Drawings - Final.pdf
PDF 8 MB Posted
- Attached to
- Z1NZ--Expand and Rewire Parking Lighting
- Solicitation number
- 36C24625B0027
About this file
These construction bid documents detail an electrical infrastructure upgrade project for the Charles George Veterans Affairs Medical Center in Asheville, North Carolina. The project (No. 637-25-132) involves expanding and rewiring parking lighting across multiple buildings, including Building 9, Building 15, Building 62, and Building 64. The comprehensive electrical drawings include site plans, electrical panel schedules, lighting fixture details, and electrical symbol references, with specific focus on rewiring existing electrical systems, replacing area lighting, and upgrading electrical distribution panels. The documents are prepared by Atriax, PLLC, an engineering firm located in Hickory, NC, with a project issue date of 02/10/2025, and include detailed technical specifications for electrical infrastructure modifications across the medical center campus.
The drawings reveal a total of 164 parking spaces across multiple zones, with new electrical circuits, panel modifications, and lighting upgrades planned. Key technical elements include installing new photo-cell controls, astronomical time clocks, replacing conductors, and strategically repositioning area light poles. The project involves working with existing electrical panels (1CHA, CH1B, EM, 64H1, EP) and adding new site lighting infrastructure while maintaining minimal disruption to existing medical center operations. The electrical scope encompasses rewiring, panel upgrades, and lighting system enhancements across various campus buildings, with careful coordination required to minimize operational downtime.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Rice vil le Roa d
Tunnel Road (HWY 70)
AREAW
AY
CANOPY
CONC. RET. W
ALL
CANOPY
686.2614
NORTH
17 16
3A
4A
ELECTRIC SWITCH GEAR
PATIENT PARKING LOTS
BUILDINGS
BELL TOWER
WALKING TRAIL
WALKING TRAIL
WALKING
HELICOPTER
TANKSO2
TRAIL
SOUTH
TOWER
WEST
TOWER
EAST
TOWER
AC
A
72T
POWER PLANT
1 EMPLOYEE PARKING LOTS
BOILER PLANT
3B 4B
5B
5C
WATER TANK
LEGEND
SMOKING
SHELTER
SMOKING
SHELTER
73T
R1
R2
R3
R4
1A
R5
R6
R7
R8
LANDING
AREA
5A
70T
Am bulatory C are Addition
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
CONSTRUCTION
BID
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
637-20-104
N/A
02/10/2025Revisions: Date:
www.atriaxgroup.com
Atriax, PLLC 703 Main Ave, SW Hickory, NC 28602 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 Exp. Date: 6/30/2025
Specialized Engineering Solutions 1300 Baxter Street, Suite 230 Charlotte, NC 28204 704.348.3097
2/10/2025
S E A L 024911
HAROLD J . MARV
I N
PR
OFESSIONAL
ENGINEER
NO
RTH CAROL I NA
G001
HJMHJM
COVER SHEET
CHARLES GEORGE
VETERANS AFFAIRS
MEDICAL CENTER
ASHEVILLE
NORTH CAROLINA
SITE
RICEVILLE RD.
UT
LENN R D .
R D .
MT N .
