This solicitation is seeking a qualified Service Disabled Veteran Owned Small Business construction company to provide all labor, material, transportation, equipment and supervision required for the Construct Cancer Center project located at the H.H. McGuire VA Medical Center in Richmond, Virginia. The two story addition of approximately 15,000 square feet shall be constructed in accordance with provided drawings and specifications within 630 calendar days from receipt of the Notice to Proceed, including final inspection and cleanup. The estimated construction cost is between $5,000,000 and $10,000,000. Questions must be submitted by email to the Contracting Officer by the stated date. This is a 100% set-aside for Service-Disabled, Veteran-Owned Small Businesses, and non-SDVOSB offers will not be considered.
36C24619B0040 S02 General.pdf
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONSTRUCT CANCER
CENTER
652-318
NO. DESCRIPTION DATE
BLDG. 500
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
COVER SHEET
& DRAWING INDEX
GI001
DRTH
UP
WALL LEGEND
1 HR. FIRE BARRIER
1 HR. SMOKE BARRIER
2 HR. FIRE BARRIER (PER EXISTING FIRE PLAN)
CORRIDOR SMOKE PARTITION
CORRIDOR SMOKE PARTITION (EXISTING)
XXX SF
X
XXX XXX
OCCUPANT LOAD TAG
ROOM AREA
LOAD FACTOR/
OCCUPANT LOAD
USE GROUP
FIRE EXTINGUISHER CABINET
FEC
X'-XX"
MAX TRAVEL DISTANCE
REQUIRED EXIT E
LIFE SAFETY LEGEND
HORIZONTAL EXIT HE
BUILDING REGULATION DATA
IBC 2015
USE GROUP
I2: INSTITUTIONAL
CONSTRUCTION TYPE TABLE 601
TYPE 1B FULLY SPRINKLERED
STRUCTURAL FRAME: 2 HOURS
BEARING WALLS: 2 HOURS
FLOOR CONSTRUCTION: 2 HOURS
ROOF CONSTRUCTION: 1 HOURS
BUILDING AREA AND HEIGHTS
TABLE 504.3, .4, 506.2
STORIES: 5
HEIGHT: 180'
AREA: UNLIMITED
HAZARDOUS AREAS TABLE 509
WASTE AND LINEN COLLECTION ROOMS IN USE
GROUP I-2 : 1 HOUR
SECTION 407 GROUP I-2
TRAVEL DISTANCE MAX 200'x0" TO BARRIER DOOR.
407.3 CORRIDOR WALL CONSTRUCTION
CORRIDOR WALLS SHALL BE CONSTRUCTED AS
SMOKE PARTITIONS
407.5 SMOKE BARRIERS
SMOKE BARRIERS SHALL BE PROVIDED TO
SUBDIVIDE EVERY STORY INTO NO FEWER THAN 2
AN AREA OF NO MORE THAN 22,500 SF.
SMOKE BARRIER DOOR TABLE 716.5
1/3 HOUR
MEANS OF EGRESS
EXIT ACCESS TRAVEL DISTANCE TABLE 1017.2
B: 200 FEET WITH SPRINKLER SYSTEM
SECTION 1007.1.1 : EXIT AND EXIT ACCESS
DOORWAYS
TWO EXITS ARE REQUIRED SEPARATION
DISTANCE 1/3 THE DIAGONAL WITH SPRINKLER
SYSTEM
EGRESS WIDTH
1005.3.1 STAIRWAYS CAPACITY IS OCCUPANT
LOAD x .2 INCHES
1005.3.2 CORRIDORS CAPACITY IS OCCUPANT
LOAD x .15 INCHES
MINIMUM CORRIDOR WIDTH TABLE 1018.2
44 INCHES
96 INCHES GROUP I-2 WHERE REQUIRED FOR
BED MOVEMENT
SHAFT ENCLOSURE 713.4
SHAFT SHALL HAVE FIRE-RESISTANT ROOFING
OF NOT LESS THAN 1 HOUR WHEN
CONNECTING LESS THAN 4 STORIES.
