613-22-135_B500 PBC BID SET_CD Submission - Drawings.pdf
PDF 27 MB Posted
- Solicitation number
- 36C24525B0001
About this file
This file appears to be a set of architectural/engineering drawings for the renovation of Building 500 into a Patient Business Center at the Martinsburg VA Medical Center. The drawings are technical construction documents intended for bidding purposes (marked as "BID SET") and are related to VA project number 613-22-135. The drawings provide detailed specifications and plans for contractors to use in developing their bids for the renovation work to be performed under solicitation 36C24525B0001 for the Department of Veterans Affairs Veterans Health Administration VISN 5.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
MMKJ
Building 500 Business Center
BID DOCUMENTS SUBMISSION
COVER SHEET
GI100
-2
-1
G I1
.p d f
Department of Veterans Affairs
Building 500 Business Center 510 Butler Avenue
Martinsburg WV, 25405
510 Butler Avenue Martinsburg WV, 25405
BID DOCUMENTS SUBMISSION
GENERAL INFORMATION
GI100 COVER SHEET
GI200 SYMBOLS, ABBREVIATION
GI300 GENERAL NOTES
GI301 TYPICAL MOUNTING HEIGHTS
GENERAL CONTRACT
GC100 EXISTING CONDITIONS PLAN
GC200 ASBESTOS PLAN
LS100 PARTIAL FIRST FLOOR LIFE SAFETY PLAN AND CODE INFO
ARCHITECTURAL DEMOLITION
AD101 DEMOLITION FLOOR PLAN
AD102 DEMOLITION RCP PLAN
ARCHITECTURAL ELEMENTS
AE100 FLOOR PLANS
AE300 DOOR SCHEDULE / HSJ DETAILS
AE301 FINISH SCHEDULE
AE302 WALL TYPES
AE303 SIGN TYPES / WALL PROTECTION
AE700 REFLECTED CEILING PLANS / DETAILS
AE900 CABINET DETAILS
EQUIPMENT (HOSPITAL)
QH100 EQUIPMENT PLANS / SCHEDULES
FIRE PROTECTION
FX001 FIRE PROTECTION AND FIRE ALARM GENERAL NOTES AND LEGEND
FX101 FIRE PROTECTION AND FIRE ALARM PLAN
MECHANICAL
M001 MECHANICAL GENERAL NOTES & LEGEND
MD111 MECHANICAL DUCT DEMOLITION FLOOR PLAN
MD112 MECHANICAL DUCT DEMOLITION PLENUM PLAN
MD121 MECHANICAL PIPING DEMOLITION FLOOR PLAN
M111 MECHANICAL DUCTWORK PLAN
M112 MECHANICAL DUCTWORK PLENUM PLAN
M121 MECHANICAL PIPING PLAN
M501 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
PLUMBING
P001 PLUMBING COVER SHEET
PD100 PLUMBING DEMOLITION PLAN
P100 PLUMBING NEW WORK PLAN
ELECTRICAL
E001 SYMBOLS LEGEND, ABBREVIATIONS AND NOTES
ED101 ELECTRICAL DEMOLITION PLAN
E101 OVERALL ELECTRICAL PLAN
E102 LIGHTING PLAN
E103 LIGHTING CALCULATIONS
E104 ELECTRICAL PLAN
E600 ELETRICAL SCHEDULES
E601 ELECTRICAL DETAILS
LOCATION MAP DRAWING LIST PROJECT DIRECTORY
Medical Center Director
Director of Facility Management Service
Medical Director
Project COR
Project CO
Infection Control
Safety Officer
CONTRACTING OFFICER REPRESENTATIVE (COR)
Muhammadali Sami 510 Butler Avenue Martinsburg, WV 25405
PHONE: (202) 285-1511
Muhammadali.Sami@va.gov
CONTRACTING OFFICER (CO)
Department of Veterans Affairs | Contracting 510 Butler Avenue Martinsburg, WV 25405
PHONE: (865) 617-3051
jerry.jones@va.gov
APPROVALS
WOOD
ALUMINUM
STEEL
EARTH
CONCRETE MASONRY UNITS
RIGID INSULATION
CONCRETE
EXISTING CONSTRUCTION
TO REMAIN
EXISTING CONSTRUCTION
TO BE REMOVED
BRICK
WOOD-FINISHED
WOOD ROUGH
PLYWOOD
GYPSUM - PLASTER
ACOUSTIC TILE
CAST STONE
ALL METALS - SMALL SCALE
GLASS - LARGE SCALE
BATT INSULATION
CERAMIC TILE
CARPET
GRAVEL
CENTER LINE
DETAIL INDICATOR
DETAIL INDICATIOR
DIMENSION LINE
DRAWING BLOCK TITLE, TYPICAL
ELEVATION INDICATOR, EXTERIOR
ELEVATION INDICATOR, INTERIOR, MULTIPLE VIEW
ELEVATION INDICATOR, INTERIOR, SINGLE VIEW
SECTION INDICATOR
TYPICAL DETAIL INDICATOR
COLUMN GRID
KEYNOTE
NORTH ARROW
A
DETAIL NUMBER
SHEET WHERE
DRAWN
XXxxx
XXxxx
X
DRAWING TITLE
SCALE: 1 1/2" = 1'-0"
1 1/2"
XXxxx
XXxxx
XXxxx
REVISION
REVISION CLOUD
NORTH
BREAK LINE
DEMOLITION KEYNOTE
A
XXxxx
D
BC
COLUMN NUMBER
COLUMN LETTER
XXxxx
ELEVATION NUMBER
SHEET WHERE
DRAWN
SECTION NUMBER
SHEET WHERE
DRAWN
ELEVATION NUMBER
SHEET WHERE
DRAWN
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL NUMBER
SHEET WHERE DRAWN
SHEET WHERE
DRAWN
ELEVATION NUMBER
DOOR / BORROWED LIGHT TAG
FURNITURE, FIXTURE, & EQUIPMENT TAG
WALL/PARTITION TAG
x'-x" VERTICAL HEIGHT INDICATOR
ROOM NAME
3333333333
A3
ROOM NUMBER
ROOM AREA
PROGRAM AREA
D1
FLR FLOOR
FLUOR FLUORESCENT
FM FLOOR MATS & FRAMES
FO __ FACE OF __
FOC FACE OF CONCRETE
FOS FACE OF STUD
FOW FACE OF WALL
FP FOLDING PANEL PARTITION
FPRF FIREPROOF(ING)
FR FIRE RATING, FRAME
FRMG FRAMING
FS FULL SIZE, FEATURE STRIPS
FT FOOT OR FEET, FLOOR TILE MOSAIC
FTCT CERAMIC MOSAIC TILE
FTG FOOTING
FUR FURRING
FUT FUTURE
GA GAUGE
GAL GALLON
GALV GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR
GCMU GLAZED FACE CMU
GD GUARD
GL GLASS
GND GROUND
GR GRADE
GT GRANITE
GUMU GLASS MASONRY UNIT
GWB GYPSUM WALLBOARD
GYP BD GYPSUM WALLBOARD
HB HOSE BIBB
HC HOLLOW CORE
HD HEAD
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HNDRL HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HP HIGH POINT
HPDL PLASTIC LAMINATE
HR HANDRAIL, HOUR
HSPL HIGH STRENGTH PLASTER
HT HEIGHT
HVAC HEATING, VENTILATION, AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE DIAMETER /
DIMENSION
IN INCH
INCL INCLUDE(D)
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
JST JOIST
JT JOINT
KC PLASTER KEENE CEMENT
KP KICK PLATE
KO KNOCKOUT
L LENGTH
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LG LONG
LH LEFT HAND
LIN LINEAR
LIQ LIQUID
LKR LOCKER
LL LEAD LINED
LLV LONG LEG VERTICAL
LM LATEX MASTIC FLOORING
LMC LINEAR METAL CEILING
LP LOW POINT
LRG LARGE
LT LIGHT
LT WT LIGHTWEIGHT
LVR LOUVER
LWC LINEAR WOOD CEILING
M MORTAR
MAS MASONRY
MAT MATERIAL
MAX MAXIMUM
MB MARBLE
MC MULTI-COLOR COATING
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MP MOP PLATE
MTD MOUNTED
MTL METAL
N NORTH
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NF NATURAL FINISH
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OFF OFFICE
OH OPPOSITE HAND, OVERHEAD
OPNG OPENING
OPP OPPOSITE
OZ OUNCE
P PAINT
PAV PAVING
PC PRECAST CONCRETE
PCT PORTLAND CEMENT TERRAZZO
PFW POLYPROPYLENE FABRIC WALLCOVERING
PL PLATE, PLASTER
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PMF PREMOLDED FILLER, PERFORATED METAL
FACING (TILE OR PANELS)
PPT PORCELAIN PAVER TILE
PR PAIR
PT POINT
PTN PARTITION
PVT PAVER TILE
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RAD RADIUS
RB RESILIENT BASE, RUBBER BASE
RCP REFLECTED CEILING PLAN,
RADIANT CEILING PANEL SYSTEM
RD ROOF DRAIN
REF REFERENCE
REFR REFRIGERATOR
REQ'D REQUIRED
REV REVISION
RFI REQUEST FOR INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RL ROOF LEADER
RM ROOM
RO ROUGH OPENING
RST RESILIENT STAIR TREAD
RT RUBBER TILE FLOORING
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SC SOLID CORE, HIGH GLAZED COATING,
STRUCTURAL CLAY
SCHED SCHEDULE
SCT FACING TILE
SDG SUSPENSION DECORATIVE GRIDS
SECT SECTION
SF SQUARE FEET, STONE FLOORING
SFTU GLAZED STRUCTURAL FACING TILE
SH SPRINKLER HEAD
SHT SHEET
SIM SIMILAR
SLG SPANDREL GLASS
SM SMOKE
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SS STAINLESS STEEL
ST STAIN
STA STATION
STD STANDARD
STO STORAGE
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
T&G TONGUE AND GROOVE
TEL TELEPHONE
TEMP TEMPERED
TGC TEXTURED GYPSUM CEILING PANEL
THK THICK
TIL TECHNICAL INFORMATION LIBRARY (VA)
TMC TEXTURED METAL CEILING PANEL
TOC TOP OF CONCRETE
TOP TOP OF PAVEMENT
TOS TOP OF STEEL
TOW TOP OF WALL
TST THIN SET TERRAZZO
TT TERRAZZO TILE
TV TELEVISION
TYP TYPICAL
UNFIN UNFINISHED
UON UNLESS OTHERWISE NOTED
VB VAPOR BARRIER, VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VP VENEER PLASTER
VSF VINYL SHEET FLOORING
VTR VENT THRU ROOF
W WEST, VINYL COATED FABRIC
WALLCOVERING
W/ WITH
WB WALL BORDER
WD WOOD
WF FABRIC WALLCOVERING
W/O WITHOUT
WP WATERPROOF
WSF VINYL SHEET FLOORING (WELDED SEAMS)
