36C24818R0737-027.pdf

PDF 27 MB Posted

Attached to
Project 546-16-104 Renovate Ambulatory Surgery
Solicitation number
36C24818R0737
Issued by

About this file

36C24818R0737 546-16-104 Final Submittal Drawings_Part4.pdf

View the file

Other files

File Type Posted
36C24818R0737-0003000.docx DOCX document
36C24818R0737-0002000.docx DOCX document
36C24818R0737-0002003.pdf PDF
36C24818R0737-0002001.pdf PDF
36C24818R0737-0002002.pdf PDF
36C24818R0737-0001001.pdf PDF
36C24818R0737-0001000.docx DOCX document
36C24818R0737-026.pdf PDF
36C24818R0737-024.pdf PDF
36C24818R0737-021.pdf PDF
36C24818R0737-029.pdf PDF
36C24818R0737-023.pdf PDF
36C24818R0737-019.docx DOCX document
36C24818R0737-020.pdf PDF
36C24818R0737-022.pdf PDF
36C24818R0737-025.pdf PDF
36C24818R0737-028.pdf PDF
36C24818R0737-000.docx DOCX document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

79392 Ryan E. Morriss, PE

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

NOTES:

1. PROVIDE STRAIGHT RIGID DUCT WITH MINIMUM LENGTH OF 3 TIMES THE INLET DIAMETER AT THE INLET OF EACH TERMINAL UNIT.

2. INLET DUCT SHALL BE THE SAME SIZE AS INLET OF TERMINAL UNIT. IF INLET DUCT EXCEEDS 5 FT. LENGTH, USE DUCT 4" LARGER

THAN INLET DIAMETER TO WITHIN 3' FROM UNIT, THEN REDUCE TO SAME SIZE AS INLET.

3. CONTRACTOR MAY USE 3'-0" MAXIMUM LENGTH OF FLEXIBLE DUCT UP TO 3 DIAMETERS FROM TERMINAL INLET TO OPTIMIZE

PLACEMENT OF UNIT AND ACCOMMODATE FOR MINOR OFFSETS.

4. LOCATE TERMINAL UNIT SO THAT WORKING CLEARANCE IS NOT OBSTRUCTED BY LIGHTS, STRUCTURE, OR OTHER ITEMS. IF

TERMINAL UNIT IS LOCATED ABOVE AN INACCESSIBLE CEILING, PROVIDE A MINIMUM 18"x18" CEILING ACCESS PANEL FOR TERMINAL

UNIT WITHIN WORKING CLEARANCE SPACE.

5. LOCATE VALVES, STRAINERS, AND OTHER APPURTENANCES ACCESSIBLE WITH WORKING CLEARANCE. INSTALL CONTROL VALVE

ACTUATOR ACCESSIBLE; DO NOT INSTALL AGAINST CEILING.

6. PROVIDE A MINIMUM 6'-0" DUCT LENGTH BETWEEN TERMINAL UNIT DISCHARGE AND FIRST BRANCH TAKE-OFF FITTING.

TYPICAL MANUAL AIR VENT

TYPICAL CHILLED AND HOT WATER PIPING

DRAIN VALVE CONNECTIONS

ELEVATION

THREADED PIPING

ELEVATION

WELDED PIPING

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

3/4" BALL VALVE

ADAPTER TO 3/4" HOSE THREAD,

PROVIDE HOSE CAP NUT

NOTES:

1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.

2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR

PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.

AIR VENT

1/2" BALL VALVE

1/4" COPPER TUBING

1/2" x 4" NIPPLE

CIRCULATING WATER PIPING

ELEVATION

NOTES:

1. VENT ALL HIGH POINTS INDICATED ABOVE.

2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.

MV

OR

AV

OROR

DRAIN VALVE CONNECTIONS DETAIL

NTS2

AIR TERMINAL UNITS DETAIL

NTS1AIR VENT CONNECTIONS DETAIL

NTS7

HWS

HWR

MIN. 3 DIAMETERS

RIGID DUCT 1-ATUX-XX

MINIMUM 6'-0"M

TO DIFFUSERS

INLET DUCTT

45 DEGREE TAKE-OFF

WITHOUT DAMPER

MAIN DUCT

AIR VALVEE

PROVIDE MINIMUM 3'-0"

WORKING CLEARANCE IN

FRONT OF CONTROL BOX

AHU SYSTEM NUMBER

TERMINAL UNIT

NUMBER

AIR TERMINAL UNIT

45 DEGREE TAKE-OFF

WITH DAMPER

NOTE 3

HOT WATER REHEAT COIL

CONTROL BOX

2 POSITION

BINARY POINT

FIRE/SMOKE DAMPER CONTROL DIAGRAM

NTS3

ADD

SMOKE DAMPER (N.C.)

SEE SCHEDULE

SD

NOTE:

UPON DETECTION OF SMOKE BY THE SMOKE DETECTOR, THE SMOKE DAMPER SHALL

CLOSE & SEND AN ALARM TO THE ECC.

M

DUCT TRANSITION

AS REQUIRED

TO FIRE

ALARM CONTROL

PANEL (FACP)

120V

ELECTRICAL

POWER

AIRFLOW

AIR

DUCT

SMOKE PARTITION

ZS

PSH

PRESSURE SWITCH HIGH

TO SHUT DOWN FAN UPON

REACHING HIGH PRESSUREE

SETPOINT

DAMPER POSITION

FEEDBACK TO ECC

TERMINAL UNIT WATER COILS -

PIPING CONNECTIONS

NTS4

COIL

TEST PLUG (TYP.)

REDUCER, IF REQUIRED

WATER RETURN

MANUAL AIR VENT

DI-ELECTRIC UNION

CONNECTIONS (TYP.)

WATER SUPPLY

SHUT OFF VALVE

DRAIN WITH

HOSE CONNECTION

MV

MODULATION CONTROL VALVE

STRAINER

5 FT

6 8 10

9 1110 12

-1312 14 -16 -

1614 17 2219 23

2725 28 3230

20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4

7 7

7 98

SIDE VIEW TRAPEZE HANGER FOR

UP TO 1000 LB. UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER

TYPE 1 - SEE SPECIFICATIONS

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

IN.

FT.

FT.

1" MAX.

PIPE HANGERS DETAIL

NTS6

PROVIDE INSULATION

SHIELD & INSERT FOR ALL

PIPING (8" MIN.)