USE GROUP
CHAPTER 18/19 NEW AND EXISTING
HEALTHCARE OCCUPANCIES
FIRE RESISTANCE RATINGS
NFPA 220 2015 ED TABLE 4.1.1
TYPE 2 (222)
BEARING WALLS 2 HOURS
COLUMNS SUPPORTING MORE THAN ONE
FLOOR: 2 HOURS
(SUPPORTING ROOF ONLY 1 HOUR)
BEAMS SUPPORTING MORE THAN ONE
FLOOR: 2 HOURS
(SUPPORTING ROOF ONLY 1 HOUR)
FLOOR - CEILING ASSEMBLIES: 2 HOURS
ROOF CEILING ASSEMBLIES: 1 HOURS
NUMBER OF STORIES TABLE 18.1.6.1
UNLIMITED
NOTE (3) - INTERSTITIAL SPACES USED
SOLELY FOR BUILDING OR PROCESS
SYSTEMS DIRECTLY RELATED TO THE
LEVEL ABOVE OR BELOW ARE NOT
CONSIDERED A SEPARATE STORY.
HAZARDOUS AREA PROTECTION TABLE
18.3.2.1
ROOMS WITH SOILED LINEN IN VOLUME
GREATER THAN 64 GAL: 1 HOUR
STORAGE ROOMS GREATER THAN 50 SF
AND LESS THAN 100 SF STORING
COMBUSTIBLE MATERIAL PROVIDE SMOKE
PARTITION
STORAGE ROOMS GREATER THAN 100 SF W/
COMBUSTIBLE MATERIAL: 1 HOUR
ROOMS WITH COLLECTING TRASH IN
VOLUME EXCEEDING 64 GAL: 1 HOUR
CONSTRUCTION OF CORRIDOR HALLS
18.3.6.2.3
CORRIDOR WALLS SHALL FORM A BARRIER
TO BLOCK THE TRANSFER OF SMOKE.
CORRIDOR WALLS PERMITTED TO
TERMINATE AT INTERSTITIAL LEVEL.
19.3.6.2.4 & 19.3.6.2.6
SUB DIVISION OF BUILDING SPACE 18.3.7
EVERY STORY OF AMBULATORY
HEALTHCARE FACILITY SHALL DIVIDE INTO
NOT LESS THAN 2 SMOKE COMPARTMENTS
NOT EXCEEDING 22,500SF
TRAVEL DISTANCE FROM ANY POINT TO
REACH SMOKE BARRIER DOOR : 200'-0"
SMOKE BARRIER DOOR EXHIBIT 18.3.7.6
DOORS IN SMOKE BARRIERS SHALL BE 1
3/4"SOLID BONDED WOOD DOOR OR 20
MINUTE FIRE RATED DOORS.
LATCHING HARDWARE NOT REQUIRED
18.3.7.8
NFPA 101 2015
INTERNATIONAL BUILDING CODE (IBC 2015)
NFPA-101 LIFE SAFETY CODE (2015)
NFPA-220 STANDARD TYPE OF BUILDING CONSTRUCTION (2015)
NFPA-10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS (2013)
NFPA-70 NATIONAL ELECTRIC CODE (2014)
NFPA-101 LIFE SAFETY CODE (2015) CHAPTER 43.6 RECONSTRUCTION
APPLICABLE CODES AND STANDARDS:
MEANS OF EGRESS
TRAVEL DISTANCE TO EXIT 18.2.6.2.1
TRAVEL DISTANCE SHALL NOT EXCEED 200
FEET WITH SPRINKLER SYSTEM
NUMBER OF MEANS OF EGRESS 18.2.4.2
NOT LESS THAN 2
SEPARATION DISTANCE NOT LESS THAN 1/3 THE
DIAGONAL 7.5.1.3.3
EGRESS WIDTH TABLE 7.3.3.1
STAIRWAYS : OCCUPANCY LOAD x .3 INCHES CORRIDORS : OCCUPANCY LOAD x .2 INCHES
CAPACITY OF MEANS OF EGRESS 18.2.3.4
SHALL NOT BE LESS THAN 8' CLEAR
18.2.3.4 (1) MINIMUM WIDTH OF 44 INCHES IN
NON PATIENT AREAS
SHAFT 8.6.5 ITEM 2
SHAFTS LESS THAN 4 STORIES SHALL HAVE 1-
HOUR FIRE BARRIER.
