Project 546-16-104 Renovate Ambulatory Surgery
Solicitation number
36C24818R0737
Issued by

About this file

36C24818R0737 546-16-104 Final Submittal Drawings_Part3.pdf

View the file

Other files

File Type Posted
36C24818R0737-0003000.docx DOCX document
36C24818R0737-0002000.docx DOCX document
36C24818R0737-0002003.pdf PDF
36C24818R0737-0002001.pdf PDF
36C24818R0737-0002002.pdf PDF
36C24818R0737-0001001.pdf PDF
36C24818R0737-0001000.docx DOCX document
36C24818R0737-024.pdf PDF
36C24818R0737-021.pdf PDF
36C24818R0737-029.pdf PDF
36C24818R0737-023.pdf PDF
36C24818R0737-019.docx DOCX document
36C24818R0737-020.pdf PDF
36C24818R0737-022.pdf PDF
36C24818R0737-027.pdf PDF
36C24818R0737-025.pdf PDF
36C24818R0737-028.pdf PDF
36C24818R0737-000.docx DOCX document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

79392 Ryan E. Morriss, PE

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

GENERAL NOTES

A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING

FACILITY MUST BE SCHEDULED AT LEAST 3

WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK

AND OUTAGE REQUIREMENTS WITH THE COR.

B. REFER TO SHEET G200 FOR PHASING PLAN.

C. THESE DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NOT NECESSARILY SHOW ALL

ELBOWS, OFFSETS, UNION, VALVES AND

FITTINGS REQUIRED TO COMPLETE THE

INSTALLATION OF THE WORK.

D. ISOMETRIC IS FOR DIAGRAMMATIC PURPOSES

ONLY AND SHOULD NOT BE SCALED. REFER TO

ARCHITECTURAL PLANS FOR SCALED

DRAWINGS.

E. ALL DOMESTIC WATER PIPING SHALL BE 1/2"

UNLESS NOTED OTHERWISE.

F. ALL WASTE PIPING SHALL BE 4" AND ALL VENT

PIPING SHALL BE 2" UNLESS NOTED OTHERWISE.

Scale:1 SEVENTH FLOOR SANITARY - PLUMBING ISOMETRIC N.T.S.

ISOMETRIC KEYNOTES--

1. EXISTING PIPING RISER CONTINUES TO 8TH

FLOOR AND ABOVE.

2. EXISTING PIPING RISER CONTINUES TO 6TH

FLOOR AND BELOW.

S-1

1.4 wsfu

S-2

1.4 wsfu

S-3

1.4 wsfu

ICE MAKER

SS-1

3.0 wsfu

LAV-1

2.0 wsfu

LAV-1

2.0 wsfu

LAV-1

2.0 wsfu

LAV-1

2.0 wsfu

LAV-22

2.0 wsfu

LAV-2

2.0 wsfu

LAV-2

2.0 wsfu

LAV-2

2.0 wsfu

LAV-2

2.0 wsfu

LAV-2

2.0 wsfu

LAV-2

2.0 wsfu

LAV-2

2.0 wsfu

WC-1

10.0 wsfu

WC-1

10.0 wsfu

WC-1

10.0 wsfu

WC-1

4 dfu

WC-1

4 dfu

WC-1

4 dfu

LAV-2

2 dfu

LAV-2

2 dfu

LAV-2

2 dfu

LAV-2

2 dfu

LAV-2

2 dfu

LAV-2

2 dfu

LAV-2

2 dfu

LAV-2

2 dfu

LAV-1

2 dfu

LAV-1

2 dfu

LAV-1

2 dfu

LAV-1

2 dfu

SS-1

2 dfu

S-3 2 dfu S-2

2 dfu

S-1 2 dfu

Scale:2 SEVENTH FLOOR DOMESTIC WATER - PLUMBING ISOMETRIC N.T.S.

FD-1

2 dfu

3/4" HW

1-1/4" CW

3/4" HW

1-1/4" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

3/4" HW

1-1/4" CW

IB-1

0.25 wsfu

WCO

FD-1

2 dfu

WCO

WCO

WCO

WCO

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

8TH FLOOR

7TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

7TH FLOOR

6TH FLOOR

11 11

FD-1

2 dfu

FD-1

2 dfu

FD-1

2 dfu

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1-1/4" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CWW1

1/2" HW

1/2" CW

3/4" HWW

1-1/4" CW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1/2" CW

1/2" HW

1-1/4" CW

1/2" HW

1/2" CW

1-1/4" CW

1" CW

1" CW

1" CW

2" SAN

2" SAN

4" SAN

2" SAN

4" SAN

2" SAN

4" SAN

2" SAN

2" SAN

2" SAN

2" VENT

2" VENT

2" VENT

2" VENT

2" VENT

2" VENT

2" VENT

4" SAN

4" VENT

4" SAN (E)

4" VENT (E)

4" SAN (E)

4" VENT (E)

4" SAN (E)

4" VENT (E)

4" SAN

4" VENT

4" SAN

4" VENT

4" SAN

4" VENT

2" VENT

4" SAN (E)

4" VENT (E)

4" SAN (E)

4" VENT (E)

4" SAN (E)

4" VENT (E)

4" SAN (E)

4" VENT (E)

4" SAN (E)

4" VENT (E)

2" SAN

2" SAN

4" SAN

2" SAN

3" SAN

4" SAN

4" SAN

2" SAN

4" SAN

4" SAN

4" SAN

4" SAN

2" SAN

4" SAN

2" SAN

2" SAN

2" SAN

4" SAN

4" VENTT

4" SAN

4" VENT

2" VENT

2" VENT

2" VENT

4" VENT

4" VENT

4" VENT

4" SAN

4" VENT

2" VENT

2" VENT

2" VENT

2" SAN

4" VENTT

2" VENT

2" VENT

2" VENTTT

2" VENT

2" VENT

4" VENT

FD-1

2 dfu

79392 Ryan E. Morriss, PE

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

GENERAL NOTES

A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING

FACILITY MUST BE SCHEDULED AT LEAST 3

WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK

AND OUTAGE REQUIREMENTS WITH THE COR.

B. REFER TO SHEET G200 FOR PHASING PLAN.

C. THESE DRAWINGS ARE DIAGRAMMATIC IN

NATURE AND DO NOT NECESSARILY SHOW ALL

ELBOWS, OFFSETS, UNION, VALVES AND

FITTINGS REQUIRED TO COMPLETE THE

INSTALLATION OF THE WORK.

D. ISOMETRIC IS FOR DIAGRAMMATIC PURPOSES

ONLY AND SHOULD NOT BE SCALED. REFER TO

ARCHITECTURAL PLANS FOR SCALED

DRAWINGS.

Scale:1 SEVENTH FLOOR ISOMETRIC - MEDICAL GAS N.T.S.

ISOMETRIC KEYNOTES--

1. EXISTING MEDGAS PIPING CONTINUES TO

OUTSIDE OF SCOPE.