BAND

1-5/8" 12 GAUGE CHANNEL

OR 2" x 2" x 1/4" ANGLE

1/2" DIA. HANGER RODS

WITH 36" MAX. SPACING

ON EACH CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION

(9 PSF MIN. DENSITY)

UNDER INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

NOTE:

SEE SPECIFICATIONS FOR

DETAILED HANGER

REQUIREMENTS

ADJUSTABLE CLEVIS HANGER

TYPE 43 - SEE SPECIFICATIONS

420ONE 1 x 18 GA STRAP36

TWO 1/2ø RODS TWO 3/8ø. RODS ONE 1 x 16 GA STRAP

50 700

ONE 1 x 22 GA STRAP

QUANTITY/SIZEMAX. DUCT ø

MAX. LOAD

LBS.

MAX.

IN.

SPACING

IN. IN.

HANGER RODS

BAND OF SAME

SIZE AS HANGER

STRAP

LOAD RATED

FASTENERS

50" ø &

UNDER

HANGER STRAPS OR RODS

BAND

OVER 50"ø

ROUND DUCT HANGERS

NTS5

NOTE:

TABULATED DATA FROM SMACNA

ALLOWS FOR DUCT REINFORCING

AND INSULATION, BUT NO EXTERNAL

LOAD.

EXTERIOR SKIN

WALL PANEL

AS SPECIFIED

MASTIC

INTERIOR SKIN

GASKET

S.S. WALL PLATE

SECURED WITH S.S.

SCREWS

PIPE INSULATION AS

SPECIFIED

SEAL INSULATION

AGAINST SKIN

OF WALL PANEL

TUBING, PIPING

OR CONDUIT

S.S. WALL PLATE

SECURED WITH S.S.

SCREWS

FIELD APPLIED INSULATION AFTER

INSERTION OF RESPECTIVE SERVICEC

FACILITY

TUBING, PIPING, AND CONDUITS PASSING

THROUGH PRE-FAB INSULATED WALL PANELS

NTS8

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

NOTE:

1.

2.

3.

4.

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE

REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

WHEN W1 EQUALS W2 AND W1 IS GREATER THAN 36" [500mm] VANES SHALL BE DOUBLE

VANE TYPE.

VANE

VANE

NOTE:

1.

2.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL

SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,

SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R SHALL

EQUAL OR

BE

GREATER

THAN W.

R SHALL

EQUAL OR

BE

GREATER

THAN 1/3W.

R SHALL

EQUAL OR

BE

GREATER

THAN 1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

PLAN VIEW

AIR

FLOW AIR

FLOW

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" MIN.

BRANCH DUCT

AIR

FLOW

TURNING VANES

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

PROVIDE VOLUME DAMPER

1/4 W OR 4" MIN.

MAIN DUCT

ROUND BRANCH DUCT TAKE-OFF

PLAN VIEW

RECTANGULAR OR

ROUND SHEET

METAL DUCT. SEE

PLANS FOR SIZES.

12" MIN

END OF DUCT

CONNECTING

TO AIR DEVICE

AIR SPLIT DUCT TAKE-OFF PLAN

VIEW

BRANCH DUCT TAKE-OFF PLAN VIEW

AIRAIR

FLOWFLOW

A

IR

A

IR

FL

O

W

FL

O W

SUPPLY REGISTERSUPPLY REGISTER

OR BRANCH DUCTOR BRANCH DUCT

PROVIDE VOLUMEPROVIDE VOLUME

DAMPERDAMPER

AIRAIR

FLOWFLOW

A

IR

A

IR

FL

O

W

FL

O W

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8" CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION STAND-OFFOFF

1/2" ROUND ROD PIN

DUCTT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

RETURN AIR

GRILLE/REGISTER

NOTE:

1. PAINT INTERIOR SURFACE (VISIBLE FROM BELOW) WITH FLAT BLACK

ENAMEL PAINT.

ACCOUSTICALLY

LINED SHEET METAL

PLENUM

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED

CONNECTION ON FAN

SIDE

WASHER 1-1/2" MIN. TO 3" MAX. INSTALLED.

6" NOMINAL WITH MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1" x 1/8" DRAW BAND

1" x 1/8" BAND IRON

BOLT ON 4" CENTERS

5/16" FLANGE

DUCT

SHEET METAL SCREWS

ON 12" CENTERS

RIVET ON

4" CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK

1" x 1/8" BAND IRON

BOLT ON 4" CENTERS

1" FLANGE & HEMALTERNATE

POSITION

OF BOLT 1 1/2" POCKET SLIP

DUCT

SHEET METAL AS SPECIFIED

FOR DUCTWORK

1/2" 1-1/2"

1-1/2" MIN. TO 3" MAX. INSTALLED.

6" NOMINAL WITH MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL

AS SPECIFIED

NOTES:

1. A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION IS SIMILAR. FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE

INSTALLED IN THE PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.

2. GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER FRAME AND TO PERIMETER

ANGLES.

3. PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1-1/2" x 1-1/2", 14 GAGE, TO PROVIDE 1" MINIMUM OVERLAP OF

OPENING ON ALL 4 SIDES.

4. BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.

5. ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

6. PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH ROCK WOOL FIRESTOP FIBER.

7. ALL DUCTWORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND MECHANICAL ROOM FLOORS, SHALL

BE PROVIDED WITH 3" HIGH CONCRETE CURB AROUND OPENING FOR DUCT.

SLEEVE, NOTE 2

DUCT

CONNECTION,

NOTE 4

DAMPER,

NOTE 1

DAMPER COLLAR

EXTENSION INTEGRAL

PART OF SLEEVE

SLEEVE, NOTE 2

NOTE 6FIRE BARRIER

PARTITION OR CHASE

TYPICAL DUCT

INSULATION

PERIMETER ANGLE, NOTE 3

(NOTE FASTENED TO PARTITION)

ACCESS

PANEL,

NOTE 5

SECTION "A-A"

"B" "B""

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

4. USE ACCESS DOORS ON AIR HANDLING UNITS AND DUCTWORK INSTALLED IN EQUIPMENT ROOMS.

5. USE ACCESS PANELS ON ALL EQUIPMENT AND DUCTWORK INSTALLED ABOVE FINISHED CEILINGS.

ACCESS PANEL

ACCESS DOOR

CASING

GASKET HANDLE INSIDE

FLEXIBLE WASHER

FACTORY FABRICATED LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

NOTE:

1. UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

MAX.X

M

AX

E Q

U

IP

M E

N T

AIR

FLOW

AIR

FLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

MAX.