FINISH REQUIREMENTS (NFPA 101 10.2.2):
EXIT ENCLOSURES/EXIT PASSAGEWAYS:
CLASS A OR B
EXIT ACCESS CORRIDORS & OTHER EXIT WAYS:
CLASS A OR B
ROOMS & ENCLOSED SPACES:
CLASS A, B, OR C
FLOORS IN EXIT ENCLOSURES, EXIT
PASSAGEWAYS AND CORRIDORS (OTHER THAN
WOOD, VINYL, LINOLEUM, AND RESILIENT
FLOORS W/O FIBER MATERIALS):
CLASS I OR II
FIRE PROTECTION:
AUTOMATIC SPRINKLER SYSTEMS: FULLY
SPRINKLERED
PORTABLE FIRE EXTINGUISHERS (NFPA 10):
CLASS ABC TYPE, MIN RATING 2-A
WHERE INDICATED ON LIFE SAFETY PLAN
MAXIMUM TRAVEL DISTANCE TO FEC: 75'
STRUCTURAL STEEL FIRE PROOFING: UL N706
IBC 2015
USE GROUP
I2: INSTITUTIONAL
CONSTRUCTION TYPE TABLE 601
TYPE 1B FULLY SPRINKLERED
STRUCTURAL FRAME: 2 HOURS
BEARING WALLS: 2 HOURS
FLOOR CONSTRUCTION: 2 HOURS
ROOF CONSTRUCTION: 1 HOURS
BUILDING AREA AND HEIGHTS
TABLE 504.3, .4, 506.2
STORIES: 5
HEIGHT: 180'
AREA: UNLIMITED
USE GROUP
CHAPTER 18/19 NEW AND EXISTING
HEALTHCARE OCCUPANCIES
FIRE RESISTANCE RATINGS
NFPA 220 2015 ED TABLE 4.1.1
TYPE 2 (222)
BEARING WALLS 2 HOURS
COLUMNS SUPPORTING MORE THAN ONE
FLOOR: 2 HOURS
(SUPPORTING ROOF ONLY 1 HOUR)
BEAMS SUPPORTING MORE THAN ONE
FLOOR: 2 HOURS
(SUPPORTING ROOF ONLY 1 HOUR)
FLOOR - CEILING ASSEMBLIES: 2 HOURS
ROOF CEILING ASSEMBLIES: 1 HOURS
NUMBER OF STORIES TABLE 18.1.6.1
UNLIMITED
NFPA 101 2015
EXISTING BUILDING DATA:
878 SF
A
1Z-200
203 SF
I
1Z-202
303 SF
B
1Z-209
155 SF
B
1Z-212
100 SF
B
1Z-237
252 SF
M
1Z-217
S F
2I
1Z -2
S F
2I
1Z -2
S F
2I
1Z -2
S F
2I
1Z -2
S F
2I
1Z -2
S F
2I
1Z -2
S F
2I
1Z -2
S F
2I
1Z -2
S F
3B
1Z -2
S F
2I
1Z -2
S F
2I
1Z -2
102 SF
B
1Z-206
68 SF
B
1Z-207
1620 SF
I
1Z-208
TRAVEL DISTANCE = 76' - 0"
E
DIAGONAL DISTANCE = 190' -
0"
T R A V E L D
IS
T A N C E
E
328 SF
B
1Z-201
180 SF
B
1Z-211
440 SF
M
1Z-218136 SF
M
1Z-216
S F
2B
1Z -2
S
F
1B
1Z -2
S F
2B
1Z -2
HE
48 SF
M
1Z-215
71 SF
B
1Z-210
56 SF
I
1Z-221
NOTE:
ALL CORRIDOR WALLS TO BE
CONSTRUCTED PER NFPA 101, 2015
SECTION 18.3.6.2.3
A Se rv ic e D i s a b l e d Vet e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: ####
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
BID DOCUMENTS
FULLY SPRINKLERED
ACTUAL & PLAN
NORTH
NTS
CONSTRUCT CANCER
CENTER
VAMC RICHMOND, VA
652-318
11-08-2018
BLDG. 500
