C Corridors - Final Technical Report.pdf
PDF 1 MB Posted
- Solicitation number
- 36C24525R0052
About this file
This document is a final technical report for an Asbestos-Containing Materials Survey conducted by Boggs Environmental Consultants (BEC) at the Martinsburg VA Medical Center's Building C Corridors. The survey was performed on September 24, 2015, at the request of the facility's Industrial Hygienist to update the existing asbestos-containing materials database and ensure compliance with US EPA and State of West Virginia regulations.
The comprehensive survey involved collecting 42 bulk samples across various building materials, which were analyzed using Polarized Light Microscopy (PLM) and Transmission Electron Microscopy (TEM). Key findings include the detection of asbestos in several materials: drywall caulk (2% chrysotile), window glazing (3% chrysotile), yellow sheet flooring mastic (5% chrysotile), and trace amounts in black mastic and interior door caulk. The report recommends treating all materials with asbestos content as asbestos-containing, following specific EPA and OSHA regulations for renovation, demolition, and maintenance activities. Additionally, the survey noted that some materials like fire doors and roof materials were presumed asbestos-containing due to limited accessibility for sampling.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Inspection Report_Data- Sheets Final.xls | XLS spreadsheet | |
| A-1.01 Heating Distribution System 2-4-08.pdf | ||
| C200 - Final Technical Report.pdf | ||
| 36C24525R0052 0003.docx | DOCX document | |
| C300 Even - Final Technical Report.pdf | ||
| RFIs - 36C24525R0052 Technical Questions.docx | DOCX document | |
| 36C24525R0052 0002.docx | DOCX document | |
| Site Visit Sign-In Sheet.pdf | ||
| 36C24525R0052 0001.docx | DOCX document | |
| WAGE-RATES 02.docx | DOCX document | |
| Contractor Response Postures_040716 - Copy.docx | DOCX document | |
| 613-22-128 Replace Steam Main B320_dwgs - Copy.pdf | ||
| 613-22-128 Replace Steam Main B320 to B500_SpecS - Copy.pdf | ||
| 36C24525R0052.docx | DOCX document | |
| 613-22-128 Steam Phase I_Past Performance Questionaire.docx | DOCX document | |
| 613-22-128 Replace Steam Main B320 to B500__ISLMPCRA - Copy.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS-CONTAINING MATERIALS SURVEY
BUILDING C Corridors
Martinsburg VA Medical Center
510 Butler Avenue Martinsburg, West Virginia 25405
Ms. Krista Bowen, Industrial Hygienist
BEC Project # WV15032
Fieldwork Conducted: September 24, 2015
Final Technical Report Date: November 3, 2015
Prepared by:
| Middletown MD | ~ | Morgantown, | WV | |||
| Corporate | Office: | 200 | W. | Main | Street, | Middle |
Tel:
| town, | MD | 21769 | |||
| (301) | 694‐5687 | ~ | Fax: | (301) | 694‐9799 |
ENVIRONMENTAL SCIENCE, ENGINEERING & INDUSTRIAL HYGIENE SERVICES
ASBESTOS-CONTAINING MATERIALS SURVEY
BUILDING C Corridors
TABLE OF CONTENTS
SECTION I SITE DESCRIPTION 1.0
SECTION II ASBESTOS-CONTAINING MATERIALS SURVEY 1.0
SECTION III CONCLUSIONS & RECOMMENDATIONS 7.0
APPENDICES
APPENDIX A EMSL SAMPLE RESULTS & EMSL CHAIN OF CUSTODY
APPENDIX B SAMPLING LOG
APPENDIX C BEC STAFF QUALIFICATIONS
BOGGS ENVIRONMENTAL CONSULTANTS, INC.
Final Technical Report & Onsite Fieldwork Conducted By:
Derrick A. Klein Environmental Specialist State of West Virginia US EPA AHERA Asbestos Inspector (#AI008308)
SECTION 1.0 SITE DESCRIPTION
Project Site: Building C Corridors
Requester Name: Ms. Krista Bowen, Industrial Hygienist
Requester Address: Department of Veteran Affairs
Subject Site Description & Scope of Work:
The subject site is Building C Corridors located on the campus at Martinsburg VA Medical Center 510 Butler Avenue, Martinsburg West Virginia 25405, hereinafter referred to as the subject site.
BEC received authorization from Ms. Krista Bowen, Martinsburg VA Medical Center, Industrial Hygienist, to provide support services to update the existing asbestos containing materials data base previously developed by others. Ms. Bowen requested the asbestos inspection to ensure compliance with United States Environmental Protection Agency’s (US EPA) and State of West Virginia, regulations, prior to disturbance of building construction materials anticipated (scheduled) to occur during renovation activities and to update the inventory of asbestos containing materials.
SECTION 2.0 ASBESTOS-CONTAINING MATERIAL SURVEY
BOGGS ENVIRONMENTAL CONSULTANTS, INC. (BEC) conducted an asbestos-containing building construction materials (ACBMs) re-inspection survey of the interior and exterior of the subject site to evaluate materials that were previously not sampled, collection and further evaluation of non-friable organically bound materials via Transmission Electron Microscopy (TEM) and updates of the existing locations and quantities of building construction materials. The asbestos inspection was conducted in accordance with the US EPA "Asbestos Hazard Emergency Response Act (AHERA) of 1986" (40 CFR Part 763) and the "Asbestos School Hazard Abatement Reauthorization Act (ASHARA) of 1992" (40 CFR Part 763, Appendix C-E, Model Accreditation Plan).
BEC staff member, Mr. Derrick Klein, conducted a preliminary field walk inspection for the purpose of developing an understanding of the previously sampled components. Subsequently, Mr. Klein collected multiple bulk samples of suspect ACBMs observed at the subject site, on September 24, 2015.