M

AX

M A

X

M

AX

EXHAUST OR

RETURN MAIN

OR SUB-MAIN

HOUSING WELDED

TO DUCT SECTION

ROUND OR

FLAT OVAL

DUCT SECTION

COVER WITH HANDLE

AND CHAIN RETAINER

GASKETED AND

PRESSURE SEALED

1/2"

FIRE DAMPER DETAIL

NTS1

RETURN AIR GRILLE DUCT CONNECTION DETAIL

NTS2

DUCTWORK TRANSITIONS DETAIL

NTS3EXHAUST OR RETURN BRANCH DUCTWORK

NTS5

DUCT TAKEOFF DETAILS

NTS4

DUCTWORK SQUARE VANE ELBOWS

NTS6

DUCTWORK RADIUS ELBOWS

NTS7

VOLUME DAMPER DETAIL

NTS8

ACCESS PANEL AND DOOR DETAIL

NTS9

FLEXIBLE DUCT CONNECTIONS

NTS10

ACCESS SECTION FOR ROUND/OVAL DUCT

NTS11

D

(DIAMETER))( ))))))))))((((((((((

1" WIDE FLANGE WITH

NEOPRENE GASKET

SEAL AROUND ENTIRE

PERIMETER

NOTE:

1. WHEREVER THE DEPTH OF THE TRUNK DUCT IS

LESS THAN ROUND RUNOUT DUCT DIAMETER,

PROVIDE TRANSITION FITTING OF EQUIVALENT

AREA TO THE RUNOUT DUCT.

AIRAIR

FLOWFLOW

SMACNA FIGURE 4-6

45° ENTRY

1" WIDE FLANGE WITH

NEOPRENE GASKET SEAL

AROUND ENTIRE PERIMETER

PROVIDE OPPOSED BLADE

MANUAL BALANCING

DAMPER; OPERATOR SHALL

PENETRATE INSULATION

USE ROUND TAKE-OFF FOR

SUPPLY AIR TO NOT MORE

THAN ONE TERMINAL

R

R

WW

15°

W

R

W

2/3W

1/ 3W

W

1/2W

1/ 3W

1/6W

W

W1

W

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

ROOM THERMOSTAT/SENSOR

WALL MOUNTED 48" AFF.

ATU

RHCHWS

HWR

V-1

REHEAT

COIL

AIRA

TERMINAL

UNIT

AIR

FLOW

T

ATU

CONTROLLER

PC

TE

A

IR

F

LO

W (C

FM

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

SP

VAV BOX CONTROL SEQUENCE

W/DEADBAND

100%

VA

V

AI

R

FL

OWREHEAT FLOW

A. SET POINTS SHALL BE SET AS FOLLOWS:

COOLING 75°F (ADJUSTABLE)

HEATING 70°F(ADJUSTABLE)

DEADBAND OF 5° F BETWEEN HEATING AND

COOLING SET POINTS WILL BE MAINTAINED.

B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER WILL

MODULATE TO MINIMUM POSITION.

C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE V-1 WILL

MODULATE TO MAINTAIN SET POINT + 0.5°F. THE ADJUSTABLE

TOLERANCE OF + 0.5°F HAS BEEN SELECTED TO PREVENT VALVE

HUNTING

D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE TEMPERATURE.

FE

VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM

NTS

NOTES:

EACH TERMINAL UNIT SHALL BE CONTROLLED BY A DEDICATED, UNIT

MOUNTED, STANDALONE CONTROLLER. THE CONTROLLER SHALL MONITOR

AND CONTROL EACH UNIT IN STAND-ALONE MODE OR AS DIRECTED BY

BUILDING AUTOMATION SYSTEM.

ALL AIR TERMINAL UNITS SHALL BE PRESSURE INDEPENDENT TYPE WITH

VELOCITY RESET CONTROLLERS. ALL TERMINAL UNITS SHALL BE CAPABLE

OF VARIABLE VOLUME ALTHOUGH SOME WILL ACT AS CONSTANT VOLUME.

INPUTS

ANALOG

MEASURED

BINARY BINARY ANALOG ALARMS PROGRAMS

GENERAL

OUTPUTS SYSTEM FEATURES

SYSTEM

APPARATUS

OR AREA

POINT

DESCRIPTION

BUILDING AUTOMATION SYSTEM INPUT/OUTPUT AIR TERMINAL UNIT

X1-ATU66-01

1-ATU66-02

1-ATU66-03

1-ATU66-04

1-ATU66-05

1-ATU66-06

1-ATU66-07

1-ATU66-08

1-ATU66-09

1-ATU66-10

1-ATU66-11

1-ATU66-12

1-ATU66-13

1-ATU66-14

1-ATU66-15

1-ATU66-16

1-ATU66-17

1-ATU66-18

1-ATU66-19

1-ATU66-20

1-ATU66-21

A

IR

F

LO

W S

E N

S O

R

S P

A C

E T

E M

P E

R A

TU

R

E S

E N

S O

R

D

IS

C H

A R

G E

A

IR

T E

M P

V O

L.

A

IR

F

LO

W

O

FF

S E

T

TR

A C

K

IN

G

S P

A C

E H

U M

ID

IT

Y

A

IR

C O

N

TR

O L

D A

M P

E R

U N

O C

C U

P

IE

D T

E N

A N

T O

V E

R R

ID

E

H E

A

TI

N G

M O

D E

C O

O

LI

N G

M O

D E

H E

A

TI

N G

W A

TE

R

C O

N

TR

O L

V A

LV

E

U N

O C

C U

P

IE

D M

O D

E

S P

A C

E E

N V

IR

O

N M

E N

TA

L

C O

N

TR

O

LL

E R

X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

X X X X X X X XXXX

H

IG

H T

E M

P E

R A

TU

R

E L

E V

E L

LO

W

T E

M P

E R

A

TU

R E

L E

V E

L

H

IG

H H

U M

ID

IT

Y L

E V

E L

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

LI

V

E D

A

TA

S

TR

E A

M

C O

LO

R

G R

A P

H

IC

S

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

Dale A Bacik, PE

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

1. THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS AND ABBREVIATIONS FOR

REFERENCE ONLY. SYMBOLS SHOWN ON THIS DRAWING MAY NOT APPEAR ON THE

FOLLOWING DRAWINGS.

2. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED SHUTDOWNS ON EXISTING

UTILITIES WITH THE VA IN ORDER TO MINIMIZE IMPACT TO OTHER AREAS.

3. ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE NEC, IBC, NFPA, AND ANY

APPLICABLE LOCAL ORDINANCE AND STANDARDS.

4. ALL WIRING SHALL BE IN CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4". MINIMUM

CONDUCTOR SIZE SHALL BE #12 AWG. ALL NEW CIRCUITS SHALL BE PROVIDED WITH AN

INDIVIDUAL NEUTRAL AND GROUNDING CONDUCTOR WITH THE PHASE CONDUCTOR.

5. THE ELECTRICAL DRAWINGS ARE SCHEMATIC IN NATURE. BEFORE STARTING THE WORK

THE CONTRACTOR SHALL REVIEW ALL OTHER DISCIPLINE DRAWINGS AND VERIFY FIELD

CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA

COST TO THE VA. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE

ATTENTION OF THE VA REPRESENTATIVE BEFORE PERFORMING CHANGES.

