36C24818R0737-024.pdf

PDF 27 MB Posted

Attached to
Project 546-16-104 Renovate Ambulatory Surgery
Solicitation number
36C24818R0737
Issued by

About this file

36C24818R0737 546-16-104 Final Submittal Drawings_Part1.pdf

View the file

Other files

File Type Posted
36C24818R0737-0003000.docx DOCX document
36C24818R0737-0002000.docx DOCX document
36C24818R0737-0002003.pdf PDF
36C24818R0737-0002001.pdf PDF
36C24818R0737-0002002.pdf PDF
36C24818R0737-0001001.pdf PDF
36C24818R0737-0001000.docx DOCX document
36C24818R0737-026.pdf PDF
36C24818R0737-021.pdf PDF
36C24818R0737-029.pdf PDF
36C24818R0737-023.pdf PDF
36C24818R0737-019.docx DOCX document
36C24818R0737-020.pdf PDF
36C24818R0737-022.pdf PDF
36C24818R0737-027.pdf PDF
36C24818R0737-025.pdf PDF
36C24818R0737-028.pdf PDF
36C24818R0737-000.docx DOCX document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOCATION MAP

IF SHEET MEASURES LESS THAN 30x42 IT IS A

REDUCED PRINT. ADJUST SCALE ACCORDINGLY

RENOVATE AMBULATORY SURGERY

PROJECT NO. 546-16-104

DRAWING

NUMBER DRAWING TITLE

G001 LOCATION, SITE PLAN, AND SHEET INDEX PG107 SEVENTH FLOOR PLAN - MEDICAL GAS

G100 CODE DATA PL701 SEVENTH FLOOR ISOMETRICS - PLUMBING

G200 PHASING PLANS PL702 SEVENTH FLOOR ISOMETRICS - MEDICAL GAS

AD107 DEMOLITION PLAN MH001 SCHEDULES, LEGENDS, AND NOTES - MECHANICAL

A107 SEVENTH FLOOR PLAN MH107 SEVENTH FLOOR PLAN - MECHANICAL HVAC

A127 SEVENTH FLOOR REFLECTED CEILING MP107 SEVENTH FLOOR PLAN - MECHANICAL PIPING

A401 INTERIOR ELEVATIONS MH501 DETAILS - MECHANICAL

A402 INTERIOR ELEVATIONS & DETAILS MH502 DETAILS - MECHANICAL

A511 CASEWORK SECTIONS & DETAILS MH601 CONTROLS - MECHANICAL

A601 DOOR SCHEDULE & DETAILS E001 ELECTRICAL LEGEND, NOTES, AND ABBREVIATIONS

AF107-F FLOOR FINISH PLAN EL107 SEVENTH FLOOR PLAN - ELECTRICAL LIGHTING

AF107-P WALL PROTECTION PLAN EP107 SEVENTH FLOOR PLAN - ELECTRICAL POWER

AF107-W WALL FINISH PLAN EP107.1 SEVENTH FLOOR PLAN - MECHANICAL POWER

AF601 FINISH SCHEDULE EY107 SEVENTH FLOOR PLAN - ELECTRICAL SPECIAL SYSTEMS

IF107-E EQUIPMENT PLAN E501 DETAILS - ELECTRICAL

IF107-S SIGNAGE PLAN E502 DETAILS - ELECTRICAL

IF107-D SIGN DETAILS E601 SCHEDULES - ELECTRICAL

FP107 SEVENTH FLOOR PLAN - FIRE PROTECTION E701 RISER DIAGRAMS - ELECTRICAL

PL001 SCHEDULE, LEGEND, AND NOTES - PLUMBING

PL107 SEVENTH FLOOR PLANS - PLUMBING

PL117 SIXTH AND EIGHTH FLOOR PLAN - PLUMBING

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

36564 Dale A Bacik, PE

J K P Q R R.4M.3K.8

10.8

J.9

10.5

9.5

8.8

9.8

Prep/Recovery

C702CC

Prep/Recovery C702I

Prep/Recovery

C702HH

Prep/Recovery

C702GC702G

Prep/Recovery C702F

Prep/Recovery C702E

Prep/Recovery

C702DD

Prep/Recovery C702B

Sterile Supply C711

Clean Linen C710

Toilet C705

Prep/Recovery

C702NN

Prep/Recovery

C702MC702M

Prep/Recovery C702L

Prep/Recovery

C702KK

Prep/Recovery C702J

Nurse Manager

C707

Storage C712

Soiled Utility C706

Staff Lounge/ Lockers

B732

Elece

B732AB732

Toilet C703C703

Isolation

C702AA

Nurse Station C708

Toilet C704

HAC

C709

Prep Recovery

Area C702

Stair S7-6

Corridor C7-3-1

Elec

Comm 72T727272Elec

E72 ElecElec

Elec 713713C713713713

CorridorCorrido C7-8-1

CorridoCorridoCorrido

RECOVERY

C709

RECOVERY

C710

PATIENT ROOM

C711

C711A C710A C709A

OUTPATIENT RECOVERY

C707

C707A

Comm T72

Elec E72

Elec C713

LOUNGE

C706

LINEN

C705

PROGRAM MANAGER

C705B

NURSE MANAGER

C704B

ENGINEERING STORAGE

B732

SOILED UTILITY

C702

OFFICE

C703

FOYER

C704

C706AC705A