WT WEIGHT
WWF WELDED WIRE FRAME
NOTES
1. ALL ABBREVIATIONS SHOWN MAY NOT BE USED ON THIS PROJECT.
2. CERTAIN COMMON ABBREVIATIONS MAY NOT BE SHOWN.
3. TEXT IN BOLD DENOTES ABBREVIATIONS FROM THE TIL.
L
& AND
@ AT
C CENTERLINE
# NUMBER, POUND
AA ANODIZED ALUMINUM, NATURAL FINISH
AAC ANODIZED ALUMINUM, COLORED
AB ANCHOR BOLT
ABA ARCHITECTURAL BARRIERS ACT
ABV ABOVE
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJUSTABLE
AF ACCESS FLOORING
AFF ABOVE FINISHED FLOOR
AFP ACCORDION FOLDING PARTITION
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
ALT ALTERNATE
ALUM ALUMINUM
AMP ACOUSTICAL METAL PLAN CEILING
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AT ACOUSTICAL CEILING TILE
AT (SP) ACOUSTICAL CEILING, SPECIAL FACED
AUTO AUTOMATIC
AVG AVERAGE
AWF ACOUSTICAL WALLCOVERING
AWP ACOUSTICAL WALL PANEL
AWT ACOUSTICAL WALL TREATMENT
BD BOARD
BE BAKED ON ENAMEL
BEL BELOW
BF BRICK FLOORING
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BP BRICK PAVING
BR BUMPER RAIL, BRICK FACE
BRG BEARING
BRK BRICK
C, CONC CONCRETE
CAB CABINET
CAF CARPET ATHLETIC FLOORING
CB CATCH BASIN
CCT CUBICLE CURTAIN TRACK
CEM CEMENT
CG CORNER GUARD
CGFB CERAMIC GLAZED FACING BRICK
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CLOSET
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CONTRACTING OFFICER
COL COLUMN
CONF CONFERENCE
CONT CONTINUOUS
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CARPET
CPT CARPET MODULE TILE
CT CERAMIC TILE
CU CUBIC
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DOOR OPENING
DOZ DOZEN
DP DAMPPROOFING
DR DOOR
DS MB DIVIDER STRIPS, MARBLE
DWG DRAWING
DWGS DRAWINGS
DWR DRAWER
E EAST, EXISTING
EA EXHAUST AIR, EACH
EC EPOXY COATING
EFS EXTERIOR FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATION
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
ERF EPOXY RESIN FLOORING
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EXIST EXISTING
EXP EXPANSION, EXPOSED DIVIDER STRIPS
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK
FC FLUOROCARBON
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FACE
FG FOOT GRILLE
FHC FIRE HOSE CABINET
FIN FINISH
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
AuthorChecker
Building 500 Business Center
BID DOCUMENTS SUBMISSION
SYMBOLS, ABBREVIATION
GI200
-2
-1
G I2
.p d f
510 Butler Avenue Martinsburg WV, 25405
SYMBOLS OF MATERIALSDRAWING SYMBOLSARCHITECTURAL ABBREVIATIONS
1. HOSPITAL STAFF SHALL ENSURE THE REMOVAL OF ANY MEDICAL WASTE, INCLUDING SHARPS CONTAINERS, FROM AREAS TO
BE RENOVATED, PRIOR TO THE START OF THE PROJECT.
2. INFECTION CONTROL SHALL BE NOTIFIED BY FACILITIES MANAGEMENT STAFF IMMEDIATELY IF UNEXPECTED MEDICAL WASTE
IS ENCOUNTERED.
IN STRIVING TO PROVIDE A HEALTHY AND SAFE ENVIRONMENT AT VA FACILITIES, VHA IS IMPLEMENTING A SMOKE-FREE POLICY FOR ALL VHA HEALTH CARE FACILITIES AND PROPERTY ASSIGNED TO VHA THAT IS UNDER THE CHARGE AND CONTROL OF VA. THE POLICY APPLIES TO CIGARETTES, CIGARS, PIPES OR ANY OTHER COMBUSTION OF TOBACCO, INCLUDING BUT NOT LIMITED TO
ELECTRONIC OR E-CIGARETTES, VAPE PENS OR E-CIGARS.
UNDER VHA DIRECTIVE 1085, ALL VHA HEALTH CARE FACILITIES WILL BE SMOKE-FREE FOR PATIENTS, VISITORS, CONTRACTORS, VOLUNTEERS AND VENDORS EFFECTIVE OCTOBER 1, 2019.
1. ITEMS AND CONDITIONS NOTED, DETAILED, OR OTHERWISE IDENTIFIED ON DRAWINGS ARE APPLICABLE AND BINDING TO SIMILAR CONDITIONS ON ALL DRAWINGS. FOR CONDITIONS NOT NOTED OR NOT DETAILED, PROVIDE MATERIALS OF EQUAL QUALITY AND PERFORMANCE TO OTHER SIMILAR CONDITIONS
ON THE JOB.
2. SECTIONS SHOWN ARE INTENDED TO SHOW THE SPECIFIC CONSTRUCTION WHERE INDEXED AS WELL AS ESTABLISH THE GENERAL CONSTRUCTION DETAILS FOR SECTIONS THROUGHOUT THE PROJECT. ANY SPECIFIC QUESTIONS CONCERNING CONSTRUCTION NOT ADEQUATELY COVERED BY THE ABOVE SHOULD
BE DIRECTED TO THE CONTRACTING OFFICER DURING THE BID PERIOD.
3. ALL CONSTRUCTION IS TO BE NEW AND FURNISHED AND INSTALLED BY THE CONTRACTOR, UNLESS NOTED OTHERWISE.
4. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR NOTES PERTAINING TO THEIR PARTICULAR DISCIPLINES. COORDINATE THE WORK OF ALL TRADES AND REPORT TO THE CONTRACTING OFFICER ANY PERCEIVED DISCREPANCIES. CONTRACTOR SHALL BE RESPONSIBLE FOR ESTABLISHING SEQUENCES OF CONSTRUCTION AND MEANS AND METHODS FOR HOW TO PERFORM THE WORK REQUIRED IN THE CONTRACT DOCUMENTS.
5. CONTRACTOR SHALL CAREFULLY REVIEW ALL EXISTING CONDITIONS AND DETERMINE THE MOST FEASIBLE SEQUENCE FOR PERFORMING THE NEW WORK
SOLE AS TO AVOID CONFLICTS IN THE FIELD.
6. ANY AREAS OR SPACES NOT CLEARLY DEFINED OR INDICATED BY NOTES SHALL BE OF SAME MATERIAL AND FINISH AS AREAS OF SIMILAR USE OR FUNCTION
ELSEWHERE IN THE BUILDING.
7. WALL AND CEILING FINISHES SHALL INCLUDE PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, PILASTERS AND OTHER SIMILAR ITEMS.
8. ALL APPURTENANCES BUILT INTO OR THROUGH WALLS, INCLUDING DOORS, WINDOWS, DUCTS, FRAMES, LOUVERS, GRILLES, MECHANICAL WORK, ETC., SHALL FIT SNUGLY AND BE THOROUGHLY SEALED AROUND PERIMETERS. INSTALL FIRE SEALANT AROUND ALL PENETRATIONS THROUGH FLOORS, FIRE RATED WALLS AND SMOKE PARTITIONS IN ACCORDANCE WITH A UL LISTED ASSEMBLY. WORK AT EXTERIOR WALLS SHALL BE FLASHED OR OTHERWISE WATERPROOF
SEALED.
