36C24818R0737-027.pdf
PDF 27 MB Posted
- Attached to
- Project 546-16-104 Renovate Ambulatory Surgery
- Solicitation number
- 36C24818R0737
About this file
36C24818R0737 546-16-104 Final Submittal Drawings_Part4.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24818R0737-0003000.docx | DOCX document | |
| 36C24818R0737-0002000.docx | DOCX document | |
| 36C24818R0737-0002003.pdf | ||
| 36C24818R0737-0002001.pdf | ||
| 36C24818R0737-0002002.pdf | ||
| 36C24818R0737-0001001.pdf | ||
| 36C24818R0737-0001000.docx | DOCX document | |
| 36C24818R0737-026.pdf | ||
| 36C24818R0737-024.pdf | ||
| 36C24818R0737-021.pdf | ||
| 36C24818R0737-029.pdf | ||
| 36C24818R0737-023.pdf | ||
| 36C24818R0737-019.docx | DOCX document | |
| 36C24818R0737-020.pdf | ||
| 36C24818R0737-022.pdf | ||
| 36C24818R0737-025.pdf | ||
| 36C24818R0737-028.pdf | ||
| 36C24818R0737-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
79392 Ryan E. Morriss, PE
COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
NOTES:
1. PROVIDE STRAIGHT RIGID DUCT WITH MINIMUM LENGTH OF 3 TIMES THE INLET DIAMETER AT THE INLET OF EACH TERMINAL UNIT.
2. INLET DUCT SHALL BE THE SAME SIZE AS INLET OF TERMINAL UNIT. IF INLET DUCT EXCEEDS 5 FT. LENGTH, USE DUCT 4" LARGER
THAN INLET DIAMETER TO WITHIN 3' FROM UNIT, THEN REDUCE TO SAME SIZE AS INLET.
3. CONTRACTOR MAY USE 3'-0" MAXIMUM LENGTH OF FLEXIBLE DUCT UP TO 3 DIAMETERS FROM TERMINAL INLET TO OPTIMIZE
PLACEMENT OF UNIT AND ACCOMMODATE FOR MINOR OFFSETS.
4. LOCATE TERMINAL UNIT SO THAT WORKING CLEARANCE IS NOT OBSTRUCTED BY LIGHTS, STRUCTURE, OR OTHER ITEMS. IF
TERMINAL UNIT IS LOCATED ABOVE AN INACCESSIBLE CEILING, PROVIDE A MINIMUM 18"x18" CEILING ACCESS PANEL FOR TERMINAL
UNIT WITHIN WORKING CLEARANCE SPACE.
5. LOCATE VALVES, STRAINERS, AND OTHER APPURTENANCES ACCESSIBLE WITH WORKING CLEARANCE. INSTALL CONTROL VALVE
ACTUATOR ACCESSIBLE; DO NOT INSTALL AGAINST CEILING.
6. PROVIDE A MINIMUM 6'-0" DUCT LENGTH BETWEEN TERMINAL UNIT DISCHARGE AND FIRST BRANCH TAKE-OFF FITTING.
TYPICAL MANUAL AIR VENT
TYPICAL CHILLED AND HOT WATER PIPING
DRAIN VALVE CONNECTIONS
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" BALL VALVE
ADAPTER TO 3/4" HOSE THREAD,
PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR
PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
AIR VENT
1/2" BALL VALVE
1/4" COPPER TUBING
1/2" x 4" NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
MV
OR
AV
OROR
DRAIN VALVE CONNECTIONS DETAIL
NTS2
AIR TERMINAL UNITS DETAIL
NTS1AIR VENT CONNECTIONS DETAIL
NTS7
HWS
HWR
MIN. 3 DIAMETERS
RIGID DUCT 1-ATUX-XX
MINIMUM 6'-0"M
TO DIFFUSERS
INLET DUCTT
45 DEGREE TAKE-OFF
WITHOUT DAMPER
MAIN DUCT
AIR VALVEE
PROVIDE MINIMUM 3'-0"
WORKING CLEARANCE IN
FRONT OF CONTROL BOX
AHU SYSTEM NUMBER
TERMINAL UNIT
NUMBER
AIR TERMINAL UNIT
45 DEGREE TAKE-OFF
WITH DAMPER
NOTE 3
HOT WATER REHEAT COIL
CONTROL BOX
2 POSITION
BINARY POINT
FIRE/SMOKE DAMPER CONTROL DIAGRAM
NTS3
ADD
SMOKE DAMPER (N.C.)
SEE SCHEDULE
SD
NOTE:
UPON DETECTION OF SMOKE BY THE SMOKE DETECTOR, THE SMOKE DAMPER SHALL
CLOSE & SEND AN ALARM TO THE ECC.
M
DUCT TRANSITION
AS REQUIRED
TO FIRE
ALARM CONTROL
PANEL (FACP)
120V
ELECTRICAL
POWER
AIRFLOW
AIR
DUCT
SMOKE PARTITION
ZS
PSH
PRESSURE SWITCH HIGH
TO SHUT DOWN FAN UPON
REACHING HIGH PRESSUREE
SETPOINT
DAMPER POSITION
FEEDBACK TO ECC
TERMINAL UNIT WATER COILS -
PIPING CONNECTIONS
NTS4
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
DI-ELECTRIC UNION
CONNECTIONS (TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH
HOSE CONNECTION
MV
MODULATION CONTROL VALVE
STRAINER
5 FT
6 8 10
9 1110 12
-1312 14 -16 -
1614 17 2219 23
2725 28 3230
20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
SIDE VIEW TRAPEZE HANGER FOR
UP TO 1000 LB. UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
FT.
FT.
1" MAX.
PIPE HANGERS DETAIL
NTS6
PROVIDE INSULATION
SHIELD & INSERT FOR ALL
PIPING (8" MIN.)
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2" x 2" x 1/4" ANGLE
1/2" DIA. HANGER RODS
WITH 36" MAX. SPACING
ON EACH CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION
(9 PSF MIN. DENSITY)
UNDER INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTE:
SEE SPECIFICATIONS FOR
DETAILED HANGER
REQUIREMENTS
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
420ONE 1 x 18 GA STRAP36
TWO 1/2ø RODS TWO 3/8ø. RODS ONE 1 x 16 GA STRAP
50 700
ONE 1 x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT ø
MAX. LOAD
LBS.
MAX.
IN.
SPACING
IN. IN.