FIELD SAMPLING
BEC advises, based upon current US EPA asbestos hazard control regulations, the minimum number of samples necessary to definitively determine the presence (or absence) of ACBMs is dependent on the nature and quantity of the suspect building construction material. Additionally, the US EPA has established a standardized schedule for bulk sample collection of suspect ACBMs based upon homogeneous areas.
BEC advises, based upon onsite visual inspection and bulk sampling activities, forty-two (42) samples of the suspect ACBMs were collected and submitted to the analytical laboratory which upon laboratory analysis revealed a total of forty-four (44) individual PLM/DS analyses were required due to multiple layered bulk samples. BEC advises, based upon US EPA asbestos analytical regulations, the laboratory analyst has the sole discretion/responsibility in determining whether the bulk sample is composed of one or multiple layers.
http://www.law.cornell.edu/uscode/html/uscode20/usc_sec_20_00004011----000-.html http://www.law.cornell.edu/uscode/html/uscode15/usc_sec_15_00002641----000-.html
LABORATORY ANALYSIS
Pursuant to the field screen and bulk sample collection, BEC submitted the bulk samples to EMSL of Cinnaminson, New Jersey for asbestos content analysis. EMSL is accredited by the American Industrial Hygiene Association and the National Institute of Standards and Technology (NIST)-National Voluntary Laboratory Accreditation Program as proficient in the analysis of asbestos in bulk samples.
EMSL performed Polarized Light Microscopy with Dispersion Staining (PLM/DS) of the bulk samples in accordance with the “Method for the Determination of Asbestos in Bulk Building Materials” (US EPA. Method 600/R-93/116, July 1993).
BEC advises PLM/DS analysis revealed asbestos WAS DETECTED in a number of the suspect ACBM bulk samples collected and submitted to EMSL. BEC provides the results of the PLM/DS analyses in Table A - Asbestos Containing Material Testing Results:
TABLE A- ASBESTOS CONTAINING MATERIAL TESTING RESULTS
HA# Sample # Material
Class.
Sampling Location
Building Construction Material
Asbestos (%)
12 Gray Leveling Compound None Detected
C4-92415-1 M
C4 Corridor Center Under Radiator Black Mastic None Detected
3 C4-92415-2 M C4 Corridor Center
Under Radiator Tan Sheet Flooring Mastic None Detected
1 C4-92415-3 M C4 Corridor Center
Under Radiator White Vinyl Sheet Flooring None Detected
2 C4-92415-4 M C4 Corridor Center
Under Radiator Blue Vinyl Sheet Flooring None Detected
8 C4-92415-5 M C4 Corridor North
Wall Window White Window Glazing None Detected
6 C4-92415-6 M C4 Corridor South Wall Drywall Caulk 2% Chrysotile
18 C4-92415-7 M C4 Corridor East Wall
Above Doorway Red Fire Stop None Detected
11 C4-92415-8 M C4 Corridor East Wall Dividing C2 Corridor
Interior Door Caulk None Detected
5 C4-92415-9 M C3 Corridor North Wall White Joint Compound None Detected
5 C4-92415-10 M C9 Corridor
South Ceiling White Joint Compound None Detected
19 C4-92415-11 M C9 Corridor North Wall White Fire Stop None Detected
16 C4-92415-12 M C9 Corridor
West Wall Floor Purple Vinyl
Sheet Flooring None Detected
17 C4-92415-13 M C9 Corridor
West Wall Floor Yellow Sheet
Flooring Mastic 5% Chrysotile
26 C4-92415-14 M C9 Corridor West Wall by Sliding Door Off-White Radiator Caulk None Detected
25 C4-92415-15 M Exterior Sliding Door in C9 Corridor Black Exterior Door Caulk None Detected
22 C4-92415-16 M C13 Corridor Under South Wall Radiator
Brown Mastic (Sublayer) None Detected
20 C4-92415-17 M C13 Corridor Under South Wall Radiator
Black Vinyl Sheet Flooring None Detected
LABORATORY ANALYSIS (continued)
Class.
Sampling Location
Building Construction Material
Asbestos (%)
21 C4-92415-18 M C3 Corridor Under East
Hallway Sprinkler Closet Threshold
White Leveling Compound
None Detected
7 C4-92415-19 M C13 Corridor South Wall
Window East Corridor White Interior Window
Caulk None Detected
24 C4-92415-20 M North Hallway Exterior Door at Center of C13 Corridor Red Exterior Door
Caulk None Detected
23 C4-92415-21 M North Exterior Wall Metal Baseboard Flashing Caulk
White Masonry Seam Sealant
None Detected
15 C4-92415-22 M C6 Corridor South Wall Black Baseboard None Detected
14 C4-92415-23 M C6 Corridor Above 12”x 12”
Ceiling Tile Brown Mastic Glue
Dots None Detected
27 C4-92415-24 M North Exterior Door in C6 Corridor White Exterior Door
Caulk None Detected
28 C4-92415-25 M North Exterior Crawl Space
Hatch C6 Corridor Red Exterior Masonry
Seam Sealant None Detected
10 C4-92415-26 M North Exterior Wall Siding
C4 Corridor White Siding Caulk None Detected
29 C4-92415-27 M Crawl Space Pipe White Pipe Mastic None Detected 30 C4-92415-28 M C Crawl Space Pipe Off-White Pipe Mastic None Detected
32 C4-92415-29 M Crawl Space Pipe Brown Mastic
Glue Dots None Detected
31 C4-92415-30 M Crawl Space Pipe Fabric Pipe Wrap None Detected
33 C4-92415-31 TSI
Crawl Space East
Sample Location #1 18” MAG Pipe
Insulation None Detected
33 C4-92415-32 TSI
Crawl Space East
Sample Location #2 18” MAG Pipe
Insulation None Detected
33 C4-92415-33 TSI
Crawl Space East
Sample Location #3 18” MAG Pipe
Insulation None Detected
34 C4-92415-34 TSI
Crawl Space East
Sample Location #1 12” MAG Pipe
Insulation None Detected
34 C4-92415-35 TSI
Crawl Space East
Sample Location #2 12” MAG Pipe
Insulation None Detected
34 C4-92415-36 TSI
Crawl Space East
Sample Location #3 12” MAG Pipe
Insulation None Detected
35 C4-92415-37 TSI
Crawl Space East
Sample Location #1 9” MAG Pipe
Insulation None Detected
35 C4-92415-38 TSI
Crawl Space East
Sample Location #2 9” MAG Pipe
Insulation None Detected
35 C4-92415-39 TSI
Crawl Space East
Sample Location #3 9” MAG Pipe
Insulation None Detected
Class.