Department of
Veterans Affairs
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
GI002
LIFE SAFETY PLAN - LEVEL 1
JCHDJP
11/08/18
OCCUPANT LOAD - LEVEL 1 - PER TYPE
USE
GROUP
OCCUPANCY
FACTOR AREA
OCCUPANCY
LOAD
A 15 878 SF 59
B 100 1915 SF 26
I 100 3061 SF 41
M 300 876 SF 5
6730 SF 131
NOTE - ROOMS OF SIMILAR OCCUPANCY HAVE BEEN COMBINED
• SEE SHEET GI003 FOR SMOKE ZONE AREAS
3/32" = 1'-0"
LIFE SAFETY PLAN - LEVEL 1 - PHASE 2
ROOM LEGEND - LEVEL 1 - PHASE 2
NUMBER NAME
1Z-200 WAITING
1Z-201 RECEPTION
1Z-202 BLOOD DRAW / VITALS
1Z-203 TOILET
1Z-204 TOILET
1Z-205 STORAGE
1Z-206 CLEAN LINEN
1Z-207 SOILED LINEN
1Z-208 CHEMOTHERAPY TREATMENT ROOM
1Z-209 NURSE STATION
1Z-210 PHARMACIST
1Z-211 ANTE
1Z-212 HD BUFFER
1Z-213 TOILET
1Z-214 TOILET
1Z-215 ELEV. EQUIP.
1Z-216 TELE. / DATA
1Z-217 ELEC.
1Z-218 MECH.
1Z-219 CONFERENCE / CONSULT
1Z-220 EXAM ROOM 8
1Z-221 TOILET
1Z-222 EXAM ROOM 7
1Z-223 EXAM ROOM 6
1Z-224 EXAM ROOM 5
1Z-225 EXAM / PROCEDURE
1Z-226 EXAM ROOM 9
1Z-227 EXAM ROOM 4
1Z-228 EXAM ROOM 3
1Z-229 EXAM ROOM 2
1Z-230 TEAM ROOM
1Z-231 TOILET
1Z-232 EXAM ROOM 1
1Z-234 STORAGE
1Z-235 MEDICINE
1Z-236 LOUNGE
1Z-237 KITCHEN
1Z-C1 CORRIDOR
1Z-C2 CORRIDOR
1Z-C3 CORRIDOR
1Z-C4 CORRIDOR
1Z-E1 ELEV.
1Z-S1 STAIR 1
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
ARCHITEC
T
E.J.
COVER
PLATE
PLATE
E.J. COVER
E.J.
COVER
PLATE
STATION
TUG DOCK
BLK
FC
FC
UP
UP
DN
9518 SF
CARE SUITE & SMOKE
ZONE 1
10500 SF
CARE SUITE & SMOKE
ZONE 2
S M
O K
E Z
O N
E S
P E
R E
X
IS
T
IN
G C
O N
D
IT
IO
N
S
SMOKE ZONES PER EXISTING CONDITIONS
S M
O K
E Z
O N
E S
P E
R E
X
IS
T
IN
G C
O N
D
IT
IO
N
S
HE
TRAVEL DISTANCE =
163'
TRAVEL DISTANCE =
189'
HE
XXX SF
X
XXX XXX
OCCUPANT LOAD TAG
ROOM AREA
LOAD FACTOR/
OCCUPANT LOAD
USE GROUP
FIRE EXTINGUISHER CABINET
FEC
X'-XX"
MAX TRAVEL DISTANCE
REQUIRED EXIT E
LIFE SAFETY LEGEND
HORIZONTAL EXIT HE
WALL LEGEND
1 HR. FIRE BARRIER
1 HR. SMOKE BARRIER
2 HR. FIRE BARRIER (PER EXISTING FIRE PLAN)
CORRIDOR SMOKE PARTITION
CORRIDOR SMOKE PARTITION (EXISTING)
400 SF
A
2Z-243
289 SF
A
2Z-242
79 SF
B
2Z-255
82 SF
B
2Z-257
82 SF
B
2Z-259
170 SF
B
2Z-261
84 SF
B
2Z-258
82 SF
B
2Z-256
97 SF
M
2Z-240
83 SF
M
2Z-241
88 SF
B
2Z-251
203 SF
B
2Z-250
110 SF
B
2Z-247
172 SF