6. ALL CONDUITS INSTALLED INTERIOR SHALL BE EMT. ALL CONDUITS INSTALLED

EXTERIOR SHALL BE PVC SCHEDULED 40.

7. CONDUCTORS #10 AND SMALL SHALL BE STRANDED COPPER. CONDUCTORS #8 AND

LARGER SHALL BE STRANDED COPPER. UNLESS NOTED OTHERWISE, CONDUCTORS

INSULATION SHALL BE DUAL RATED AT THHN/THWN.

8. ALL DEVICES, EQUIPMENT MATERIAL AND LABOR SHALL BE PROVIDED BY THE

CONTRACTOR UNLESS NOTED OTHERWISE.

9. FOR EQUIPMENT TO BE CONNECTED TO EXISTING PANELBOARDS, THE CONTRACTOR

SHALL BE RESPONSIBLE FOR INSTALLING NEW BREAKERS. NEW BREAKERS SHALL HAVE

INTERRUPTING CAPACITIES EQUAL TO EXISTING UNITS. THE CONTRACTOR SHALL

VERIFY THAT PANELBOARDS HAVE ADEQUATE CAPACITY FOR THE NEW LOAD. IF A

PANELBOARD IS FOUND NOT TO HAVE ENOUGH CAPACITY, THE CONTRACTOR SHALL

THE BRING ISSUE TO THE ATTENTION OF THE VA REPRESENTATIVE.

10.

11. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE MOUNTED AS PER EQUIPMENT

AND DEVICE MANUFACTURER RECOMMENDATIONS.

12. CONTRACTOR SHALL PROVIDE SUBMITTALS TO VA REPRESENTATIVE FOR REVIEW AND

APPROVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES DESCRIBED IN THE SUBMITTAL

REGISTER. SUBMITTALS SHALL INCLUDE CUT SHEETS, DIMENSIONS, WIRING DIAGRAMS,

ACCESSORIES, OPERATION MANUALS, AND ALL NECESSARY INFORMATION FOR

REVIEWER TO MAKE A SOUND EVALUATION.

13. PROVIDE STARTUP OF ALL ELECTRICAL SYSTEMS AND COORDINATE WITH VA

REPRESENTATIVE FOR STARTUP WITNESSING.

14. PROVIDED LAMINATED PLASTIC NAMEPLATES FOR EACH EQUIPMENT ENCLOSURE. EACH

NAMEPLATE IDENTIFY EQUIPMENT FUNCTION, PANELBOARD CONNECTED AND CIRCUIT

NUMBER. NAMEPLATE SHALL BE MELAMINE PLASTIC (0.125 INCHES THICK), WHITE

LETTERS ON BLACK BACKGROUND (NORMAL POWER) AND WHITE LETTERS ON RED

BACKGROUND (CRITICAL POWER). MINIMUM SIZE OF LETTERS SHALL BE 2.5 INCHES. IN

ADDITION TO EQUIPMENT TAGGING, CONTRACTOR SHALL PROVIDE ARC-FLASH

WARNING SIGNS FOR PANELBOARDS.

15. PROVIDE COMPUTER PRINTED ON WHITE WRAPAROUND PAPER WITH CLEAR PLASTIC

PROTECTION TAIL FOR ALL WIRE MARKERS. MARKER SHALL STATE PANELBOARD NAME

AND CIRCUIT NUMBER ON ALL WIRES IN JUNCTION/PULL BOXES AND IN EQUIPMENT

TERMINAL BOXES.

16. PROVIDE PUNCHED TAPE LABELS ON ALL WIRING DEVICES FOR IDENTIFICATION. SHALL

BE ½” BLACK TAPE WITH WHITE RAISED LETTERS. TAPE LABELS SHALL STATE

PANELBOARD NAME AND CIRCUIT NUMBER.

17. PROVIDE DIRECTORIES ON ALL PANELBOARDS. BALANCE ALL LOADS ON PANELBOARD

WITHIN 10%.

18. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE SET OF RECORD

DRAWINGS TO THE VA AT THE END OF THE CONSTRUCTION.

19. ALL MATERIALS AND EQUIPMENT TO BE INSTALLED SHALL BE NEW AND FREE OF

DEFECTS. ALL ELECTRICAL EQUIPMENT SHALL COMPLY WITH NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION (NEMA) STANDARDS AND SHALL BE UL LABELED. ALL

ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN A WORKMANLIKE

MANNER.

20. ALL CONNECTORS AND SPLICES FOR CABLE SIZE #10 AWG AND SMALLER SHALL BE

INSULATED, PRESSURE-TYPE. FOR LARGER SIZE CONDUCTORS USE BOLTED CLAMPS

WITH INSULATING TAPE.

21. PROVIDE INSULATION AND CONTINUITY TEST OF ALL 1000V AND LESS WIRES AND

CABLES. USE TESTING PROCEDURES DESCRIBED IN INTERNATIONAL ELECTRICAL

TESTING AGENCY (NETA) STANDARDS. REPLACE ANY CABLES WITH INSULATION

RESISTANCE LESS THAN 100 MEGA OHMS (MOHMS). TEST ALL GROUND FAULT CIRCUIT

INTERRUPTING (GFCI) RECEPTACLES. TEST ALL GROUNDING ELECTRODE SYSTEMS WITH

FALL OF POTENTIAL METHOD. MAKE RESISTANCE MEASUREMENTS 48 HOURS AFTER

LAST RAIN FALL. MAXIMUM RESISTANCE TO GROUND SHALL BE 5 OHMS.

1. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE

WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND

REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.

2. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

3. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

1. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED

FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.

2. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS

CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND SWITCH.

3. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH

BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

4. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

ELEMENTARY DIAGRAM SYMBOLS

ELECTRICAL DEVICES

DM

30A 3P 20A

RRRRR

K

A

METERING DEVICES:

A = AMMETER

V = VOLTMETER

PF = POWER FACTOR

HZ = FREQUENCY METER

N E

L

1000AT

1000AF

30A 3P

20A

INDICATOR OR PILOT LIGHT:

R = RED

G = GREEN

B = BLUE

W = WHITE

A = AMBER

100A

TRANSFORMER

(DELTA ~ WYE GROUND SHOWN)

RATINGS AS INDICATED

CIRCUIT BREAKER - DRAWOUT

RATINGS AS INDICATED

DRAWOUT POWER CIRCUIT BREAKER, RATINGS

AS INDICATED

MOLDED CASE CIRCUIT BREAKER OR MCP

(OPEN OR ENCLOSED)

MOTOR STARTER CONTACTOR AND THERMAL

OVERLOAD

CONTACT

(NORMALLY OPEN OR NORMALLY CLOSED)

