36C24518B0233-008.pdf

PDF 3 MB Posted

Attached to
CONST DOM CLINIC & CLC ADMIN PROJ 613-121 Federal contract opportunity
Solicitation number
36C24518B0233
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 5

About this file

36C24518B0233 6 Mechanical Drawings.pdf

View the file

Other files for this federal contract opportunity

Other files attached to CONST DOM CLINIC & CLC ADMIN PROJ 613-121, newest first.
File Type Posted
36C24518C0215-000.docx DOCX document
36C24518B0233-0001001.pdf PDF
36C24518B0233-0001000.docx DOCX document
36C24518B0233-009.pdf PDF
36C24518B0233-007.pdf PDF
36C24518B0233-001.docx DOCX document
36C24518B0233-002.pdf PDF
36C24518B0233-010.pdf PDF
36C24518B0233-003.pdf PDF
36C24518B0233-013.pdf PDF
36C24518B0233-012.pdf PDF
36C24518B0233-011.pdf PDF
36C24518B0233-005.pdf PDF
36C24518B0233-004.pdf PDF
36C24518B0233-006.pdf PDF
36C24518B0233-000.docx DOCX document
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

# DEMOLITION NOTE IDENTIFICATION

INDICATES ITEM TO BE REMOVED

FLEXIBLE DUCT CONNECTION

VERTICAL FIRE DAMPER

VOLUME DAMPER

CEILING RETURN, EXHAUST OR TRANSFER REGISTER

CEILING SUPPLY DIFFUSER

MITERED ELBOW WITH TURNING VANES

RETURN DUCT TURNING UP

RETURN DUCT TURNING DOWN

EXHAUST DUCT TURNING UP

EXHAUST DUCT TURNING DOWN

SUPPLY DUCT TURNING UP (ROUND OR RECTANGULAR)

SUPPLY DUCT TURNING DOWN (ROUND OR RECTANGULAR)

10"x10" SQUARE OR RECTANGULAR DUCTWORK

PIPE TURNING UP

PIPE TURNING DOWN

THERMOSTAT (C=COOLING, H=HEATING,

H,C=HEATING AND COOLING

DUCT SMOKE DETECTOR

G

(CFM)

EXHAUST GRILLE DESIGNATION

WITH CFM INDICATED

A

(CFM)

CEILING DIFFUSER DESIGNATION

WITH CFM INDICATED

G20/20 RETURN GRILLE DESIGNATION

GENERAL

DUCTWORK

MOTORIZED CONTROL DAMPER

INDICATES ROUND DUCTWORK

FLEXIBLE CONNECTION

RETURN, EXHAUST OR TRANSFER AIR FLOW

SUPPLY AIR FLOW

ACCESS DOORAD

ABOVE FINISHED FLOORAFF

ABOVE FINISHED GRADEAFG

ALUMINUMALUM

ARCHITECTURALARCH

DIAMETERDIA

DRAWINGDWG

EXISTINGEX

EXISTING TO REMAINEXR

GAUGEGA

GOVERNMENT FURNISHED

CONTRACTOR INSTALLED

GFCI

MISCELLANEOUSMISC

NOT IN CONTRACTNIC

TYPICALTYP

UNLESS OTHERWISE

NOTED

UON

GALVANIZEDGALV

RUN THRU JOISTSRBJ

REMOVE EXISTINGREX

AUTOMATIC AIR VENT

VALVES AND ACCESSORIES

AUTOMATIC FLOW CONTROL VALVE

BACKFLOW PREVENTER

BALL VALVE

BOTTOM CONNECTION

BUTTERFLY VALVE

CAPPED PIPE

CHECK VALVE

CLEAN OUT

CONCENTRIC REDUCER

DIRECTION OF FLOW

ECCENTRIC REDUCER

FLANGED CONNECTION

FLEXIBLE CONNECTION

FLOW METER

BALL VALVE FOR 2" & UNDER

BUTTERFLY FOR 2.5" AND LARGER

GLOBE VALVE

MANUAL AIR VENT

METERED BALANCING VALVE

W/PRESSURE TAPS

PRESSURE/TEMPERATURE TEST PLUG

PT

NEEDLE VALVE

PLUG VALVE

PIPE ANCHOR (W=WALL, C=CEILING, F=FLOOR)

W,C,F

PIPE GUIDE

PIPE SLEEVE

PITCH

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

PRESSURE GAUGE WITH GAUGE COCK

SQUARE HEAD COCK

STEAM TRAP

STRAINER

STRAINER W/BLOW DOWN VALVE

THREE WAY CONTROL VALVE

TWO WAY CONTROL VALVE

THERMOMETER

THERMOSTATIC RADIATOR VALVE

TOP CONNECTION

UNION

VACUUM BREAKER

VALVE IDENTIFICATION

CONTROLS

ANALOG INPUT (TO PANEL)

ANALOG OUTPUT (OUT OF PANEL)

DIGITAL INPUT (TO PANEL)

DIGITAL OUTPUT (OUT OF PANEL)

TWO WAY CONTROL VALVE

THREE WAY CONTROL VALVE

BYPASS TIMER SWITCH

COMMON

CONTROL WIRING (SIGNAL PATH)

DATA TERMINAL CABINET

DIFFERENTIAL PRESSURE SWITCH

DIFFERENTIAL PRESSURE SENSOR

DUCT SMOKE DETECTOR

FAN ON-OFF SWITCH

FAN VARIABLE SPEED SWITCH

AI

DI

DO

C

FLOW MEASURING SYSTEM

FIRESTAT

FREEZESTAT

HIGH LIMIT TEMPERATURE SENSOR

HUMIDISTAT

LOW LIMIT TEMPERATURE SENSOR

LOCAL TEMPERATURE CONTROL PANEL

MOTOR

MOTORIZED CONTROL DAMPER

MOTOR STARTER

NORMALLY CLOSEDNC

NORMALLY OPENEDNO

POWER WIRINGEP

SENSOR

STATIC PRESSURE SENSOR

STATIC TOTALIZER STATION

SWITCH

ZONE TEMPERATURE SENSOR

TEMPERATURE TRANSMITTER

H,C

TIME CLOCK

VALVE IDENTIFICATION

CSR CURRENT SENSING RELAY

NORMALLY OPEN CONTROLS

NORMALLY CLOSED CONTROLS

CWR

CHS

CHR

CDWS

HRS

HRR

HPS

HPC

FOR

FOS

FOV

CDWR

MPS

MPC

HWS

HWR

LPS

PC

V

RS

RL

G

LPC

D

DFR

DFS

CWS

RHG

CHILLED WATER RETURN

MEDIUM PRESSURE CONDENSATE

DOMESTIC HOT WATER RECIRCULATING

HEAT RECOVERY RETURN

HIGH PRESSURE STEAM

NATURAL GAS PIPING

MEDIUM PRESSURE STEAM

LOW PRESSURE STEAM

HOT WATER SUPPLY

HOT WATER RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

STEAM VENT LINE

PUMPED CONDENSATE

LOW PRESSURE CONDENSATE

HIGH PRESSURE CONDENSATE

DIRECTION OF FLOW

DIESEL FUEL RETURN

DIESEL FUEL SUPPLY

DOMESTIC HOT WATER

DOMESTIC COLD WATER

FUEL OIL SUPPLY

FUEL OIL RETURN

HEAT RECOVERY SUPPLY

FUEL OIL VENT

CONDENSATE DRAIN LINE

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

CHILLED/HOT WATER SUPPLY

CHILLED/HOT WATER RETURN

CHILLED WATER SUPPLY

REFRIGERANT HOT GAS

PIPING

FLEXIBLE DUCT CONNECTION

LEGEND

M

M

M

AO

S

P

T

TT

TC

DTC

DPS

DSD

FMS

FZ

HL

LL

TCP

MS

STS

V-1

BT

DP

F

VSF

FS

H

S

T

SUPPLY DUCT TURNING UP (OVAL)

SUPPLY DUCT TURNING DOWN (OVAL)

10"/10" OVAL DUCTWORK

SD

V-1

# CONSTRUCTION NOTE IDENTIFICATION

INDICATES NEW ITEM

INDICATES EXISTING ITEM

REMOVE TO THIS POINT

CONNECT NEW TO EXISTING

ROOM NUMBER IDENTIFICATIONXXX

Ø

WITH ASSOCIATED EQUIPMENT ID

VAV-X-X

1.

2.

3.

4.

5.

7.

8.

9.

16.

15.

14.

13.

12.

11.

10.

6.

17.

18.

19.

20.

GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH

MECHANICAL DRAWING OF THIS SET. NOTES SPECIFIC TO

INDIVIDUAL MECHANICAL DRAWINGS WILL BE SHOWN ON THE

RESPECTIVE MECHANICAL DRAWING.

THE CONTRACTOR SHALL PROVIDE A COMPLETE HVAC SYSTEM

TO INCLUDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENT

FOR A COMPLETE AND FUNCTIONAL SYSTEM INCLUDING ALL

NECESSARY APPURTENANCES CUSTOMARILY INCLUDED IF NOT

SPECIFICALLY CALLED OUT.

