36C24518B0233-008.pdf
PDF 3 MB Posted
- Attached to
- CONST DOM CLINIC & CLC ADMIN PROJ 613-121 Federal contract opportunity
- Solicitation number
- 36C24518B0233
About this file
36C24518B0233 6 Mechanical Drawings.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24518C0215-000.docx | DOCX document | |
| 36C24518B0233-0001001.pdf | ||
| 36C24518B0233-0001000.docx | DOCX document | |
| 36C24518B0233-009.pdf | ||
| 36C24518B0233-007.pdf | ||
| 36C24518B0233-001.docx | DOCX document | |
| 36C24518B0233-002.pdf | ||
| 36C24518B0233-010.pdf | ||
| 36C24518B0233-003.pdf | ||
| 36C24518B0233-013.pdf | ||
| 36C24518B0233-012.pdf | ||
| 36C24518B0233-011.pdf | ||
| 36C24518B0233-005.pdf | ||
| 36C24518B0233-004.pdf | ||
| 36C24518B0233-006.pdf | ||
| 36C24518B0233-000.docx | DOCX document |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
# DEMOLITION NOTE IDENTIFICATION
INDICATES ITEM TO BE REMOVED
FLEXIBLE DUCT CONNECTION
VERTICAL FIRE DAMPER
VOLUME DAMPER
CEILING RETURN, EXHAUST OR TRANSFER REGISTER
CEILING SUPPLY DIFFUSER
MITERED ELBOW WITH TURNING VANES
RETURN DUCT TURNING UP
RETURN DUCT TURNING DOWN
EXHAUST DUCT TURNING UP
EXHAUST DUCT TURNING DOWN
SUPPLY DUCT TURNING UP (ROUND OR RECTANGULAR)
SUPPLY DUCT TURNING DOWN (ROUND OR RECTANGULAR)
10"x10" SQUARE OR RECTANGULAR DUCTWORK
PIPE TURNING UP
PIPE TURNING DOWN
THERMOSTAT (C=COOLING, H=HEATING,
H,C=HEATING AND COOLING
DUCT SMOKE DETECTOR
G
(CFM)
EXHAUST GRILLE DESIGNATION
WITH CFM INDICATED
A
(CFM)
CEILING DIFFUSER DESIGNATION
WITH CFM INDICATED
G20/20 RETURN GRILLE DESIGNATION
GENERAL
DUCTWORK
MOTORIZED CONTROL DAMPER
INDICATES ROUND DUCTWORK
FLEXIBLE CONNECTION
RETURN, EXHAUST OR TRANSFER AIR FLOW
SUPPLY AIR FLOW
ACCESS DOORAD
ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
ALUMINUMALUM
ARCHITECTURALARCH
DIAMETERDIA
DRAWINGDWG
EXISTINGEX
EXISTING TO REMAINEXR
GAUGEGA
GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFCI
MISCELLANEOUSMISC
NOT IN CONTRACTNIC
TYPICALTYP
UNLESS OTHERWISE
NOTED
UON
GALVANIZEDGALV
RUN THRU JOISTSRBJ
REMOVE EXISTINGREX
AUTOMATIC AIR VENT
VALVES AND ACCESSORIES
AUTOMATIC FLOW CONTROL VALVE
BACKFLOW PREVENTER
BALL VALVE
BOTTOM CONNECTION
BUTTERFLY VALVE
CAPPED PIPE
CHECK VALVE
CLEAN OUT
CONCENTRIC REDUCER
DIRECTION OF FLOW
ECCENTRIC REDUCER
FLANGED CONNECTION
FLEXIBLE CONNECTION
FLOW METER
BALL VALVE FOR 2" & UNDER
BUTTERFLY FOR 2.5" AND LARGER
GLOBE VALVE
MANUAL AIR VENT
METERED BALANCING VALVE
W/PRESSURE TAPS