B
2Z-249
82 SF
B
2Z-248
D
IA
G O N A L D
IS
T A N C E
E
81 SF
B
2Z-246
81 SF
B
2Z-245
HE
104 SF
B
2Z-253
199 SF
B
2Z-260
TRAVEL DISTANCE = 112' - 0"
NOTE:
ALL CORRIDOR WALLS TO BE
CONSTRUCTED PER NFPA 101, 2015
SECTION 18.3.6.2.3
A Se rv ic e D i s a b l e d Vet e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: ####
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
BID DOCUMENTS
FULLY SPRINKLERED
ACTUAL & PLAN
NORTH
NTS
CONSTRUCT CANCER
CENTER
VAMC RICHMOND, VA
652-318
11-08-2018
BLDG. 500
Department of
Veterans Affairs
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
GI003
LIFE SAFETY PLAN - LEVEL 2, SUITE
PLANS AND EXISTING TRAVEL
DISTANCE
JCHDJP
11/08/18
1/16" = 1'-0"
SMOKE ZONE PLAN - LEVEL 1
1" = 30'-0"
TRAVEL DISTANCE - EXISTING BUILDING
3/32" = 1'-0"
LIFE SAFETY PLAN - LEVEL 2
NOTE - ROOMS OF SIMILAR OCCUPANCY HAVE BEEN COMBINED
OCCUPANT LOAD - LEVEL 2 - PER TYPE
USE
GROUP
OCCUPANCY
FACTOR AREA
OCCUPANCY
LOAD
M 300 180 SF 2
B 100 1700 SF 22
A 15 690 SF 47
2569 SF 71
ROOM LEGEND - LEVEL 2 - PHASE 2
NUMBER NAME
ROOM LEGEND - LEVEL 2 - PHASE 2
NUMBER NAME
2Z-253 N.P. OFFICE
2Z-254 CORRIDOR
2Z-255 F.T. ATTEND
2Z-256 F.T. ATTEND
2Z-257 F.T. ATTEND
2Z-258 F.T. ATTEND
2Z-259 F.T. ATTEND
2Z-260 MICROSCOPE
2Z-261 RECEPTION / ADMIN.
2Z-262 STORAGE
2Z-C1 CORRIDOR
2Z-C2 CORRIDOR
2Z-C3 CORRIDOR
2Z-E1 ELEV.
2Z-S1 STAIR 1
ROOM LEGEND - LEVEL 2 - PHASE 2
NUMBER NAME
2Z-238 TOILET
2Z-239 TOILET
2Z-240 TELE. / DATA
2Z-241 ELEC.
2Z-242 TELE. MED / SMALL CONF.
2Z-243 FLEX CONF. SPACE
2Z-244 COPY ROOM
2Z-245 F.T. ATTEND.
2Z-246 F.T. ATTEND.
2Z-247 CHIEF RADIATION ONCOLOGY
2Z-248 F.T. ATTEND.
2Z-249 N.P. OFFICE
2Z-250 PHYSICS W.S.
2Z-251 CHIEF PHYSICS
2Z-252 CORRIDOR
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST
FC
T
Q
P
20 23 25 28
MIN.
6' - 0"
R.3 R.3
W
25 28
M
IN
GENERAL PHASING NOTES
-SEE SHEET GI004 FOR ICRA MATRIX AND REQUIREMENTS.
-THE CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND COMMUNICATIONS AS
REQUIRED TO SUPPORT TEMPORARY RELOCATED EQUIPMENT AND MAINTAIN OPERATIONS
IN AREAS NOT UNDER CONSTRUCTION.
-THE CONTRACTOR SHALL COORDINATE WORK OUTSIDE THE AREA UNDER CONSTRUCTION
WITH THE COR. NOTE THAT WORK MAY NEED TO BE PERFORMED AT NIGHT.