3/4" MA

3/4" MO2

1" MV

3/4" MA

3/4" MO2

1" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

3/4" MA

3/4" MO2

3/4" MV

3/4" MA

3/4" MO2

1" MV

3/4" MA

3/4" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

ZVB

ZVB

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

MGO-1

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

1/2" MA

1/2" MO2

3/4" MV

A C

B

S S

S

AS-1

S

AS-1

S

S

NOTES:

1. BASIS OF DESIGN EQUIPMENT WITH REQUIRED PERFORMANCE CHARACTERISTICS IS SCHEDULED. OTHER MANUFACTURES ARE ACCEPTABLE; HOWEVER EQUIPMENT NOT MEETING EQUIVALENT PERFORMANCE

CRITERIA CANNOT BE CONSIDERED.

2. HOT WATER REHEAT COIL SHALL HAVE A MAXIMUM WATER PRESSURE DROP OF 3.0 FT. WG.

3. ALL AIR TERMINAL UNITS SHALL BE PRESSURE INDEPENDENT TYPE WITH VELOCITY RESET CONTROLLERS.

4. FURNISH AND INSTALL SPACE ENVIRONMENTAL CONTROLLER AND DISPLAY, PRESSURE DIFFERENTIAL SENSORS AND INTERLOCKS TO MAINTAIN REQUIRED SPACE PRESSURE DIFFERENTIAL.

5. PROVIDE FACTORY WIRED NON-FUSED DISCONNECT SWITCH ON TERMINAL UNIT.

1. IN GENERAL, PLANS DRAWINGS, PLANS AND DETAILS ARE DIAGRAMMATIC IN NATURE AND SHOULD NOT BE SCALED. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY SPACE ALLOCATED PRIOR TO ORDERING EQUIPMENT.

2. THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH SUBMITTED EQUIPMENT TO ENSURE ALL INLET/OUTLET CONNECTIONS COORDINATE WITH FIELD INSTALLED DUCTWORK AND MAKE ANY NECESSARY DUCT

MODIFICATIONS TO ENSURE PROPER OPERATION OF MECHANICAL EQUIPMENT.

3. SUBMITTALS SHALL MEET SCHEDULED DESIGN CHARACTERISTICS. THIS INCLUDES BUT NOT LIMITED TO CFMS, EAT(DB/WB), ESP, CAPACITIES, VOLTAGES/PHASES, MCA/MOCP, SONES, ETC.

4. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING BUILDING CODE REQUIREMENTS:

* FLORIDA BUILDING CODE (FBC) 2014

* FBC ENERGY CONSERVATION 2014

* FBC MECHANICAL CODE 2014

* FBC PLUMBING CODE 2014

5. ALL WALL-MOUNTED THERMOSTATS AND/OR TEMPERATURE SENSORS SHALL BE INSTALLED AT AN ELEVATION OF 48" ABOVE FINISHED FLOOR TO THE TOP UNLESS OTHERWISE NOTED ON DRAWINGS. LOCATION OF WALL-MOUNTED THERMOSTATS SHALL BE COORDINATED WITH OTHER TRADES FOR A NEAT APPEARANCE. FINAL LOCATION OF THERMOSTATS SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER OR REPRESENTATIVE IN THE FIELD.

6. ALL SUPPLY AIR DIFFUSERS SHALL BE 4-WAY THROW UNLESS OTHERWISE NOTED. CONTRACTOR SHALL PAINT INSIDE EACH RETURN GRILLE'S PLENUM AND DUCT CONNECTION FLAT BLACK TO CONCEAL CONNECTION. COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES AND FIRE SPRINKLER HEADS. PRIOR TO INSTALLATION, THE CONTRACTOR IS TO REFER TO AND COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.

7. DIFFUSERS/GRILLES SHALL NEVER BE INSTALLED ON SURFACE OF ACOUSTICAL LAY-IN TILE. ALL DIFFUSERS/GRILLES IN LAY-IN CEILINGS SHALL BE LAY-IN PANEL MOUNT. REFER TO SCHEDULE. GYPSUM BOARD SURFACE MOUNT DIFFUSERS

SHALL NOT BE BEVEL MOUNT.

8. CONTRACTOR SHALL COORDINATE DIFFUSER/GRILLE LOCATIONS WITH STRUCTURE IN EXPOSED SITUATIONS IN ORDER TO ENSURE AIR IS NOT DIRECTLY SUPPLIED OR RETURNED OVER STRUCTURE OR OTHER TRADE COMPONENTS SUCH AS FIRE SPRINKLER PIPING, PLUMBING PIPING, ETC., CAUSING DUST ACCUMULATION. DUCTWORK ALONG WITH DIFFUSER/GRILLE LOCATIONS SHALL BE INSTALLED SYMMETRICALLY WITH ANY ADJACENT DUCTWORK/GRILLES.

CENTER DIFFUSERS/GRILLES BETWEEN STRUCTURAL MEMBERS WHERE DUCTWORK AND STRUCTURAL MEMBERS ARE EXPOSED. CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL INSTALLATION APPEARANCE AND SHALL MAKE APPROPRIATE CHANGES WHERE DIRECTED BY ARCHITECT/ENGINEER AT THEIR OWN EXPENSE WHERE ITEMS ARE NOT

INSTALLED PER ABOVE STANDARDS.

9. CONTRACTOR SHALL PROVIDE A COPY OF THE TEST AND BALANCE REPORT BY AN AABC OR NEBB CERTIFIED AGENCY.

THIS REPORT MUST BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR TO THE FINAL INSPECTION. THE CONTRACTOR MUST ALSO PROVIDE ALL REPORTS REQUIRED BY THE SPECIFICATION. OUTDOOR TEMPERATURE (DB);

OUTSIDE AIR (DB/WB & CFM); SUPPLY AIR AT UNIT DISCHARGE (DB/WB & CFM); RETURN AIR {MIXED} (DB/WB & CFM);

LEAVING COIL (DB/WB); DIFFUSER/GRILLE (DB/WB); EQUIPMENT (EWT/LWT); EQUIPMENT (EAT/LAT); EQUIPMENT (GPM);

EQUIPMENT (PRESSURES). OUTSIDE AIR CFM SHALL BE MEASURED DIRECTLY AND NOT CALCULATED FROM THE

DIFFERENCE BETWEEN SUPPLY AIR CFM AND RETURN AIR CFM.

10. ALL DUCTWORK MUST BE INSTALLED 6" AWAY FROM ANY FIRE RATED WALL TO FACILITATE INSPECTION.

11. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL TRADES INSTALLATION SCHEDULES. FIXED WORK SUCH AS DUCTWORK AND PLUMBING SHALL BE INSTALLED PRIOR TO ANY TRADE WORK THAT CAN BE EASILY RELOCATED OR OFFSET SUCH AS ELECTRICAL CONDUITS, SMALL WATER LINES, ETC. IDEALLY DUCTWORK SHALL BE INSTALLED FIRST.

