C200 - Final Technical Report.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24525R0052
About this file
This document is a detailed Asbestos-Containing Materials Survey technical report for Building C200 at the Martinsburg VA Medical Center in West Virginia, conducted by Boggs Environmental Consultants (BEC) in July and September 2015. The survey involved comprehensive sampling and laboratory analysis of various building materials to identify potential asbestos-containing materials (ACBMs), utilizing Polarized Light Microscopy (PLM) and Transmission Electron Microscopy (TEM) testing methods.
Key findings include the identification of several EPA-regulated asbestos-containing materials: tan vinyl sheet flooring (sublayer) in the 209-207 corridor, pipe fitting elbows and gaskets in the crawl space, assumed roofing material, fire doors across multiple corridors, and window caulk in various corridor sections. The report notes that while most samples tested negative for asbestos, some materials like a 14" pipe gasket and a pipe fitting elbow contained chrysotile asbestos. The survey was conducted to ensure compliance with US EPA and State of West Virginia regulations, specifically in preparation for anticipated renovation activities, with recommendations for further testing and careful handling of suspect materials during any future construction work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| C Corridors - Final Technical Report.pdf | ||
| 36C24525R0052 0003.docx | DOCX document | |
| A-1.01 Heating Distribution System 2-4-08.pdf | ||
| C300 Even - Final Technical Report.pdf | ||
| RFIs - 36C24525R0052 Technical Questions.docx | DOCX document | |
| Inspection Report_Data- Sheets Final.xls | XLS spreadsheet | |
| 36C24525R0052 0002.docx | DOCX document | |
| Site Visit Sign-In Sheet.pdf | ||
| 36C24525R0052 0001.docx | DOCX document | |
| 613-22-128 Replace Steam Main B320 to B500_SpecS - Copy.pdf | ||
| 36C24525R0052.docx | DOCX document | |
| Contractor Response Postures_040716 - Copy.docx | DOCX document | |
| 613-22-128 Replace Steam Main B320_dwgs - Copy.pdf | ||
| 613-22-128 Steam Phase I_Past Performance Questionaire.docx | DOCX document | |
| 613-22-128 Replace Steam Main B320 to B500__ISLMPCRA - Copy.pdf | ||
| WAGE-RATES 02.docx | DOCX document |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS-CONTAINING MATERIALS SURVEY
BUILDING C200
Martinsburg VA Medical Center
510 Butler Avenue Martinsburg, West Virginia 25405
Ms. Krista Bowen, Industrial Hygienist
BEC Project # WV15032
Fieldwork Conducted: July 27, 2015, September 16, 2015, & September 17, 2015
Final Technical Report Date: November 3, 2015
Prepared by:
| Middletown MD | ~ | Morgantown, | WV | |||
| Corporate | Office: | 200 | W. | Main | Street, | Middle |
Tel:
| town, | MD | 21769 | |||
| (301) | 694‐5687 | ~ | Fax: | (301) | 694‐9799 |
ENVIRONMENTAL SCIENCE, ENGINEERING & INDUSTRIAL HYGIENE SERVICES
ASBESTOS-CONTAINING MATERIALS SURVEY
BUILDING C200
TABLE OF CONTENTS
SECTION I SITE DESCRIPTION 1.0
SECTION II ASBESTOS-CONTAINING MATERIALS SURVEY 1.0
SECTION III CONCLUSIONS & RECOMMENDATIONS 7.0
APPENDICES
APPENDIX A EMSL SAMPLE RESULTS & EMSL CHAIN OF CUSTODY
APPENDIX B SAMPLING LOG
APPENDIX C BEC STAFF QUALIFICATIONS
BOGGS ENVIRONMENTAL CONSULTANTS, INC.
Final Technical Report & Onsite Fieldwork Conducted By:
Derrick A. Klein Environmental Specialist State of West Virginia US EPA AHERA Asbestos Inspector (#AI008308)
SECTION 1.0 SITE DESCRIPTION
Project Site: Building C200
Requester Name: Ms. Krista Bowen, Industrial Hygienist
Requester Address: Department of Veteran Affairs
Subject Site Description & Scope of Work:
The subject site is Building C200 located on the campus at Martinsburg VA Medical Center 510 Butler Avenue, Martinsburg West Virginia 25405, hereinafter referred to as the subject site.
BEC received authorization from Ms. Krista Bowen, Martinsburg VA Medical Center, Industrial Hygienist, to provide support services to update the existing asbestos containing materials data base previously developed by others. Ms. Bowen requested the asbestos inspection to ensure compliance with United States Environmental Protection Agency’s (US EPA) and State of West Virginia, regulations, prior to disturbance of building construction materials anticipated (scheduled) to occur during renovation activities and to update the inventory of asbestos containing materials.
SECTION 2.0 ASBESTOS-CONTAINING MATERIAL SURVEY
BOGGS ENVIRONMENTAL CONSULTANTS, INC. (BEC) conducted an asbestos-containing building construction materials (ACBMs) re-inspection survey of the interior and exterior of the subject site to evaluate materials that were previously not sampled, collection and further evaluation of non-friable organically bound materials via Transmission Electron Microscopy (TEM) and updates of the existing locations and quantities of building construction materials. The asbestos inspection was conducted in accordance with the US EPA "Asbestos Hazard Emergency Response Act (AHERA) of 1986" (40 CFR Part 763) and the "Asbestos School Hazard Abatement Reauthorization Act (ASHARA) of 1992" (40 CFR Part 763, Appendix C-E, Model Accreditation Plan).
BEC staff member, Mr. Derrick Klein, conducted a preliminary field walk inspection for the purpose of developing an understanding of the previously sampled components. Subsequently, Mr. Klein collected multiple bulk samples of suspect ACBMs observed at the subject site, on July 27, 2015, September 16, 2015 & September 17, 2015.
