This document is an electrical schedules and details drawing (Sheet E200) for the Charles George VAMC parking lighting expansion project in Asheville, NC. The drawing includes a comprehensive existing lighting fixture schedule detailing specific luminaire types, manufacturers, and specifications, with six different fixture types mapped out: bollards (B1), architectural post-top lights (P1), large and small area single and dual-head LED area luminaires (S1, S2, S3), and ground flood lights (U1). The document provides detailed technical specifications including manufacturer catalog numbers, lumen outputs, color temperature (CCT), color rendering index (CRI), and mounting details.

The drawing also includes critical installation notes regarding substitution policies, which allow alternative manufacturers like Acuity Brands, Eaton/Cooper, Hubbell, Williams, and Phillips/Signify, provided equivalent fixture quality and performance. Additional technical details cover site light pole base configurations, electrical grounding requirements, lighting control programming (normal nighttime/daytime hours), and photocell mounting instructions. The project is part of VA solicitation 36C24625B0027 for expanding and rewiring parking lighting at the Charles George VAMC, with the drawing prepared by Specialized Engineering Solutions and Atriax PLLC, dated 07/11/2025.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REMARKS: (LIGHTING FIXTURE SCHEDULE)

1. REFER TO PLANS CIRCUITING FOR REQUIRED VOLTAGE.

GENERAL NOTES: (LIGHTING FIXTURE SCHEDULE)

A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS

AND CATALOG NUMBER PRIOR TO ORDERING.

B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH

'P' (PRIOR APPROVAL), SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM.

WHERE INDICATED WITH 'Y' (YES), THE FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND

CHARACTERISTICS AS THAT SCHEDULED:

1. ACUITY BRANDS

2. EATON/COOPER BRANDS

3. HUBBELL

4. WILLIAMS

5. PHILLIPS/SIGNIFY BRANDS

C. FIXTURE FINISH - WHERE CATALOG NUMBER LISTED INDICATES '**' IN LIEU OF MANUFACTURER'S FINISH OPTION, COORDINATE WITH ARCHITECT FOR EXACT FINISH PRIOR TO ORDERING.

A

B

24"

30"

HANDHOLE

BASE COVER TO MATCH POLE

3/4" CHAMFER

ANCHOR BOLTS

FURNISHED WITH POLE

ROUND POURED

CONCRETE BASE

(EXISTING

UNLESS NOTED

AS NEW ON SITE

PLAN)

SIX (6) #6 VERTICAL REBARS

AND #4 HORIZONTAL

REBARS 12" ON CENTER

16"8'-15'

16'-29'

30'-40'

20"

24"

A (MINIMUM

CONCRETE BASE

DIAMETER OR 2"

LARGER THAN FINAL

SELECTED POLE)

GROUT BETWEEN POLE BASE PLATE

AND CONCRETE BASE

TOOL FINISH AT EDGE OF BASE PLATE

8'-15'

16'-29'

30'-40'

60"

72"

B

48"

#12 (MIN.) TO FIXTURE HEADS

IN-LINE FUSE - EACH PHASE

SPLICE

PHASE CONDUCTORS PER PLAN

POLE

HEIGHT

POLE

HEIGHT

FINISHED SURFACE

SITE LIGHT POLE

(EXISTING UNLESS

NOTED AS NEW ON

SITE PLAN)

#6 BARE BONDED TO REBAR AND POLE

GENERAL NOTE:

1. BOND EQUIPMENT GROUNDING CONDUCTOR TO POLE.

BOND TO EQUIPMENT GROUNDING

CONDUCTOR SIZED PER DRAWINGS.

EXISTING QUAZITE PULL BOX UNLESS

NOTED AS NEW ON SITE PLAN.

PULL NEW CONDUCTORS FROM

EXISTING BOX TO NEW LUMINAIRE

WHERE NOTED.

NOTES:

1. PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE

INSTALLATION.

2. PROGRAM REQUIREMENTS:

NORMAL NIGHTTIME HOURS - LIGHT FIXTURES "ON"

NORMAL DAYTIME HOURS - LIGHT FIXTURES "OFF"

3. COORDINATE PROGRAMMING WITH OWNER.

LIGHTING

CONTROL

PANEL

(PER PLANS)

UNSWITCHED

BRANCH CIRCUIT

POWER PHOTO CELL FROM

BRANCH CIRCUIT HOUSE1-78

PHOTOELECTRIC CONTROL AIMED NORTH.

MOUNT ON 24" RIGID STEM ON ROOF,

LOCATION PER SHEET ES101

LOW VOLTAGE WIRING

PER MANUFACTURER'S

RECOMMENDATIONS

INDIVIDUAL LOW

VOLTAGE INPUT

INDIVIDUAL LIGHTING RELAY

EXTERIOR BUILDING

MOUNTED FIXTURE(S)

EXTERIOR POLE

MOUNTED FIXTURE(S)

Location

Issue Date www.atriaxgroup.com

Atriax PLLC

703 Main Ave, SW

Hickory, NC 28602

Phone: 828.315.9962

Fax: 828.315.9964

NC Engineering License No.: P-0214

Exp. Date: 6/30/2021

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND

REWIRING

Charles George VAMC, ASHEVILLE NC

Dwg. of

VA FORM 08 - 6231

A

CONSTRUCTION

BID

DOCUMENTS

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

637-20-104

N/A

07/11/2025 20363

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

704.348.3097

02/10/2025

B

IM

/2

V A

A s h e v ill e E x p a n d P a rk in g L ig h ti n g

/2

V A

A s h e v ill e E x p a n d P a rk in g L ig h ti n g S

E S

.r v t

/1

/2

:5

:3

P

M

E200

ELECTRICAL SCHEDULES &

DETAILS

SBH CJF

EXISTING LIGHTING FIXTURE SCHEDULE - FOR REFERENCE ONLY

MARK DESCRIPTION MANUFACTURER CATALOG # (NOTE A)

LAMP /

NOMINAL

LUMENS CCT

MINIMUM

CRI MOUNTING REMARKS

B1 BOLLARD LUMEC BOR80-480-TBC1-BKTX 800 4000 70 BOLLARD 1

P1 ARCHITECTUAL POST TOP LIGHT LUMEC L80-SE-SF80-70MH-SE5-480-CRA-APR4-LB

C3-BKTX

1800 4000 70 POST 1

S1 LARGE AREA SINGLE HEAD AREA POLE MOUNTED

LUMINAIRE

GARDCO ECF-L-80L-1.2A-NW-G2-AR-3-480-FP1-BK 36,453 4000 70 POLE 1

S2 SMALL AREA SINGLE HEAD LED AREA LUMINAIRE GARDCO ECF-S-48L-1.2A-NW-G2-AR-2-480-FP2-BK 22,156 4000 70 POLE 1

S3 SMALL AREA DUAL HEAD LED AREA LUMINAIRE GARDCO ECF-S-48L-1.2A-NW-G2-AR-5-480-FP2-BK 23,560 4000 70 POLE 1

U1 GROUND FLOOD LIGHT INSIGHT 5SP-15-40K-15°-TR-UNV-NO-**-DV 927 4000 70 GROUND FLOOD 1

NO SCALEE200

SITE LIGHT POLE BASE - SIZE MAY VARY, REFER TO SITE PLAN2

NO SCALEE200

EXTERIOR LIGHTING (RELAY PANEL)1

1 1

1 1 1