ALB
KC
L B
E U
D R
I
EG
Y
K P
Approved: Date: Approved: Date:
Approved: Date: Approved: Date:
Approved: Date: Approved: Date:
Approved: Date: Approved: Date:
Approved: Date: Approved: Date:
Requesting ServiceChief, FMS
Infection ControlMedical Center Director
M & O SupervisorAssociate Director
Safety ManagerChief of Staff
AFGEAssociate Director for Patient Care Services
HOURS OF
OPERATION "CONFIDENTIAL"
ASHEVILLE
MEDICAL CENTER
DEPARTMENT of VETERANS AFFAIRS
NORTH CAROLINA
EXPAND AND REWIRE PARKING LIGHTING
PROJECT NO. 637-25-132
CONSTRUCTION BID DOCUMENTS
INDEX OF DRAWINGS
64 FIRE PUMP ROOM
63 STORAGE
47 MAIN HOSPITAL
24 CREDIT UNION
15 ADMINISTRATION/HUMAN RESOURCES
14 ADMINISTRATION / FMS SHOPS
12 GROUNDS - MAINTENANCE
11 LINEN
9 MENTAL HEALTH
2 & 3 QUARTERS
BUILDING FUNCTION
62 COMMUNITY LIVING CENTER
65 BLDG.15 GROUND SOURCE HEAT PUMP
70T MENTAL HEALTH
4,5,6,7
72T SWING SPACE
MENTAL HEALTH
73T MENTAL HEALTH
STATEMENT OF BID ITEM(S)
WORK ON GOVERNMENT HOLIDAYS MUST BE
REQUESTED AND APPROVED BY THE COR
AutoCAD SHX Text T
AutoCAD SHX Text
CONC. WALL
AutoCAD SHX Text C & G
AutoCAD SHX Text
RAMP
AutoCAD SHX Text
ASPHALT DRIVE
AutoCAD SHX Text C & G
AutoCAD SHX Text
BLOCK WALL
AutoCAD SHX Text
BLOWER PAD
AutoCAD SHX Text Dwg. of
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NORMAL BUSINESS HOURS 8:00AM - 4:30PM. CONTRACT WORK HOURS - EVENINGS AFTER 4PM AND WEEKENDS UNLESS APPROVED BY THE C.O.R. NO WORK ON GOVERNMENT HOLIDAYS
AutoCAD SHX Text THESE DRAWINGS MUST BE RETURNED TO MUST BE RETURNED TO BE RETURNED TO FACILITIES MANAGEMENT SERVICE, PROJECT SECTION, UPON COMPLETION, OR FINAL USE BY THE CONTRACTOR FOR BIDDING PURPOSES.
AutoCAD SHX Text G001 1 COVER SHEET 1 COVER SHEET COVER SHEET E000 2 ELECTRICAL SYMBOLS AND ABBREVIATIONS 2 ELECTRICAL SYMBOLS AND ABBREVIATIONS ELECTRICAL SYMBOLS AND ABBREVIATIONS E100 3 SITE PLAN - ELECTRICAL 3 SITE PLAN - ELECTRICAL SITE PLAN - ELECTRICAL E200 4 ELECTRICAL SCHEDULES & DETAILS 4 ELECTRICAL SCHEDULES & DETAILS ELECTRICAL SCHEDULES & DETAILS E201 5 ELECTRICAL PANEL SCHEDULES 5 ELECTRICAL PANEL SCHEDULES ELECTRICAL PANEL SCHEDULES
AutoCAD SHX Text
DWG.#
AutoCAD SHX Text
SHEET #
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text BID ITEM I (BASE BID): ALL WORK SHOWN OR SPECIFIED WITHIN THE DRAWINGS AND SPECIFICATIONS. THE PROJECT WILL FINISH THE UPGRADE AND EXPANSION OF THE PARKING LOT LIGHTING AND WIRING AT THE CHARLES GEORGE VA MEDICAL CENTER. CONTRACTOR TO PROVIDE ALL MATERIAL AND LABOR NECESSARY TO CONSTRUCT WORK SHOWN ON CONTRACT DRAWINGS INCLUDING LOCATING AND MARKING OF ALL UNDERGROUND UTILITIES, PROTECTING UTILITIES DURING CONSTRUCTION, DEMO, INSTALLATION OF NEW POLES, NEW CONCRETE BASES, LED STREETLIGHTS, REWIRING OF ALL STREETLIGHTS ON CAMPUS PER CONTRACT DRAWINGS, PROVIDING ANY EROSION AND SEDIMENT CONTROL NEEDED DURING INSTALLATION AND REPAIRING ANY SURFACES OR UTILITIES TO THAT ARE DAMAGED DURING CONSTRUCTION BACK TO EXISTING CONDITIONS OR BETTER. PHASING IS PRESCRIPTIVE TO CONTROL BUILDING AND PARKING LOT INTERRUPTIONS AND DOWN TIMES. WORK IS EXPECTED TO BE PERFORMED OUTSIDE OF NORMAL BUSINESS HOURS. CONTRACT COMPLETION TIME: 180 CALENDAR DAYS AFTER CONSTRUCTION NOTICE TO PROCEED.