PRESSURE/TEMPERATURE TEST PLUG
PT
NEEDLE VALVE
PLUG VALVE
PIPE ANCHOR (W=WALL, C=CEILING, F=FLOOR)
W,C,F
PIPE GUIDE
PIPE SLEEVE
PITCH
PRESSURE REDUCING VALVE
PRESSURE RELIEF VALVE
PRESSURE GAUGE WITH GAUGE COCK
SQUARE HEAD COCK
STEAM TRAP
STRAINER
STRAINER W/BLOW DOWN VALVE
THREE WAY CONTROL VALVE
TWO WAY CONTROL VALVE
THERMOMETER
THERMOSTATIC RADIATOR VALVE
TOP CONNECTION
UNION
VACUUM BREAKER
VALVE IDENTIFICATION
CONTROLS
ANALOG INPUT (TO PANEL)
ANALOG OUTPUT (OUT OF PANEL)
DIGITAL INPUT (TO PANEL)
DIGITAL OUTPUT (OUT OF PANEL)
TWO WAY CONTROL VALVE
THREE WAY CONTROL VALVE
BYPASS TIMER SWITCH
COMMON
CONTROL WIRING (SIGNAL PATH)
DATA TERMINAL CABINET
DIFFERENTIAL PRESSURE SWITCH
DIFFERENTIAL PRESSURE SENSOR
DUCT SMOKE DETECTOR
FAN ON-OFF SWITCH
FAN VARIABLE SPEED SWITCH
AI
DI
DO
C
FLOW MEASURING SYSTEM
FIRESTAT
FREEZESTAT
HIGH LIMIT TEMPERATURE SENSOR
HUMIDISTAT
LOW LIMIT TEMPERATURE SENSOR
LOCAL TEMPERATURE CONTROL PANEL
MOTOR
MOTORIZED CONTROL DAMPER
MOTOR STARTER
NORMALLY CLOSEDNC
NORMALLY OPENEDNO
POWER WIRINGEP
SENSOR
STATIC PRESSURE SENSOR
STATIC TOTALIZER STATION
SWITCH
ZONE TEMPERATURE SENSOR
TEMPERATURE TRANSMITTER
H,C
TIME CLOCK
VALVE IDENTIFICATION
CSR CURRENT SENSING RELAY
NORMALLY OPEN CONTROLS
NORMALLY CLOSED CONTROLS
CWR
CHS
CHR
CDWS
HRS
HRR
HPS
HPC
FOR
FOS
FOV
CDWR
MPS
MPC
HWS
HWR
LPS
PC
V
RS
RL
G
LPC
D
DFR
DFS
CWS
RHG
CHILLED WATER RETURN
MEDIUM PRESSURE CONDENSATE
DOMESTIC HOT WATER RECIRCULATING
HEAT RECOVERY RETURN
HIGH PRESSURE STEAM
NATURAL GAS PIPING
MEDIUM PRESSURE STEAM
LOW PRESSURE STEAM
HOT WATER SUPPLY
HOT WATER RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
STEAM VENT LINE
PUMPED CONDENSATE
LOW PRESSURE CONDENSATE
HIGH PRESSURE CONDENSATE
DIRECTION OF FLOW
DIESEL FUEL RETURN
DIESEL FUEL SUPPLY
DOMESTIC HOT WATER
DOMESTIC COLD WATER
FUEL OIL SUPPLY
FUEL OIL RETURN
HEAT RECOVERY SUPPLY
FUEL OIL VENT
CONDENSATE DRAIN LINE
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CHILLED/HOT WATER SUPPLY
CHILLED/HOT WATER RETURN
CHILLED WATER SUPPLY
REFRIGERANT HOT GAS
PIPING
FLEXIBLE DUCT CONNECTION
LEGEND
M
M
M
AO
S
P
T
TT
TC
DTC
DPS
DSD
FMS
FZ
HL
LL
TCP
MS
STS
V-1
BT
DP
F
VSF
FS
H
S
T
SUPPLY DUCT TURNING UP (OVAL)
SUPPLY DUCT TURNING DOWN (OVAL)
10"/10" OVAL DUCTWORK
SD
V-1
# CONSTRUCTION NOTE IDENTIFICATION
INDICATES NEW ITEM
INDICATES EXISTING ITEM
REMOVE TO THIS POINT
CONNECT NEW TO EXISTING
ROOM NUMBER IDENTIFICATIONXXX
Ø
WITH ASSOCIATED EQUIPMENT ID
VAV-X-X
1.