Sampling Location
Building Construction Material
Asbestos (%)
36 Fabric Pipe Wrap None Detected
C4-92415-40 M Crawl Space Pipe
Associated Black Mastic
None Detected
36 C4-92415-41 M Crawl Space Pipe Fabric Pipe Wrap None Detected
36 C4-92415-42 M Crawl Space Pipe Fabric Pipe Wrap None Detected
See APPENDIX B – SAMPLING LOG for the comprehensive sampling log sheet complete with historical sampling data.
Upon completion of PLM/DS laboratory data, EMSL was directed by Krista Bowen to conduct further analysis via “Gravimetric Reduction and Transmission Electron Microscopy” (ELAP 198.4) on twenty-four (24) non-friable organically-bound (NOB) suspect materials reported as none-detected by PLM.
The request for TEM analysis is based upon the understanding that small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. In addition, binding materials in certain building products can cause matrix interference, which may obscure underlying asbestos fibers from view and result in a false-negative analytical result. Therefore, PLM is not consistently reliable in detecting asbestos in NOB materials.
Quantitative transmission electron microscopy (TEM) is currently the only method that can definitively pronounce NOB materials as non-asbestos containing.
BEC advises TEM analysis revealed asbestos WAS DETECTED in the suspect NOB bulk samples submitted to EMSL. BEC provides the results of the NOB TEM analyses hereunder in Table B - Asbestos Survey NOB TEM Analysis Results.
TABLE B – ASBESTOS SURVEY - NOB TEM ANALYSIS RESULTS
Class.
Sampling Location
Building Construction
Material Asbestos (%)
38 C4-92415-1 M C4 Corridor Center
Under Radiator Black Mastic <0.1% Chrysotile
3 C4-92415-2 M C4 Corridor Center
Under Radiator Tan Sheet Flooring
Mastic None Detected
1 C4-92415-3 M C4 Corridor Center
Under Radiator White Vinyl Sheet
Flooring None Detected
2 C4-92415-4 M C4 Corridor Center
Under Radiator Blue Vinyl Sheet
Flooring None Detected
8 C4-92415-5 M C4 Corridor North
Wall Window White Window
Glazing 3% Chrysotile
18 C4-92415-7 M C4 Corridor East Wall
Above Doorway Red Fire Stop None Detected
11 C4-92415-8 M C4 Corridor East Wall Dividing C2 Corridor
Interior Door Caulk <0.37% Chrysotile
19 C4-92415-11 M C9 Corridor North Wall White Fire Stop None Detected
TABLE B – ASBESTOS SURVEY - NOB TEM ANALYSIS RESULTS
Class.
Sampling Location
Building Construction
Material Asbestos (%)
16 C4-92415-12 M C9 Corridor
West Wall Floor Purple Vinyl
Sheet Flooring None Detected
26 C4-92415-14 M C9 Corridor West Wall by Sliding Door Off-White Radiator
Caulk None Detected
25 C4-92415-15 M Exterior Sliding Door in
C9 Corridor Black Exterior Door
Caulk None Detected
22 C4-92415-16 M C13 Corridor Under South Wall Radiator
Brown Mastic (Sublayer)
None Detected
20 C4-92415-17 M C13 Corridor Under South Wall Radiator
Black Vinyl Sheet Flooring
None Detected
7 C4-92415-19 M C13 Corridor South Wall
Window East Corridor White Interior Window Caulk
None Detected
24 C4-92415-20 M North Hallway Exterior Door at Center of C13
Corridor
Red Exterior Door Caulk
None Detected
23 C4-92415-21 M North Exterior Wall
Metal Baseboard Flashing Caulk
White Masonry Seam Sealant
None Detected
15 C4-92415-22 M C6 Corridor South Wall Black Baseboard None Detected
14 C4-92415-23 M C6 Corridor Above 12”x
12” Ceiling Tile Brown Mastic Glue
Dots None Detected
27 C4-92415-24 M North Exterior Door in C6 Corridor White Exterior Door
Caulk None Detected
28 C4-92415-25 M North Exterior Crawl
Space Hatch C6 Corridor
Red Exterior Masonry Seam
Sealant None Detected
10 C4-92415-26 M North Exterior Wall Siding C4 Corridor
White Siding Caulk None Detected
29 C4-92415-27 M Crawl Space Pipe White Pipe Mastic None Detected
30 C4-92415-28 M C Crawl Space Pipe Off-White Pipe
Mastic None Detected
32 C4-92415-29 M Crawl Space Pipe Brown Mastic
Glue Dots None Detected
ASBESTOS SURVEY LIMITATIONS
The above limited inspection was characterized by close visual inspection of Building C Corridors, in accordance with US EPA regulations and generally accepted engineering work practices associated with the conduct of an asbestos survey. It is relevant to note, BEC did NOT conduct exploratory demolition to gain access to enclosed building conditions (e.g., wall cavities, pipe chases, HVAC ductwork shafts, ceiling plenums, etc.). Additionally, BEC sampling strategy was based on materials not previously sampled or non organically bound materials which were not evaluated via TEM. As such, BEC assumes no responsibility that the historical information provided is accurate or complete.