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
COLOR TEMP CONTROL
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
B. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
C. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
D. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
E. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
F. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
G. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
703 Main Ave, SW
Hickory, NC 28602
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2025
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
02/10/2025 20363
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
02/10/2025
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/1
/2
:3
:0
P
M
E000
ELECTRICAL SYMBOLS AND
ABBREVIATIONS
SBH CJF
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
PANEL NAME - CIRCUIT NUMBER
LIGHTING FIXTURE
SYMBOLS
PLAN SYMBOL NAME
AREA POLE LIGHT WITH
DESIGNATION
BOLLARD OR POST TOP
LUMINAIRE
EMERGENCY HATCH
SHEET INDEX - ELECTRICAL
Sheet Number Sheet Name
E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E100 SITE PLAN - ELECTRICAL
E200 ELECTRICAL SCHEDULES & DETAILS
E201 ELECTRICAL PANEL SCHEDULES
#AXX
NO SCALEE000
BUILDING 9 - PANEL EM3
NO SCALEE000
BUILDING 15 - PANEL EP4
NO SCALEE000
BUILDING 62 - PANEL CH1B5
NO SCALEE000
BUILDING 64 - PANEL 64H16
Revisions: Date: 52
BELL TOWER
WALKING TRAIL
WALKING TRAIL
WALKING
HELICOPTER LANDING AREA
TRAIL
686.2614
T78.0726
S
.0
0.00
0 .00000000 0000000
0.0
13 Spaces
10 Spaces
9 Spaces
17 Spaces
22 Spaces
22 Spaces
18 Spaces
18 Spaces
18 Spaces
17 Spaces
(164 Total Spaces)
J
A. ALL LIGHT POLES, POLE BASES AND LUMINAIRES ARE EXISTING UNLESS OTHERWISE NOTED ON
PLANS.
B. CONTRACTOR SHALL PROVIDE A PER FOOT ALLOWANCE FOR REPLACING ANY EXISTING DAMAGED
CONDUITS FOUND. ALLOWANCE SHALL INCLUDE HDPE REPAIR/REPLACEMENT WITH 2#8, 1#10G.
INCLUDE ALLOWANCE WITH BIDDING DOCUMENTS.
(ELECTRICAL GENERAL NOTES APPLY TO ALL ELECTRICAL PLANS AND ALL ELECTRICAL
WORK)
ELECTRICAL GENERAL NOTES:
S1
S2
S1
S2
S3
64H1-25,27
64H1-25,27
64H1-25,27
64H1-25,27
PB
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-35,37
CH1B-35,37
CH1B-35,37 CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-31,33
CH1B-35,37
CH1B-35,37
CH1B-35,37
CH1B-35,37
64H1-21,23
64H1-25,27
64H1-25,27
64H1-21,23
64H1-25,27
64H1-21,23
64H1-21,23
64H1-21,23
64H1-21,23
64H1-21,23
64H1-21,23
64H1-21,23
64H1-25,27
64H1-21,23
64H1-25,27
64H1-21,23
64H1-25,27
64H1-25,27
64H1-25,27
64H1-21,23
64H1-21,23
64H1-25,27
BUILDING
47SOUTH
TOWER
EAST
TOWER
WEST
TOWER
BUILDING
BUILDING
ACA
BUILDING
BUILDING
BUILDING
BUILDING
BUILDING
64H1-25,27
EX
EX
EX
EX
EX
EX
EX
EX
EM-14,16
EM-14,16
EM-14,16
EM-14,16
EM-14,16
EM-14,16
EM-14,16
73T
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-22,24
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-18,20
1CHA-22,24
1CHA
1CHA-18,20,22,24
CH1B-31,33
1CHA-22,24
64H1-21,23
2#6, 1#10G HDPE
LOCATED IN BASEMENT
OF BUILDING 9. PROVIDE
NEW PHOTO-CELL AND
ASTRONOMICAL TIME
CLOCK TO CONTROL
CIRCUITS.
REMOVE EXISTING #8
CONDUCTORS
CURRENTLY INSTALLED.
EXISTING BUILDING
CIRCUIT TO
REMAIN.
EXISTING BUILDING
#24 CIRCUIT
EXISTING BUILDING #14
CIRCUIT
CH1B
CL1B
64H1
64L1
EP
CH1B-31,33
EX
EM-14,16
JB-1
JB1A
JB-2
JB3 1CHA-18,20
JB4
EX
EX
EX
EX
EX
EX
EX
EXEX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EXEX
EXTEND NEW 2#8, 1#10
TO EXISTING AREALIGHT
#A21 WITH HDPE CABLE.
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EXEX
EXEX
EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EP-17
NEW LOCATION OF POLE BASE,
POLE, AND LUMINAIRE. UTILIZE
FROM EXISTING STOCK.
INSTALL NEW PULL BOX.