ENTIRE INSTALLATION, INCLUDING MATERIALS, EQUIPMENT, AND

WORKMANSHIP, SHALL CONFORM WITH ALL APPLICABLE LAWS,

CODES, AND REGULATIONS OF MUNICIPAL, STATE AND FEDERAL

AUTHORITIES.

THIS PROJECT SHALL CONFORM TO APPLICABLE ASHRAE, NFPA,

AND SMACNA STANDARDS AND OTHER REGULATORY BODIES

HAVING JURISDICTION OVER THE CLASS OF WORK.

MATERIALS AND EQUIPMENT SHALL HAVE STAMPS OR SEALS OF

ARI, ASME, UL, AND ASTM.

THE CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE AND

APPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OF

APPLICABLE REGULATORY AGENCIES. REQUIRED TESTS SHALL

BE PERFORMED IN THE PRESENCE OF THE GOVERNMENT

UNLESS OTHERWISE WAIVED IN WRITING.

THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS,

LICENSES, DOCUMENTS, AND SERVICES RELATED TO

INSTALLATION OF THE WORK.

EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BE

FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT IS

APPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICE,

CIRCUIT BREAKERS AND CONDUIT SIZES ARE APPROPRIATELY

MODIFIED AT NO COST TO THE OWNER.

THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE

OTHER TRADES IN ORDER TO RESOLVE ANY CONFLICT THAT

MIGHT ARISE DUE TO THE LOCATION OF EQUIPMENT OR THE USE

OF SPACE.

RUN ALL HORIZONTAL PIPING AND DUCTWORK ABOVE CEILING

UNLESS OTHERWISE NOTED.

CUT OPENINGS, AS REQUIRED, IN THE EXISTING CONSTRUCTION

FOR THE INSTALLATION OF PIPING, DUCTWORK, AND EQUIPMENT.

PATCH AND REPAIR TO MATCH THE EXISTING ADJACENT

CONSTRUCTION.

ALL ELBOWS IN DUCTWORK SHALL BE RADIUS ELBOWS UNLESS

OTHERWISE NOTED. WHERE SQUARE ELBOWS ARE SHOWN,

INSTALL TURNING VANES.

MAKE DUCT PENETRATIONS OF ALL WALLS WITH SHEET METAL

DUCTS. FLEXIBLE DUCT PENETRATIONS OF WALLS ARE NOT

ACCEPTABLE.

REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR

EXACT LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES.

FINISH AND COLOR TO BE SELECTED BY GOVERNMENT FROM

MANUFACTURER'S STANDARD PALETTE.

DO NOT INSTALL EQUIPMENT, PIPING OR DUCTWORK OVER ANY

ELECTRICAL EQUIPMENT OR ELECTRICAL SERVICE SPACE.

PROVIDE DYNAMIC FIRE DAMPERS IN ACCORDANCE WITH THEIR U.L.

LISTING AND THE REQUIREMENTS OF NFPA-90A.

EXTEND DRAIN LINES TO NEAREST DRAIN OR AS INDICATED. ALL

CONDENSATE DRAIN PIPING SHALL BE TRAPPED AND PITCHED

DOWN IN DIRECTION OF FLOW A MINIMUM OF 1/8" PER FOOT.

LAYOUT OF PIPING AND DUCTWORK IS DIAGRAMMATIC. RUN ALL

EXPOSED PIPING AND DUCTWORK AS HIGH AS POSSIBLE UNLESS

OTHERWISE NOTED. ALLOW FOR RISES, DROPS AND OFFSETS AS

REQUIRED.

DUCTWORK SIZES ARE INSIDE CLEAR DIMENSIONS.

INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING,

MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT

COMPONENTS. AS MUCH AS PRACTICAL, CONNECT EQUIPMENT FOR

EASE OF DISCONNECTING, WITH A MINIMUM OF INTERFERENCE WITH

OTHER INSTALLATIONS. PIPING SHALL NOT INTERFERE WITH FILTER

PULL.

21.

22.

23.

24.

25.

26.

27.

31.

30.

29.

28.

MECHANICAL CONTRACTOR SHALL PROVIDE AUTOMATIC CONTROL DEVICES,

SUCH AS TEMPERATURE SENSORS, RELAYS, PRESSURE SWITCHES WHICH ARE

ASSOCIATED WITH MECHANICAL EQUIPMENT AND ASSOCIATED CONTROL

WIRING FROM STARTER TO THE CONTROL DEVICE. ELECTRICAL CONTRACTOR

SHALL PROVIDE CONDUIT AND WIRING FROM POWER SOURCE TO DISCONNECT

SWITCH, FROM DISCONNECT SWITCH TO STARTER, AND FROM STARTER TO THE

EQUIPMENT.

ALIGN THERMOSTATS WITH LIGHT SWITCHES.

PROVIDE AUXILIARY DRAIN PANS UNDER EQUIPMENT LOCATED ABOVE

CEILINGS.

ALL VALVES ARE FULL LINE SIZE EXCEPT CONTROL AND BALANCING VALVES.

PROVIDE PRESSURE/TEMPERATURE (P/T) PLUGS, WITH CAPS UP AND

DOWNSTREAM OF ALL EQUIPMENT, AT THE SUPPLY AND RETURN TAPS OF

ALL PIPING BRANCHES AND/OR WHERE INDICATED. PROVIDE EXTENDED

PLUGS AND LABELS WHERE PIPING IS INSULATED. PROVIDE REMOVABLE

INSULATION PLUG.

PROVIDE FLUSHING VALVES AND TEES AT BOTH SIDES OF ALL

EQUIPMENT. TAPS SHALL MATCH EQUIPMENT PIPING UP TO 1". FOR

LARGER EQUIPMENT AND PIPE LOOPS PROVIDE 1 1/2" TAPS AND

VALVES.

PROVIDE MANUAL AIR VENTS AT ALL HIGH SPOTS AND THE ENDS OF ALL

PIPING LOOPS. PROVIDE 1/2" DRAIN VALVES AT LOW POINTS IN PIPING.

PROVIDE MINIMUM PITCH SUFFICIENT TO INSURE ADEQUATE VENTING AND

DRAINING.

LOCATE AND SIZE 5 1/2" THICK CONCRETE HOUSEKEEPING PADS AND

CURBS IN ACCORDANCE WITH ACTUAL EQUIPMENT PURCHASED.

EXTEND PAD BEYOND EQUIPMENT FOR 6" IN ALL DIRECTIONS.

ALL EQUIPMENT REMOVED FROM THE BUILDING, DURING DEMOLITION,

SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE

REMOVED FROM THE SITE UNLESS OTHERWISE NOTED.

EXISTING DUCT, PIPE AND EQUIPMENT SIZES NOTED ARE FOR THE

CONVENIENCE OF THE CONTRACTOR ONLY AND ARE NOT WARRANTED

TO BE CORRECT. THE CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING DUCT, PIPE AND EQUIPMENT SIZES AND THEIR RESPECTIVE

LOCATIONS BEFORE PROCEEDING WITH ANY ASSOCIATED WORK.

PRIOR TO SUBMITTING A PROPOSAL THE CONTRACTOR IS

STRONGLY ENCOURAGED TO VISIT THE SITE AND THOROUGHLY

INSPECT ALL EXISTING CONDITIONS TO INSURE THAT THE WORK

REPRESENTED ON THE DRAWINGS CAN BE INSTALLED AS

INDICATED.

GENERAL NOTES

REFER TO ELECTRICAL DRAWINGS FOR VOLTAGE AND PHASE

REQUIREMENTS FOR ALL EQUIPMENT REQUIRING AN ELECTRICAL

CONNECTION.

32.

th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

MECHANICAL LEGEND AND GENERAL NOTES CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

M001

613-121

JUNE 27, 2018 WAW WNW

501D & 502F501D & 502F501D & 502F

C-107

438 SQ. FT.

C-108

808 SQ. FT.

C-109

549 SQ. FT.

C-109A

132 SQ. FT.

C-110

181 SQ. FT.

CW-1

507 SQ. FT.

C-112

150 SQ. FT.

E-1

88 SQ. FT.

C-113

450 SQ. FT.

C-114

396 SQ. FT.

C-111

63 SQ. FT.

C-125

3,053 SQ. FT.

C-124

111 SQ. FT.

C-126

1688 SQ. FT.

623 SQ. FT.660 SQ. FT.

CC-4

368 SQ. FT.

WOMEN'S LOCKER

MECHANICAL ROOM

ELECTRIC ROOM

GENERATOR ROOM

STAIR # 1

WALKWAY

SERVICE ELEVATOR

LOBBY

ELEV.

SOILED UTILITY

PHARMACY

OXYGEN STORAGE

DINING

TOILET

RECREATION

CORRIDOR

UPDN.

D.F.

F.E.C.

F.E.C.

