Inspection Report_Data- Sheets Final.xls

XLS spreadsheet 4 MB Posted

Attached to
Z2DA--613-22-128 Repair Steam Piping Building 500 to 320 (VA-25-00033489)
Solicitation number
36C24525R0052
Issued by

About this file

This file is an Inspection Report detailing the condition of the heating distribution system at the Martinsburg VA Medical Center in West Virginia. The comprehensive report documents extensive infrastructure issues across multiple pump rooms and tunnel areas, including: widespread pipe insulation damage, missing insulation sections, numerous pipe leaks (steam, condensate, and water), non-functioning sump pumps, suspected asbestos presence, and structural deficiencies like missing support columns and corroded electrical components. The inspection, conducted on December 27, 2007, systematically catalogs 144 specific observations, with photographic evidence, covering pipe sizes ranging from 1/2" to 12" and highlighting critical maintenance and repair needs across steam, condensate, and utility systems.

The related federal contract opportunity (Solicitation Number: 36C24525R0052) specifically seeks to address these infrastructure challenges through a project labeled "Z2DA--613-22-128 Repair Steam Piping Building 500 to 320" for the Department of Veterans Affairs Veterans Health Administration. The solicitation amendment shifts the response time to 1:00pm on Thursday, July 10, 2025, indicating an upcoming procurement process to remediate the extensive system deficiencies documented in the detailed inspection report. The comprehensive inspection provides a clear technical foundation for the proposed steam piping repair project.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

HEATING DISTRIBUTION SYSTEM

VAMC MARTINSBURG, WV

Re: Drawing A-1.01INSPECTION REPORT
Notes:

Pipe Pipe system note Ins Insulation note Asb Asbestos (suspected) issue Misc Miscellaneous issues