HANGER RODS
BAND OF SAME
SIZE AS HANGER
STRAP
LOAD RATED
FASTENERS
50" ø &
UNDER
HANGER STRAPS OR RODS
BAND
OVER 50"ø
ROUND DUCT HANGERS
NTS5
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING
AND INSULATION, BUT NO EXTERNAL
LOAD.
EXTERIOR SKIN
WALL PANEL
AS SPECIFIED
MASTIC
INTERIOR SKIN
GASKET
S.S. WALL PLATE
SECURED WITH S.S.
SCREWS
PIPE INSULATION AS
SPECIFIED
SEAL INSULATION
AGAINST SKIN
OF WALL PANEL
TUBING, PIPING
OR CONDUIT
S.S. WALL PLATE
SECURED WITH S.S.
SCREWS
FIELD APPLIED INSULATION AFTER
INSERTION OF RESPECTIVE SERVICEC
FACILITY
TUBING, PIPING, AND CONDUITS PASSING
THROUGH PRE-FAB INSULATED WALL PANELS
NTS8
COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
NOTE:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W1 EQUALS W2 AND W1 IS GREATER THAN 36" [500mm] VANES SHALL BE DOUBLE
VANE TYPE.
VANE
VANE
NOTE:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL
SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,
SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
R SHALL
EQUAL OR
BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/3W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/6W.
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
PLAN VIEW
AIR
FLOW AIR
FLOW
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" MIN.
BRANCH DUCT
AIR
FLOW
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
PROVIDE VOLUME DAMPER
1/4 W OR 4" MIN.
MAIN DUCT
ROUND BRANCH DUCT TAKE-OFF
PLAN VIEW
RECTANGULAR OR
ROUND SHEET
METAL DUCT. SEE
PLANS FOR SIZES.
12" MIN
END OF DUCT
CONNECTING
TO AIR DEVICE
AIR SPLIT DUCT TAKE-OFF PLAN
VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
AIRAIR
FLOWFLOW
A
IR
A
IR
FL
O
W
FL
O W
SUPPLY REGISTERSUPPLY REGISTER
OR BRANCH DUCTOR BRANCH DUCT
PROVIDE VOLUMEPROVIDE VOLUME
DAMPERDAMPER
AIRAIR
FLOWFLOW
A
IR
A
IR
FL
O
W
FL
O W
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION STAND-OFFOFF
1/2" ROUND ROD PIN
DUCTT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
RETURN AIR
GRILLE/REGISTER
NOTE:
1. PAINT INTERIOR SURFACE (VISIBLE FROM BELOW) WITH FLAT BLACK
ENAMEL PAINT.
ACCOUSTICALLY
LINED SHEET METAL
PLENUM
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED
CONNECTION ON FAN
SIDE
WASHER 1-1/2" MIN. TO 3" MAX. INSTALLED.
6" NOMINAL WITH MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1" x 1/8" DRAW BAND
1" x 1/8" BAND IRON
BOLT ON 4" CENTERS
5/16" FLANGE
DUCT
SHEET METAL SCREWS
ON 12" CENTERS
RIVET ON
4" CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
1" x 1/8" BAND IRON
BOLT ON 4" CENTERS
1" FLANGE & HEMALTERNATE
POSITION
OF BOLT 1 1/2" POCKET SLIP
DUCT
SHEET METAL AS SPECIFIED
FOR DUCTWORK
1/2" 1-1/2"
1-1/2" MIN. TO 3" MAX. INSTALLED.
6" NOMINAL WITH MATERIAL TAUT
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
NOTES:
1. A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION IS SIMILAR. FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE
INSTALLED IN THE PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.
2. GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER FRAME AND TO PERIMETER
ANGLES.
3. PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1-1/2" x 1-1/2", 14 GAGE, TO PROVIDE 1" MINIMUM OVERLAP OF
OPENING ON ALL 4 SIDES.
4. BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
5. ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.
6. PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH ROCK WOOL FIRESTOP FIBER.
7. ALL DUCTWORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND MECHANICAL ROOM FLOORS, SHALL
BE PROVIDED WITH 3" HIGH CONCRETE CURB AROUND OPENING FOR DUCT.
SLEEVE, NOTE 2
DUCT
CONNECTION,
NOTE 4
DAMPER,
NOTE 1
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6FIRE BARRIER
PARTITION OR CHASE
TYPICAL DUCT
INSULATION
PERIMETER ANGLE, NOTE 3
(NOTE FASTENED TO PARTITION)
ACCESS
PANEL,
NOTE 5
SECTION "A-A"
"B" "B""
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
4. USE ACCESS DOORS ON AIR HANDLING UNITS AND DUCTWORK INSTALLED IN EQUIPMENT ROOMS.
5. USE ACCESS PANELS ON ALL EQUIPMENT AND DUCTWORK INSTALLED ABOVE FINISHED CEILINGS.
ACCESS PANEL
ACCESS DOOR
CASING
GASKET HANDLE INSIDE
FLEXIBLE WASHER
FACTORY FABRICATED LATCH
SECTION "B-B"
INSULATION
DUCT
GASKET
INSULATION
INSULATION
"A"
"A"
NOTE:
1. UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
MAX.X
M
AX
E Q
U
IP
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
MAX.
M
AX
M A
X
M
AX
EXHAUST OR
RETURN MAIN
OR SUB-MAIN
HOUSING WELDED
TO DUCT SECTION
ROUND OR
FLAT OVAL
DUCT SECTION
COVER WITH HANDLE
AND CHAIN RETAINER
GASKETED AND
PRESSURE SEALED
1/2"
FIRE DAMPER DETAIL
NTS1
RETURN AIR GRILLE DUCT CONNECTION DETAIL
NTS2
DUCTWORK TRANSITIONS DETAIL
NTS3EXHAUST OR RETURN BRANCH DUCTWORK
NTS5
DUCT TAKEOFF DETAILS
NTS4
DUCTWORK SQUARE VANE ELBOWS
NTS6
DUCTWORK RADIUS ELBOWS
NTS7
VOLUME DAMPER DETAIL
NTS8
ACCESS PANEL AND DOOR DETAIL
NTS9
FLEXIBLE DUCT CONNECTIONS
NTS10
ACCESS SECTION FOR ROUND/OVAL DUCT
NTS11
D
(DIAMETER))( ))))))))))((((((((((
1" WIDE FLANGE WITH
NEOPRENE GASKET
SEAL AROUND ENTIRE
PERIMETER
NOTE:
1. WHEREVER THE DEPTH OF THE TRUNK DUCT IS
LESS THAN ROUND RUNOUT DUCT DIAMETER,
PROVIDE TRANSITION FITTING OF EQUIVALENT
AREA TO THE RUNOUT DUCT.
