36C24619B0040-008.pdf

PDF Posted

Attached to
652-318 Construct Cancer Center (VA-19-00013696)
Solicitation number
36C24619B0040
Issued by

About this file

This solicitation seeks proposals for a construction project to build a 15,000 square foot cancer center addition at a VA medical center in Richmond, Virginia. The project is valued between $5-10 million and has a period of performance of 630 calendar days from notice to proceed. The NAICS code is 236220 with a $36.5 million small business size standard. Drawings and specifications will be provided in the solicitation, which is open only to Service-Disabled Veteran-Owned Small Businesses. Proposals are due on or around August 15, 2019 following a pre-proposal site visit. The selected contractor will provide all labor, materials, equipment, transportation and supervision to complete the project in accordance with the construction documents prepared by Miller-Remick, LLC.

36C24619B0040 S02 Architectural.pdf

View the file

Other files

File Type Posted
36C24619B0040-0003007.pdf PDF
36C24619B0040-0003001.pdf PDF
36C24619B0040-0003004.pdf PDF
36C24619B0040-0003006.pdf PDF
36C24619B0040-0003003.pdf PDF
36C24619B0040-0003005.pdf PDF
36C24619B0040-0003000.docx DOCX document
36C24619B0040-0003002.pdf PDF
36C24619B0040-0003000.docx DOCX document
36C24619B0040-0003004.pdf PDF
36C24619B0040-0003001.pdf PDF
36C24619B0040-0003007.pdf PDF
36C24619B0040-0003002.pdf PDF
36C24619B0040-0003003.pdf PDF
36C24619B0040-0003006.pdf PDF
36C24619B0040-0003005.pdf PDF
36C24619B0040-0002000.docx DOCX document
36C24619B0040-0002000.docx DOCX document
36C24619B0040-0001000.docx DOCX document
36C24619B0040-0001000.docx DOCX document
36C24619B0040-003.pdf PDF
36C24619B0040-004.pdf PDF
36C24619B0040-010.pdf PDF
36C24619B0040-001.docx DOCX document
36C24619B0040-013.pdf PDF
36C24619B0040-005.pdf PDF
36C24619B0040-007.pdf PDF
36C24619B0040-011.pdf PDF
36C24619B0040-006.pdf PDF
36C24619B0040-012.pdf PDF
36C24619B0040-009.pdf PDF
36C24619B0040-002.docx DOCX document
36C24619B0040-003.pdf PDF
36C24619B0040-009.pdf PDF
36C24619B0040-008.pdf PDF
36C24619B0040-011.pdf PDF
36C24619B0040-013.pdf PDF
36C24619B0040-002.docx DOCX document
36C24619B0040-007.pdf PDF
36C24619B0040-004.pdf PDF
36C24619B0040-012.pdf PDF
36C24619B0040-001.docx DOCX document
36C24619B0040-010.pdf PDF
36C24619B0040-006.pdf PDF
36C24619B0040-005.pdf PDF
36C24619B0040-000.docx DOCX document
36C24619B0040-000.docx DOCX document
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAXIMUM

MECHANICAL

MOUNTING

METAL

NOT IN CONTRACT

OPPOSITE HAND

PLASTIC LAMINATE

PAINT

PAINTED

RISER

RETURN AIR

RUBBER BASE

SEALED CONCRETE

SOLID SURFACE

SHEET VINYL

SIMILAR

STORAGE

SUSPENDED

TREAD

TOP OF BOND BEAM

TOP OF STRUCTURE

TYPICAL

VA FURNISHED

CONTRACTOR INSTALLED

VA FURNISHED

VA INSTALLED

VERTICAL

VINYL WALL COVERING

EXPANDED POLY STYRENE

AT

ANGLE

CENTER LINE

DIAMETER

ABOVE FINISH FLOOR

ACOUSTICAL TILE

ALUMINUM THRESHOLD

VINYL BASE

CUBICLE CURTAIN

CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CONTRACTOR FURNISHED

VA INSTALLED

CORNER GUARD

CEILING

COLUMN

CONCRETE

CONTINUOUS

CORRIDOR

CERAMIC TILE

ELECTRIC(AL)

ELEVATOR

EXISTING TO REMAIN

ELECTRIC WATER COOLER

EXISTING

FINISH(ED)

FACE OF FINISH

FACE OF STUD

GYSPUM WALLBOARD

HARDWARE

HOUR

HEIGHT

LENGTH

LUXURY VINYL TILE

A.F.F.

ACT

ATH.

BV

CC

CFCI

CFVA

CG

CLG

COL

CONC

CONT

CORR

CT

ELEC

ELEV

ETR

EWC

EXST

FIN

FOF

FOS

GWB

HDWR

HR

HT

L

LVT

MAX

MECH

MTG

MTL

NIC

O H

PLAM

PNT

PTD

R

RA

RB

SC

SS

SV

SIM

STOR

SUSP

T

TOBB

TOS

TYP

VACI

VAVA

VERT

WVW

XPS

O

ABBREVIATIONS

DOOR TAG

TYP.

1i

M349

ACE

EXISTING DOOR

NEW DOOR

DEMO DOOR

NEW WALL

EXISTING WALL

DEMO WALL OR ITEMS

ABOVE OR BELOW

WALL PROTECTION TAG

WALL TAG

ROOM NUMBER

REVISION TAG

EQUIPMENT TAG

TOILET ACCESSORY TAG

DEMOLITION NOTE

NEW WORK NOTE

A810

DEMO ROOM NUMBER

CURTAINWALL AND

WINDOW MARKER

1i

INTERIOR ELEVATION

MARKER

SECTION OR WALL

SECTION NUMBER

COLUMN GRID NUMBER

EXISTING COLUMN

GRID NUMBER

A120

BUILDING ELEVATION

MARKER

A810

A810 DETAIL MARKER

ARCHITECTURAL SYMBOL LEGEND

1 PHASING NOTES

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

BID DOCUMENTS

FULLY SPRINKLERED

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AG001

EXTERIOR RENDERING PREVIEWS,

ABBREVIATIONS, AND SYMBOLS

JCHDJP

11/08/18

NORTHEAST AERIAL VIEWNORTH GROUND LEVEL VIEW

SECOND LEVEL VIEW FROM DIALYSIS

WALL TYPE SCHEDULE

TYPE STC DESCRIPTION FIRE RATING UL REMARKS

C8_1 N/A

8" CMU WITH CONTINUOUS HORIZONTAL JOINT REINFORCING @

16" O.C. VERTICALY. EXTEND WALL ASSEMBLY TO DECK ABOVE

1 HR BARRIER U905

PROVIDE 3" STENCILED TEXT EVERY 8' O.C. MAX. READING "1 HR FIRE

BARRIER". PROVIDE FIRE SAFING WHERE COMPONETS MEET DECK

ABOVE.

C8_1f N/A

8" CMU, CONTINUOUS HORIZONTAL JOINT REINFORCING @ 16"

O.C. VERTICALY, 7/8" METAL FURRING CHANNEL, 5/8" GWB.

EXTEND WALL ASSEMBLY TO DECK ABOVE

1 HR BARRIER U905

PROVIDE 3" STENCILED TEXT EVERY 8' O.C. MAX. READING "1 HR FIRE

BARRIER". PROVIDE FIRE SAFING WHERE COMPONETS MEET DECK

ABOVE.

M1 h N/A

7/8" METAL HAT CHANNEL AT 16" O.C. MAX. 5/8" GWB ONE SIDE.

EXTEND WALL ASSEMBLY TO 4" ABOVE FINISHED CEILING.

N/A N/A

M1_C N/A

1 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE.

EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.

SMOKE PARTITION N/A

PROVIDE 3" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE

PARTITION". PROVIDE INSULATION WHERE COMPONENTS MEET

DECK ABOVE. PROVIDE ACOUSTICAL SEALANT AT RUNNER AND

HEAD PRIOR TO INSTALLATION OF GWB.

M1B N/A

1 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE.