9. FIELD CHECK ROUGH AND/OR FINISHED DIMENSIONS FOR ACCURATE FITTING OF CABINETS, COUNTERS, STOREFRONT, DOORS, FRAMES, FIXTURES, MILLWORK AND ALL OTHER INSTALLATIONS PRIOR TO SHOP OR FACTORY FABRICATION. PROVIDE AND INSTALL NECESSARY FILLER STRIPS, SCRIBE STRIPS, BASES, CLOSURES, FINISHES AND TRIM TO COMPLETE SUCH INSTALLATIONS. DIMENSIONS OF SUCH INSTALLATIONS SHALL BE CONSIDERED "NOMINAL".
CONTRACTORS SHALL ACCOUNT FOR ALL MANUFACTURER'S REQUIRED TOLERANCES, CLEARANCES AND SHIM SPACE TO ENSURE PROPER INSTALLATION OF
THE NEW WORK.
10. SEE EQUIPMENT PLANS AND FLOOR PLANS FOR CASEWORK, CABINETS, MILLWORK AND OTHER BUILT-IN ITEMS. COORDINATE WITH MEP DRAWINGS FOR
SINKS, OUTLETS, AND OTHER ITEMS TO BE BUILT INTO SUCH ITEMS.
11. IF A DISCREPANCY APPEARS TO EXIST BETWEEN DRAWINGS AND/OR SPECIFICATIONS, THE MORE STRINGENT (TYPICALLY THE MORE COSTLY) REQUIREMENT SHALL APPLY. ITEMS DESCRIBED ON DRAWINGS, BUT NOT SPECIFIED, SHALL BE PROVIDED. CONTRACTOR SHALL BE RESPONSIBLE TO SUBMIT AN RFI TO
SEEK CLARIFICATION OF ANY PERCEIVED DISCREPANCY DURING BID PHASE.
12. WRITTEN INFORMATION ON DRAWINGS TAKES PRECEDENT OVER DRAWING LINES.
13. IN THE ABSENCE OF A WRITTEN DIMENSION, OR IN CASE OF DOUBT AS TO THE PROPER MEASUREMENT, CONSULT CONTRACTING OFFICER . DO NOT SCALE DRAWINGS. ASSUMPTIONS MADE, OR ACTIONS TAKEN, BASED ON SCALED DIMENSIONS SHALL BE AT THE CONTRACTOR'S RISK AND ANY RESULTING CORRECTIONS SHALL BE PERFORMED BY CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
14. EACH CONTRACTOR OR SUB-CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH THE WORK OF OTHER TRADES SHOWN THROUGHOUT THE COMPLETE SET OF CONTRACT DOCUMENTS. CHANGES RESULTING FROM A CONTRACTOR OR SUB-CONTRACTOR'S FAILURE TO OBTAIN AND REVIEW A COMPLETE SET OF CONTRACT DOCUMENTS SHALL BE CORRECTED AT NO ADDITIONAL COST TO THE GOVERNMENT.
15. AT ALL CHANGES IN FLOOR FINISHES, PROVIDE AND INSTALL AN APPROPRIATE TRANSITION STRIP AS SHOWN ON THE DRAWINGS.
16. CONSULT HVAC AND ELECTRICAL DRAWINGS FOR LOCATIONS AND DESCRIPTIONS OF ACCESS PANELS, LOUVER OPENINGS, VENTILATORS, GRILLES, VALVE CABINETS, FIRE DAMPERS OR OTHER APPURTENANCES AFFECTING WALLS, CEILINGS OR FLOORS AND PROVIDE NECESSARY LINTELS, SUPPORT OR
ANCHORING. IN COORDINATION WITH SHOP DRAWINGS.
17. ELECTRIC SWITCHES, OUTLETS, THERMOSTATS, CONTROLS, CLOCKS, SPEAKERS, OR OTHER WALL-MOUNTED ACCESSORIES SHALL BE INSTALLED IN LOCATIONS WHICH ARE UNOBSTRUCTED BY CABINETS, COUNTERS, RACKS, MARKER AND TACKBOARDS, FIXTURES, SHELVING OR OTHER FURNISHING OR EQUIPMENT DESIGNATED FOR SPACES SHOWN ON DRAWINGS. WALL MOUNTED ITEMS ARE NOT TO BE INSTALLED ON, THROUGH, OR INTO, ANY EQUIPMENT
OTHER THAN WALLS, UNLESS SPECIFICALLY NOTED OTHERWISE.
18. ELECTRICAL OUTLETS, CLOCKS, P.A. SPEAKERS, PULL STATIONS, EXIT SIGNS, OR OTHER DEVICES SHOWN DIAGRAMMATICALLY ON THE ARCHITECTURAL DRAWINGS SERVE TO ALERT CONTRACTORS OF THE PRESENCE OF SUCH DEVICES. CONSULT THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION AND ADVISE CONTRACTING OFFICER OF ANY PERCEIVED DISCREPANCY BETWEEN ARCHITECTURAL AND ELECTRICAL DRAWINGS REGARDING LOCATION OR TYPE
OF DEVICES SHOWN PRIOR TO PREPARING SUBMITTALS.
19. ELECTRIC SWITCHES, THERMOSTATS OR OTHER ELECTRONIC CONTROLS IN THE SAME VICINITY SHALL BE MOUNTED AT THE SAME HEIGHT FROM FLOOR
(UNLESS NOTED OTHERWISE) IN A UNIFORM, ORDERLY FASHION.
20. SUBMITTAL REVIEW - THE CONTRACT DOCUMENTS PROVIDE SIZES, DIMENSIONS, PRODUCT REQUIREMENTS, ETC. CONTRACTOR SHALL VERIFY THAT SUBMITTALS ARE COORDINATED WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS PRIOR TO SUBMISSION. A/E REVIEW OF SUBMITTALS IS NOT FOR THE PURPOSE OF DETERMINING THAT SIZES, DIMENSIONS, ETC MATCH WHAT HAS ALREADY BEEN PROVIDED IN THE CONTRACT DOCUMENTS. ALL DEVIATIONS FROM WHAT IS SHOWN ON THE CONTRACT DOCUMENTS SHALL BE CLOUDED ON THE SUBMITTAL OR OTHERWISE CLEARLY BROUGHT TO THE ATTENTION OF THE REVIEWER. FAILURE TO CLEARLY BRING ANY DEVIATION(S) TO THE ATTENTION OF THE REVIEWER SHALL BE UNDERSTOOD BY ALL PARTIES THAT WHAT IS SHOWN IN THE SUBMITTAL COMPLIES WITH THE CONTRACT DOCUMENTS REGARDLESS OF WHETHER OR NOT THE REVIEWER DISCOVERS THE DEVIATION.
CHANGES RESULTING FROM THE CONTRACTOR'S FAILURE TO CLEARLY IDENTIFY DEVIATIONS IN SUBMITTALS SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY AND SHALL BE CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
21. CONTRACTORS SHALL CAREFULLY REVIEW EXISTING FIELD CONDITIONS AND COORDINATE ALL QUANTITIES, DIMENSIONS, AND TOLERANCES REQUIRED TO PERFORM THE WORK SHOWN ON THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR DETERMINING INFORMATION THAT PERTAINS SOLELY TO FABRICATION PROCESSES, INSTALLATION TECHNIQUES (MEANS AND METHODS), AND SEQUENCING OF THE WORK TO MEET THE REQUIREMENTS OF THE PROJECT SCHEDULE. EACH SUBCONTRACTOR SHALL COORDINATE WITH THE GENERAL CONTRACTOR PRIOR TO BEGINNING THEIR PORTION OF THE WORK.
ALL SUBMITTAL ARE TO BE APPROVED BY THE VA PRIOR TO START OF WORK.
22. CONTRACTOR SHALL, AT ALL TIMES, MAINTAIN THE INTEGRITY OF EXISTING SMOKE PARTITION WALLS, SMOKE BARRIER WALLS, AND FIRE RATED WALLS TO REMAIN. SEE LIFE SAFETY DRAWINGS AND ARCHITECTURAL DRAWINGS FOR THE LOCATION OF THESE WALLS. CONSULT COR AND LOCAL VA FIRE / SAFETY PERSONNEL FOR CONFIRMATION OF THESE WALLS PRIOR TO BEGINNING DEMOLITION. DAMAGE TO ANY EXISTING-TO-REMAIN SMOKE PARTITION WALLS, SMOKE BARRIER WALLS, OR FIRE RATED WALLS, INCLUDING DAMAGE FROM REMOVAL OF INTERSECTING WALLS, SHALL BE REPAIRED AT CONTRACTOR’S
EXPENSE.
23. PUBLIC EXITS SHALL REMAIN CLEAR AT ALL TIMES WHILE THE BUILDING IS OCCUPIED. NO STORAGE SHALL BE PERMITTED IN THE EXIT ACCESS. STORAGE WILL ONLY BE PERMITTED IN THE ENCLOSED CONSTRUCTION SITE, AND DESIGNATED SPACE WITH PRIOR APPROVAL OF THE VA.