2.
3.
4.
5.
7.
8.
9.
16.
15.
14.
13.
12.
11.
10.
6.
17.
18.
19.
20.
GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH
MECHANICAL DRAWING OF THIS SET. NOTES SPECIFIC TO
INDIVIDUAL MECHANICAL DRAWINGS WILL BE SHOWN ON THE
RESPECTIVE MECHANICAL DRAWING.
THE CONTRACTOR SHALL PROVIDE A COMPLETE HVAC SYSTEM
TO INCLUDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENT
FOR A COMPLETE AND FUNCTIONAL SYSTEM INCLUDING ALL
NECESSARY APPURTENANCES CUSTOMARILY INCLUDED IF NOT
SPECIFICALLY CALLED OUT.
ENTIRE INSTALLATION, INCLUDING MATERIALS, EQUIPMENT, AND
WORKMANSHIP, SHALL CONFORM WITH ALL APPLICABLE LAWS,
CODES, AND REGULATIONS OF MUNICIPAL, STATE AND FEDERAL
AUTHORITIES.
THIS PROJECT SHALL CONFORM TO APPLICABLE ASHRAE, NFPA,
AND SMACNA STANDARDS AND OTHER REGULATORY BODIES
HAVING JURISDICTION OVER THE CLASS OF WORK.
MATERIALS AND EQUIPMENT SHALL HAVE STAMPS OR SEALS OF
ARI, ASME, UL, AND ASTM.
THE CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE AND
APPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OF
APPLICABLE REGULATORY AGENCIES. REQUIRED TESTS SHALL
BE PERFORMED IN THE PRESENCE OF THE GOVERNMENT
UNLESS OTHERWISE WAIVED IN WRITING.
THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS,
LICENSES, DOCUMENTS, AND SERVICES RELATED TO
INSTALLATION OF THE WORK.
EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BE
FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT IS
APPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICE,
CIRCUIT BREAKERS AND CONDUIT SIZES ARE APPROPRIATELY
MODIFIED AT NO COST TO THE OWNER.
THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE
OTHER TRADES IN ORDER TO RESOLVE ANY CONFLICT THAT
MIGHT ARISE DUE TO THE LOCATION OF EQUIPMENT OR THE USE
OF SPACE.
RUN ALL HORIZONTAL PIPING AND DUCTWORK ABOVE CEILING
UNLESS OTHERWISE NOTED.
CUT OPENINGS, AS REQUIRED, IN THE EXISTING CONSTRUCTION
FOR THE INSTALLATION OF PIPING, DUCTWORK, AND EQUIPMENT.
PATCH AND REPAIR TO MATCH THE EXISTING ADJACENT
CONSTRUCTION.
ALL ELBOWS IN DUCTWORK SHALL BE RADIUS ELBOWS UNLESS
OTHERWISE NOTED. WHERE SQUARE ELBOWS ARE SHOWN,
INSTALL TURNING VANES.
MAKE DUCT PENETRATIONS OF ALL WALLS WITH SHEET METAL
DUCTS. FLEXIBLE DUCT PENETRATIONS OF WALLS ARE NOT
ACCEPTABLE.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
EXACT LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES.
FINISH AND COLOR TO BE SELECTED BY GOVERNMENT FROM
MANUFACTURER'S STANDARD PALETTE.
DO NOT INSTALL EQUIPMENT, PIPING OR DUCTWORK OVER ANY
ELECTRICAL EQUIPMENT OR ELECTRICAL SERVICE SPACE.
PROVIDE DYNAMIC FIRE DAMPERS IN ACCORDANCE WITH THEIR U.L.
LISTING AND THE REQUIREMENTS OF NFPA-90A.