DIGITAL METER

AUTOMATIC TRANSFER SWITCH

CURRENT TRANSFORMER

FUSED SWITCH; RATINGS AS INDICATED

SWITCH; RATINGS AS INDICATED

FUSE; FUSE SIZE INDICATED

KIRK KEY INTERLOCK

POTENTIAL TRANSFORMER

THERMAL OVERLOAD

MOTOR - NUMERAL INDICATES HP

GROUND

SINGLE-POLE, DOUBLE-POLE, 3-WAY AND

4-WAY SWITCHES (48" AFF)

A

LR

T

PCC

(MOUNTING HEIGHT TO CENTER LINE

OF BOX UNLESS NOTED OTHERWISE)

LOCAL WALL DIMMER SWITCH (48" AFF)

LOW-VOLTAGE SWITCH (48" AFF)

FAN SWITCH (48" AFF)

WALL MOUNTED OCCUPANCY SENSOR SWITCH;

DUAL TECHNOLOGY

(PASSIVE INFRARED/ULTRASONIC)

CEILING MOUNTED OCCUPANCY SENSOR;

DUAL TECHNOLOGY

(PASSIVE INFRARED/ULTRASONIC)

OS

DAYLIGHT SENSORDS

LIGHTING RELAY

(UL924 GENERATOR TRANSFER DEVICE)

TIMECLOCK (REFER TO PLANS)

PHOTOCELL (REFER TO PLANS)

DUPLEX RECEPTACLE (18" AFF)

DOUBLE DUPLEX RECEPTACLE (18" AFF)

DUPLEX RECEPTACLE -

CEILING MOUNTED

DOUBLE DUPLEX RECEPTACLE -

CEILING MOUNTED

SIMPLEX RECEPTACLE (18" AFF)

DUPLEX RECEPTACLE MOUNTED 6" ABOVE

COUNTER OR BACKSPLASH

DUPLEX RECEPTACLE - FLOOR MOUNTED

SPECIAL RECEPTACLE (18" AFF)

20A, 2P, 3W, 208V, NEMA 6-20R

B

SPECIAL RECEPTACLE (18" AFF)

30A, 2P, 3W, 208V, NEMA 6-30R

C

SPECIAL RECEPTACLE (18" AFF)

20A, 3P, 4W, 120/208V, NEMA 14-20R

D

SPECIAL RECEPTACLE (18" AFF)

30A, 3P, 4W, 208V, NEMA 15-30R

PLUG MOLD/WIRE MOLD RACEWAY

POWER DISTRIBUTION

ELECTRICAL LIGHTING FIXTURE SYMBOLS

VFD

CP

J FB

F

PANELBOARD

TRANSFORMER

MOTOR CONNECTION - NUMERAL INDICATES HP

DISCONNECT SWITCH - FUSED

DISCONNECT SWITCH - NON-FUSED

DISCONNECT SWITCH -

MOTOR/STARTER COMBINATION

VARIABLE FREQUENCY DRIVE

CONTROL PANEL

JUNCTION BOX OR PULL BOX

WALL MOUNTED JUNCTION BOX OR PULL BOX

FLOOR BOX

J

J

2X4 FIXTURE - RECESSED, SURFACE, OR

PENDANT MOUNTED - TYPE AS SPECIFIED

2X4 EMERGENCY BRANCH FIXTURE - RECESSED,

SURFACE OR PENDANT MOUNTED - TYPE AS

SPECIFIED

2X2 FIXTURE - RECESSED, SURFACE, OR

PENDANT MOUNTED - TYPE AS SPECIFIED

2X2 EMERGENCY BRANCH FIXTURE - RECESSED,

SURFACE, OR PENDANT MOUNTED - TYPE AS

SPECIFIED

1X4 FIXTURE - RECESSED, SURFACE, OR

PENDANT MOUNTED - TYPE AS SPECIFIED

1X4 EMERGENCY BRANCH FIXTURE - RECESSED,

SURFACE, OR PENDANT MOUNTED - TYPE AS

SPECIFIED

1X4 FIXTURE - WALL MOUNTED - TYPE AS

SPECIFIED

1X4 EMERGENCY BRANCH FIXTURE - WALL

MOUNTED - TYPE AS SPECIFIED

4' STRIP FIXTURE - TYPE AS SPECIFIED

4' STRIP EMERGENCY BRANCH FIXTURE - TYPE AS

SPECIFIED

LIGHTING FIXTURE - RECESSED OR SURFACE

MOUNTED - TYPE AS SPECIFIED

LIGHTING FIXTURE CONNECTED TO LIFE SAFETY

BRANCH - RECESSED, SURFACE, OR PENDANT

MOUNTED - TYPE AS SPECIFIED

WALL MOUNTED - TYPE AS SPECIFIED

WALL MOUNTED CONNECTED TO LIFE SAFETY

BRANCH - TYPE AS SPECIFIED

EXTERIOR POLE MOUNTED FIXTURE - TYPE AS

SPECIFIED

EXTERIOR POST TOP FIXTURE - TYPE AS

SPECIFIED

SELF CONTAINED EMERGENCY LIGHTING UNIT -

TYPE AS SPECIFIED

EXIT SIGN-CEILING MOUNTED - TYPE AS

SPECIFIED

EXIT SIGN-WALL MOUNTED - TYPE AS SPECIFIED

COMMUNICATION DEVICES

S

CRR

DC

ES

K

MDMD

P

TELEPHONE OUTLET (18" AFF); PROVIDE DOUBLE

GANG BACKBOX WITH 1"C AND PULL STRING TO

ACCESSIBLE CEILING (TYP), PROVIDE INSULATED

NYLON BUSHING ON END OF CONDUIT FOR

PROTECTION OF WIRE

CABLE TV OUTLET, MOUNTED BEHID TV LOCATION

WITH RECESSED DOUBLE GANG BACKBOX.

COORDINATE MOUNTING HEIGHT WITH

ARCHITECTURAL PLANS; PROVIDE 1 CATV JACK

12"x6" COMMUNICATION CABLE TRAY MOUNTED

ABOVE SUSPENDED CEILING

TELE/DATA WIREMOLD; PROVIDE 1 TELEPHONE

JACK AND 1 DATA JACK AT EACH DEVICE

LOCATION

8" CEILING MOUNTED PAGING SPEAKER;

PROVIDED WITH BAFFLE, GRILL AND MATCHING

TRANSFORMER

CARD READER. FLUSHED MOUNTED AT 42" AFF.