EXTEND WALL ASSEMBLY TO 4" ABOVE FINISHED CEILING.

N/A N/A

M2B N/A

2 1/2" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE.

EXTEND WALL ASSEMBLY TO 4" ABOVE FINISHED CEILING.

N/A N/A

M3 N/A

3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES.

EXTEND WALL ASSEMBLY TO 4" ABOVE FINISHED CEILING.

N/A N/A

M3_1 40

3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH

SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK

ABOVE.

1 HR BARRIER U419

PROVIDE 3" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE

BARRIER". PROVIDE INSULATION WHERE COMPONENTS MEET DECK

ABOVE. PROVIDE SEALANT AT RUNNER AND HEAD PRIOR TO

INSTALLATION OF GWB

M3_1C 40

3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH

SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK

ABOVE.

1 HR SMOKE

BARRIER

U419

PROVIDE 3" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE &

SMOKE BARRIER". PROVIDE INSULATION WHERE COMPONENTS

MEET DECK ABOVE. PROVIDE SEALANT AT RUNNER AND HEAD PRIOR

TO INSTALLATION OF GWB

M3_2 50

3 5/8" METAL STUDS AT 16" O.C. MAX. 2 LAYERS 5/8" FIRE RATED

GWB BOTH SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF

DECK ABOVE.

2 HR SMOKE

BARRIER

U419

PROVIDE 3" STENCILED TEXT EVERY 8' O.C. READING "2 HR FIRE

BARRIER". PROVIDE INSULATION WHERE COMPONENTS MEET DECK

ABOVE. PROVIDE ACOUSTICAL SEALANT AT RUNNER AND HEAD

PRIOR TO INSTALLATION OF GWB. PROVIDE ACOUSTICAL SEALANT

AT ALL WALL PENETRATIONS.

M3_C N/A

3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" FIRE RATED GWB BOTH

SIDES. EXTEND WALL ASSEMBLY TO UNDERSIDE OF DECK

ABOVE.

SMOKE PARTITION N/A

PROVIDE 3" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE

PARTITION. PROVIDE INSULATION WHERE COMPONENTS MEET DECK

ABOVE. PROVIDE ACOUSTICAL SEALANT AT RUNNER AND HEAD

PRIOR TO INSTALLATION OF GWB.

M3B N/A

3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE.

EXTEND WALL ASSEMBLY TO 4" ABOVE FINISHED CEILING.

N/A N/A

M4B N/A 4" METAL STUDS AT 16" O.C. MAX. 3/4" PLYWOOD SHEATHING N/A N/A

M6 N/A

6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES.

EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS

TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48" O.C.

MAX

N/A N/A

M340B 40

3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" GWB ONE SIDE.

PROVIDE 3" MINERAL WOOL. EXTEND WALL ASSEMBLY TO

UNDERSIDE OF DECK ABOVE

N/A N/A

PROVIDE SOUND INSULATION WHERE COMPONENTS MEET DECK

ABOVE. PROVIDE ACOUSTICAL SEALANT AT RUNNER AND HEAD

PRIOR TO INSULATION OF GWB. PROVIDE ACOUSTICAL SEALANT AT

ALL WALL PENETRATIONS.

M349 49

3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" GWB BOTH SIDES.

PROVIDE 3" SAFB CREASED MINERAL WOOL. EXTEND WALL

ASSEMBLY TO UNDERSIDE OF DECK ABOVE

N/A N/A

PROVIDE SOUND INSULATION WHERE COMPONENTS MEET DECK

ABOVE. PROVIDE ACOUSTICAL SEALANT AT RUNNER AND HEAD

PRIOR TO INSULATION OF GWB. PROVIDE ACOUSTICAL SEALANT AT

ALL WALL PENETRATIONS.

M349_1 49

3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH

SIDES. PROVIDE 3" MINERAL WOOL. EXTEND WALL ASSEMBLY TO

UNDERSIDE OF DECK ABOVE ABOVE.

1 HR BARRIER U419

PROVIDE 3" STENCILED WITH 3/8" STROKE TEXT EVERY 8' O.C.

READING "1 HR FIRE BARRIER. PROVIDE INSULATION WHERE

COMPONENTS MEET DECK ABOVE. PROVIDE ACOUSTICAL SEALANT

AT RUNNER AND HEAD PRIOR TO INSTALLATION OF GWB. PROVIDE

ACOUSTICAL SEALANT AT ALL WALL PENETRATIONS.

M349_C 49

3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" GWB BOTH SIDES.

PROVIDE 3" MINERAL WOOL. EXTEND WALL ASSEMBLY TO

UNDERSIDE OF DECK ABOVE

SMOKE PARTITION N/A

PROVIDE 3" STENCILED WITH 3/8" STROKE TEXT EVERY 8' O.C.

READING "SMOKE PARTITION". PROVIDE INSULATION WHERE

COMPONENTS MEET DECK ABOVE. PROVIDE ACOUSTICAL SEALANT

AT RUNNER AND HEAD PRIOR TO INSTALLATION OF GWB. PROVIDE

ACOUSTICAL SEALANT AT ALL WALL PENETRATIONS.

M355_2S 55

3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 1/2" FIRE RATED

GWB BOTH SIDES. 3" CREASED SAFB MINERAL WOOL. EXTEND

WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.

2 HR SMOKE

BARRIER

U419

PROVIDE 3" STENCILED TEXT EVERY 8' O.C. READING "2 HR SMOKE

BARRIER. PROVIDE INSULATION WHERE COMPONENTS MEET DECK

ABOVE.

M640 40

6" METAL STUDS AT 16" O.C.MAX. 5/8" GWB BOTH SIDES.

PROVIDE 3" SAFB CREASED MINERAL WOOL. EXTEND WALL

ASSEMBLY TO UNDERSIDE OF DECK ABOVE

N/A N/A

PROVIDE SOUND INSULATION WHERE COMPONENTS MEET DECK

ABOVE. PROVIDE ACOUSTICAL SEALANT AT RUNNER AND HEAD

PRIOR TO INSULATION OF GWB. PROVIDE ACOUSTICAL SEALANT AT

ALL WALL PENETRATIONS.

M649_1 49

6" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH

SIDES. PROVIDE 3" MINERAL WOOL. EXTEND WALL ASSEMBLY TO

UNDERSIDE OF DECK ABOVE ABOVE.

1 HR BARRIER U419

PROVIDE 3" STENCILED WITH 3/8" STROKE TEXT EVERY 8' O.C.

READING "1 HR FIRE BARRIER. PROVIDE INSULATION WHERE

COMPONENTS MEET DECK ABOVE. PROVIDE ACOUSTICAL SEALANT

AT RUNNER AND HEAD PRIOR TO INSTALLATION OF GWB. PROVIDE

ACOUSTICAL SEALANT AT ALL WALL PENETRATIONS.

SW_1 N/A

2 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE

AND 5/8" GWB OTHER SIDE SIDE. EXTEND WALL ASSEMBLY TO

DECK ABOVE.

1 HR BARRIER

U 415

SYSTEM

A

NO.

A I

N I

G

RI

V

FOHTLA

E W

N O

M M

O

C JOSEPH H. TROST

ARCHITEC

T

EXISTING EMERGENCY

POWER GENERATOR

EXISTING BASKETBALL COURT

EXST MRI

EXST DIALYSIS

EXST BUILDING 500

EXST MULTIPURPOSE

EXISTING RADIATION ONCOLOGY

FUTURE LINEAR

ACCELERATOR

ADDITION

EXST SERVICE ROAD

NEW WALKWAY

SEE CIVIL DRAWINGS

MECHANICAL R.T.U.

S T

A N

D O

F F

D

IS

T A

N C

E

R

STAND OFF DISTANCE

R 50' - 0"

EXISTING SECURITY FENCE

EXISTING GATE

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

BID DOCUMENTS

FULLY SPRINKLERED

ACTUAL & PLAN

NORTH

NTS

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AS110

SITE PLAN

JCHDJP

11/08/18

1" = 20'-0"

ARCHITECTURAL SITE PLAN

NO.