BEC collected random bulk samples of suspect ACBMs. BEC has made every effort to identify all locations and types of asbestos- construction materials. BEC asbestos survey sampling strategy included multiple samples of the same materials chosen at random. However, BEC advises, due to the inconsistencies of manufacturer processes and contractor installation methods, materials of similar construction may have varied quantities of asbestos.
Furthermore, BEC advises locating all asbestos materials can only be definitively achieved by conducting exploratory demolition and sampling every section of pipe insulation, every fitting or valve covering, every square yard of fireproofing, and every square foot of other surface coating materials. Therefore, BEC makes no warranty, expressed or implied, that all asbestos has been found. Additionally, BEC recommends bulk sampling and analysis of all suspect ACBMs (not otherwise evaluated during this survey) encountered within a building area, prior to renovation or demolition.
SECTION 3.0 CONCLUSIONS AND RECOMMENDATIONS
CONCLUSIONS
1. BEC concludes, based upon onsite visual inspection, review of analytical data and review of historical analytical data, US EPA-regulated ACBMs (defined as >1% asbestos content) were identified at the subject site and are listed in Table C – Asbestos Containing Materials.
TABLE C: ASBESTOS CONTAINING MATERIALS
Building Construction
Location
EPA
Regulated
OSHA
Regulated Estimated Quantity
Drywall Caulk
C2-Corridor, C3-Corridor, C4-Corridor, C6-Corridor, C7-Corridor, C9-Coridor, C10-Corridor, C13-Corridor, C14, Corridor
YES YES ~5,255 SF
Window Glazing
C2-Corridor, C3-Corridor, C4-Corridor, C6-Corridor, C7-Corridor, C9-Coridor, C10-Corridor, C13-Corridor, C14, Corridor
YES YES ~76 Windows
Yellow Linoleum Floor Sheeting Mastic
C9-Coridor, C10-Corridor YES YES ~4,025 SF
Assumed Roofing Material* Exterior Roof YES YES ~12,720 SF
CONCLUSIONS (continued)
TABLE C: ASBESTOS CONTAINING MATERIALS
Location
EPA
Regulated
OSHA
Regulated Estimated Quantity
Fire Door**
203C Corridor, 203 Corridor, 205-203 Corridor, 205 Corridor, 207-205 Corridor, 207 Corridor, 209-207 Corridor, 209 Corridor, 211-209 Corridor, 211 Corridor
211-213 Corridor
YES YES ~30 Doors
Window Caulk***
C2-Corridor, C3-Corridor, C4-Corridor, C6-Corridor, C7-Corridor, C9-Coridor, C10-Corridor, C13-Corridor, C14, Corridor
YES YES ~76 Windows
White Pipe Seam Sealant****
C2-Corridor, C3-Corridor, C4-Corridor, C6-Corridor, C7-Corridor, C9-Coridor, C10-Corridor, C13-Corridor, C14, Corridor
YES YES ~178 SF
*BEC advises that access to the roof was not available during the time of the inspection; therefore BEC was unable to sample any suspect material. As such, BEC advises this material shall be presumed asbestos containing until samples can be collected of the material.
**BEC advises the typical construction feature of a Fire Door encloses all suspect material making it inaccessible without causing damage to the Fire Door. As such, BEC advises this material shall be presumed asbestos containing until samples can be collected of the material.
***BEC advises current sampling data (TEM) of the window caulking revealed, “no asbestos detected”. However, BEC advises the typical construction feature at each window opening encloses the original “off-white” window caulk thereby making the material inaccessible without causing damage to the existing window frame.
Furthermore, it is BEC opinion that the historical sample collection of window caulk was not of the original and likely of the new window caulking associated with the storm windows. As such, BEC recommends in an abundance of caution, treat all exterior Off-White Window Caulking as Asbestos Containing Material until it can undergo further analysis via “Gravimetric Reduction and Transmission Electron Microscopy” (ELAP 198.4).
**** BEC advises current sampling data (TEM) of White Pipe Seam Sealant revealed, “no asbestos detected”.
However, BEC advises the historical sampling data has shown that the White Pipe Seam Sealant is asbestos containing material. As Such, BEC recommends in an abundance of caution, treating all White Pipe Seam Sealant as Asbestos Containing Material until it can go under further analysis within each individual location of the building.
2. BEC concludes, based upon review of US EPA and State of West Virginia law, specific regulations governing the disturbance, removal, and disposal of asbestos, DO APPLY to any work, of which is planned and/or can be reasonably anticipated to, result in the disturbance of the materials identified in the course of this inspection.
3. BEC concludes, based upon review of United States Occupational, Safety and Health Administration (Construction Industry-29 CFR 1926.1101 and General Industry-29 CFR 1910.1001) regulations governing non-occupational and occupational exposure to asbestos, DO APPLY to ANY renovation/demolition, housekeeping, maintenance and repair activities directly and/or indirectly impacting (disturbance/damage) the asbestos containing materials.
4. BEC concludes, based upon onsite visual inspection and review of analytical data; US OSHA regulated (<1% asbestos) construction materials ARE PRESENT within the subject site, as listed in Table D – Summary of Trace ACBM
TABLE D: SUMMARY OF TRACE ACBMs
Location
EPA
Regulated
OSHA
Regulated Estimated Quantity
Black Mastic
C2-Corridor, C3-Corridor, C4-Corridor, C6-Corridor, C7-Corridor, C9-Coridor, C10-Corridor, C13-Corridor, C14, Corridor
NO YES ~12,720 SF
Interior Door Frame Caulk
C2-Corridor, C3-Corridor, C4-Corridor, C6-Corridor, C7-Corridor, C9-Coridor, C10-Corridor, C13-Corridor, C14, Corridor
NO YES ~30 Each
RECOMMENDATIONS
1. BEC recommends should the renovation activities result in the discovery of additional suspect ACBMs, halting all work activities with subsequent bulk sample collection and analysis of discovered ACBMs, to determine asbestos content.
