36C24818R0737-024.pdf
PDF 27 MB Posted
- Attached to
- Project 546-16-104 Renovate Ambulatory Surgery
- Solicitation number
- 36C24818R0737
About this file
36C24818R0737 546-16-104 Final Submittal Drawings_Part1.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24818R0737-0003000.docx | DOCX document | |
| 36C24818R0737-0002000.docx | DOCX document | |
| 36C24818R0737-0002003.pdf | ||
| 36C24818R0737-0002001.pdf | ||
| 36C24818R0737-0002002.pdf | ||
| 36C24818R0737-0001001.pdf | ||
| 36C24818R0737-0001000.docx | DOCX document | |
| 36C24818R0737-026.pdf | ||
| 36C24818R0737-021.pdf | ||
| 36C24818R0737-029.pdf | ||
| 36C24818R0737-023.pdf | ||
| 36C24818R0737-019.docx | DOCX document | |
| 36C24818R0737-020.pdf | ||
| 36C24818R0737-022.pdf | ||
| 36C24818R0737-027.pdf | ||
| 36C24818R0737-025.pdf | ||
| 36C24818R0737-028.pdf | ||
| 36C24818R0737-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAP
IF SHEET MEASURES LESS THAN 30x42 IT IS A
REDUCED PRINT. ADJUST SCALE ACCORDINGLY
RENOVATE AMBULATORY SURGERY
PROJECT NO. 546-16-104
DRAWING
NUMBER DRAWING TITLE
G001 LOCATION, SITE PLAN, AND SHEET INDEX PG107 SEVENTH FLOOR PLAN - MEDICAL GAS
G100 CODE DATA PL701 SEVENTH FLOOR ISOMETRICS - PLUMBING
G200 PHASING PLANS PL702 SEVENTH FLOOR ISOMETRICS - MEDICAL GAS
AD107 DEMOLITION PLAN MH001 SCHEDULES, LEGENDS, AND NOTES - MECHANICAL
A107 SEVENTH FLOOR PLAN MH107 SEVENTH FLOOR PLAN - MECHANICAL HVAC
A127 SEVENTH FLOOR REFLECTED CEILING MP107 SEVENTH FLOOR PLAN - MECHANICAL PIPING
A401 INTERIOR ELEVATIONS MH501 DETAILS - MECHANICAL
A402 INTERIOR ELEVATIONS & DETAILS MH502 DETAILS - MECHANICAL
A511 CASEWORK SECTIONS & DETAILS MH601 CONTROLS - MECHANICAL
A601 DOOR SCHEDULE & DETAILS E001 ELECTRICAL LEGEND, NOTES, AND ABBREVIATIONS
AF107-F FLOOR FINISH PLAN EL107 SEVENTH FLOOR PLAN - ELECTRICAL LIGHTING
AF107-P WALL PROTECTION PLAN EP107 SEVENTH FLOOR PLAN - ELECTRICAL POWER
AF107-W WALL FINISH PLAN EP107.1 SEVENTH FLOOR PLAN - MECHANICAL POWER
AF601 FINISH SCHEDULE EY107 SEVENTH FLOOR PLAN - ELECTRICAL SPECIAL SYSTEMS
IF107-E EQUIPMENT PLAN E501 DETAILS - ELECTRICAL
IF107-S SIGNAGE PLAN E502 DETAILS - ELECTRICAL
IF107-D SIGN DETAILS E601 SCHEDULES - ELECTRICAL
FP107 SEVENTH FLOOR PLAN - FIRE PROTECTION E701 RISER DIAGRAMS - ELECTRICAL
PL001 SCHEDULE, LEGEND, AND NOTES - PLUMBING
PL107 SEVENTH FLOOR PLANS - PLUMBING
PL117 SIXTH AND EIGHTH FLOOR PLAN - PLUMBING
COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
36564 Dale A Bacik, PE
J K P Q R R.4M.3K.8
10.8
J.9
10.5
9.5
8.8
9.8
Prep/Recovery
C702CC
Prep/Recovery C702I
Prep/Recovery
C702HH
Prep/Recovery
C702GC702G
Prep/Recovery C702F
Prep/Recovery C702E
Prep/Recovery
C702DD
Prep/Recovery C702B
Sterile Supply C711
Clean Linen C710
Toilet C705
Prep/Recovery
C702NN
Prep/Recovery
C702MC702M
Prep/Recovery C702L
Prep/Recovery
C702KK
Prep/Recovery C702J
Nurse Manager
C707
Storage C712
Soiled Utility C706
Staff Lounge/ Lockers
B732
Elece
B732AB732
Toilet C703C703
Isolation
C702AA
Nurse Station C708
Toilet C704
HAC
C709
Prep Recovery
Area C702
Stair S7-6
Corridor C7-3-1
Elec
Comm 72T727272Elec
E72 ElecElec
Elec 713713C713713713
CorridorCorrido C7-8-1
CorridoCorridoCorrido
RECOVERY
C709
RECOVERY
C710
PATIENT ROOM
C711
C711A C710A C709A
OUTPATIENT RECOVERY
C707
C707A
Comm T72
Elec E72
Elec C713
LOUNGE
C706
LINEN
C705
PROGRAM MANAGER
C705B
NURSE MANAGER
C704B
ENGINEERING STORAGE
B732
SOILED UTILITY
C702
OFFICE
C703
FOYER
C704
C706AC705A
SUPPLY
C712
Toilet B701
11C7
5A7055A0505A0505
C 117111711
A
AAAAAAA007070 A05055700 A AAAAC
AC711A1C7 A
79392 Ryan E. Morriss, PE
KEY PLAN
COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
1. REMOVE EXISTING FIRE SPRINKLER HEADS
AND ASSOCIATED PIPING IN PROJECT AREA.