12. PROVIDE FIRE, SMOKE, AND FIRE/SMOKE DAMPERS WHERE REQUIRED BY SECTION 607.5 OF THE FBC - MECHANICAL, AND PROVIDE ACCESS AND IDENTIFICATION AS REQUIRED BY SECTION 607.4 OF THE FBC - MECHANICAL. MECHANICAL CONTRACTOR SHALL PROVIDE CEILING RADIATION DAMPERS WHERE REQUIRED BY SECTION 607.6.2 OF THE FBC - MECHANICAL. ALL FIRE DAMPERS SHALL BE DYNAMIC FIRE DAMPERS, UNLESS OTHERWISE NOTED.

13. WHERE SMOKE OR FIRE/SMOKE DAMPERS ARE REQUIRED, THE ELECTRICAL OR FIRE ALARM CONTRACTOR (MECHANICAL CONTRACTOR TO COORDINATE) SHALL PROVIDE 120V POWER AND ENSURE PROPER OPERATION UPON ACTIVATION. DAMPER ACTUATION SHALL BE BY ONE OF THE METHODS LISTED IN SECTION 607.3.3.2 OF THE FBC - MECHANICAL. WHEN SECTION 607.3.3.2 REQUIRES A DUCT SMOKE DETECTOR AT THE DAMPER, THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL THE DETECTOR WITHIN THE DUCTWORK. THE ELECTRICAL OR FIRE ALARM CONTRACTOR (MECHANICAL CONTRACTOR TO COORDINATE) SHALL PROVIDE 120V POWER AND ENSURE PROPER DETECTOR OPERATION. OTHER THAN IN MECHANICAL SMOKE CONTROL SYSTEMS, UPON ACTIVATION, THE DAMPER SHALL CLOSE, THE ASSOCIATED AIR DISTRIBUTION SYSTEM SHALL SHUT DOWN, AND A SUPERVISORY SIGNAL SHALL BE

GENERATED PER SECTION 606.4 OF THE FBC - MECHANICAL.

14. OTHER THAN IN MECHANICAL SMOKE CONTROL SYSTEMS, DURING AN AUTOMATIC FIRE ALARM ACTIVATION, FANS OPERATING IN THE ZONE IN ALARM SHALL SHUT DOWN AND SMOKE AND FIRE/SMOKE DAMPERS SHALL CLOSE.

15. PENETRATIONS THROUGH SMOKE OR FIRE-RATED ASSEMBLIES: PENETRATIONS FOR PIPES, CONDUITS OR OTHER PURPOSES THROUGH ASSEMBLIES (FLOORS, ROOF, WALLS, PARTITIONS, ETC.) WITH A REQUIRED FIRE RESISTANCE RATING SHALL BE SEALED TO THE PENETRATING MEMBER IN AN APPROVED MANNER WHICH MAINTAINS THE REQUIRED

FIRE RESISTANCE RATING OF THE ASSEMBLY AS FOLLOWS:

16. WHERE HOLES FOR PENETRATIONS ARE FORMED CIRCULAR OR CORE-BORED, THE PENETRATION SHALL BE PROTECTED WITH FIRE-SEAL BRAND SMOKE AND FIRE STOP FITTINGS MFG. BY O-Z GEDLEY, LINK SEAL BRAND BY

THUNDER LINE OR AN EQUAL APPROVED BY ENGINEER.

17. WHERE HOLES FOR PENETRATIONS ARE IRREGULAR (NON-CIRCULAR) IN SHAPE, THE PENETRATION SHALL BE PROTECTED WITH DOW CORNING 3-6548, SILICONE RTV FOAM, 3M FIRE BARRIER PENETRATION SEAL SYSTEM OR AN

EQUAL APPROVED BY THE ENGINEER.

18. INTENT OF THESE NOTES AND MECHANICAL NOTES ON DRAWINGS IS TO CLARIFY THE SCOPE OF WORK AND ALERT CONTRACTOR OF EXISTING CONDITIONS. THE CONTRACTOR IS TO VISIT SITE AND VERIFY ALL CLEARANCES BEFORE FABRICATION OF DUCTWORK AND PROVIDE ADDITIONAL OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS AND COORDINATE WITH ELECTRICAL, PLUMBING AND FIRE PROTECTION SUBCONTRACTORS BEFORE ANY

CONSTRUCTION WORK.

19. FLEXIBLE AND RIGID ROUND DUCT TAKE-OFFS FOR DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER NECK. MAXIMUM

FLEXIBLE DUCT LENGTH SHALL BE 5'-0".

20. COORDINATE DUCT ELEVATION WITH RAIN LEADERS, WATER PIPING, SANITARY DRAINS AND MAJOR ELECTRICAL

CONDUITS.

21. CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND/SUPPORT MECHANICAL

EQUIPMENT AND MATERIALS.

22. IT IS THE RESPONSIBILITY OF THE MECHANICAL INSTALLER TO PATCH AND REPAIR ANY DUCT OPENINGS WHICH RESULT FROM THE RELOCATION OR ELIMINATION OF ANY EXISTING AIR DEVICES. THE PATCH IS TO BE OF A SIMILAR MATERIAL

TO THE REPAIRED DUCT AND TO BE SEALED IN ACCORDANCE WITH SMACNA STANDARDS.

23. PROVIDE ADDITIONAL DUCTWORK AND PIPING SUPPORTS ON BOTH SIDES AND WITHIN 18" OF FIRE RATED WALL.

DUCTWORK OR PIPING SHALL NOT BE SUPPORTED FROM ANY FIRE RATED WALL.

24. FOR DUCTWORK PENETRATING ONE HOUR FIRE RATED WALL, THE ENTIRE DUCT SYSTEM, TO BE CONSTRUCTED PER SMACNA STANDARDS WITH A MINIMUM OF 26 GA. STEEL DUCT AND SHALL CONTINUE IN THE HORIZONTAL DIRECTION WITHOUT ANY GRILLE OR OPENING FOR NOT LESS THAN 5'-0" FROM THE WALL AND DUCT SHALL NOT EXCEED SQUARE

INCH REQUIREMENTS OF LOCAL CODE, OTHERWISE A FIRE DAMPER SHALL BE PROVIDED.

25. PROVIDE TURNING VANES IN ALL RECTANGULAR SUPPLY DUCT ELBOWS WITH ANGLES FROM 45 DEGREES TO 90 DEGREES, PER FIGURES 4-3 AND 4-4 OF THE SMACNA MANUAL. PROVIDE SINGLE WALL VANE CONSTRUCTION FOR

DUCTS UP TO 48" WIDE, AND DOUBLE WALL VANE CONSTRUCTION FOR LARGER DIMENSIONS.

26. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS (FREE AREA).

27. CONTRACTOR SHALL COORDINATE ALL INTAKE/EXHAUST LOCATIONS TO ENSURE MINIMUM 10'-0" DISTANCE BETWEEN

ANY INTAKES AND VENTILATION EXHAUSTS, PLUMBING VENTS, RELIEF, ETC.

28. ALL HVAC EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS UNLESS INDICATED

OTHERWISE.