EXTEND NEW 2#8, 1#10G FROM
EXISTING HANDHOLE TO NEW
AREALIGHT #A3 WITH
HDPE CABLE
EX
EX
EX
EX
EX
EX
#A102
#A101
#A100
#A99
#A98
#A97
#A96
#A88 #A87
#A86
#A85
#P37
#P36
#P35
#P40
#P39
#A84
#A83
#A81
#A82
#A89
#A80
#A79
#A90
#A92 #A91 #A78
#A77 #P21
#A93
#A95
#A94 #P34
#P33
#P32
#P31
#P30
#A75
#A74
#A73
#A76
#A72
#A68
#A69
#A70
#A71
#P20 #P17
#P16
#P15
#P18 #P13
#P14
#AXX
#P19
#A67
#A66
#A63
#A60
#A59
#A58
#A57 #A52
#P12
#P11
#P10
#P9
#P8
#A65
#P7 #A64
#A56
#A65
#A53
#A50
#A54
#A51
#A61 #A62
#A48
#A49
#A46
#A45
#A47
#A43
#A42
#A41
#A39
#A44
#A38
#P6
#A40
#A31
#A32
#A33 #A37
#P4
#A36
#A30
#A29
#A28
#A27
#A23
#A26
#A25
#A24
#A22 #A21
#A20
#A34
#A19
#A18
#P3
#P2 #A35
#A17
#A16
#A15
#A14
#A10
#A9
#A8
#A7
#A6
#A5
#A4
#A2
#A1
#A3
#P1
#A13
#P38
#A11
EX
#A20 #P28
#P27
#P26
#P25
#P24
#P23
#P22
BUILDING
NEW
EXTEND NEW 2#8, 1#10G
TO EXISTING AREALIGHT
#P21 WITH HDPE CABLE.
EX
EX
EX
BUILDING
PROVIDE NEW POLE
BASE PER DETAIL
5/E200.
PB
EXISTING PULLBOX TO
REMAIN. REMOVE EXISTING
POLE BASE IN THIS
LOCATION. RELOCATE POLE
BASE TOPOLE #A3 LOCATION.
MATCHLINE
EP-17
2#8, 1#10G, 1-1/4"C
64H1-25,27
64H1-25,27
NEW 2#8, #10G
HDPE
NEW 2#8, #10G
HDPE
NEW 2#8, #10G
HDPE
EX
#P5
EX
MATCHLINE: BUILDING 9 (FOR REFERENCE ONLY)
MATCHLINE: BUILDING 9 (FOR REFERENCE ONLY
MATCHLINE: BUILDING 7
INSTALL GREEN INSULATED
GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
703 Main Ave, SW
Hickory, NC 28602
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2025
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
02/10/2025 20363
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
02/10/2025
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/1
/2
:3
:0
P
M
E100
SITE PLAN - ELECTRICAL
SBH CJF
SHEET NOTES:
1. CIRCUITING TO BUILDING PANEL NOTED IS INCOMPLETE. CIRCUITING FROM AREA LIGHT #A27 IS
STUBBED UP ON BUILDING EXTERIOR. EXTEND CONDUIT AND CONDUCTORS FROM BOX JB-1A TO
PANEL NOTED. INSTALL NEW 20A BREAKERS. REFER TO DETAIL 6/E000.
2. APPROXIMATE LOCATION OF EXISTING POLE BASE TO BE REMOVED. POLE AND LUMINAIRE SHALL BE MOVED TO NEW BASE INSTALLED AT LOCATION SHOWN (#A81, #A82, #A83, #A84). APPROXIMATELY 40- SQFT OF ASPHALT PATCH WILL BE REQUIRED AT EACH EXISTING POLE BASE LOCATION. REFER TO
ASPHALT SPECIFICATIONS.
3. EXISTING RECENTLY INSTALLED POLE BASE WAS INSTALLED TO 4-FT DEPTH IN LIEU OF SPECIFIED 5-FT DEPTH DUE TO EXISTING UTILITIES BELOW. REMOVE EXISTING POLE BASE AND INSTALL NEW 6.5 FT (4
FT BELOW GRADE) X 30" DIAMETER POLE BASE.
4. REFER TO DETAIL 4/E000.
5. REFER TO DETAIL 3/E000.
6. CIRCUITING TO BUILDING PANEL NOTED IS INCOMPLETE. CIRCUITING FROM AREA LIGHTS CURRENTLY CONSIST OF EMPTY CONDUIT ROUTED FROM MANHOLE TO PANEL. EXTEND CONDUCTORS TO PANEL
NOTED AND INSTALL NEW BREAKERS. REFER TO DETAIL 5/E000.