AIRAIR
FLOWFLOW
SMACNA FIGURE 4-6
45° ENTRY
1" WIDE FLANGE WITH
NEOPRENE GASKET SEAL
AROUND ENTIRE PERIMETER
PROVIDE OPPOSED BLADE
MANUAL BALANCING
DAMPER; OPERATOR SHALL
PENETRATE INSULATION
USE ROUND TAKE-OFF FOR
SUPPLY AIR TO NOT MORE
THAN ONE TERMINAL
R
R
WW
15°
W
R
W
2/3W
1/ 3W
W
1/2W
1/ 3W
1/6W
W
W1
W
COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
ROOM THERMOSTAT/SENSOR
WALL MOUNTED 48" AFF.
ATU
RHCHWS
HWR
V-1
REHEAT
COIL
AIRA
TERMINAL
UNIT
AIR
FLOW
T
ATU
CONTROLLER
PC
TE
A
IR
F
LO
W (C
FM
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
SP
VAV BOX CONTROL SEQUENCE
W/DEADBAND
100%
VA
V
AI
R
FL
OWREHEAT FLOW
A. SET POINTS SHALL BE SET AS FOLLOWS:
COOLING 75°F (ADJUSTABLE)
HEATING 70°F(ADJUSTABLE)
DEADBAND OF 5° F BETWEEN HEATING AND
COOLING SET POINTS WILL BE MAINTAINED.
B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL
MODULATE TO MINIMUM POSITION.
C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL
MODULATE TO MAINTAIN SET POINT + 0.5°F. THE ADJUSTABLE
TOLERANCE OF + 0.5°F HAS BEEN SELECTED TO PREVENT VALVE
HUNTING
D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.
FE
VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM
NTS
NOTES:
EACH TERMINAL UNIT SHALL BE CONTROLLED BY A DEDICATED, UNIT
MOUNTED, STANDALONE CONTROLLER. THE CONTROLLER SHALL MONITOR
AND CONTROL EACH UNIT IN STAND-ALONE MODE OR AS DIRECTED BY
BUILDING AUTOMATION SYSTEM.
ALL AIR TERMINAL UNITS SHALL BE PRESSURE INDEPENDENT TYPE WITH
VELOCITY RESET CONTROLLERS. ALL TERMINAL UNITS SHALL BE CAPABLE
OF VARIABLE VOLUME ALTHOUGH SOME WILL ACT AS CONSTANT VOLUME.
INPUTS
ANALOG
MEASURED
BINARY BINARY ANALOG ALARMS PROGRAMS
GENERAL
OUTPUTS SYSTEM FEATURES
SYSTEM
APPARATUS
OR AREA
POINT
DESCRIPTION
BUILDING AUTOMATION SYSTEM INPUT/OUTPUT AIR TERMINAL UNIT
X1-ATU66-01
1-ATU66-02
1-ATU66-03
1-ATU66-04
1-ATU66-05
1-ATU66-06
1-ATU66-07
1-ATU66-08
1-ATU66-09
1-ATU66-10
1-ATU66-11
1-ATU66-12
1-ATU66-13
1-ATU66-14
1-ATU66-15
1-ATU66-16
1-ATU66-17
1-ATU66-18
1-ATU66-19
1-ATU66-20
1-ATU66-21
A
IR
F
LO
W S
E N
S O
R
S P
A C
E T
E M
P E
R A
TU
R
E S
E N
S O
R
D
IS
C H
A R
G E
A
IR
T E
M P
V O
L.
A
IR
F
LO
W
O
FF
S E
T
TR
A C
K
IN
G
S P
A C
E H
U M
ID
IT
Y
A
IR
C O
N
TR
O L
D A
M P
E R
U N
O C
C U
P
IE
D T
E N
A N
T O
V E
R R
ID
E
H E
A
TI
N G
M O
D E
C O
O
LI
N G
M O
D E
H E
A
TI
N G
W A
TE
R
C O
N
TR
O L
V A
LV
E
U N
O C
C U
P
IE
D M
O D
E
S P
A C
E E
N V
IR
O
N M
E N
TA
L
C O
N
TR
O
LL
E R
X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
X X X X X X X XXXX
H
IG
H T
E M
P E
R A
TU
R
E L
E V
E L
LO
W
T E
M P
E R
A
TU
R E
L E
V E
L
H
IG
H H
U M
ID
IT
Y L
E V
E L
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
LI
V
E D
A
TA
S
TR
E A
M
C O
LO
R
G R
A P
H
IC
S
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
Dale A Bacik, PE
COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
1. THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS AND ABBREVIATIONS FOR
REFERENCE ONLY. SYMBOLS SHOWN ON THIS DRAWING MAY NOT APPEAR ON THE
FOLLOWING DRAWINGS.
2. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED SHUTDOWNS ON EXISTING
UTILITIES WITH THE VA IN ORDER TO MINIMIZE IMPACT TO OTHER AREAS.
3. ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE NEC, IBC, NFPA, AND ANY
APPLICABLE LOCAL ORDINANCE AND STANDARDS.
4. ALL WIRING SHALL BE IN CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4". MINIMUM
CONDUCTOR SIZE SHALL BE #12 AWG. ALL NEW CIRCUITS SHALL BE PROVIDED WITH AN
INDIVIDUAL NEUTRAL AND GROUNDING CONDUCTOR WITH THE PHASE CONDUCTOR.
5. THE ELECTRICAL DRAWINGS ARE SCHEMATIC IN NATURE. BEFORE STARTING THE WORK
THE CONTRACTOR SHALL REVIEW ALL OTHER DISCIPLINE DRAWINGS AND VERIFY FIELD
CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA
COST TO THE VA. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE
ATTENTION OF THE VA REPRESENTATIVE BEFORE PERFORMING CHANGES.
6. ALL CONDUITS INSTALLED INTERIOR SHALL BE EMT. ALL CONDUITS INSTALLED
EXTERIOR SHALL BE PVC SCHEDULED 40.
7. CONDUCTORS #10 AND SMALL SHALL BE STRANDED COPPER. CONDUCTORS #8 AND
LARGER SHALL BE STRANDED COPPER. UNLESS NOTED OTHERWISE, CONDUCTORS
INSULATION SHALL BE DUAL RATED AT THHN/THWN.
8. ALL DEVICES, EQUIPMENT MATERIAL AND LABOR SHALL BE PROVIDED BY THE
CONTRACTOR UNLESS NOTED OTHERWISE.
