QA - Fire Protection FINAL.pdf
PDF 68 KB Posted
- Solicitation number
- 36C24726Q0055
About this file
This document is a comprehensive Questions and Answers (Q&A) file for a VA (Veterans Affairs) fire alarm system maintenance contract. The solicitation involves maintenance and inspection of a fire alarm system across 86 buildings with 19 control panels and 890 devices, primarily using a Honeywell Notifier system. Key requirements include a 24/7/365 three-hour emergency response time, mandatory use of Notifier components, and quarterly inspections following The Joint Commission (TJC) requirements.
Significant contract details include a $30,000 repair contingency fund managed by the Contracting Officer, potential ongoing construction projects that may impact fire alarm systems, and specific testing requirements for sensitive areas like pharmacies and surgical spaces. Contractors must provide flash badges, potentially include CLSS Gateway monitoring licenses, and are allowed to subcontract services. The existing contract will transition to this new solicitation, with the latest annual inspection expected to be completed by mid-November and subsequent annual inspections anticipated. Spare parts like smoke detectors, pull stations, and network cards will be maintained on-site to ensure timely repairs.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. Regarding the annual maintenance scope, will the replacement of consumable items such as batteries and smoke detector chambers be included, or should those be addressed through the $30,000 repair contingency fund?
The station will have some of these items in stock. Do not include the replacement of consumables in the final price.
2. Can you confirm if the CLSS Gateway monitoring licenses are provided by the government, or if they should be included as contractor-supplied items in the pricing?
The station has three gateways. The contractor should include licenses/new gateways as a precaution.
3. For emergency response requirements, does the three-hour arrival timeframe apply strictly during regular business hours, or is it expected to cover 24/7/365 situations?
Yes, the three-hour response time will be required 24/7/365.
4. The Contract states - The contractor must be able to perform all duties defined within this scope. Services may not be subcontracted, is this correct?
Services may be subcontracted. Please see updated SOW
5. Could you request and/or provide the past inspection reports of an overall asset list that the VA keeps for this campus/scope? Some details in the document are limited, which might affect our ability to provide a price or could result in increased pricing due to assumptions.
We are not able to provide an existing FA inspection at this time. Feel free to ask specific questions if needed to get a better idea of the size/complexity of the campus fire alarm system
6. Any updates or expansions to the Honeywell Notifier system since the last inspection.
No updates or upgrades since the last inspection.
7. Is there an option to perform site visit?
No site visit.
8. Are there update-to-date drawings that will be made available upon award?
Drawings will be provided. It has been noted by other contractors that there are discrepancies with the as-builts.
9. Are all the buildings at the same address with individual building numbers/names?
Yes, all buildings are located at the same address.
10. Is there an existing contract or is this a new opportunity?
There is an existing contract.
11. Has there been any corrective maintenance actions within the current contract?
No, they only inspected and provided reports. Any repairs are done by a certified notifier contractor.
. Any differences between work requirement of current contract and this RFQ?
Yes, there are several notable differences.
12. Are there any current construction projects that have an impact on the fire alarm system and its devices or programming?
Yes, there will be ongoing construction projects. We have several total renovations that will replace the fire alarm system in certain areas as a part of a total gut and renovation.
13. Are there any existing deficiencies, repairs, or maintenance that have an impact on the contractor’s requirements in this solicitation?
Discrepancies with drawings and programming issues. Currently have a one-time contract in place to correct programming deficiencies.
14. RFQ mentions “repair contingency”. Will there be a CLIN for the NTE amount added to the price schedule? If no, how will this be tracked/billed against the contract.
A Clin will be made.
15. How is it determined whether a repair qualifies for funding under the $30,000 repair contingency?
The CO will decide if an item/service will be covered under the contingency fund.
16. RFQ does mention Fire and Smoke Dampers, will 6-year inspections requirements fall within any of the contract option years?
Contractor will be required to provide inspection on fire and smoke dampers.
17. With enough advance notice for scheduling, will the contractor have the support of the HVAC shop technicians when testing the shutdown devices?
Yes, a member of the HVAC shop will escort personnel.
18. Does the existing inspection schedule follow the TJC requirements January/April/July/October?
Yes, we are requiring all JC requirements to be met.
19. Please confirm that this is only fire alarm equipment testing/inspection/maintenance, and there are no requirements to test any of the following:
a.) Wet Pipe Fire Sprinkler Systems b.) Dry Pipe Fire Sprinkler Systems c.) Kitchen Hood Suppression Systems d.) Fire Extinguishers e.) Fire Pump(s) f.) Stored Emergency Power System f.) Fire Doors:
i. Sliding & Rolling Doors
ii. Fire Door Assemblies
Correct, none of these items are to be included.
20. Are there any badging requirements?
Flash badges will be required. PIV badges are not required but may be beneficial for onsite contractors.
21. Do you require a technician to be at the panel during testing?
We do not determine means and methods.
22. Are there any before/after-hours testing requirements?
a.) Cath lab, OR, Endo, Pharmacy, etc b.) Notification devices
Yes, after hours testing may be required for certain areas such as pharmacy, SPS, Endo, etc.
23. Can these devices be tested in small groups/area with advance notice and scheduling?
Yes, for quarterly inspections.
24. Statement of work lists 86 buildings but only 19 control panels is this accurate?
Site map to be provided. Our building nomenclature is a bit confusing. Each wing of the main building is considered its own building. This count also separates floors.
25. Statement of work states 19 panels and 890 devices but is not limited to that, do you know the Actual number of panels and devices?
This is an accurate count of the panels. Current gateway shows 890 devices.
There are some that are disabled.
26. Is there a current preventive maintenance plan for power supplies, batteries, annunciators, and other panel components?
We replace as needed.
27. Any requirements/preferences for testing schedule for semiannual and or annual services?
Latest annual inspection will be complete mid-November. We except the contractor to have another completed annual inspection around this time next year.
28. For replacement parts are OEM Notifier components or fully compatible equivalents required/preferred?
ONLY Notifier. NO exceptions.
29. How do you prioritize and track Red Tag (72 hours) and Yellow Tag (2 weeks) deficiency corrections?
Priority is Red flag and yellow flags are secondary. The station would like to have both taken care of immediately and within required time frames
30. Provide past examples of red tag and yellow tag corrections?
Not pertinent to the current contract bid.
31. What common spare parts will the facility maintain on-hand to ensure timely repair completion?
Smoke detectors, pull stations, wall speak strobes, ceiling strobes, Network cards, power supplies, etc.
32. What systems or software do you use for log management and audit tracking?
We monitor via the notifier gateway system.
33. Information on VA performance standards?
No specific information to add here.