7. CIRCUITING TO BUILDING PANEL NOTED IS INCOMPLETE. CONDUIT FROM OUTDOOR JUNCTION BOX TO PANEL IS INSTALLED. EXTEND CONDUCTORS NOTED AND INSTALLED NEW BREAKERS TO PANEL 1CHA
IN ROOM 1A137.
8. CIRCUITING TO BUILDING PANEL NOTED IS INCOMPLETE. CONDUIT IS STUBBED UP ON EXTERIOR OF BUILDING. EXTEND CONDUCTORS NOTED AND INSTALL NEW BREAKERS. REFER TO DETAIL 6/E000.
1/64" = 1'-0"
SITE PLAN - ELECTRICAL
PANEL EM LOCATED IN BASEMENT
ROOM B004
Revisions: Date: 53
REMARKS: (LIGHTING FIXTURE SCHEDULE)
1. REFER TO PLANS CIRCUITING FOR REQUIRED VOLTAGE.
GENERAL NOTES: (LIGHTING FIXTURE SCHEDULE)
A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS
AND CATALOG NUMBER PRIOR TO ORDERING.
B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH
'P' (PRIOR APPROVAL), SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM.
WHERE INDICATED WITH 'Y' (YES), THE FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND
CHARACTERISTICS AS THAT SCHEDULED:
1. ACUITY BRANDS
2. EATON/COOPER BRANDS
3. HUBBELL
4. WILLIAMS
5. PHILLIPS/SIGNIFY BRANDS
C. FIXTURE FINISH - WHERE CATALOG NUMBER LISTED INDICATES '**' IN LIEU OF MANUFACTURER'S FINISH OPTION, COORDINATE WITH ARCHITECT FOR EXACT FINISH PRIOR TO ORDERING.
A
B
24"
30"
HANDHOLE
BASE COVER TO MATCH POLE
3/4" CHAMFER
ANCHOR BOLTS
FURNISHED WITH POLE
ROUND POURED
CONCRETE BASE
(EXISTING
UNLESS NOTED
AS NEW ON SITE
PLAN)
SIX (6) #6 VERTICAL REBARS
AND #4 HORIZONTAL
REBARS 12" ON CENTER
16"8'-15'
16'-29'
30'-40'
20"
24"
A (MINIMUM
CONCRETE BASE
DIAMETER OR 2"
LARGER THAN FINAL
SELECTED POLE)
GROUT BETWEEN POLE BASE PLATE
AND CONCRETE BASE
TOOL FINISH AT EDGE OF BASE PLATE
8'-15'
16'-29'
30'-40'
60"
72"
B
48"
#12 (MIN.) TO FIXTURE HEADS
IN-LINE FUSE - EACH PHASE
SPLICE
PHASE CONDUCTORS PER PLAN
POLE
HEIGHT
POLE
HEIGHT
FINISHED SURFACE
SITE LIGHT POLE
(EXISTING UNLESS
NOTED AS NEW ON
SITE PLAN)
#6 BARE BONDED TO REBAR AND POLE
GENERAL NOTE:
1. BOND EQUIPMENT GROUNDING CONDUCTOR TO POLE.
BOND TO EQUIPMENT GROUNDING
CONDUCTOR SIZED PER DRAWINGS.
EXISTING QUAZITE PULL BOX UNLESS
NOTED AS NEW ON SITE PLAN.
PULL NEW CONDUCTORS FROM
EXISTING BOX TO NEW LUMINAIRE
WHERE NOTED.
NOTES:
1. PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE
INSTALLATION.
2. PROGRAM REQUIREMENTS:
NORMAL NIGHTTIME HOURS - LIGHT FIXTURES "ON"
NORMAL DAYTIME HOURS - LIGHT FIXTURES "OFF"
3. COORDINATE PROGRAMMING WITH OWNER.
LIGHTING
CONTROL
PANEL
(PER PLANS)
UNSWITCHED
BRANCH CIRCUIT
POWER PHOTO CELL FROM
BRANCH CIRCUIT HOUSE1-78
PHOTOELECTRIC CONTROL AIMED NORTH.