9. FOR EQUIPMENT TO BE CONNECTED TO EXISTING PANELBOARDS, THE CONTRACTOR
SHALL BE RESPONSIBLE FOR INSTALLING NEW BREAKERS. NEW BREAKERS SHALL HAVE
INTERRUPTING CAPACITIES EQUAL TO EXISTING UNITS. THE CONTRACTOR SHALL
VERIFY THAT PANELBOARDS HAVE ADEQUATE CAPACITY FOR THE NEW LOAD. IF A
PANELBOARD IS FOUND NOT TO HAVE ENOUGH CAPACITY, THE CONTRACTOR SHALL
THE BRING ISSUE TO THE ATTENTION OF THE VA REPRESENTATIVE.
10.
11. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE MOUNTED AS PER EQUIPMENT
AND DEVICE MANUFACTURER RECOMMENDATIONS.
12. CONTRACTOR SHALL PROVIDE SUBMITTALS TO VA REPRESENTATIVE FOR REVIEW AND
APPROVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES DESCRIBED IN THE SUBMITTAL
REGISTER. SUBMITTALS SHALL INCLUDE CUT SHEETS, DIMENSIONS, WIRING DIAGRAMS,
ACCESSORIES, OPERATION MANUALS, AND ALL NECESSARY INFORMATION FOR
REVIEWER TO MAKE A SOUND EVALUATION.
13. PROVIDE STARTUP OF ALL ELECTRICAL SYSTEMS AND COORDINATE WITH VA
REPRESENTATIVE FOR STARTUP WITNESSING.
14. PROVIDED LAMINATED PLASTIC NAMEPLATES FOR EACH EQUIPMENT ENCLOSURE. EACH
NAMEPLATE IDENTIFY EQUIPMENT FUNCTION, PANELBOARD CONNECTED AND CIRCUIT
NUMBER. NAMEPLATE SHALL BE MELAMINE PLASTIC (0.125 INCHES THICK), WHITE
LETTERS ON BLACK BACKGROUND (NORMAL POWER) AND WHITE LETTERS ON RED
BACKGROUND (CRITICAL POWER). MINIMUM SIZE OF LETTERS SHALL BE 2.5 INCHES. IN
ADDITION TO EQUIPMENT TAGGING, CONTRACTOR SHALL PROVIDE ARC-FLASH
WARNING SIGNS FOR PANELBOARDS.
15. PROVIDE COMPUTER PRINTED ON WHITE WRAPAROUND PAPER WITH CLEAR PLASTIC
PROTECTION TAIL FOR ALL WIRE MARKERS. MARKER SHALL STATE PANELBOARD NAME
AND CIRCUIT NUMBER ON ALL WIRES IN JUNCTION/PULL BOXES AND IN EQUIPMENT
TERMINAL BOXES.
16. PROVIDE PUNCHED TAPE LABELS ON ALL WIRING DEVICES FOR IDENTIFICATION. SHALL
BE ½” BLACK TAPE WITH WHITE RAISED LETTERS. TAPE LABELS SHALL STATE
PANELBOARD NAME AND CIRCUIT NUMBER.
17. PROVIDE DIRECTORIES ON ALL PANELBOARDS. BALANCE ALL LOADS ON PANELBOARD
WITHIN 10%.
18. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE SET OF RECORD
DRAWINGS TO THE VA AT THE END OF THE CONSTRUCTION.
19. ALL MATERIALS AND EQUIPMENT TO BE INSTALLED SHALL BE NEW AND FREE OF
DEFECTS. ALL ELECTRICAL EQUIPMENT SHALL COMPLY WITH NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION (NEMA) STANDARDS AND SHALL BE UL LABELED. ALL
ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN A WORKMANLIKE
MANNER.
20. ALL CONNECTORS AND SPLICES FOR CABLE SIZE #10 AWG AND SMALLER SHALL BE
INSULATED, PRESSURE-TYPE. FOR LARGER SIZE CONDUCTORS USE BOLTED CLAMPS
WITH INSULATING TAPE.
21. PROVIDE INSULATION AND CONTINUITY TEST OF ALL 1000V AND LESS WIRES AND
CABLES. USE TESTING PROCEDURES DESCRIBED IN INTERNATIONAL ELECTRICAL
TESTING AGENCY (NETA) STANDARDS. REPLACE ANY CABLES WITH INSULATION
RESISTANCE LESS THAN 100 MEGA OHMS (MOHMS). TEST ALL GROUND FAULT CIRCUIT
INTERRUPTING (GFCI) RECEPTACLES. TEST ALL GROUNDING ELECTRODE SYSTEMS WITH
FALL OF POTENTIAL METHOD. MAKE RESISTANCE MEASUREMENTS 48 HOURS AFTER
LAST RAIN FALL. MAXIMUM RESISTANCE TO GROUND SHALL BE 5 OHMS.
1. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,
CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP
CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE
WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND
REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
2. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT
PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.
3. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS
PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
1. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED
FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
2. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS
CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND SWITCH.
3. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
4. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
ELEMENTARY DIAGRAM SYMBOLS
ELECTRICAL DEVICES
DM
30A 3P 20A
RRRRR
K
A
METERING DEVICES:
A = AMMETER
V = VOLTMETER
PF = POWER FACTOR
HZ = FREQUENCY METER
N E
L
1000AT
1000AF
30A 3P
20A
INDICATOR OR PILOT LIGHT:
R = RED
G = GREEN
B = BLUE
W = WHITE
A = AMBER
100A
TRANSFORMER
(DELTA ~ WYE GROUND SHOWN)
RATINGS AS INDICATED
CIRCUIT BREAKER - DRAWOUT
RATINGS AS INDICATED
DRAWOUT POWER CIRCUIT BREAKER, RATINGS
AS INDICATED
MOLDED CASE CIRCUIT BREAKER OR MCP
(OPEN OR ENCLOSED)
MOTOR STARTER CONTACTOR AND THERMAL
OVERLOAD
CONTACT
(NORMALLY OPEN OR NORMALLY CLOSED)
DIGITAL METER
AUTOMATIC TRANSFER SWITCH
CURRENT TRANSFORMER
FUSED SWITCH; RATINGS AS INDICATED
SWITCH; RATINGS AS INDICATED
FUSE; FUSE SIZE INDICATED
KIRK KEY INTERLOCK
POTENTIAL TRANSFORMER
THERMAL OVERLOAD
MOTOR - NUMERAL INDICATES HP
GROUND
SINGLE-POLE, DOUBLE-POLE, 3-WAY AND
4-WAY SWITCHES (48" AFF)
A
LR
T
PCC
(MOUNTING HEIGHT TO CENTER LINE
OF BOX UNLESS NOTED OTHERWISE)
LOCAL WALL DIMMER SWITCH (48" AFF)
LOW-VOLTAGE SWITCH (48" AFF)
FAN SWITCH (48" AFF)
WALL MOUNTED OCCUPANCY SENSOR SWITCH;
DUAL TECHNOLOGY
(PASSIVE INFRARED/ULTRASONIC)
CEILING MOUNTED OCCUPANCY SENSOR;
DUAL TECHNOLOGY
(PASSIVE INFRARED/ULTRASONIC)
OS
DAYLIGHT SENSORDS
LIGHTING RELAY
(UL924 GENERATOR TRANSFER DEVICE)
TIMECLOCK (REFER TO PLANS)
PHOTOCELL (REFER TO PLANS)
DUPLEX RECEPTACLE (18" AFF)
DOUBLE DUPLEX RECEPTACLE (18" AFF)
DUPLEX RECEPTACLE -
CEILING MOUNTED
DOUBLE DUPLEX RECEPTACLE -
CEILING MOUNTED
SIMPLEX RECEPTACLE (18" AFF)
DUPLEX RECEPTACLE MOUNTED 6" ABOVE
COUNTER OR BACKSPLASH
DUPLEX RECEPTACLE - FLOOR MOUNTED
SPECIAL RECEPTACLE (18" AFF)
20A, 2P, 3W, 208V, NEMA 6-20R
B
SPECIAL RECEPTACLE (18" AFF)
30A, 2P, 3W, 208V, NEMA 6-30R
C
SPECIAL RECEPTACLE (18" AFF)
20A, 3P, 4W, 120/208V, NEMA 14-20R
D
SPECIAL RECEPTACLE (18" AFF)
30A, 3P, 4W, 208V, NEMA 15-30R
PLUG MOLD/WIRE MOLD RACEWAY
POWER DISTRIBUTION
ELECTRICAL LIGHTING FIXTURE SYMBOLS
VFD
CP
J FB
F
PANELBOARD
TRANSFORMER
MOTOR CONNECTION - NUMERAL INDICATES HP
DISCONNECT SWITCH - FUSED
DISCONNECT SWITCH - NON-FUSED
DISCONNECT SWITCH -
MOTOR/STARTER COMBINATION
VARIABLE FREQUENCY DRIVE
CONTROL PANEL
JUNCTION BOX OR PULL BOX
WALL MOUNTED JUNCTION BOX OR PULL BOX
FLOOR BOX
J
J
2X4 FIXTURE - RECESSED, SURFACE, OR
PENDANT MOUNTED - TYPE AS SPECIFIED
2X4 EMERGENCY BRANCH FIXTURE - RECESSED,
SURFACE OR PENDANT MOUNTED - TYPE AS
SPECIFIED
2X2 FIXTURE - RECESSED, SURFACE, OR
PENDANT MOUNTED - TYPE AS SPECIFIED
2X2 EMERGENCY BRANCH FIXTURE - RECESSED,
SURFACE, OR PENDANT MOUNTED - TYPE AS
SPECIFIED
1X4 FIXTURE - RECESSED, SURFACE, OR
PENDANT MOUNTED - TYPE AS SPECIFIED
1X4 EMERGENCY BRANCH FIXTURE - RECESSED,
SURFACE, OR PENDANT MOUNTED - TYPE AS
SPECIFIED
1X4 FIXTURE - WALL MOUNTED - TYPE AS
SPECIFIED
1X4 EMERGENCY BRANCH FIXTURE - WALL
MOUNTED - TYPE AS SPECIFIED
4' STRIP FIXTURE - TYPE AS SPECIFIED
4' STRIP EMERGENCY BRANCH FIXTURE - TYPE AS
SPECIFIED
LIGHTING FIXTURE - RECESSED OR SURFACE
MOUNTED - TYPE AS SPECIFIED
LIGHTING FIXTURE CONNECTED TO LIFE SAFETY
BRANCH - RECESSED, SURFACE, OR PENDANT
MOUNTED - TYPE AS SPECIFIED
WALL MOUNTED - TYPE AS SPECIFIED
WALL MOUNTED CONNECTED TO LIFE SAFETY
BRANCH - TYPE AS SPECIFIED
EXTERIOR POLE MOUNTED FIXTURE - TYPE AS
SPECIFIED
EXTERIOR POST TOP FIXTURE - TYPE AS
SPECIFIED
SELF CONTAINED EMERGENCY LIGHTING UNIT -
TYPE AS SPECIFIED
EXIT SIGN-CEILING MOUNTED - TYPE AS
SPECIFIED
EXIT SIGN-WALL MOUNTED - TYPE AS SPECIFIED
COMMUNICATION DEVICES
S
CRR
DC
ES
K
MDMD
P
TELEPHONE OUTLET (18" AFF); PROVIDE DOUBLE
GANG BACKBOX WITH 1"C AND PULL STRING TO
ACCESSIBLE CEILING (TYP), PROVIDE INSULATED
NYLON BUSHING ON END OF CONDUIT FOR
PROTECTION OF WIRE
CABLE TV OUTLET, MOUNTED BEHID TV LOCATION
WITH RECESSED DOUBLE GANG BACKBOX.
COORDINATE MOUNTING HEIGHT WITH
ARCHITECTURAL PLANS; PROVIDE 1 CATV JACK
12"x6" COMMUNICATION CABLE TRAY MOUNTED
ABOVE SUSPENDED CEILING
TELE/DATA WIREMOLD; PROVIDE 1 TELEPHONE
JACK AND 1 DATA JACK AT EACH DEVICE
LOCATION
8" CEILING MOUNTED PAGING SPEAKER;
PROVIDED WITH BAFFLE, GRILL AND MATCHING
TRANSFORMER
CARD READER. FLUSHED MOUNTED AT 42" AFF.