DOOR CONTACT

ELECTRIC DOOR STRIKE

KEY PAD

MOTION DETECTOR

PUSH BUTTON/PUSH PLATE

CCTV CAMERA

(MOUNTING HEIGHT TO CENTER LINE

OF BOX UNLESS NOTED OTHERWISE)

FIRE ALARM SYMBOLS

MANUAL PULL STATION (46" AFF)

BELL/STROBE LIGHT COMBINATION (80" AFF)

STROBE LIGHT (80" AFF)

HORN (80" AFF)

HORN/STROBE LIGHT COMBINATION (80" AFF)

PROGRAM BELL (80" AFF)

CHIME/FLASH COMBINATION (80" AFF)

SPEAKER (80" AFF)

SPEAKER/STROBE COMBINATION (80" AFF)

SMOKE DETECTOR - CEILING MOUNTED

F

S

S

H

H

B

C

S

S

HEAT DETECTOR - CEILING MOUNTED

DUCT DETECTOR

COMBINATION SMOKE/HEAT DETECTOR - CEILING

MOUNTED

TAMPER SWITCH

FLOW SWITCH

SDSD

HD

DDD

SH

TS

FS

MAGNETIC DOOR HOLDER (72" AFF)

FIRE ALARM CONTROL PANEL

RECESSED FIRE ALARM CONTROL PANEL

FIRE ALARM REMOTE ANNUNCIATOR

FIRE ALARM REMOTE ANNUNCIATOR

FACP

FACP

FARA

FARA

CIRCUIT DESIGNATIONS

NUMERAL INDICATES CIRCUIT NUMBER*

A a

CAPITAL LETTER INDICATES FIXTURE TYPE

NUMERAL INDICATES CIRCUIT NUMBER*

SMALL LETTER INDICATES CONTROL SWITCH

LIGHTING

POWER

*SEE NOTES ON ASSOCIATED DRAWINGS FOR

PANEL DESIGNATION

CONDUIT AND WIRING

2A-1,3,5

BRANCH CIRCUIT RUN CONCEALED

BRANCH CIRCUIT RUN UNDER FLOOR

BRANCH CIRCUIT DOWN

BRANCH CIRCUIT UP

HOME RUN TO PANEL 2A CKTS 1, 3, & 5

LINE TYPES

GENERAL SYMBOLS

-NEW BRANCH CIRCUIT W/#12 AWG THHN WIRES

-SLASH LINES INDICATES WIRES IN CIRCUIT

-SHORT LINES DEPICTS PHASE CONDUCTOR

-LONG LINE DEPICTS NEUTRAL CONDUCTOR

-LONG LINE W/DOT DEPICTS GROUND

NEW WORK SCOPE OF WORK

EXISTING SCOPE OF WORK

DEMOLITION SCOPE OF WORK

FUTURE SCOPE OF WORK

UNDERGROUND ELECTRIC SECONDARY FEEDER

X X

X

KEY NOTE INDICATOR

EQUIPMENT INDICATOR

DRAWING REVISION INDICATOR

100AT

100AF

100AT

100AF

DOUBLE DUPLEX RECEPTACLE - FLOOR MOUNTED

GFCI DUPLEX RECEPTACLE WITH WHILE-IN-USE

WEATHERPROOF COVERGFCI/WP

GFCI DUPLEX RECEPTACLEGFCI

FLEXIBLE CONDUIT

LIGHTING FIXTURE - PENDANT MOUNTED - TYPE

AS SPECIFIED

TELEPHONE/DATA OUTLET - FLOOR MOUNTED

BOX; PROVIDE 1"C TO ABOVE ACCESSIBLE

CEILING (TYP), PROVIDE INSULATED NYLON

BUSHING ON END OF CONDUIT FOR PROTECTION

OF WIRE

TELEPHONE/DATA OUTLET - FLOOR MOUNTED

POKE-THRU; PROVIDE 1"C TO ABOVE ACCESSIBLE

CEILING (TYP), PROVIDE INSULATED NYLON

BUSHING ON END OF CONDUIT FOR PROTECTION

OF WIRE

ABOVE COUNTER TELEPHONE/DATA OUTLET (48"

AFF); PROVIDE DOUBLE GANG BACKBOX WITH 1"C

AND PULL STRING TO ACCESSIBLE CEILING (TYP),

PROVIDE INSULATED NYLON BUSHING ON END OF

CONDUIT FOR PROTECTION OF WIRE

SS2 SS3 SS4

SSD

SSLV

SSF

GENERAL PROJECT NOTES

ELECTRICAL ABBREVIATIONS

A AMP

AA AUTOMATIC ALTERNATOR

AC ALTERNATING CURRENT

ACU AIR CONDITIONER UNIT

AF AMPERAGE FRAME

AFF ABOVE FINISHED FLOOR

ANN ANNUNCIATOR

AS AMMETER SWITCH

AT AMPERE TRIP

AX AUXILIARY DELAY

BKR BREAKER

CB CIRCUIT BREAKER

COL COLUMN

CL CENTERLINE

CKT CIRCUIT

CF(P OR L) CLOSE ON FALLING

(PRESSURE OR LEVEL)

CR(P OR L) CLOSE ON RISING

(PRESSURE OR LEVEL)

CH CONVECTION HEATER

COMPT COMPARTMENT

COND CONDUCTOR

CDT CONDUIT

C-( ) CONTRACT-( ) ID

CPT CONTROL POWER TRANSFORMER

CR-( ) CONTROL RELAY-( ) ID

I/I CURRENT TO CURRENT

TRANSDUCER

I/P CURRENT TO PNEUMATIC

TRANSDUCER

CT CURRENT TRANSFORMER

D EXISTING TO BE DEMOLISHED

DC DIRECT CURRENT

DF DUST FILTER

DIA DIAMETER

DISTR DISTRIBUTION

DP DIFFERENTIAL PRESSURE

DS DISCONNECT SWITCH

DPDT DOUBLE POLE, DOUBLE THROW

E EXISTING TO REMAIN

EBB ELECTRIC BASED BOARD

EC ELECTRICAL CONTRACTOR

ECH ELECTRIC CEILING HEATER

EDH ELECTRIC DUCT HEATER

EF ELECTRIC FIN

EMT ELECTRIC METALLIC TUBING

ER EXISTING TO BE REMOVED AND

RELOCATED

ETM ELAPSED TIME METER

EUH ELECTRIC UNIT HEATER

EWC ELECTRIC WATER COOLER

F FLOW

FDR FEEDER

FLA FULL LOAD AMPS

FMC FLEXIBLE METALLIC CONDUIT

FOS FAST-OFF-SLOW

F-S FAST-SLOW

FT FEET

F-R FORWARD REVERSE

FR FRAME

FUSS FUSED SAFETY SWITCH

FVNR FULL VOLTAGE NON-REVERSING

G GREEN

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GPM GALLONS PER MINUTE

GND GROUND

GRV GRAVITY RELIEF VENT

GUH GAS UNIT HEATER

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HV HOUSE VACUUM

HZ HERTZ

ID IDENTIFICATION NUMBER

IC INTERRUPTING CAPACITY

IF INFRARED HEATER

IMC INTERMEDIATE METAL CONDUIT

INF IN LINE FAN

I/O INPUT/OUTPUT

IT INTERCHANGEABLE TRIP OR

INSTANTANEOUS TRIP

JB JUNCTION BOX

kcmil THOUSAND CIRCULAR MILS

KUH/EUH ELECTRIC UNIT HEATER

KVA KILOVOLT AMPERE

KV KILOVOLT

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

L LEVEL

LC LOUVER CONTROLLER

LFMC LIQUID-TIGHT FLEXIBLE

METAL CONDUIT

LM LOUVER MOTOR

LP( )-( ) LIGHTING CIRCUIT ( )