29. CONTRACTOR SHALL THOROUGHLY CLEAN AND ENSURE PROPER OPERATION OF ANY EXISTING HVAC EQUIPMENT. ANY CHANGE TO THE SYSTEM SHALL RESULT IN EQUIPMENT MODIFICATIONS (AS REQUIRED) INCLUDING BUT NOT LIMITED

TO REPLACING MOTORS, VFDS, PULLEYS, SHEAVES, BELTS, ETC.

30. CONTRACTOR SHALL PROVIDE A PERMANENT/PROFESSIONAL LABEL FOR EACH PIECE OF EQUIPMENT AND ASSOCIATED

THERMOSTAT(S) AND/OR SENSOR(S).

31. DUCTWORK, DIFFUSERS, REGISTERS, GRILLES, AND OTHER ITEMS OF THE AIR HANDLING SYSTEM SHALL NOT BE

SUPPORTED BY THE CEILING OR CEILING SUSPENSION SYSTEM.

32. ALL SUPPLY AND RETURN DUCTWORK SHALL BE EXTERNALLY INSULATED SHEET METAL CONSTRUCTION IN ACCORDANCE WITH LATEST SMACNA STANDARDS. DUCT INSULATION TO BE 2.0" THICK FOIL BACK WRAP, K=0.25 BTUH-IN./SF. HR° 1.50#/CF AS MANUFACTURED BY JOHNS MANVILLE. JOINTS TO BE STAPLED AND TAPED WITH PRESSURE SENSITIVE TAPE AS MANUFACTURED BY COMPAC INDUSTRIES MODEL #120 (FLAME SPREAD = 5, SMOKE

DEVELOPED = 10) OTHER ACCEPTABLE MANUFACTURERS ARE OWENS CORNING AND KNAUF.

33. EXPOSED DUCTWORK SHALL BE DOUBLE WALL INSULATED DUCT EQUAL TO LINDAB "SPIROSAFE OR SPIROOVAL DOUBLE WALL SELF SEALING DUCT" W/2" R=8 INSULATION. DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH LATEST SMACNA STANDARDS UNLESS OTHERWISE NOTED. ALL EXPOSED DUCT SHALL CONTAIN FACTORY ADDED DIFFUSERS/GRILLES. EQUAL TO SCHEDULED MAKE AND MODEL. PAINT GRIP AND PAINT PER ARCHITECT. UNLESS

OTHERWISE NOTED.

34. ALL EXHAUST DUCT WORK SHALL BE NON-INSULATED SHEET METAL UNLESS OTHER WISE NOTED.

35. FLEXIBLE DUCT SHALL HAVE CONTINUOUS TEAR RESISTANT LINER ENCASED BY INSULATING MATERIAL WITH AN OUTER VAPOR JACKET CONFORMING TO UL181 UNLESS THE FLEX DUCT MEETS THE CRITERIA STATED IN 2014 FLORIDA

BUILDING CODE-BUILDING SECTION 419.3.6.4.

36. COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES, FIRE SPRINKLER HEADS, AND OTHER DEVICES.

37. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

38. CLOSE OUT DOCUMENTS: CONTRACTOR SHALL MAINTAIN A SET OF AS-BUILT DRAWINGS AND KEEP CURRENT DURING CONSTRUCTION OF THE PROJECT. IT IS TO INCLUDE ALL CONTRACT CHANGES, MODIFICATIONS AND CLARIFICATIONS.

THIS SET TOGETHER WITH ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER AFTER

CONSTRUCTION COMPLETION.

MECHANICAL NOTES MECHANICAL LEGEND

DUCTWORK SYMBOLS

LIMIT OF DEMOLITION

(WALL TYPE)

(WALL TYPE)

DN

DN

UP

UP

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

SQUARE 4-WAY CEILING DIFFUSERS

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE

EXHAUST OR RETURN REGISTER OR TOP GRILLE

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

CONNECT NEW DUCT TO EXISTING DUCT

D

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

R

DNUP RETURN DUCT (UP & DOWN)

SQUARE 3-WAY CEILING DIFFUSERS

SQUARE 2-WAY CEILING DIFFUSERS

FC

10ø

FLEXIBLE CONNECTION, EQUIPMENT,

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW ROUND DUCT (INSIDE DIMENSIONS: DIAMETER)

EXISTING DUCT TO REMAIN

SMOKE DAMPER

MANUAL VOLUME DAMPER

FLEXIBLE DUCTWORK (INSULATED)

FIRE DAMPER

VIBRATION, OR SEISMIC

SUPPLY

RETURN45°

RETURN, NO SPLITTER (45° TAP)

STANDARD BRANCH SUPPLY OR

45°

COMBINATION FIRE/SMOKE DAMPER

AUTOMATIC CONTROL DAMPER MODULATING

AUTOMATIC CONTROL DAMPER TWO POSITION

AIR TERMINAL SYMBOLS

TERMINAL UNIT WITH ELECTRIC HEAT

PIPING SYMBOLS

HOT WATER HEATING SUPPLY

DRAIN LINE

HOT WATER HEATING RETURN

HWSH S

HWRH R

D

XXX EXISTING PIPE TO BE REMOVED

GENERAL PIPING SYMBOLS

ANCHOR

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE CONNECTION

ECCENTRIC REDUCER

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN)

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

PRESSURE GAGE

THERMOMETER

PIPE UP

PIPE DOWN

VALVE SYMBOLS

BALL VALVE

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

THREE-WAY TWO POSITION CONTROL VALVE

FLEXIBLE CONNECTION

DUCTWORK SYMBOLS

DD FS

D

CONTROLS SYMBOLS

T ROOM THERMOSTAT - WALL MOUNTED

H ROOM HUMIDITY SENSOR - WALL MOUNTED

10x8 NEW RECTANGULAR DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

10x8ø NEW OVAL DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

DRAWING SYMBOLS

1-ATU28-10

SYSTEM NUMBER

BUILDING NUMBER

TERMINAL UNIT NUMBER TYPICAL TERMINAL UNIT DESIGNATION

FD

SD

79392 Ryan E. Morriss, PE

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

AIR DEVICE SCHEDULE (SUPPLY)

MARK

BASIS OF DESIGN

TYPE

AIRFLOW PANEL

SIZE(IN.)

NECK

SIZE(IN.) REMARKS

MANUFACTURER MODEL MIN. MAX.

CD-1 PRICE ASPD PLAQUE FACE 30 CFM 80 CFM 24x24 6ø 1,2,3 CD-2 PRICE ASPD 85 CFM 180 CFM 24x24 8ø

AIR TERMINAL UNIT SCHEDULE

MARK LOCATION SYSTEM NOMINAL

SIZE

AIRFLOW MAX. TOTAL

UNIT

PRESSURE

DROP

HOT WATER HEATING COIL

CONTROL

TYPE

BASIS OF DESIGN

REMARKS

MAX CFM MIN CFM

HEATING

AIRFLOW

CFM

ENTERING

AIR TEMP.