A. ALL SERVICE INTERRUPTIONS TO THIS
EXISTING FACILITY MUST BE SCHEDULED AT
LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO
A MINIMUM. COORDINATE ALL DISRUPTIVE
WORK AND OUTAGE REQUIREMENTS WITH THE
COR.
B. EXISTING EQUIPMENT, PIPING, DUCTWORK,
DIFFUSERS, GRILLES, AND ASSOCIATED
COMPONENTS SHOWN ON DRAWINGS ARE
APPROXIMATE LOCATIONS AND IS PROVIDED
FOR REFERENCE USE ONLY. FIELD VERIFY
AND COORDINATE WITH EXACT LOCATIONS,
ELEVATIONS, SIZES, AND CONDITIONS OF
EXISTING COMPONENTS.
C. PHASE BOUNDARIES ON DRAWINGS INDICATE
ROOMS TO BE COMPLETED FOR EACH PHASE.
PERFORM ASSOCIATED WORK AS NECESSARY
TO COMPLETE EACH PHASE.
XX GENERAL NOTESDEMOLITION KEYNOTES
Scale: 1/8" = 1'-0"1 SEVENTH FLOOR RENOVATION PLAN - FIRE PROTECTION
Scale: 1/8" = 1'-0"2 SEVENTH FLOOR DEMOLITION PLAN - FIRE PROTECTION
FIRE SPRINKLER LEGEND
SYMBOL DESCRIPTION
EXISTING PENDENT TO BE REMOVED
• ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS
OF THE FLORIDA 2014 BUILDING CODE 5TH EDITION, FLORIDA FIRE
PREVENTION CODE 2014 5TH EDITION, LATEST APPROVED EDITION
NFPA FIRE CODES, AND APPLICABLE OSHA AND EPA REGULATIONS
AND GUIDELINES. WHERE CONFLICTS BETWEEN CODE AND
CONSTRUCTION DOCUMENTS OCCUR, THE MOST RESTRICTIVE
REQUIREMENTS SHALL GOVERN.
• THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION
AND PLANS FOR REVIEW ACCORDING TO NFPA 1 (2015 EDITION),
SECTION 1.14.
• A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE
COMPLETED IN ACCORDANCE WITH NFPA 13 AND FORWARDED TO
THE OWNER'S REPRESENTATIVE.
• ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK
SHALL BE DONE IN A THOROUGH AND WORKMANLIKE MANNER. THE
WORK, MATERIALS AND TEST SHALL BE IN ACCORDANCE WITH THE
CURRENT REQUIREMENTS OF NFPA 13, LATEST EDITION.
• MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS,
PARTITIONS, CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL
PENETRATIONS THROUGH RATED ASSEMBLIES WITH FIRESTOP
MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS TO MAINTAIN
THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS
FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO
PENETRATION DETAILS FOR FIRE PROTECTION PIPING
PENETRATIONS THROUGH RATED ASSEMBLIES.
• FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION
OF RISERS, CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS
WITH ALL OTHER TRADE SYSTEMS TO AVOID CONFLICTS AND
MAINTAIN ARCHITECTURAL ELEMENTS OF THE BUILDING.
• PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO
NFPA 13 (2010 EDITION).
• ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM,
UNLESS OTHERWISE NOTED.
• INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING,
AND OBSTRUCTION REQUIREMENTS.
• COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH
ARCHITECTURAL FINISHES, CEILING, LIGHTING LAYOUT, HVAC
DUCTS, OTHER CEILING MOUNTED DEVICES, AND STRUCTURAL
COMPONENTS.
• LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD
ADDITIONAL SPRINKLERS AT NO ADDITIONAL COST AND AS
NECESSARY TO MEET COVERAGE REQUIREMENTS IN ACCORDANCE
WITH NFPA 13.
• INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN
POSSIBLE. PROVIDE RETURN BENDS AT ALL SPRINKLER LOCATIONS
TO ALLOW FIELD ADJUSTMENT.
• THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL
CONFORM TO THE REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL
BE INSTALLED BY PERSONNEL WHO HAVE ENGINEERING FACILITIES
AND EXPERIENCE IN SUCH WORK AND WHO ARE REGULARLY
EMPLOYED TO DO SUCH WORK.
• PIPE SUPPORTS: HANGERS, CLAMPS, RODS AND OTHER
ACCESSORIES OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER
TO PROPERLY SUPPORT ALL PIPING SHALL BE FURNISHED AND
INSTALLED. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT
U-TYPE APPROVED ADJUSTABLE HANGERS.
• SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE
RATING EXCEPT WHERE EXCESSIVE TEMPERATURES ARE
ANTICIPATED. IN THESE LOCATIONS HIGH TEMPERATURE
SPRINKLERS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA NO.
13. PROVIDE QUICK RESPONSE SPRINKLERS IN LIGHT HAZARD
AREAS.
FIRE SPRINKLER PROVISIONS
1. SPRINKLER HEADS AND ASSOCIATED
COMPONENTS ARE TO BE SIZED, LOCATED,
AND PROVIDED ACCORDING TO NFPA 13.
XX RENOVATION KEYNOTES
FOR HEAD TYPES
SEE FLOOR PLANS
1" X 1/2" R.C.
DROP
90 EL.
ARMOVER
RISER NIPPLE
BRANCHLINE
SUSPENDED CEILING
EQ.EQ.EQ.EQ. EQ.EQ.
EQ. EQ.
E Q
. E Q
EQ. EQ.
SPRINKLER
SPEAKER OR
OTHER DEVICE
AIR DEVICE OR
LIGHT FIXTURE
CEILING LEGEND
SPRINKLER MOUNTING DETAIL
NTS4 SWING ARM ASSEMBLY DETAIL
NTS3
E Q
. E Q
E Q
. E Q
E Q
. E Q
E Q
. E Q
SPRINKLERS IN GRID CEILING SYSTEMS
SHALL BE LOCATED AT THE MIDPOINT
OR QUARTERPOINT OF THE FOUR FOOT
(4') DIMENSION AND THE MIDPOINT OF
THE TWO (2') DIMENSION. WHERE A
CONFLICT OCCURS, SYMMETRY ABOUT
THE AXIS SHALL BE MAINTAINED.
TYP.
TYP.
SEMI RECESSED PENDENT SPRINKLER, STANDARD COVERAGE,
QUICK RESPONSE, 155°F, FM APPROVED, UL LISTED
79392 Ryan E. Morriss, PE
COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
WATER CLOSET, BARRIER FREE - AMERICAN STANDARD 3351.101, OR EQUIVALENT;
BACK OUTLET, WALL MOUNTED, 18" HIGH, ELONGATED RIM, 1-1/2" TOP SPUD,
VITREOUS CHINA, 1.28 GPF SENSOR FLUSH VALVE, SIPHON JET FLUSHING ACTION,
OPEN FRONT SEAT LESS COVER, STAINLESS STEEL CHECK HINGE. 1"CW, 4" SAN.
SEE SPECIFICATIONS.
LAVATORY, BARRIER FREE - AMERICAN STANDARD LUCERNE NO. 0355.041 OR
EQUIVALENT, 20X18" VITREOUS CHINA, WALL HUNG, SINGLE HOLE, GRID DRAIN
ASSEMBLY. PROVIDE FLOOR CARRIER WITH CONCEALED ARMS. TOP OF FRONT
RIM MOUNTED 34" FROM FINISHED FLOOR. PROVIDE DECK MOUNTED GOOSENECK
SENSOR FAUCET WITH AUTOMATIC HYGIENE FLUSH, CHICAGO FAUCETS
116.597.AB.1 OR EQUIVALENT; WITH 5-1/4" GOOSENECK SPOUT, DUAL SUPPLY.
PROVIDE UNDER SINK THERMOSTATIC MIXING VALVE, WATTS MODEL LFUSG-B-M2;
ASSE 1070 COMPLIANT, LEAD FREE, BRASS BODY, WITH DUAL CHECK VALVES,
INTEGRAL STRAINER WITH STAINLESS STEEL SCREENS, AND TAMPER RESISTANT
LOCKING NUT; SET TO 110°F. PROVIDE STOPS, SUPPLIES, TRAP, ETC., TO MAKE A
COMPLETE INSTALLATION. PROTECT TRAP AND SUPPLIES WITH TRUEBRO NO.
2018-xx-x LAV SHIELD. 1/2" CW, 1/2" HW, 1-1/4" SAN.