RE

QE

10.59E 12E 12.2E 14E 15E 16E7.4E 16.6E6.5 7.5 8.4 th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

FIRST FLOOR DEMO PLAM - CLC ADMIN CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MD101

613-121

JUNE 27, 2018 WAW WNW

1/8" = 1'-0"

FIRST FLOOR DEMO PLAN - CLC ADMIN

1. REMOVE EXISTING HEATING UNIT AND ALL ASSOCIATED

CONTROLS, DUCTWORK, ETC RENDERED USELESS BY THE

REMOVAL OF THE UNIT.

2. CAP HOT WATER PIPING, REPAIR INSULATION.

3. REMOVE SUPPLY AND RETURN GRILLES.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

501D

CD-4

CD-3

D-90

D-88

D-86

D-84

D-83

CD-5

CD-6

D-154

D-155

D-156

D-157

D-158

D-177

CD-1

E-138B E-138A

E-138C E-138E-116A

E-116B

E-118

CORRIDOR

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

STORAGE

CORRIDOR

COMMUNITY ROOM

CORRIDOR

2 BEDROOM

TOILET

2 BEDROOM

TOILET

KITCWSENETTE

OFFICE

CORRIDOR

MECWS. RM. ELEC. RM.

TELE. RM.

EMERGENCY

GENERATOR

VENDING

STORAGE

PRIVATE DINING

E .W

.C

AP

T

T

T

T

T

T

3/4" 1"

H W S

H W R

1/ 2"

1/ 2"

3/4"

1/ 2"

2 1/2"

3/4"

H W S

H W R

3"

3"

HWR

HWS

1 1/4"

HWS

HWR 3/4"3/4"1"

3/4"3/4" 3/4"

1"

3/4" 3/4"

3/4"

3/4"

3/4"

1"

3/4"

HWS

HWR

3/4"1" 3/4"

1/2"

3/4"

3/4"3/4" 3/4"

502-TU-2B

2-

TU

2A

HWS

H W S

HWS

H W R

H W R

HWR

HWR

H W R

H W S

1"

4"

3"

3"

3/4"

4" 502 RF1

502-P3

502-P4

4"

4"

4"

HWR

HWS

H W S

INSTANT HW GEN

INSTANT HW GEN

HWR

HWS

C W R C W S

3"3"

3/4"

C W R

C W S

4"

4"

1 1/2"

CWR

CWS

1 1/2"3/4"

CWS

CWR

1"

1 1/2"1" 3/4"

3/4"

1 1/4"

3/4"

3/4"

CWS CWR

3/4"

1 1/4"1 1/4"

3/4"

1/2"

3/4"

3/4"

2 1/2"

3/4"

1 1/4"

1"

C W S

C W R

CWR CWS

4"

6"

4"

4"

6"

6"

6"

6"

2-1/2"

6"

C W S

CWS

CWS

CWR

CWR

CWS

6"

CWS

CWR

FAN COIL UNIT

VA

V

502-TU-1A

th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

FIRST FLOOR DEMO PLAN - DOM CLINIC CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MD102

613-121

JUNE 27, 2018 WAW WNW

1/8" = 1'-0"

FIRST FLOOR DEMO PLAN - DOM CLINIC

1. REMOVE EXISTING CHILLED WATER PUMP. LEAVE

PIPING READY FOR RECONNECTION.

2. REMOVE PIPING TO SCOPE OF WORK MARK. CAP PIPE

AND REPAIR INSULATION.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

502F

A. ALL UTILITY OUTAGES SHALL BE COORDINATED WITH

THE COR. REFER TO SPECIFICATION SECTION 01 00 00

FOR ADDITIONAL INFORMATION.

B. CHILLED WATER SUPPLY SHALL BE MAINTAINED TO

THE EXISTING SYSTEM. REMOVE AND REPLACE

PUMPS ONE AT A TIME.

DNDN

DN

C-108

C-109

C-109A

C-110

CW-1

C-112

E-1

C-113

C-111

C-125

C-126

CC-4

MECHANICAL ROOM

ELECTRIC ROOM

GENERATOR ROOM

STAIR # 1

WALKWAY

SERVICE ELEVATOR

LOBBY

ELEV.

SOILED UTILITY

OXYGEN STORAGE

DINING

TOILET

RECREATION

CORRIDOR

B

IO

M E D

S E R V

IC

E C

O R R

S C -1

M U L E S

T O R A G E

UPDN.

D.F.

F.E.C.

F.E.C.

C

12108 9

H

F

G

K

A

113.41

I

C.4

4.8

QE

10.59.94.5 5.3 6.5 7.5 8.4

AD. ASST.

501D-129

BUS. MAN.

501D-127

PROG. MAN.

501D-126

OFFICE/EXAM

501D-125

OFFICE/EXAM

501D-124

N. ADMIN.

501D-123

SERV. CHIEF.

501D-130

ENTRANCE

501D-131

LANDING

501D-136

COPY /

WORKROOM

501D-120

CUBICLES

501D-128

CORR. B

501D-C4

STAFF T.

501D-133

GUEST T.

501D-117

G. FELLOW

501D-116

G. FELLOW

501D-115

PSYCHOL.

501D-114

N. CASE MAN.

501D-113

OFF. / EX.

501D-112

OFF. / EX.

501D-110

N. CASE MAN.

501D-108

CORRIDOR

501D-C2

OFF. / EX.

501D-111

OFF. / EX.

501D-109

ADMIN. SUPP.

501D-107

WAITING

501D-106

CORR. A

501D-C3

GUEST T.

501D-132

HAC

501D-134

BREAK ROOM

501D-121

LIGHTWELL

501C-125A

ELECTRICAL

501D-104

CORR.

501D-105

LOADING

501D-103

MECHANICAL

501D-102

IT

501D-101

CORRIDOR

501D-C1

CONNECTOR

RAMP

501D-C5

ENTRANCE

501D-100

CONFERENCE

ROOM

501D-122

VAV-1-03

24"x16"

8"ø

6"ø6"ø

VAV-1-02

VAV-1-01

VAV-1-05

VAV-1-06

VAV-1-08

6"ø

8"ø

20"x16"

12"x8" 6"ø 6"ø 6"ø 6"ø

8"ø 8"x8"

5"ø

8"ø

8" x8

12"x8"

6"ø

10"ø

12"x10"

8"ø 6"ø

6"ø 12"x8" 8"ø8"ø

12"ø

5"ø

8"ø

12"x10"

10"ø

8"ø

8"ø

6"ø

8"ø

6"ø

VAV-1-07

VAV-1-04

5"ø 8"ø

5"ø

8"ø

D

D

D

D

B

B

B

B

C

B

B

B

B

A

B

B

B

B

B

C

B

B

B

B

B

B

B

B

B

B

B

B

7"ø

10"ø

12"x10"

8"ø 5"ø

VAV-1-10

VAV-1-13

G

G

G

G

G

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

AC-6AC-5

AC-4

AC-3

AC-2

CU-2

40"x14"

24"x16"

12"x10" 14"x10" 20"x8"

20"x12" 20"x14"

20"x14"20"x12"

"x

"x

16"x10" 8"x8"

8"x8"

8"x6" 6"x6"6"x6" 8"x6"

10"x8"

"x

AC-7

"ø

8"ø12 "x

8"

CU-6 CU-7

MH401

30"x16"

5"ø 8"ø12"x6"

VAV-1-09STOR.

501D-129A

8"ø6"ø 12"x8" 8"x8"

VAV-1-12 CU-8

AC-8

RE

B

B5

C.2

MH401

VAV-1-11

G.5

9.7 9.83.1

1/8" = 1'-0"

FIRST FLOOR DUCTWORK PLAN - CLC ADMIN

th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

FIRST FLOOR DUCTWORK PLAN - CLC ADMIN CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MH101

613-121

JUNE 27, 2018 WAW WNW

1. 10X10 EXHAUST DUCT UP TO EF-1 ON ROOF.

2. 4" OUTSIDE AIR DUCT UP TO ROOF.

3. COORDINATE CONDENSING UNIT LOCATION AS TO NOT

BLOCK FIRE DEPARTMENT CONNECTION ON EXTERIOR OF

BUILDING. PROVIDE CONCRETE PAD UNDER CONDENSING

UNIT.

4. O.A. INTAKE UP TO ROOF INTAKE HOOD.

5. TAP OUT OF BOTTOM OF DUCT. ROUTE DUCT UNDER

BEAM.

6. DUCT TURN DOWN. ROUTE DUCT UNDER BEAM.

7. DUCT THROUGH A SMOKE PARTITION. SEE DETAIL ON

SHEET M502.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

501D

A. THERE IS LIMITED CEILING SPACE. COORDINATE WITH ALL

DISCIPLINES TO PREVENT CONFLICTS.

B. PROVIDE A MANUAL VOLUME DAMPER ON ALL LOW

PRESSURE TAKEOFFS ON SUPPLY, RETURN, AND EXHAUST.

C. SEE SHEET MH105 FOR MECHANICAL WORK REQUIRED IF

ALTERNATE NO.5 - (BID ITEM NO. 6) IS ACCEPTED.