DOOR CONTACT
ELECTRIC DOOR STRIKE
KEY PAD
MOTION DETECTOR
PUSH BUTTON/PUSH PLATE
CCTV CAMERA
(MOUNTING HEIGHT TO CENTER LINE
OF BOX UNLESS NOTED OTHERWISE)
FIRE ALARM SYMBOLS
MANUAL PULL STATION (46" AFF)
BELL/STROBE LIGHT COMBINATION (80" AFF)
STROBE LIGHT (80" AFF)
HORN (80" AFF)
HORN/STROBE LIGHT COMBINATION (80" AFF)
PROGRAM BELL (80" AFF)
CHIME/FLASH COMBINATION (80" AFF)
SPEAKER (80" AFF)
SPEAKER/STROBE COMBINATION (80" AFF)
SMOKE DETECTOR - CEILING MOUNTED
F
S
S
H
H
B
C
S
S
HEAT DETECTOR - CEILING MOUNTED
DUCT DETECTOR
COMBINATION SMOKE/HEAT DETECTOR - CEILING
MOUNTED
TAMPER SWITCH
FLOW SWITCH
SDSD
HD
DDD
SH
TS
FS
MAGNETIC DOOR HOLDER (72" AFF)
FIRE ALARM CONTROL PANEL
RECESSED FIRE ALARM CONTROL PANEL
FIRE ALARM REMOTE ANNUNCIATOR
FIRE ALARM REMOTE ANNUNCIATOR
FACP
FACP
FARA
FARA
CIRCUIT DESIGNATIONS
NUMERAL INDICATES CIRCUIT NUMBER*
A a
CAPITAL LETTER INDICATES FIXTURE TYPE
NUMERAL INDICATES CIRCUIT NUMBER*
SMALL LETTER INDICATES CONTROL SWITCH
LIGHTING
POWER
*SEE NOTES ON ASSOCIATED DRAWINGS FOR
PANEL DESIGNATION
CONDUIT AND WIRING
2A-1,3,5
BRANCH CIRCUIT RUN CONCEALED
BRANCH CIRCUIT RUN UNDER FLOOR
BRANCH CIRCUIT DOWN
BRANCH CIRCUIT UP
HOME RUN TO PANEL 2A CKTS 1, 3, & 5
LINE TYPES
GENERAL SYMBOLS
-NEW BRANCH CIRCUIT W/#12 AWG THHN WIRES
-SLASH LINES INDICATES WIRES IN CIRCUIT
-SHORT LINES DEPICTS PHASE CONDUCTOR
-LONG LINE DEPICTS NEUTRAL CONDUCTOR
-LONG LINE W/DOT DEPICTS GROUND
NEW WORK SCOPE OF WORK
EXISTING SCOPE OF WORK
DEMOLITION SCOPE OF WORK
FUTURE SCOPE OF WORK
UNDERGROUND ELECTRIC SECONDARY FEEDER
X X
X
KEY NOTE INDICATOR
EQUIPMENT INDICATOR
DRAWING REVISION INDICATOR
100AT
100AF
100AT
100AF
DOUBLE DUPLEX RECEPTACLE - FLOOR MOUNTED
GFCI DUPLEX RECEPTACLE WITH WHILE-IN-USE
WEATHERPROOF COVERGFCI/WP
GFCI DUPLEX RECEPTACLEGFCI
FLEXIBLE CONDUIT
LIGHTING FIXTURE - PENDANT MOUNTED - TYPE
AS SPECIFIED
TELEPHONE/DATA OUTLET - FLOOR MOUNTED
BOX; PROVIDE 1"C TO ABOVE ACCESSIBLE
CEILING (TYP), PROVIDE INSULATED NYLON
BUSHING ON END OF CONDUIT FOR PROTECTION
OF WIRE
TELEPHONE/DATA OUTLET - FLOOR MOUNTED
POKE-THRU; PROVIDE 1"C TO ABOVE ACCESSIBLE
CEILING (TYP), PROVIDE INSULATED NYLON
BUSHING ON END OF CONDUIT FOR PROTECTION
OF WIRE
ABOVE COUNTER TELEPHONE/DATA OUTLET (48"
AFF); PROVIDE DOUBLE GANG BACKBOX WITH 1"C
AND PULL STRING TO ACCESSIBLE CEILING (TYP),
PROVIDE INSULATED NYLON BUSHING ON END OF
CONDUIT FOR PROTECTION OF WIRE
SS2 SS3 SS4
SSD
SSLV
SSF
GENERAL PROJECT NOTES
ELECTRICAL ABBREVIATIONS
A AMP
AA AUTOMATIC ALTERNATOR
AC ALTERNATING CURRENT
ACU AIR CONDITIONER UNIT
AF AMPERAGE FRAME
AFF ABOVE FINISHED FLOOR
ANN ANNUNCIATOR
AS AMMETER SWITCH
AT AMPERE TRIP
AX AUXILIARY DELAY
BKR BREAKER
CB CIRCUIT BREAKER
COL COLUMN
CL CENTERLINE
CKT CIRCUIT
CF(P OR L) CLOSE ON FALLING
(PRESSURE OR LEVEL)
CR(P OR L) CLOSE ON RISING
(PRESSURE OR LEVEL)
CH CONVECTION HEATER
COMPT COMPARTMENT
COND CONDUCTOR
CDT CONDUIT
C-( ) CONTRACT-( ) ID
CPT CONTROL POWER TRANSFORMER
CR-( ) CONTROL RELAY-( ) ID
I/I CURRENT TO CURRENT
TRANSDUCER
I/P CURRENT TO PNEUMATIC
TRANSDUCER
CT CURRENT TRANSFORMER
D EXISTING TO BE DEMOLISHED
DC DIRECT CURRENT
DF DUST FILTER
DIA DIAMETER
DISTR DISTRIBUTION
DP DIFFERENTIAL PRESSURE
DS DISCONNECT SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
E EXISTING TO REMAIN
EBB ELECTRIC BASED BOARD
EC ELECTRICAL CONTRACTOR
ECH ELECTRIC CEILING HEATER
EDH ELECTRIC DUCT HEATER
EF ELECTRIC FIN
EMT ELECTRIC METALLIC TUBING
ER EXISTING TO BE REMOVED AND
RELOCATED
ETM ELAPSED TIME METER
EUH ELECTRIC UNIT HEATER
EWC ELECTRIC WATER COOLER
F FLOW
FDR FEEDER
FLA FULL LOAD AMPS
FMC FLEXIBLE METALLIC CONDUIT
FOS FAST-OFF-SLOW
F-S FAST-SLOW
FT FEET
F-R FORWARD REVERSE
FR FRAME
FUSS FUSED SAFETY SWITCH
FVNR FULL VOLTAGE NON-REVERSING
G GREEN
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GPM GALLONS PER MINUTE
GND GROUND
GRV GRAVITY RELIEF VENT
GUH GAS UNIT HEATER
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HV HOUSE VACUUM
HZ HERTZ
ID IDENTIFICATION NUMBER
IC INTERRUPTING CAPACITY
IF INFRARED HEATER
IMC INTERMEDIATE METAL CONDUIT
INF IN LINE FAN
I/O INPUT/OUTPUT
IT INTERCHANGEABLE TRIP OR
INSTANTANEOUS TRIP
JB JUNCTION BOX
kcmil THOUSAND CIRCULAR MILS
KUH/EUH ELECTRIC UNIT HEATER
KVA KILOVOLT AMPERE
KV KILOVOLT
KVAR KILOVOLT AMPERES REACTIVE
KW KILOWATT
