AFCI Arc Fault Circuit Interrupter Lighting: - 1.25 - Phase B: 2,660 Mains: 150A MCB GFCI GFCI-Personnel (4-6 mA) Receptacles - First 10 kVA: 5,180 1.00 5,180 Phase C: - Rating: 10K AIC GF-E GFCI-Equipment (30 mA) Receptacles - Over 10 kVA: - 0.50 - Total (VA): 5,180 Minimum Bus Rating: 150A GFP Ground Fault Protection Motors: - 1.00 - Mounting: Surface ST Shunt Trip Largest Motor: - 0.25 - Enclosure Type: NEMA 1 L-ON CB Lock in Closed Position Air Conditioning: - - - Panel Service Isolated Ground: No L-OFF CB Lock in Open Position Heat Pumps: - 1.00 - Fed From: See Riser Sub-feed Lugs: No TC/TC Timeclock On/Timeclock Off Electric Space Heating: - 1.00 - Feeder: See Riser Feed-thru Lugs: No PC/TC Photocell On/Timeclock Off Kitchen: - 1.00 - PC/PC Photocell On/Photocell Off Elevators: - 1.00 - Notes:
Continuous Loads: - 1.25 - Existing Square D NQOD panelboard. See Wire and Conduit Schedule Non-continuous Loads: - 1.00 - for wire and conduit sizes.
Totals (VA): 5,180 5,180
Total (A): 14
NEW PANEL: RC-7MH-2 PANELBOARD SCHEDULE
Description Circuit Breakers Wire and
Condiut Load (VA)
P ha se Load (VA) Wire and Condiut
Circuit Breakers Description # Trip (A) Poles Options A B C A B C Options Poles Trip (A) #
1 CHARTING C702 20 1 C2-20 900 A 720 C2-20 1 20 HEADWALL C702I 2
3 RECEPT C708 20 1 C2-20 720 B 720 C2-20 1 20 HEADWALL C702J 4
5 RECEPT C708 20 1 C2-20 720 C 720 C2-20 1 20 HEADWALL C702K 6
7 T7.2--REPT 20 1 ETR - A 720 C2-20 1 20 HEADWALL C702L 8
9 C704/C705--REPT 20 1 ETR - B - ETR 1 20 C705-REPT/Q, T7.2--REPT--L 10
11 T7.2--REPT/S 20 1 ETR - C - ETR 1 20 C701--REPT/Q 12
13 C707--OUTLET STRIP, REPT/C--L 20 1 ETR - A - ETR 1 20 C707/C709--REPT/Q, D708--L 14
15 HEADWALL C702A 20 1 C2-20 720 B 720 C2-20 1 20 HEADWALL C702M 16
17 HEADWALL C702B 20 1 C2-20 720 C 720 C2-20 1 20 HEADWALL C702N 18
19 HEADWALL C702C 20 1 C2-20 720 A 360 C2-20 1 20 PIXIS 20
21 HEADWALL C702D 20 1 C2-20 720 B 360 C2-20 1 20 PIXIS 22
23 HEADWALL C702E 20 1 C2-20 720 C 720 C2-20 1 20 NURSE STATION C708 24
25 HEADWALL C702F 20 1 C2-20 720 A 180 C2-20 1 20 NURSE STATION C708 26
27 HEADWALL C702G 20 1 C2-20 720 B 540 C2-20 1 20 NURSE STATION C708 28
29 HEADWALL C702H 20 1 C2-20 720 C 1,000 C2-20 1 20 REFRIGERATOR 30
31 PREP/RECOVERY C702A-B 20 1 C2-20 720 A 360 C2-20 1 20 RECEPT STORAGE C712 32
33 PREP/RECOVERY C702C-D 20 1 C2-20 720 B 720 C2-20 1 20 RECEPT STORAGE C712 34
35 PREP/RECOVERY C702E-F 20 1 C2-20 720 C 360 C2-20 1 20 CRASH CART 36
37 PREP/RECOVERY C702G-H 20 1 C2-20 720 A 360 C2-20 1 20 CRASH CART 38
39 PREP/RECOVERY C702I-J 20 1 C2-20 720 B 720 C2-20 1 20 PREP/RECOVERY C702K-L 40
41 FIRE SMOKE DAMPER 20 1 C2-20 500 C 720 C2-20 1 20 PREP/RECOVERY C702M-N 42
43 NURSE CALL TERMINAL 20 1 C2-20 500 A - 1 20 LIGHTING 44