A I

N I

G

RI

V

FOHTLA

E W

N O

M M

O

C JOSEPH H. TROST

U

1Z-127

1Z-128

1Z-126

M349_1

M3_1

M1B

E0948

M9025

M4100

A1132

M4200

A5106

F2010

F0205

F0230 M1801

A1011

A5075

A5080

A5145

F3200

M3070

NIC

MIN.

6' - 0"

/8

/4

U

T

1Z-128

1Z-127

1Z-126

NIC

DC1Z-2

D1Z-126

D1Z-127

D1Z-128

U

T

TYP.

MIN.

6' - 0"

NIC

5' - 7 1/2" 2' - 11"

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

BID DOCUMENTS

FULLY SPRINKLERED

ACTUAL & PLAN

NORTH

NTS

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AD100

DEMOLITION, NEW WORK, AND

REFLECTED CEILING PLAN - LEVEL 1 -

PHASE 1

JCHDJP

11/08/18

1/4" = 1'-0"

NEW WORK - LEVEL 1 - PHASE 1

GENERAL NEW WORK NOTES - PHASE 1

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND

LOCAL CODES AND ORDINANCES.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF

CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE ARCHITECT FOR A RESOLUTION.

EACH SUB CONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS AND EVALUATE

THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE TRADE AND ANY CONFLICTS WITH

OTHER TRADES. ANY CONFLICTS WILL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE

ARCHITECT FOR A RESOLUTION.

PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL

ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR ITS INTENDED USE.

WHERE WORK ABUTTS OR ADJOINS EXISTING SURFACES, WHICH WILL REMAIN EXPOSED,

ALIGN NEW WORK FLUSH WITH EXISTING ADJACENT SURFACES.

CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND CHASES FOR OWNER

FURNISHED OWNER INSTALLED EQUIPMENT WITH THE OWNER.

CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA.

BARRIERS SHALL NOT INTERFERE WITH THE OWNERS USE OF THE SITE OR SAFE MEANS OF

EGRESS.

THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO

PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF THE BUILDING.

ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY

UNLESS OTHERWISE NOTED.

• ALL DOORS TO BE MOUNTED 6" FROM FACE OF FINISH UON.

ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN ACCORDANCE WITH VAMC'S

EXISTING ROOF WARRANTY. COORDINATE ALL MODIFICATIONS TO THE ROOF WITH THE COR.

ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE REFERENCED FROM

SHEET AG001

• SEE SHEET AG001 FOR WALL TYPE SCHEDULE.

• SEE OVERALL NEW WORK PLANS FOR EXTERIOR AND OVERALL INTERIOR DIMENSIONS

• SEE ENLARGED PLANS FOR WALL TYPE LOCATIONS AND INTERIOR DIMENSIONING

• SEE EQUIPMENT PLANS FOR INTERIOR ELEVATION LOCATIONS

CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER SEPARATE

CONTRACT BY VA COR.

• SEE LIFE SAFETY PLAN FOR FIRE BARRIER AND SMOKE PARTITION LOCATIONS.

• SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LIGHTING AND DIFFUSER TYPES.

ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH ADJACENT

MATERIALS.

ROOM LEGEND - LEVEL 1 - PHASE 1

NUMBER NAME

1Z-126 HAC

1Z-127 SOILED LINEN

1Z-128 EXAM

1Z-100 CHIEF

1Z-101 SEC.

1Z-102 ADMIN. OFFICE

1Z-103 OFFICE

1Z-104 CONFERENCE ROOM

NEW WORK NOTES - LEVEL 1 - PHASE 1

1 ALIGN NEW WALL WITH ADJACENT EXISTING WALL

DENOTES TEMPORARY FIRE RATED DOOR AND ICRA HARDWALL BARRIER - 1 HR SMOKE

BARRIER. WALL TO BE: 5/8" TYPE X GWB BOTH SIDES OF 3 5/8" MTL STUDS AT 16" OC,

EXTEND TO DECK / SLAB ABOVE WITH FIRE RATED SEALANT AT TOP AND BOTTOM

CONNECTIONS ON BOTH SIDES. SEAL TIGHT AROUND ALL PENETRATIONS. REMOVE

TEMPORARY PARTIITION IN IT'S ENTIRETY AFTER THE COMLETION OF NEW WORK.

3 PROVIDE ACCENT PAINT THIS WALL, PNT #3, SEE AE603.

PROVIDE BUMPER GUARD [BG#1] TO 34" A.F.F. THIS ROOM WHERE APPLICABLE. SEE

FINISH SPECIFICATIONS FOR INFORMATION.

1/8" = 1'-0"

REFLECTED CEILNG PLAN - LEVEL 1 - PHASE 1

EQUIPMENT SCHEDULE - PHASE 1

MARK DESCRIPTION VACI VAVA CFCI COMMENTS

A1011 TELEPHONE, DESK *** PROVIDE POWER & DATA

A1132 ACCESSORY RAIL *** PROVIDE BLOCKING AS REQUIRED

A5075 SOAP DISPENSER ***

A5080 PAPER TOWEL DISPENSER ***

A5106 SHARPS DISPOSAL *** ---

A5145 ROBE HOOK ***

E0948 STORAGE CART *** ---

F0205 SIDE CHAIR WITH ARMS ***

F0230 ROTARY STOOL *** ---

F2010 BASKET, WASTEPAPER, STEP ON *** ---

F3200 CLOCK *** PROVIDE POWER

M1801 COMPUTER WITH FLAT PANEL MONITOR *** PROVIDE POWER & DATA

M3070 HAMPER, LINEN, MOBILE, W/ LID *** ---

M4100 SYPHYGMOMANOMETER *** ---

M4200 OTOSCOPE *** ---

M9025 EXAM TABLE *** PROVIDE POWER

1/4" = 1'-0"

DEMOLITION PLAN - LEVEL 1 - PHASE 1

DEMOLITION NOTES - LEVEL 1 - PHASE 1

1 REMOVE WALL AS INDICATED IN ITS ENTIRETY.

2 REMOVE WALL FINISHES, BASE, AND FLOOR FINISH THIS ROOM.

3 REMOVE DOOR, FRAME, AND HARDWARE IN ITS ENTIRETY

4 PLUMBING FIXTURE TO BE REMOVED ENTIRELY.

5 REMOVE CEILING IN ITS ENTIRETY.

6 EXISTING PLUMBING FIXTURE TO REMAIN.

7 REMOVE PORTION OF WALL FOR NEW DOOR.

DENOTES TEMPORARY FIRE RATED DOOR AND ICRA HARDWALL BARRIER - 1 HR SMOKE BARRIER. WALL TO BE:

5/8" TYPE X GWB BOTH SIDES OF 3 5/8" MTL STUDS AT 16" OC, EXTEND TO DECK / SLAB ABOVE WITH FIRE

RATED SEALANT AT TOP AND BOTTOM CONNECTIONS ON BOTH SIDES

GENERAL DEMOLITION NOTES - PHASE 1

DEMOLITION DRAWINGS INDICATE IN GENERAL, THE EXTENT OF DEMOLITION. REMOVE ALL ASSOCIATED APPURTENANCES NOT REQUIRED IN THE NEW WORK, ALL ABANDONED ITEMS, AND ALL ITEMS REQUIRED FOR THE INSTALLATION OF NEW WORK, TO PROVIDE FOR A COMPLETE PROJECT. ITEMS NOT SPECIFICALLY INDICATED THAT ARE QUESTIONABLE FOR REMOVAL SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR A DECISION.

THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO THE

START OF CONSTRUCTION.

THE CONTRACTOR SHALL PATCH ALL EXISTING SURFACES TO MATCH EXISTING WHERE AFFECTED BY CONSTRUCTION OPERATIONS, INCLUDING BUT NOT LIMITED TO PLUMBING, MECHANICAL AND ELECTRICAL WORK.