LP( ) LIGHTING PANELBOARD

LS LIMIT SWITCH

LV LOUVER

M MANUAL MOTOR STARTER

mA MILLIAMPERES

MC METAL CLAD CABLE

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MEZZ MEZZANINE

MF-( ) MAIN FEEDER-( ) ID

MGD MILLION GALLONS PER DAY

MS MOTOR STARTER

MTD MOUNTED

MTR MOTORIZED TIMING RELAY

MUAU MAKE UP AIR UNIT

MX MOTOR AUXILIARY RELAYS

(N) NEW

NAC NOTIFICATION APPLIANCE CIRCUIT

NP NAMEPLATE

NF NON FUSED

NFSS NON FUSED SAFETY SWITCH

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

No. NUMBER

( )OL OVERLOAD ( ) NUMBER OF

P PRESSURE

( )P POLES ( ) NO OF POLES

Ø or PH PHASE

P/I PNEUMATIC TO CURRENT

TRANSDUCER

PLC PROGRAMMABLE LOGIC

CONTROLLER

PRE POWER ROOF EXHAUSTER

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER

PTAC PACKAGE TERMINAL

AIR CONDITIONER

PTR PNEUMATIC TIMING RELAY

PVC POLYVINYL CHLORIDE

RIGID CONDUIT

PVC-RSC PVC COATED RIGID

STEEL CONDUIT

PWV POWER WALL VENTILATOR

QTY QUANTITY

R EXISTING AT RELOCATED POSITION

RAC RIGID ALUMINUM

RECPT RECEPTACLE

REQ REQUIRED

RMS ROOT MEAN SQUARE

RSC RIGID STEEL CONDUIT

RTU REMOTE TERMINAL UNIT

SAF SUPPLY AIR FAN

STP SHIELDED TWISTED PAIR

SL STOP LOCKOUT

SMC SMART MOTOR CONTROLLER

SPDT SINGLE POLE, DOUBLE THROW

SS SELECTOR SWITCH

S/S START/STOP

S/SL START/STOP LOCKOUT

SV SOLENOID VALVE

SYM SYMMETRICAL

T or T'STAT THERMOSTAT

T-( ) TELEPHONE CONDUIT-( )

TCC TIME-CLOSE CONTACT

TEMP TEMPERATURE

TC TEMPERATURE CONTRACTOR

TOC TIME-OPEN CONTACT

TR TIMING RELAY

TRI SHIELDED TRIPLE CABLE

TS TEMPERATURE SWITCH

TSP TWISTED SHIELDED PAIR

TYP TYPICAL

UF UNDERGROUND FEEDER

UH UNIT HEATER

VA VOLT - AMPERE

VAC VOLTS ALTERNATING CURRENT

VDC VOLTS DIRECT CURRENT

VFD VARIABLE FREQUENCY DRIVE

VS VOLTMETER SWITCH

VT VOLTAGE TRANSFORMER

W WATT

WH WATER HEATER

WP WEATHERPROOF

NURSE CALL SYMBOLS

NURSE STATION (46" AFF)

CODE BLUE STATION (46" AFF)

VA GENERAL DEMOLITION NOTES

VA GENERAL NOTES

BED NURSE CALL (46" AFF)

TOILET NURSE CALL (46" AFF)

SHOWER NURSE CALL (46" AFF)

DOCTOR DICTATION (46" AFF)

DOCTOR PAGE (46" AFF)

NURSE CALL MASTER

NURSE CALL DOME LIGHT (CEILING)

DUTY STATION (46" AFF)

NURSE CALL ZONE LIGHT (CEILING)

Z

N

CC

B

T

S

DIDI

D

NDND

SS

TELEPHONE/DATA OUTLET - CEILING MOUNTED;

PROVIDE DOUBLE GANG BACKBOX WITH 1"C AND

PULL STRING TO ACCESSIBLE CEILING (TYP),

PROVIDE INSULATED NYLON BUSHING ON END OF

CONDUIT FOR PROTECTION OF WIRE

C

CABLE TV HUBCATV

P PUSH BUTTON/PUSH PLATE

DOOR BUZZER

SECURITY PANELSEC

TELEPHONE/DATA OUTLET - CEILING MOUNTED;

PROVIDE DOUBLE GANG BACKBOX WITH 1"C AND

PULL STRING TO ACCESSIBLE CEILING (TYP),

PROVIDE INSULATED NYLON BUSHING ON END OF

CONDUIT FOR PROTECTION OF WIRE

MANUAL MOTOR STARTER WITH THERMAL

OVERLOADSSSM

RELAY MODULER

NURSE CALL TERMINAL CABINETNCT

36564

9' - 0" 9' 0" 9' - 0" 9' 0" 9' 0" 9' - 0" 9' - 0"

8' - 0"

8' - 0"

9' - 0"

9' - 0"9' - 0"9' - 0"9' - 0"

8' 6"

8' - 0"-

8' - 0"8'

9' - 0"9999

8' - 0"

- 6"8'8' --

9' - 0" 9' - 0" 9' - 0"

8' - 0"

8' - 6"

9' - 2"9 "2 9 2""229'9 2 ' - 0"000 "0'''8888888

0""0"0""0- 008' - 08 - 08'88'

J K P Q R R.4M.3K.8

10.8

J.9

10.5

9.5

8.8

9.8

--8'

000"0''8'88'88' """""

000- 00000

Stair S7-6

9' 0" Prep/Recoveryeep/Recovevep//Recovov/

C702CCCC702CCC9 - 09 - 0CCCCC

9 Prep/RecoveryeryRe9' - 0"9' 0"

C70770279' - 0" Prep/Recoveryovrrep/RecocoPrerep/Recece

2HHC702H2HC702 - 0 - 0 H9' - 0"

Prep/Recoveryrp/Recoveve/Rp RecovvR

C702GCCCC7C702G79 - 09 - 0GGC9' 0"

Prep/Recoveryveeep/Recovovepp/Recoop

C702FFCC702FFC9 - 09 - 09' 0"