FLOOR DRAIN

CORRIDOR

CD-3

CORRIDOR

D-90

OFFICE

D-88

OFFICE

D-86

OFFICE

D-84

OFFICE

D-83

STORAGE

CD-5

CORRIDOR

D-154

2 BEDROOM

D-155

TOILET

D-156

2 BEDROOM

D-157

TOILET

D-158

KITCHENETTE

CD-1

CORRIDOR

E-138B

MECH. RM.

E-138A

ELEC. RM.RAISED SLAB (TYP.)

E-116B

STORAGE

RAISED SLAB (TYP.)

AP

PSYCH.

502F-127

PSYCH.

502F-129

PSYCH.

502F-125

HAC

502F-122

SOC. WORK.

502F-121

IT

502F-120

PA OFFICE

502F-126DIETICIAN

502F-118

PEER SUPP.

502F-119

DOM SUPV.

SCREEN.

502F-117

DOM STAFF

SCREENER

502F-115

DOM SCREENING

CLERK

502F-113

N. ASSESS.

502F-114

REC. THER.

502F-116

MECHANICAL

502F-128

ELECT

502F-130VESTIBULE

502F-110

SPEC. VEST.

502F-111

N. ASSESS.

502F-109

N. ASSESS.

502F-108

TRIAGE

502F-104

CHECK IN

502F-102

LOBBY

502F-100

PAT. T.

502F-101

WAITING

502F-103

CORR. A

502F-C1

MEDS

502F-106

N. STATION

502F-107

CORR. B

502F-C2

VAV-2-08

VAV-2-07

VAV-2-05

VAV-2-11

VAV-2-10

VAV-2-03

VAV-2-06

VAV-2-04

D

B

B

B

B

B

200B

B

B

A

A

A

C

C

C

C

B

A

D

A

A

A

B

B

B

D

B

B

B

B

B

8"ø

8"ø

20"x15" 20"x15"16"x16"12"x14"

12"ø 16"x15"

10"ø 10"ø

12"ø

10"ø

6"ø

10"ø

10"ø

12"x10"

8"ø 6"ø 8"ø

6"ø

8" x1

0"

"x

"x

5"ø

8"x6"

8"ø 8"ø

8"ø

8"ø

6"ø 6"ø

8"ø

8"ø

6"ø

12"x8"

8"ø

8"ø

8"ø

12"x8"

12"x10"

8"ø

8"ø8"ø

6"ø

12"x12"

7"ø

7"ø

8"ø

12"x8"

8"ø

8"ø

8"ø

7"ø

VAV-2-02

6"ø

"x

8"

AC-1

MANAGER

502F-123

B

170 STAFF T.

502F-124

SPEC. T.

502F-112

18"x12" 14"x12"

22"x14"18"x14" 10"x8"

8"x8"

12"x12"

"x

"x

"x

"x

"x

"x

8" x8

"x

"x

8"

10"x8"

8"x8"

E

175 E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

F

F

VAV-2-09

EF-2

EF-2

EF-2

EF-2

CU-1

VAV-2-01

N. STATION

502F-105

MH401

A

6"ø

AC-9

CU-9

MH401

23 23

22 22

21.4 21.4

21 21

20 20

AA

AA

BB

BB

CC

CC

DD

DD

EE

EE

FF

FF

1/8" = 1'-0"

DOMICILARY DUCTWORK PLAN

th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

FIRST FLOOR DUCTWORK PLAN - DOM CLINIC CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MH102

613-121

JUNE 27, 2018 WAW WNW

1. EXHAUST DUCT UP THROUGH ROOF.

2. ROUTE DUCT UNDER STEEL BEAM AND THEN UP IN

BETWEEN BAR JOIST.

3. TAP OUT OF BOTTOM OF RETURN DUCT.

4. DUCT THROUGH A SMOKE PARTITION. SEE DETAIL ON

SHEET M502.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

502F

A. THERE IS LIMITED CEILING SPACE. COORDINATE WITH

ALL DISCIPLINES TO PREVENT CONFLICTS.

B. CHILLED WATER SUPPLY SHALL BE MAINTAINED TO

THE EXISTING SYSTEM. REMOVE AND REPLACE

PUMPS ONE AT A TIME.

C. PROVIDE A MANUAL VOLUME DAMPER ON ALL LOW

PRESSURE TAKEOFFS ON SUPPLY, RETURN, AND

EXHAUST.

C

12108 9

H

F

G

K

A

I

C.4

4.8 10.59.94.5 5.3 6.5 7.5

EF-1

CU-3

CU-4 CU-5

GV-1

RE

B

B5

C.2

C C C C

G.5

9.7 9.8 th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

ROOF PLAN - CLC ADMIN CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MH103

613-121

JUNE 27, 2018 WAW WNW

1/8" = 1'-0"

ROOF PLAN - CLC ADMIN

1. 4" OUTSIDE AIR DUCT DOWN TO CEILING CASSETTE.

2. REFRIGERANT AND CONDENSATE PIPING DOWN TO

CEILING CASSETTE. SEE SHEET MP101 FOR CONTINUATION.

3. OUTSIDE AIR INTAKE HOOD FOR AHU-1. SEE SHEET

MH101 FOR CONTINUATION.

4. PROVIDE ROOF PIPING SUPPORT. MAXIMUM SPACING

SHALL BE AS DEFINED IN SPECIFICATION SECTIONS 23 21 13

AND 23 23 00.

5. SEE DETAIL ON M502 FOR UNIT SUPPORT.

6. ROUTE CONDENSATE PIPING TO NEAREST ROOF DRAIN.

7. CONDENSATE PIPING UP FROM AC-6.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

501D

6 6 6 6

HWR1 1/2" HWR

HWS1 1/2" HWSCWS2" CWS

CWR2" CWR

GV-1

21.4

AABBCCDDEEFF

th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

ROOF PLAN - DOM CLINIC CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MH104

613-121

JUNE 27, 2018 WAW WNW

1/8" = 1'-0"

ROOF PLAN - DOM CLINIC

1. PIPING DOWN THROUGH ROOF. SEE CONTINUATION ON

SHEET MP102.

2. 6" EXHAUST DUCT TO CEILING MOUNTED EXHAUST FAN.

SEE SHEET MH102 FOR CONTINUATION.

3. OUTDOOR AIR INTAKE HOOD FOR AHU-2. SEE SHEET

MH102 FOR CONTINUATION.

4. PROVIDE ROOF PIPING SUPPORT. MAXIMUM SPACING

SHALL BE AS DEFINED IN SPECIFICATION SECTIONS 23 21

13 AND 23 23 00.

5. PROVIDE FLEXIBLE EXPANSION JOINT TO ALLOW FOR A

1" DEFLECTION BETWEEN BUILDINGS. SEE DETAIL C ON

SHEET M501.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

502F

C-108

C-109

C-109A

C-110

CW-1

C-112

E-1

C-113

C-111

C-125

C-126

CC-4

MECHANICAL ROOM

ELECTRIC ROOM

GENERATOR ROOM

STAIR # 1

WALKWAY

SERVICE ELEVATOR

LOBBY

ELEV.

SOILED UTILITY

OXYGEN STORAGE

DINING

TOILET

RECREATION

CORRIDOR

B

IO

M E D

S E R V

IC

E C

O R R

S C -1

M U L E S

T O R A G E

UPDN.

D.F.

F.E.C.

F.E.C.

C

12108 9

H

F

G

K

A

113.41

I

C.4

4.8

QE

10.59.94.5 5.3 6.5 7.5 8.4

RE

B

B5

C.2

ELECTRICAL

501D-104

LOADING

501D-103

LIGHTWELL

501C-125A

MECHANICAL

501D-102

IT

501D-101

AC-3 AC-4 AC-5 AC-6

AC-2

AC-8

CU-6 CU-7 CU-8

AC-7

UH-1

EF-3

CU-2

UH-ALT

UH-ALT

UH-ALT

UH-ALT

GV-ALT

EF-ALT

EF-ALT

4 44

G.5

9.7 9.83.1 th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

FIRST FLOOR MECHANCIAL PLAN - CLC ADMIN

- ALTERNATE NO.5 - (BID ITEM NO. 6)

CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MH105

613-121

JUNE 27, 2018 WAW WNW

1/8" = 1'-0"

FIRST FLOOR MECHANCIAL PLAN - CLC ADMIN - ALTERNATE NO. 5 - (BID ITEM NO. 6)

1. ELECTRIC UNIT HEATER. MOUNT 10' AFF.

2. EXHAUST FAN ON ROOF, OPEN TO SPACE BELOW.

PROVIDE WITH ROOF CURB AND BACKDRAFT DAMPER.

3. GRAVITY VENTILATOR ON ROOF, OPEN TO SPACE

BELOW. PROVIDE WITH ROOF CURB AND GRAVITY

DAMPER.

4. SEE SHEET MH103 FOR CONDENSING UNIT LOCATION

ON ROOF.

5. 4" OUTSIDE AIR DUCT UP TO ROOF.

6. REFRIGERANT AND CONDENSATE PIPING TO ROOF.

SEE SHEET MH103 FOR CONTINUATION.