24. PATCH ALL EXISTING AND NEW HOLES IN FLOORS, WALLS AND CEILINGS WITHIN THE PROJECT LIMITS. ENSURE THAT ALL EXISTING AND NEW PATCH WORK IS RATED TO THE LEVEL OF FLOORS, WALLS AND CEILINGS TO THE REQUIRED EXISTING CONDITION, PRIOR TO THE START OF NEW WORK.
25. UNLESS SPECIFIC DIMENSIONS ARE PROVIDED, MEP DRAWINGS ARE CONSIDERED "DIAGRAMMATIC". IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR(S) TO FIELD COORDINATE LOCATIONS, SEQUENCES, ETC FOR UNOBSTRUCTED INSTALLATION OF ITEMS THAT ARE SHOWN ON MEP DRAWINGS IN DIAGRAMMATIC FORM. COORDINATE ABOVE-CEILING WORK OF MEP TRADES TO THAT EACH TRADE LOCATES THEIR WORK AS TIGHT TO THE STRUCTURE / DECK ABOVE AS IS FEASIBLE. EACH SUCCESSIVE TRADE SHALL LOCATE THEIR WORK AS TIGHT TO THE TRADE BEFORE.
26. ALTHOUGH THE DRAWINGS AND SPECIFICATIONS ARE COMPLIMENTARY, SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. WHAT IS REQUIRED BY EITHER THE DRAWINGS OR SPECIFICATIONS SHALL BE INTERPRETED AS BEING REQUIRED AS PART OF THE SCOPE OF WORK FOR THIS PROJECT. ITEMS SPECIFIED, BUT NOT INDICATED ON THE DRAWINGS, SHALL BE PROVIDED. ITEMS SHOWN ON THE DRAWINGS, BUT NOT SPECIFIED, SHALL BE PROVIDED. ANY DISCREPANCIES BETWEEN THE CONTRACT DRAWINGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO SEEK CLARIFICATION PRIOR TO SUBMITTING A BID AMOUNT IF THERE SHOULD APPEAR TO BE A DISCREPANCY BETWEEN DRAWINGS AND/OR THE SPECIFICATIONS. OTHERWISE, THE MOST STRINGENT (TYPICALLY THE MOST EXPENSIVE) REQUIREMENT SHALL APPLY AT THE DISCRETION OF THE COR AT NO ADDITIONAL COST TO THE GOVERNMENT.
27. ABOVE-CEILING INTERSTITIAL COORDINATION – PRIOR TO PERFORMING ANY ABOVE-CEILING INTERSTITIAL WORK, CONTRACTOR, WORKING WITH ALL SUB- CONTRACTORS, SHALL CREATE DRAWINGS THAT SHOW COORDINATION OF ALL ABOVE-CEILING WORK ITEMS WITH EXISTING CONDITIONS AND PROPOSED CEILINGS. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE SEQUENCES OF INSTALLATION TO ENSURE THAT ABOVE-CEILING ITEMS CAN FIT ABOVE THE CEILING HEIGHTS INDICATED ON THE REFLECTED CEILING PLAN(S). CONTRACTOR SHALL BRING ALL PERCEIVED CONFLICTS TO THE ATTENTION OF THE ARCHITECT / ENGINEER FOR RESOLUTION PRIOR TO THE START OF THE WORK. CONFLICTS RESULTING FROM INACCURATE COORDINATION DRAWINGS AND / OR FAILURE TO IDENTIFY CONFLICTS PRIOR TO INSTALLATION OF THE WORK SHALL BE CORRECTED / ADJUSTED AT THE
CONTRACTOR’S EXPENSE AND SHALL RESULT IN NO ADDITIONAL COST TO THE GOVERNMENT.
1. THE WORK OF THIS CONTRACT MAY REQUIRE PARTIAL REMOVAL OR DISASSEMBLY OF EXISTING CEILINGS AND/OR WALLS FOR ACCESS TO SPACES WHERE NEW ITEMS ARE REQUIRED TO BE INSTALLED OR EXISTING ITEMS ARE REQUIRED TO BE DEMOLISHED. EXAMPLES INCLUDE TELECOMMUNICATIONS, PLUMBING, ELECTRICAL, MECHANICAL, FIRE PROTECTION, STRUCTURAL, ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THOROUGHLY REVIEWING THE CONSTRUCTION DOCUMENTS AND FOR DETERMINING THE EXTENT OF REMOVAL OR DISASSEMBLY WORK NECESSARY TO PERFORM THE
WORK OF THIS PROJECT IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS.
2. THE CONTRACTOR SHALL FIELD-VERIFY AND DOCUMENT THE EXISTING CONDITIONS OF CEILING OR WALL SURFACES TO
BE REMOVED OR DISASSEMBLED PRIOR TO BEGINNING THE WORK.
3. THE CONTRACTOR SHALL CAREFULLY REMOVE, OR DISASSEMBLE, EACH EXISTING CEILING OR WALL SURFACE IN A
MANNER THAT MINIMIZES DAMAGE TO ADJACENT EXISTING SURFACES.
4. AFTER THE WORK HAS BEEN COMPLETED, THE CONTRACTOR SHALL REPLACE, PATCH, AND FINISH THE EXISTING
SURFACE TO THE CONDITION IT WAS IN PRIOR TO REMOVAL.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
AuthorChecker
Building 500 Business Center
BID DOCUMENTS SUBMISSION
GENERAL NOTES
GI300
-2
-1
G I3
.p d f
510 Butler Avenue Martinsburg WV, 25405
SMOKING POLICY
MEDICAL WASTE NOTES
GENERAL NOTES
ACCESS TO EXISTING CONCEALED AREA NOTES
CLOCK OR
CLOCK
OUTLET
MANUAL FIRE
ALARM PULL
STATION
LIGHT
SWITCH &
DIMMER
DUPLEX
OUTLET
(LOW)
DUPLEX
OUTLET
(HIGH)
DESK
INTERCOM
OUTLET
INTERCOM
STATION
PHONE/DATA
OUTLET
THERMOSTAT SPECIAL
PURPOSE
OUTLETS
OR
JUNCTION
BOX
SPECIAL
PURPOSE
OUTLETS
DARK ROOM
STATUS LIGHT
SWITCH AT
DOOR OR
CASED OPENING
AUDIBLE
AND/OR VISUAL
FIRE ALARM
SECURITY
STROBE LIGHT
(BLUE LIGHT)
FIREMAN'S
TELEPHONE
JACK
EMERGENCY
STROBE OR
LIGHT
RACEWAY
7'
T O
C O
N T
R O
LS
4'
-0
M A
X H
IG
H
R E
A C
H
3' -0
M
IN
T
O C
O N
T R
O
LS
1' -3
M
IN
L
O W
R E
A C
H
1'
A
LI
G N
W
IT
H T
O P
O F
A D
JA
C
E N
T F
R A
M
E 8" TYP 8" TYP
T O
P O
F B
O X
4'
7'
7'
7'
NURSE CALL
STATION
WITH
CONTROLS
NURSE CALL
STATION
WITHOUT
CONTROLS
5'
NURSE CALL
CORRIDOR
LIGHT (DOME
LIGHT)
7'
DUPLEX OUTLET
ABOVE
COUNTER /
BACKSPLASH
3"
WALL-MTD
TELEPHONE
OUTLET
CARD READER,
LOCAL ALARM,
OR ARMING
STATION
3'
COUNTER
TOP / TOP OF
BACKSPLASH
COAT
HOOKS
(WALL-MTD)
COAT HOOK
(DOOR-MTD)
6"
5'
EQ EQ
6'
T O
C O
N T
R O
LS
4'
-0
M A
X H
IG
H
R E
A C
H
3' -0
M
IN
T
O C
O N
T R
O
LS
1' -3
M
IN
L
O W
R E
A C
H
MEDICAL
GAS ALARM
PANEL
FEC OR
FHV CABINET
1' - 0"
5'
4'
"12" 42"
40"
P L U
M B
IN
G
W A
L L
6" 42"
T O
IL
E
T S
ID
E
W A
L L
6" 36"
S
ID
E W
A L L
12"36"
C O
N T
R O
L W
A L L
T O
IL
E
T S
ID
E
W A
L L
7"
IF A DOUBLE ROLL
DISPENSER IS PROVIDED,
DIMENSION IS TO ROLL
CLOSEST TO TOILET
TOILET PAPER
DISPENSER
S
ID
E W
A L L
15"
COUNTER
MOUNTED
LAVATORY
S
ID
E W
A L L
15"
WALL
MOUNTED
LAVATORY
C O
U N
T E
R H
E
IG
H T
WALL MOUNTED
POSTURE MIRROR
WALL MOUNTED
MIRROR
T O
R
E F
L E
C T
IN
G
S U
R F
A C
E
18"
MIRROR TO
BE 18" X 36" U.N.O
T O
O P
E R
T A
T
IO
N
CENTER
MIRROR
OVER SINK
U.N.O
S H
O W
E R
W A
L L
WALL MOUNTED
SHOWER SEAT
T O
WALL MOUNTED
SOAP DISPENSER
T O
O P
E R
A T
IO
N
S H
O W
E R
W A
L L
T O
IL
E
T C
.L
18"
SWING UP
GRAB BAR
T O
O P
E R
T A
T
IO
N
T O
T O
P
FIRE
EXTINGUISHER IN
FULLY RECESSED CABINET
WALL MOUNTED
MOP HOLDER
T O
F R
O N
T T
P
D G
E O
F D
E C
K
L
IP
W H
N
L
W E
R E
D
WALL MOUNTED
HORIZONTAL
DIAPER CHANGING
STATION
WALL MOUNTED
GRAB BAR
(TOILET SIDE)
WALL MOUNTED
GRAB BAR
(TOILET REAR)
WALL MOUNTED
SHOWER
GRAB BARS
WALL MOUNTED PAPER
TOWEL DISPENSER
(WITH OR WITHOUT
INTEGRAL
TRASH RECEPTICLE)
OR TO TOP OF
RIM, WHICHEVER
IS GREATER.