SINK - DOUBLE COMPARTMENT, COUNTER TOP ASME A119.19.3, KITCHEN SINK,
33"x22", 7-1/2" DEEP, WITH 8" GOOSNECK SPOUT FAUCET. PROVIDE STOPS, SUPPLIES, TRAP, ETC., TO COMPLETE INSTALLATION. 1/2" CW, 1/2" HW, 1-1/2" SAN.
SEE SPECIFICATIONS.
SINK - ZURN MODEL NO. Z5410, WALL MOUNT BLOWOUT SINK, 21-1/2"X19", WITH
ZURN CLINICAL SERVICE SINK FAUCET. 1"CW FOR BLOWOUT. 1/2"CW, 1/2"HW, 4"
SAN.
SINK- SINGLE COMPARTMENT, COUNTER TOP ASME A119.19.3, KITCHEN SINK,
16"X20", WITH 8" GOOSENECK SPOUT FAUCET. PROVIDE STOPS, SUPPLIES, TRAP,
ETC. TO COMPLETE INSTALLATION. 1/2"CW, 1/2"HW, 3" SAN.
MOP SINK - FIAT, NO. TSBC6000; 24X24" NEO-CORNER TERRAZZO SERVICE BASIN,
12" DEEP, COMBINATION DOME STRAINER AND LINT BASKET. FIAT NO. 830-AA
SERVICE SINK FAUCET WITH VACUUM BREAKER. PROVIDE WITH HOSE AND HOSE
HOOK, MOP BRACKET, 1/2" CW, 1/2" HW, 3" SAN.
WATER HAMMER ARRESTOR - ZURN SHOCKTROL Z-1700, OR EQUIVALENT. INSTALL
AT HIGH END OF EACH BRANCH THAT CONTAINS QUICK-CLOSING OR FLUSH
VALVES.
FLOOR DRAIN - ZURN Z-415S-P WITH TYPE "S" 5X5" NICKEL FINISH. DURA COATED
CAST IRON BODY WITH TRAP PRIMER CONNECTION. SIZE TO PIPE SIZE.
WALL CLEAN OUT - ZURN NO. CO2411/CO2530-SS7, SMOOTH STAINLESS STEEL
ACCESS COVER, PVC PLUG AND BODY. SIZE TO PIPE SIZE.
ICE BOX - WATER-TITE 9700HA, ICE MAKER BOX WITH ARRESTER, SOLDER
CONNECTION, ROUGH-IN AND MAKE COLD WATER CONNECTION, 4'-0" A.F.F., WALL
BOX W/ 3/8" ANGLE STOP. 3/8" CW
PLUMBING FIXTURES
WC-1
LAV-1
S-1
S-2
S-3
SS-1
WHA
FD-1
WCO
IB-1
PLUMBING LEGEND
PIPE UP
PIPE DOWN
VENT THRU ROOF
EQUIPMENT OR FIXTURE MARK
POINT OF NEW CONNECTION
DRAWING KEYNOTE
FLOOR DRAIN
BALL VALVE
CHECK VALVE
GATE VALVE
STRAINER
UNION
WALL CLEAN OUT
FLOOR CLEAN OUT
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER PIPING
DOMESTIC HOT WATER RETURN PIPING
SANITARY, SOIL, OR WASTE PIPING
EXISTING DOMESTIC COLD WATER PIPING
EXISTING DOMESTIC HOT WATER RETURN PIPING
EXISTING DOMESTIC HOT WATER PIPING
EXISTING PIPING TO BE REMOVED
EXISTING SANITARY, SOIL, OR WASTE PIPING
SANITARY VENT PIPING
OR
WCO
POINT OF DEMOLITION LIMIT
V
SAN
DHWR
DHW
DCW
(E)DCW
(E)DHWR
(E)DHW
(E)SAN
VTR
FCO
WCO
00000000
ZONE VALVE BOX - AMICO ALERT-1 SERIES MODEL ZIU-PX, ZONE VALVE
BOX, PROVIDE WITH GAS SHUTOFF VALVES.
MASTER AREA ALARM PANEL - AMICO ALERT-2 SERIES MODEL A2M-E-20.
AREA ALARM PANEL REMOTE SENSORS
AMICO MEDAES, PIN INDEX, WALL OUTLET; 1-OXYGEN, 1-AIR, 1-VACUUM.
CONTRACTOR SHALL VERIFY WALL OUTLET IS LOCATED ON HEADWALL,
REFER TO ARCHITECTURAL PLANS FOR MORE INFORMATION.
AMICO HI/LOW OXYGEN PRESSURE SWITCH MODEL# M-PRSW-OXY.
AMICO HI/LOW MEDICAL AIR PRESSURE SWITCH MODEL# M-PRSW-AIR.
AMICO HI/LOW VACUUM PRESSURE SWITCH MODEL# M-PRSW-VAC.
AMICO 3/4" SOURCE VALVE WITH LOCKING HANDLE MODEL# VV-ISO-GL-07.