EXTEND DRAIN LINES TO NEAREST DRAIN OR AS INDICATED. ALL
CONDENSATE DRAIN PIPING SHALL BE TRAPPED AND PITCHED
DOWN IN DIRECTION OF FLOW A MINIMUM OF 1/8" PER FOOT.
LAYOUT OF PIPING AND DUCTWORK IS DIAGRAMMATIC. RUN ALL
EXPOSED PIPING AND DUCTWORK AS HIGH AS POSSIBLE UNLESS
OTHERWISE NOTED. ALLOW FOR RISES, DROPS AND OFFSETS AS
REQUIRED.
DUCTWORK SIZES ARE INSIDE CLEAR DIMENSIONS.
INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING,
MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT
COMPONENTS. AS MUCH AS PRACTICAL, CONNECT EQUIPMENT FOR
EASE OF DISCONNECTING, WITH A MINIMUM OF INTERFERENCE WITH
OTHER INSTALLATIONS. PIPING SHALL NOT INTERFERE WITH FILTER
PULL.
21.
22.
23.
24.
25.
26.
27.
31.
30.
29.
28.
MECHANICAL CONTRACTOR SHALL PROVIDE AUTOMATIC CONTROL DEVICES,
SUCH AS TEMPERATURE SENSORS, RELAYS, PRESSURE SWITCHES WHICH ARE
ASSOCIATED WITH MECHANICAL EQUIPMENT AND ASSOCIATED CONTROL
WIRING FROM STARTER TO THE CONTROL DEVICE. ELECTRICAL CONTRACTOR
SHALL PROVIDE CONDUIT AND WIRING FROM POWER SOURCE TO DISCONNECT
SWITCH, FROM DISCONNECT SWITCH TO STARTER, AND FROM STARTER TO THE
EQUIPMENT.
ALIGN THERMOSTATS WITH LIGHT SWITCHES.
PROVIDE AUXILIARY DRAIN PANS UNDER EQUIPMENT LOCATED ABOVE
CEILINGS.
ALL VALVES ARE FULL LINE SIZE EXCEPT CONTROL AND BALANCING VALVES.
PROVIDE PRESSURE/TEMPERATURE (P/T) PLUGS, WITH CAPS UP AND
DOWNSTREAM OF ALL EQUIPMENT, AT THE SUPPLY AND RETURN TAPS OF
ALL PIPING BRANCHES AND/OR WHERE INDICATED. PROVIDE EXTENDED
PLUGS AND LABELS WHERE PIPING IS INSULATED. PROVIDE REMOVABLE
INSULATION PLUG.
PROVIDE FLUSHING VALVES AND TEES AT BOTH SIDES OF ALL
EQUIPMENT. TAPS SHALL MATCH EQUIPMENT PIPING UP TO 1". FOR
LARGER EQUIPMENT AND PIPE LOOPS PROVIDE 1 1/2" TAPS AND
VALVES.
PROVIDE MANUAL AIR VENTS AT ALL HIGH SPOTS AND THE ENDS OF ALL
PIPING LOOPS. PROVIDE 1/2" DRAIN VALVES AT LOW POINTS IN PIPING.
PROVIDE MINIMUM PITCH SUFFICIENT TO INSURE ADEQUATE VENTING AND
DRAINING.
LOCATE AND SIZE 5 1/2" THICK CONCRETE HOUSEKEEPING PADS AND
CURBS IN ACCORDANCE WITH ACTUAL EQUIPMENT PURCHASED.
EXTEND PAD BEYOND EQUIPMENT FOR 6" IN ALL DIRECTIONS.
ALL EQUIPMENT REMOVED FROM THE BUILDING, DURING DEMOLITION,
SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE UNLESS OTHERWISE NOTED.
EXISTING DUCT, PIPE AND EQUIPMENT SIZES NOTED ARE FOR THE
CONVENIENCE OF THE CONTRACTOR ONLY AND ARE NOT WARRANTED
TO BE CORRECT. THE CONTRACTOR SHALL FIELD VERIFY ALL
EXISTING DUCT, PIPE AND EQUIPMENT SIZES AND THEIR RESPECTIVE
LOCATIONS BEFORE PROCEEDING WITH ANY ASSOCIATED WORK.