SWING UP
GRAB BAR
EQUIPMENT, PANEL BOARD,
CABINET, OR SIMILAR FEATURE
CRASH RAIL (ALL TYPES), UON
TYPE NO 1 (SHOWN),
TYPE NO 2, OR TYPE
NO 4 CORNER OR
EDGE GUARD
WHERE BUMPER/CRASH
RAILS TERMINATE OR DO
NOT TURN CORNER
BUMPER RAIL
(ALL TYPES),
UON
DOOR FRAME OR
CASED OPENING
FRAME
OUTLET OR SIMILAR
OUTLET OR
SIMILAR WHEN
ADJ TO FRAME
WHERE
BUMPER/CRASH
RAILS TURN
CORNER
CORNER OR
EDGE GUARD
CORNER OR EDGE
GUARD
COMBINATION
HANDRAIL/CRASH
RAIL (ALL TYPES),
UON
WHERE
TERMINATES
WHERE
COMBINATION
HANDRAIL /
CRASH RAIL
TURNS CORNER
DOOR FRAME OR
CASED
OPENING FRAME
CORNER OR EDGE
GUARD
RECESSED CORNER OR EDGE
GUARD EXTENDING FROM
FLOOR TO CEILING OR
HEADER, TYPICAL UNLESS
OTHERWISE NOTED
EQUIPMENT,
PANEL BOARD,
CABINET, OR
SIMILAR FEATURE
2'
0"
U O
N
1'
U O
N
6" 3'
T
Y P
E
2" TYP 2" TYP 2" TYP
4" TYP 4" TYP
2" TYP
2'
0"
T O
P O
F R
A
IL
2" TYP 2" TYP 2" TYP
6" 6'
T Y
P E
N O
S
A N
D
42" TYP 2" TYP 2" TYP
T O
P O
F R
A
IL
2'
0"
6" 6'
T Y
P E
N O
S
A N
D
42" TYP
8" 4" TYP
8"
1'
2"
WP-01 WP-01
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
AuthorChecker
Building 500 Business Center
BID DOCUMENTS SUBMISSION
TYPICAL MOUNTING HEIGHTS
GI301
-2
-1
G I3
/2
/2
.p d f
510 Butler Avenue Martinsburg WV, 25405
GENERAL MOUNTING HEIGHT NOTESTYPICAL MOUNTING HEIGHTS AND CLEARANCES
CORNER GUARD / BUMPER RAIL / CRASH RAIL / CORRIDOR HANDRAIL TYPICAL MOUNTING HEIGHTS AND CONFIGURATION DIAGRAMS
A. IT IS THE INTENT OF THE DESIGN THAT ALL ITEMS SHOWN MOUNTED AT TYPICAL HEIGHTS BE ACCESSIBLE TO PERSONS WITH DISABILITIES.
B. THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE TYPICAL MOUNTING HEIGHTS AND - WHERE APPLICABLE - TYPICAL MINIMUM OR MAXIMUM CLEARANCES AND/OR TYPICAL MOUNTING CONFIGURATIONS FOR A VARIETY OF ITEMS. CAUTION: THIS SHEET MAY ILLUSTRATE ITEMS OR CONFIGURATIONS WHICH DO NOT OCCUR AS PART OF THE WORK OF THIS PROJECT. REFER TO THE PLANS, ELEVATIONS, SECTIONS, DETAILS, AND SCHEDULES TO DETERMINE WHICH ITEMS AND CONFIGURATIONS APPLY TO THE WORK OF THIS PROJECT.
C. THE MOUNTING HEIGHTS, CLEARANCES, AND CONFIGURATIONS SHOWN ON THIS SHEET ARE TYPICAL AND SHALL APPLY TO ALL INSTANCES OF THE ITEM (OR GROUP OF ITEMS) SHOWN UNLESS SPECIFICALLY NOTED OR DIMENSIONED OTHERWISE.
D. SPECIAL OR NON-TYPICAL MOUNTING HEIGHTS OCCUR ONLY WHERE INDICATED BY ANNOTATED SYMBOLS; BY KEY NOTES; BY NOTES ON
PLANS, ELEVATIONS, OR DETAILS; OR BY UNIQUE DIMENSIONS ON ELEVATIONS OR DETAILS.
E. MOUNTING CONFIGURATION DIAGRAMS ARE ELEVATIONS WHICH ILLUSTRATE TYPICAL RULES GOVERNING THE RELATIONSHIPS BETWEEN, AND PLACEMENT OF, ITEMS WHICH OCCUR IN GROUPS OF RELATED ITEMS OR IN CLOSE PROXIMITY TO OTHER PARTS OF THE WORK (SUCH AS SWITCHES AND DOOR FRAMES). UNLESS OTHER MOUNTING CONFIGURATIONS ARE SPECIFICALLY NOTED, DIMENSIONED, OR ELEVATED, THE TYPICAL RELATIONSHIPS, ARRANGEMENTS, AND THE TYPICAL CONFIGURATION DIAGRAMS APPLY THROUGHOUT THE WORK OF THIS
PROJECT.
UP
AA
BB
C C
D
D
EE
B.1B.1
B.6B.6
B.8B.8
D.1D.1
D.2D.2
D.4D.4
D.6 D.6
D.8
D.8
E.2E.2
E.4E.4
FF
F.3F.3
GG
HH
JJ
KK
G.7G.7
1.1
1.1
6.9
6.9
7.6
7.6
7.7
7.7
8.3
8.3
8.4
8.4
9.1
9.1
LL
NOT IN SCOPE
AREA OF SCOPE
ELECTRICAL ROOM
1D-180D
COMPACTOR
1B-101A
RECEPTION
1A-162
VIC CARD ROOM
1A-163
OFFICE
1A-164
OFFICE
1A-165
OFFICE
1A-165A
OFFICE
1A-167
OFFICE
1A-168
OFFICE
1A-169
OFFICE
1A-170
OFFICE
1A-171
OFFICE
1A-172
OFFICE
1A-173
TOILET
1A-174
STORAGE
1A-175
OFFICE
1A-176
OFFICE
1A-177
OFFICE
1A-178
H.A.C.
1A-179FEMALE TOILET
1A-180
MALE TOILET
1A-181
OFFICE
1A-166
TOILET
1A-173A
OFFICE
1A-177A
OFFICE
1A-168A
OFFICE
1A-168B
LAB
1A-160
RECEPTION
1A-160A
TOILET
1A-160B
WAITING ROOM
1A-161 OFFICE
1A-161A
OFFICE
1A-161B
HOLDING
1A-164A
VACANT
1A-182
CORRIDOR
1A-C19
CORRIDOR
1A-C20
CORRIDOR
1A-C21
CORRIDOR
1A-C22
CORRIDOR
1A-C14
CORRIDOR
1A-C25
STAIR #1
1-S1
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
AuthorChecker
Building 500 Business Center
BID DOCUMENTS SUBMISSION
EXISTING CONDITIONS PLAN
GC100
-2
-1
G C
/2
/2
.p d f
510 Butler Avenue Martinsburg WV, 25405
1/16" = 1'-0"A12
EXISTING FIRST FLOOR PLAN
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
AuthorChecker
Building 500 Business Center
BID DOCUMENTS SUBMISSION
ASBESTOS PLAN
GC200
-2
-1
G C
/2
/2
.p d f
510 Butler Avenue
F
N
WAITING ROOM
1A-166
OFFICE
1A-173
OFFICE
1A-170
KITCHENETTE
1A-175
OFFICE
1A-174
OFFICE
1A-176
OFFICE
1A-177
OFFICE
1A-178
HAC
1A-179
STORAGE
1A-180
RECEPTION
1A-162
CORRIDOR
1A-C21
131' - 1"
30 sec
AREA OF WORK
NFPA 101 LIFE SAFETY CODE 2021 MARTINSBURG VA RENOVATE BUIDLING 500
TOTAL PROJECT AREA 1,900 SF
OCCUPANCY COUNT BUSINESS USE:
344 SF / 50 SF PER
OCCUPANT =17 OCCUPANTS
EGRESS CAPACITY PROVIDED EXIT DOOR: 57" DOOR 57/.2=285
OCCUPANTS MAX
TOTAL EGRESS CAPACITY 285 OCCUPANTS
CORRIDOR MINIMUM 72" ALLOWED BY VA STANDARDS 96"
EXISTING EXIT CORRIDORS
CHAPTER 39 - EXISTING BUSINESS OCCUPANCY
39.2 MEANS OF EGRESS REQUIREMENTS
39.2.1.1 ALL MEANS OF EGRESS SHALL BE CONTINOUSLY MAINTAINED FREE OF ALL OBSTRUCTIONS OR
IMPEDIMENTS TO FULL INSTANT USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
7.1.10 MEANS OF EGRESS RELIABILITY
7.1.10.1 MEANS OF EGRESS SHALL BE CONTINIOUSLY MAINTAINED FREE OF ALL OBSTRUCTIONS OR
IMPEDIMENTS TO FULL INSTANT USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
39.5.2 HEATING, VENTILATING, AND AIR-CONDITIONING. HEATING, VENTILATING, AND AIR-CONDITIONING EQUIPMENT
SHALL COMPLY WITH THE PROVISIONS OF SECTION 9.2.