2. BEC recommends that all materials found to contain “Trace” amounts of asbestos be treated as asbestos-containing
APPENDIX A
EMSL SAMPLE RESULTS
EMSL CHAIN OF CUSTODY
EMSL Analytical, Inc.
200 Route 130 North Cinnaminson, NJ 08077
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041529583
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Attn:
Proj: C4 (Asbestos Survey)
Phone: (304) 263-3412
Fax: (304) 262-4881
Collected: 9/24/2015
Received: 10/02/2015
Analyzed: 10/09/2015
Krista Bowen
VA Medical Center
510 Butler Avenue
Martinsburg, WV 25405-9991
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0001C4-92415-1-Leveler
Under Radiator- Center C4 Corridor/Gray Leveling Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Gray None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0001AC4-92415-1-Mastic
Under Radiator- Center C4 Corridor/Gray Leveling Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Black None Detected
10/09/2015 0.0% 100% ChrysotileTEM Grav. Reduction Black <0.1%
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0002C4-92415-2
Under Radiator- Center C4 Corridor/Tan Sheet Flooring Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Tan None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedTan
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0003C4-92415-3
Under Radiator- Center C4 Corridor/White Vinyl Sheet Flooring
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0004C4-92415-4
Under Radiator- Center C4 Corridor/Blue Vinyl Sheet Flooring
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Blue None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBlue
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0005C4-92415-5
North Wall Window- C4/White Window Glazing
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
10/09/2015 0.0% 97.0% ChrysotileTEM Grav. Reduction White 3.0%
Test Report:EPAMultiTests-7.32.2.D Printed: 10/09/2015 06:31PM Page 1 of 7
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041529583
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0006C4-92415-6
South Wall- C4/Drywall Caulk
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 98% 2% ChrysotilePLM Tan/White/Green
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0007C4-92415-7
East Wall above Doorway- C4/Red Fire Stop
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 5% 95%PLM Red None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedRed
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0008C4-92415-8
East Wall Dividing C2 Corridor/Interior Door Caulk
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Tan None Detected
10/09/2015 0.0% 100% ChrysotileTEM Grav. Reduction Tan <0.37%
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0009C4-92415-9
North Wall- C3/White Joint Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0010C4-92415-10
South Ceiling- C9/White Joint Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0011C4-92415-11
North Wall- C9/White Fire Stop
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0012C4-92415-12
West Wall Floor- C9/Purple Vinyl Sheet Flooring
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Purple None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedPurple
Test Report:EPAMultiTests-7.32.2.D Printed: 10/09/2015 06:31PM Page 2 of 7
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041529583
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0013C4-92415-13
West Wall Floor- C9/Yellow Sheet Flooring Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 95% 5% ChrysotilePLM Yellow
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0014C4-92415-14
West Wall by Sliding Door Exit- C9/Off-White Radiator Caulk
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Beige None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBeige
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0015C4-92415-15
Sliding Door in C9 Corridor- Exterior/Black Exterior Door Caulk
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Black None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBlack
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0016C4-92415-16
Under South Wall Radiator- C13/Brown Mastic (Sub-layer)
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Brown None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBrown
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0017C4-92415-17
Under South Wall Radiator- C13/Black Vinyl Sheet Flooring
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Black None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBlack
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0018C4-92415-18
Under East Hallway Sprinkler Closet Threshold C13/White Leveling Compound
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0019C4-92415-19
South Wall Window East Corridor- C13/White Interior Window Caulk
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Test Report:EPAMultiTests-7.32.2.D Printed: 10/09/2015 06:31PM Page 3 of 7
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041529583
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0020C4-92415-20
North Hallway Exterior Door Center C13 Corridor Ex/Red Exterior Door Caulk
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Red None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedRed
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0021C4-92415-21
North Exterior Wall Baseboard Flashing Caulk- Ext/White Masonary Seam Sealant
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Gray/White None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedGray/White
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0022C4-92415-22
South Wall- C6/Black Baseboard
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Black None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBlack
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0023C4-92415-23
Above 12"x12" Ceiling Tile- C6/Brown Mastic Glue Dots