PRIOR TO SUBMITTING A PROPOSAL THE CONTRACTOR IS
STRONGLY ENCOURAGED TO VISIT THE SITE AND THOROUGHLY
INSPECT ALL EXISTING CONDITIONS TO INSURE THAT THE WORK
REPRESENTED ON THE DRAWINGS CAN BE INSTALLED AS
INDICATED.
GENERAL NOTES
REFER TO ELECTRICAL DRAWINGS FOR VOLTAGE AND PHASE
REQUIREMENTS FOR ALL EQUIPMENT REQUIRING AN ELECTRICAL
CONNECTION.
32.
th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
MECHANICAL LEGEND AND GENERAL NOTES CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
M001
613-121
JUNE 27, 2018 WAW WNW
501D & 502F501D & 502F501D & 502F
C-107
438 SQ. FT.
C-108
808 SQ. FT.
C-109
549 SQ. FT.
C-109A
132 SQ. FT.
C-110
181 SQ. FT.
CW-1
507 SQ. FT.
C-112
150 SQ. FT.
E-1
88 SQ. FT.
C-113
450 SQ. FT.
C-114
396 SQ. FT.
C-111
63 SQ. FT.
C-125
3,053 SQ. FT.
C-124
111 SQ. FT.
C-126
1688 SQ. FT.
623 SQ. FT.660 SQ. FT.
CC-4
368 SQ. FT.
WOMEN'S LOCKER
MECHANICAL ROOM
ELECTRIC ROOM
GENERATOR ROOM
STAIR # 1
WALKWAY
SERVICE ELEVATOR
LOBBY
ELEV.
SOILED UTILITY
PHARMACY
OXYGEN STORAGE
DINING
TOILET
RECREATION
CORRIDOR
UPDN.
D.F.
F.E.C.
F.E.C.
RE
QE
10.59E 12E 12.2E 14E 15E 16E7.4E 16.6E6.5 7.5 8.4 th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR DEMO PLAM - CLC ADMIN CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MD101
613-121
JUNE 27, 2018 WAW WNW
1/8" = 1'-0"
FIRST FLOOR DEMO PLAN - CLC ADMIN
1. REMOVE EXISTING HEATING UNIT AND ALL ASSOCIATED
CONTROLS, DUCTWORK, ETC RENDERED USELESS BY THE
REMOVAL OF THE UNIT.
2. CAP HOT WATER PIPING, REPAIR INSULATION.
3. REMOVE SUPPLY AND RETURN GRILLES.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
501D
CD-4
CD-3
D-90
D-88
D-86
D-84
D-83
CD-5
CD-6
D-154
D-155
D-156
D-157
D-158
D-177
CD-1
E-138B E-138A
E-138C E-138E-116A
E-116B
E-118
CORRIDOR
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
CORRIDOR
COMMUNITY ROOM
CORRIDOR
2 BEDROOM
TOILET
2 BEDROOM
TOILET
KITCWSENETTE
OFFICE
CORRIDOR
MECWS. RM. ELEC. RM.
TELE. RM.