AMICO 3/4" MEDICAL AIR COMPRESSOR SOURCE VALVE WITH LOCKING
HANDLE MODEL# VV-ISO-GL-07.
AMICO 1" MEDICAL VACUUM PUMP SOURCE VALVE WITH LOCKING
HANDLE MODEL# VV-ISO-GL-10.
MEDICAL GAS FIXTURES
ZVB
AAP
AS
MGO-1
"A"
"B"
"C"
"D"
"E"
"F"
(E) EXISTING
AFF ABOVE FINISHED FLOOR
BFF BELOW FINISHED FLOOR
BV BALL VALVE
CO PIPE CLEANOUT
CO2 CARBON DIOXIDE
COR CONTRACTING OFFICER'S REPRESENTATIVE
CRS CORROSION-RESISTANT STEEL
CTE CONNECT TO EXISTING
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DEMO DEMOLISH OR DEMOLITION
DFU DRAINAGE FIXTURE UNITS
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EX EXISTING
FBC FLORIDA BUILDING CODE
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
GPM GALLONS PER MINUTE
IBC INTERNATIONAL BUILDING CODE
IE INVERT ELEVATION
LAV LAVATORY
MA MEDICAL AIR
MS MOP SINK
MV MEDICAL VACUUM
N NITROGEN
N2O NITROUS OXIDE
NC NORMALLY CLOSED
NO NORMALLY OPEN
O OXYGEN
SAN SANITARY, SOIL, OR WASTE
UNO UNLESS NOTED OTHERWISE
V VENT
VTR VENT THROUGH ROOF
WAG WASTE ANESTHETIC GAS
WC WATER CLOSET
WCO WALL CLEAN OUT
WSFU WATER SUPPLY FIXTURE UNITS
ABBREVIATIONS
1. MEDICAL GAS SYSTEMS SHALL BE FURNISHED, INSTALLED, AND TESTED IN STRICT
ACCORDANCE WITH NFPA 99, 2018 EDITION.
2. INSTALLATION AND TERMINATIONS OF ALL LOW VOLTAGE AREA ALARM WIRING AND
CONDUIT PER NFPA 99 BY PLUMBING MEDICAL GAS CONTRACTOR.
3. PLUMBING CONTRACTOR TO SUPPLY THE REQUIRED NUMBER OF VACUUM
REGULATORS, OXYGEN FLOW METERS MEDICAL AIR FLOW METERS AS PART OF
MEDICAL GAS EQUIPMENT PACKAGE.
4. PROVIDE MEDICAL GAS PIPE LABELS IN COMPLIANCE WITH NFPA 99, AND AT
LOCATIONS INCLUDING BUT NOT LIMITED TO: AT INTERVALS OF NOT MORE THAN 20
FT., AT LEAST ONCE WITHIN EACH SPACE, AND ON BOTH SIDES OF EVERY WALL AND
FLOOR SLAB PENETRATION. MEDICAL GAS PIPING SHALL BE IDENTIFIABLE BY
APPROPRIATE LABELING WITH NAME OF GAS CONTAINED.
5. CONTRACTOR TO FIELD VERIFY LOCATION OF EXISTING OXYGEN AIR AND VACUUM
PIPING AND ADJUST PIPING LAYOUT TO ACCOMMODATE CONNECTIONS.
6. CONTRACTOR SHALL INCLUDE THE COST OF THE SYSTEM FUNCTIONAL TEST TO HIS
FEE.
7. EXISTING MEDICAL GAS SYSTEMS MUST BE KEPT IN SERVICE AT ALL TIMES DURING
CONSTRUCTION OF THE NEW SYSTEMS. THE FINAL CONNECTIONS OF THE NEW
SYSTEMS TO THE EXISTING MEDICAL GAS SYSTEMS SHALL BE COORDINATED WITH
THE OWNER'S OPERATIONS AND SHALL BE MADE AFTER HOURS OF THE OWNERS
OPERATIONS SO AS NOT TO PRESENT ANY DISRUPTION TO THE OWNER'S
OPERATIONS.
8. ALL TESTING OF THE NEW SYSTEMS AND PIPING SHALL BE DONE PRIOR TO THE
FINAL MEDICAL GAS PIPE CONNECTIONS TO THE EXISTING PIPING AND SHALL BE
RETESTED AFTER THE FINAL CONNECTION AS WARRANTED.
MEDICAL GAS NOTES
DOMESTIC WATER PIPING:
• HOT AND COLD WATER PIPING SHALL BE TYPE L HARD COPPER PIPING WITH
ASSOCIATED WROUGHT COPPER FITTINGS. ISOLATION VALVES SHALL BE TWO-PIECE
BALL VALVES WITH STAINLESS STEEL TRIM AND FULL PORT CONFIGURATION.
