Attachment III - Sheet - E000 - ELECTRICAL SYMBOLS AND ABBREVIATIONS.pdf

PDF 6 MB Posted

Attached to
Z1NZ--Expand and Rewire Parking Lighting
Solicitation number
36C24625B0027
Issued by

About this file

This document is an Electrical Symbols and Abbreviations sheet for a Veterans Affairs (VA) project involving parking lighting expansion and rewiring at the Charles George VAMC in Asheville, NC. The sheet provides comprehensive electrical abbreviations, including standard industry acronyms for electrical components like amperage (A, AF, AT), circuit breakers (CB), transformers (XFMR), and various technical descriptors. The document also includes several critical general electrical notes, such as requirements for fire-rated wall penetrations, equipment damage replacement, wiring device matching, and specific electrical system bonding and protection guidelines for critical and life safety branch circuits.

The sheet is part of the construction bid documents for project number 637-20-104, prepared by Atriax PLLC and Specialized Engineering Solutions, with a bid/issue date of 07/11/2025. It includes electrical symbols for branch circuits, conduit, lighting fixtures, and security elements, along with a sheet index for the electrical drawing set. The document is specifically associated with the VA Veterans Health Administration's project for expanding and rewiring parking lighting at the Asheville, NC medical center, with detailed technical specifications to guide electrical installation and compliance.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATIONS

ABBREVIATION DESCRIPTION

REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.

MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)

AMPERE

AMPERE FRAME

ABOVE FINISHED FLOOR

ALUMINUM

AMPERE TRIP

CEILING

CIRCUIT BREAKER

COLOR TEMP CONTROL

COPPER

DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)

DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)

EXISTING

ELECTRICALLY OPERATED

ENERGY REDUCING MAINTENANCE SWITCH

FUSE

FULL LOAD AMPS

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT ALARM

GROUND FAULT PROTECTION

HORSEPOWER

KILOAMPERE INTERRUPTING CAPACITY

KILOVOLT AMPERE

KILOWATT

MAXIMUM

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MINIMUM

MAIN LUGS ONLY

MANUALLY OPERATED

NORMALLY CLOSED

NON-FUSED

NOT IN CONTRACT

NORMALLY OPEN

POLES

PARTIAL

RELOCATE

SHORT CIRCUIT CURRENT RATING

SURGE PROTECTIVE DEVICE

SHUNT TRIP

TYPICAL

UNLESS NOTED OTHERWISE

VOICE

WALL PHONE

WIRE

WEATHER RESISTANT

TRANSFORMER

ZONE SELECTIVE INTERLOCKING

A

AF

AFF

AL

AT

C

CB

CCT

CU

D

D

E

EO

ERMS

F

FLA

G, GFCI

GFA

GFP

HP

KAIC

KVA

KW

MAX

MCA

MCB

MIN

MLO

MO

NC

NF

NIC

NO

P

PART

R

SCCR

SPD

ST

TYP

UNO

V

W

W

WR

XFMR

ZSI

A. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE

SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.

B. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL

COST TO THE OWNER.

C. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR

INSTALLED DEVICES.

D. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS

ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND

PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.

E. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL

NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME

INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.

F. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE

ENTIRE CIRCUIT LENGTH.

G. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN

CABLING.

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

ELECTRICAL GENERAL NOTES:

Location

Issue Date www.atriaxgroup.com

Atriax PLLC

703 Main Ave, SW

Hickory, NC 28602

Phone: 828.315.9962

Fax: 828.315.9964

NC Engineering License No.: P-0214

Exp. Date: 6/30/2021

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND

REWIRING

Charles George VAMC, ASHEVILLE NC

Dwg. of

VA FORM 08 - 6231

A

CONSTRUCTION

BID

DOCUMENTS

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

637-20-104

N/A

07/11/2025 20363

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

704.348.3097

02/10/2025

B

IM

/2

V A

A s h e v ill e E x p a n d P a rk in g L ig h ti n g

/2

V A

A s h e v ill e E x p a n d P a rk in g L ig h ti n g S

E S

.r v t

/1

/2

:4

:1

P

M

E000

ELECTRICAL SYMBOLS AND

ABBREVIATIONS

SBH CJF

ELECTRICAL MISC SYMBOLS

PLAN SYMBOL NAME

BRANCH CIRCUIT CONCEALED IN

CEILING OR WALL

BRANCH CIRCUIT CONCEALED IN

FLOOR OR BELOW GRADE

CLEARANCE SPACE

CONDUIT BREAK

CONDUIT DOWN

CONDUIT STUB-OUT

CONDUIT UP

HOMERUN TO PANEL

G = GFCI CIRCUIT

(PART) = PARTIAL CIRCUIT

PANEL NAME - CIRCUIT NUMBER

LIGHTING FIXTURE

SYMBOLS

PLAN SYMBOL NAME

AREA POLE LIGHT WITH

DESIGNATION

BOLLARD OR POST TOP

LUMINAIRE

EMERGENCY HATCH

SHEET INDEX - ELECTRICAL

Sheet Number Sheet Name

E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS

E100 SITE PLAN - ELECTRICAL

E200 ELECTRICAL SCHEDULES & DETAILS

E201 ELECTRICAL PANEL SCHEDULES

#AXX

NO SCALEE000

BUILDING 9 - PANEL EM3

NO SCALEE000

BUILDING 15 - PANEL EP4

NO SCALEE000

BUILDING 62 - PANEL CH1B5

NO SCALEE000

BUILDING 64 - PANEL 64H16

SECURITY SYMBOLS

PLAN SYMBOL NAME

POLE-MOUNTED CAMERA WITH

LIGHT

Revisions: Date:

Addendum #1 7/11/2025

Sheets
E000 - ELECTRICAL SYMBOLS AND ABBREVIATIONS
E100 - SITE PLAN - ELECTRICAL
E200 - ELECTRICAL SCHEDULES & DETAILS