9.2.1 AIR-CONDITIONING, HEATING, VENTILATING, DUCTWORK, AND RELATED EQUIPMENT. AIR CONDITIONING, HEATING, VENTILATING DUCTWORK, AND RELATED EQUIPMENT SHALL BE IN ACCORDANCE WITH THE NFPA 90A.
39.2.2.2 DOORS
39.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE PERMITTED.
39.2.3 CAPACITY OF MEANS OF EGRESS.
38.2.3.1 THE CAPACITY OF MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH SECTION 7.3
7.3 / TABLE 7.3.3.1 THE CAPACITY OF MEANS OF EGRESS PROVIDING TRAVEL BY MEANS OF STAIRS SHALL BE
0.3 IN. PER PERSON, AND THE CAPACITY OF MEANS OF EGRESS PROVIDING HARIZONTAL TRAVEL (WITHOUT STAIRS) BY MEANS SUCH AS DOORS, RAMPS, OR HARIZONTAL TRAVEL (WITHOUT STAIRS) BY MEANS SUCH
AS DOORS, RAMPS, OR HORIZONTAL EXITS SHALL BE 0.2 IN. PER PERSON.
38.2.3.2 THE CLEAR WIDTH OF ANY CORRIDOR OR PASSAGEWAY SERVING AN OCCIPANT LOAD OF 50 OR MORE
SHALL BE NOT LESS THAN 44 IN.
39.2.4 NUMBER OF MEANS OF EGRESS
38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE FOLLOWING, EXCEPT AS OTHERWISE PERMITED
(2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED ON EVERY STORY.
39.2.5 ARRANGEMENT OF MEANS OF EGRESS
38.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN ACCORDANCE WITH SECTION 7.5.
7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVIED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7. THE MINIMUM SPEARATION DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT DISCHARGES, MEASURED IN ACCORDANCE WITH 7.5.1.3.2, SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA
TO BE SERVED.
38.2.5.2.1 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER
SYSTEM IN ACCORDANCE WITH 9.7.1.1(1), DEAD-END CORRIDORS SHALL NOT EXCEED 50FT.
38.2.5.3.1 COMMON PATH OF TRAVEL SHALL NOT EXCEED 100 FT IN A BUILDING PROTECTED THROUGHTOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1).
39.2.6 TRAVEL DISTANCE TO EXITS
39.2.6.3 TRAVEL DISTANCE SHALL NOT EXCEED 300 FT IN BUSINESS OCCUPANCIES THROUGHOUT BY AN
APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.
39.2.7 DISCHARGE FROM EXITS. EXITS SHALL COMPLY WITH SECTION 7.7.
7.7.1 EXIT TERMINATION. EXITS SHALL TERMINATE DIRECTLY, AT A PUBLIC WAY OR AT AN
EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH 7.7.1.4
7.7.1.2 THE REQUIREMENT OF 7.7.1 SHALL NOT APPLY TO INTERIOR EXIT DISCHARGE AS
OTHERWISE PROVIDED IN 7.7.2.
7.7.2 EXIT DISCHARGE THROUGH INTERIOR BUILDING AREAS. EXITS SHALL BE PERMITTED TO DISCHARGE THROUGH INTERIOR BUILDING AREAS, PROVIDE THAT ALL OF THE FOLLOWING ARE MET:
(1) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER OF EXIT STAIRS SERVING
NORMALL OCCUPIED AREAS OF EACH FLOOR, AND NOT MORE THAN 50 PERCENT OF THE EXIT
STAIR CAPACITY REQUIRED FOR NORMALLY OCCUPIED AREAS OF EACH FLOOR, SHALL
DISCHARGE THROUGH AREAS ON ANY LEVEL OF DISCHARGE, EXCEPT AS OTHERWISE
PERMITTED BY ONE OF THE FOLLOWING:
(A)ONE HUNDRED PERCENT OF THE EXITS SHALL BE PERMITTED TO DISCHARGE THROUGH
AREAS ON ANY LEVEL OF DISCHARGE IN DETENTION AND CORRECTIONAL OCCUPANCIES AS
OTHERWISE PROVIDED IN CHAPTERS 22 AND 23.
(B) IN EXISTING BUILDINGS, THE 50 PERCENT LIMIT ON EGRESS CAPACITY SHALL NOT APPLY IF
THE 50 PERCENT LIMIT ON THE REQUIRED NUMBER OF EXITS IS MET.
(2) EACH LEVEL OF DISCHARGE SHALL DISCHARGE DIRECTLY OUTSIDE AT THE FINISHED
GROUND LEVEL OR DISCHARGE DIRECTLY OUTSIDE AND PROVIDE ACCESS TO THE FINISHED
GROUND LEVEL BY OUTSIDE STAIRS OR OUTSIDE RAMPS.
(3) THE INTERIOR EXIT DISCHARGE SHALL LEAD TO A FREE AND UNOBSTRUCTED WAY TO THE
EXTERIOR OF THE BUILDING, AND SUCH WAY SHALL BE READILY APPARENT OR SHALL BE
IDENTIFIABLE BY EXIT SIGNAGE FROM THE POINT OF DISCHARGE FROM THE EXIT.
(4) THE INTERIOR EXIT DISCHARGE SHALL BE PROTECTED BY ONE OF THE FOLLOWING
METHODS:
(A) THE LEVEL OF DISCHARGE SHALL BE PROTECTED THROUGHOUT BY AN APPROVED
AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7, OR THE PORTION OF THE
LEVEL OF DISCHARGE USED FOR INTERIOR EXIT DISCHARGE SHALL BE PROTECTED BY AN
APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7 AND SHALL BE
SEPARATED FROM THE NONSPRINKLERED PORTION OF THE FLOOR BY FIRE BARRIERS WITH A
FIRE RESISTANCE RATING MEETING THE REQUIREMENTS FO RTHE ENCLOSURE OF EXITS.
(5) THE ENTIRE AREA ON THE LEVEL OF DISCHARGE SHALL BE SEPARATED FROM AREAS
BELOW BY CONSTRUCTION HAVING A FIRE RESISTANCE RATING NOT LESS THAN THAT
REQUIRED FOR THE EXIT ENCLOSURE, UNLESS OTHERWISE PERMITED IN 7.7.2(6).
(6) LEVELS BELOW THE LEVEL OF DISCHARGE IN AN ATRIUM SHALL BE PERMITTED TO BE OPEN
TO THE LEVEL OF DISCHARGE WHERE SUCH LEVEL OF DISCHARGE IS PROTECTED IN
ACCORDANCE WITH 8.6.7.
CODE LEGEND
1 HOUR FIRE BARRIER PER NFPA 101 SECTION 7.3. OPENINGS FIRE RATED FOR 45
MINUTES UNLESS SHAFT, EXIT ENCLOSURE, OR EXIT PASSAGEWAY WALLS WHICH
REQUIRE 1 HOUR RATED OPENINGS.
FIRE EXTINGUISHER CABINET
EXIT SIGN
FEC
DOOR/STAIR ID
ACTUAL EGRESS
CAPACITY
WIDTH
DOOR/STAIR ID
ACTUAL EGRESS
CAPACITY
WIDTH
DOOR
0"
0 0
OPENING RATING IN
MINUTES
2 HOUR FIRE BARRIER PER NFPA 101 SECTION 7.3. OPENINGS FIRE RATED FOR 90
MINUTES.