7. ROUTE CONDENSATE PIPING TO FLOOR DRAIN IN

MECHANICAL ROOM. FOLLOW AHU HOUSE KEEPING PAD

OVER TO FLOOR DRAIN. SEE PLUMBING DRAWINGS FOR

DRAIN LOCATION.

8. ROUTE REFRIGERANT PIPING UP WALL AND INTO

BUILDING ABOVE CEILING. ROUTE PIPING IN ELECTRICAL

ROOM TO AVOID RUNNING ABOVE A ELECTRICAL PANEL.

9. MOUNT AC-2 DIRECTLY ABOVE THE DOOR. ROUTE

CONDENSATE PIPING THROUGH WALL TO MECHANICAL

ROOM.

10. ROUTE CONDENSATE PIPING TO ROOF DRAIN.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

A. THIS PLAN SHOWS WORK REQUIRED IF BID ITEM NO. 6

IS TAKEN. CLC ADMIN SPACE SHALL BE HEATED AND

VENTILATED ONLY.

501D

F

G

1110.5

EF-3

26"x20"

30"x16"

26"x20"

14"x60"

AHU-1

1-RF1

24"x16"

40"x14"

30"x16"

AVD

AVD

UH-1

MH401PMP-1

H W

S

1/ 2"

H W

S H

W R

1/

2" H

W R

C W

R 2"

C W

R

CWS2" CWS

MECHANICAL

501D-102

1-SH1

DDC

11 1210.5

PMP-1

PMP-2

30"x16"

CB B.5 C.2

12"ø

6"x6" VAV-1-12 5"ø14"x10" 8"x8"

OFFICE/EXAM

501D-124

CORR. A

501D-C3

CC

12"x18"12"x14"

30"x12"

DOM SUPV.

SCREEN.

502F-117

E

CC

40"x16"

2-RF1 AHU-2

24"x16"

24"x24"

EF-4

UH-2

24"x24"

AVD

AVD

MECHANICAL

502F-128

2-SH1

DDC

CC

th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

ENLARGED PLANS CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MH401

613-121

JUNE 27, 2018 WAW WNW

501D & 502F

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

1/4" = 1' - 0" 0 5' 10' 15'1'

1/4" = 1'-0"

LARGE SCALE MECHANICAL ROOM PLAN - CLC ADMIN

1. RELIEF AIR DAMPER.

2. RETURN AIR DAMPER.

3.24X24 O.A. INTAKE UP TO INTAKE HOOD ON ROOF.

OFFSET TO MISS STRUCTURE.

4. CHILLED WATER PUMP IN PARALLEL. MOUNT ON WALL

ABOUT DOMESTIC WATER PUMPS.

5. DOMESTIC WATER PUMPS.

6. 72X30 RELIEF AIR LOUVER ABOVE THE DOOR.

7. DUCT ROUTED BETWEEN JOIST.

1/4" = 1'-0"

CHILLED WATER PUMP SECTION - CLC ADMIN

1/4" = 1'-0"

CLC ADMIN SECTION

1/4" = 1'-0"

DUCT ROUTING SECTION DETAIL - DOM CLINIC

1/4" = 1'-0"

LARGE SCALE MECHANICAL ROOM PLAN - DOM CLINIC

DN

P-1P-2

4" C

W R

4" C

W S

4"

4" CWR

CWS

4"

C W S

C W R

3" CWS

3" CWR

C W S

5" CWS

5" CWR

P-3P-4

H W R

H W S

1"

H W S

H W R

1/2"

1 1/4"

1/2"

1 1/4" HWS

HWS 3"

1 1/4"

H W R

2" 2"

3"

H W S

HWR

H W R

3" HWR

C-107

C-108

C-109

C-109A

C-110

181 SQ. FT.

CW-1

507 SQ. FT.

C-112

E-1

C-113

C-114

C-111

C-125

59 SQ. FT.

C-124

C-126

C-127

623 SQ. FT.

C-128

660 SQ. FT.

CC-4

WOMEN'S LOCKER

MECHANICAL ROOM

ELECTRIC ROOM

GENERATOR ROOM

STAIR # 1

WALKWAY

SERVICE ELEVATOR

LOBBY

ELEV.

SOILED UTILITY

PHARMACY

OXYGEN STORAGE

DINING

ALCOVE

TOILET

RECREATION

RECREATIONEXAM

CORRIDOR

B

IO

M E D

S E R V

IC

E C

O R R

S C -1

M U L E S

T O R A G E

UPDN.

D.F.

F.E.C.

F.E.C.

C

12108 9

H

F

G

K

A

113.41

I

C.4

4.8

QE

10.59.94.5 5.3 6.5 7.5 8.4

AD. ASST.

501D-129

BUS. MAN.

501D-127

PROG. MAN.

501D-126

OFFICE/EXAM

501D-125

OFFICE/EXAM

501D-124

N. ADMIN.

501D-123

LIGHTWELL

501C-125A CORR.

501D-105

ELECTRICAL

501D-104

LOADING

501D-103

MECHANICAL

501D-102

IT

501D-101

ENTRANCE

501D-100

CONNECTOR

RAMP

501D-C5

CORRIDOR

501D-C1

CORRIDOR

501D-C2

WAITING

501D-106

ADMIN. SUPP.

501D-107

OFF. / EX.

501D-109

OFF. / EX.

501D-111

CONFERENCE

ROOM

501D-122

CORR. A

501D-C3

COPY /

WORKROOM

501D-120

BREAK ROOM

501D-121

CUBICLES

501D-128

SERV. CHIEF.

501D-130

ENTRANCE

501D-131

LANDING

501D-136

CORR. B

501D-C4

GUEST T.

501D-132

STAFF T.

501D-133

HAC

501D-134

STAFF T.

501D-118

GUEST T.

501D-117

G. FELLOW

501D-116

G. FELLOW

501D-115

PSYCHOL.

501D-114

N. CASE MAN.

501D-113

OFF. / EX.

501D-112

OFF. / EX.

501D-110

N. CASE MAN.

501D-108

VAV-1-03VAV-1-04

VAV-1-02

VAV-1-01

VAV-1-07

VAV-1-06

VAV-1-05

VAV-1-08

VAV-1-10 HWR3/4" HWR

HWS3/4" HWS

HWR1" HWR

HWS1" HWS

C W

S 2"

C W

S

H W

S

1/ 2"

H W

S H

W R

1/

2" H

W R

C W

S 2"

C W

S C

W R

2" C

W R

H W

S

1/ 2"

H W

S H

W R

1/

2" H

W R

HWS1 1/4" HWS

HWR1 1/4" HWR

R

AC-2

CU-2

AC-3 AC-4

AC-5

AC-6

AC-7

C

H W

S

1/ 2"

H W

S H

W R

1/

2" H

W R

CU-6

CU-7

AHU-1

VAV-1-13

VAV-1-12

VAV-1-09

T

VAV-1-12

T

VAV-1-08TVAV-1-09

TVAV-1-10

T

VAV-1-06

T

VAV-1-07

TVAV-1-13

T VAV-1-05

VAV-1-11

T

VAV-1-11

T

VAV-1-04

T

VAV-1-03

T

VAV-1-02 T

VAV-1-01

AC-8

CU-8

RE

B

B5

C.2

T

UH-1

UH-1

TEF-3

EF-3

C

G.5

9.7 9.83.1 th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

FIRST FLOOR PIPING PLAN - CLC ADMIN CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MP101

613-121

JUNE 27, 2018 WAW WNW

1/8" = 1'-0"

FIRST FLOOR PIPING PLAN - CLC ADMIN

1. CONNECT TO EXISTING PIPING. REPAIR INSULATION.

2. ROUTE CONDENSATE PIPING TO DRAIN. SEE PLUMBING

DRAWINGS FOR DRAIN LOCATIONS.

3. REFRIGERANT AND CONDENSATE PIPING TO ROOF.

SEE SHEET MH103 FOR CONTINUATION.

4. ROUTE CONDENSATE PIPING TO FLOOR DRAIN IN

MECHANICAL ROOM. ROUTE DOWN WALL AND ALONG

AHU HOUSE KEEPING PAD TO FLOOR DRAIN. SEE

PLUMBING DRAWINGS FOR DRAIN LOCATION.

5. ROUTE REFRIGERANT PIPING UP WALL AND INTO

BUILDING ABOVE CEILING. ROUTE PIPING IN ELECTRICAL

ROOM TO AVOID RUNNING ABOVE A ELECTRICAL PANEL.

6. PIPE THROUGH A SMOKE PARTITION. SEE DETAIL ON

SHEET M502.

7. ROUTE CONDENSATE PIPING TO ROOF DRAIN.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

A. ALL RUNOUTS TO VAVs ARE 3/4" UNLESS NOTED

OTHERWISE.

TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

501D

CD-3

D-90

D-88

D-86

D-84

D-83

CD-5

CD-6

D-154

D-155

D-156

D-157

D-158

D-177

CD-1

E-138B E-138A

E-138C E-138E-116A

E-116B

E-118

CORRIDOR

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

STORAGE

CORRIDOR

CORRIDOR

2 BEDROOM

TOILET

2 BEDROOM

TOILET

KITCWSENETTE

KITCWSENETTEOFFICE

OFFICE

CORRIDOR

MECWS. RM.

ELEC. RM.

TELE. RM.

EMERGENCY

GENERATOR

VENDING

STORAGE

PRIVATE DINING

T

T

T

T

T

H W S

H W R

FAN COIL UNIT

1/ 2"

1/ 2"

3/4"

1/ 2"

2 1/2"

HWR

HWS

3/4"

3/4"

H W S

H W R

3"

3"

HWR

HWS

1 1/4"

HWS

HWR

3/4" 3/4"1"

3/4"

3/4"

3/4"

3/4"

1"

3/4" 3/4"

3/4"

3/4"

3/4" 1"

3/4"

HWS HWR

3/4"1" 3/4"

1/2"

3/4"

3/4"3/4" 3/4"

502-TU-1A

2-

TU

2A

HWS

H W S

HWS

H W R

H W R

HWR

HWR

H W R

H W S

1"

4"

3"

3"

3/4"

4" 502 RF1

502-P3

502-P4

4"

4"

4"

HWR

HWS

H W S

INSTANT HW GEN

INSTANT HW GEN

C W R C W S

3"3"

3/4"

CWS

CWR

C W R

C W S

4"

4"

1 1/2"

CWR

CWS 1 1/2"3/4" CWS

CWR

1"

1 1/2"1" 3/4"

3/4"

1 1/4"

3/4"

3/4"

CWS CWR

3/4"

1 1/4"1 1/4"

3/4"

1/2"

3/4"

3/4"

2 1/2"

3/4"

1 1/4"

1"

C W S

C W R

CWR CWS

4"

6"

4"

4"

6"

6"

6"

6"

2-1/2"

6"

C W S

CWS

CWS

CWR

CWR

CWS

6"

VA

V

FF

DD CC AAEE

BB

21.4

MEDS

502F-106

N. STATION

502F-107

WAITING

502F-103

PAT. T.

502F-101

LOBBY

502F-100

CHECK IN

502F-102

TRIAGE

502F-104

N. ASSESS.

502F-108

N. ASSESS.

502F-109

SPEC. VEST.

502F-111

SPEC. T.

502F-112

VESTIBULE

502F-110

N. ASSESS.

502F-114

ELECT

502F-130

MECHANICAL

502F-128

REC. THER.

502F-116

DIETICIAN

502F-118

IT

502F-120

STAFF T.

502F-124

PA OFFICE

502F-126

CORR. B

502F-C2

PSYCH.

502F-125

PSYCH.

502F-127

PSYCH.

502F-129

MANAGER

502F-123

HAC

502F-122

SOC. WORK.

502F-121

PEER SUPP.

502F-119

DOM SUPV.

SCREEN.

502F-117

DOM STAFF

SCREENER

502F-115

DOM SCREENING

CLERK

502F-113

N. STATION

502F-105

CORR. A

502F-C1

VAV-2-08

VAV-2-07

VAV-2-10

VAV-2-11

VAV-2-05

VAV-2-03

VAV-2-06VAV-2-04

VAV-2-02

AC-1

VAV-2-01

VAV-2-09

HWR1 1/2" HWR

HWS1 1/2" HWS

CWS2" CWS

CWR2" CWR

HWR1" HWR

HWS1" HWS

C W

S 2"

C W

S C

W R

2" C

W R

HWR1 1/2" HWR

HWS1 1/2" HWS

CWS2" CWS

CWR2" CWR

H W

S

1/ 2"

H W

S H

W R

1/

2" H

W R

CU-1

R

EF-2 EF-2

EF-2

EF-2

CWP-1

CWP-2

T

VAV-2-01

T

VAV-2-04

TVAV-2-06

T

VAV-2-07

T VAV-2-09

T VAV-2-10

T

VAV-2-08

T

VAV-2-05

TVAV-2-03

TVAV-2-02

T

VAV-2-11

R

AC-9

CU-9

UH-2

T UH-2T

EF-4

EF-4

MH401

th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

FIRST FLOOR PIPING PLAN - DOM CLINIC CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

MP102

613-121

JUNE 27, 2018 WAW WNW

1/8" = 1'-0"

FIRST FLOOR PIPING PLAN - DOM CLINIC

1. CONNECT CHILLED WATER PUMP TO EXISTING PIPING,

REPAIR INSULATION.

2. PIPING DOWN FROM ROOF. CONNECT TO EXISTING

PIPING. REPAIR INSULATION.

3. PIPING UP TO ROOF. SEE SHEET MH104 FOR

CONTINUATION.

4. ROUTE CONDENSATE PIPING TO FLOOR DRAIN. SEE

PLUMBING DRAWING FOR CONTINUATION.

5. PROVIDE CONCRETE PAD FOR CONDENSING UNIT.

6. THERE IS VERY LIMITED CEILING SPACE, THE TAPS

FOR THE HOT AND CHILLED WATER PIPING SHALL BE

MADE ON TOP OF THE PIPE. ACCESS TO THE TOP OF

THE PIPE WILL BE THROUGH THE ROOF.

7. PIPE THROUGH A SMOKE PARTITION. SEE DETAIL ON

SHEET M502.

8. ROUTE CONDENSATE TO FLOOR DRAIN IN CORNER OF

ROOM.

9. ROUTE CONDENSATE THROUGH THE WALL AND INTO

THE MECHANICAL ROOM. ROUTE DOWN THE WALL AND

OVER TO THE AHU HOUSE KEEPING PAD AND TO FLOOR

DRAIN.

GENERAL NOTES

KEY NOTES

GRAPHIC SCALE(S)

A. ALL RUNOUTS TO VAVs ARE 3/4" UNLESS NOTED

OTHERWISE.

TRUE

NORTH

PLAN

NORTH

1/8" = 1' - 0" 0 5' 10' 15' 30'

502F

A

NTS

PIPE HANGERS

B

DETAIL FOR SUPPORTING PIPE ON ROOF

NTS

8"x8"x3/8" [203x203x8.0mm] STEEL

PLATE

WELD PLATE TO

PIPE

SECURE TO ROOF SLAB WITH

(4) 3/8" [8.0mm]∅ EXPANSION

BOLTS OR WELD TO STEEL

DECK

CONCRETE ROOF SLAB OR

STEEL ROOF DECK

NOTES:

PROVIDE RESTRAINING CLAMPS 8'-0" [2438] O.C.

C

NTS

NOTE:

1. SEISMIC SEPARATION ASSEMBLY DETAIL SHOWN IN NFPA 13 (SPRINKLER PIPING),

UTILIZING FLEXIBLE MECHANICAL COUPLINGS, MAY BE USED IN LIEU OF PIPING DETAIL

SHOW ABOVE.

DETAIL "A"

(STEEL PIPE FOR WATER/GLYCOL)

HANGER (TYPICAL)

ANCHOR (TYPICAL)

FLEXIBLE

MECHANICAL

COUPLING

(TYPICAL)

SEISMIC

JOINT

PIPING CROSSING A SEISMIC

JOINT DETAIL "A"

d

PIPING CONNECTIONS

D

NTS

COIL

TEST PLUG (TYP.)

REDUCER, IF REQUIRED

WATER RETURN

MANUAL AIR VENT

UNION CONNECTIONS (TYP.)

WATER SUPPLY

TERMINAL UNIT WATER COILS -

SHUT OFF VALVE

DRAIN WITH HOSE

CONNECTION

MV

MODULATION CONTROL VALVE

E

NTS

DUCTWORK SQUARE VANE ELBOWS F

NTS

(WITH EQUIPMENT MOUNTED IN DUCT)

DUCTWORK TRANSITIONS

G

NTS

SUPPLY DUCTWORK TAKE-OFFS

BRANCH DUCT TAKE-OFF PLAN VIEW

AIR FLOW

AIR FLOW

AI

R

FL

O W

PROVIDE VOLUME

DAMPER

1/4 W OR

4" [100mm]

MIN.

AIR FLOW

MAIN SUPPLY DUCT

AI

R

FL

O W

H

NTS

SUPPLY DUCT TAKEOFF - AIR TERMINAL UNIT

SCHEDULE FOR PIPING CROSSING

A SEISMIC JOINT

LOCATION PIPE

DIMENSIONS INCHES [mm]

502F-DOM CLINIC CW 12 12 72 60 - -

--HW

a b c d e f

12 12 72 60502F-DOM CLINIC5 FT

THRU [20]

6 8 10

[32][25] [40]

[65]

[50]

[75]

-1312 14 -16 -

[125][100]

[150]

[250]

[200]

[300]

[400]

[350]

[450]

[600]

[500]

20 241814 16128 1064 532 2 1/21 1/21 1 1/4

[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]

--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]

THRU 3/4

[2100] [2100]

[2100]

[2700]

[2400]

SIDE VIEW TRAPEZE HANGER FOR UP TO 1000

LB. [453KG] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE 1

- SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE

43 - SEE SPECIFICATIONS

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" [200mm] MIN.)