F

ENTERING

WATER

TEMP.

LEAVING

WATER

TEMP.

HEATING

WA.FLOW

GPM

COIL

CAPACITY

BTU/H

HOT WATER

PIPING

RUNOUT SIZE

MANUFACTURER MODEL

NUMBER

1-ATU66-01 C702 (E)1-AH66 5 310 310 0.25 54.8 180 160 1.5 11,800 3/4" VAV CARRIER 35E-05 1,2,3,5

AIR DEVICE SCHEDULE (RETURN & EXHAUST)

MARK

BASIS OF DESIGN

TYPE

AIRFLOW PANEL

SIZE(IN.)

NECK

SIZE(IN.) REMARKS

MANUFACTURER MODEL MIN. MAX.

RG-1 PRICE 630D LOUVERED 40 CFM 100 CFM 24x24 - RG-2 PRICE 630D 300 CFM 595 CFM 24x24 - 1

NOTES:

1. FURNISH AND INSTALL WITH WHITE ALUMINUM GRILLE AND FACTORY PROVIDED SPEED CONTROLLER.

2. FURNISH AND INSTALL HANGING VIBRATION ISOLATOR AND NEOPRENE MOUNT HANGERS.

3. BASIS OF DESIGN EQUIPMENT WITH REQUIRED PERFORMANCE CHARACTERISTICS IS SCHEDULED. OTHER MANUFACTURERS ARE ACCEPTABLE, HOWEVER

EQUIPMENT NOT MEETING EQUIVALENT CRITERIA CANNOT BE CONSIDERED.

4. EQUIPMENT TO BE CONTROLLED BY ENVIRONMENTAL CONTROL PANEL, IN ORDER TO MAINTAIN SPACE PRESSURIZATION.

5. FURNISH AND INSTALL VFD TO MODULATE FAN OUTPUT FOR MAINTAINING ROOM PRESSURE SET POINT.

EXHAUST FAN SCHEDULE

MARK

BASIS OF DESIGN

TYPE SERVICE AIR FLOW

EXTERNAL

STATIC

PRESSURE

FAN

RPM

FAN

MOTOR

POWER

MOTOR

RPM

FAN

DRIVE

SOUND

LEVEL

(SONES)

ELECTRICAL

REMARKS

MANUFACTURER MODEL

NUMBER VOLTAGE PHASE

1-EFC703 GREENHECK SP-110-VG CEILING C703 100 CFM 0.30 in-wg 940 8 W 940 ECM 1.5 115 V 1 1,2,3

ABBREVIATIONS

(E) EXISTING

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ATU AIR TERMINAL UNIT

CAV CONSTANT AIR VOLUME

CD CEILING SUPPLY AIR DIFFUSER

CFM CUBIC FEET PER MINUTE

COR CONTRACTING OFFICER'S REPRESENTATIVE

CTE CONNECT TO EXISTING

EA EXHAUST AIR

EF EXHAUST FAN

FBC FLORIDA BUILDING CODE

FD FIRE DAMPER

FO FLAT OVAL

FPM FEET PER MINUTE

FSD COMBINATION FIRE SMOKE DAMPER

FT FOOT

GPM GALLONS PER MINUTE

HHWR HEATING HOT WATER RETURN

HHWS HEATING HOT WATER SUPPLY

IBC INTERNATIONAL BUILDING CODE

IN INCH

NC NOISE CRITERIA

OA OUTSIDE AIR

OAL OUTSIDE AIR LOUVER

OBD OPPOSED BLADE DAMPER

RA RETURN AIR

RG RETURN AIR GRILLE

SA SUPPLY AIR

SD SMOKE DAMPER

TAB TEST AND BALANCE

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

WG WATER GAGE

1-ATU66-02 (E)1-AH66 4 140 VAV

1-ATU66-03 (E)1-AH66 8 740 VAV

1-ATU66-04 (E)1-AH66 4 40 VAV

1-ATU66-05 (E)1-AH66 5 275 VAV

1-ATU66-06 (E)1-AH66 180 VAV

1-ATU66-07 (E)1-AH66 170 VAV 1,2,3,4,5

1-ATU66-08 (E)1-AH66 VAV

1-ATU66-09 (E)1-AH66 VAV

1-ATU66-10 (E)1-AH66 VAV

1-ATU66-11 (E)1-AH66 VAV

1-ATU66-12 (E)1-AH66 VAV

1-ATU66-13 (E)1-AH66 VAV

1-ATU66-14 (E)1-AH66 VAV

1-ATU66-15 (E)1-AH66 VAV

1-ATU66-16 (E)1-AH66 310 VAV

1-ATU66-17 (E)1-AH66 435 VAV

1-ATU66-18 (E)1-AH66 435 VAV

1-ATU66-19 (E)1-AH66 435 VAV

1-ATU66-20 (E)1-AH66 435 VAV

C708 C702 C707 B732

C710,C711,C712 C702A

1-EFC704 GREENHECK SP-110-VG CEILING C704 100 CFM 0.30 in-wg 940 8 W 940 ECM 1.5 115 V 1 1,2,3 1-EFC705 GREENHECK SP-110-VG CEILING C705 100 CFM 0.30 in-wg 940 8 W 940 ECM 1.5 115 V 1 1,2,3 1-EFC706 GREENHECK SP-110-VG CEILING C706 100 CFM 0.30 in-wg 940 8 W 940 ECM 1.5 115 V 1 1,2,3

C702B C702C C702D C702E C702F C702G C702H C702I C702N C702M C702L C702K C702J

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

CARRIER

35E-04 35E-08 35E-04 35E-05 35E-04 35E-04 35E-04 35E-04 35E-04 35E-04 35E-04 35E-04 35E-04 35E-04 35E-05 35E-06 35E-06 35E-06 35E-06

3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"

5,300 28,300 1,100 5,300 3,400 4,800 4,800 4,800 4,800 4,800 4,800 4,800 4,800 4,800 8,600

12,200

11,600

12,200 12,200

180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160 180 160

1.0 3.0 0.5 1.0 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 1.0 1.5 1.5 1.5 1.5

54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8 54.8

1-EFC702A GREENHECK SQ-80-VG IN-LINE C702A 260 CFM 0.30 in-wg 1408 0.04 HP 1408 ECM 6.2 115 V 1 2,3,4,5

CD-3 PRICE ASPD 185 CFM 340 CFM 24x24 10ø CD-4 PRICE ASPD 345 CFM 500 CFM 24x24 12ø

NOTES:

1. BASIS OF DESIGN EQUIPMENT WITH REQUIRED PERFORMANCE CHARACTERISTICS IS SCHEDULED. OTHER MANUFACTURES ARE ACCEPTABLE, HOWEVER

EQUIPMENT NOT MEETING EQUIVALENT CRITERIA CANNOT BE CONSIDERED.

