Attachment V - Sheet - E200 - ELECTRICAL SCHEDULE DETAILS.pdf
PDF 398 KB Posted
- Attached to
- Z1NZ--Expand and Rewire Parking Lighting
- Solicitation number
- 36C24625B0027
About this file
This document is an electrical schedules and details drawing (Sheet E200) for the Charles George VAMC parking lighting expansion project in Asheville, NC. The drawing includes a comprehensive existing lighting fixture schedule detailing specific luminaire types, manufacturers, and specifications, with six different fixture types mapped out: bollards (B1), architectural post-top lights (P1), large and small area single and dual-head LED area luminaires (S1, S2, S3), and ground flood lights (U1). The document provides detailed technical specifications including manufacturer catalog numbers, lumen outputs, color temperature (CCT), color rendering index (CRI), and mounting details.
The drawing also includes critical installation notes regarding substitution policies, which allow alternative manufacturers like Acuity Brands, Eaton/Cooper, Hubbell, Williams, and Phillips/Signify, provided equivalent fixture quality and performance. Additional technical details cover site light pole base configurations, electrical grounding requirements, lighting control programming (normal nighttime/daytime hours), and photocell mounting instructions. The project is part of VA solicitation 36C24625B0027 for expanding and rewiring parking lighting at the Charles George VAMC, with the drawing prepared by Specialized Engineering Solutions and Atriax PLLC, dated 07/11/2025.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REMARKS: (LIGHTING FIXTURE SCHEDULE)
1. REFER TO PLANS CIRCUITING FOR REQUIRED VOLTAGE.
GENERAL NOTES: (LIGHTING FIXTURE SCHEDULE)
A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS
AND CATALOG NUMBER PRIOR TO ORDERING.
B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH
'P' (PRIOR APPROVAL), SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM.
WHERE INDICATED WITH 'Y' (YES), THE FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND
CHARACTERISTICS AS THAT SCHEDULED:
1. ACUITY BRANDS
2. EATON/COOPER BRANDS
3. HUBBELL
4. WILLIAMS
5. PHILLIPS/SIGNIFY BRANDS
C. FIXTURE FINISH - WHERE CATALOG NUMBER LISTED INDICATES '**' IN LIEU OF MANUFACTURER'S FINISH OPTION, COORDINATE WITH ARCHITECT FOR EXACT FINISH PRIOR TO ORDERING.
A
B
24"
30"
HANDHOLE
BASE COVER TO MATCH POLE
3/4" CHAMFER
ANCHOR BOLTS
FURNISHED WITH POLE
ROUND POURED
CONCRETE BASE
(EXISTING
UNLESS NOTED
AS NEW ON SITE
PLAN)
SIX (6) #6 VERTICAL REBARS
AND #4 HORIZONTAL
REBARS 12" ON CENTER
16"8'-15'
16'-29'
30'-40'
20"
24"
A (MINIMUM
CONCRETE BASE
DIAMETER OR 2"
LARGER THAN FINAL
SELECTED POLE)
GROUT BETWEEN POLE BASE PLATE
AND CONCRETE BASE
TOOL FINISH AT EDGE OF BASE PLATE
8'-15'
16'-29'
30'-40'
60"
72"
B
48"
#12 (MIN.) TO FIXTURE HEADS
IN-LINE FUSE - EACH PHASE
SPLICE
PHASE CONDUCTORS PER PLAN
POLE
HEIGHT
POLE
HEIGHT
FINISHED SURFACE
SITE LIGHT POLE
(EXISTING UNLESS
NOTED AS NEW ON
SITE PLAN)
#6 BARE BONDED TO REBAR AND POLE
GENERAL NOTE:
1. BOND EQUIPMENT GROUNDING CONDUCTOR TO POLE.
BOND TO EQUIPMENT GROUNDING
CONDUCTOR SIZED PER DRAWINGS.