THE CONTRACTOR SHALL PATCH NAIL HOLES, ETC, AND REMOVE MISCELLANEOUS APPURTENANCES ON EXISTING

WALLS TO BE PAINTED OR COVERED WITH WALL COVERING.

ALL EXISTING FLOORING MATERIALS WHICH ARE TO REMAIN IN PLACE SHALL BE COMPLETELY CLEANED AND

STRIPPED OF WAX IN ORDER TO RECEIVE NEW FINISHES.

• ALL NEW WORK SHALL ALIGN WITH EXISTING WHERE THEY INTERSECT UNLESS OTHERWISE NOTED.

THE CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING SURFACES WHICH WERE PREVIOUSLY DAMAGED PRIOR TO CONSTRUCTION OPERATIONS IF VISIBLE AFTER NEW WORK IS COMPLETE, REGARDLESS IF THE ITEM WAS

SPECIFICALLY NOTED OR NOT.

THE CONTRACTOR SHALL REMOVE AND PATCH ANY AREAS UNCOVERED WHERE WOOD NAILERS OR GROUNDS ARE FOUND TO EXIST BEHIND ANY TRIM ITEMS OR EQUIPMENT REMOVED. WALLS SHALL BE MADE FLUSH WITH EXISTING

ADJACENT SURFACES AND READY TO RECEIVE NEW FINISHES.

IF ANY ASBESTOS CONTAINING MATERIAL IS ENCOUNTERED DURING THE COURSE OF CONSTRUCTION OPERATIONS WHICH IS NOT INDICATED ON THE CONTRACT DOCUMENTS THE CONTRACTOR SHALL NOTIFY THE ARCHITECT

IMMEDIATELY.

ALL SIGNAGE WHICH OCCURS ON WALL OR ON DOORS TO BE REMOVED SHALL BE REMOVED BY THE CONTRACTOR

AND TURNED OVER TO THE OWNER.

ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE

NOTED.

THESE DEMOLITION NOTES ARE FOR ARCHITECTURAL WORK ONLY. SEE ALL OTHER DRAWINGS FOR DEMOLITION

INFORMATION PERTAINING TO OTHER DISCIPLINES.

• FOR ICRA WALL INFORMATION SEE SHEET GI004.

DOORS, FRAMES, AND HARDWARE TO BE REMOVED SHALL BE SALVAGED FOR OWNER USE. UNLESS OTHERWISE

NOTED.

• LIGHT FIXTURES TO BE REMOVED SHALL BE SALVAGED FOR OWNER USE UNLESS OTHERWISE NOTED

NO.

A I

N I

G

RI

V

FOHTLA

E W

N O

M M

O

C JOSEPH H. TROST

S

R

Q

20 21 22 23 24 25 26 2725A

9 10

ABV.

ABV.

ABV.

MIN

6' - 0"

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

BID DOCUMENTS

FULLY SPRINKLERED

ACTUAL & PLAN

NORTH

NTS

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AD101

DEMOLITION PLAN - LEVEL 1 - PHASE

JCHDJP

11/08/18

1/8" = 1'-0"

DEMOLITION PLAN - LEVEL 1 - PHASE 2

DEMOLITION NOTES - LEVEL 1 - PHASE 2

1 REMOVE AND RELOCATE MECHANICAL EQUIPMENT. SEE MECHANICAL DRAWINGS.

2 REMOVE FIRE DEPARTMENT CONNECTION. SEE FIRE PROTECTION DRAWINGS TO PREPARE EXISTING FDC CONNECTION FOR NEW WORK.

3 REMOVE DOOR, FRAME, AND HARDWARE IN ITS ENTIRETY

4 REMOVE PORTION OF CONCRETE PAD.

5 REMOVE STOREFRONT SYSTEM IN ITS ENTIRETY.

6 REMOVE PAVEMENT. SEE CIVIL DRAWINGS FOR EXTENTS OF DEMOLITION.

7 REMOVE BRICK VENEER AND EXTERIOR SUBSTRATE TO FACE OF METAL STUD.

8 SEE CIVIL DRAWINGS FOR DEMOLITON AND RELOCATION OF EMERGENCY POWER DUCT BANK

9 REMOVE WALL MOUNTED EXTERIOR LIGHT FIXTURE

10 REMOVE AND DISCARD "LAMBS TOUNGE" FLANGE, SEE PLUMBING DRAWINGS TO PREPARE EXISTING OVERFLOW DRAIN FOR NEW WORK.

11 REMOVE LOUVER AND PATCH OPENING, SEE MECHANICAL DRAWINGS FOR EXTENTS OF INTERIOR DEMOLITION.

12 REMOVE EXTERIOR FACE BRICK AND METAL STUD BACKUP COMPLETE

13 REMOVE AREA / YARD DRAIN. SEE CIVIL DRAWINGS FOR DEMOLITION REQUIREMENTS.

GENERAL DEMOLITION NOTES - PHASE 2

• DEMOLITION DRAWINGS INDICATE IN GENERAL, THE EXTENT OF DEMOLITION. REMOVE ALL ASSOCIATED APPURTENANCES NOT REQUIRED IN THE NEW WORK, ALL ABANDONED ITEMS, AND ALL ITEMS REQUIRED FOR THE INSTALLATION OF NEW WORK, TO PROVIDE FOR A COMPLETE PROJECT.

ITEMS NOT SPECIFICALLY INDICATED THAT ARE QUESTIONABLE FOR REMOVAL SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR A

DECISION.

• THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION.

• THE CONTRACTOR SHALL PATCH ALL EXISTING SURFACES TO MATCH EXISTING WHERE AFFECTED BY CONSTRUCTION OPERATIONS, INCLUDING

BUT NOT LIMITED TO PLUMBING, MECHANICAL AND ELECTRICAL WORK.

• THE CONTRACTOR SHALL PATCH NAIL HOLES, ETC, AND REMOVE MISCELLANEOUS APPURTENANCES ON EXISTING WALLS TO BE PAINTED OR

COVERED WITH WALL COVERING.

• ALL EXISTING FLOORING MATERIALS WHICH ARE TO REMAIN IN PLACE SHALL BE COMPLETELY CLEANED AND STRIPPED OF WAX IN ORDER TO

RECEIVE NEW FINISHES.

• ALL NEW WORK SHALL ALIGN WITH EXISTING WHERE THEY INTERSECT UNLESS OTHERWISE NOTED.

• THE CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING SURFACES WHICH WERE PREVIOUSLY DAMAGED PRIOR TO CONSTRUCTION OPERATIONS IF VISIBLE AFTER NEW WORK IS COMPLETE, REGARDLESS IF THE ITEM WAS SPECIFICALLY NOTED OR NOT.

• THE CONTRACTOR SHALL REMOVE AND PATCH ANY AREAS UNCOVERED WHERE WOOD NAILERS OR GROUNDS ARE FOUND TO EXIST BEHIND ANY TRIM ITEMS OR EQUIPMENT REMOVED. WALLS SHALL BE MADE FLUSH WITH EXISTING ADJACENT SURFACES AND READY TO RECEIVE NEW

FINISHES.

• IF ANY ASBESTOS CONTAINING MATERIAL IS ENCOUNTERED DURING THE COURSE OF CONSTRUCTION OPERATIONS WHICH IS NOT INDICATED ON

THE CONTRACT DOCUMENTS THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY.

• ALL SIGNAGE WHICH OCCURS ON WALL OR ON DOORS TO BE REMOVED SHALL BE REMOVED BY THE CONTRACTOR AND TURNED OVER TO THE

OWNER.

• ALL FINISHES LISTED IN THE DEMOLITION SCHEDULE SHALL BE REMOVED COMPLETELY UNLESS INDICATED OTHERWISE. DEMOTION SHALL INCLUDE BACKINGS, MASTIC AND GLUES, SETTING BEDS, AND SUBSTRATE AS REQUIRED TO PREPARE THE MATERIAL FOR NEW WORK AND/OR

FINISHES.

• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.

• THESE DEMOLITION NOTES ARE FOR ARCHITECTURAL WORK ONLY. SEE ALL OTHER DRAWINGS FOR DEMOLITION INFORMATION PERTAINING TO

OTHER DISCIPLINES.

• FOR ICRA WALL INFORMATION SEE SHEETS GI004.

• DOORS, FRAMES, AND HARDWARE TO BE REMOVED SHALL BE SALVAGED FOR OWNER USE. UNLESS OTHERWISE NOTED.

• LIGHT FIXTURES TO BE REMOVED SHALL BE SALVAGED FOR OWNER USE UNLESS OTHERWISE NOTED

NO.

A I

N I

G

RI

V

FOHTLA

E W

N O

M M

O

C JOSEPH H. TROST

FC

W

V

T

R

Q

20 21 22 23 24 25

10' - 7"

12' - 5" 20' - 8"

1' - 0"

1' - 0"

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

BID DOCUMENTS

FULLY SPRINKLERED

ACTUAL & PLAN

NORTH

NTS

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AD102

DEMOLITION PLAN - ROOF - PHASE 2

JCHDJP

11/08/18

1/8" = 1'-0"

DEMOLITION PLAN - ROOF - PHASE 2

GENERAL DEMOLITION NOTES - PHASE 2

• DEMOLITION DRAWINGS INDICATE IN GENERAL, THE EXTENT OF DEMOLITION. REMOVE ALL ASSOCIATED APPURTENANCES NOT REQUIRED IN THE NEW WORK, ALL ABANDONED ITEMS, AND ALL ITEMS REQUIRED FOR THE INSTALLATION OF NEW WORK, TO PROVIDE FOR A COMPLETE PROJECT.

ITEMS NOT SPECIFICALLY INDICATED THAT ARE QUESTIONABLE FOR REMOVAL SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR A

DECISION.

• THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION.

• THE CONTRACTOR SHALL PATCH ALL EXISTING SURFACES TO MATCH EXISTING WHERE AFFECTED BY CONSTRUCTION OPERATIONS, INCLUDING

BUT NOT LIMITED TO PLUMBING, MECHANICAL AND ELECTRICAL WORK.

• THE CONTRACTOR SHALL PATCH NAIL HOLES, ETC, AND REMOVE MISCELLANEOUS APPURTENANCES ON EXISTING WALLS TO BE PAINTED OR

COVERED WITH WALL COVERING.

• ALL EXISTING FLOORING MATERIALS WHICH ARE TO REMAIN IN PLACE SHALL BE COMPLETELY CLEANED AND STRIPPED OF WAX IN ORDER TO

RECEIVE NEW FINISHES.

• ALL NEW WORK SHALL ALIGN WITH EXISTING WHERE THEY INTERSECT UNLESS OTHERWISE NOTED.

• THE CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING SURFACES WHICH WERE PREVIOUSLY DAMAGED PRIOR TO CONSTRUCTION OPERATIONS IF VISIBLE AFTER NEW WORK IS COMPLETE, REGARDLESS IF THE ITEM WAS SPECIFICALLY NOTED OR NOT.

• THE CONTRACTOR SHALL REMOVE AND PATCH ANY AREAS UNCOVERED WHERE WOOD NAILERS OR GROUNDS ARE FOUND TO EXIST BEHIND ANY TRIM ITEMS OR EQUIPMENT REMOVED. WALLS SHALL BE MADE FLUSH WITH EXISTING ADJACENT SURFACES AND READY TO RECEIVE NEW

FINISHES.

• IF ANY ASBESTOS CONTAINING MATERIAL IS ENCOUNTERED DURING THE COURSE OF CONSTRUCTION OPERATIONS WHICH IS NOT INDICATED ON

THE CONTRACT DOCUMENTS THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY.

• ALL SIGNAGE WHICH OCCURS ON WALL OR ON DOORS TO BE REMOVED SHALL BE REMOVED BY THE CONTRACTOR AND TURNED OVER TO THE

OWNER.

• ALL FINISHES LISTED IN THE DEMOLITION SCHEDULE SHALL BE REMOVED COMPLETELY UNLESS INDICATED OTHERWISE. DEMOTION SHALL INCLUDE BACKINGS, MASTIC AND GLUES, SETTING BEDS, AND SUBSTRATE AS REQUIRED TO PREPARE THE MATERIAL FOR NEW WORK AND/OR

FINISHES.

• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.

• THESE DEMOLITION NOTES ARE FOR ARCHITECTURAL WORK ONLY. SEE ALL OTHER DRAWINGS FOR DEMOLITION INFORMATION PERTAINING TO

OTHER DISCIPLINES.

• FOR ICRA WALL INFORMATION SEE SHEETS GI004.

• DOORS, FRAMES, AND HARDWARE TO BE REMOVED SHALL BE SALVAGED FOR OWNER USE. UNLESS OTHERWISE NOTED.

• LIGHT FIXTURES TO BE REMOVED SHALL BE SALVAGED FOR OWNER USE UNLESS OTHERWISE NOTED

DEMOLITION NOTES - ROOF - PHASE 2

1 REMOVE AND DISCARD GRAVEL STOP AND FASCIA. SEE SHEETS AE112 AND AE113 FOR EXTENTS, PROTECT EDGES OF ROOF AND PREPARE IT

FOR NEW CONSTRUCTION.

2 REMOVE AND DISCARD ROOF SYSTEM AND INSULATION TO ROOF DECK. PROTECT REMAINING ROOF AND DECK UNTIL NEW WORK IS COMPLETE.

3 REMOVE AND DISCARD LOUVER. COORDINATE PHASING AND TEMPORARY EXHAUST WITH MECHANICAL DRAWINGS.

4 REMOVE WALL TO ACCEPT NEW CORRIDOR. SEE AE112 FOR EXTENTS.

NO.

A I

N I

G

RI

V

FOHTLA

E W

N O

M M

O

C JOSEPH H. TROST

UP

AE402

AE402

AE402

T

R

Q

20 23

AE500

AE4001

AE500

AE500

R.1

21.1

21.1 22.1

22.1

Q.2 Q.2

20.1

20.1

R.2

S.2

23.1 24.1

24.1

25.1

25.1

27.1

27.1

P.1

QQ

RR

SS

25.3

25.4

25.4

21.2

S.1

26.1

26.1

AE400

Q.1 Q.1

25.2

5' - 0" 24' - 10 1/2" 27' - 0" 1' - 8" 20' - 10" 20' - 10" 21' - 8"

21' - 8"

21' - 4"

17' - 8"

1Z-232

1Z-229

1Z-228

1Z-227

1Z-225

1Z-230

1Z-237

1Z-2141Z-213

1Z-212

1Z-209

1Z-208

1Z-224

1Z-223

1Z-222

1Z-220

1Z-217

1Z-226

1Z-231

Z

-2

1Z-E1

1Z-206

1Z-207

1Z-S1

1Z-211

1Z-202

1Z-200

1Z-203

1Z-204

1Z-205

10' - 10 1/4"

1Z-C

1Z-C2 Z

-C

1Z-201

1Z-210

E100

AE510

1Z-216

17' - 10 1/2" 8' - 1 1/2" 9' - 3 1/2" 15' - 6" 36' - 0 9/16"

/1

6"

5'

3/

8"

/4

6' - 1 1/4"

33' - 8 3/4"

10' - 0 5/8"

M .O

.4'

0"

6'

8" M

.O .4'

0"

6'

8" M .O

.4'

0"

1' - 8" 5' - 4"

M .O

4' - 0"

6' - 8"

M .O

4' - 0"

6' - 8"

M .O

4' - 0"

6' - 8"

M .O

4' - 0"

6' - 8"

M .O

4' - 0"

/8

3' - 8"

M .O

4' - 0" 3' - 2 1/4"

3'

8" M .O

.3'

4"

± 30' - 8" 65' - 0"