2. EQUIPMENT TO BE CONTROLLED VIA A HIGH HUMIDITY SIGNAL FROM THE ISOLATION ROOM ENVIRONMENTAL CONTROL PANEL. FURNISH AND INSTALL ALL

REQUIRED ACCESSORIES FOR A COMPLETE AND FUNCTIONING INSTALLATION.

DEHUMIDIFIER SCHEDULE

MARK

BASIS OF DESIGN

TYPE SERVICE CAPACITY

EXTERNAL

STATIC

PRESSURE

CURRENT

DRAW

DRAIN

CONNECTION

SOUND

LEVEL

dBA

ELECTRICAL

REMARKS

MANUFACTURER MODEL

NUMBER VOLTAGE PHASE

1-DHC702A APRILAIRE 1830 DUCTED C702A 3/4" 47 120 V 1 1,2

1-ATU66-21 C702 (E)1-AH66 5 300 300 54.8 180 160 1.5 11,800 3/4" VAV CARRIER 35E-05300

RG-3 PRICE 630 40 CFM 100 CFM 24x24 8x8 1,2

PC ROOM PRESSURE CONTROLLER & DISPLAY - WALL MOUNTED

PS ROOM PRESSURE SENSOR - WALL MOUNTED

NOTES:

1. RUNOUT BRANCH DUCT SHALL BE SAME SIZE AS INDICATED NECK SIZE.

2. FURNISH AND INSTALL VOLUME DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.

3. FURNISH AND INSTALL ALL REQUIRED ACCESSORIES FOR A COMPLETE INSTALLATION.

4. FURNISH AND INSTALL FIELD FABRICATED PLENUM.

NOTES:

1. FURNISH AND INSTALL ALL REQUIRED ACCESSORIES FOR A COMPLETE INSTALLATION.

2. FURNISH AND INSTALL WITH RETURN AIR SILENCER.

PLAQUE FACE

PLAQUE FACE

PLAQUE FACE

1,2,3 1,2,3 1,2,3

LOUVERED

LOUVERED

0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25

CD-5 PRICE AS - - 48x3 6øONE SLOT LINEAR 1,2,3,4

70 PPD 0.0-0.4 W.C. 160-70 6.3 A

AIR

FLOW

CFM

1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5

1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5 1,2,3,5

1-EFC709 GREENHECK SP-110-VG CEILING C709 100 CFM 0.30 in-wg 940 8 W 940 ECM 1.5 115 V 1 1,2,3

J K P Q R R.4M.3K.8

10.8

J.9

10.5

9.5

8.8

9.8

Stair S7-6

Prep/Recovery

C702CC

Prep/Recovery C702I

Prep/Recovery

C702HH

Prep/Recovery

C702GC702G

Prep/Recovery C702F

Prep/Recovery C702E

Prep/Recovery

C702DD

Prep/Recovery C702B

Sterile Supply C711

Clean Linen C710

Elec E72

Comm T72

Elec C713

Toilet C705

Prep/Recovery

C702NN

Prep/Recovery

C702MC702M

Prep/Recovery C702L

Prep/Recovery

C702KK

Prep/Recovery C702J

Nurse Manager

C707

Storage C712

Soiled Utility C706

Staff Lounge/ Lockers

B732

Elece

B732AB732

Toilet C703C703

Isolation

C702AA

Nurse Station C708

Toilet C704

HAC

C709

Prep Recovery

Area C702

Corridor C7-3-1

Corridor C7-8-1 g

7 n eri ly ile p e

8088C7088 M

00600

20X14

U

-0

1-

A

TUU

1 1- A

TU

-0

1- A

TU

-0

U

1-ATU66-04

1- A

TU

-0

1-

A T

1- A

T g1- A

TU

-0

T 6-toratora

1- A

TU

-0

1- A

TU

-0

1- A

TU

-0

1- A

TU

-1

1- A

TU

-1

1- A

TU

-1

1- A

TU

-1

1- A

TU

-1

1- A

TU

-1

1- A

TU

-1

1- A

TU

-1

1- A

TU

-1

1- A

TU

-1

1- A

TU

-2

Corridor

UUU

TT

UUU

AAA

5" Ø

4"Ø

4" Ø

4" Ø

4" Ø

4" Ø

4" Ø

4" Ø

4" Ø

4" Ø

4" Ø

5" Ø

6" Ø

6" Ø

6" Ø

6" Ø

4" Ø

18X12

X

Re

/R C7 oilet 703703 e

Ut it

6"Ø

6"Ø

6"Ø" 6" Ø

6" Ø

6" Ø

16X12

UU

4" Ø

TT

8" Ø

C

Nurs a

Nu

14X101

12X8 10X610X6

6X

6X

6X

X

8X

8X

8X

8X

88X

8X

8X

6X

6X 10 6X

202AA02A2A2A2A7700000007C7777C77777777C7C7CC7CC7CCCCCCCCCCCCCCCCCCCCCCCCCCC

yy

CC7C7711777777C7CC7C7C77C77711717111771771711777110111111111

Lii 00000 inniiiiinnennennnnnneeeneeeneeeennnnnnnnnnn

MMMaManMMMM N

CD-2

8"ø

170 CFM

CD-2

8"ø

170 CFM

CD-2

8"ø

170 CFM

CD-2

8"ø

170 CFM

CD-2

8"ø

170 CFM

CD-2

8"ø

170 CFM

CD-2

8"ø

170 CFM

CD-2

8"ø

175 CFM

CD-3

10"ø

200 CFM

CD-2

8"ø

100 CFM

CD-2

8"ø

175 CFM

CD-3

10"ø

310 CFM

CD-444

12"ø

435 CFM

CD-4

12"ø

435 CFM

CD-4

12"ø

435 CFM

CD-4

12"ø

415 CFM

P e Pre P e P e P p/ C verye

UUUU

10X8

CD-5

6"ø

80 CFM

CD-2D 2DD 2-2DDDDD 2DD 222DDD 222222DDD 22-DDDD 2222

8"øøøøøøøøøøøøøøøø" 150 CFMFCC00 MMFMC M0 CC00 MFMCF0 CCFMMMM00 CCCCFMM0 CCFFFMMMMMMMCC MMFFCCCCCC00 MMFFFFCCC555

CD-2

8"ø

150 CFM

CD-3

10"ø10"

200 CFM (2)

CD-2

8"ø

170 CFM70 CF

CD-2

8"ø

170 CFM

CD-2

8"ø

140 CFM CD-1

6"ø

40 CFM

CD-1

6"ø6"ø

40 CFM

CD-11

6"ø6 ø

40 CFM

CD-1CD

6"ø6"ø

40 CFM

5"Ø ery

1-EFC7037 3037077

1-EFC706C

1-EFC705705505

1-EFC70404

1-DHC702AACHHCCHHHHHCC AAA2AA02077C

FS

D

FS

D

FS

D

FS

D

FS

D

1- E

FC

2A2

10"Ø10 ØØ

10"Ø

10X80 8

5" Ø

5" Ø

10X810 810X81

1-ATU66-21UUU111

RG-2

12x12

RG-1

8x8

RG-1

8x8

RG-1

8x8

RG-1

8x8

RG-1

8x8

RG-1

8x8

RG-1

8x8

RG-1

8x8

RG-3

8x8

RG-1

8x8

RG-2

12x12

RG-2

12x12

RG-2

12x12

RG-2

12x12

RG-2

12x12

RG-2

12x12

RG-2

12x12

RG-22

12x122x1 ep ery

CD-2

8"ø 150 CFMCFC0055 M1 FMCF0 C00551 MMFM1 000 CFFMM550 CCFFM15000 CCFMMMMFMFFCCC001 MMMFFFC555511 MMFCC00555150 CFMCF5 M005 FM1150 C50005 CFMCFMFFCC