45 MED GAS ALARM PANEL 20 1 C2-20 500 B 1,000 C2-20 1 20 REFRIGERATOR 46
47 SPARE 20 1 - C - 1 20 SPARE 48
49 SPARE 20 1 - A - 1 20 SPARE 50
51 SPARE 20 1 - B - 1 20 SPARE 52
53 SPARE 20 1 - C - 1 20 SPARE 54
Connected Demand Demand Connected Load (VA) Panel Options Circuit Breaker Options Load Description Load (VA) Factor Load (VA) Phase A: 6,980 Voltage: 208Y/120V, 3Ø , 4W AFCI Arc Fault Circuit Interrupter Lighting: - 1.25 - Phase B: 9,600 Mains: 100A MCB GFCI GFCI-Personnel (4-6 mA) Receptacles - First 10 kVA: 10,000 1.00 10,000 Phase C: 8,340 Rating: 10K AIC GF-E GFCI-Equipment (30 mA) Receptacles - Over 10 kVA: 13,420 0.50 6,710 Total (VA): 24,920 Minimum Bus Rating: 100A GFP Ground Fault Protection Motors: - 1.00 - Mounting: Surface ST Shunt Trip Largest Motor: - 0.25 - Enclosure Type: NEMA 1 L-ON CB Lock in Closed Position Air Conditioning: - - - Panel Service Isolated Ground: No L-OFF CB Lock in Open Position Heat Pumps: - 1.00 - Fed From: See Riser Sub-feed Lugs: No TC/TC Timeclock On/Timeclock Off Electric Space Heating: - 1.00 - Feeder: See Riser Feed-thru Lugs: No PC/TC Photocell On/Timeclock Off Kitchen: - 1.00 - PC/PC Photocell On/Photocell Off Elevators: - 1.00 - Notes:
Continuous Loads: 1,500 1.25 1,875 See Wire and Conduit Schedule Non-continuous Loads: - 1.00 - for wire and conduit sizes.
Totals (VA): 24,920 18,585
Total (A): 52
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NUMBER DESCRIPTION
LAMPS
VOLTS MOUNTING REMARKS BALLAST/
TRANSFORMER
INPUT
WATTSQty Type
A HE WILLIAMS HETL-GS22-L46-FA-DIM-UNV RECESSED 2'X2' TROFFER, 4600 LUMENS - LED UNV RECESSED ELECTRONIC 52
B HE WILLIAMS HETL-GS24-L93835-FA-DIM-UNV RECESSED 2'X4' TROFFER, 9300 LUMENS,
0-10V DIMMING, GRID CEILING - LED UNV RECESSED ELECTRONIC 92
B1 HE WILLIAMS HETL-FS24-L93835-FA-DIM-UNV RECESSED 2'X4' TROFFER, 9300 LUMENS,
0-10V DIMMING, HARD CEILING - LED UNV RECESSED ELECTRONIC 92
C HE WILLIAMS L45-L11C835-CSM-DIM-120 4.5" DOWNLIGHT, 1000 LUMENS - LED 120 RECESSED ELECTRONIC 15
D HE WILLIAMS AX2WD-2L16835-S-DRV VANITY FIXTURE - LED UNV WALL ELECTRONIC 18
F LILIBEND
LIGHTING LP400 3500K PS048 XT435 FLEXIBLE LED COVE TAPE LIGHT, 430
LUMENS/FOOT LED 24/120 SURFACE- MLV 4.5
W/FT
G SONNEMAN 2622.13 24" LED PENDANT - LED 120 PENDANT ELECTRONIC 20
H HE WILLIAMS HET-G24-L40-ADRV-UNV RECESSED 2'X4' TROFFER, 4000 LUMENS - LED UNV RECESSED ELECTRONIC 41
X BEGHELLI VA4R HT EMERGENCY EXIT SIGN, THERMOPLASTIC - LED UNV SURFACE UNIVERSAL MOUNT NA 3.2
LIGHTING SCHEDULE NOTES:
1. ALL LAMPS SHALL BE 80+ CRI AND 3500K UNLESS NOTED OTHERWISE
SCHEDULE KEY
EXISTING PANEL
RN-7MH-2A
EXISTING PANEL
RN-7MH-2B
EXISTING PANEL
RN-7MH-2C
LIGHTING
FIXTURE
SCHEDULE
EXISTING PANEL
RC-7MH-2
GENERAL NOTES
A. ELECTRICAL CONTRACTOR SHALL TRACE ALL CIRCUITS IN EXISTING
PANELBOARDS PRIOR TO THE START OF DEMOLITION.