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Brown None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBrown
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0024C4-92415-24
North Exterior Door in C6 Corridor- Exterior/White Exterior Door Caulk
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Gray/White None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedGray/White
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0025C4-92415-25
North Exterior Crawlspace Hatch C6 Corridor- Ext/Exterior Red Masonary Seam Sealant
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Red None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedRed
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0026C4-92415-26
North Exterior Wall Siding C4 Corridor- Exterior/White Siding Caulk
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Test Report:EPAMultiTests-7.32.2.D Printed: 10/09/2015 06:31PM Page 4 of 7
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041529583
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0027C4-92415-27
Crawlspace Pipe- Exterior/White Pipe Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM White None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedWhite
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0028C4-92415-28
Crawlspace Pipe- Exterior/Off-White Pipe Cap Mastic
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Beige None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBeige
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0029C4-92415-29
Crawlspace Pipe- Exterior/Brown Mastic Glue Dots
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Brown None Detected
10/09/2015 0.0% 100%TEM Grav. Reduction None DetectedBrown
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0030C4-92415-30
Crawlspace Pipe- Exterior/Fabric Pipe Wrap
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 80% 20%PLM Brown None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0031C4-92415-31
Crawlspace East Sample Location #1-C4-C5/18" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 25% 75%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0032C4-92415-32
Crawlspace Center Sample Location #2-C4-C5/18" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 25% 75%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0033C4-92415-33
Crawlspace West Sample Location #3-C4-C5/18" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 30% 70%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0034C4-92415-34
Crawlspace East Sample Location #1-C4-C5/12" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 30% 70%PLM White None Detected
Test Report:EPAMultiTests-7.32.2.D Printed: 10/09/2015 06:31PM Page 5 of 7
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041529583
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0035C4-92415-35
Crawlspace Center Sample Location #2-C4-C5/12" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 30% 70%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0036C4-92415-36
Crawlspace West Sample Location #3-C4-C5/12" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 30% 70%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0037C4-92415-37
Crawlspace East Sample Location #1-C4-C5/9" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 30% 70%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0038C4-92415-38
Crawlspace Center Sample Location #2-C4-C5/9" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 30% 70%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0039C4-92415-39
Crawlspace West Sample Location #3-C4-C5/9" MAG Pipe Insulation
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 30% 70%PLM White None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0040C4-92415-40-Pipe Wrap
Crawlspace- C4-C5/Fabric Pipe Wrap
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 65% 35%PLM Brown None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0040AC4-92415-40-Mastic
Crawlspace- C4-C5/Fabric Pipe Wrap
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 0% 100%PLM Black None Detected
Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0041C4-92415-41
Crawlspace- C4-C5/Fabric Pipe Wrap
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 70% 30%PLM Brown None Detected
Test Report:EPAMultiTests-7.32.2.D Printed: 10/09/2015 06:31PM Page 6 of 7
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
VAMD78
041529583
613-C50025
Asbestos Survey
EMSL Order ID:
Customer ID:
Customer PO:
Project ID:
Summary Test Report for Asbestos Analysis of Bulk Material via EPA 600/R-93/116 Method via
Polarized Light Microscopy Client Sample ID:
Sample Description:
Lab Sample ID: 041529583-0042C4-92415-42
Crawlspace- C4-C5/Fabric Pipe Wrap
DateTEST Non-Fibrous Asbestos CommentColor Fibrous
Non-AsbestosAnalyzed
10/08/2015 70% 30%PLM Brown None Detected
Analyst(s):
TEM Grav. Reduction (24)Chris Little
PLM (39)Kelly Mulholland
PLM (5)Seri Smith
Benjamin Ellis, Laboratory Manager or Other Approved Signatory
Reviewed and approved by:
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. This test report must not be used to claim product endorsement by NVLAP or any agency of the U.S.
Government. EMSL bears no responsibility for sample collection activities or analytical method limitations. The laboratory is not responsible for the accuracy of results when requested to physically separate and analyze layered samples. PLM alone is not consistently reliable in detecting asbestos in floor coverings and similar NOBs
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA-LAP, LLC-IHLAP Lab 100194, NYS ELAP
10872, NJ DEP 03036
Initial report from: 10/09/201518:31:48
Test Report:EPAMultiTests-7.32.2.D Printed: 10/09/2015 06:31PM Page 7 of 7
OrderID: 041529583
APPENDIX B
SAMPLING LOG
Building #:
Date: 9/24/2015
HA# Sample #
Lab initials/Chain of Custody #
Sample location Material Description
General Material
Category or substrate Notes
Bldg # Floor Wing Space # Location of Sample Asb. Type Asb. Content