SUPPLY

C712

Toilet B701

11C7

5A7055A0505A0505

C 117111711

A

AAAAAAA007070 A05055700 A AAAAC

AC711A1C7 A

79392 Ryan E. Morriss, PE

KEY PLAN

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

1. REMOVE EXISTING FIRE SPRINKLER HEADS

AND ASSOCIATED PIPING IN PROJECT AREA.

A. ALL SERVICE INTERRUPTIONS TO THIS

EXISTING FACILITY MUST BE SCHEDULED AT

LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO

A MINIMUM. COORDINATE ALL DISRUPTIVE

WORK AND OUTAGE REQUIREMENTS WITH THE

COR.

B. EXISTING EQUIPMENT, PIPING, DUCTWORK,

DIFFUSERS, GRILLES, AND ASSOCIATED

COMPONENTS SHOWN ON DRAWINGS ARE

APPROXIMATE LOCATIONS AND IS PROVIDED

FOR REFERENCE USE ONLY. FIELD VERIFY

AND COORDINATE WITH EXACT LOCATIONS,

ELEVATIONS, SIZES, AND CONDITIONS OF

EXISTING COMPONENTS.

C. PHASE BOUNDARIES ON DRAWINGS INDICATE

ROOMS TO BE COMPLETED FOR EACH PHASE.

PERFORM ASSOCIATED WORK AS NECESSARY

TO COMPLETE EACH PHASE.

XX GENERAL NOTESDEMOLITION KEYNOTES

Scale: 1/8" = 1'-0"1 SEVENTH FLOOR RENOVATION PLAN - FIRE PROTECTION

Scale: 1/8" = 1'-0"2 SEVENTH FLOOR DEMOLITION PLAN - FIRE PROTECTION

FIRE SPRINKLER LEGEND

SYMBOL DESCRIPTION

EXISTING PENDENT TO BE REMOVED

• ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS

OF THE FLORIDA 2014 BUILDING CODE 5TH EDITION, FLORIDA FIRE

PREVENTION CODE 2014 5TH EDITION, LATEST APPROVED EDITION

NFPA FIRE CODES, AND APPLICABLE OSHA AND EPA REGULATIONS

AND GUIDELINES. WHERE CONFLICTS BETWEEN CODE AND

CONSTRUCTION DOCUMENTS OCCUR, THE MOST RESTRICTIVE

REQUIREMENTS SHALL GOVERN.

• THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION

AND PLANS FOR REVIEW ACCORDING TO NFPA 1 (2015 EDITION),

SECTION 1.14.

• A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE

COMPLETED IN ACCORDANCE WITH NFPA 13 AND FORWARDED TO

THE OWNER'S REPRESENTATIVE.

• ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK

SHALL BE DONE IN A THOROUGH AND WORKMANLIKE MANNER. THE

WORK, MATERIALS AND TEST SHALL BE IN ACCORDANCE WITH THE

CURRENT REQUIREMENTS OF NFPA 13, LATEST EDITION.

• MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS,

PARTITIONS, CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL

PENETRATIONS THROUGH RATED ASSEMBLIES WITH FIRESTOP

MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS TO MAINTAIN

THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS

FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO

PENETRATION DETAILS FOR FIRE PROTECTION PIPING

PENETRATIONS THROUGH RATED ASSEMBLIES.

• FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION

OF RISERS, CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS

WITH ALL OTHER TRADE SYSTEMS TO AVOID CONFLICTS AND

MAINTAIN ARCHITECTURAL ELEMENTS OF THE BUILDING.

• PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO

NFPA 13 (2010 EDITION).

• ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM,

UNLESS OTHERWISE NOTED.

• INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING,

AND OBSTRUCTION REQUIREMENTS.

• COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH

ARCHITECTURAL FINISHES, CEILING, LIGHTING LAYOUT, HVAC

DUCTS, OTHER CEILING MOUNTED DEVICES, AND STRUCTURAL

COMPONENTS.

• LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD

ADDITIONAL SPRINKLERS AT NO ADDITIONAL COST AND AS

NECESSARY TO MEET COVERAGE REQUIREMENTS IN ACCORDANCE

WITH NFPA 13.

• INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN

POSSIBLE. PROVIDE RETURN BENDS AT ALL SPRINKLER LOCATIONS

TO ALLOW FIELD ADJUSTMENT.

• THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL

CONFORM TO THE REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL

BE INSTALLED BY PERSONNEL WHO HAVE ENGINEERING FACILITIES

AND EXPERIENCE IN SUCH WORK AND WHO ARE REGULARLY

EMPLOYED TO DO SUCH WORK.

• PIPE SUPPORTS: HANGERS, CLAMPS, RODS AND OTHER

ACCESSORIES OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER

TO PROPERLY SUPPORT ALL PIPING SHALL BE FURNISHED AND

INSTALLED. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT

U-TYPE APPROVED ADJUSTABLE HANGERS.

• SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE

RATING EXCEPT WHERE EXCESSIVE TEMPERATURES ARE

ANTICIPATED. IN THESE LOCATIONS HIGH TEMPERATURE

SPRINKLERS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA NO.

13. PROVIDE QUICK RESPONSE SPRINKLERS IN LIGHT HAZARD

AREAS.

FIRE SPRINKLER PROVISIONS

1. SPRINKLER HEADS AND ASSOCIATED

COMPONENTS ARE TO BE SIZED, LOCATED,

AND PROVIDED ACCORDING TO NFPA 13.

XX RENOVATION KEYNOTES

FOR HEAD TYPES

SEE FLOOR PLANS

1" X 1/2" R.C.

DROP

90 EL.

ARMOVER

RISER NIPPLE

BRANCHLINE

SUSPENDED CEILING

EQ.EQ.EQ.EQ. EQ.EQ.

EQ. EQ.

E Q

. E Q

EQ. EQ.

SPRINKLER

SPEAKER OR

OTHER DEVICE

AIR DEVICE OR

LIGHT FIXTURE

CEILING LEGEND

SPRINKLER MOUNTING DETAIL

NTS4 SWING ARM ASSEMBLY DETAIL

NTS3

E Q

. E Q

E Q

. E Q

E Q

. E Q

E Q

. E Q

SPRINKLERS IN GRID CEILING SYSTEMS

SHALL BE LOCATED AT THE MIDPOINT

OR QUARTERPOINT OF THE FOUR FOOT

(4') DIMENSION AND THE MIDPOINT OF

THE TWO (2') DIMENSION. WHERE A

CONFLICT OCCURS, SYMMETRY ABOUT

THE AXIS SHALL BE MAINTAINED.

TYP.

TYP.

SEMI RECESSED PENDENT SPRINKLER, STANDARD COVERAGE,

QUICK RESPONSE, 155°F, FM APPROVED, UL LISTED

79392 Ryan E. Morriss, PE

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

WATER CLOSET, BARRIER FREE - AMERICAN STANDARD 3351.101, OR EQUIVALENT;

BACK OUTLET, WALL MOUNTED, 18" HIGH, ELONGATED RIM, 1-1/2" TOP SPUD,

VITREOUS CHINA, 1.28 GPF SENSOR FLUSH VALVE, SIPHON JET FLUSHING ACTION,

OPEN FRONT SEAT LESS COVER, STAINLESS STEEL CHECK HINGE. 1"CW, 4" SAN.

SEE SPECIFICATIONS.

LAVATORY, BARRIER FREE - AMERICAN STANDARD LUCERNE NO. 0355.041 OR

EQUIVALENT, 20X18" VITREOUS CHINA, WALL HUNG, SINGLE HOLE, GRID DRAIN

ASSEMBLY. PROVIDE FLOOR CARRIER WITH CONCEALED ARMS. TOP OF FRONT

RIM MOUNTED 34" FROM FINISHED FLOOR. PROVIDE DECK MOUNTED GOOSENECK

SENSOR FAUCET WITH AUTOMATIC HYGIENE FLUSH, CHICAGO FAUCETS

116.597.AB.1 OR EQUIVALENT; WITH 5-1/4" GOOSENECK SPOUT, DUAL SUPPLY.

PROVIDE UNDER SINK THERMOSTATIC MIXING VALVE, WATTS MODEL LFUSG-B-M2;

ASSE 1070 COMPLIANT, LEAD FREE, BRASS BODY, WITH DUAL CHECK VALVES,

INTEGRAL STRAINER WITH STAINLESS STEEL SCREENS, AND TAMPER RESISTANT

LOCKING NUT; SET TO 110°F. PROVIDE STOPS, SUPPLIES, TRAP, ETC., TO MAKE A

COMPLETE INSTALLATION. PROTECT TRAP AND SUPPLIES WITH TRUEBRO NO.

2018-xx-x LAV SHIELD. 1/2" CW, 1/2" HW, 1-1/4" SAN.

SINK - DOUBLE COMPARTMENT, COUNTER TOP ASME A119.19.3, KITCHEN SINK,

33"x22", 7-1/2" DEEP, WITH 8" GOOSNECK SPOUT FAUCET. PROVIDE STOPS, SUPPLIES, TRAP, ETC., TO COMPLETE INSTALLATION. 1/2" CW, 1/2" HW, 1-1/2" SAN.

SEE SPECIFICATIONS.

SINK - ZURN MODEL NO. Z5410, WALL MOUNT BLOWOUT SINK, 21-1/2"X19", WITH

ZURN CLINICAL SERVICE SINK FAUCET. 1"CW FOR BLOWOUT. 1/2"CW, 1/2"HW, 4"

SAN.

SINK- SINGLE COMPARTMENT, COUNTER TOP ASME A119.19.3, KITCHEN SINK,

16"X20", WITH 8" GOOSENECK SPOUT FAUCET. PROVIDE STOPS, SUPPLIES, TRAP,

ETC. TO COMPLETE INSTALLATION. 1/2"CW, 1/2"HW, 3" SAN.

MOP SINK - FIAT, NO. TSBC6000; 24X24" NEO-CORNER TERRAZZO SERVICE BASIN,

12" DEEP, COMBINATION DOME STRAINER AND LINT BASKET. FIAT NO. 830-AA

SERVICE SINK FAUCET WITH VACUUM BREAKER. PROVIDE WITH HOSE AND HOSE

HOOK, MOP BRACKET, 1/2" CW, 1/2" HW, 3" SAN.

WATER HAMMER ARRESTOR - ZURN SHOCKTROL Z-1700, OR EQUIVALENT. INSTALL

AT HIGH END OF EACH BRANCH THAT CONTAINS QUICK-CLOSING OR FLUSH

VALVES.

FLOOR DRAIN - ZURN Z-415S-P WITH TYPE "S" 5X5" NICKEL FINISH. DURA COATED

CAST IRON BODY WITH TRAP PRIMER CONNECTION. SIZE TO PIPE SIZE.

WALL CLEAN OUT - ZURN NO. CO2411/CO2530-SS7, SMOOTH STAINLESS STEEL

ACCESS COVER, PVC PLUG AND BODY. SIZE TO PIPE SIZE.

ICE BOX - WATER-TITE 9700HA, ICE MAKER BOX WITH ARRESTER, SOLDER

CONNECTION, ROUGH-IN AND MAKE COLD WATER CONNECTION, 4'-0" A.F.F., WALL

BOX W/ 3/8" ANGLE STOP. 3/8" CW

PLUMBING FIXTURES

WC-1

LAV-1

S-1

S-2

S-3

SS-1

WHA

FD-1

WCO

IB-1

PLUMBING LEGEND

PIPE UP

PIPE DOWN

VENT THRU ROOF

EQUIPMENT OR FIXTURE MARK

POINT OF NEW CONNECTION

DRAWING KEYNOTE

FLOOR DRAIN

BALL VALVE

CHECK VALVE

GATE VALVE

STRAINER

UNION

WALL CLEAN OUT

FLOOR CLEAN OUT

DOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER PIPING

DOMESTIC HOT WATER RETURN PIPING

SANITARY, SOIL, OR WASTE PIPING

EXISTING DOMESTIC COLD WATER PIPING

EXISTING DOMESTIC HOT WATER RETURN PIPING

EXISTING DOMESTIC HOT WATER PIPING

EXISTING PIPING TO BE REMOVED

EXISTING SANITARY, SOIL, OR WASTE PIPING

SANITARY VENT PIPING

OR

WCO

POINT OF DEMOLITION LIMIT

V

SAN

DHWR

DHW

DCW

(E)DCW

(E)DHWR

(E)DHW

(E)SAN

VTR

FCO

WCO

00000000

ZONE VALVE BOX - AMICO ALERT-1 SERIES MODEL ZIU-PX, ZONE VALVE

BOX, PROVIDE WITH GAS SHUTOFF VALVES.

MASTER AREA ALARM PANEL - AMICO ALERT-2 SERIES MODEL A2M-E-20.

AREA ALARM PANEL REMOTE SENSORS

AMICO MEDAES, PIN INDEX, WALL OUTLET; 1-OXYGEN, 1-AIR, 1-VACUUM.

CONTRACTOR SHALL VERIFY WALL OUTLET IS LOCATED ON HEADWALL,

REFER TO ARCHITECTURAL PLANS FOR MORE INFORMATION.

AMICO HI/LOW OXYGEN PRESSURE SWITCH MODEL# M-PRSW-OXY.

AMICO HI/LOW MEDICAL AIR PRESSURE SWITCH MODEL# M-PRSW-AIR.

AMICO HI/LOW VACUUM PRESSURE SWITCH MODEL# M-PRSW-VAC.

AMICO 3/4" SOURCE VALVE WITH LOCKING HANDLE MODEL# VV-ISO-GL-07.

AMICO 3/4" MEDICAL AIR COMPRESSOR SOURCE VALVE WITH LOCKING

HANDLE MODEL# VV-ISO-GL-07.

AMICO 1" MEDICAL VACUUM PUMP SOURCE VALVE WITH LOCKING

HANDLE MODEL# VV-ISO-GL-10.

MEDICAL GAS FIXTURES

ZVB

AAP

AS

MGO-1

"A"

"B"

"C"

"D"

"E"

"F"

(E) EXISTING

AFF ABOVE FINISHED FLOOR

BFF BELOW FINISHED FLOOR

BV BALL VALVE

CO PIPE CLEANOUT

CO2 CARBON DIOXIDE

COR CONTRACTING OFFICER'S REPRESENTATIVE

CRS CORROSION-RESISTANT STEEL

CTE CONNECT TO EXISTING

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DEMO DEMOLISH OR DEMOLITION

DFU DRAINAGE FIXTURE UNITS

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EX EXISTING

FBC FLORIDA BUILDING CODE

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

GPM GALLONS PER MINUTE

IBC INTERNATIONAL BUILDING CODE

IE INVERT ELEVATION

LAV LAVATORY

MA MEDICAL AIR

MS MOP SINK

MV MEDICAL VACUUM

N NITROGEN

N2O NITROUS OXIDE

NC NORMALLY CLOSED

NO NORMALLY OPEN

O OXYGEN

SAN SANITARY, SOIL, OR WASTE

UNO UNLESS NOTED OTHERWISE

V VENT

VTR VENT THROUGH ROOF

WAG WASTE ANESTHETIC GAS

WC WATER CLOSET

WCO WALL CLEAN OUT

WSFU WATER SUPPLY FIXTURE UNITS

ABBREVIATIONS

1. MEDICAL GAS SYSTEMS SHALL BE FURNISHED, INSTALLED, AND TESTED IN STRICT

ACCORDANCE WITH NFPA 99, 2018 EDITION.

2. INSTALLATION AND TERMINATIONS OF ALL LOW VOLTAGE AREA ALARM WIRING AND

CONDUIT PER NFPA 99 BY PLUMBING MEDICAL GAS CONTRACTOR.

3. PLUMBING CONTRACTOR TO SUPPLY THE REQUIRED NUMBER OF VACUUM

REGULATORS, OXYGEN FLOW METERS MEDICAL AIR FLOW METERS AS PART OF

MEDICAL GAS EQUIPMENT PACKAGE.

4. PROVIDE MEDICAL GAS PIPE LABELS IN COMPLIANCE WITH NFPA 99, AND AT

LOCATIONS INCLUDING BUT NOT LIMITED TO: AT INTERVALS OF NOT MORE THAN 20

FT., AT LEAST ONCE WITHIN EACH SPACE, AND ON BOTH SIDES OF EVERY WALL AND

FLOOR SLAB PENETRATION. MEDICAL GAS PIPING SHALL BE IDENTIFIABLE BY

APPROPRIATE LABELING WITH NAME OF GAS CONTAINED.

5. CONTRACTOR TO FIELD VERIFY LOCATION OF EXISTING OXYGEN AIR AND VACUUM

PIPING AND ADJUST PIPING LAYOUT TO ACCOMMODATE CONNECTIONS.

6. CONTRACTOR SHALL INCLUDE THE COST OF THE SYSTEM FUNCTIONAL TEST TO HIS

FEE.

7. EXISTING MEDICAL GAS SYSTEMS MUST BE KEPT IN SERVICE AT ALL TIMES DURING

CONSTRUCTION OF THE NEW SYSTEMS. THE FINAL CONNECTIONS OF THE NEW

SYSTEMS TO THE EXISTING MEDICAL GAS SYSTEMS SHALL BE COORDINATED WITH

THE OWNER'S OPERATIONS AND SHALL BE MADE AFTER HOURS OF THE OWNERS

OPERATIONS SO AS NOT TO PRESENT ANY DISRUPTION TO THE OWNER'S

OPERATIONS.

8. ALL TESTING OF THE NEW SYSTEMS AND PIPING SHALL BE DONE PRIOR TO THE

FINAL MEDICAL GAS PIPE CONNECTIONS TO THE EXISTING PIPING AND SHALL BE

RETESTED AFTER THE FINAL CONNECTION AS WARRANTED.

MEDICAL GAS NOTES

DOMESTIC WATER PIPING:

• HOT AND COLD WATER PIPING SHALL BE TYPE L HARD COPPER PIPING WITH

ASSOCIATED WROUGHT COPPER FITTINGS. ISOLATION VALVES SHALL BE TWO-PIECE

BALL VALVES WITH STAINLESS STEEL TRIM AND FULL PORT CONFIGURATION.

• ALL HORIZONTAL PIPING PENETRATIONS SHALL BE PROVIDED WITH ESCUTCHEONS

TO PROVIDE A CLEAN INSTALLATION.

• PIPING PENETRATIONS THROUGH BUILDINGS STRUCTURE SHALL BE UL RATED AND

FIRESTOPPED, WHERE REQUIRED.

MEDICAL GAS SYSTEMS:

• AN AREA ALARM PANEL SHALL BE PROVIDED IN RECOVERY AS INDICATED, WITH GAS

SPECIFIC SYSTEM PRESSURE READINGS.

• MEDICAL GASES SHALL BE DISTRIBUTED THROUGH PIPING TO ZONE VALVE BOXES.

ALL VALVES SHALL BE THREE PIECE BALL TYPE WITH BLOW-OUT PROOF STEMS,

LOCKING HANDLES AND FULL PORT DESIGN.

• FROM ZONE VALVE BOXES, MEDICAL GASES SHALL BE DISTRIBUTED TO MEET THE

SPACE REQUIREMENTS.

• ALL MEDICAL GAS PIPING SHALL BE PRECLEANED, TYPE K, ASTM B 819, HARD DRAWN,

SEAMLESS COPPER TUBING WITH BRAZED WROUGHT COPPER FITTINGS, ASTM B16.22

OR MSS SP-73; FACTORY CLEANED, PURGED, AND SEALED FOR MEDICAL GAS

SERVICE. STORE PRECLEANED AND SEALED MEDICAL GAS PIPE, FITTINGS, VALVES,

AND SPECIALTIES WITH SEALING PLUGS AND SEALING PACKAGING INTACT.

• LABEL MEDICAL GAS PIPE, FITTINGS, VALVES, AND SPECIALTIES THAT HAVE NOT

BEEN PRECLEANED, OR THAT HAVE BEEN PRECLEANED BUT HAVE SEAL OR

PACKAGING THAT IS NOT INTACT, WITH TEMPORARY LABELS INDICATING THAT

CLEANING IS REQUIRED BEFORE INSTALLATION.

MISCELLANEOUS:

• HANGERS: FOR CAST IRON, PROVIDE HEAVY DUTY PIPE HANGERS, BRACKETS OR

CLAMPS AT 5' INTERVALS. ALL MATERIAL SHALL BE NON-FERROUS AND

NON-CORRODING. FASTEN WITH LAG SCREW OR WITH EXPANSION SHIELDS AS

APPLICABLE. FOR WATER PIPING, PROVIDE ADJUSTABLE COPPER PLATED HANGERS

AT 6' INTERVALS MAXIMUM. PROVIDE HANGERS TO ALLOW FOR FULL THICKNESS OF

INSULATION.

• VALVES AND SHUTOFFS: FULL SIZE BRONZE GATE OR BALL VALVES FOR HOT AND

COLD WATER MAINS, STANDARD PORT BRONZE BALL VALVES FOR HOT AND COLD

WATER BRANCHES. PROVIDE DRAINAGE VALVES ON MAINS. PROVIDE UNITS BY

APOLLO, GRINNELL, HAMMOND, MILWAUKEE, LUNKENHEIMER, OR WATTS. ALL

VALVES SHALL BE MANUFACTURED IN THE U.S. USE OF IMPORTS IS PROHIBITED.

• INSTALL SHUTOFF VALVES ON EACH PIECE OF EQUIPMENT.

• CLEARLY LABEL ALL VALVES AND COMPONENTS. ALL PIPING SYSTEMS AND FLOW

DIRECTION SHALL BE CLEARLY LABELED WITH COMMERCIAL PIPE LABELING DEVICES.

• DISINFECT DOMESTIC WATER DISTRIBUTION SYSTEM. FLUSH AND TEST ALL SYSTEMS

FOR PROPER OPERATION. ADJUST SYSTEM TO PREVENT WATER HAMMER.

• MAINTAIN INDICATED FIRE RATINGS OF WALLS, PARTITIONS, CEILINGS AND FLOORS

AT PENETRATIONS. SEAL WITH FIRESTOPPING TO MAINTAIN FIRE RATING.

• RESTORE DAMAGED FINISHES. CLEAN AND PROTECT WORK FROM DAMAGE.

• INSTRUCT OWNER'S PERSONNEL IN PROPER OPERATION OF SYSTEMS.

PLUMBING DESIGN PROVISIONS

1. ALL WORK SHALL COMPLY WITH APPLICABLE NATIONAL, STATE, AND LOCAL CODES. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, THE 2014 FLORIDA PLUMBING CODE. WHERE CONFLICTS OCCUR BETWEEN CODES, OR BETWEEN CONSTRUCTION DOCUMENTS AND CODES, THE MOST RESTRICTIVE REQUIREMENTS SHALL GOVERN.

2. REVIEW PLANS OF ALL TRADES PRIOR TO BIDDING AND BEGINNING WORK. INSTALLATIONS ARE TO INCLUDE ALL

PLUMBING FOR COMPLETE SYSTEMS SHOWN ON THE PLANS AND AS REQUIRED.

3. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC DUCTS, STRUCTURE, ELECTRICAL, LIGHTING, AND OTHER PIPING IN THE CEILING SPACE. VENT PIPING AND WATER PIPING SHALL BE HELD EITHER ABOVE

OR BELOW HVAC DUCTWORK, AS COORDINATED WITH THE HVAC CONTRACTOR.

4. ALL CHANGES SHALL BE REVIEWED BY THE ARCHITECT.

5. COORDINATE WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING-IN PLUMBING FIXTURES AND EQUIPMENT

SUPPLIES.

6. THE PLUMBING SUBCONTRACTOR SHALL FURNISH AND INSTALL ALL PLUMBING FIXTURES, UNLESS NOTED OTHERWISE.

7. VERIFY MOUNTING HEIGHT AND WATER CONNECTION SIZES OF ALL PLUMBING FIXTURES PRIOR TO ROUGH-IN. FURNISH CUT-OUT TEMPLATES, FOR PLUMBING FIXTURES TO BE INSTALLED IN MILLWORK, TO THE GENERAL CONTRACTOR.

8. MAKE PROPER HOT AND COLD WATER, WASTE AND VENT PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT

EVEN THOUGH ALL FITTINGS AND CONNECTIONS ARE NOT SHOWN.

9. VERIFY LOCATION OF EXISTING WATER SERVICE AND THE LOCATION/INVERTS OF SANITARY PIPING PRIOR TO

INSTALLATION.

10. CUT AND PATCH CONCRETE AS REQUIRED.

11. IT IS NOT THE INTENT OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THESE DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY THE ARCHITECT) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AS PART OF

HIS TOTAL WORK.

12. THE EQUIPMENT ROUGH-IN ITEMS AND THEIR DIMENSIONED LOCATIONS FOR ALL CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE. IN SOME INSTANCES THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR EQUIPMENT ITEMS MAY VARY FROM WHAT IS SHOWN. THEREFORE, THESE ITEMS AND DIMENSIONS SHALL BE VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR EQUIPMENT ROUGH-IN DRAWING. FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH-INS OR THEIR LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION

AND/OR ADDITIONAL ROUGH-INS DIRECTLY UPON THAT CONTRACTOR.

13. CONTRACTOR SHALL SUPPLY TO THE ARCHITECT/ENGINEER THE REQUIRED COPIES OF SHOP DRAWINGS FOR APPROVAL SO THE QUALITY OF INTENDED MATERIALS OR EQUIPMENT CAN BE REVIEWED BEFORE INSTALLATION.

THERE WILL BE NO DRAW UNTIL SHOP DRAWINGS HAVE BEEN SUBMITTED AND REVIEWED BY THE

ARCHITECT/ENGINEER.

14. DO NOT SCALE THIS DRAWING. REFER TO ARCHITECTURAL FLOOR PLAN FOR BUILDING DIMENSIONS.

15. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW ALL ELBOWS, OFFSETS, UNIONS, VALVES, FITTINGS, ETC. REQUIRED TO COMPLETE THE INSTALLATION OF THE WORK. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF WITH THE PLANS AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY COULD HAVE BEEN FORESEEN HAD PROPER EXAMINATION BEEN

MADE.

16. THE CONTRACTOR SHALL COOPERATE FULLY AMONG THE TRADES.

17. THE POTABLE WATER SUPPLY SHALL BE PROTECTED AGAINST BACKFLOW AND SIPHONAGE, BOTH NATURAL AND INDUCED. ALL EQUIPMENT CONNECTED TO THE POTABLE WATER SYSTEM BEING CAPABLE OF POLLUTING OR CONTAMINATING THE POTABLE WATER DISTRIBUTION SYSTEM OR ANY PART THEREOF BY MEANS OF A REVERSAL OF FLOW, PRESSURE DROP, PRESSURE LOSS, INDUCED VACUUM, OR BY INJECTION BECAUSE OF ANY PRIMARY OR AUXILIARY PUMPING SYSTEM CONNECTED, MUST BE ISOLATED AND CONTAINED BY MEANS OF APPROVED BACKFLOW DEVICES, CHECK VALVES, AIR GAPS, OR VACUUM BREAKERS. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL

THESE DEVICES PER LOCAL CODE REQUIREMENTS.

18. THE WATER PIPING SYSTEM SHALL BE FLUSHED AND STERILIZED IN ACCORDANCE WITH LOCAL REGULATIONS.

19. HOT AND COLD WATER SUPPLY BRANCHES FOR ALL SYSTEMS HAVING QUICK CLOSING VALVES OF ANY TYPE SHALL HAVE WATER HAMMER ARRESTORS INSTALLED AT THE HIGH POINT ON THE END OF EACH BRANCH.

20. FURNISH AND INSTALL SHUTOFF BALL VALVE AND DIELECTRIC UNIONS FOR ALL EQUIPMENT HOT AND COLD WATER LINES. PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO EQUIPMENT. COORDINATE WITH EQUIPMENT

SUPPLIER FOR EXACT REQUIREMENTS.

21. VERIFY MOUNTING HEIGHTS OF ALL BARRIER FREE FIXTURES WITH ARCHITECTURAL PLANS.

22. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL COPPER INDIRECT WASTE PIPING REQUIRED FROM EQUIPMENT TO FLOOR DRAINS. PIPING SHALL COMPLY WITH FEDERAL, STATE AND LOCAL CODES. COORDINATE WITH ALL EQUIPMENT SUPPLIERS AND SIZES AS REQUIRED BY PIECE OF EQUIPMENT SERVED. HOLD PIPING TIGHT TO WALL WHERE APPLICABLE. PROPERLY SECURE AS REQUIRED. COORDINATE WITH CASEWORK SUPPLIER FOR MAXIMUM

CLEARANCE UNDER CABINETS.

23. PROVIDE CHROME PLATED ESCUTCHEONS AT ALL WALL PENETRATIONS.

24. PLUMBING CONTRACTOR SHALL INSTALL 4" SOIL AND WASTE PIPING WITH MINIMUM SLOPE OF 1/8" PER FOOT UNLESS

OTHERWISE REQUIRED.

25. ALL FLOOR DRAINS ARE TO BE PROVIDED WITH MINIMUM 3" DRAIN LINES, DEEP SEAL TRAPS, AND AUTOMATIC TRAP PRIMERS. TRAP PRIMERS SHALL BE LOCATED IN A SERVICEABLE LOCATION AND INSTALLED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. HOLD TOP OF FLOOR DRAINS FLUSH WITH FINISHED FLOOR; SEE ARCHITECTURAL

SHEETS FOR FLOOR SLOPES AND PROPER FINISHED FLOOR ELEVATION.

26. ALL VENT PIPE TO BE COMPATIBLE WITH STRUCTURE, MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL EQUIPMENT, AND LIGHTING. ALL V.T.R.'S SHALL BE EXTENDED TO A MINIMUM OF 2" ABOVE PARAPET HEIGHT AND MAINTAINED 10'-0"

MINIMUM FROM ALL OUTSIDE AIR INTAKES.

27. MATERIALS, EQUIPMENT, ASSEMBLIES AND SYSTEMS SHALL MEET ALL PERTINENT REQUIREMENTS OF NATIONALLY RECOGNIZED TESTING ORGANIZATIONS SUCH AS UL, ASTM, ASSE, AWWE, AGA AND NFPA AS WELL AS THE MOST

CURRENT VERSION OF THE STATE AND LOCAL CODES.

28. ALL INSTALLED SYSTEMS, DEVICES AND RELATED ITEMS SHALL BE TESTED IN PLACE. REPLACE ANY AND ALL CONTRACTOR SUPPLIED DEFECTIVE DEVICES, ITEMS, OR SYSTEMS AT CONTRACTOR'S EXPENSE, BEFORE COMPLETION

OF PROJECT.

29. WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS THAT DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE

OWNER. NO OTHER CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION OF THE ENGINEER.

30. ALL EQUIPMENT, FIXTURES AND MATERIALS SHALL BE NEW AND UNUSED, AND INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS (UNO). PROVIDE COMPLETE WITH ALL TRIM, STOPS, HANGERS, CARRIERS, SUPPORTS, ETC., INCLUDING PROVISIONS FOR BARRIER FREE USE, IF REQUIRED. WHERE FIXTURES ARE ACCESSIBLE

THEY MUST COMPLY WITH ALL FEDERAL A.D.A. REGULATIONS.

31. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE FURNISHED, FABRICATED, FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED, AND ALL WORK IN CONNECTION WITH INSTALLATION OF MANUFACTURER'S GUARANTEED EQUIPMENT. THE CONTRACTOR'S GUARANTEE SHALL LAST ONE YEAR FROM THE FINAL OWNER ACCEPTANCE OF THE WORK AND SHALL APPLY TO ALL

DEFECTS IN MATERIALS AND WORKMANSHIP OF ANY KIND.

32. ALL FAUCET CONTROLS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRE TIGHTGRASPING.

33. ALL BARRIER FREE WATER CLOSET CONTROLS SHALL BE LOCATED ON UNIT TOWARDS WIDE SIDE OF STALL. VERIFY IF

RIGHT OR LEFT SIDE LOCATION.

PLUMBING NOTES

PIPE PENETRATION

File details come from the government source that posted it.