-THE CONTRACTOR SHALL COORDINATE WITH THE COR THE SCHEDULING OF ALL
INTERRUPTIONS IN SERVICES REQUIRED BY THIS PROJECT.
-THE CONTRACTOR SHALL MAINTAIN THE EXISTING WEATHERTIGHT CONDITION
THROUGHOUT THE CONSTRUCTION PERIOD AND REPAIR ALL DAMAGE CAUSED BY
CONSTRUCTION OPERATIONS.
-THE CONTRACTOR SHALL PROVIDE TEMPORARY DIRECTIONAL SIGNS FOR EACH PHASE OF
THE CONSTRUCTION PROJECT TO BE LOCATED AS DIRECTED BY THE COR.
-TEMPORARY PARTITIONS INDICATED ARE THE MINIMUM REQUIREMENTS AND ARE FOR
DESIGN INTENT ONLY. IF ADDITIONAL PARTITIONS ARE REQUIRED TO ENSURE SAFETY AND
TO FACILITATE THE HOSPITAL’S OPERATIONS IT IS THE CONTRACTOR’S RESPONSIBILITY TO
PROVIDE. DOORS SHALL BE PROVIDED IN PARTITIONS AS REQUIRED BY THE COR.
-ALL WORK INDICATED OR NOT INDICATED WITHIN A SPECIFIED PHASING PLAN SHALL BE
COORDINATED WITH THE COR PRIOR TO COMMENCEMENT OF THE WORK.
-THE CONTRACTOR SHALL MAINTAIN INTERIM LIFE SAFETY STANDARDS AT ALL TIMES
DURING CONSTRUCTION.
-THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO
PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF THE BUILDING.
-ALL DEBRIS CARTS UTILIZED SHALL HAVE TIGHT FITTING COVERS TO MINIMIZE THE SPREAD
OF DUST.
-EACH PHASE MUST BE COMPLETE AND OCCUPIED BY THE COR PRIOR TO BEGINNING THE
NEXT PHASE. CONTRACTOR SHALL ALLOW SEVEN (7) DAYS BETWEEN PHASES TO ALLOW
THE COR TO MOVE.
-ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY
UNLESS OTHERWISE NOTED.
-ARCHITECTURAL WORK SUCH AS CEILING REMOVAL/REPLACEMENT, PATCHING, ETC. SHALL
BE PROVIDED AS REQUIRED BY MECHANICAL, PLUMBING AND ELECTRICAL WORK OUTSIDE
OF THE MAJOR WORK AREAS. CONTRACTOR SHALL REVIEW ALL DRAWINGS AND FIELD
VERIFY EXISTING CONDITIONS TO DETERMINE SCOPE OF THIS WORK.
-ICRA WALLS SHOWN ARE AT A MINIMUM. ADDITIONAL LOCATIONS MAY BE REQUIRED AS
DIRECTED BY COR.
KEY NOTES
1. DENOTES TEMPORARY FIRE RATED DOOR AND ICRA HARDWALL BARRIER - 1 HR SMOKE
BARRIER. WALL TO BE: 5/8" TYPE X GWB BOTH SIDES OF 3 5/8" MTL STUDS AT 16" OC, EXTEND
TO DECK / SLAB ABOVE WITH FIRE RATED SEALANT AT TOP AND BOTTOM CONNECTIONS ON
BOTH SIDES
2. PROVIDE TEMPORARY 1/3 HOUR RATED DOOR, FRAME AND HARDWARE. PROVIDE 1-1/2
PAIRS OF HINGES, CLOSER AND CLASSROOM (F84) LOCKSET, AUTOMATIC DOOR BOTTOMS
AND RUBBER SEALS
LEGEND
1 HR. RATED TEMPORARY PARTITION
AREA NOT IN SCOPE
T
20 23
MIN.
6' - 0"
PATIENT RISK GROUP TABLE
GROUP 1
LOW RISK
GROUP 2
MEDIUM RISK
GROUP 3
HIGH RISK
GROUP 4
HIGHEST RISK
- ADMINISTRATIVE OFFICES
- PUBLIC CORRIDORS
- ELEVATORS
- DAY ROOMS
- CANTEEN RETAIL STORE
- VACANT WARDS OR
VACANT ICU'S ETC.