ITEMCATEGORYDESCRIPTIONPHOTO NO.PHOTOORIG NO
1InsInsulation missing from 6" & 12" pipe ~10' each.1
2MiscSump pump not working.2
3InsDamaged insulation @ access point, 2", 5" &12" diameter.3
4MiscSump pit full of mud.4
5InsBadly damaged 12, 6, 5, & 2 inch pipe insulation, ~6' each.PH015
6InsDamaged insulation on 2" union.6
7InsDamaged insulation at access point, 5", 2", ~3' each.7
8InsDamaged insulation. 2", 5", ~6' each.PH028
9MiscPump Room 'F'. Inactive.PH2475
10.1InsMissing insulation (mag block), 1.5" ~21'.72a
10.2PipeMissing pipe hangers, ~2 each, uninsulated pipe near floor.72b
11MiscElectric junction box resting on pipe.11
12.1PipePump Room 'A'. 12" Low pressure steam line.PH2576a
12.2PipeLeak at expansion coupling.PH2676b
13PipePump in Pump Room 'A'.PH2777
14.1InsMag block insulation damage.PH1973a
14.2InsPH2073b
14.3InsPH2173c
14.4InsPH2273d
14.5InsPH2373e
15InsDamaged insulation on ell10
16PipeSteam leak in 12" union.9
17PipeLeaking PRV.PH3380
18InsMissing insulation 12" ~50'12
19InsMissing insulation 12" ~50', 6" ~50'13
20InsMissing insulation 2" & 12" @ access.14
21.1PipePRV old leak (or not leaking now).PH3179a
21.2MiscWood support loose, cable attached to it.PH3279b
22InsMissing insulation 6" ~3'.15
23.1PipePit 'Z'. Drip at 2" relief valve.PH2878a
23.2PipeLeak at pressure relief valve.PH2978b
23.3PipeDrip from 1/2" valve.PH3078c
24InsMissing insulation 12" ~6'.16
25InsMissing insulation 2.5" ~6'.17
26PipeNear Pit 'Y', Leaking 8" expansion coupling.PH3481
27InsDamaged insulation. No packing on mag block insulation at hangers this section. Missing hanger at joint.PH0318
28PipePit 'Y', PRV leaking at stem packing.PH3582
29MiscWater flowing into Pit 'Y'.PH3683
30PipePit 'Y', condensate pump.PH3784
31PipeLeak at 1/2" valve.PH3884a
32InsValve station, general condition of all: missing insulation.PH0419
33PipeLeak at 2" valve.PH3985
34.1PipeLeak at PRV.PH4086a
34.2PipeLeak at 1.5" valve.PH4186b
35.1PipePit 'X'.PH4287a
35.2PipeLeak at 1/2" valve.PH4387b
36InsMissing insulation 1" ~6'. Damaged insulation 12". Damaged insulation this section @ hangers & joints.20
37PipeLeak at 12" expansion coupling.PH4488
38InsMissing insulation 8" & 12" joints.21
39MiscIntersection #5. Conduit and electrical box on pipe.PH4589
40InsInsulation this section fair to good.22
41MiscSump pump not working.90
42InsInsulation missing from small diameter pipe.23
43PipeIntersection #6. Leak at 12" expansion coupling.PH4691
44.1PipePH0524a
44.2InsPump Room #3. Leak in 1 1/4" diameter pipe at wall.PH0624b
45MiscLeak in sump pump line.PH4792
46MiscContinuous flow from condensate pump onto floor.93
47PipeLeak at threads to nipple into 1" valve.94
48PipeLeak in condensate pump on left at near electric pressure switch. Leak from right rear pump.95
49PipePump Room #3. Pump making loud grinding noise.PH4896
50InsNew fiber glass insulation this section.25
51PipeLeak at 2" valve, outside of Pump Room #3.PH4997
52MiscCable on floor.PH5098
53InsNew fiber glass insulation from Intersection #7 to Pump Room #3.PH0726a
54MiscLoose cable.PH0826b
55.1PipeIntersection #7. Valve, not leaking now.PH5199a
55.2PipeIntersection #7. Valve, not leaking now.PH5299b
56InsDamaged insulation at access point, 6" ~3'. Used as a step.27
57PipeLeak in 1/2" Ell.PH53100
58InsLoose insulation on small diameter pipe.31
59InsMissing insulation, 1" ~60'.28
60PipeHanger missing on 1/2" pipe at access door.101
61InsMissing insulation, 1" ~15'.29
62PipeHanger missing from conduit just under B203. Hanger missing from 3" pipe near floor.102
63InsMissing insulation, 2" & 5" ~10' each.30
64InsMissing insulation on 1 1/2" ~24'.32
65PipeLeaking 6" expansion coupling.PH55104
66MiscJunction box corroded and loose.PH54103
67InsMissing insulation, 2" ~6', 5" ~12'.33
68InsMissing insulation, various sizes ~50'.34
69InsMissing insulation, 1 1/4" ~6'.64
70MiscPipe & insulation in water.65
71PipeLeak around 6" sprinkler line coming from floor above.105
71.1MiscNo pump in sump.66a
71.2AsbSuspected asbestos debris on floor.66b
72PipeLeak from 1.5" Cu valve.PH56106
73.1InsMissing insulation, 2 1/2" ~15'. Damaged insulation, 1 1/4" ~9' 5" ~30'.68a
73.2MiscSump filled with mud.68b
74.1InsMissing insulation, 5" ~20' 2 1/2" ~40' 1 1/4" ~9'.67a
74.2MiscSump filled with mud.67b
76.1InsMissing insulation, 3/4" ~24'.35a
76.2MiscFloor insulation falling down.35b
77PipeLeak at 1/2" valve near PRV.PH57107
78.1InsMissing insulation, 1 1/4" ~9'. Damaged insulation, 2 1/2" ~40' 5" ~40.69a
78.2MiscSump filled with mud.69b
79PipeLeak in 3/4" Cu valve.PH58108
80.1InsMissing insulation, 1 1/2" ~9'. Damaged insulation, 5" & 2 1/2" ~30' each.70a
80.2MiscNo pump in sump.70b
80.3MiscLoose electric box.70c
81PipeLeak at 1/2" valve.PH59109
82.1InsMissing insulation, 5" & 2.5" ~40' each.71a
82.2MiscMissing lolly column.71b
82.3MiscSump full of mud. 2' of water in tunnel.71c
83PipeLeak at 5" valve.PH60110
84PipeLeak at 2" union.PH61111
85PipeLeak at condensate pump.PH62112
86InsMissing insulation 3/4" ~3'.36
87.1InsNew fiber glass insulation.44a
87.2MiscTwo (2) sumps without pumps filled with water (but floor is dry).44b
88PipeBad leak in 1 x 1/2 x 1 Tee at 1/2" threads.PH85142
89PipeLeaking expansion coupling.PH84141
90PipeAbout 5 hangers missing from 1" pipe.140
91.1MiscSump pump off.45a
91.2InsDamaged insulation, all lines this section.45b
91.3AsbAsbestos insulation, 1" ~6'.45c
92InsMissing insulation 5" valve, 1 1/4" pipe.46
93PipeLeak at expansion coupling.PH63113
94InsMissing insulation, 2" 3 1/2" ~30' each.42
95InsMissing insulation, 3/4" 1" ~10' each. Damaged insulation at floor, 5" ~40'. Missing insulation, 1/2" ~20'.41
95MiscSump pump line leaking near pump.114
97.1InsMissing insulation, 4" ~6'.60a
97.2MiscSump filled with mud.60b
98PipeBadly corroded valve.PH64115
99.1InsMissing insulation, 2" 2" 3 1/2" ~30' each. Deteriorating insulation.43a
99.2MiscSump pump not working.43b
100.1MiscSump filled with mud.61a
100.2MiscMissing lolly column.61b
101PipeSteam leak in expansion coupling.PH65117
102PipePipe hanger missing from small and medium size pipe.116
103PipeBadly calcified and leaking Cu valves and nipples.PH66118
104PipeLeaking condensate pump.PH67119
105PipeSteam pump, continuous leak.62
106PipeLeaking PRV.PH68120
107InsMissing insulation, 1 1/8 Cu ~6'.63
108.1MiscLoose cable.PH0940a
108.2InsDeteriorating insulation at floor.PH1040b
108.3InsMissing insulation at floor, 5" ~40'PH1140c
108.4InsMissing insulation, misc ~40'PH1240d
108.5MiscCorroding conduit.PH1340e
108.6MiscCorroding conduit.PH1440f
109PipeLeaking PRV and 1" valve leading to it.PH69121
110InsMissing insulation, 1 1/4" ~30', 1 1/4" Cu ~30', 3" ~30'. Water on floor and in shallow trench. Deteriorating insulation in trench, 3" ~50'.38
111MiscLeak coming from floor above. Told maintenance crew.37
112PipeBadly corroded sprinkler line (1") caused by leaking H2O drain valve above. Leaking 2" Cu valve nearby.122
113PipeCondensate pump leaking.39
114PipeLeaking 3" union.PH70123
116PipeSteam coming from covered pit.PH83139
117AsbAsbestos insulation on pipe & fittings in niche. Needs to be sealed.PH1848
118.1AsbAsbestos insulation on pipe in 12' x 12" encasement. Needs to be sealed.PH1547a
118.2AsbPH1647b
118.3AsbPH1747c
119PipeLeft side of tunnel, badly corroded 3/4" PRV and leaking relief valve.PH82138
120PipeBadly leaking 1 x 1/2 x 1 Tee.PH81137
121.1PipeBadly corroded PRV.PH79136a
121.2PipePH80136b
122MiscLolly column missing from end of floor support beam.135
123InsMissing insulation, 5" valve and fittings.49
124InsMissing insulation, 1 1/2" ~9'.50
125MiscSump pump off, floor is wet.51
126MiscMissing lolly column.134
127PipeLarge diameter pipe expansion coupling, steam leak at zurk fitting.PH78133
128MiscSump full of mud.52
129PipeBadly corroded 1.25" Cu to Galv connection each end of Cu pipe running across main pipe lines.PH77132
130MiscSump full of mud.131
131InsMissing insulation, 1 1/4" ~6'.53
132PipePartially assembled expansion coupling.PH75129
133PipeLeaking condensate pump.PH76130
134PipeBad leak at Cu to Galv connection.PH74128
135PipeBad leak at thread in LP return line.PH73127
136MiscNo sump pump.54
137MiscNo sump pump. Floor is wet.55
138PipeLeaking 2" valve.PH72126
139MiscSump filled with mud.56
140MiscSump filled with mud.57
141MiscMissing lolly column.59
142MiscMissing lolly column middle of this section.125
143PipeLeaking 4" valve. Near firewall, pin hole leak in 1.25" capped pipe.PH71124
144InsMissing insulation, 1 1/4" ~6'.58

&L&9NIKA Technologies, Inc.

Powell Architects, Inc.&C&9Martinsburg VMAC Steam & Condensate Pipe Inspection December 27. 2007&R&9&P of &N