EMERGENCY
GENERATOR
VENDING
STORAGE
PRIVATE DINING
E .W
.C
AP
T
T
T
T
T
T
3/4" 1"
H W S
H W R
1/ 2"
1/ 2"
3/4"
1/ 2"
2 1/2"
3/4"
H W S
H W R
3"
3"
HWR
HWS
1 1/4"
HWS
HWR 3/4"3/4"1"
3/4"3/4" 3/4"
1"
3/4" 3/4"
3/4"
3/4"
3/4"
1"
3/4"
HWS
HWR
3/4"1" 3/4"
1/2"
3/4"
3/4"3/4" 3/4"
502-TU-2B
2-
TU
2A
HWS
H W S
HWS
H W R
H W R
HWR
HWR
H W R
H W S
1"
4"
3"
3"
3/4"
4" 502 RF1
502-P3
502-P4
4"
4"
4"
HWR
HWS
H W S
INSTANT HW GEN
INSTANT HW GEN
HWR
HWS
C W R C W S
3"3"
3/4"
C W R
C W S
4"
4"
1 1/2"
CWR
CWS
1 1/2"3/4"
CWS
CWR
1"
1 1/2"1" 3/4"
3/4"
1 1/4"
3/4"
3/4"
CWS CWR
3/4"
1 1/4"1 1/4"
3/4"
1/2"
3/4"
3/4"
2 1/2"
3/4"
1 1/4"
1"
C W S
C W R
CWR CWS
4"
6"
4"
4"
6"
6"
6"
6"
2-1/2"
6"
C W S
CWS
CWS
CWR
CWR
CWS
6"
CWS
CWR
FAN COIL UNIT
VA
V
502-TU-1A
th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR DEMO PLAN - DOM CLINIC CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MD102
613-121
JUNE 27, 2018 WAW WNW
1/8" = 1'-0"
FIRST FLOOR DEMO PLAN - DOM CLINIC
1. REMOVE EXISTING CHILLED WATER PUMP. LEAVE
PIPING READY FOR RECONNECTION.
2. REMOVE PIPING TO SCOPE OF WORK MARK. CAP PIPE
AND REPAIR INSULATION.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
502F
A. ALL UTILITY OUTAGES SHALL BE COORDINATED WITH
THE COR. REFER TO SPECIFICATION SECTION 01 00 00
FOR ADDITIONAL INFORMATION.
B. CHILLED WATER SUPPLY SHALL BE MAINTAINED TO
THE EXISTING SYSTEM. REMOVE AND REPLACE
PUMPS ONE AT A TIME.
DNDN
DN
C-108
C-109
C-109A
C-110
CW-1
C-112
E-1
C-113
C-111
C-125
C-126
CC-4
MECHANICAL ROOM
ELECTRIC ROOM
GENERATOR ROOM
STAIR # 1
WALKWAY
SERVICE ELEVATOR
LOBBY
ELEV.
SOILED UTILITY
OXYGEN STORAGE
DINING
TOILET
RECREATION
CORRIDOR
B
IO
M E D
S E R V
IC
E C
O R R
S C -1
M U L E S
T O R A G E
UPDN.
D.F.
F.E.C.
F.E.C.
C
12108 9
H
F
G
K
A
113.41
I
C.4
4.8
QE
10.59.94.5 5.3 6.5 7.5 8.4
AD. ASST.
501D-129
BUS. MAN.
501D-127
PROG. MAN.
501D-126
OFFICE/EXAM
501D-125
OFFICE/EXAM
501D-124
N. ADMIN.
501D-123
SERV. CHIEF.
501D-130
ENTRANCE
501D-131
LANDING
501D-136
COPY /
WORKROOM
501D-120
CUBICLES
501D-128
CORR. B
501D-C4
STAFF T.
501D-133
GUEST T.
501D-117
G. FELLOW
501D-116
G. FELLOW
501D-115
PSYCHOL.
501D-114
N. CASE MAN.
501D-113
OFF. / EX.
501D-112
OFF. / EX.
501D-110
N. CASE MAN.
501D-108
CORRIDOR
501D-C2
OFF. / EX.
501D-111
OFF. / EX.
501D-109
ADMIN. SUPP.
501D-107
WAITING
501D-106
CORR. A
501D-C3
GUEST T.
501D-132
HAC
501D-134
BREAK ROOM
501D-121
LIGHTWELL
501C-125A
ELECTRICAL
501D-104
CORR.