- OUTPATIENT, URGENT
CARE & PRIMARY CARE
CLINICS
- LABORATORY
- CARDIOLOGY
- ECHOCARDIOGRAPHY
- ENDOSCOPY
- FOOD SERVICES
- INTERIM CARE & MEDICAL
UNITS
- NUCLEAR MEDICINE
- PHARMACY
- PHYSICAL THERAPY
- RADIOLOGY & NUCLEAR
MEDICINE
- RESPIRATORY THERAPY
- CCU
- EMERGENCY ROOM
- LABORATORY
- OUTPATIENT SURGERY
- PHARMACY
- POST ANESTHESIA CARE
UNIT
- SURGICAL UNITS
- ANY AREA CARING FOR
IMMUNICOMPROMISED
PATIENTS
- SPD STORAGE /
STERILIZATION
- INTENSIVE CARE UNITS
- TB NEGATIVE PRESSURE
ISOLATION ROOMS
-OPERATING ROOM
INFECTION CONTROL MATRIX - CLASS OF PRECAUTIONS:
CONSTRUCTION PROJECT BY PATIENT RISK
PATIENT RISK GROUP
LOW RISK GROUP 1
MEDIUM RISK GROUP 2
HIGH RISK GROUP 3
HIGHEST RISK GROUP 4
TYPE A TYPE B TYPE C TYPE D
I
I
I
II
II
II
II
III/IV
II
II
III/IV
III/IV
III/IV
IV
IV
IV
CONSTRUCTION PROJECT TYPE
NOTE: INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK LEVEL
INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.
1. EXECUTE WORK BY METHODS TO
MINIMIZE RAISING DUST FROM
CONSTRUCTION OPERATIONS.
2. IMMEDIATELY REPLACE A CEILING TILE
DISPLACED FOR VISUAL INSPECTIONS.
DURING CONSTRUCTION PROJECT UPON COMPLETION OF PROJECT
C L A
S
I
C L
A
II
1. PROVIDE ACTIVE MEANS TO PREVENT
AIRBORNE DUST FROM DISPERSING INTO
ATMOSPHERE.
2.WATER MIST WORK SURFACES TO
CONTROL DUST WHILE CUTTING.
3.SEAL UNUSED DOORS WITH DUCT TAPE.
4.BLOCK OFF AND SEAL AIR VENTS.
5.PLACE DUST MAT AT ENTRANCE AND EXIT
OF WORK AREA.
6.REMOVE OR ISOLATE HVAC SYSTEM IN
AREAS WHERE WORK IS BEING
PERFORMED.
1.WIPE WORK SURFACES WITH DISINFECTANT.
2.CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
3.WIPE WORK SURFACES WITH DISINFECTANT,
WET MOP AND/OR VACUUM WITH HEPA
VACUUM BEFORE LEAVING WORK AREA.
4.REMOVE ISOLATION OF HVAC.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE THE FOLLOWING INFECTION CONTROL PRECAUTIONS
DEPENDING UPON THE AREA CLASS DESIGNATION
C L A
II
I
C L A
IV
1.REMOVE OR ISOLATE HVAC SYSTEM IN AREA
WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM.
2.COMPLETE ALL CRITICAL BARRIERS, I.E.,
SHEETROCK, PLYWOOD, PLASTIC, TO SEAL
AREA FROM NON-WORK AREA OR IMPLEMENT
CONTROL CUBE METHOD (CART WITH PLASTIC
COVERING AND SEALED CONNECTION TO
WORK SITE WITH HEPA VACUUM FOR
VACUUMING PRIOR TO EXIT) BEFORE
CONSTRUCTION BEGINS.
3.MAINTAIN NEGATIVE AIR PRESSURE WITHIN
WORK SITE UTILIZING HEPA EQUIPPED AIR
FILTRATION UNITS.
4.CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
5.COVER TRANSPORT RECEPTACLES OR
CARTS. TAPE COVERING UNLESS SOLID LID.