B. CONTRACTOR SHALL DEVELOP A NEW PANELBOARD DIRECTORY FOR
PANELS.
C. NEW CIRCUIT BREAKERS SHALL MATCH OR EXCEED EXISTING
PANELBOARD AIC RATINGS.
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
PANEL
RN-7MH-2ARN-7MH-2A
PANEL
RN-7MH-2BRN-7MH-2B
PANEL
RN-7MH-2CRN-7MH-2C
PANEL
LC-7MH-2
PANEL
RC-7MH-2
XFMR
TC-7MH-2
480V~208/120V 45kVA, 3Ø, 4W
XFMR
TN-7MH2
480V~208/120V 45kVA, 3Ø, 4W
TN-7MH2
FEED FROM
BN-MH-E
480V/277V, 3Ø, 3W100AF/
100AT
RN-7MH-2 A-B-C FEED800A, 600V, 3Ø,
4W, BUS DUCT
50,000 RMS SYM
I-LINE II BUSWAY
BY SQUARE D
200AF/
200AT
WIRE TROUGH
TO DC-2MH-A
EMH1R
7TH FLOOR
8TH FLOOR
7TH FLOOR
8TH FLOOR
ELECTRICAL ROOM C713
Scale: N.T.S.1 EXISTING RISER DIAGRAM - ELECTRICAL
COPPER WIRE AND CONDUIT SCHEDULE
Designation Parallel Runs
3 Phase, 4 Wire 3 or 1 Phase, 3 Wire 1 Phase, 2 Wire
Conductors Ground Conduit Conductors Ground Conduit Conductors Ground Conduit
(AWG/kcmil) (AWG/kcmil) (AWG/kcmil) (AWG/kcmil) (AWG/kcmil) (AWG/kcmil) C_-20 1 4 # 12 1 # 12 3/4" 3 # 12 1 # 12 3/4" 2 # 12 1 # 12 3/4" C_-30 1 4 # 10 1 # 10 3/4" 3 # 10 1 # 10 3/4" 2 # 10 1 # 10 3/4" C_-40 1 4 # 8 1 # 10 1" 3 # 8 1 # 10 3/4" 2 # 8 1 # 10 3/4" C_-60 1 4 # 6 1 # 10 1" 3 # 6 1 # 10 1" 2 # 6 1 # 10 1" C_-70 1 4 # 4 1 # 8 1-1/2" 3 # 4 1 # 8 1" 2 # 4 1 # 8 1" C_-90 1 4 # 3 1 # 8 1-1/2" 3 # 3 1 # 8 1-1/2" 2 # 3 1 # 8 1" C_-100 1 4 # 3 1 # 8 1-1/2" 3 # 3 1 # 8 1-1/2" 2 # 3 1 # 8 1" C_-110 1 4 # 2 1 # 6 1-1/2" 3 # 2 1 # 6 1-1/2" 2 # 2 1 # 6 1-1/2" C_-150 1 4 # 1/0 1 # 6 2" 3 # 1/0 1 # 6 1-1/2" 2 # 1/0 1 # 6 1-1/2" C_-175 1 4 # 2/0 1 # 6 2" 3 # 2/0 1 # 6 1-1/2" 2 # 2/0 1 # 6 1-1/2" C_-200 1 4 # 3/0 1 # 6 2" 3 # 3/0 1 # 6 2" 2 # 3/0 1 # 6 2" Notes
1. All conductors indicated in schedule shall be copper.
2. Designation followed with "V" indicates conductor size increased due to voltage drop.
3. Designation followed with "SE" indicates service entrance conductors with no ground.
1. EXISTING 208/120V, 100A MCB, 100A RATED, 3Ø, 4W 30 SPACE SQUARE D
NQOD PNALEBOARD TO BE REMOVED AND REPLACED WITH A NEW
208/120V, 100A MCB, 100A RATED, 3Ø, 4W, 54 SPACE PANELBOARD IN
SAME LOCATION. EXISTING CIRCUITS INDICATED ON PANEL SCHEDULE
TO REMAIN SHALL BE FED FROM NEW PANELBOARD BEING PROVIDED.
EXISTING CIRCUITS SHALL REMAIN OPERATION DURING CONSTRUCTION.
COORDINATE ANY SHUT DOWNS OF THE POWER SOURCE WITH THE VA
COR.
2. DISCONNECT EXISTING FEEDERS AND PREP FOR RECONNECTION TO
NEW PANELBOARD. COORDINATE ANY SHUT DOWNS OF THE POWER
SOURCE WITH THE VA COR.