BAND

1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE

1/2" [15mm] DIA.

HANGER RODS WITH

36" [900mm] MAX.

SPACING ON EACH

CHANNEL

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

IN.

[mm]

FT.

[mm]

FT.

[mm]

[2 5m m

1"

M

AX

NOTES:

SEE SPECIFER FOR DETAILED

HANGER REQUIREMENTS

8"

[2 m m

4" [1 m m

M

IN

[3 m m

ROOF SYSTEM INSULATION

AND MEMBRANE

PRE-MOULDED FLEXIBLE

PIPE COUNTER FLASHING

CLAMPING RING

ROOF SURFACE

WELD PIPE SADDLE

SUPPORT TO PIPE.

PROVIDE WATER TIGHT

CONNECTION

HIGH COMPRESSIVE

STRENGTH INSULATION

INSERT UNDER SHIELD

PIPE AND

INSULATION

INSULATION

PROTECTION

SHIELD

SEALANT

2" [50mm] STEEL

PIPE

2-1/2" [65mm] STEEL

PIPE

PROVIDE ALUMINUM JACKET

NOTE:

1.

2.

3.

4.

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY

SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE

TYPE REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING

EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL

BE DOUBLE VANE TYPE.

W

W1

NOTE:

UNLESS OTHERWISE INDICATED ON PLANS,

MAXIMUM ANGLES SHOWN SHALL APPLY.

M

AX

30°

MAX.

EQ

U

IP

M

EN

T

AIR FLOW AIR FLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEW

TYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

MA

X.

M

AX.

M

AX

M

AX

AIR SPLIT DUCT TAKE-OFF PLAN VIEW

SUPPLY REGISTER

TAKE-OFF PLAN

VIEW

SUPPLY REGISTER

OR BRANCH DUCT

TURNING VANES

MAIN SUPPLY

DUCT

SEE FLOOR PLAN

FOR SPLIT DIMENSION

PROVIDE VOLUME

DAMPER

ADJUSTABLE METAL

ROD OR LINKAGE

TOP REGISTER

MAIN SUPPLY DUCT

VOLUME EXTRACTOR; ADJUSTABLE FROM

FULLY CLOSED POSITION TO CFM NOTED ON

FLOOR PLANS

AIR FLOW AIR FLOW

RIGID DUCT TO AIR

TERMINAL UNIT.

ROUND SHEET

METAL DUCT.

MAIN SUPPLY

"D"

45°M

AX.

PLAN VIEW

AT ANCHOR POINTS

PROVIDE SECURE

CONNECTION

WELD

SADDLE

HANGER ROD

d c b a b

15°

W th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

DETAILS CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

M501

613-121

501D & 502F

A

NTS

DUCT CONNECTIONS - AIR TERMINAL UNITS

NOTE:

1.

2.

3.

4.

5.

6.

RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A

MINIMUM OF 3 TIMES THE DIAMETER OF INLET

A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT

ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0" [900mm].

A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX

INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES

NOT EXCEED 10 FEET (3 METERS). FOR LONGER LENGTHS, INCREASE THE DUCT

SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE

DROP AT OR BELOW 0.2"/100' [1.64Pa/m].

FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR

DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID ELBOWS FOR

CHANGE OF DIRECTION GREATER THAN 45°.

COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE

INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.

USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE

DEDICATED AHU SERVING THE SURGICAL SUITE.

AIR TERMINAL UNIT

(CV OR VAV)

REHEAT COIL

SOUND ATTENUATOR

SEE EQUIPMENT

SCHEDULE

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL

DIFFUSER (TYP.)

SEE SPECIFICATIONS FOR CLAMPS

AND SEALANT (TYP.)

SEE NOTE 5

F

NTS

EXHAUST OR RETURN BRANCH DUCTWORK

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR FLOW

AIR FLOW

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" [100mm]

MIN.

BRANCH DUCT

VD

G

NTS

VOLUME DAMPER DETAIL

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE

DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8" [6mm]

CLEARANCE ALL

AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING QUADRANT

INSULATION STAND-OFF

1/2" [15mm] ROUND

ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

SECTION "A-A"

"B" "B"

D

ACCESS PANEL AND DOOR DETAIL

NTS

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS PANEL

ACCESS DOOR

CASING

GASKET

HANDLE INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

E

NTS

FLEXIBLE DUCT CONNECTIONS

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED CONNECTION

ON FAN SIDE

WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" [25x3mm] DRAW BAND

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS ON 12"

[300mm] CENTERS

RIVET ON 4"

[100mm] CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEMALTERNATE

POSITION OF

BOLT 1 1/2" [40mm]

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

[15mm] [15mm] [40mm]

1 1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLANGED

CONNECTION ON

FAN SIDE

WASHER

FLEXIBLE MATERIAL AS

SPECIFIED

WATER COILS - PIPING CONNECTIONS

B

NTS

SINGLE COIL

WATER COIL

AIR VENT WHEN

COIL

IS NOT

SELF-VENTING

DRAIN WHEN COIL IS NOT

SELF-DRAINING

TEST PLUG

(TYP.)

PIPE HANGER SHALL SUPPORT PIPING

INDEPENDENT OF COIL

REDUCER, IF REQUIRED

DRAIN

WATER COIL

AIR VENT WHEN

COIL

IS NOT

SELF-VENTING

TEST PLUG

(TYP.)

PIPE HANGER SHALL SUPPORT PIPING

INDEPENDENT OF COIL

WATER COIL

REDUCER, IF REQUIRED

FLOW ELEMENT

DRAIN WHEN COIL IS NOT

SELF-DRAINING

DRAIN

DOUBLE COIL

NOTE:

1.

2.

3.

WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 4" [100mm]∅ PIPE & SMALLER. TYPE "H-P" FOR 5" [125mm]∅ PIPE & LARGER.

PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALES, OR

EQUIPMENT.

THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM

UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE RETURN PIPING.

FE

MV

MV

MV

MV

MVMV

FE

TI

TI

TEMPERATURE

INDICATION TO ECC

SEE CONTROL DIAGRAM

MV

PIPING CONNECTIONS

C

NTS

UNIT HEATERS (HOT WATER) -

TYPICAL CONNECTIONS TO VERTICAL HOT

WATER UNIT HEATER

TYPICAL CONNECTIONS TO HORIZONTAL HOT

WATER UNIT HEATER

UNIT HEATER

HO

T

WA

TE

R

SU

PP

LY

HO

T

WA

TE

R

RE

TU

RN

HO

T

WA

TE

R

SU

PP

LY

HO

T

WA

TE

R

RE

TU

RN

UNIT HEATER

AIR VENT

TEST PLUG, TYP.

SHUTOFF BALL

VALVE, TYP.

WYE STRAINER,

TYP.

MV

MV

AUTOMATIC FLOW

CONTROL VALVE

NOTE: UNIT MOUNTED

THERMOSTAT SHALL

MAINTAIN SPACE

TEMPERATURE BY

CYCLING

AUTOMATIC FLOW

CONTROL VALVE

H

NTS

INLINE FAN SUPPORT DETAIL

VIBRATION ISOLATORS

TRANSITION

FLEXIBLE CONNECTION

RETURN FAN

MOTOR

SEE FLOOR PLAN

FOR DUCT SIZES

FLEXIBLE CONNECTION

3/8" THREADED ROD

I

NTS

AHU-1 AND AHU-2 COMPONENT DIAGRAM

NOTE:

1.

2.

3.

MIXING BOX

AIR FILTER

HOT WATER COIL

4.

5.

CHILLED WATER COIL

SUPPLY AIR PLENUM FAN

1 2 3 4 5RETURN AIR

SUPPLY AIROUTSIDE AIR

MAX DIMENSIONS

(LXWXH)

13' 4" X 5' 7" X 3' 5"

MOUNTING PLATFORM

ROOF

PIPING

SUSPENDED CEILING

CEILING RECESSED INDOOR UNIT

SPLIT-TYPE AIR CONDITIONER

ROOF CAP

W/ BIRDSCREENSHEET METAL CAP

REFRIGERANT

GALV. METAL

FLASHING

24 GAUGE

FLASHING

AIR CONDITIONER

SPLIT-TYPE

FRONT FAN GRILLE

OUTDOOR UNIT.

ANCHOR BOLTS

OUTSIDE AIR DUCT

SEE FLOOR PLAN

FOR DUCT SIZE

J

NTS

SPLIT SYSTEM AC - CEILING MOUNTED CASSETTE

K

PENETRATION OF SMOKE/FIRE BARRIERS

NTS

NOTE:

1. APPLICABLE TO PENETRATIONS OF ALL

FIRE RATED MEMBRANES, IN ACCORDANCE

WITH NFPA 101. REFER TO

SPECIFICATIONS SECTION 07 84 00, FIRE

STOPPING SYSTEMS.