• ALL HORIZONTAL PIPING PENETRATIONS SHALL BE PROVIDED WITH ESCUTCHEONS
TO PROVIDE A CLEAN INSTALLATION.
• PIPING PENETRATIONS THROUGH BUILDINGS STRUCTURE SHALL BE UL RATED AND
FIRESTOPPED, WHERE REQUIRED.
MEDICAL GAS SYSTEMS:
• AN AREA ALARM PANEL SHALL BE PROVIDED IN RECOVERY AS INDICATED, WITH GAS
SPECIFIC SYSTEM PRESSURE READINGS.
• MEDICAL GASES SHALL BE DISTRIBUTED THROUGH PIPING TO ZONE VALVE BOXES.
ALL VALVES SHALL BE THREE PIECE BALL TYPE WITH BLOW-OUT PROOF STEMS,
LOCKING HANDLES AND FULL PORT DESIGN.
• FROM ZONE VALVE BOXES, MEDICAL GASES SHALL BE DISTRIBUTED TO MEET THE
SPACE REQUIREMENTS.
• ALL MEDICAL GAS PIPING SHALL BE PRECLEANED, TYPE K, ASTM B 819, HARD DRAWN,
SEAMLESS COPPER TUBING WITH BRAZED WROUGHT COPPER FITTINGS, ASTM B16.22
OR MSS SP-73; FACTORY CLEANED, PURGED, AND SEALED FOR MEDICAL GAS
SERVICE. STORE PRECLEANED AND SEALED MEDICAL GAS PIPE, FITTINGS, VALVES,
AND SPECIALTIES WITH SEALING PLUGS AND SEALING PACKAGING INTACT.
• LABEL MEDICAL GAS PIPE, FITTINGS, VALVES, AND SPECIALTIES THAT HAVE NOT
BEEN PRECLEANED, OR THAT HAVE BEEN PRECLEANED BUT HAVE SEAL OR
PACKAGING THAT IS NOT INTACT, WITH TEMPORARY LABELS INDICATING THAT
CLEANING IS REQUIRED BEFORE INSTALLATION.
MISCELLANEOUS:
• HANGERS: FOR CAST IRON, PROVIDE HEAVY DUTY PIPE HANGERS, BRACKETS OR
CLAMPS AT 5' INTERVALS. ALL MATERIAL SHALL BE NON-FERROUS AND
NON-CORRODING. FASTEN WITH LAG SCREW OR WITH EXPANSION SHIELDS AS
APPLICABLE. FOR WATER PIPING, PROVIDE ADJUSTABLE COPPER PLATED HANGERS
AT 6' INTERVALS MAXIMUM. PROVIDE HANGERS TO ALLOW FOR FULL THICKNESS OF
INSULATION.
• VALVES AND SHUTOFFS: FULL SIZE BRONZE GATE OR BALL VALVES FOR HOT AND
COLD WATER MAINS, STANDARD PORT BRONZE BALL VALVES FOR HOT AND COLD
WATER BRANCHES. PROVIDE DRAINAGE VALVES ON MAINS. PROVIDE UNITS BY
APOLLO, GRINNELL, HAMMOND, MILWAUKEE, LUNKENHEIMER, OR WATTS. ALL
VALVES SHALL BE MANUFACTURED IN THE U.S. USE OF IMPORTS IS PROHIBITED.
• INSTALL SHUTOFF VALVES ON EACH PIECE OF EQUIPMENT.
• CLEARLY LABEL ALL VALVES AND COMPONENTS. ALL PIPING SYSTEMS AND FLOW
DIRECTION SHALL BE CLEARLY LABELED WITH COMMERCIAL PIPE LABELING DEVICES.
• DISINFECT DOMESTIC WATER DISTRIBUTION SYSTEM. FLUSH AND TEST ALL SYSTEMS
FOR PROPER OPERATION. ADJUST SYSTEM TO PREVENT WATER HAMMER.
• MAINTAIN INDICATED FIRE RATINGS OF WALLS, PARTITIONS, CEILINGS AND FLOORS
AT PENETRATIONS. SEAL WITH FIRESTOPPING TO MAINTAIN FIRE RATING.
• RESTORE DAMAGED FINISHES. CLEAN AND PROTECT WORK FROM DAMAGE.
• INSTRUCT OWNER'S PERSONNEL IN PROPER OPERATION OF SYSTEMS.
PLUMBING DESIGN PROVISIONS
1. ALL WORK SHALL COMPLY WITH APPLICABLE NATIONAL, STATE, AND LOCAL CODES. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, THE 2014 FLORIDA PLUMBING CODE. WHERE CONFLICTS OCCUR BETWEEN CODES, OR BETWEEN CONSTRUCTION DOCUMENTS AND CODES, THE MOST RESTRICTIVE REQUIREMENTS SHALL GOVERN.