3. EXISTING 208/120V, 150A MCB, 150A RATED, 3Ø, 4W 42 SPACE SQUARE D
NQOD PNALEBOARD TO BE REMOVED AND REPLACED WITH A NEW
208/120V, 150A MCB, 150A RATED, 3Ø, 4W, 54 SPACE PANELBOARD IN
SAME LOCATION. EXISTING CIRCUITS INDICATED ON PANEL SCHEDULE
TO REMAIN SHALL BE FED FROM NEW PANELBOARD BEING PROVIDED.
EXISTING CIRCUITS SHALL REMAIN OPERATION DURING CONSTRUCTION.
COORDINATE ANY SHUT DOWNS OF THE POWER SOURCE WITH THE VA
COR.
A. ALL ITEMS INDICATED ON THE ELECTRICAL RISER DIAGRAM ARE
EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
X ELECTRICAL RISER KEYNOTES
GENERAL NOTES
7TH FLOOR
8TH FLOOR
7TH FLOOR
8TH FLOOR
Scale: N.T.S.2 COMMUNICATIONS SYSTEM RISER
CORRIDOR
CEILING
IT ROOM T72
X COMMUNICATIONS SYSTEM NOTES
1. SEE EY107 FOR NUMBER OF DEVICES, TYPICAL.
2. 1" EMT CONDUIT TO IT ROOM T72. PROVIDE CAT6 CABLING FROM
OUTLET BOX TO IT ROOM T72 FOR DATA CABLING. PROVIDE CAT6
CABLING FROM OUTLET BOX TO IT ROOM T72 FOR VOICE CABLING. SEE
DRAWING EY107 FOR TYPE AND QUANTITY OF CAT6 CABLING. ALL
CABLING SHALL BE PLENUM RATED. DATA CABLES SHALL HAVE
BLUE/WHITE JACKET. VOICE CABLES SHALL HAVE GRAY JACKET.
3. EXISTING COMMUNICATIONS RACK IN IT ROOM T72.
4. CONTRACTOR SHALL PROVIDE NETWORK RJ45, 48 PORT, CAT6 PATCH
PANELS AS REQUIRED IN EXISTING COMMUNICATIONS RACK FOR DATA
CABLING.
5. CONTRACTOR SHALL PROVIDE NETWORK RJ45, 48 PORT, CAT6 PATCH
PANELS AS REQUIRED IN EXISTING COMMUNICATIONS RACK FOR VOICE
CABLING.
Scale: N.T.S.3 NURSECALL SYSTEM RISER
Scale: N.T.S.4 FIRE ALARM SYSTEM RISER
X NURSECALL SYSTEM NOTES
1. USE 1#18AWG TWISTED SHIELDED PAIR AND MULTICONDUCTOR CABLE
FOR WIRING DEVICES. MINIMUM SIZE CONDUIT SHALL BE 3/4"Ø. FOLLOW
MANUFACTURER RECOMMENDATIONS FOR WIRING AND INSTALLATION,
TYPICAL.
2. NURSECALL EQUIPMENT AND DEVICES SHALL BE RESPONDER V AS
MANUFACTURED BY RAULAND OR APPROVED EQUAL.
3. SEE DRAWING EY107 FOR NUMBER OF DEVICES, TYPICAL.
NCT T BNDND
(TOILET) (BED)
C
(CODE
BLUE)
Z
X FIRE ALARM SYSTEM NOTES
1. EXISTING SIMPLEX FIRE ALARM SYSTEM TERMINAL CABINET . THE FIRE
ALARM SYSTEM PROVIDED FOR THIS PROJECT SHALL BE AN EXTENSION
OF THE EXISTING SIMPLEX FIRE SYSTEM. ALL DEVICES AND APPLIANCES
SHALL BE COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM.
2. SEE DRAWING EY107 FOR QUANTITIES OF DEVICES AND APPLIANCES,
TYPICAL.
3. SUPERVISION CIRCUIT (TSP #14AWG, 3/4"C).
4. SIGNALING LINE CIRCUIT (TSP #14AWG, 3/4"C).
5. POWER CIRCUIT (TSP #14AWG, 3/4"C).
6. EXISTING SIMPLEX FIRE ALARM CONTROL PANEL.SDSD
FIRE ALARM
TERMINAL
CABINET
F
S H
7TH FLOOR
8TH FLOOR
7TH FLOOR
8TH FLOOR
1ST FLOOR 1ST FLOOR
FIRE ALARM
CONTROL
PANEL
(ROOM A139)
R