1.DO NOT REMOVE BARRIERS FROM WORK
AREA UNTIL COMPLETED PROJECT IS
INSPECTED BY THE ENVIRONMENTAL HEALTH
AND SAFETY AND INFECTION CONTROL AND
THOROUGHLY CLEANED BY ENVIRONMENTAL
SANITATION SECTION.
2.REMOVE BARRIER MATERIALS CAREFULLY TO
MINIMIZE SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH CONSTRUCTION.
3.VACUUM WORK AREA WITH HEPA FILTERED
VACUUMS.
4.WET MOP AREA WITH DISINFECTANT.
5.REMOVE ISOLATION OF HVAC SYSTEM IN AREAS
WHERE WORK IS BEING PERFORMED.
1.OBTAIN INFECTION CONTROL PERMIT BEFORE
CONSTRUCTION BEGINS.
2. ISOLATE HVAC SYSTEM IN AREA WHERE WORK
IS BEING DONE TO PREVENT CONTAMINATION
OF DUCT SYSTEM.
3.COMPLETE ALL CRITICAL BARRIERS OR
IMPLEMENT CONTROL CUBE METHOD BEFORE
CONSTRUCTION BEGINS.
4.MAINTAIN NEGATIVE AIR PRESSURE WITHIN
WORK SITE UTILIZING HEPA EQUIPPED AIR
FILTRATION UNITS.
5.SEAL HOLES, PIPES, CONDUITS AND
PUNCTURES APPROPRIATELY.
6.CONSTRUCT ANTEROOM AND REQUIRE ALL
PERSONNEL TO PASS THROUGH THIS ROOM
SO THEY CAN BE VACUUMED USING A HEPA
VACUUM CLEANER BEFORE LEAVING WORK SITE
OR THEY CAN WEAR CLOTH OR PAPER
COVERALLS THAT ARE REMOVED EACH TIME
THEY LEAVE THE WORK SITE.
7.ALL PERSONNEL ENTERING WORK SITE ARE
REQUIRED TO WEAR SHOE COVERS.
1.DO NOT REMOVE BARRIERS FROM WORK
AREA UNTIL COMPLETED PROJECT IS
THOROUGHLY CLEANED BY ENVIRONMENTAL
MANAGEMENT.
2.VACUUM WORK AREA WITH HEPA FILTERED
VACUUMS.
3.WET MOP AREA WITH DISINFECTANT.
4.REMOVE BARRIER MATERIALS CAREFULLY
TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH CONSTRUCTION.
5.CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
6.COVER TRANSPORT RECEPTACLES OR
CARTS. TAPE COVERING.
7.REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK IS BEING
PERFORMED.
DURING CONSTRUCTION PROJECT UPON COMPLETION OF PROJECT
A Se rv ic e D i s a b l e d Vet e r an Owned
S m a l l B u s iness
SDVOSB
CVE
www.pfa-architect.com - Project No: ####
ARCHITECTURE, PLANNING,
INTERIORS
World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510 Phone: 757-471-0537 Fax: 757-471-4205
PF&A DESIGN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0004
B
A
C
D
E
F
NO. DESCRIPTION DATE
KEYPLAN
BID DOCUMENTS
FULLY SPRINKLERED
ACTUAL & PLAN
NORTH
NTS
CONSTRUCT CANCER
CENTER
VAMC RICHMOND, VA
652-318
11-08-2018
BLDG. 500
Department of
Veterans Affairs
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
GI004
ICRA ASSESSMENT PLAN
JCHDJP
11/08/18
3/32" = 1'-0"
ICRA PLAN - LEVEL 1 - PHASE 2
3/32" = 1'-0"
ICRA PARTIAL PLAN - LEVEL 2 - PHASE 2
3/32" = 1'-0"
ICRA PLAN - LEVEL 1 - PHASE 1
CONSTRUCTION TYPE: C
PATIENT RISK GROUP: MEDIUM RISK, GROUP 3
INFECTIION CONTROL PRECAUTIONS: CLASS IV
FOR ALL WORK:
NO.
A I
N I
G
RI
V
FOHTLA
E W
N O
M M
O
C JOSEPH H. TROST