FS

D

FFFFFFFFS

D

FFS

D

FFFS

D

FFS

D

FFFFS

D

FFFFFS

D

FFSFFFFFS

D

FFFFF

CD-5

6"ø

80 CFM

C

707709

ACHA

AAACCC

1-EFC709

6X

6X

6X

6X

6X

6X

RECOVERY

C709

RECOVERY

C710

PATIENT ROOM

C711

C711A C710A C709A

OUTPATIENT RECOVERY

C707

C707A

Comm T72

Elec E72

Elec C713

LOUNGE

C706

LINEN

C705

PROGRAM MANAGER

C705B

NURSE MANAGER

C704B

ENGINEERING STORAGE

B732

SOILED UTILITY

C702

OFFICE

C703

FOYER

C704

C706AC705A

SUPPLY

C712

Toilet B701

OO

O

NNAAMM

CC7

MANMMAM

MA

UU

OOOO EDLE

C

E

CC

EE

5B5

MAAMMAM

OIOSOO EDEDELEEE UU

CCCC 202

OSOOSO

C7C7C

ELLEEE

C 22

UUDD UU

T

SS

S

A MMM MM

CC

NANA

55B05

A NN

OOO

CCC 505

AMM

MMMMAMM NAANNN N

O

A C

AA

C

A C

A C

A

OV

OV

OVO

C O

N N

NN

79392 Ryan E. Morriss, PE

KEY PLAN

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

1. ALL EQUIPMENT WITHIN HATCHED AREA AND ALL PREVIOUSLY

ABONDONED EQUIPMENT SHALL BE REMOVED AND DISCARDED.

2. ALL EXISTING HYDRONIC PIPING IS TO BE REMOVED AND DISCARDED.

CAP HYDRONIC PIPING AT EXISTING FIRE RATED BARRIER WITHIN

SCOPE AREA.

3. REMOVE AND DISCARD ALL CONDENSATE BRANCH PIPING. ALL

CONDENSATE RISERS SERVING THE FLOORS ABOVE SHALL REMAIN.

4. ALL EXISTING PNEUMATIC CONTROL BRANCH PIPING SHALL BE

REMOVED AND DISCARDED. EXISTING PNEUMATIC MAIN RISERS

SHALL REMAIN AND BE CAPPED AT CONNECTION POINT.

A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE SCHEDULED AT

LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM. COORDINATE ALL

DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH THE COR.

B. EXISTING EQUIPMENT, PIPING, DUCTWORK, DIFFUSERS, GRILLES, AND ASSOCIATED

COMPONENTS SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS AND IS

PROVIDED FOR REFERENCE USE ONLY. FIELD VERIFY AND COORDINATE WITH EXACT

LOCATIONS, ELEVATIONS, SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

C. ALL EXISTING DUCTWORK TO BE REUSED SHALL BE PRESSURE TESTED,

THOROUGHLY CLEANED, AND SANITIZED TO AVOID POSSIBLE CONTAMINATION.

D. CONTRACTOR SHALL PAINT INTERIOR OF ALL GRILLES/DIFFUSERS VISIBLE FROM

SPACE FLAT BLACK. TYPICAL OF ALL.

E. PROVIDE THERMOSTAT AT 48" AFF WITH VENTILATED COVER AS DIRECTED.

F. ALL DUCTWORK/PIPING SHALL BE PROPERLY INSULATED AND ROUTED ABOVE

CEILING THROUGH FREE AREA OF STRUCTURAL MEMBERS. CONTRACTOR SHALL

COORDINATE AN FIELD VERIFY ALL ROUTING WITH OTHER TRADES PRIOR TO WORK.

G. CONTRACTOR SHALL PROVIDE A PERMANENT/PROFESSIONAL LABEL FOR EACH (AHU,

ATU) AND ASSOCIATED THERMOSTAT(S) AND TEMPERATURE SENSOR(S).

H. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

I. CONTRACTOR SHALL PROPERLY SEAL CAULK ALL PENETRATION THRU FIRE

RATED/SMOKE RATED/FIRE SMOKE RATED WALLS. (PER CODE)

J. ALL DUCTWORK/DIFFUSERS/GRILLES PENETRATING FIRE RATED CEILING/WALLS

SHALL CONTAIN FIRE DAMPERS, PER DETAILS.

K. CONTRACTOR SHALL VERIFY WALL/FLOOR TYPES PRIOR TO WORK INSTALLING FIRE

AND/OR SMOKE DAMPERS IN DUCT WORK AT ALL FIRE/SMOKE RATED WALL/FLOOR

PENETRATIONS. PER SPEC.

L. DUCTWORK UP STREAM OF ATU BOX SHALL EQUAL ATU BOX OPENING. ALL

DUCTWORK DOWN STREAM OF ATU BOX SHALL ADAPT TO ATU OPENING VIA

FLEXIBLE CONNECTIONS.

XX

GENERAL NOTES

DEMOLITION KEYNOTES

Scale: 1/8" = 1'-0"2 SEVENTH FLOOR RENOVATION PLAN - MECHANICAL HVAC

Scale: 1/8" = 1'-0"1 SEVENTH FLOOR DEMOLITION PLAN - MECHANICAL HVAC

11 TYP.T

22 TYP.T

33 TYP.YPPT

44TYP.

1. PROVIDE SPACE WITH WALL-MOUNTED SPACE TEMPERATURE,

HUMIDITY, AND PRESSURE DIFFERENTIAL SENSORS, AND

ENVIRONMENTAL CONTROLLER FOR DISPLAY AND CONTROL OF

OCCUPANCY STATUS. INTERLOCK WITH DEVICES TO PROVIDE SPACE

EXHAUST AIR AND AIR TERMINAL UNIT TO MAINTAIN AIRFLOW OFFSET

AND SPACE PRESSURE DIFFERENTIAL DURING ANY CHANGE IN

SUPPLY AIRFLOW. COORDINATE EXACT LOCATIONS OF

WALL-MOUNTED DEVICES WITH THE VA.

2. LOCATE ENVIRONMENTAL CONTROL PANEL WITHIN LINE OF SIGHT OF

ENTRANCE TO ISOLATION ROOM.

3. LOCATE DEHUMIDIFIER WITHIN THE CEILING SPACE ABOVE THE DOOR

OF THE RESTROOM.