F

/2

/8

/4

/2

AE402

AE502

CLEAR

6' - 0"

AE402

/2

/2

/2

D

D

A

E

A

A

A

A

A

A

A

A

A

A

/4

/1

/1

AE401 1

AE401

TEMPORARY CONSTRUCTION BARRIER,

SEE ICRA ASSESSMENT PLAN

TEMPORARY CONSTRUCTION

BARRIER, SEE ICRA

ASSESSMENT PLAN

.0

135.00°

M .O

/2

/2

.0

± 2' - 11"

135.00°

1Z-219

1Z-235

1Z-236

Z

-C

1Z-221

1Z -C

1'

8" M

.O .3'

4"

3'

8"

A

M .O

.4'

0"

9'

2"

1Z-234

1Z-218

NOTE: SEE AE121 FOR OPENING

DIMENSIONS AT COURTYARD

A E

A E

R.3

MATCHLINE

WORK

POINT

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

BID DOCUMENTS

FULLY SPRINKLERED

ACTUAL & PLAN

NORTH

NTS

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AE111

NEW WORK PLAN - LEVEL 1 - PHASE 2

JCHDJP

11/08/18

1/8" = 1'-0"

OVERALL NEW WORK PLAN - LEVEL 1 - PHASE 2

ROOM LEGEND - LEVEL 1 - PHASE 2

NUMBER NAME

1Z-200 WAITING

1Z-201 RECEPTION

1Z-202 BLOOD DRAW / VITALS

1Z-203 TOILET

1Z-204 TOILET

1Z-205 STORAGE

1Z-206 CLEAN LINEN

1Z-207 SOILED LINEN

1Z-208 CHEMOTHERAPY TREATMENT ROOM

1Z-209 NURSE STATION

1Z-210 PHARMACIST

1Z-211 ANTE

1Z-212 HD BUFFER

1Z-213 TOILET

1Z-214 TOILET

1Z-215 ELEV. EQUIP.

1Z-216 TELE. / DATA

1Z-217 ELEC.

1Z-218 MECH.

1Z-219 CONFERENCE / CONSULT

1Z-220 EXAM ROOM 8

1Z-221 TOILET

1Z-222 EXAM ROOM 7

1Z-223 EXAM ROOM 6

1Z-224 EXAM ROOM 5

1Z-225 EXAM / PROCEDURE

1Z-226 EXAM ROOM 9

1Z-227 EXAM ROOM 4

1Z-228 EXAM ROOM 3

1Z-229 EXAM ROOM 2

1Z-230 TEAM ROOM

1Z-231 TOILET

1Z-232 EXAM ROOM 1

1Z-234 STORAGE

1Z-235 MEDICINE

1Z-236 LOUNGE

1Z-237 KITCHEN

1Z-C1 CORRIDOR

1Z-C2 CORRIDOR

1Z-C3 CORRIDOR

1Z-C4 CORRIDOR

1Z-E1 ELEV.

1Z-S1 STAIR 1

GENERAL NEW WORK NOTES - PHASE 2

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE

FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO

THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT

TO THE IMMEDIATE ATTENTION OF THE ARCHITECT FOR A RESOLUTION.

EACH SUB CONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS

AND EVALUATE THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE

TRADE AND ANY CONFLICTS WITH OTHER TRADES. ANY CONFLICTS WILL BE

BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT FOR A

RESOLUTION.

PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE

WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR ITS

INTENDED USE.

WHERE WORK ABUTTS OR ADJOINS EXISTING SURFACES, WHICH WILL

REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH EXISTING ADJACENT

SURFACES.

CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND

CHASES FOR OWNER FURNISHED OWNER INSTALLED EQUIPMENT WITH THE

OWNER.

CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE

CONSTRUCTION AREA. BARRIERS SHALL NOT INTERFERE WITH THE OWNERS

USE OF THE SITE OR SAFE MEANS OF EGRESS.

THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF

RENOVATION TO PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF

THE BUILDING.

ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS

SHEET ONLY UNLESS OTHERWISE NOTED.

• ALL DOORS TO BE MOUNTED 6" FROM FACE OF FINISH UON.

ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN

ACCORDANCE WITH VAMC'S EXISTING ROOF WARRANTY. COORDINATE ALL

MODIFICATIONS TO THE ROOF WITH THE COR.

ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE

REFERENCED FROM SHEET AG001

• SEE SHEET AG001 FOR WALL TYPE SCHEDULE.

SEE OVERALL NEW WORK PLANS FOR EXTERIOR AND OVERALL INTERIOR

DIMENSIONS

SEE ENLARGED PLANS FOR WALL TYPE LOCATIONS AND INTERIOR

DIMENSIONING

• SEE EQUIPMENT PLANS FOR INTERIOR ELEVATION LOCATIONS

CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER

SEPARATE CONTRACT BY VA COR.

SEE LIFE SAFETY PLAN FOR FIRE BARRIER AND SMOKE PARTITION

LOCATIONS.

SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LIGHTING AND

DIFFUSER TYPES.

ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH

ADJACENT MATERIALS.

NO.

A I

N I

G

RI

V

FOHTLA

E W

N O

M M

O

C JOSEPH H. TROST

DN

RR

AE500

AE4001

AE500

AE500

2Z-248

2Z-250

2Z-247

2Z-241 2Z-240

2Z-258

2Z-2562Z-255

2Z-257

2Z-259

2Z-239

2Z-S1

2Z-261

R.1 R.1

22.1

22.1

Q.2Q.2

S.2

23.1

23.1

24.1

24.1

25.1

25.1

SS

25.3

2Z-242

2Z-243

2Z-249

2Z-251

2Z-C2

2Z-252

Z

-2

AE401 1

AE400

2Z-244

2Z-E1

Q.1

25.2

AE502

2Z-245

2Z-246

24' - 0" 56' - 7"

1' - 8"

20' - 10" 20' - 10" 21' - 8" 22' - 10 1/2"

9' - 4"

M.O.

4' - 0" 3' - 8"

M.O.

4' - 0" 3' - 8"

M.O.

4' - 0" 15' - 0" 15' - 0"

M.O.

4' - 0" 4' - 0"

1' - 8" 20' - 10" 20' - 10" 21' - 8"

1' - 8"

/8

/8

J

AE900

2Z-C3

2Z-C1

AE402

AE502

2Z-253

2Z-260 A

A

A

A

A

AAAA

A

A

A

A

A

B

A

A

AE40211

M .O

M .O

M .O

M .O

M .O

M .O

A

M .O

M .O

M .O

M .O

M .O

/8

M.O.

4' - 0" 3' - 8" 4' - 0" 5' - 7"

AE403

AE4029

AE123

TYP.

AE310

AE310

SIM

C2B

2Z-238 2Z-262

1' - 6"

66' - 8" 22' - 4"

R.3

AE401

J

A R

E A

B

A R

E A

A

W

25 2625A

SS25.3

S.1

25.2

8' - 5" 12' - 1"

Z

-C

AE502

AE502

22' - 4"

M .O

M .O

M .O

M .O

M .O

M .O

M .O

/4

C1A

M3_2

M349_2S

AE502

A

A

C

C

C

C

AE403

AE403

AE502

C

C

M.O.

4' - 0" 3' - 8" 4' - 0" 5' - 7"

12' - 1"

6' - 1"

A L

IG

N

CLEAR

5' - 10"

2Z-C2

C1C

M3_2

/1

R A

M P

0' - 0"

0' - 0"

-0' - 4"

-0' - 4"

-0' - 4"

C2B

C1B

2Z-238 2Z-262

R.3

A R

E A

B

A R

E A

A

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

BID DOCUMENTS

FULLY SPRINKLERED

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AE112

NEW WORK PLAN - LEVEL 2 - PHASE 2

JCHDJP

11/08/18

1/8" = 1'-0"

NEW WORK - LEVEL 2 - AREA A - PHASE 2

1/8" = 1'-0"

NEW WORK - LEVEL 2 - AREA B - PHASE 2

ROOM LEGEND - LEVEL 2 - PHASE 2

NUMBER NAME

ROOM LEGEND - LEVEL 2 - PHASE 2

NUMBER NAME

2Z-253 N.P. OFFICE

2Z-254 CORRIDOR

2Z-255 F.T. ATTEND

2Z-256 F.T. ATTEND

2Z-257 F.T. ATTEND

2Z-258 F.T. ATTEND

2Z-259 F.T. ATTEND

2Z-260 MICROSCOPE

2Z-261 RECEPTION / ADMIN.