2. REVIEW PLANS OF ALL TRADES PRIOR TO BIDDING AND BEGINNING WORK. INSTALLATIONS ARE TO INCLUDE ALL
PLUMBING FOR COMPLETE SYSTEMS SHOWN ON THE PLANS AND AS REQUIRED.
3. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC DUCTS, STRUCTURE, ELECTRICAL, LIGHTING, AND OTHER PIPING IN THE CEILING SPACE. VENT PIPING AND WATER PIPING SHALL BE HELD EITHER ABOVE
OR BELOW HVAC DUCTWORK, AS COORDINATED WITH THE HVAC CONTRACTOR.
4. ALL CHANGES SHALL BE REVIEWED BY THE ARCHITECT.
5. COORDINATE WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING-IN PLUMBING FIXTURES AND EQUIPMENT
SUPPLIES.
6. THE PLUMBING SUBCONTRACTOR SHALL FURNISH AND INSTALL ALL PLUMBING FIXTURES, UNLESS NOTED OTHERWISE.
7. VERIFY MOUNTING HEIGHT AND WATER CONNECTION SIZES OF ALL PLUMBING FIXTURES PRIOR TO ROUGH-IN. FURNISH CUT-OUT TEMPLATES, FOR PLUMBING FIXTURES TO BE INSTALLED IN MILLWORK, TO THE GENERAL CONTRACTOR.
8. MAKE PROPER HOT AND COLD WATER, WASTE AND VENT PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT
EVEN THOUGH ALL FITTINGS AND CONNECTIONS ARE NOT SHOWN.
9. VERIFY LOCATION OF EXISTING WATER SERVICE AND THE LOCATION/INVERTS OF SANITARY PIPING PRIOR TO
INSTALLATION.
10. CUT AND PATCH CONCRETE AS REQUIRED.
11. IT IS NOT THE INTENT OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THESE DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY THE ARCHITECT) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AS PART OF
HIS TOTAL WORK.
12. THE EQUIPMENT ROUGH-IN ITEMS AND THEIR DIMENSIONED LOCATIONS FOR ALL CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE. IN SOME INSTANCES THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR EQUIPMENT ITEMS MAY VARY FROM WHAT IS SHOWN. THEREFORE, THESE ITEMS AND DIMENSIONS SHALL BE VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR EQUIPMENT ROUGH-IN DRAWING. FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH-INS OR THEIR LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION
AND/OR ADDITIONAL ROUGH-INS DIRECTLY UPON THAT CONTRACTOR.
13. CONTRACTOR SHALL SUPPLY TO THE ARCHITECT/ENGINEER THE REQUIRED COPIES OF SHOP DRAWINGS FOR APPROVAL SO THE QUALITY OF INTENDED MATERIALS OR EQUIPMENT CAN BE REVIEWED BEFORE INSTALLATION.
THERE WILL BE NO DRAW UNTIL SHOP DRAWINGS HAVE BEEN SUBMITTED AND REVIEWED BY THE
ARCHITECT/ENGINEER.
14. DO NOT SCALE THIS DRAWING. REFER TO ARCHITECTURAL FLOOR PLAN FOR BUILDING DIMENSIONS.
15. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW ALL ELBOWS, OFFSETS, UNIONS, VALVES, FITTINGS, ETC. REQUIRED TO COMPLETE THE INSTALLATION OF THE WORK. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF WITH THE PLANS AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY COULD HAVE BEEN FORESEEN HAD PROPER EXAMINATION BEEN
MADE.
16. THE CONTRACTOR SHALL COOPERATE FULLY AMONG THE TRADES.
17. THE POTABLE WATER SUPPLY SHALL BE PROTECTED AGAINST BACKFLOW AND SIPHONAGE, BOTH NATURAL AND INDUCED. ALL EQUIPMENT CONNECTED TO THE POTABLE WATER SYSTEM BEING CAPABLE OF POLLUTING OR CONTAMINATING THE POTABLE WATER DISTRIBUTION SYSTEM OR ANY PART THEREOF BY MEANS OF A REVERSAL OF FLOW, PRESSURE DROP, PRESSURE LOSS, INDUCED VACUUM, OR BY INJECTION BECAUSE OF ANY PRIMARY OR AUXILIARY PUMPING SYSTEM CONNECTED, MUST BE ISOLATED AND CONTAINED BY MEANS OF APPROVED BACKFLOW DEVICES, CHECK VALVES, AIR GAPS, OR VACUUM BREAKERS. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL
THESE DEVICES PER LOCAL CODE REQUIREMENTS.
18. THE WATER PIPING SYSTEM SHALL BE FLUSHED AND STERILIZED IN ACCORDANCE WITH LOCAL REGULATIONS.
19. HOT AND COLD WATER SUPPLY BRANCHES FOR ALL SYSTEMS HAVING QUICK CLOSING VALVES OF ANY TYPE SHALL HAVE WATER HAMMER ARRESTORS INSTALLED AT THE HIGH POINT ON THE END OF EACH BRANCH.