Gray Leveling Compound
Leveling Compound NAD NAD
38 Black Mastic Mastic Chrysotile <0.1% Via TEM
3 C4‐92415‐2 41529583 C4 1st C4 C4 Corridor Center Under Radiator
Tan Sheet Flooring Mastic
Sheet Flooring Mastic NAD NAD (Via TEM) Via TEM
1 C4‐92415‐3 41529583 C4 1st C4 C4 Corridor Center Under Radiator
White Vinyl Sheet Flooring Sheet Flooring NAD NAD (Via TEM)
2 C4‐92415‐4 41529583 C4 1st C4 C4 Corridor Center Under Radiator
Blue Vinyl Sheet Flooring Sheet Flooring NAD NAD (Via TEM)
8 C4‐92415‐5 41529583 C4 1st C4 C4 Corridor North Wall
Window White Window
Glazing Window Glazing Chrysotile 3%
6 C4‐92415‐6 41529583 C4 1st C4 C4 Corridor South Wall Drywall Caulk Drywall Caulk Chrysotile 2% Via TEM
18 C4‐92415‐7 41529583 C4 1st C4 C4 Corridor East Wall
Above Doorway Red Fire Stop Fire Stop NAD NAD (Via TEM)
11 C4‐92415‐8 41529583 C4 1st C4 C4 Corridor East Wall Dividing C2 Corridor Interior Door Caulk Door Caulk Chrysotile <0.37%
5 C4‐92415‐9 41529583 C4 1st C3 C3 Corridor North Wall White Joint Compound
Join Compound (Drywall) NAD NAD Via TEM
5 C4‐92415‐10 41529583 C4 1st C9 C9 Corridor South
Ceiling White Joint Compound
Join Compound (Drywall) NAD NAD
19 C4‐92415‐11 41529583 C4 1st C9 C9 Corridor North Wall White Fire Stop Fire Stop NAD NAD (Via TEM)
16 C4‐92415‐12 41529583 C4 1st C9 C9 Corridor West Wall
Floor Purple Vinyl Sheet
Flooing Sheet Flooring NAD NAD (Via TEM)
17 C4‐92415‐13 41529583 C4 1st C9 C9 Corridor West Wall
Floor Yellow Sheet
Flooring Mastic Sheet Flooring
Mastic Chrysotile 5%
26 C4‐92415‐14 41529583 C4 1st C9 C9 Corridor West Wall by Sliding Door Off‐White Radiator
Caulk Radiator Caulk NAD NAD (Via TEM)
25 C4‐92415‐15 41529583 C4 1st Exterior Exterior Sliding Door in
C9 Corridor Black Exterior Door
Caulk Door Caulk NAD NAD (Via TEM)
22 C4‐92415‐16 41529583 C4 1st C13 C13 Corridor Under South Wall Radiator
Brown Mastic (Sublayer) Mastic NAD NAD (Via TEM)
C4 C4 Corridor Center Under RadiatorC4‐92415‐1 41529583 C4 1st
Lab Results
Sampling Log Sheet BEC Inspector: Derrick Klein C400
20 C4‐92415‐17 41529583 C4 1st C13 C13 Corridor Under South Wall Radiator
Black Vinyl Sheet Flooring Sheet Flooring NAD NAD (Via TEM)
21 C4‐92415‐18 41529583 C4 1st C13
C13 Corridor Under East Hallway Sprinkler Closet
Threshold White Leveling Compound
Leveling Compound NAD NAD
7 C4‐92415‐19 41529583 C4 1st C13 C13 Corridor South Wall Window East Corridor
White Interior Window Caulk Window Caulk NAD NAD (Via TEM)
24 C4‐92415‐20 41529583 C4 1st Exterior
North Hallway Exterior Door at Center of C13
Corridor Red Exterior Door
Caulk Door Caulk NAD NAD (Via TEM)
23 C4‐92415‐21 41529583 C4 1st Exterior
North Exterior Wall Metal Baseboard Flashing Caulk
White Masonry Seam Sealant Seam Sealant NAD NAD (Via TEM)
15 C4‐92415‐22 41529583 C4 1st C6 C6 Corridor South Wall Black Baseboard Baseboard NAD NAD (Via TEM)
14 C4‐92415‐23 41529583 C4 1st C6 C6 Corridor Above 12"x
12" Ceiling Tile Brown Mastic Glue
Dots ACT Mastic NAD NAD (Via TEM)
27 C4‐92415‐24 41529583 C4 1st Exterior North Exterior Door in
C6 Corridor White Exterior Door
Caulk Door Caulk NAD NAD (Via TEM)
28 C4‐92415‐25 41529583 C4 1st Exterior North Exterio Crawl
Space Hatch C6 Corridor
Red Exterior Masonry Seam
Sealant Seam Sealant NAD NAD (Via TEM)
10 C4‐92415‐26 41529583 C4 1st Exterior North Exterior Wall Siding C4 Corridor White Siding Caulk Siding Caulk NAD NAD (Via TEM)
29 C4‐92415‐27 41529583 C4 Crawl Space Exterior Crawl Space Pipe White Pipe Mastic Pipe Mastic NAD NAD (Via TEM)
30 C4‐92415‐28 41529583 C4 Crawl Space Exterior Crawl Space Pipe
Off‐White Pipe Cap Mastic
Pipe Cap Mastic NAD NAD (Via TEM)
32 C4‐92415‐29 41529583 C4 Crawl Space Exterior Crawl Space Pipe
Brown Mastic Glue Dots
Mastic Glue Dots NAD NAD (Via TEM)
31 C4‐92415‐30 41529583 C4 Crawl Space Exterior Crawl Space Pipe Fabric Pipe Wrap Pipe Wrap NAD NAD
33 C4‐92415‐31 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #1
18" MAG Pipe Insulation Pipe Insulation NAD NAD
33 C4‐92415‐32 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #2
18" MAG Pipe Insulation Pipe Insulation NAD NAD
33 C4‐92415‐33 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #3
18" MAG Pipe Insulation Pipe Insulation NAD NAD
34 C4‐92415‐34 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #1
12" MAG Pipe Insulation Pipe Insulation NAD NAD
34 C4‐92415‐35 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #2
12" MAG Pipe Insulation Pipe Insulation NAD NAD
34 C4‐92415‐36 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #3
12" MAG Pipe Insulation Pipe Insulation NAD NAD
35 C4‐92415‐37 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #1
9" MAG Pipe Insulation Pipe Insulation NAD NAD
35 C4‐92415‐38 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #2
9" MAG Pipe Insulation Pipe Insulation NAD NAD
35 C4‐92415‐39 41529583 C4 Crawl Space Exterior
Crawl Space East Sample Location #3
9" MAG Pipe Insulation Pipe Insulation NAD NAD
36 Fabric Pipe Wrap Pipe Wrap NAD NAD
Associated Black
Mastic Black Mastic NAD NAD
36 C4‐92415‐41 41529583 C4 Crawl Space Exterior Crawl Space Pipe Fabric Pipe Wrap Pipe Wrap NAD NAD
36 C4‐92415‐42 41529583 C4 Crawl Space Exterior Crawl Space Pipe Fabric Pipe Wrap Pipe Wrap NAD NAD
1 12108C401 217826 C4 1st C4 C4 Corridor. Along north wall White linoleum floor sheeting Sheet Flooring NAD NAD
2 12108C402 217826 C4 1st C4 C4 Corridor. Along south wall Blue linoleum floor sheeting Sheet Flooring NAD NAD
3 12108C403 217826 C4 1st C4 C4 Corridor. Along north wall Tan linoleum flooring mastic Sheet Flooring NAD NAD
3 12108C404 217826 C4 1st C4 C4 Corridor. Along south wall Tan linoleum flooring mastic Sheet Flooring NAD NAD
11 12108C405 217826 C4 1st C4 C4 Corridor. Along south wall Door frame caulk
(Interior) Door Caulk NAD NAD
4 12108C406 217826 C4 1st C4 C4 Corridor. Along north wall Drywall Drywall NAD NAD
5 12108C407 217826 C4 1st C4 C4 Corridor. Along ceiling.