L LEVEL
LC LOUVER CONTROLLER
LFMC LIQUID-TIGHT FLEXIBLE
METAL CONDUIT
LM LOUVER MOTOR
LP( )-( ) LIGHTING CIRCUIT ( )
LP( ) LIGHTING PANELBOARD
LS LIMIT SWITCH
LV LOUVER
M MANUAL MOTOR STARTER
mA MILLIAMPERES
MC METAL CLAD CABLE
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MEZZ MEZZANINE
MF-( ) MAIN FEEDER-( ) ID
MGD MILLION GALLONS PER DAY
MS MOTOR STARTER
MTD MOUNTED
MTR MOTORIZED TIMING RELAY
MUAU MAKE UP AIR UNIT
MX MOTOR AUXILIARY RELAYS
(N) NEW
NAC NOTIFICATION APPLIANCE CIRCUIT
NP NAMEPLATE
NF NON FUSED
NFSS NON FUSED SAFETY SWITCH
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
No. NUMBER
( )OL OVERLOAD ( ) NUMBER OF
P PRESSURE
( )P POLES ( ) NO OF POLES
Ø or PH PHASE
P/I PNEUMATIC TO CURRENT
TRANSDUCER
PLC PROGRAMMABLE LOGIC
CONTROLLER
PRE POWER ROOF EXHAUSTER
PS PRESSURE SWITCH
PT POTENTIAL TRANSFORMER
PTAC PACKAGE TERMINAL
AIR CONDITIONER
PTR PNEUMATIC TIMING RELAY
PVC POLYVINYL CHLORIDE
RIGID CONDUIT
PVC-RSC PVC COATED RIGID
STEEL CONDUIT
PWV POWER WALL VENTILATOR
QTY QUANTITY
R EXISTING AT RELOCATED POSITION
RAC RIGID ALUMINUM
RECPT RECEPTACLE
REQ REQUIRED
RMS ROOT MEAN SQUARE
RSC RIGID STEEL CONDUIT
RTU REMOTE TERMINAL UNIT
SAF SUPPLY AIR FAN
STP SHIELDED TWISTED PAIR
SL STOP LOCKOUT
SMC SMART MOTOR CONTROLLER
SPDT SINGLE POLE, DOUBLE THROW
SS SELECTOR SWITCH
S/S START/STOP
S/SL START/STOP LOCKOUT
SV SOLENOID VALVE
SYM SYMMETRICAL
T or T'STAT THERMOSTAT
T-( ) TELEPHONE CONDUIT-( )
TCC TIME-CLOSE CONTACT
TEMP TEMPERATURE
TC TEMPERATURE CONTRACTOR
TOC TIME-OPEN CONTACT
TR TIMING RELAY
TRI SHIELDED TRIPLE CABLE
TS TEMPERATURE SWITCH
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
UF UNDERGROUND FEEDER
UH UNIT HEATER
VA VOLT - AMPERE
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
VS VOLTMETER SWITCH
VT VOLTAGE TRANSFORMER
W WATT
WH WATER HEATER
WP WEATHERPROOF
NURSE CALL SYMBOLS
NURSE STATION (46" AFF)
CODE BLUE STATION (46" AFF)
VA GENERAL DEMOLITION NOTES
VA GENERAL NOTES
BED NURSE CALL (46" AFF)
TOILET NURSE CALL (46" AFF)
SHOWER NURSE CALL (46" AFF)
DOCTOR DICTATION (46" AFF)
DOCTOR PAGE (46" AFF)
NURSE CALL MASTER
NURSE CALL DOME LIGHT (CEILING)
DUTY STATION (46" AFF)
NURSE CALL ZONE LIGHT (CEILING)
Z
N
CC
B
T
S
DIDI
D
NDND
SS
TELEPHONE/DATA OUTLET - CEILING MOUNTED;
PROVIDE DOUBLE GANG BACKBOX WITH 1"C AND
PULL STRING TO ACCESSIBLE CEILING (TYP),
PROVIDE INSULATED NYLON BUSHING ON END OF
CONDUIT FOR PROTECTION OF WIRE
C
CABLE TV HUBCATV
P PUSH BUTTON/PUSH PLATE
DOOR BUZZER
SECURITY PANELSEC
TELEPHONE/DATA OUTLET - CEILING MOUNTED;
PROVIDE DOUBLE GANG BACKBOX WITH 1"C AND
PULL STRING TO ACCESSIBLE CEILING (TYP),
PROVIDE INSULATED NYLON BUSHING ON END OF
CONDUIT FOR PROTECTION OF WIRE
MANUAL MOTOR STARTER WITH THERMAL
OVERLOADSSSM
RELAY MODULER
NURSE CALL TERMINAL CABINETNCT
36564
9' - 0" 9' 0" 9' - 0" 9' 0" 9' 0" 9' - 0" 9' - 0"
8' - 0"
8' - 0"
9' - 0"
9' - 0"9' - 0"9' - 0"9' - 0"
8' 6"
8' - 0"-
8' - 0"8'
9' - 0"9999
8' - 0"
- 6"8'8' --
9' - 0" 9' - 0" 9' - 0"
8' - 0"
8' - 6"
9' - 2"9 "2 9 2""229'9 2 ' - 0"000 "0'''8888888
0""0"0""0- 008' - 08 - 08'88'
J K P Q R R.4M.3K.8
10.8
J.9
10.5
9.5
8.8
9.8
--8'
000"0''8'88'88' """""
000- 00000
Stair S7-6
9' 0" Prep/Recoveryeep/Recovevep//Recovov/
C702CCCC702CCC9 - 09 - 0CCCCC
9 Prep/RecoveryeryRe9' - 0"9' 0"
C70770279' - 0" Prep/Recoveryovrrep/RecocoPrerep/Recece
2HHC702H2HC702 - 0 - 0 H9' - 0"
Prep/Recoveryrp/Recoveve/Rp RecovvR
C702GCCCC7C702G79 - 09 - 0GGC9' 0"
Prep/Recoveryveeep/Recovovepp/Recoop
C702FFCC702FFC9 - 09 - 09' 0"
Prep/Recoveryeep/Recovovep/ep/Recoop/
C702EECC702EEC9 - 09 - 09' - 0"
Prep/Recoveryvreep/Recocovepp/Recocop
C702DDC7022D9 - 09 - 0 DD- 0"
Prep/RecoverycP ecPrrep/Reer
C702B2022C700- 0- 0 B
SterileSt ile upplypSuSuSS0"0" C7117C
Clean Linen C710
Elec E72
Comm T72
Elec C713
Toilet C705
Prep/Recoveryy/R
C702NC N
Prep/Recoveryep e
C702MC MC
Prep/Recoverye v C702L
Prep/Recoveryep
C702KK
Prep/Recovery C702J
NurseN ManagerM
C707
Storager g
C7127CCC
Soiled Utility C706C
Staff Lounge/n Lockerss
B732 cccccccEleleEEEEEEEElEEEE eeee
B732A2AB 2AA73B773 AAA3B 2AAA77 2A227BB 33B7323327B
Toilet C703C703
IsolationI ossos lsos
C702AC7CCCC7C77777CC A
StationaNurse StNNN StaNNurse SSu8 - 68 - 6
C70888C7088
Toilet C704
HAC
C709
PrepeppPrePPPrerepeppPP peeP eeeerr RecoveryR yRe vc ryoveR ovvvRRe ee yco yye yvvvvooeeRR rcoRRRR