OPENING RATING IN
MINUTES
EGRESS PATH WITH NAME, SEGMENT LENGTH, AND DIRECTION INDICATED
DOOR/STAIR INDICATORS
*NOTE: AS DEPICTED ON THE SHEET, ALL FIRE
EXTINGUISHER CABINETS MEET MIN. 75 FT
REQUIREMENTS
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
AuthorChecker
Building 500 Business Center
BID DOCUMENTS SUBMISSION
LIFE SAFETY PLAN
LS-100
-2
-1
L S
-1
/2
/2
.p d f
510 Butler Avenue Martinsburg WV, 25405
1/4" = 1'-0"A15
LIFE SAFETY PLAN
KEY PLAN
AA
BB
B.1B.1
B.6B.6
RECEPTION
1A-162
VIC CARD ROOM
1A-163
OFFICE
1A-170
OFFICE
1A-171
OFFICE
1A-172
OFFICE
1A-173
TOILET
1A-174
STORAGE
1A-175
OFFICE
1A-176
OFFICE
1A-177
OFFICE
1A-178
H.A.C.
1A-179
FEMALE TOILET
1A-180
MALE TOILET
1A-181
OFFICE
1A-166
TOILET
1A-173A
OFFICE
1A-177A
RECEPTION
1A-160A
TOILET
1A-160B
WAITING ROOM
1A-161
OFFICE
1A-161A
HOLDING
1A-164A
CORRIDOR
1A-C19
CORRIDOR
1A-C20
CORRIDOR
1A-C21
CORRIDOR
1A-C22
CORRIDOR
1A-C25
2 2
IK1
IK2
IK3
IK5
IK6IK6
IG1
IG1
AREA OF WORK
DEMOLITION PLAN LEGEND
EXISTING WALLS TO REMAIN
EXISTING WALLS TO BE REMOVED
EXISTING DOORS TO BE REMOVED
ICRA TEMPORARY WALLS
ICRA TEMPORARY DOORS
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
AuthorChecker
Building 500 Business Center
BID DOCUMENTS SUBMISSION
DEMOLITION FLOOR PLAN
AD101
-2
-1
A D
.p d f
510 Butler Avenue Martinsburg WV, 25405
GENERAL NOTES - DEMOLITION
G1 CONTRACTOR SHALL NOTIFY COR IMMEDIATELY OF ANY DEVIATIONS BETWEEN EXISTING CONDITIONS AND DEMOLITION DRAWINGS
DISCOVERED DURING DEMOLITION ACTIVITIES.
G2 CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING AND COORDINATING ALL EXISTING AND NEW CONSTRUCTION.
G3 ALL ITEMS SHOWN DASHED INDICATE ITEMS TO BE DEMOLISHED OR SALVAGED. SEE SPECIFIC KEY NOTES ON THISS SHEET FOR ADDITIONAL INFORMATION. REFER TO MECHANICAL, FIRE PROTECTION, PLUMBING, ELECTRICAL, AND TELECOM DRAWINGS FOR ADDITIONAL DEMOLITION
REQUIREMENTS.
G4 ALL OPENINGS AND SURFACES MADE BARE BY DEMOLITION AND/OR REMOVAL OF MATERIALS SHALL BE REPAIRED AND/OR PATCHED TO
MATCH ADJACENT FINISH. PREPARE SURFACES TO RECEIVE NEW FINISH(ES).
G5 CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ICRA STANDARDS AND POLICIES. COORDINATE WITH ICRA PLAN AND COR.
G6 DEPICTION OF EXISTING CONDITIONS IS BASED ON OWNER-FURNISHED DOCUMENTS AND LIMITED FIELD OBSERVATIONS. EXISTING ELEMENTS AND CONDITIONS CONCEALED BY IN-PLACE EQUIPMENT AND FINISHES WERE NOT OBSERVED OR INVESTIGATED. ONCE CUTTING AND SELECTIVE DEMOLITION WORK IS COMPLETE, REPORT ANY CONFLICTS TO COR. THE CONTRACTOR SHALL MAKE ADJUSTMENTS AND/OR ALTERATIONS AS NECESSARY TO INSTALL COMPLETE AND OPERABLE SYSTEMS IN ACCORDANCE WITH THE CODES HAVING JURISDICTION AT
NO ADDITIONAL COST TO THE GOVERNMENT.
G7 VAMC AND/OR VAMC EQUIPMENT SUPPLIER TO REMOVE EXISTING UNMOUNTED AND MOUNTED EQUIPMENT PRIOR TO CONSTRUCTION. ONCE OWNER AND/OR EQUIPMENT SUPPLIER HAVE REMOVED EQUIPMENT, PHOTOGRAPHICALLY DOCUMENT ENTIRE AREA OF NEW WORK. TAKE NOTE OF ANY DAMAGED SURFACES OR ELEMNETS. PREPARE WRITTEN AND PHOTOGRAPHIC REPORT OF SURVEY AND SUBMIT TO OWNER
AND DESIGNER.
G8 PROTECT ALL EXISTING FINISHES AND ELEMENTS TO REMAIN. REPAIR OR REPLACE DAMAGED SURFACES TO MATCH ADJACENT FINISHES.
G9 "CUTTING" IS DEFINED AS THE REMOVAL OF IN-PLACE CONSTRUCTION NECESSARY TO PERMIT INSTALLATION OR PERFORMANCE OF OTHER WORK. "PATCHING" IS DEFINED AS THE FITTING AND REPAIR WORK REQUIRED TO RESTORE SURFACES TO ORIGINIAL CONDITIONS AFTER INSTALLATION OF OTHER WORK. "REMOVE" IS DEFINED AS DETACH ITEMS FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF THEM OFF-SITE, UNLESS INDICATED TO BE "SALVAGED" OR "REMOVED AND REINSTALLED". "SALVAGE" IS DEFINED AS DETACH ITEMS FROM EXISTING CONSTRUCTION AND DELIVER THEM TO OWNER READY FOR REUSE. "REMOVE AND REINSTALL" IS DEFINED AS DETACH ITEMS FROM EXISTING CONSTRUCTION, PREPARE THEM FOR REUSE, AND REINSTALL THEM WHERE INDICATED. "EXISTING TO REMAIN" IS DEFINED AS EXISTING ITEMS OF CONSTRUCTION NOT TO BE REMOVED AND ARE NOT OTHERWISE INDICATED TO BE "REMOVED", "SALVAGED", OR "REMOVED AND
REINSTALLED".
G10 REMOVE EXISTING FLOORING, WALL PROTECTION (HANDRAILS, CRASHRAILS, CORNER GUARDS, SHEET WALL PROTECTION PANELS, ETC), CEILING AND ALL CEILING DEVICES, AND PLUMBING FIXTURES THROUGHOUT LIMITS OF THE WORK.
G11 COORDINATE SLAB DEMOLITION AND RESTORATION WITH NEW PLUMBING WORK.
G12 DELIVER TO OWNER ALL EQUIPMENT, FIXTURES, OR ACCESSORIES IDENTIFIED BY THE OWNER TO BE SALVAGED.
G13 ALL AREAS SCHEDULED TO RECIEVE NEW FLOORING (SEE A15/AE301), REMOVE FLOOR FINISHES DOWN TO EXISTING SLAB. PREP / PATCH /
LEVEL EXISTING SLAB TO RECIEVE NEW FINISHES.
KEYNOTES - DEMOLITION
1 DEMOLISH AND REMOVE PORTION OF PARTITION WALL AS REQUIRED.
2 DEMOLISH TO WIDEN OPENING PER NEW CONSTRUCTION PLAN
4 REPLACE EXISITNG DOOR, PER DOOR SCHEDULE
5 DEMO PLUMBING, SEE PLUMBING SHEET FOR DETAILS
6 CONTRACTOR SHALL PROTECT EXISTING CONNECTING WALLS AND REPAIR.
7 DEMOLISH SUSPENDED CEILING GRID, ACOUSTICAL TILES, AND ASSOCIATED APPURTENANCES.
8 CONTRACTOR SHALL REFER TO NEW RCP PLAN AND DISASSEMBLE CEILING AT NEW WALL CROSS SECTION.
9 CEILING TILE TO REMAIN, MAINTAIN IN PLACE CEILING GRID. REFER TO ELECTRICAL AND MECHANICAL DOCUMENTS FOR LIGHTIG FIXTURES, AND DIFFUSERS. CONTRACTOR OPTION TO ADD NEW GRID AND CEILING TILES PER SPECIFICATIONS.
10 REMOVE EXISTING GYPSUM CEILING. CONTRACTORS OPTION TO PATCH AND REPAIR.
1/4" = 1'-0"A15
PARTIAL DEMO FLOOR PLAN
KEY PLAN
KEYNOTES - PLAN
1 CONTRACTOR SHALL COMPLETE ALL REPAIR AND FINISH WORK IN CORRIDORS 1A-C19 AND 1A-C25 OUT SIDE OF ZONED AREA AFTER HOURS.
2 CONTRACTOR SHALL PROTECT EXISTING HAND GUARD DURING CONSTRUCTION .
3 PATCH WALL WHERE EXISTING WALL WAS REMOVED AND FINISH TO MATCH ADJACENT WALL.
ICRA NOTES - CONSTRUCTION
IC1 ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.
IC2 COMPLETE ALL CRITICAL BARRIERS (I.E. SHEETROCK, PLYWOOD, & PLASTIC) TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO
EXIT) BEFORE CONSTRUCTION BEGINS.