EXISTING QUAZITE PULL BOX UNLESS
NOTED AS NEW ON SITE PLAN.
PULL NEW CONDUCTORS FROM
EXISTING BOX TO NEW LUMINAIRE
WHERE NOTED.
NOTES:
1. PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE
INSTALLATION.
2. PROGRAM REQUIREMENTS:
NORMAL NIGHTTIME HOURS - LIGHT FIXTURES "ON"
NORMAL DAYTIME HOURS - LIGHT FIXTURES "OFF"
3. COORDINATE PROGRAMMING WITH OWNER.
LIGHTING
CONTROL
PANEL
(PER PLANS)
UNSWITCHED
BRANCH CIRCUIT
POWER PHOTO CELL FROM
BRANCH CIRCUIT HOUSE1-78
PHOTOELECTRIC CONTROL AIMED NORTH.
MOUNT ON 24" RIGID STEM ON ROOF,
LOCATION PER SHEET ES101
LOW VOLTAGE WIRING
PER MANUFACTURER'S
RECOMMENDATIONS
INDIVIDUAL LOW
VOLTAGE INPUT
INDIVIDUAL LIGHTING RELAY
EXTERIOR BUILDING
MOUNTED FIXTURE(S)
EXTERIOR POLE
MOUNTED FIXTURE(S)
Location
Issue Date www.atriaxgroup.com
Atriax PLLC
703 Main Ave, SW
Hickory, NC 28602
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
Exp. Date: 6/30/2021
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT EXPAND PARKING LIGHTING AND
REWIRING
Charles George VAMC, ASHEVILLE NC
Dwg. of
VA FORM 08 - 6231
A
CONSTRUCTION
BID
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
637-20-104
N/A
07/11/2025 20363
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
704.348.3097
02/10/2025
B
IM
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g
/2
V A
A s h e v ill e E x p a n d P a rk in g L ig h ti n g S
E S
.r v t
/1
/2
:5
:3
P
M
E200
ELECTRICAL SCHEDULES &
DETAILS
SBH CJF
EXISTING LIGHTING FIXTURE SCHEDULE - FOR REFERENCE ONLY
MARK DESCRIPTION MANUFACTURER CATALOG # (NOTE A)
LAMP /
NOMINAL
LUMENS CCT
MINIMUM
CRI MOUNTING REMARKS
B1 BOLLARD LUMEC BOR80-480-TBC1-BKTX 800 4000 70 BOLLARD 1
P1 ARCHITECTUAL POST TOP LIGHT LUMEC L80-SE-SF80-70MH-SE5-480-CRA-APR4-LB
C3-BKTX
1800 4000 70 POST 1
S1 LARGE AREA SINGLE HEAD AREA POLE MOUNTED
LUMINAIRE
GARDCO ECF-L-80L-1.2A-NW-G2-AR-3-480-FP1-BK 36,453 4000 70 POLE 1
S2 SMALL AREA SINGLE HEAD LED AREA LUMINAIRE GARDCO ECF-S-48L-1.2A-NW-G2-AR-2-480-FP2-BK 22,156 4000 70 POLE 1
S3 SMALL AREA DUAL HEAD LED AREA LUMINAIRE GARDCO ECF-S-48L-1.2A-NW-G2-AR-5-480-FP2-BK 23,560 4000 70 POLE 1
U1 GROUND FLOOD LIGHT INSIGHT 5SP-15-40K-15°-TR-UNV-NO-**-DV 927 4000 70 GROUND FLOOD 1
NO SCALEE200
SITE LIGHT POLE BASE - SIZE MAY VARY, REFER TO SITE PLAN2
NO SCALEE200
EXTERIOR LIGHTING (RELAY PANEL)1
1 1
1 1 1
Revisions: Date:
Addendum #1 7/11/2025
1 1 1
| Sheets |
| E200 - ELECTRICAL SCHEDULES & DETAILS |
File details come from the government source that posted it. Updated .