20. FURNISH AND INSTALL SHUTOFF BALL VALVE AND DIELECTRIC UNIONS FOR ALL EQUIPMENT HOT AND COLD WATER LINES. PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO EQUIPMENT. COORDINATE WITH EQUIPMENT
SUPPLIER FOR EXACT REQUIREMENTS.
21. VERIFY MOUNTING HEIGHTS OF ALL BARRIER FREE FIXTURES WITH ARCHITECTURAL PLANS.
22. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL COPPER INDIRECT WASTE PIPING REQUIRED FROM EQUIPMENT TO FLOOR DRAINS. PIPING SHALL COMPLY WITH FEDERAL, STATE AND LOCAL CODES. COORDINATE WITH ALL EQUIPMENT SUPPLIERS AND SIZES AS REQUIRED BY PIECE OF EQUIPMENT SERVED. HOLD PIPING TIGHT TO WALL WHERE APPLICABLE. PROPERLY SECURE AS REQUIRED. COORDINATE WITH CASEWORK SUPPLIER FOR MAXIMUM
CLEARANCE UNDER CABINETS.
23. PROVIDE CHROME PLATED ESCUTCHEONS AT ALL WALL PENETRATIONS.
24. PLUMBING CONTRACTOR SHALL INSTALL 4" SOIL AND WASTE PIPING WITH MINIMUM SLOPE OF 1/8" PER FOOT UNLESS
OTHERWISE REQUIRED.
25. ALL FLOOR DRAINS ARE TO BE PROVIDED WITH MINIMUM 3" DRAIN LINES, DEEP SEAL TRAPS, AND AUTOMATIC TRAP PRIMERS. TRAP PRIMERS SHALL BE LOCATED IN A SERVICEABLE LOCATION AND INSTALLED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. HOLD TOP OF FLOOR DRAINS FLUSH WITH FINISHED FLOOR; SEE ARCHITECTURAL
SHEETS FOR FLOOR SLOPES AND PROPER FINISHED FLOOR ELEVATION.
26. ALL VENT PIPE TO BE COMPATIBLE WITH STRUCTURE, MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL EQUIPMENT, AND LIGHTING. ALL V.T.R.'S SHALL BE EXTENDED TO A MINIMUM OF 2" ABOVE PARAPET HEIGHT AND MAINTAINED 10'-0"
MINIMUM FROM ALL OUTSIDE AIR INTAKES.
27. MATERIALS, EQUIPMENT, ASSEMBLIES AND SYSTEMS SHALL MEET ALL PERTINENT REQUIREMENTS OF NATIONALLY RECOGNIZED TESTING ORGANIZATIONS SUCH AS UL, ASTM, ASSE, AWWE, AGA AND NFPA AS WELL AS THE MOST
CURRENT VERSION OF THE STATE AND LOCAL CODES.
28. ALL INSTALLED SYSTEMS, DEVICES AND RELATED ITEMS SHALL BE TESTED IN PLACE. REPLACE ANY AND ALL CONTRACTOR SUPPLIED DEFECTIVE DEVICES, ITEMS, OR SYSTEMS AT CONTRACTOR'S EXPENSE, BEFORE COMPLETION
OF PROJECT.
29. WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS THAT DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE
OWNER. NO OTHER CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION OF THE ENGINEER.
30. ALL EQUIPMENT, FIXTURES AND MATERIALS SHALL BE NEW AND UNUSED, AND INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS (UNO). PROVIDE COMPLETE WITH ALL TRIM, STOPS, HANGERS, CARRIERS, SUPPORTS, ETC., INCLUDING PROVISIONS FOR BARRIER FREE USE, IF REQUIRED. WHERE FIXTURES ARE ACCESSIBLE
THEY MUST COMPLY WITH ALL FEDERAL A.D.A. REGULATIONS.
31. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE FURNISHED, FABRICATED, FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED, AND ALL WORK IN CONNECTION WITH INSTALLATION OF MANUFACTURER'S GUARANTEED EQUIPMENT. THE CONTRACTOR'S GUARANTEE SHALL LAST ONE YEAR FROM THE FINAL OWNER ACCEPTANCE OF THE WORK AND SHALL APPLY TO ALL
DEFECTS IN MATERIALS AND WORKMANSHIP OF ANY KIND.
32. ALL FAUCET CONTROLS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRE TIGHTGRASPING.
33. ALL BARRIER FREE WATER CLOSET CONTROLS SHALL BE LOCATED ON UNIT TOWARDS WIDE SIDE OF STALL. VERIFY IF
RIGHT OR LEFT SIDE LOCATION.
PLUMBING NOTES