IC3 MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS. AIR PRESSURE SHALL BE CONTINUOUSLY MONITORED. THE CONTRACTOR SHALL USE TEMPORARY PRESSURE SENSORS CONNECTED TO THE BUILDING AUTOMATION SYSTEM (BAS) VIA AHU-7 CONNECTION. THE CONTRACTOR SHALL TRACK, TREND, AND ALARM PROJECT AREA PRESSURE TO ENSURE PROOF OF NEGATIVE PRESSURE ENVIRONMENT AT ALL TIMES UNTIL APPROVED BY VA COR TO REMOVE.
IC4 SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES AIRTIGHT AND/OR FIRE SEAL AS REQUIRED.
IC5 CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE
WORK SITE.
IC6 ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER
EXITS THE WORK AREA.
IC7 DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS APPROVED BY THE COR, INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL DEPARTMENT AND THOROGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL SERVICES
DEPARTMENT.
IC8 REMOVE CONSTRUCTION WASTE DAILY DURING THE HOURS OUTSIDE OF 0800-1630.
IC9 CONTRACTOR TO USE ROUTE AGREED UPON BY THE ICRA TEAM AND COR FOR TRANSPORT OF CONTAINERS THROUGH THE FACILITY.
IC10 PLACE DUST MATS AT ENTRANCE AND EXIT OF WORK AREA.
ICRA KEY NOTES
IG1 PROVIDE TEMPORARY / PERMANENT RATED ICRA PARTITIONS AS CONCEPTUALLY INDICATED ON PLANS. CONTRACTOR SHALL SUBMIT AN ICRA
PLAN FOR APPROVAL OF THE COR PRIOR TO BEGINNING ANY WORK.
IG2 DOORS IN ICRA PARTITIONS SHALL HAVE CLOSERS, PANIC DEVICES, STOREROOM FUNCTION LOCKS, AND ALARMS. DOORS SHALL
AUTOMATICALLY LOCK UPON CLOSURE.
IG3 CONTRACTOR SHALL INSTALL "CONSTRUCTION ZONE - AUTHORIZED PERSONNEL ONLY" SIGN ON THE PUBLIC SIDE OF ALL ICRA DOORS.
IG4 ALL ICRA PARTITIONS SHALL BE WALL TYPE "R3.1t". REFER TO AE302 FOR MORE INFORMATION.
IG5 CONTRACTOR SHALL COMPLY WITH NFPA 241 FOR DURATION OF DEMOLITION AND CONSTRUCTION.
ICRA NOTES - KEYNOTES
IK1 AIRTIGHT ANTEROOM. CONTRACTOR SHALL MAINTAIN 44" CLEAR IN CORRIDOR OUTSIDE.
IK2 TEMPORARY WALK-OFF MAT
IK3 HEPA FILTER EXHAUST FAN SYSTEM VENTED THROUGH EXISTING WINDOW. CONTRACTOR SHALL VERIFY LOCATION WITH COR.
IK4 CONTRACTOR ENTRANCE AND DEBRIS REMOVAL DOOR. CONTRACTOR SHOULD COORDINATE LOCATION WITH COR.
IK5 CONSTRUCTION LAYDOWN/STAGING AREA. CONTRACTOR SHALL CONFIRM EXTENTS WITH COR.
IK6 AREA OUTSIDE OF ICRA BARRIER WHERE REPAIRS AND FINISH SHALL OCCUR. REPAIRS AND FINISHES IN THIS AREA SHALL OCCUR OUTSIDE OF BUSINESS HOURS. CONTRACTOR SHALL SUBMIT FOR VA INFECTION CONTROL NURSE APPROVAL PLANS BEFORE ACCOMPLISHING ANY
WORK IN THESE AREAS.
ICRA NOTES - REMOVAL
IR1 REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
IR2 CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
IR3 COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
IR4 VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.
IR5 WET MOP AREA WITH DISINFECTANT. VA COR SHALL APPROVE DISINFECTANT.
IR6 REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
IG2
AREA OF WORK
AA
BB
B.1B.1
B.6B.6
7'
1/
2"
OFFICE
1A-177
OFFICE
1A-176
TOILET
1A-173A
TOILET
1A-174
OFFICE
1A-173
OFFICE
1A-172
OFFICE
1A-171
CORRIDOR
1A-C21
OFFICE
1A-177A
OFFICE
1A-178
MALE TOILET
1A-181
FEMALE TOILET
1A-180
CORRIDOR
1A-C22
RECEPTION
1A-162
STORAGE
1A-175
OFFICE
1A-170
VIC CARD ROOM
1A-163
OFFICE
1A-166
CORRIDOR
1A-C19CORRIDOR
1A-C25
CORRIDOR
1A-C20
SUSPENDED CEILING SYSTEM TO BE DEMOLISHED
RCP LEGEND
GYPSUM CEILING TO BE DEMOLISHED
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
COFFMAN ENGINEERS
8171 MAPLE LAWN BLVD
SUITE 320
FULTON, MD 20759
301-323-3599
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
06/07/2024
613-22-135
AuthorChecker
Building 500 Business Center
BID DOCUMENTS SUBMISSION
DEMOLITION RCP PLAN
AD102
-2
-1
A D
/0
/2
.p d f
510 Butler Avenue Martinsburg WV, 25405
GENERAL NOTES - DEMOLITION
G1 CONTRACTOR SHALL NOTIFY COR IMMEDIATELY OF ANY DEVIATIONS BETWEEN EXISTING CONDITIONS AND DEMOLITION DRAWINGS
DISCOVERED DURING DEMOLITION ACTIVITIES.
G2 CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING AND COORDINATING ALL EXISTING AND NEW CONSTRUCTION.
G3 ALL ITEMS SHOWN DASHED INDICATE ITEMS TO BE DEMOLISHED OR SALVAGED. SEE SPECIFIC KEY NOTES ON THISS SHEET FOR ADDITIONAL INFORMATION. REFER TO MECHANICAL, FIRE PROTECTION, PLUMBING, ELECTRICAL, AND TELECOM DRAWINGS FOR ADDITIONAL DEMOLITION
REQUIREMENTS.
G4 ALL OPENINGS AND SURFACES MADE BARE BY DEMOLITION AND/OR REMOVAL OF MATERIALS SHALL BE REPAIRED AND/OR PATCHED TO
MATCH ADJACENT FINISH. PREPARE SURFACES TO RECEIVE NEW FINISH(ES).
G5 CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ICRA STANDARDS AND POLICIES. COORDINATE WITH ICRA PLAN AND COR.
G6 DEPICTION OF EXISTING CONDITIONS IS BASED ON OWNER-FURNISHED DOCUMENTS AND LIMITED FIELD OBSERVATIONS. EXISTING ELEMENTS AND CONDITIONS CONCEALED BY IN-PLACE EQUIPMENT AND FINISHES WERE NOT OBSERVED OR INVESTIGATED. ONCE CUTTING AND SELECTIVE DEMOLITION WORK IS COMPLETE, REPORT ANY CONFLICTS TO COR. THE CONTRACTOR SHALL MAKE ADJUSTMENTS AND/OR ALTERATIONS AS NECESSARY TO INSTALL COMPLETE AND OPERABLE SYSTEMS IN ACCORDANCE WITH THE CODES HAVING JURISDICTION AT
NO ADDITIONAL COST TO THE GOVERNMENT.
G7 VAMC AND/OR VAMC EQUIPMENT SUPPLIER TO REMOVE EXISTING UNMOUNTED AND MOUNTED EQUIPMENT PRIOR TO CONSTRUCTION. ONCE OWNER AND/OR EQUIPMENT SUPPLIER HAVE REMOVED EQUIPMENT, PHOTOGRAPHICALLY DOCUMENT ENTIRE AREA OF NEW WORK. TAKE NOTE OF ANY DAMAGED SURFACES OR ELEMNETS. PREPARE WRITTEN AND PHOTOGRAPHIC REPORT OF SURVEY AND SUBMIT TO OWNER
AND DESIGNER.
G8 PROTECT ALL EXISTING FINISHES AND ELEMENTS TO REMAIN. REPAIR OR REPLACE DAMAGED SURFACES TO MATCH ADJACENT FINISHES.
G9 "CUTTING" IS DEFINED AS THE REMOVAL OF IN-PLACE CONSTRUCTION NECESSARY TO PERMIT INSTALLATION OR PERFORMANCE OF OTHER WORK. "PATCHING" IS DEFINED AS THE FITTING AND REPAIR WORK REQUIRED TO RESTORE SURFACES TO ORIGINIAL CONDITIONS AFTER INSTALLATION OF OTHER WORK. "REMOVE" IS DEFINED AS DETACH ITEMS FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF THEM OFF-SITE, UNLESS INDICATED TO BE "SALVAGED" OR "REMOVED AND REINSTALLED". "SALVAGE" IS DEFINED AS DETACH ITEMS FROM EXISTING CONSTRUCTION AND DELIVER THEM TO OWNER READY FOR REUSE. "REMOVE AND REINSTALL" IS DEFINED AS DETACH ITEMS FROM EXISTING CONSTRUCTION, PREPARE THEM FOR REUSE, AND REINSTALL THEM WHERE INDICATED.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .