This document contains multiple test reports for oil samples collected from transformers at the VA Medical Center in Martinsburg, West Virginia. The reports provide detailed analysis and diagnostics on the condition of the transformer oil, including dissolved gas analysis, general oil quality, moisture content, interfacial tension, and acid number. The reports were generated by Weidmann Electrical Technology, an ISO/IEC 17025:2005 accredited laboratory. The reports indicate some transformers have elevated levels of certain dissolved gases, requiring recommended actions such as resampling to monitor the generation rate. Overall, the reports provide critical information on the maintenance and condition of the transformers at this facility.
The related federal contract opportunity is a solicitation (Solicitation Number: 36C24524Q0607) issued by the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 5 for contractor services to perform inspection, testing and maintenance on various electrical equipment at the Martinsburg VA Medical Center. The services required include work on 12 kV vacuum switchgear breakers, automatic transfer switches, cable, 480V switchgear breakers, automatic and manual transfer switches, molded case breakers, and 12 kV/480V pad mounted transformers.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24524Q0607 0002_1.docx | DOCX document | |
| Maintenance Report 2014.pdf | ||
| Pre-Bid RFIs Test Facility Electrical Sysstem 2024 07 08 -.xlsx | XLSX spreadsheet | |
| Draft Schedule 2024-07-01.pdf | ||
| Draft Schedule 2024-07-01 02.pdf | ||
| 4.2 - Breaker Settings.xls | XLS spreadsheet | |
| Master Site Electrical Dist System_30x42.pdf | ||
| Master Site Plan.pdf | ||
| Appendix G - One-lines - MRTN 100.pdf | ||
| 36C24524Q0607 0002 AMENDMENT.pdf | ||
| 36C24524Q0607 0001_1.docx | DOCX document | |
| 36C24524Q0607 0001 EXTENDING RFQ DATE.pdf | ||
| VHA Directive 1028_D_2020-02-24.pdf | ||
| 36C24524Q0607_1.docx | DOCX document | |
| 36C24524Q0607 --RFQ.pdf | ||
| WAGE DETERMINATION BERKELEY COUNTY WV.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lab Control Number: 6774065
Date Sampled: 04/22/2015
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: PC22009001 Mfr: Control#: 6774065
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004415 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: SIL Sampled By:
Customer ID: 500.A
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774065-473705-00
Dissolved Gas Analysis (DGA) Hydrogen (H2) (ppm): 50
ASTM Methane (CH4) (ppm): 41
D-36121 Ethane (C2H6) (ppm): 3
Ethylene (C2H4) (ppm): 1
Acetylene (C2H2) (ppm): <1
Carbon Monoxide (CO) (ppm): 2160
Carbon Dioxide (CO2) (ppm): 10595
Nitrogen (N2) (ppm): 129982
Oxygen (O2) (ppm): 3503
Total Dissolved Gas (TDG) (ppm): 146335
Total Dissolved Combustible Gas (TDCG) (ppm): 2255
Equivalent TCG (%): 1.2397
DGA
Diagnostics
DGA Keys Gas / Interpretive Method:
PER IEEE C57.146-2005
(most recent sample)
Hydrogen within limits (200 ppm).
No indications of electrical arcing (H2 200 ppm C2H2 1 ppm).
Carbon Monoxide within limits (3000 ppm).
Carbon Monoxide and Carbon Dioxide within limits (33000 ppm).
DGA TDCG Rate Interpretive Method:
PER IEEE C57.146-2005
(two most recent sample)
IEEE Guidelines not applicable for this fluid type.
DGA Cellulose (Paper) Insulation: CO2/CO Ratio not applicable for this fluid type.
WDS DGA Condition Code:
WDS Recommended Action:
WDS DGA Condition Code & Recommended Action for Transformers with Mineral Oil only.
Comment:
General Oil Quality (GOQ)
D-15331 Moisture in Oil (ppm): 22
D-9741 Acid Number (mg KOH/g): 0.016
D-21291 Color Number (Relative): 10
D-15241 Visual Exam. (Relative): CLR&SPRK
D-15241 Sediment Exam. (Relative): ND
D-8771 Dielectric Breakdown (kV): 40
D-9241 Power Factor @ 25C (%): <0.001
D-1298 Specific Gravity (Relative): 0.9628
GOQ Diagnostics Moisture in Oil: Acceptable for in-service oil (100 ppm max).
PER IEEE C57.111-1989 Acid Number: Acceptable for in-service oil (0.2 mg KOH/g max).
(most recent sample) Color Number and Visual: Diagnostic not applicable. Visual acceptable for in-service oil (CLR&SPRK).
Dielectric Breakdown D-877: Acceptable for in-service oil (25 kV min).
Power Factor @25C: Acceptable for in-service oil (0.2% max).
Comment:
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
A Member of the WICOR Group
Lab Control Number: 6774065
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: PC22009001 Mfr: Control#: 6774065
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004415 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: SIL Sampled By:
Customer ID: 500.A
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774065-473705-00
End of Test Report
Authorized By:
KENNETH COCCIA
LABORATORY SUPERVISOR
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774067
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 826000558 Mfr: Control#: 6774067
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004432 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: 500 B
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774067-473705-00
Dissolved Gas Analysis (DGA) Hydrogen (H2) (ppm): 110
ASTM Methane (CH4) (ppm): 202
D-36121 Ethane (C2H6) (ppm): 61
Ethylene (C2H4) (ppm): 29
Acetylene (C2H2) (ppm): <1
Carbon Monoxide (CO) (ppm): 1388
Carbon Dioxide (CO2) (ppm): 8086
Nitrogen (N2) (ppm): 69353
Oxygen (O2) (ppm): 1137
Total Dissolved Gas (TDG) (ppm): 80366
Total Dissolved Combustible Gas (TDCG) (ppm): 1790
Equivalent TCG (%): 1.737
DGA
Diagnostics
DGA Keys Gas / Interpretive Method:
PER IEEE C57.104-2008
(most recent sample)
Hydrogen: Condition 2 Indications of partial discharge activity (100 ppm).
Methane: Condition 2 Indications of overheated (>150°C) oil (120 ppm).
Ethane within condition 1 limits (65 ppm).
Ethylene within condition 1 limits (50 ppm).
Acetylene within condition 1 limits (1 ppm).
Carbon Monoxide: Condition 3 Indications of significantly overheated cellulose insulation (570 ppm).
Carbon Dioxide: Condition 3 Significant Indications of overheated cellulose insulation (4000 ppm).
TDCG: Condition 2 Levels exceed normal concentrations. Fault may be present (720 ppm).
DGA TDCG Rate Interpretive Method:
PER IEEE C57.104-2008
(two most recent sample)
No previous sample available.
DGA Cellulose (Paper) Insulation: Normal decomposition of cellulose insulation.
WDS DGA Condition Code:
WDS Recommended Action:
CAUTION
Resample at earliest opportunity to establish gas generation rate.
Comment:
General Oil Quality (GOQ)
D-15331 Moisture in Oil (ppm): 17
D-9711 Interfacial Tension (dynes/cm): 30.2
D-9741 Acid Number (mg KOH/g): 0.019
D-15001 Color Number (Relative): L1.5
D-15241 Visual Exam. (Relative): CLR&SPRK
D-15241 Sediment Exam. (Relative): TRACE
D-8771 Dielectric Breakdown (kV): 46
D-9241 Power Factor @ 25C (%): 0.020
D-1298 Specific Gravity (Relative): 0.8818
GOQ Diagnostics Moisture in Oil: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (20 ppm max).
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774067
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 826000558 Mfr: Control#: 6774067
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004432 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: 500 B
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774067-473705-00
PER IEEE C57.106-2006 Interfacial Tension: Exceeds limit for equipment >= 230 kV for in-service oil - kV not provided (32 dynes/cm min).
(most recent sample) Acid Number: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.1 mg KOH/g max).
Color Number and Visual: Diagnostic not applicable. Diagnostic not applicable.
Dielectric Breakdown D-877: Diagnostic not applicable.
Power Factor @25C: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.5% max).
Comment:
End of Test Report
Authorized By:
KENNETH COCCIA
LABORATORY SUPERVISOR
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774070
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: PCT785002 Mfr: Control#: 6774070
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004458 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: 501
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774070-473705-00
Dissolved Gas Analysis (DGA) Hydrogen (H2) (ppm): 4
ASTM Methane (CH4) (ppm): 43
D-36121 Ethane (C2H6) (ppm): 18
Ethylene (C2H4) (ppm): 9
Acetylene (C2H2) (ppm): <1
Carbon Monoxide (CO) (ppm): 507
Carbon Dioxide (CO2) (ppm): 7750
Nitrogen (N2) (ppm): 68558
Oxygen (O2) (ppm): 600
Total Dissolved Gas (TDG) (ppm): 77489
Total Dissolved Combustible Gas (TDCG) (ppm): 581
Equivalent TCG (%): 0.5525
DGA
Diagnostics
DGA Keys Gas / Interpretive Method:
PER IEEE C57.104-2008
(most recent sample)
Hydrogen within condition 1 limits (100 ppm).
Methane within condition 1 limits (120 ppm).
Ethane within condition 1 limits (65 ppm).
Ethylene within condition 1 limits (50 ppm).
Acetylene within condition 1 limits (1 ppm).
Carbon Monoxide: Condition 2 Indications of overheated cellulose insulation (350 ppm).
Carbon Dioxide: Condition 3 Significant Indications of overheated cellulose insulation (4000 ppm).
TDCG within condition 1 limits (720 ppm).
DGA TDCG Rate Interpretive Method:
PER IEEE C57.104-2008
(two most recent sample)
No previous sample available.
DGA Cellulose (Paper) Insulation: CO2/CO >= 10: Indication of thermal decomposition of cellulose insulation.
WDS DGA Condition Code:
WDS Recommended Action:
CAUTION
Resample at earliest opportunity to establish gas generation rate.
Comment:
General Oil Quality (GOQ)
D-15331 Moisture in Oil (ppm): 4
D-9711 Interfacial Tension (dynes/cm): 29.87
D-9741 Acid Number (mg KOH/g): 0.029
D-15001 Color Number (Relative): L3.0
D-15241 Visual Exam. (Relative): CLR&SPRK
D-15241 Sediment Exam. (Relative): ND
D-8771 Dielectric Breakdown (kV): 48
D-9241 Power Factor @ 25C (%): 0.040
D-1298 Specific Gravity (Relative): 0.8724
GOQ Diagnostics Moisture in Oil: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (20 ppm max).
PER IEEE C57.106-2006 Interfacial Tension: Exceeds limit for equipment >= 230 kV for in-service oil - kV not provided (32 dynes/cm min).
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774070
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: PCT785002 Mfr: Control#: 6774070
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004458 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: 501
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774070-473705-00
(most recent sample) Acid Number: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.1 mg KOH/g max).
Color Number and Visual: Diagnostic not applicable. Diagnostic not applicable.
Dielectric Breakdown D-877: Diagnostic not applicable.
Power Factor @25C: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.5% max).
Comment:
End of Test Report
Authorized By:
KENNETH COCCIA
LABORATORY SUPERVISOR
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774072
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: PCT785001 Mfr: Control#: 6774072
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004462 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: 502
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774072-473705-00
Dissolved Gas Analysis (DGA) Hydrogen (H2) (ppm): 7
ASTM Methane (CH4) (ppm): 24
D-36121 Ethane (C2H6) (ppm): 18
Ethylene (C2H4) (ppm): 7
Acetylene (C2H2) (ppm): <1
Carbon Monoxide (CO) (ppm): 518
Carbon Dioxide (CO2) (ppm): 11442
Nitrogen (N2) (ppm): 67370
Oxygen (O2) (ppm): 2646
Total Dissolved Gas (TDG) (ppm): 82032
Total Dissolved Combustible Gas (TDCG) (ppm): 574
Equivalent TCG (%): 0.5633
DGA
Diagnostics
DGA Keys Gas / Interpretive Method:
PER IEEE C57.104-2008
(most recent sample)
Hydrogen within condition 1 limits (100 ppm).
Methane within condition 1 limits (120 ppm).
Ethane within condition 1 limits (65 ppm).
Ethylene within condition 1 limits (50 ppm).
Acetylene within condition 1 limits (1 ppm).
Carbon Monoxide: Condition 2 Indications of overheated cellulose insulation (350 ppm).
Carbon Dioxide: Condition 4 Severe Indications of overheated cellulose insulation (10000 ppm).
TDCG within condition 1 limits (720 ppm).
DGA TDCG Rate Interpretive Method:
PER IEEE C57.104-2008
(two most recent sample)
No previous sample available.
DGA Cellulose (Paper) Insulation: CO2/CO >= 10: Indication of thermal decomposition of cellulose insulation.
WDS DGA Condition Code:
WDS Recommended Action:
WARNING
Resample at earliest opportunity to establish gas generation rate.
Comment:
General Oil Quality (GOQ)
D-15331 Moisture in Oil (ppm): 28
D-9711 Interfacial Tension (dynes/cm): 30.5
D-9741 Acid Number (mg KOH/g): 0.037
D-15001 Color Number (Relative): L2.5
D-15241 Visual Exam. (Relative): CLR&SPRK
D-15241 Sediment Exam. (Relative): ND
D-8771 Dielectric Breakdown (kV): 48
D-9241 Power Factor @ 25C (%): 0.058
D-1298 Specific Gravity (Relative): 0.8731
GOQ Diagnostics Moisture in Oil: Exceeds limit for equipment >= 230 kV for in-service oil - kV not provided (20 ppm max).
PER IEEE C57.106-2006 Interfacial Tension: Exceeds limit for equipment >= 230 kV for in-service oil - kV not provided (32 dynes/cm min).
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774072
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: PCT785001 Mfr: Control#: 6774072
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004462 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: 502
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774072-473705-00
(most recent sample) Acid Number: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.1 mg KOH/g max).
Color Number and Visual: Diagnostic not applicable. Diagnostic not applicable.
Dielectric Breakdown D-877: Diagnostic not applicable.
Power Factor @25C: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.5% max).
Comment:
End of Test Report
Authorized By:
KENNETH COCCIA
LABORATORY SUPERVISOR
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774074
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 979006945 Mfr: Control#: 6774074
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004452 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: 508
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774074-473705-00
Dissolved Gas Analysis (DGA) Hydrogen (H2) (ppm): 13
ASTM Methane (CH4) (ppm): 22
D-36121 Ethane (C2H6) (ppm): <1
Ethylene (C2H4) (ppm): 20
Acetylene (C2H2) (ppm): <1
Carbon Monoxide (CO) (ppm): 702
Carbon Dioxide (CO2) (ppm): 2508
Nitrogen (N2) (ppm): 63313
Oxygen (O2) (ppm): 1167
Total Dissolved Gas (TDG) (ppm): 67745
Total Dissolved Combustible Gas (TDCG) (ppm): 757
Equivalent TCG (%): 0.8331
DGA
Diagnostics
DGA Keys Gas / Interpretive Method:
PER IEEE C57.104-2008
(most recent sample)
Hydrogen within condition 1 limits (100 ppm).
Methane within condition 1 limits (120 ppm).
Ethane within condition 1 limits (65 ppm).
Ethylene within condition 1 limits (50 ppm).
Acetylene within condition 1 limits (1 ppm).
Carbon Monoxide: Condition 3 Indications of significantly overheated cellulose insulation (570 ppm).
Carbon Dioxide: Condition 2 Indications of overheated cellulose insulation (2500 ppm).
TDCG: Condition 2 Levels exceed normal concentrations. Fault may be present (720 ppm).
DGA TDCG Rate Interpretive Method:
PER IEEE C57.104-2008
(two most recent sample)
No previous sample available.
DGA Cellulose (Paper) Insulation: CO2/CO Ratio not applicable - at least one gas doesn't exceed its limit.
WDS DGA Condition Code:
WDS Recommended Action:
CAUTION
Resample at earliest opportunity to establish gas generation rate.
Comment:
General Oil Quality (GOQ)
D-15331 Moisture in Oil (ppm): 5
D-9711 Interfacial Tension (dynes/cm): 30.89
D-9741 Acid Number (mg KOH/g): 0.018
D-15001 Color Number (Relative): L1.5
D-15241 Visual Exam. (Relative): CLR&SPRK
D-15241 Sediment Exam. (Relative): ND
D-8771 Dielectric Breakdown (kV): 48
D-9241 Power Factor @ 25C (%): 0.032
D-1298 Specific Gravity (Relative): 0.8714
GOQ Diagnostics Moisture in Oil: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (20 ppm max).
PER IEEE C57.106-2006 Interfacial Tension: Exceeds limit for equipment >= 230 kV for in-service oil - kV not provided (32 dynes/cm min).
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774074
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 979006945 Mfr: Control#: 6774074
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004452 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: 508
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774074-473705-00
(most recent sample) Acid Number: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.1 mg KOH/g max).
Color Number and Visual: Diagnostic not applicable. Diagnostic not applicable.
Dielectric Breakdown D-877: Diagnostic not applicable.
Power Factor @25C: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.5% max).
Comment:
End of Test Report
Authorized By:
KENNETH COCCIA
LABORATORY SUPERVISOR
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774076
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 89V5439 Mfr: Control#: 6774076
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004434 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: T-A
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774076-473705-00
Dissolved Gas Analysis (DGA) Hydrogen (H2) (ppm): 55
ASTM Methane (CH4) (ppm): 17
D-36121 Ethane (C2H6) (ppm): 3
Ethylene (C2H4) (ppm): 33
Acetylene (C2H2) (ppm): <1
Carbon Monoxide (CO) (ppm): 582
Carbon Dioxide (CO2) (ppm): 5880
Nitrogen (N2) (ppm): 74122
Oxygen (O2) (ppm): 673
Total Dissolved Gas (TDG) (ppm): 81365
Total Dissolved Combustible Gas (TDCG) (ppm): 690
Equivalent TCG (%): 0.6945
DGA
Diagnostics
DGA Keys Gas / Interpretive Method:
PER IEEE C57.104-2008
(most recent sample)
Hydrogen within condition 1 limits (100 ppm).
Methane within condition 1 limits (120 ppm).
Ethane within condition 1 limits (65 ppm).
Ethylene within condition 1 limits (50 ppm).
Acetylene within condition 1 limits (1 ppm).
Carbon Monoxide: Condition 3 Indications of significantly overheated cellulose insulation (570 ppm).
Carbon Dioxide: Condition 3 Significant Indications of overheated cellulose insulation (4000 ppm).
TDCG within condition 1 limits (720 ppm).
DGA TDCG Rate Interpretive Method:
PER IEEE C57.104-2008
(two most recent sample)
No previous sample available.
DGA Cellulose (Paper) Insulation: CO2/CO >= 10: Indication of thermal decomposition of cellulose insulation.
WDS DGA Condition Code:
WDS Recommended Action:
CAUTION
Resample at earliest opportunity to establish gas generation rate.
Comment:
General Oil Quality (GOQ)
D-15331 Moisture in Oil (ppm): 7
D-9711 Interfacial Tension (dynes/cm): 32.12
D-9741 Acid Number (mg KOH/g): 0.017
D-15001 Color Number (Relative): L1.5
D-15241 Visual Exam. (Relative): CLR&SPRK
D-15241 Sediment Exam. (Relative): TRACE
D-8771 Dielectric Breakdown (kV): 51
D-9241 Power Factor @ 25C (%): 0.021
D-1298 Specific Gravity (Relative): 0.8735
GOQ Diagnostics Moisture in Oil: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (20 ppm max).
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774076
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 89V5439 Mfr: Control#: 6774076
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004434 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: T-A
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774076-473705-00
PER IEEE C57.106-2006 Interfacial Tension: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (32 dynes/cm min).
(most recent sample) Acid Number: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.1 mg KOH/g max).
Color Number and Visual: Diagnostic not applicable. Diagnostic not applicable.
Dielectric Breakdown D-877: Diagnostic not applicable.
Power Factor @25C: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.5% max).
Comment:
End of Test Report
Authorized By:
KENNETH COCCIA
LABORATORY SUPERVISOR
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774080
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 89V5445 Mfr: Control#: 6774080
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004457 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: T-B
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774080-473705-00
Dissolved Gas Analysis (DGA) Hydrogen (H2) (ppm): 34
ASTM Methane (CH4) (ppm): 19
D-36121 Ethane (C2H6) (ppm): 6
Ethylene (C2H4) (ppm): 11
Acetylene (C2H2) (ppm): <1
Carbon Monoxide (CO) (ppm): 620
Carbon Dioxide (CO2) (ppm): 6118
Nitrogen (N2) (ppm): 65607
Oxygen (O2) (ppm): 930
Total Dissolved Gas (TDG) (ppm): 73345
Total Dissolved Combustible Gas (TDCG) (ppm): 690
Equivalent TCG (%): 0.7669
DGA
Diagnostics
DGA Keys Gas / Interpretive Method:
PER IEEE C57.104-2008
(most recent sample)
Hydrogen within condition 1 limits (100 ppm).
Methane within condition 1 limits (120 ppm).
Ethane within condition 1 limits (65 ppm).
Ethylene within condition 1 limits (50 ppm).
Acetylene within condition 1 limits (1 ppm).
Carbon Monoxide: Condition 3 Indications of significantly overheated cellulose insulation (570 ppm).
Carbon Dioxide: Condition 3 Significant Indications of overheated cellulose insulation (4000 ppm).
TDCG within condition 1 limits (720 ppm).
DGA TDCG Rate Interpretive Method:
PER IEEE C57.104-2008
(two most recent sample)
No previous sample available.
DGA Cellulose (Paper) Insulation: Normal decomposition of cellulose insulation.
WDS DGA Condition Code:
WDS Recommended Action:
CAUTION
Resample at earliest opportunity to establish gas generation rate.
Comment:
General Oil Quality (GOQ)
D-15331 Moisture in Oil (ppm): 21
D-9711 Interfacial Tension (dynes/cm): 41.11
D-9741 Acid Number (mg KOH/g): 0.015
D-15001 Color Number (Relative): L0.5
D-15241 Visual Exam. (Relative): CLR&SPRK
D-15241 Sediment Exam. (Relative): ND
D-8771 Dielectric Breakdown (kV): 54
D-9241 Power Factor @ 25C (%): 0.022
D-1298 Specific Gravity (Relative): 0.8722
GOQ Diagnostics Moisture in Oil: Exceeds limit for equipment >= 230 kV for in-service oil - kV not provided (20 ppm max).
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774080
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 89V5445 Mfr: Control#: 6774080
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004457 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: T-B
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774080-473705-00
PER IEEE C57.106-2006 Interfacial Tension: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (32 dynes/cm min).
(most recent sample) Acid Number: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.1 mg KOH/g max).
Color Number and Visual: Diagnostic not applicable. Diagnostic not applicable.
Dielectric Breakdown D-877: Diagnostic not applicable.
Power Factor @25C: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (0.5% max).
Comment:
End of Test Report
Authorized By:
KENNETH COCCIA
LABORATORY SUPERVISOR
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774088
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 89V5437 Mfr: Control#: 6774088
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year Mf'd: Received: 04/22/2015
ATTN: STEVE JONES Breathing: SEAL Syringe ID: 53004437 Reported: 04/30/2015
PO#: 4367-100162 Bank: Phase: Bottle ID:
Project ID: ELY8013 Fluid: MIN Sampled By:
Customer ID: T-C
WEIDMANN ELECTRICAL TECHNOLOGY
3430 PROGRESS DRIVE, UNIT B + BENSALEM, PA + 19020
215 639 8599 + 215 639 8577
WWW.WEIDMANN-DIAGNOSTICS.COM
TEST REPORT
01-6774088-473705-00
Dissolved Gas Analysis (DGA) Hydrogen (H2) (ppm): 22
ASTM Methane (CH4) (ppm): 9
D-36121 Ethane (C2H6) (ppm): 2
Ethylene (C2H4) (ppm): 4
Acetylene (C2H2) (ppm): <1
Carbon Monoxide (CO) (ppm): 508
Carbon Dioxide (CO2) (ppm): 5652
Nitrogen (N2) (ppm): 65245
Oxygen (O2) (ppm): <500
Total Dissolved Gas (TDG) (ppm): 71874
Total Dissolved Combustible Gas (TDCG) (ppm): 545
Equivalent TCG (%): 0.6176
DGA
Diagnostics
DGA Keys Gas / Interpretive Method:
PER IEEE C57.104-2008
(most recent sample)
Hydrogen within condition 1 limits (100 ppm).
Methane within condition 1 limits (120 ppm).
Ethane within condition 1 limits (65 ppm).
Ethylene within condition 1 limits (50 ppm).
Acetylene within condition 1 limits (1 ppm).
Carbon Monoxide: Condition 2 Indications of overheated cellulose insulation (350 ppm).
Carbon Dioxide: Condition 3 Significant Indications of overheated cellulose insulation (4000 ppm).
TDCG within condition 1 limits (720 ppm).
DGA TDCG Rate Interpretive Method:
PER IEEE C57.104-2008
(two most recent sample)
No previous sample available.
DGA Cellulose (Paper) Insulation: CO2/CO >= 10: Indication of thermal decomposition of cellulose insulation.
WDS DGA Condition Code:
WDS Recommended Action:
CAUTION
Resample at earliest opportunity to establish gas generation rate.
Comment:
General Oil Quality (GOQ)
D-15331 Moisture in Oil (ppm): 18
D-9711 Interfacial Tension (dynes/cm): 39.26
D-9741 Acid Number (mg KOH/g): 0.014
D-15001 Color Number (Relative): L0.5
D-15241 Visual Exam. (Relative): CLR&SPRK
D-15241 Sediment Exam. (Relative): ND
D-8771 Dielectric Breakdown (kV): 56
D-9241 Power Factor @ 25C (%): 0.030
D-1298 Specific Gravity (Relative): 0.8735
GOQ Diagnostics Moisture in Oil: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (20 ppm max).
PER IEEE C57.106-2006 Interfacial Tension: Acceptable for equipment >= 230 kV for in-service oil - kV not provided (32 dynes/cm min).
Notations: 1. Analysis is ISO/IEC 17025:2005 accredited, L-A-B Accredited Certificate Number L2303.02 2. This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has received ISO Standard 17025 accreditation for this test. 5.
This test is conducted by Weidmann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 accreditation for this test. 7. Imported Sample: WEIDMANN Electrical Technology accepts no responsibility for these results;
accreditation status does not apply to these results. 8. Imported Equipment
Accreditation applies to current analysis only. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. WEIDMANN Electrical Technology does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. Any interpretations or opinions expressed represent the best judgment of WEIDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or representation, expressed or implied as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever. This test report shall not be reproduced except in full, without written approval of the laboratory.
Lab Control Number: 6774088
Order Number: 473705
Oil Temp:
Eaton Corp Serial#: 89V5437 Mfr: Control#: 6774088
7451 COCA COLA DRIVE Location: VA MEDICAL kV: Order#: 473705
SUITE A Equipment: TRANSFORMER kVA: Account: 568
HANOVER, MD 21076 US Compartment: MAIN(BOTTOM) Year…