Drywall joint compound
Joint Compund (Drywall) NAD NAD
6 12108C408 217826 C4 1st C4 C4 Corridor. Along south wall Wall caulk Wall caulk NAD NAD
6 12108C409 217826 C4 1st C4 C4 Corridor. Along north wall Wall caulk Wall caulk NAD NAD
4 12108C410 217826 C4 1st C4 C4 Corridor. Along ceiling Drywall Drywall NAD NAD
7 12108C411 217826 C4 1st C4 C4 Corridor. Along ceiling Drywall joint compound
Joint Compund (Drywall) NAD NAD
27 12108C412 217826 C4 1st C4 C4 Corridor. Along ceiling Drywall Drywall NAD NAD
28 12108C413 217826 C4 1st C4 C4 Corridor. Along south wall Drywall Drywall NAD NAD
10 12108C414 217826 C4 1st C4 C4 Corridor. Along south wall Window glazing Window Glazing NAD NAD
7 12108C415 217826 C4 1st C4 C4 Corridor. Along south wall Interior window caulk Window Caulk NAD NAD
C441529583C4‐92415‐40 Crawl Space PipeExterior Crawl Space
27 12108C416 217826 C4 1st C4 C4 Corridor. Exterior south wall Exterior window caulk Window Caulk NAD NAD
28 12108C417 217826 C4 1st C4 C4 Corridor. Exterior, along south wall
Exterior crawl space hatch Caulk
Crawl Space Hatch Caulk NAD NAD
10 12108C418 217826 C4 1st C4 C4 Corridor. Exterior, along south wall Exterior wall caulk Wall Caulk NAD NAD
7 12108C419 217826 C4 1st C4 C4 Corridor. Along north wall Interior window caulk Window Caulk NAD NAD
8 12108C420 217826 C4 1st C4 C4 Corridor. Along north wall Interior window glazing Window Glazing NAD NAD
20 12108C421 217826 C4 1st C4 C4 North. At west wall, near room 3 Black sheet flooring Sheet Flooring NAD NAD
3 12108C422 217826 C4 1st C4 C4 North. At west wall Tan sheet flooring mastic Sheet Flooring
Mastic NAD NAD
N/A 12108C423 217826 C4 1st C4 C4 North. At west wall Transite wall panel Transite wall panel Chrysotile 15% Removed
N/A 12108C424 217826 C4 1st C4 C4. At west wall, near room 5 Transite wall panel Transite wall panel Chrysotile 15% Removed
20 12108C425 217826 C4 1st C4 C4. At west wall, near room 5 Black sheet flooring Sheet Flooring NAD NAD
N/A 12108C426 217826 C4 1st C4 C4. At west wall, near room 5 Tan sheet flooring Sheet Flooring NAD NAD Removed
29 12108C427 217826 C4 1st C4 C4 North. West wall, near room 5 White pipe seam sealant Pipe Seam Sealant NAD NAD
4 12108C428 217826 C4 1st C4 C4 North. West wall, near room 5 Drywall Drywall NAD NAD
5 12108C429 217826 C4 1st C4 C4 North. West wall, near room 5 Drywall joint compound
Joint Compund (Drywall) NAD NAD
6 12108C430 217826 C4 1st C4 C4 North. West wall, near room 5 Wall caulk Wall Caulk Chrysotile 2%
11 12108C431 217826 C4 1st C4 C4 North. At north wall Interior door caulk Door Caulk NAD NAD
27 12108C432 217826 C4 1st C4 C4 North. North exterior. 1st door Exterior door caulk Door Caulk NAD NAD
29 12108C433 217826 C4 1st C4 C4 North. At southeast corner White pipe seam sealant Pipe Seam Sealant Chrysotile 2%
4 12108C434 217826 C4 1st C4 C4 North. At south wall Drywall Drywall NAD NAD
5 12108C435 217826 C4 1st C4 C4 North. At south wall Drywall joint compound
Joint Compund (Drywall) NAD NAD
12108C436 217826 C4 1st C4 C4 North. At west wall Window caulk Window caulk Chrysotile <1%
8 12108C437 217826 C4 1st C4 C4 North. At west wall Window glazing Window glazing NAD NAD
1 12108C438 217826 C4 1st C4 C4 North. At north way threshold White sheet flooring Sheet Flooring NAD NAD
13 12108C439 217826 C4 1st C4 C4 North. At west, near room 5, 1st window Window caulk Window caulk NAD NAD
8 12108C440 217826 C4 1st C4 C4 North. At west, near room 5, 1st window Window glazing
Window glazing NAD NAD
13 12108C441 217826 C4 1st C4 C4 North. At ceiling above drywall ceiling
1’ x 1’ White ceiling tile Ceiling Tile NAD NAD
28 12108C442 217826 C4 1st C4 C4 Exterior. North Crawl space door caulk Door Caulk NAD NAD
23 12108C443 217826 C4 1st C4 C4 North. Exterior, north wall Soffit caulk Soffit caulk NAD NAD
28 12108C444 217826 C4 1st C4 C4 North. North wall closet 1’ x 1’ White ceiling tile Ceiling Tile NAD NAD
14 12108C445 217826 C4 1st C4 C4 North. North wall closet Brown mastic dots Ceiling Tile Mastic NAD NAD
22 12108C446 217826 C4 1st C4 C4 North. North wall closet at east wall
Brown baseboard mastic
Baseboard Mastic NAD NAD
N/A 12108C447 217826 C4 1st C4 C4 North. North wall closet Stone pattern linoleum Sheet Flooring Chrysotile 20% Removed
N/A 12108C448 217826 C4 1st C4 C4 North. North wall closet Linoleum mastic Flooring Mastic Chrysotile 2% Removed
28 12108C449 217826 C4 1st Exterior C4. North wall exterior Crawl space door caulk Door Caulk NAD NAD
23 12108C450 217826 C4 1st Exterior C4. North wall exterior Wall caulk (exterior) Wall caulk NAD NAD
APPENDIX C
BEC STAFF QUALIFICATIONS
| C4 Sampling Logsheet.pdf |
| Sampling Log |
File details come from the government source that posted it. Updated .