MOUNT ON 24" RIGID STEM ON ROOF,
LOCATION PER SHEET ES101
LOW VOLTAGE WIRING
PER MANUFACTURER'S
RECOMMENDATIONS
INDIVIDUAL LOW
VOLTAGE INPUT
INDIVIDUAL LIGHTING RELAY
EXTERIOR BUILDING
MOUNTED FIXTURE(S)
EXTERIOR POLE
MOUNTED FIXTURE(S)
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
703 Main Ave, SW
Hickory, NC 28602
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2025
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
02/10/2025 20363
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
02/10/2025
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/1
/2
:3
:0
P
M
E200
ELECTRICAL SCHEDULES &
DETAILS
SBH CJF
EXISTING LIGHTING FIXTURE SCHEDULE
MARK DESCRIPTION MANUFACTURER CATALOG # (NOTE A)
LAMP /
NOMINAL
LUMENS CCT
MINIMUM
CRI MOUNTING REMARKS
B1 BOLLARD LUMEC BOR80-480-TBC1-BKTX 800 4000 70 BOLLARD 1
P1 ARCHITECTUAL POST TOP LIGHT LUMEC L80-SE-SF80-70MH-SE5-480-CRA-APR4-LB
C3-BKTX
1800 4000 70 POST 1
S1 LARGE AREA SINGLE HEAD AREA POLE MOUNTED
LUMINAIRE
GARDCO ECF-L-80L-1.2A-NW-G2-AR-3-480-FP1-BK 36,453 4000 70 POLE 1
S2 SMALL AREA SINGLE HEAD LED AREA LUMINAIRE GARDCO ECF-S-48L-1.2A-NW-G2-AR-2-480-FP2-BK 22,156 4000 70 POLE 1
S3 SMALL AREA DUAL HEAD LED AREA LUMINAIRE GARDCO ECF-S-48L-1.2A-NW-G2-AR-5-480-FP2-BK 23,560 4000 70 POLE 1
U1 GROUND FLOOD LIGHT INSIGHT 5SP-15-40K-15°-TR-UNV-NO-**-DV 927 4000 70 GROUND FLOOD 1
NO SCALEE200
SITE LIGHT POLE BASE - SIZE MAY VARY, REFER TO SITE PLAN2
NO SCALEE200
EXTERIOR LIGHTING (RELAY PANEL)1
208 V
Revisions: Date: 54
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
703 Main Ave, SW
Hickory, NC 28602
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2025
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
02/10/2025 20363
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
02/10/2025
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/1
/2
:3
:1
P
M
E201
ELECTRICAL PANEL SCHEDULES
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING
PROVISIONS / 'R' - PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
86 A
SPARE CAPACITY:
86 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 14347 A
DEMAND CURRENT: 14 A
DEMAND LOAD: 11478 VA
PWR-C 9182 VA 125.00% 11478 VA CONNECTED CURRENT: 11 A
LTG 0 VA 0.00% 0 VA CONNECTED LOAD: 9182 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 10 A 7 A 17 A
TOTAL LOAD: 2726 VA 1865 VA 4591 VA
23 SPARE -- -- 1 -- 1865... 24
21 SPARE -- -- 1 -- 1865 VA
2 20 A SITE LTG (EXISTING)
19 SPARE -- -- 1 -- 2726 VA 20
17 -- 2726...
2 20 A SITE LTG (EXISTING)
15 -- -- 1 -- -- SPARE 16
EXHAUST FAN ABOVE EMV ROOM -- -- 3
-- -- 1 -- -- SPARE 14
11 ISO PANEL 1C12 RM 1A195 -- -- 1 -- -- 1 -- -- SPARE 12
9 OBS/LIGHTING A114, A115, A106,... -- -- 1 -- -- 1 -- -- SPARE 10
7 OBS/LIGHTING A105, A104, A103 -- -- 1 -- -- 1 -- -- SPARE 8
5 CANOPY LIGHTING WEST -- -- 1 -- -- 1 -- -- CANOPY LIGHTING SOUTH 6
3 CANOPY LIGHTING WEST -- -- 1 -- -- 1 -- -- LIGHTING OFFICES 4
1 ISO PANEL 1C11 RM 1A136 -- -- 1 -- -- 1 -- -- LIGHTING ER AREA 2
C... CIRCUIT DESCRIPTION OPT RATI... POL... A B C POL... RATI... OPT CIRCUIT DESCRIPTION C...
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): NA PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: CRITICAL WIRES: 4 MCB OPTIONS: NA
SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: VOLTS: 480/277 WYE MAINS TYPE: MCB
EXISTING PANEL: 1CHA
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING
PROVISIONS / 'R' - PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
79 A
SPARE CAPACITY:
78 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 22170 A
DEMAND CURRENT: 21 A
DEMAND LOAD: 17736 VA
PWR-C 14094 VA 125.00% 17618 VA CONNECTED CURRENT: 17 A
LTG 95 VA 125.00% 118 VA CONNECTED LOAD: 14189 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 26 A 13 A 12 A
TOTAL LOAD: 7094 VA 3650 VA 3444 VA
41 SPACE -- -- 1 -- -- 1 -- -- SPACE 42
39 SPACE -- -- 1 -- -- 1 -- -- SPACE 40
37 3444... -- 1 -- -- SPACE 38
SITE LTG (EXISTING) 20 A 2
3444 VA -- 1 -- -- SPACE 36
33 3650 VA -- 1 -- -- SPACE 34
SITE LTG (EXISTING) 20 A 2
3650... -- 1 -- -- SPACE 32
29 -- -- 1 -- -- SPACE 30
27 -- -- 1 -- -- SPACE 28
PANEL CH2B -- -- 3
-- -- 1 -- -- SPACE 26
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 -- -- 1 -- -- SPACE 18
15 -- -- 1 -- -- SPACE 16
PANEL CL1B -- -- 3
-- -- 1 -- -- SPACE 14
11 SPACE -- -- 1 -- -- 1 -- -- SPACE 12
9 SPARE -- -- 1 -- -- 1 -- -- SPACE 10
7 PAT. RM. LIGHTS -- -- 1 -- -- 1 -- -- SPARE 8
5 SPARE -- -- 1 -- -- 1 -- -- PAT. RM. LIGHTS 6
3 PAT. RM. LIGHTS -- -- 1 -- -- 1 -- -- SPARE 4
1 PAT. RM. LIGHTSS -- -- 1 -- -- 1 -- -- CORE LIGHTS 2
C... CIRCUIT DESCRIPTION OPT RATI... POL... A B C POL... RATI... OPT CIRCUIT DESCRIPTION C...
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): NA PANEL POLES: 42
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: CRITICAL WIRES: 4 MCB OPTIONS: NA
SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: VOLTS: 480/277 WYE MAINS TYPE: MCB
EXISTING PANEL: CH1B
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING
PROVISIONS / 'R' - PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
96 A
SPARE CAPACITY:
95 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 2002 A
DEMAND CURRENT: 4 A
DEMAND LOAD: 1601 VA
CONNECTED CURRENT: 4 A
LTG 1281 VA 125.00% 1601 VA CONNECTED LOAD: 1281 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 6 A 6 A 0 A
TOTAL LOAD: 641 VA 641 VA 0 VA
41 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 42
39 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 40
37 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 38
35 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 36
33 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 34
31 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 32
29 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 30
27 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 28
25 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 26
23 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 24
21 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 22
19 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 20
17 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 18
15 EXISTING -- -- 1 -- 641 VA 16
13 EXISTING -- -- 1 -- 641 VA
2 20 A SITE LTG (NEW)
11 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 12
9 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 10
7 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 8
5 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 6
3 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 4
1 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 2
C... CIRCUIT DESCRIPTION OPT RATI... POL... A B C POL... RATI... OPT CIRCUIT DESCRIPTION C...
NEMA ENCLOSURE: NEMA
MOUNTING: SURFACE AVAILABLE SCC (kA): NA PANEL POLES: 42
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS: NA
SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: VOLTS: 208/120 WYE MAINS TYPE: MCB
EXISTING PANEL: EM
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING
PROVISIONS / 'R' - PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
60 A
SPARE CAPACITY:
60 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 41248 A
DEMAND CURRENT: 40 A
DEMAND LOAD: 32999 VA
PWR-C 26210 VA 125.00% 32763 VA CONNECTED CURRENT: 32 A
LTG 189 VA 125.00% 236 VA CONNECTED LOAD: 26399 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 38 A 38 A 24 A
TOTAL LOAD: 9900 VA 9900 VA 6600 VA
41 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 42
39 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 40
37 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 38
35 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 36
33 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 34
31 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 32
29 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 30
27 3300 VA -- 1 -- -- EXISTING 28
SITE LTG (NEW) 20 A 2
3300... -- 1 -- -- EXISTING 26
23 3300 VA -- 1 -- -- EXISTING 24
SITE LTG (NEW) 20 A 2
3300 VA -- 1 -- -- EXISTING 22
19 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 20
17 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 18
15 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 16
13 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 14
11 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 12
9 EXISTING -- -- 1 -- -- 1 -- -- EXISTING 10
7 3300... -- 1 -- -- EXISTING 8
SITE LTG (NEW) 20 A 2
3300 VA -- 1 -- -- EXISTING 6
3 3300 VA -- 1 -- -- EXISTING 4
SITE LTG (NEW) 20 A 2
3300... -- 1 -- -- EXISTING 2
C... CIRCUIT DESCRIPTION OPT RATI... POL... A B C POL... RATI... OPT CIRCUIT DESCRIPTION C...
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): NA PANEL POLES: 42
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS: NA
SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: VOLTS: 480/277 WYE MAINS TYPE: MCB
EXISTING PANEL: 64H1
PROVIDE NEW PANEL INTERIOR FOR
EXISTING PANEL CH1B LOCATED IN
BUILDING 42. RECONNECT EXISTING
CIRCUITS NOTED. COORDINATE
DOWNTIME WITH THE VA.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING
PROVISIONS / 'R' - PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
94 A
SPARE CAPACITY:
94 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 2573 A
DEMAND CURRENT: 6 A
DEMAND LOAD: 2059 VA
CONNECTED CURRENT: 5 A
LTG 1647 VA 125.00% 2059 VA CONNECTED LOAD: 1647 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 0 A 0 A 14 A
TOTAL LOAD: 0 VA 0 VA 1647 VA
41 GEN RECPT OUTSIDE -- -- 1 -- -- 1 -- -- SPACE 42
39 GEN RECPT OUTSIDE -- -- 1 -- -- 1 -- -- SPACE 40
37 DC CONVERTER -- -- 1 -- -- 1 -- -- UPS 38
35 UPS -- -- 1 -- -- 1 -- -- UPS 36
33 UPS -- -- 1 -- -- 1 -- -- UPS 34
31 RECPT ON EP PANEL -- -- 1 -- -- 1 -- -- AUTOMATIC DOORS 32
29 DOOR ACCESS -- -- 1 -- -- 1 -- -- AUTOMATIC DOORS 30
27 STORE ROOMS HALL END -- -- 1 -- -- 1 -- -- AREA OF RESCUE 28
25 SPARE -- -- 1 -- -- 1 -- -- SMOKE DAMPER 1ST FLOOR 26
23 ELEV EXIT 2ND FLOOR HALL LT -- -- 1 -- -- 1 -- -- CONTROL PANEL BASE 24
21 WEST END STAIRWELL -- -- 1 -- -- 1 -- -- FIRE ALARM PANEL 1ST PANEL 22
19 SITE LIGHTING -- -- 1 -- -- 1 -- -- RECPT HALLWAY 2ND FLOOR 20
17 SITE LIGHTING (NEW) 20 A 1 1647 VA -- 1 -- -- IRM RECEPT 211 + 318 18
15 WEST END STAIRWELL -- -- 1 -- -- 1 -- -- CENTER STAIRWELL REC,... 16
13 OLD FIRE ALARM -- -- 1 -- -- 1 -- -- RECPT 3RD FLOOR HALLWAY 14
11 3STOP ELEVATOR -- -- 1 -- -- 1 -- -- CONTROL ROOM CIRCUIT 12
9 4STOP ELEVATOR -- -- 1 -- -- 1 -- -- LIGHTING STAIRWELL 2ND FLOOR 10
7 3RD FLOOR -- -- 1 -- -- 1 -- -- FRONT OUTSIDE LIGHT LOWER 8
5 EMEMRGENCY RECPT IN HALLWAY -- -- 1 -- -- 1 -- -- RECPT 3RD FLOOR HALLWAY 6
3 -- -- 1 -- -- RECPT 2ND FLOOR 4
SPARE -- -- 2
-- -- 1 -- -- EMERGENCY LIGHTING 2
C... CIRCUIT DESCRIPTION OPT RATI... POL... A B C POL... RATI... OPT CIRCUIT DESCRIPTION C...
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): NA PANEL POLES: 42
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS: NA
SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: VOLTS: 208/120 WYE MAINS TYPE: MCB
EXISTING PANEL: EP
Revisions: Date: 55
| Sheets and Views |
| GI001 |
| 2-E000 - ELECTRICAL SYMBOLS AND ABBREVIATIONS |
| 3-E100 - SITE PLAN - ELECTRICAL |
| 4-E200 - ELECTRICAL SCHEDULES & DETAILS |
| 5-E201 - ELECTRICAL PANEL SCHEDULES |
File details come from the government source that posted it. Updated .