FIELD SAMPLING
BEC advises, based upon current US EPA asbestos hazard control regulations, the minimum number of samples necessary to definitively determine the presence (or absence) of ACBMs is dependent on the nature and quantity of the suspect building construction material. Additionally, the US EPA has established a standardized schedule for bulk sample collection of suspect ACBMs based upon homogeneous areas.
BEC advises, based upon onsite visual inspection and bulk sampling activities, forty-two (42) samples of the suspect ACBMs were collected and submitted to the analytical laboratory which upon laboratory analysis revealed a total of forty-three (43) individual PLM/DS analyses were required due to multiple layered bulk samples. BEC advises, based upon US EPA asbestos analytical regulations, the laboratory analyst has the sole discretion/responsibility in determining whether the bulk sample is composed of one or multiple layers.
http://www.law.cornell.edu/uscode/html/uscode20/usc_sec_20_00004011----000-.html http://www.law.cornell.edu/uscode/html/uscode15/usc_sec_15_00002641----000-.html
LABORATORY ANALYSIS
Pursuant to the field screen and bulk sample collection, BEC submitted the bulk samples to EMSL of Cinnaminson, New Jersey for asbestos content analysis. EMSL is accredited by the American Industrial Hygiene Association and the National Institute of Standards and Technology (NIST)-National Voluntary Laboratory Accreditation Program as proficient in the analysis of asbestos in bulk samples.
EMSL performed Polarized Light Microscopy with Dispersion Staining (PLM/DS) of the bulk samples in accordance with the “Method for the Determination of Asbestos in Bulk Building Materials” (US EPA. Method 600/R-93/116, July 1993).
BEC advises PLM/DS analysis revealed asbestos WAS DETECTED in a number of the suspect ACBM bulk samples collected and submitted to EMSL. BEC provides the results of the PLM/DS analyses in Table A - Asbestos Containing Material Testing Results:
TABLE A- ASBESTOS CONTAINING MATERIAL TESTING RESULTS
HA# Sample # Material
Class.
Sampling Location
Building Construction Material
Asbestos (%)
29 C200-91715-1 M 207-205 Corridor
South Hallway Ceiling Brown Mastic Glue Dots None Detected
15 C200-91715-2 M 207-205 Corridor
South Hallway Ceiling 12"x 12" White Pinhole
ACT
None Detected
30 C200-91715-3 M 207-205 Corridor
South Hallway Ceiling White Drywall None Detected
31 C200-91715-4 M 207-205 Corridor
South Hallway Ceiling Yellow Drywall None Detected
32 C200-91715-5 M 207-205 Corridor
South Hallway Ceiling Joint Compound (Yellow
Drywall) None Detected
33 C200-91715-6 M 207 Corridor South
Doorway by Junction Box
White Masonry Seam Sealant
None Detected
34 C200-91715-7 M 205-203 Corridor
West Wall White Window Glazing None Detected
27 C200-91715-8 M 205-203 Corridor
West Wall White Window Caulk None Detected
35 C200-91715-9 M 205-203 Corridor
West Wall Red Exterior Door Caulk None Detected
36 C200-91715-10 M 203C Corridor
West Wall Yellow Masonry Seam
Sealant None Detected
5 C200-91715-11 M 207 Corridor South Wall
White Joint Compound None Detected
37 C200-91715-12 M West Exterior Wall Crawl Space Hatch
White Caulking None Detected
12 C200-91715-13 M 207 Corridor South Wall
Tan Baseboard Mastic None Detected
LABORATORY ANALYSIS (continued)
Class.
Sampling Location
Building Construction Material
Asbestos (%)
25 C200-CS916-1 TSI
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
MAG Insulation None Detected
25 C200-CS916-2 TSI
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
MAG Insulation 45% Chrysotile
25 C200-CS916-3 TSI
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
MAG Insulation None Detected
38 C200-CS916-4 TSI
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Pipe Fitting Elbows None Detected
17 C200-CS916-5 TSI
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Pipe Fitting Elbows None Detected
39 C200-CS916-6 TSI
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Pipe Fitting Elbows None Detected
18 C200-CS916-7 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
14" Pipe Gasket 20% Chrysotile
18 C200-CS916-8 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
14" Pipe Gasket None Detected
18 C200-CS916-9 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
6" Pipe Gasket None Detected
19 C200-CS916-10 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
White Pipe Mastic None Detected
19 C200-CS916-11 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
White Pipe Mastic None Detected
19 C200-CS916-12 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
White Pipe Mastic None Detected
20 C200-CS916-13 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Black Pipe Mastic None Detected
20 C200-CS916-14 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Black Pipe Mastic None Detected
Class.
Sampling Location
Building Construction Material
Asbestos (%)
20 C200-CS916-15 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Black Pipe Mastic None Detected
21 C200-CS916-16 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Pipe Cap Mastic None Detected
21 C200-CS916-17 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Pipe Cap Mastic None Detected
21 C200-CS916-18 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Pipe Cap Mastic None Detected
22 C200-CS916-19 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Fabric Pipe Wrap None Detected
22 C200-CS916-20 M
Crawl Space Pit Adjacent to
West Exterior Door by 217 Hallway
Fabric Pipe Wrap None Detected
22 C200-CS916-21 M
Crawl Space Pit Adjacent to
West Exterior Door
Fabric Pipe Wrap None Detected
White W/Specks Vinyl
Sheet Flooring None Detected
C200-C72715-1 M 211-209 Corridor Floor
Yellow Sheet Flooring Mastic
None Detected
6 C200-72715-2 M 211-209 Corridor Floor Gray Leveling
Compound None Detected
13 C200-72715-3 M 211-209 Corridor Floor Tan & Black Sheet
Flooring Mastic None Detected
2 C200-72715-4 M 209-207 Corridor Floor Blue w/Blue Specks Vinyl Sheet Flooring
None Detected
7 C200-72715-5 M 209-207 Corridor Floor Tan Vinyl Sheet
Flooring (Sublayer) None Detected
16 C200-72715-6 M 209-207 Corridor Floor Black Felt Paper None Detected 9 C200-72715-7 M 205 Corridor Floor 12"x 24" Tan VFT None Detected
14 C200-72715-8 M 205 Corridor Floor 12"x 24" White VFT None Detected
See APPENDIX B – SAMPLING LOG for the comprehensive sampling log sheet complete with historical sampling data.
Upon completion of PLM/DS laboratory data, EMSL was directed by Krista Bowen to conduct further analysis via “Gravimetric Reduction and Transmission Electron Microscopy” (ELAP 198.4) on twent-four (24) non-friable organically-bound (NOB) suspect materials reported as none-detected by PLM.
The request for TEM analysis is based upon the understanding that small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. In addition, binding materials in certain building products can cause matrix interference, which may obscure underlying asbestos fibers from view and result in a false-negative analytical result. Therefore, PLM is not consistently reliable in detecting asbestos in NOB materials.
Quantitative transmission electron microscopy (TEM) is currently the only method that can definitively pronounce NOB materials as non-asbestos containing.
BEC advises TEM analysis revealed asbestos WAS DETECTED in the suspect NOB bulk samples submitted to EMSL. BEC provides the results of the NOB TEM analyses hereunder in Table B - Asbestos Survey NOB TEM Analysis Results.
TABLE B – ASBESTOS SURVEY - NOB TEM ANALYSIS RESULTS
Class.
Sampling Location
Building Construction
Material Asbestos (%)
29 C200-91715-1 M 207-205 Corridor
South Hallway Ceiling Brown Mastic Glue
Dots None Detected
33 C200-91715-6 M 207 Corridor South
Doorway by Junction Box
White Masonry Seam Sealant
None Detected
34 C200-91715-7 M 205-203 Corridor
West Wall White Window
Glazing None Detected
27 C200-91715-8 M 205-203 Corridor
West Wall White Window Caulk None Detected
35 C200-91715-9 M 205-203 Corridor
West Wall Red Exterior Door
Caulk None Detected
36 C200-91715-10 M 203C Corridor
West Wall Yellow Masonry
Seam Sealant None Detected
37 C200-91715-12 M West Exterior Wall Crawl
Space Hatch White Caulking None Detected
12 C200-91715-13 M 207 Corridor South Wall
Tan Baseboard Mastic
None Detected
19 C200-CS916-10 M
Crawl Space Pit Adjacent to West Exterior Door by 217 Hallway
White Pipe Mastic None Detected
19 C200-CS916-11 M
Crawl Space Pit Adjacent to West Exterior Door by 217 Hallway
White Pipe Mastic None Detected
19 C200-CS916-12 M
Crawl Space Pit Adjacent to West Exterior Door by 217 Hallway
White Pipe Mastic None Detected
20 C200-CS916-13 M
Crawl Space Pit Adjacent to West Exterior Door
Black Pipe Mastic None Detected
TABLE B – ASBESTOS SURVEY - NOB TEM ANALYSIS RESULTS
Class.
Sampling Location
Building Construction
Material Asbestos (%)
20 C200-CS916-14 M
Crawl Space Pit Adjacent to West Exterior Door by 217 Hallway
Black Pipe Mastic None Detected
20 C200-CS916-15 M
Crawl Space Pit Adjacent to West Exterior Door by 217 Hallway
Black Pipe Mastic None Detected
21 C200-CS916-16 M
Crawl Space Pit Adjacent to West Exterior Door by 217 Hallway
Pipe Cap Mastic None Detected
21 C200-CS916-17 M
Crawl Space Pit Adjacent to West Exterior Door by 217 Hallway
Pipe Cap Mastic None Detected
21 C200-CS916-18 M
Crawl Space Pit Adjacent to West Exterior Door
Pipe Cap Mastic None Detected
White W/Specks
Vinyl Sheet Flooring None Detected
C200-C72715-1 M 211-209 Corridor Floor
Yellow Sheet Flooring Mastic
None Detected
13 C200-72715-3 M 211-209 Corridor Floor Tan & Black Sheet
Flooring Mastic None Detected
2 C200-72715-4 M 209-207 Corridor Floor Blue w/Blue Specks Vinyl Sheet Flooring
None Detected
7 C200-72715-5 M 209-207 Corridor Floor Tan Vinyl Sheet
Flooring (Sublayer) 19.3% Chrysotile
16 C200-72715-6 M 209-207 Corridor Floor Black Felt Paper None Detected
9 C200-72715-7 M 205 Corridor Floor 12"x 24" Tan VFT None Detected
14 C200-72715-8 M 205 Corridor Floor 12"x 24" White VFT None Detected
ASBESTOS SURVEY LIMITATIONS
The above limited inspection was characterized by close visual inspection of Building C200, in accordance with US EPA regulations and generally accepted engineering work practices associated with the conduct of an asbestos survey. It is relevant to note, BEC did NOT conduct exploratory demolition to gain access to enclosed building conditions (e.g., wall cavities, pipe chases, HVAC ductwork shafts, ceiling plenums, etc.). Additionally, BEC sampling strategy was based on materials not previously sampled or non organically bound materials which were not evaluated via TEM. As such, BEC assumes no responsibility that the historical information provided is accurate or complete.
ASBESTOS SURVEY LIMITATIONS (continued)
BEC collected random bulk samples of suspect ACBMs. BEC has made every effort to identify all locations and types of asbestos- construction materials. BEC asbestos survey sampling strategy included multiple samples of the same materials chosen at random. However, BEC advises, due to the inconsistencies of manufacturer processes and contractor installation methods, materials of similar construction may have varied quantities of asbestos.
Furthermore, BEC advises locating all asbestos materials can only be definitively achieved by conducting exploratory demolition and sampling every section of pipe insulation, every fitting or valve covering, every square yard of fireproofing, and every square foot of other surface coating materials. Therefore, BEC makes no warranty, expressed or implied, that all asbestos has been found. Additionally, BEC recommends bulk sampling and analysis of all suspect ACBMs (not otherwise evaluated during this survey) encountered within a building area, prior to renovation or demolition.
SECTION 3.0 CONCLUSIONS AND RECOMMENDATIONS
CONCLUSIONS
1. BEC concludes, based upon onsite visual inspection, review of analytical data and review of historical analytical data, US EPA-regulated ACBMs (defined as >1% asbestos content) were identified at the subject site and are listed in Table C – Asbestos Containing Materials.
TABLE C: ASBESTOS CONTAINING MATERIALS
Building Construction
Location
EPA
Regulated
OSHA
Regulated Estimated Quantity
Tan Vinyl Sheet Flooring (Sublayer)
209-207 Corridor YES YES ~320 SF
10” Pipe Fitting Elbow Crawl Space YES YES ~1 Each 14” Pipe Gasket Crawl Space YES YES ~10 Each
Assumed Roofing Material* Exterior Roof YES YES ~8,500 SF
Fire Door**
203C Corridor, 203 Corridor, 205-203 Corridor, 205 Corridor, 207-205 Corridor, 207 Corridor, 209-207 Corridor, 209 Corridor, 211-209 Corridor, 211 Corridor
211-213 Corridor
YES YES ~22 Doors
Window Caulk*** 203C Corridor, 205-203 Corridor
207-205 Corridor, 209-207 Corridor 211-209 Corridor, 211-213 Corridor
YES YES ~15 Windows
*BEC advises that access to the roof was not available during the time of the inspection; therefore BEC was unable to sample any suspect material. As such, BEC advises this material shall be presumed asbestos containing until samples can be collected of the material.
**BEC advises the typical construction feature of a Fire Door encloses all suspect material making it inaccessible without causing damage to the Fire Door. As such, BEC advises this material shall be presumed asbestos containing until samples can be collected of the material.
CONCLUSIONS (continued)
***BEC advises historical sampling data (TEM) of the window caulking revealed, “no asbestos detected”.
However, BEC advises the typical construction feature at each window opening encloses the original “off-white” window caulk thereby making the material inaccessible without causing damage to the existing window frame.
Furthermore, it is BEC opinion that the historical sample collection of window caulk was not of the original and likely of the new window caulking associated with the storm windows. As such, BEC recommends in an abundance of caution, treat all exterior Off-White Window Caulking as Asbestos Containing Material until it can undergo further analysis via “Gravimetric Reduction and Transmission Electron Microscopy” (ELAP 198.4).
2. BEC concludes, based upon review of US EPA and State of West Virginia law, specific regulations governing the disturbance, removal, and disposal of asbestos, DO APPLY to any work, of which is planned and/or can be reasonably anticipated to, result in the disturbance of the materials identified in the course of this inspection.
3. BEC concludes, based upon review of United States Occupational, Safety and Health Administration (Construction Industry-29 CFR 1926.1101 and General Industry-29 CFR 1910.1001) regulations governing non-occupational and occupational exposure to asbestos, DO APPLY to ANY renovation/demolition, housekeeping, maintenance and repair activities directly and/or indirectly impacting (disturbance/damage) the asbestos containing materials.
RECOMMENDATIONS
1. BEC recommends should the renovation activities result in the discovery of additional suspect ACBMs, halting all work activities with subsequent bulk sample collection and analysis of discovered ACBMs, to determine asbestos content.
APPENDIX A
EMSL SAMPLE RESULTS
EMSL CHAIN OF CUSTODY
OrderID: 041523222
EMSL Analytical, Inc.
200 Route 130 North Cinnaminson, NJ 08077
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041523222
613-C50025
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Attn:
Proj: C200 Asb Survey
Phone: (304) 263-3412
Fax: (304) 262-4881
Collected: 7/27/2015
Received: 8/04/2015
Analyzed: 8/11/2015
Krista Bowen
VA Medical Center
510 Butler Avenue
Martinsburg, WV 25405-9991
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0001C200-72715-1-Sheet Flooring
C200-B: Corridor Floor/White Vinyl Sheet w/ Specks Flooring
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 0% 100%PLM Gray/White None Detected
8/11/2015 0.0% 100%TEM Grav. Reduction None DetectedGray/White
Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0001AC200-72715-1-Mastic
C200-B: Corridor Floor/White Vinyl Sheet w/ Specks Flooring
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 0% 100%PLM Yellow None Detected
8/11/2015 0.0% 100%TEM Grav. Reduction None DetectedYellow
Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0002C200-72715-2
C200-B: Corridor Floor/Gray Leveling Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 0% 100%PLM Gray None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0003C200-72715-3
C200-B: Corridor Floor/Tan & Black Sheet Flooring Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 0% 100%PLM Tan/Black None Detected
8/11/2015 0.0% 100%TEM Grav. Reduction None DetectedTan/Black
Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0004C200-72715-4
C200-D: Corridor Floor/Blue w/ Blue Specks Vinyl Sheet Flooring
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 0% 100%PLM Blue None Detected
8/11/2015 0.0% 100%TEM Grav. Reduction None DetectedBlue
Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0005C200-72715-5
C200-D: Corridor Floor/Tan Vinyl Sheet Flooring
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 0% 100%PLM Tan None Detected
8/11/2015 0.0% 80.7% ChrysotileTEM Grav. Reduction Tan 19.3%
Test Report:EPAMultiTests-7.32.2.D Printed: 8/11/2015 12:25AM Page 1 of 2
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041523222
613-C50025
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0006C200-72715-6
C200-D: Corridor Floor/Black Felt Paper
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 60% 40%PLM Black None Detected
8/11/2015 0.0% 100%TEM Grav. Reduction None DetectedBlack
Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0007C200-72715-7
C200-G: Corridor Floor/12"x24" Tan Vinyl Floor Tile
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 0% 100%PLM Tan None Detected
8/11/2015 0.0% 100%TEM Grav. Reduction None DetectedTan
Client Sample ID:
Sample Description:
Lab Sample ID: 041523222-0008C200-72715-8
C200-G: Corridor Floor/12"x24" White Vinyl Floor Tile
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
8/05/2015 0% 100%PLM White None Detected
8/11/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Analyst(s):
PLM (5)Andrew Castellano
PLM (4)Chelsey Bilhear
TEM Grav. Reduction (8)Samantha Rundstorm
Benjamin Ellis, Laboratory Manager or Other Approved Signatory
Reviewed and approved by:
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S.
Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM alone is not consistently reliable in detecting asbestos in floor coverings and similar NOBs
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA-LAP, LLC-IHLAP Lab 100194, NYS ELAP
10872, NJ DEP 03036
Initial report from: 08/05/201519:41:28
Test Report:EPAMultiTests-7.32.2.D Printed: 8/11/2015 12:25AM Page 2 of 2
OrderID: 041528036
OrderID: 041528036
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041528036
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Attn:
Proj: C200 Asb Survey (Asbestos Survey)
Phone: (304) 263-3412
Fax: (304) 262-4881
Collected: 9/16/2015
Received: 9/17/2015
Analyzed: 9/22/2015
Krista Bowen
VA Medical Center
510 Butler Avenue
Martinsburg, WV 25405-9991
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0001C200-C5916-1
C200 Crawlspace/Mag Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 20% 80%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0002C200-C5916-2
C200 Crawlspace/Mag Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 20% 80%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0003C200-C5916-3
C200 Crawlspace/Mag Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 25% 75%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0004C200-C5916-4
C200 Crawlspace/Cementitious Pipe Fitting
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 40% 60%PLM Gray None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0005C200-C5916-5
C200 Crawlspace/Cementitious Pipe Fitting
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 55% 45% ChrysotilePLM Gray The sample group is not homogeneous
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0006C200-C5916-6
C200 Crawlspace/Cementitious Pipe Fitting
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 35% 65%PLM Gray None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0007C200-C5916-7
C200 Crawlspace/14" Pipe Flange Gasket
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 80% 20% ChrysotilePLM Gray
Test Report:EPAMultiTests-7.32.2.D Printed: 9/22/2015 11:45AM Page 1 of 4
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041528036
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0008C200-C5916-8
C200 Crawlspace/14" Pipe Flange Gasket
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 20% 80%PLM Gray None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0009C200-C5916-9
C200 Crawlspace/6" Pipe Flange Gasket
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM Red None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0010C200-C5916-10
C200 Crawlspace/White Pipe Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 5% 95%PLM White None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0011C200-C5916-11
C200 Crawlspace/White Pipe Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM White None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0012C200-C5916-12
C200 Crawlspace/White Pipe Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM White None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0013C200-C5916-13
C200 Crawlspace/Black Pipe Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM Black None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedBlack
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0014C200-C5916-14
C200 Crawlspace/Black Pipe Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM Black None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedBlack
Test Report:EPAMultiTests-7.32.2.D Printed: 9/22/2015 11:45AM Page 2 of 4
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041528036
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0015C200-C5916-15
C200 Crawlspace/Black Pipe Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM Black None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedBlack
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0016C200-C5916-16
C200 Crawlspace/White Pipe Cap Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM Yellow None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedYellow
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0017C200-C5916-17
C200 Crawlspace/White Pipe Cap Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM White None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0018C200-C5916-18
C200 Crawlspace/White Pipe Cap Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 0% 100%PLM White None Detected
9/22/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0019C200-C5916-19
C200 Crawlspace/Fabric Pipe Wrap
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 90% 10%PLM Tan None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0020C200-C5916-20
C200 Crawlspace/Fabric Pipe Wrap
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 90% 10%PLM Tan None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528036-0021C200-C5916-21
C200 Crawlspace/Fabric Pipe Wrap
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
9/18/2015 90% 10%PLM Tan None Detected
Test Report:EPAMultiTests-7.32.2.D Printed: 9/22/2015 11:45AM Page 3 of 4
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041528036
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy
Analyst(s):
PLM (7)Amy Johnson
PLM (14)Quynh Vu
TEM Grav. Reduction (9)Wayne Froehlich
Benjamin Ellis, Laboratory Manager or Other Approved Signatory
Reviewed and approved by:
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S.
Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM alone is not consistently reliable in detecting asbestos in floor coverings and similar NOBs
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA-LAP, LLC-IHLAP Lab 100194, NYS ELAP
10872, NJ DEP 03036
Initial report from: 09/18/201510:23:18
Test Report:EPAMultiTests-7.32.2.D Printed: 9/22/2015 11:45AM Page 4 of 4
OrderID: 041528397
OrderID: 041528397
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041528397
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Attn:
Proj: C200 Asb Survey (Asbestos Survey)
Phone: (304) 263-3412
Fax: (304) 262-4881
Collected: 9/17/2015
Received: 9/21/2015
Analyzed: 10/04/2015
Krista Bowen
VA Medical Center
510 Butler Avenue
Martinsburg, WV 25405-9991
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0001C200-91715-1
207-205C South Hallway Ceiling/Brown Mastic Glue Daubs
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM Brown Recommend TEMNone Detected
10/04/2015 0.0% 100%TEM Grav. Reduction None DetectedBrown
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0002C200-91715-2
207-205C South Hallway Ceiling/12"x12" White Pinhole ACT
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 80% 20%PLM Gray/White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0003C200-91715-3
207-205C South Hallway Ceiling/White Drywall
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 10% 90%PLM Brown/White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0004C200-91715-4
207-205C South Hallway Ceiling/Yellow Drywall
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 10% 90%PLM White/Yellow None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0005C200-91715-5
207-205C South Hallway Ceiling/Yellow Drywall Joint Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 90% 10%PLM Brown/White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0006C200-91715-6
207C South Doorway by Junction Box/White Masonary Seam Sealant
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM White None Detected
10/04/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Test Report:EPAMultiTests-7.32.2.D Printed: 10/04/2015 10:28PM Page 1 of 3
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041528397
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0007C200-91715-7
205-203C West Wall/White Window Glazing Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM White None Detected
10/04/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0008C200-91715-8
205-203C West Wall/White Window Caulking
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM White None Detected
10/04/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0009C200-91715-9
205-203C East Wall/Red Door Caulking
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM Red None Detected
10/04/2015 0.0% 100%TEM Grav. Reduction None DetectedRed
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0010C200-91715-10
203-203C West Wall/Yellow Masonary Seam Sealant
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM White None Detected
10/04/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0011C200-91715-11
205-203C South Wall/White Joint Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0012C200-91715-12
Exterior West Side Crawlspace Hatch/White Caulking
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM White None Detected
10/04/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041528397-0013C200-91715-13
207C East Wall/Tan Baseboard Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/02/2015 0% 100%PLM Tan None Detected
10/04/2015 0.0% 100%TEM Grav. Reduction None DetectedTan
Test Report:EPAMultiTests-7.32.2.D Printed: 10/04/2015 10:28PM Page 2 of 3
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041528397
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy
Analyst(s):
PLM (13)Alexis Kum
TEM Grav. Reduction (8)Chris Little
Benjamin Ellis, Laboratory Manager or Other Approved Signatory
Reviewed and approved by:
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S.
Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM alone is not consistently reliable in detecting asbestos in floor coverings and similar NOBs
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA-LAP, LLC-IHLAP Lab 100194, NYS ELAP
10872, NJ DEP 03036
Initial report from: 10/04/201522:28:05
Test Report:EPAMultiTests-7.32.2.D Printed: 10/04/2015 10:28PM Page 3 of 3
APPENDIX B
SAMPLING LOG
Building #:
Date:
HA# Sample #
Lab initials/Chain of
Custody # Sample location
Material Description
General Material Category or substrate Notes
Bldg # Floor Wing Space # Location of Sample Asb. Type Asb. Content
29 C200‐91715‐1 41528397 C200 1st C 207‐205 (Corridor)
207‐205 Corridor South Hallway Ceiling
Brown Mastic Glue Dots ACT Mastic NAD NAD (Via TEM)
15 C200‐91715‐2 41528397 C200 1st C 207‐205 (Corridor)
207‐205 Corridor South Hallway Ceiling
12"x 12" White Pinhole ACT Ceiling Tile NAD NAD
30 C200‐91715‐3 41528397 C200 1st C 207‐205 (Corridor)
207‐205 Corridor South Hallway Ceiling White Drywall Drywall NAD NAD
31 C200‐91715‐4 41528397 C200 1st C 207‐205 (Corridor)
207‐205 Corridor South Hallway Ceiling Yellow Drywall Drywall NAD NAD
32 C200‐91715‐5 41528397 C200 1st C 207‐205 (Corridor)
207‐205 Corridor South Hallway Ceiling
Joint Compound (Yellow Drywall) Joint Compound NAD NAD
33 C200‐91715‐6 41528397 C200 1st C
(Corridor)
207 Corridor South Doorway by Junction
Box White Masonry Seam Sealant Seam Sealant NAD NAD (Via TEM)
34 C200‐91715‐7 41528397 C200 1st C 205‐203 (Corridor
205‐203 Corridor West Wall
White Window Glazing Window Glazing NAD NAD (Via TEM)
27 C200‐91715‐8 41528397 C200 1st C 205‐203 (Corridor
205‐203 Corridor West Wall
White Window Caulk Window Caulk NAD NAD (Via TEM)
35 C200‐91715‐9 41528397 C200 1st C 205‐203 (Corridor
205‐203 Corridor West Wall
Red Exterior Door Caulk Door Caulk NAD NAD (Via TEM)
36 C200‐91715‐10 41528397 C200 1st C 203C
(Corridor) 203C Corridor West
Wall Yellow Masonry Seam Sealant Seam Sealant NAD NAD (Via TEM)
5 C200‐91715‐11 41528397 C200 1st C
(Corridor) 207 Corridor South
Wall White Joint Compound Joint Compound NAD NAD
37 C200‐91715‐12 41528397 C200 1st C Exterior West Exterior Wall Crawl Space Hatch White Caulking White Caulk NAD NAD (Via TEM)
12 C200‐91715‐13 41528397 C200 1st C
(Corridor) 207 Corridor South
Wall Tan Baseboard
Mastic Baseboard Mastic NAD NAD (Via TEM)
Lab Results
Sampling Log Sheet BEC Inspector: Derrick Klein C200
7/27/15 & 9/16/15 & 9/17/15
25 C200‐CS916‐1 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway MAG Insulation Pipe Insulation NAD NAD
Different HA# on
COC
25 C200‐CS916‐2 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway MAG Insulation Pipe Insulation NAD NAD
Different HA# on
COC
25 C200‐CS916‐3 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway MAG Insulation Pipe Insulation NAD NAD
Different HA# on
COC
38 C200‐CS916‐4 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway
Pipe Fitting Elbows Pipe Insulation NAD NAD
Different HA# on
COC
17 C200‐CS916‐5 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway
Pipe Fitting Elbows Pipe Insulation Chrysotile 45%
39 C200‐CS916‐6 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway
Pipe Fitting Elbows Pipe Insulation NAD NAD
Different HA# on
COC
18 C200‐CS916‐7 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway 14" Pipe Gasket Pipe Gasket Chrysotile 20%
18 C200‐CS916‐8 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway 14" Pipe Gasket Pipe Gasket NAD NAD
40 C200‐CS916‐9 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway 6" Pipe Gasket Pipe Gasket NAD NAD
Different HA# on
COC
19 C200‐CS916‐10 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway White Pipe Mastic Pipe Mastic NAD NAD (Via TEM)
19 C200‐CS916‐11 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway White Pipe Mastic Pipe Mastic NAD NAD (Via TEM)
19 C200‐CS916‐12 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway White Pipe Mastic Pipe Mastic NAD NAD (Via TEM)
20 C200‐CS916‐13 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Black Pipe Mastic Pipe Mastic NAD NAD (Via TEM)
20 C200‐CS916‐14 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Black Pipe Mastic Pipe Mastic NAD NAD (Via TEM)
20 C200‐CS916‐15 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Black Pipe Mastic Pipe Mastic NAD NAD (Via TEM)
21 C200‐CS916‐16 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Pipe Cap Mastic Pipe Cap Mastic NAD NAD (Via TEM)
21 C200‐CS916‐17 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Pipe Cap Mastic Pipe Cap Mastic NAD NAD (Via TEM)
21 C200‐CS916‐18 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Pipe Cap Mastic Pipe Cap Mastic NAD NAD (Via TEM)
22 C200‐CS916‐19 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Fabric Pipe Wrap Pipe Wrap NAD NAD
22 C200‐CS916‐20 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Fabric Pipe Wrap Pipe Wrap NAD NAD
22 C200‐CS916‐21 41528036 C200
Crawl Space C Exterior
Crawl Space Pit Adjacent to West
Exterior Door by 217 Hallway Fabric Pipe Wrap Pipe Wrap NAD NAD
White W/Specks Vinyl Sheet Flooring Sheet Flooring NAD NAD (Via TEM)
Yellow Sheet
Flooring Mastic Sheet Flooring
Mastic NAD NAD (Via TEM)
6 C200‐72715‐2 41523222 C200 1st C 211‐209 (Corridor) 211‐209 Corridor Floor
Gray Leveling Compound
Leveling Compound NAD NAD
13 C200‐72715‐3 41523222 C200 1st C 211‐209 (Corridor) 211‐209 Corridor Floor
Tan & Black Sheet Flooring Mastic
Sheet Flooring Mastic NAD NAD (Via TEM)
C200‐72715‐1 41523222 C200 1st C 211‐209 (Corridor) 211‐209 Corridor Floor
2 C200‐72715‐4 41523222 C200 1st C 209‐207 (Corridor) 209‐207 Corridor Floor
Blue w/Blue Specks Vinyl Sheet Flooring Sheet Flooring NAD NAD (Via TEM)
7 C200‐72715‐5 41523222 C200 1st C 209‐207 (Corridor) 209‐207 Corridor Floor
Tan Vinyl Sheet Flooring (Sublayer) Sheet Flooring Chrysotile 19.3% Via TEM
16 C200‐72715‐6 41523222 C200 1st C 209‐207 (Corridor) 209‐207 Corridor Floor Black Felt Paper Felt Paper NAD NAD (Via TEM)
9 C200‐72715‐7 41523222 C200 1st C
(Corridor) 205 Corridor Floor 12"x 24" Tan VFT Floor Tile NAD NAD (Via TEM)
14 C200‐72715‐8 41523222 C200 1st C
(Corridor) 205 Corridor Floor 12"x 24" White
VFT Floor Tile NAD NAD (Via TEM)
2 12108C20001 217843 C200 1st C
(Corridor) Section 211. Along north wall Blue linoleum floor sheeting Sheet Flooring NAD NAD
1 12108C20002 217843 C200 1st C
(Corridor) Section 211. Along north wall White linoleum floor sheeting Sheet Flooring NAD NAD
13 12108C20003 217843 C200 1st C
(Corridor) Section 211.
Southwest corner
Tan linoleum floor sheeting mastic Sheet Flooring NAD NAD
6 12108C20004 217843 C200 1st C
(Corridor) Section 211.
Southwest corner Gray sub‐flooring Flooring NAD NAD
13 12108C20005 217843 C200 1st C
(Corridor) Section 211. Along north wall
Tan linoleum floor sheeting mastic Sheet Flooring NAD NAD
33 12108C20006 217843 C200 1st C 209‐211 (Corridor)
Between section 209 & section 211. Along north wall Door frame caulk Door Caulk NAD NAD
3 12108C20007 217843 C200 1st C
(Corridor) Section 209.
2’ x 4’ White fissured ceiling tile Ceiling Tile NAD NAD
15 12108C20008 217843 C200 1st C 209‐211 (Corridor)
Between section 209 & section 211. Along west wall 12” x 12” White ceiling tile Ceiling Tile NAD NAD
4 12108C20009 217843 C200 1st C 209‐211 (Corridor)
Between section 209 & section 211. Drywall Drywall NAD NAD
5 12108C20010 217843 C200 1st C 209‐211 (Corridor)
Between section 209 & section 211.
Drywall joint compound
Joint Compound (Drywall) NAD NAD
35 12108C20011 217843 C200 1st C 209‐211 (Corridor)
Between section 209 &
211. Along west wall
Red door frame caulk Door Caulk NAD NAD
27 12108C20012 217843 C200 1st C
(Corridor) North of section 203.
Along east wall Window caulk Window Caulk NAD NAD
35 12108C20013 217843 C200 1st C
(Corridor) North of section 203.
Along west wall Red door frame caulk Door Caulk NAD NAD
2 12108C20014 217843 C200 1st C 205‐207 (Corridor)
Between 205 & 207 buildings. Along north wall Blue linoleum floor sheeting Sheet Flooring NAD NAD
1 12108C20015 217843 C200 1st C 205‐207 (Corridor)
Between 205 & 207 buildings. Along north wall White linoleum floor sheeting Sheet Flooring NAD NAD
6 12108C20016 217843 C200 1st C 205‐207 (Corridor)
Between 205 & 207 buildings. Along north wall
Gray floor leveling compound Flooring NAD NAD
13 12108C20017 217843 C200 1st C 205‐207 (Corridor)
Between 205 & 207 buildings. Along north wall Tan linoleum flooring mastic Sheet Flooring NAD NAD
33 12108C20018 217843 C200 1st C 205‐207 (Corridor)
Between 205 & 207.
Along north wall
Interior door frame caulk Door Caulk NAD NAD
24 12108C20019 217843 C200 1st C 205‐207 (Corridor)
Between 205 & 207.
Along north wall. Red fire stop Fire Stop NAD NAD
3 12108C20020 217843 C200 1st C
(Corridor) Building 205.
Northeast corner
2’ x 4’ White fissured ceiling tile Ceiling Tile NAD NAD
33 12108C20021 217843 C200 1st C
(Corridor) Building 205. Along west wall Interior door frame caulk Door Caulk NAD NAD
4 12108C20022 217843 C200 1st C
(Corridor) Building 205. Along west wall Drywall Drywall NAD NAD
5 12108C20023 217843 C200 1st C
(Corridor) Building 205. Along west wall Drywall joint compound
Joint Compound (Drywall) NAD NAD
4 12108C20024 217843 C200 1st C
(Corridor) Building 205. Drywall Drywall NAD NAD
5 12108C20025 217843 C200 1st C
(Corridor) Building 205.
Drywall joint compound
Joint Compound (Drywall) NAD NAD
15 12108C20026 217843 C200 1st C 203‐205 (Corridor)
Between 203 & 205.
Along east wall
12” x 12” White ceiling tile Ceiling Tile NAD NAD
27 12108C20027 217843 C200 1st C 203‐205 (Corridor)
Between 203 & 205.
Along west wall Window caulk Window Caulk NAD NAD
24 12108C20028 217843 C200 1st C
(Corridor) Bldg. 211. Along east wall Red fire stop Fire Stop NAD NAD
24 12108C20029 217843 C200 1st C
(Corridor) Bldg. 211. Along east wall Red fire stop Fire Stop NAD NAD
33 12108C20030 217843 C200 1st C
(Corridor) Bldg. 211. Along north wall Interior door frame caulk Door Caulk NAD NAD
34 12108C20031 217843 C200 1st C 209‐211 (Corridor)
Between 209 & 211.
Along west wall Window glazing Window Glazing NAD NAD
34 12108C20032 217843 C200 1st C 207‐209 (Corridor)
Between 207 & 209.
Along east wall Window glazing Window Glazing NAD NAD
27 12108C20033 217843 C200 1st C
(Corridor) Exterior. East wall, outside 207 Exterior window caulk Window Caulk Chrysotile 2%
35 12108C20034 217843 C200 1st C
(Corridor) Exterior. East wall, outside 207 Exterior door caulk Door Caulk NAD NAD
37 12108C20035 217843 C200 1st C
(Corridor) Exterior. East wall, outside 207
Exterior crawlspace hatch caulk Crawl Space Hatch Caulk NAD NAD
35 12108C20036 217843 C200 1st C
(Corridor) Exterior. East wall, outside 203 Exterior door caulk Door Caulk NAD NAD
35 12108C20037 217843 C200 1st C
(Corridor) Exterior. East wall, outside 203 Exterior window caulk Window Caulk Chrysotile 2%
37 12108C20038 217843 C200 1st C
(Corridor) Exterior. East wall, outside 203
Exterior crawlspace hatch caulk Crawl Space Hatch Caulk NAD NAD
26 12108C20039 217843 C200 1st C
(Corridor)
West side entrance foyer. Along south wall
Masonite board ceiling Masonite Board NAD NAD
26 12108C20040 217843 C200 1st C
(Corridor) Bldg. 20. Along south wall Masonite board wall Masonite Board NAD NAD
4 12108C20041 217843 C200 1st C
(Corridor) Bldg. 203. Along east wall Drywall Drywall NAD NAD
5 12108C20042 217843 C200 1st C
(Corridor) Bldg. 203. Along east wall Drywall joint compound
Joint Compound (Drywall) NAD NAD
APPENDIX C
BEC STAFF QUALIFICATIONS
| C200 Sampling Logsheet.pdf |
| Sampling Log |
File details come from the government source that posted it. Updated .