AreareaAreaAAA aarreaaaAreaaA
C7020C 02C70C700CC 2C7000777CC 02CC
Corridoro C7-3-17
CorridorCCorridorC C7-8-1
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS D
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS3333 eeeeeeeeeeeeeeee
SSSSSSS
SS
lalaaalal aa aaaaaaaaaaa 00000000
SSSSSS DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD SSSSSS DD
SSSSSSS33333 eeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeee
Clean LineC nClean LinClean Lin
CC nClean Lin y 2J
RR
C7
RR
RRR
ery 02J ry 02J ry 02J
Soiled Utilityyy
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSaaaaaaaaaaaaaa
HACHACHACHACHACHAC
SSSSSSSSSSSS DDDDDSSSSS DDDDDDDDDSSSSSDDDDDSSSSS DDDDDDDSSSSSDDDDD
0 ryy
702II
PPPPPP 0 0 ryy0"0" C70202
00 ryy0 7022I
00 ryy0
SSSSSS DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD SSSSSS DD SSSSSS DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD SSSSSS DD SSSSSS DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD SSSSSSS DD
B1B1B1BBBBBB11B11BBBBBBBBBBB1111BBBBB1
H H
H
A A
A A A A A A A
AA
A
XXXXXXXX
X A
AA
AA
AAAAAAAAAAAAAAAAAAAAAA A
A
AA
AAAA
GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG
A
XXA
A
B1B1BB1B1BBB1BBB1BB11BBBBBBBB111BB11BBBBB111B111111 BBBBBBBB BBBBBBBB BBBBB BBBBBBBB BBBBBB BBBBBBBB BBBBBB
BBBBBBB
BB
BB
BBBB
BBBBBBBB0"0"BBBB
H
HHHHH
H
HH
HH
H HH
FFFFFFFFFFFFFFFFFFF
CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCC
CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCC
CCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG
GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG
1111111111111111 11
44444444444444444444444444444444444449'9 44444444444444444444444444444444444444444444 444444 444444 444444 444444 444444 444444 444444
44444444444444
444444
444444444444444
4444444444444444444444444444
444444444444444444444444444444444444444
11 11
1 1 1 1 1 1
11111111
33333333333333333333
3333333333333333333333333333333
3333333333333333333333333333333333333333
3333333333333333333333333333333333
33333333333333333333333
3 3 33 3 333 33 333 33 33 3333 33 333333 3 333333 3333 333333333 333333 333333333333333333333333
3 33 3 33 33 33 33 33 33 333333 333 333 3 3333 333 3 33 333333333333333 3333333 333333333 3 33333333 3 3 333
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSbbbbbbbbbbbbbbbbb SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSccccccccccc44444
444444444 a a a aaaaaaaaaaa a a aaaaaaaaaaa aa aaaaaaaaa aaaaa aa aa aaaaaaaaaaaaaaaa a a a aa a a a bbbbbbbb bbccccccccccccccccccccccccccccccccccccccccccccc ccccccccccccccccccccccccccccccc cccccccccccccccccccccccccccccc dddddddddddddddddddd
11111111
A
X
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSddddddddddd
D
DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD
11111111
DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD
e e e e e e e ee e eeeeeeeeeee aa eeeeeeeee
OS
RECOVERY
C709
RECOVERY
C710
PATIENT ROOM
C711
C711A C710A C709A
OUTPATIENT RECOVERY
C707
C707A
Comm T72
Elec E72
Elec C713
LOUNGE
C706
LINEN
C705
PROGRAM MANAGER
C705B
NURSE MANAGER
C704B
ENGINEERING STORAGE
B732
SOILED UTILITY
C702
OFFICE
C703
FOYER
C704
C706AC705A
SUPPLY
C712
Toilet B701
706A C707A
9A7
COVE
C710
1A
SS SS SS
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS
SSSSSSSSSSSSSSSSSSSSSSSSS
SS
SS
SSSSSSS
SS SS
705A
SSSSSSSSS
SS
PP
Y
SSSS
SSSSS
SSSS
SS
SS
SSSS
SSSSSSSS
SSSSSSSSS
SSSSSS
SS
SSSSSS
SS
SS
SS
SSSSSS
SSSSSSSSSS
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSED UUU EEEOO
C703C703C703
SRI
B
SS
7 A
KEY PLAN
COA # 8304 Project # 2016627
550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700
A R C H I T E C T SJ O H N P O E
3131 NEWMARK DRIVE
SUITE 200
MIAMISBURG, OHIO 45342
937 461 3290 PHONE
jpa@johnpoe.com
Scale: 1/8" = 1'-0"1 SEVENTH FLOOR RENOVATION PLAN - LIGHTING
Scale: 1/8" = 1'-0"2 SEVENTH FLOOR DEMOLITION PLAN - LIGHTING
A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 2 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. NORMAL LIGHTING SHALL BE FED FROM PANEL RN-7MH-2C UNLESS
OTHERWISE NOTED.
C. CRITICAL POWER LIGHTING SHALL BE FED FROM PANEL RC-7MH-2
UNLESS OTHERWISE NOTED.
D. LIFE SAFETY LIGHTING SHALL BE FED FROM EXISTING LIFE SAFETY
LIGHTING CIRCUIT IN AREA.
GENERAL NOTES