PARTITION OR CHASE PENETRATION

PIPE/DUCT

[150mm] [150mm]

MASONRY PARTITION

PARTITION SUPPORT

FIRESTOP

MATERIAL

[150mm] [150mm]

3/4" [19mm] APPROVED

FIRESTOP INSULATION WITH

VAPOR BARRIER

DRYWALL PARTITION

INSULATED

DUCT

OR PIPE

SE

E N O

TE

SEE NOTE 3

SEE NOTE 2

SEE NOTE 1

W

1/2" 1/2" 1 1/2"

6" 6"

6" 6" th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

DETAILS CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

M502

613-121 th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

SCHEDULES CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

M601

613-121 th re e in ch es o ne fo ot 6"

Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot

6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot

6"

6"

VA FORM 08-6231

Revisions:

1 2 3 4 5 6 7 8 9

Date:

CONSULTANTS: ARCHITECT/ENGINEERS:

590 MEANS ST NW ATLANTA, GA 30318

Drawing Title:

Approved Project Director:

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number:

Building Number:

Project Number:

Dwg. of

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

BID DOCUMENTS

SCHEDULES CONSTRUCT DOM CLINIC

AND CLC ADMINISTRATION

ADDITION

MARTINSBURG, WV

M602

613-121

CWR

CWR

CWR

CWR

NTS

HWS

HWR

V-2ROOM THERMOSTAT/SENSOR

WALL MOUNTED

48" [1200mm] AFF.

ROOM THERMOSTAT/SENSOR

WALL MOUNTED

48" [1200mm] AFF.

VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM

NO SUPPLEMENTAL HEATING WITH SUPPLEMENTAL HEATING

A

IR

F L O

W (C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

VAV BOX CONTROL SEQUENCE

SP

TU

RHCHWS

HWR

V-1

REHEAT

COIL

AIR

TERMINAL

UNIT

AIR FLOW

TE

ATU

CONTROLLERPC

TE

TU

RHC

HWS

HWR

V-1

REHEAT

COIL

AIR

TERMINAL

UNIT

AIR FLOW

TE

ATU

CONTROLLER

PC

TE

A

IR

F L O

W (C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

SP

A

IR

F L O

W (C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

SP

A

IR

F L O

W (C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

NO DEADBAND

VAV BOX CONTROL SEQUENCE

W/DEADBAND

VAV BOX CONTROL SEQUENCE

NO DEADBAND

VAV BOX CONTROL SEQUENCE

W/DEADBAND

SUPPLEMENTAL

HEAT

SP

FE

100% 100%

100% 100%

R

EH

EAT FLO

W

VAV A

IR

F

LO

W

V A V A

IR

F

LO

W

VAV A

IR

F

LO

W

V A V A

IR

F

LO

W

R E H E A

T FLO

W

REHEAT FLO

W

SUPP FLO

W

R E H E

AT FLO

W

S U

PP

FLO

W

A. UPON FALL IN SPACE TEMPERATURE THE

VAV DAMPER WILL MODULATE TO MINIMUM

POSITION.

B. UPON FURTHER DROP IN SPACE

TEMPERATURE VALVE V-1 WILL MODULATE

TO MAINTAIN SET POINT + .5° F. THE

ADJUSTABLE TOLERANCE OF + .5° F HAS

BEEN SELECTED TO PREVENT VALVE

HUNTING

C. THE REVERSE SHALL OCCUR ON THE RISE

IN SPACE TEMPERATURE.

A. SET POINTS SHALL BE SET AS FOLLOWS:

COOLING 75°F (ADJ)

HEATING 70°F(ADJ)

DEADBAND OF 5° F BETWEEN HEATING AND

COOLING SET POINTS WILL BE MAINTAINED.

B. UPON FALL IN SPACE TEMPERATURE THE

VAV DAMPER WILL MODULATE TO MINIMUM

POSITION.

C. UPON FURTHER DROP IN SPACE

TEMPERATURE VALVE V-1 WILL MODULATE

TO MAINTAIN SET POINT + .5° F. THE

ADJUSTABLE TOLERANCE OF + .5° F HAS

BEEN SELECTED TO PREVENT VALVE

HUNTING

D. THE REVERSE SHALL OCCUR ON THE RISE

IN SPACE TEMPERATURE.

A. UPON FALL IN SPACE TEMPERATURE THE

VAV DAMPER WILL MODULATE TO MINIMUM

POSITION.

B. UPON FURTHER DROP IN SPACE

TEMPERATURE VALVE V-1 WILL MODULATE

TO MAINTAIN SET POINT + .5° F. THE

ADJUSTABLE TOLERANCE OF + .5° F HAS

BEEN SELECTED TO PREVENT VALVE

HUNTING

C. VALVE V-2 SHALL BE ENABLED WHEN

OUTSIDE AIR FALLS BELOW 40° F (ADJ)

AND VALVE V-1 HAS BEEN MODULATED

OPEN ABOVE 30% (ADJ). VALVE V-2

SHALL MAINTAIN SET POINT + .5° F. THE

ADJUSTABLE TOLERANCE OF + .5°F HAS

BEEN SELECTED TO PREVENT VALVE

HUNTING. THE REVERSE SHALL OCCUR ON

A RISE IN SPACE TEMPERATURE.

A. SET POINTS SHALL BE SET AS FOLLOWS:

COOLING 75°F (ADJ)

HEATING 70°F(ADJ)

DEADBAND OF 5° F BETWEEN HEATING AND

COOLING SET POINTS WILL BE MAINTAINED.

B. UPON FALL IN SPACE TEMPERATURE THE

VAV DAMPER WILL MODULATE TO MINIMUM

POSITION.

C. UPON FURTHER DROP IN SPACE

TEMPERATURE VALVE V-1 WILL MODULATE

TO MAINTAIN SET POINT + .5° F. THE

ADJUSTABLE TOLERANCE OF + .5° F HAS

BEEN SELECTED TO PREVENT VALVE

HUNTING

D. VALVE V-2 SHALL BE ENABLED WHEN

OUTSIDE AIR FALLS BELOW 40° F (ADJ)

AND VALVE V-1 HAS BEEN MODULATED

OPEN ABOVE 30% (ADJ). VALVE V-2

SHALL MAINTAIN SET POINT + .5° F. THE

ADJUSTABLE TOLERANCE OF + .5°F HAS

BEEN SELECTED TO PREVENT VALVE

HUNTING.

E. THE REVERSE SHALL OCCUR ON THE RISE

IN SPACE TEMPERATURE.

FE

NTS

VARIABLE AIR VOLUME AIR HANDLING UNIT WITH OUTSIDE AIR CONTROL DIAGRAM (AHU-1 AND AHU-2)

EXHAUST AIR

D-3

D-2

P R

E

F

IL

T E

R

OUTSIDE

AIR

D-1

C O

IL

P

R E

H E

A T

C O

IL

C

O O

L

IN

G

LOCATE SENSOR

OUTSIDE UNDER

SHIELD

MPS

V-2

V-1

CHR

CHS

RETURN FAN

SUPPLY FAN

A F

M D

RETURN

AIR

A F

M D

SUPPLY AIR TO

TERMINAL UNIT

TT

TT

TT TT

FTA

F T

E R

F

IL

T

E R

TT MT

D-4

A F

M D

MINIMUM

OUTSIDE

AIR

HS

IT

VSMC

HSVSMC

FT

3 6

H-1

SD

HOT WATER

CURRENT

TRANSMITTER

FOR FAN

STATUS ,TYP.

PRESSURE SWITCH LOW

TO DISABLE RETURN FAN WHEN SMOKE

DAMPER IN RETURN DUCT CLOSES

PRESSURE SWITCH HIGH

TO DISABLE FAN WHEN

HIGH PRESSURE LIMIT

SETPOINT IS REACHED

PSH

SMOKE

DETECTOR

VARIABLE SPEED MOTOR

CONTROLLER, TYP.

ZC

ZC

ZC

ZC

FT PDS PDS

TT

SST

PSL

IT

SST

SD

SPSTSL

TSL-1

NO

V-3

LPS

V-4

ELECTRIC TO STEAM HUMIDIFIER

MS

MC

ECC

ECC

MT

1. GENERAL

1.1 UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE

"AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS

"OFF" D-1, D-3, SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" D-1, SD-1 AND SD-2 SHALL BE FULLY OPEN. D-2

AND D-3 SHALL MODULATE IN ACCORDANCE WITH THE FOLLOWING SEQUENCE:

2. TEMPERATURE CONTROL

2.1

2.2

2.3

2.4

3. AIR FLOW CONTROL

3.1

3.2

3.3

4. HUMIDITY CONTROL

4.1

4.2

5. FREEZE PROTECTION

5.1

6. AUTOMATIC SHUTDOWN/RESTART

6.1

6.2

7. EMERGENCY CONSTANT SPEED OPERATION

7.1

SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT VIA DIGITAL CONTROL

PANEL BY MODULATING V-1 OR D-2 AND D-3 OR V-2 IN SEQUENCE.

WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS ABOVE 75°F (ADJ) [23.8°C], THE DIGITAL

CONTROL PANEL SHALL PREVENT…