4. ALL ATU BOXES SHALL BE LOCATED WITHIN LAYIN CEILING AREAS.

5. PROVIDE FIRE/SMOKE DAMPER AT RATED WALLS. FIRE/SMOKE

DAMPERS TO REQUIRE 120V POWER AND 24V SIGNAL FROM FAP.

COORDINATE WITH DIVISION 26 & 28 CONTRACTOR FOR FINAL

CONNECTIONS.

6. CONTRACTOR TO COORDINATE WITH V.A. ADMINISTRATION TO

ENSURE EXISTING EXHAUST FAN IS OPERATIONAL.

7. EXHAUST DUCTED INTO EXISTING EXHAUST CHASE. TYPICAL.

8. EXHAUST DUCTED UP INTO EXISTING EXHAUST CHASE AT FLOOR

ABOVE. PROVIDE FSD AT CHASE PENETRATION.

9. ALL THERMOSTATS SHALL BE MERCURY FREE.

10. DURING CONSTRUCTION, NO REFRIGERANT SHALL BE DISCHARGED

AT ANY TIME.

XXXXXXXXXXXXXXXXXXXX RENOVATION KEYNOTES

44 TYP.YP 55TYP.

TYP.

J K P Q R R.4M.3K.8

10.8

J.9

10.5

9.5

8.8

9.8

Stair S7-6

Prep/Recovery

C702CC

Prep/Recovery C702I

Prep/Recovery

C702HH

Prep/Recovery

C702GC702G

Prep/Recovery C702F

Prep/Recovery C702E

Prep/Recovery

C702DD

Prep/Recovery C702B

Sterile Supply C711

Clean Linen C710

Elec E72

Comm T72

Elec C713

Toilet C705

Prep/Recovery

C702NN

Prep/Recovery

C702MC702M

Prep/Recovery C702L

Prep/Recovery

C702KK

Prep/Recovery C702J

Nurse Manager

C707

Storage C712

Soiled Utility C706

Staff Lounge/ Lockers

B732

Elece

B732AB732

Toilet C703C703

Isolation

C702AA

Nurse Station C708

Toilet C704

HAC

C709

Prep Recovery

Area C702

Corridor C7-3-1

Corridor C7-8-1

1-ATU66-0111111111

1-ATU66-02

1-ATU66-03U6

1-ATU66-04

1-ATU66-051 ATUU66 055

1-ATU66-06-

1-ATU66-076111---AAAAAAA

1-ATU66-08 1-ATU66-09 1-ATU66-10 1-ATU66-11

1-ATU66-12

1-ATU66-13 1-ATU66-14 1-ATU66-15

1-ATU66-16 1-ATU66-17 1-ATU66-18 1-ATU66-19 1-ATU66-20

y

P

1 1/2" HHWR

1 1/2" HHWS

1" HHWSH WWWWWWWWWWWWWWWWWWWWWSWWWWWSWWSSSSSSSSSSSSSSSSSSSWWWWWWWWWWWWWSSSSSSWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWWSSSSSSSSSSSSSWWWW1111111111111111111111111111111111

1" HHWRH

3/ 4"

H H

W

SS

3/ 4"

H H

W R

1/

4" H

H W

S

1/

4" H

H W

R y P

3/ 4"

H H

W S

3/ 4"

H H

W R

1-ATU66-21

3/4" HHWS TYP.W

3/4" HHWR TYP.W

1 1/4" HHWR

1 1/4" HHWS

3/4" HHWSHH

3/4" HHWRHHHH

ery

RECOVERY

C709

RECOVERY

C710

PATIENT ROOM

C711

C711A C710A C709A

OUTPATIENT RECOVERY

C707

C707A

Comm T72

Elec E72

Elec C713

LOUNGE

C706

LINEN

C705

PROGRAM MANAGER

C705B

NURSE MANAGER

C704B

ENGINEERING STORAGE

B732

SOILED UTILITY

C702

OFFICE

C703

FOYER

C704

C706AC705A

SUPPLY

C712

Toilet B701

E

A07ACCA 706C7C

E

OY

C7

OYE

C

Y

C7 5A CC7 6A 7CC 077A

C O

7040047 O

YERE

C707 AA 707C7C7 6AA C7CCCC 7AA777A

FFFFF R

C711A7 AC 1

79392 Ryan E. Morriss, PE

KEY PLAN

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

1. REMOVE EXISTING MECHANICAL PIPING BACK TO BRANCH MAIN OR AS

INDICATED. CAP PIPING TO MATCH EXISTING.

2. CONTRACTOR TO FIELD DETERMINE SIZE, LOCATION, CONDITION, AND

MATERIAL TYPE OF THE EXISTING HOT WATER HYDRONIC PIPING. REPAIR

AS NEEDED.

A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.

COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH

THE COR.

B. EXISTING EQUIPMENT, PIPING, DUCTWORK, DIFFUSERS, GRILLES, AND

ASSOCIATED COMPONENTS SHOWN ON DRAWINGS ARE APPROXIMATE

LOCATIONS AND IS PROVIDED FOR REFERENCE USE ONLY. FIELD VERIFY

AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS, SIZES, AND

CONDITIONS OF EXISTING COMPONENTS.

C. PROVIDE MERCURY FREE THERMOSTAT AT 48" AFF WITH VENTILATED COVER

AS DIRECTED.

D. CONTRACTOR SHALL PROVIDE A PERMANENT/PROFESSIONAL LABEL FOR

EACH (AHU, ATU) AND ASSOCIATED THERMOSTAT(S) AND TEMPERATURE

SENSOR(S).

E. ALL TERMINAL UNITS ABOVE CEILING REQUIRE FACTORY FABRICATED

ACCESS PANELS. COORDINATE WITH ARCHITECT FOR CEILING TYPE.

F. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

G. CONTRACTOR SHALL PROPERLY SEAL CAULK ALL PENETRATIONS THRU FIRE

RATED/SMOKE RATED/FIRE SMOKE RATED WALLS. (PER CODE)

H. HOT WATER PIPES INTERNAL TO BUILDING SHALL BE INSULATED WITH 3/4"

THICK FIBERGLASS INSULATION.

XX

GENERAL NOTES

DEMOLITION KEYNOTES

Scale: 1/8" = 1'-0"1 SEVENTH FLOOR PLAN - MECHANICAL PIPING

Scale: 1/8" = 1'-0"2 SEVENTH FLOOR DEMOLITION PLAN - MECHANICAL PIPING

11TYP.

1. PERFORM TEST AND BALANCE OF HEATING HOT WATER SYSTEM AND

BALANCE AIR TERMINAL UNIT WATER COIL TO SCHEDULED VALUES.

2. PROVIDE SHUT OFF VALVES FOR SUPPLY AND RETURN HEATING HOT

WATER AT ALL ATU'S.

3. CONNECT NEW TO EXISTING. FIELD VERIFY EXISTING SIZE AND LOCATION.

XXXXXXXXXXXXXXXXXXXX RENOVATION KEYNOTES

22TYP.

11 TYP.TTYPT PP