2Z-262 STORAGE

2Z-C1 CORRIDOR

2Z-C2 CORRIDOR

2Z-C3 CORRIDOR

2Z-E1 ELEV.

2Z-S1 STAIR 1

ROOM LEGEND - LEVEL 2 - PHASE 2

NUMBER NAME

2Z-238 TOILET

2Z-239 TOILET

2Z-240 TELE. / DATA

2Z-241 ELEC.

2Z-242 TELE. MED / SMALL CONF.

2Z-243 FLEX CONF. SPACE

2Z-244 COPY ROOM

2Z-245 F.T. ATTEND.

2Z-246 F.T. ATTEND.

2Z-247 CHIEF RADIATION ONCOLOGY

2Z-248 F.T. ATTEND.

2Z-249 N.P. OFFICE

2Z-250 PHYSICS W.S.

2Z-251 CHIEF PHYSICS

2Z-252 CORRIDOR

GENERAL NEW WORK NOTES - PHASE 2

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE

FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO

THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT

TO THE IMMEDIATE ATTENTION OF THE ARCHITECT FOR A RESOLUTION.

EACH SUB CONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS

AND EVALUATE THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE

TRADE AND ANY CONFLICTS WITH OTHER TRADES. ANY CONFLICTS WILL BE

BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT FOR A

RESOLUTION.

PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE

WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR ITS

INTENDED USE.

WHERE WORK ABUTTS OR ADJOINS EXISTING SURFACES, WHICH WILL

REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH EXISTING ADJACENT

SURFACES.

CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND

CHASES FOR OWNER FURNISHED OWNER INSTALLED EQUIPMENT WITH THE

OWNER.

CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE

CONSTRUCTION AREA. BARRIERS SHALL NOT INTERFERE WITH THE OWNERS

USE OF THE SITE OR SAFE MEANS OF EGRESS.

THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF

RENOVATION TO PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF

THE BUILDING.

ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS

SHEET ONLY UNLESS OTHERWISE NOTED.

• ALL DOORS TO BE MOUNTED 6" FROM FACE OF FINISH UON.

ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN

ACCORDANCE WITH VAMC'S EXISTING ROOF WARRANTY. COORDINATE ALL

MODIFICATIONS TO THE ROOF WITH THE COR.

ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE

REFERENCED FROM SHEET AG001

• SEE SHEET AG001 FOR WALL TYPE SCHEDULE.

SEE OVERALL NEW WORK PLANS FOR EXTERIOR AND OVERALL INTERIOR

DIMENSIONS

SEE ENLARGED PLANS FOR WALL TYPE LOCATIONS AND INTERIOR

DIMENSIONING

• SEE EQUIPMENT PLANS FOR INTERIOR ELEVATION LOCATIONS

CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER

SEPARATE CONTRACT BY VA COR.

SEE LIFE SAFETY PLAN FOR FIRE BARRIER AND SMOKE PARTITION

LOCATIONS.

SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LIGHTING AND

DIFFUSER TYPES.

ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH

ADJACENT MATERIALS.

NEW WORK NOTES - LEVEL 2 - PHASE 2

1 ROOF AND OVERFLOW DRAIN, SEE PLUMBING DRAWINGS.

2 PREFINISHED METAL COPING. INSTALL PER MANUFACTURER SPECIFICATIONS.

3 ELECTRIC WATER COOLER TO MATCH BUILDING STANDARD. SEE PLUMBING DRAWINGS.

4 FIRE EXTINGUISHER CABINET. SEE SPECS.

DENOTES TEMPORARY FIRE RATED DOOR AND ICRA HARDWALL BARRIER - 1 HR FIRE RATED

CONSTRUCTION BARRIER. WALL TO BE: 5/8" TYPE X GWB BOTH SIDES OF 3 5/8" MTL STUDS AT 16" OC, EXTEND TO DECK / SLAB ABOVE WITH FIRE RATED SEALANT AT TOP AND BOTTOM CONNECTIONS ON BOTH

SIDES

NO.

A I

N I

G

RI

V

FOHTLA

E W

N O

M M

O

C JOSEPH H. TROST

DN

TT

S

R

Q

20 21

22 23

AE500

AE500

AE500

R.1

21.1

22.1

22.1

Q.2

20.1

R.2

S.2

23.1

23.1

24.1

24.1

25.1

25.1

27.1

27.1

P.1

QQ

RR

SS

25.3

25.4

21.2

26.1

26.1

26.2

Q.1

25.2

AE502

S1.1

AE900

AE502

OPEN TO

BELOW

9' - 9 1/4"

1Z-S1

C8_1

M649_1

M649_1

INTERSTITIAL

SPACE

SW_1

SW_1

AE310

SW_1

C L E

A R

/4

C L E

A R

C L E

A R

5' - 7"

CLEAR

3' - 6"

CLEAR

14' - 3 5/8"

/4

SW_1 SW_1

4' - 11 1/2"

CLEAR

10"

5' - 2 3/4"

CLEAR

10"

/4

C

L E

A R

/4

/4

C L E

A R

26' - 8 3/4"

R.3

7 7

AE602

R

AE500

AE500

R.1

22.1

22.1

Q.2

S.2

23.1

23.1

24.1

24.1

25.1

25.1

S.1

AE502

S1.4

AE900

C8_1C8_1

9' - 9 1/4"

2Z-S1

INTERSTITIAL

SPACE

AE511

SHAFT BELOW

4' - 11 1/2"

10"

5' - 2 3/4"

10"

R.3

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

BID DOCUMENTS

FULLY SPRINKLERED

ACTUAL & PLAN

NORTH

NTS

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AE113

NEW WORK PLAN - INTERSTITIALS -

PHASE 2

JCHDJP

11/08/18

1/8" = 1'-0"

NEW WORK PLAN - LEVEL 1 INTERSTITIAL - PHASE 2

NEW WORK NOTES - INTERSTITIALS - PHASE 2

1 EXISTING EXTERIOR FINISH TO REMAIN EXPOSED WHERE INTERSTITAL SPACE MEETS EXISTING BUILDING, TYPICAL.

2 FIRE EXTINGUISHER CABINET. SEE SPECS

3 NEW STEEL SHIP LADDER FOR ROOF ACCESS.

4 PROVIDE FIRE SAFING AND SEAL JOINTS TO MAINTAIN FIRE RATING.

5 PROVIDE SEALANT AND BACKER ROD CONTINUOUS AT ALL EXPANSION JOINTS, TYPICAL.

6 PROVIDE FLOOR TO WALL INTERIOR EXPANSION JOINT COVER.

7 PROVIDE WALL TO WALL INTERIOR EXPANSION JOINT COVER.

8 MECHANICAL PIPING, SEE MECHANICAL DRAWINGS.

1/8" = 1'-0"

NEW WORK - LEVEL 2 INTERSTITIAL - PHASE 2

GENERAL NEW WORK NOTES - PHASE 2.

• ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE

BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT FOR A RESOLUTION.

EACH SUB CONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS AND EVALUATE THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE TRADE AND ANY CONFLICTS WITH OTHER TRADES. ANY CONFLICTS WILL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE

ARCHITECT FOR A RESOLUTION.

PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE READY

FOR ITS INTENDED USE.

WHERE WORK ABUTTS OR ADJOINS EXISTING SURFACES, WHICH WILL REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH EXISTING ADJACENT

SURFACES.

CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND CHASES FOR OWNER FURNISHED OWNER INSTALLED EQUIPMENT WITH

THE OWNER.

CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA. BARRIERS SHALL NOT INTERFERE WITH THE

OWNERS USE OF THE SITE OR SAFE MEANS OF EGRESS.

THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO PREVENT THE SPREAD OF DUST TO OCCUPIED

AREAS OF THE BUILDING.

• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.

• ALL DOORS TO BE MOUNTED 6" FROM FACE OF FINISH UON.

ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN ACCORDANCE WITH VAMC'S EXISTING ROOF WARRANTY. COORDINATE ALL

MODIFICATIONS TO THE ROOF WITH THE COR.

• ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE REFERENCED FROM SHEET AG001

• SEE SHEET AG001 FOR WALL TYPE SCHEDULE.

• SEE OVERALL NEW WORK PLANS FOR EXTERIOR AND OVERALL INTERIOR DIMENSIONS

• SEE ENLARGED PLANS FOR WALL TYPE LOCATIONS AND INTERIOR DIMENSIONING

• SEE EQUIPMENT PLANS FOR INTERIOR ELEVATION LOCATIONS

• CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER SEPARATE CONTRACT BY VA COR.

• SEE LIFE SAFETY PLAN FOR FIRE BARRIER AND SMOKE PARTITION LOCATIONS.

• SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LIGHTING AND DIFFUSER TYPES.

• ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH ADJACENT MATERIALS.

NO.

A I

N I

G

RI

V

FOHTLA

E W

N O

M M

O

C JOSEPH H. TROST

R

Q

AE500

AE500

R.1

21.1 22.120.1

R.2

S.2

23.1 24.1 25.121.2

S.1

AE402 5

AE502

/2

1Z-214

1Z-213

1Z-209

1Z-208

1Z-217

1Z-215

1Z-E1

1Z-206

1Z-207

1Z-S1

1Z-211

1Z-202

1Z-200

1Z-203

1Z-204

1Z-205

1Z-C2

1Z-C1

1Z-201

1Z-210

C1

1Z-216

/8

/4

/2

/2

/2 "13

/8

/8

22' - 10 1/2" 11' - 6"

/8

/8

/8

± 8' - 0 9/16"

/4

/4

/8

AE122

AE900

AE900

208B

202 203

208A

213 214

S1B

M3

M3

M3

M3

M3

M3

M3

M349

M349

M3

M349

M349

M349M349

M349

M349

M3

M3_1

SW_1

M1B

M3_1

M3_1

M3_1

M3_1

M3_1

M3_1

M3

M3_1

M3_1

M349

M3

M3

M3

M640 M3

M349

M640

M6

M340B

M349

M349

M349

M349

M349

M3

M349

M3

M3

200A

208C

M349

M6

2' - 8" 8' - 6 1/8" 3' - 3 1/2"

/8

/8

/8

3' - 10 1/4" 17' - 6 7/8"

8' - 0" MIN. CLEAR

8' - 1 1/2" 9' - 3 1/2" 15' - 6" 25' - 10"

/8

M1B

A L

IG

N

/2

/8

3' - 8 5/8"

2' - 0 7/8"

3' - 3 1/2"

/8

5' - 5 1/4"5' - 5 1/4"

EQ EQ

11' - 2 7/8"

9' - 0" TYP

E Q

E Q

6 1/8"

10' - 2 3/4"

S

IN

K

M3

M349

M349

1'

3/

4" M

.O .4'

0"

2'

8"

M .O

.10

4'

0"

M .O

.10

2'

8" M

.O .3'

4"

/4

COURTYARD

SEE CIVIL DRAWINGS

13' - 9 1/8" 8' - 1" 13' - 2 1/2"

/2

/8

11' - 5 5/8" 11' - 1"

1Z-237

1Z-212

1Z-C4

/8

1Z-211A

3' - 6 3/8"

211A

/4

M3

S1A

AE122

AE602

/8

7' - 9 3/8" 7' - 9 7/8" 9' - 6 1/16" 11' - 4 5/8" 11' - 0 1/2"

/8

3' - 6"

6"

4" 4"

M1B

M1B

M1B

M349 M349

3' - 0"

/4

/4

/8

9' - 1 5/8" 6' - 2 5/16" 3' - 10 3/8" 3' - 9 5/8" 13' - 10 1/4"

1' - 7 3/4"

3' - 10"

4' - 0 1/8"

R.3

SW_1

M3_1C

M1BM1B

M340B

M3B

TYP ENTIRE LEGNTH

OF EXISTING WALL

2 1

9 9

M3

M640

/2

M340B

M340B

M340B

O F

D O

O R

CONTRACTOR'S NOTE

FOR INTERIOR ELEVATIONS AND EQUIPMENT

PLANS SEE AE700, AE701, AE702, AE703.

A Se rv ic e D i s a b le d Ve t e r an Owned

S m a l l B u s iness

SDVOSB

CVE

www.pfa-architect.com - Project No: ####

ARCHITECTURE, PLANNING,

INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0500-0004

B

A

C

D

E

F

NO. DESCRIPTION DATE

KEYPLAN

BID DOCUMENTS

FULLY SPRINKLERED

ACTUAL & PLAN

NORTH

NTS

CONSTRUCT CANCER

CENTER

VAMC RICHMOND, VA

652-318

11-08-2018

BLDG. 500

Department of

Veterans Affairs

MILLER-REMICK LLC

PROFESSIONAL

ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

AE121

ENLARGED PLAN - LEVEL 1A - PHASE 2

JCHDJP

11/08/18

1/4" = 1'-0"

ENLARGED PLAN - LEVEL 1 - AREA A - PHASE 2

GENERAL NEW WORK NOTES - PHASE 2

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE

FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO

THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT

TO THE IMMEDIATE ATTENTION OF THE ARCHITECT FOR A RESOLUTION.

EACH SUB CONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS

AND EVALUATE THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE

TRADE AND ANY CONFLICTS WITH OTHER TRADES. ANY CONFLICTS WILL BE

BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT FOR A

RESOLUTION.

PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE

WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR ITS

INTENDED USE.

WHERE WORK ABUTTS OR ADJOINS EXISTING SURFACES, WHICH WILL

REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH EXISTING ADJACENT

SURFACES.

CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND

CHASES FOR OWNER FURNISHED OWNER INSTALLED EQUIPMENT WITH THE

OWNER.

CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE

CONSTRUCTION AREA. BARRIERS SHALL NOT INTERFERE WITH THE OWNERS

USE OF THE SITE OR SAFE MEANS OF EGRESS.

THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF

RENOVATION TO PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF

THE BUILDING.

ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS

SHEET ONLY UNLESS OTHERWISE NOTED.

• ALL DOORS TO BE MOUNTED 6" FROM FACE OF FINISH UON.

ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN

ACCORDANCE WITH VAMC'S EXISTING ROOF WARRANTY. COORDINATE ALL

MODIFICATIONS TO THE ROOF WITH THE COR.

ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE

REFERENCED FROM SHEET AG001

• SEE SHEET AG001 FOR WALL TYPE SCHEDULE.

SEE OVERALL NEW WORK PLANS FOR EXTERIOR AND OVERALL INTERIOR

DIMENSIONS

SEE ENLARGED PLANS FOR WALL TYPE LOCATIONS AND INTERIOR

DIMENSIONING

• SEE EQUIPMENT PLANS FOR INTERIOR ELEVATION LOCATIONS

CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER

SEPARATE CONTRACT BY VA COR.

SEE LIFE SAFETY PLAN FOR FIRE BARRIER AND SMOKE PARTITION

LOCATIONS.

SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LIGHTING AND

DIFFUSER TYPES.

ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH

ADJACENT MATERIALS.

NEW WORK NOTES - LEVEL 1A - PHASE 2

PROVIDE WALL TO WALL INTERIOR EXPANSION JOINT COVER TYPICAL. SEE

1/AE602

PROVIDE FLOOR…