Prep/Recoveryeep/Recovovep/ep/Recoop/

C702EECC702EEC9 - 09 - 09' - 0"

Prep/Recoveryvreep/Recocovepp/Recocop

C702DDC7022D9 - 09 - 0 DD- 0"

Prep/RecoverycP ecPrrep/Reer

C702B2022C700- 0- 0 B

SterileSt ile upplypSuSuSS0"0" C7117C

Clean Linen C710

Elec E72

Comm T72

Elec C713

Toilet C705

Prep/Recoveryy/R

C702NC N

Prep/Recoveryep e

C702MC MC

Prep/Recoverye v C702L

Prep/Recoveryep

C702KK

Prep/Recovery C702J

NurseN ManagerM

C707

Storager g

C7127CCC

Soiled Utility C706C

Staff Lounge/n Lockerss

B732 cccccccEleleEEEEEEEElEEEE eeee

B732A2AB 2AA73B773 AAA3B 2AAA77 2A227BB 33B7323327B

Toilet C703C703

IsolationI ossos lsos

C702AC7CCCC7C77777CC A

StationaNurse StNNN StaNNurse SSu8 - 68 - 6

C70888C7088

Toilet C704

HAC

C709

PrepeppPrePPPrerepeppPP peeP eeeerr RecoveryR yRe vc ryoveR ovvvRRe ee yco yye yvvvvooeeRR rcoRRRR

AreareaAreaAAA aarreaaaAreaaA

C7020C 02C70C700CC 2C7000777CC 02CC

Corridoro C7-3-17

CorridorCCorridorC C7-8-1

SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS D

SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS3333 eeeeeeeeeeeeeeee

SSSSSSS

SS

lalaaalal aa aaaaaaaaaaa 00000000

SSSSSS DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD SSSSSS DD

SSSSSSS33333 eeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeee

Clean LineC nClean LinClean Lin

CC nClean Lin y 2J

RR

C7

RR

RRR

ery 02J ry 02J ry 02J

Soiled Utilityyy

SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSaaaaaaaaaaaaaa

HACHACHACHACHACHAC

SSSSSSSSSSSS DDDDDSSSSS DDDDDDDDDSSSSSDDDDDSSSSS DDDDDDDSSSSSDDDDD

0 ryy

702II

PPPPPP 0 0 ryy0"0" C70202

00 ryy0 7022I

00 ryy0

SSSSSS DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD SSSSSS DD SSSSSS DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD SSSSSS DD SSSSSS DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD SSSSSSS DD

B1B1B1BBBBBB11B11BBBBBBBBBBB1111BBBBB1

H H

H

A A

A A A A A A A

AA

A

XXXXXXXX

X A

AA

AA

AAAAAAAAAAAAAAAAAAAAAA A

A

AA

AAAA

GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG

A

XXA

A

B1B1BB1B1BBB1BBB1BB11BBBBBBBB111BB11BBBBB111B111111 BBBBBBBB BBBBBBBB BBBBB BBBBBBBB BBBBBB BBBBBBBB BBBBBB

BBBBBBB

BB

BB

BBBB

BBBBBBBB0"0"BBBB

H

HHHHH

H

HH

HH

H HH

FFFFFFFFFFFFFFFFFFF

CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCC

CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCC

CCCCCCCCCCCCCCCCCCCCCCCCCCCCCC

GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG

GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG

1111111111111111 11

44444444444444444444444444444444444449'9 44444444444444444444444444444444444444444444 444444 444444 444444 444444 444444 444444 444444

44444444444444

444444

444444444444444

4444444444444444444444444444

444444444444444444444444444444444444444

11 11

1 1 1 1 1 1

11111111

33333333333333333333

3333333333333333333333333333333

3333333333333333333333333333333333333333

3333333333333333333333333333333333

33333333333333333333333

3 3 33 3 333 33 333 33 33 3333 33 333333 3 333333 3333 333333333 333333 333333333333333333333333

3 33 3 33 33 33 33 33 33 333333 333 333 3 3333 333 3 33 333333333333333 3333333 333333333 3 33333333 3 3 333

SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSbbbbbbbbbbbbbbbbb SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSccccccccccc44444

444444444 a a a aaaaaaaaaaa a a aaaaaaaaaaa aa aaaaaaaaa aaaaa aa aa aaaaaaaaaaaaaaaa a a a aa a a a bbbbbbbb bbccccccccccccccccccccccccccccccccccccccccccccc ccccccccccccccccccccccccccccccc cccccccccccccccccccccccccccccc dddddddddddddddddddd

11111111

A

X

SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSddddddddddd

D

DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD

11111111

DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD

e e e e e e e ee e eeeeeeeeeee aa eeeeeeeee

OS

RECOVERY

C709

RECOVERY

C710

PATIENT ROOM

C711

C711A C710A C709A

OUTPATIENT RECOVERY

C707

C707A

Comm T72

Elec E72

Elec C713

LOUNGE

C706

LINEN

C705

PROGRAM MANAGER

C705B

NURSE MANAGER

C704B

ENGINEERING STORAGE

B732

SOILED UTILITY

C702

OFFICE

C703

FOYER

C704

C706AC705A

SUPPLY

C712

Toilet B701

706A C707A

9A7

COVE

C710

1A

SS SS SS

SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS

SSSSSSSSSSSSSSSSSSSSSSSSS

SS

SS

SSSSSSS

SS SS

705A

SSSSSSSSS

SS

PP

Y

SSSS

SSSSS

SSSS

SS

SS

SSSS

SSSSSSSS

SSSSSSSSS

SSSSSS

SS

SSSSSS

SS

SS

SS

SSSSSS

SSSSSSSSSS

SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSED UUU EEEOO

C703C703C703

SRI

B

SS

7 A

KEY PLAN

COA # 8304 Project # 2016627

550 North Reo Street Suite 203, Tampa, FL 33609 813.289.4700

A R C H I T E C T SJ O H N P O E

3131 NEWMARK DRIVE

SUITE 200

MIAMISBURG, OHIO 45342

937 461 3290 PHONE

jpa@johnpoe.com

Scale: 1/8" = 1'-0"1 SEVENTH FLOOR RENOVATION PLAN - LIGHTING

Scale: 1/8" = 1'-0"2 SEVENTH FLOOR DEMOLITION PLAN - LIGHTING

A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 2 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE COR.

B. NORMAL LIGHTING SHALL BE FED FROM PANEL RN-7MH-2C UNLESS

OTHERWISE NOTED.

C. CRITICAL POWER LIGHTING SHALL BE FED FROM PANEL RC-7MH-2

UNLESS OTHERWISE NOTED.

D. LIFE SAFETY LIGHTING SHALL BE FED FROM EXISTING LIFE SAFETY

LIGHTING CIRCUIT IN AREA.

GENERAL NOTES

36564