501D-105
LOADING
501D-103
MECHANICAL
501D-102
IT
501D-101
CORRIDOR
501D-C1
CONNECTOR
RAMP
501D-C5
ENTRANCE
501D-100
CONFERENCE
ROOM
501D-122
VAV-1-03
24"x16"
8"ø
6"ø6"ø
VAV-1-02
VAV-1-01
VAV-1-05
VAV-1-06
VAV-1-08
6"ø
8"ø
20"x16"
12"x8" 6"ø 6"ø 6"ø 6"ø
8"ø 8"x8"
5"ø
8"ø
8" x8
12"x8"
6"ø
10"ø
12"x10"
8"ø 6"ø
6"ø 12"x8" 8"ø8"ø
12"ø
5"ø
8"ø
12"x10"
10"ø
8"ø
8"ø
6"ø
8"ø
6"ø
VAV-1-07
VAV-1-04
5"ø 8"ø
5"ø
8"ø
D
D
D
D
B
B
B
B
C
B
B
B
B
A
B
B
B
B
B
C
B
B
B
B
B
B
B
B
B
B
B
B
7"ø
10"ø
12"x10"
8"ø 5"ø
VAV-1-10
VAV-1-13
G
G
G
G
G
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
AC-6AC-5
AC-4
AC-3
AC-2
CU-2
40"x14"
24"x16"
12"x10" 14"x10" 20"x8"
20"x12" 20"x14"
20"x14"20"x12"
"x
"x
16"x10" 8"x8"
8"x8"
8"x6" 6"x6"6"x6" 8"x6"
10"x8"
"x
AC-7
"ø
8"ø12 "x
8"
CU-6 CU-7
MH401
30"x16"
5"ø 8"ø12"x6"
VAV-1-09STOR.
501D-129A
8"ø6"ø 12"x8" 8"x8"
VAV-1-12 CU-8
AC-8
RE
B
B5
C.2
MH401
VAV-1-11
G.5
9.7 9.83.1
1/8" = 1'-0"
FIRST FLOOR DUCTWORK PLAN - CLC ADMIN
th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR DUCTWORK PLAN - CLC ADMIN CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MH101
613-121
JUNE 27, 2018 WAW WNW
1. 10X10 EXHAUST DUCT UP TO EF-1 ON ROOF.
2. 4" OUTSIDE AIR DUCT UP TO ROOF.
3. COORDINATE CONDENSING UNIT LOCATION AS TO NOT
BLOCK FIRE DEPARTMENT CONNECTION ON EXTERIOR OF
BUILDING. PROVIDE CONCRETE PAD UNDER CONDENSING
UNIT.
4. O.A. INTAKE UP TO ROOF INTAKE HOOD.
5. TAP OUT OF BOTTOM OF DUCT. ROUTE DUCT UNDER
BEAM.
6. DUCT TURN DOWN. ROUTE DUCT UNDER BEAM.
7. DUCT THROUGH A SMOKE PARTITION. SEE DETAIL ON
SHEET M502.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
501D
A. THERE IS LIMITED CEILING SPACE. COORDINATE WITH ALL
DISCIPLINES TO PREVENT CONFLICTS.
B. PROVIDE A MANUAL VOLUME DAMPER ON ALL LOW
PRESSURE TAKEOFFS ON SUPPLY, RETURN, AND EXHAUST.
C. SEE SHEET MH105 FOR MECHANICAL WORK REQUIRED IF
ALTERNATE NO.5 - (BID ITEM NO. 6) IS ACCEPTED.
FLOOR DRAIN
CORRIDOR
CD-3
CORRIDOR
D-90
OFFICE
D-88
OFFICE
D-86
OFFICE
D-84
OFFICE
D-83
STORAGE
CD-5
CORRIDOR
D-154
2 BEDROOM
D-155
TOILET
D-156
2 BEDROOM
D-157
TOILET
D-158
KITCHENETTE
CD-1
CORRIDOR
E-138B
MECH. RM.
E-138A
ELEC. RM.RAISED SLAB (TYP.)
E-116B
STORAGE
RAISED SLAB (TYP.)
AP
PSYCH.
502F-127
PSYCH.
502F-129
PSYCH.
502F-125
HAC
502F-122
SOC. WORK.
502F-121
IT
502F-120
PA OFFICE
502F-126DIETICIAN
502F-118
PEER SUPP.
502F-119
DOM SUPV.
SCREEN.
502F-117
DOM STAFF
SCREENER
502F-115
DOM SCREENING
CLERK
502F-113
N. ASSESS.
502F-114
REC. THER.
502F-116
MECHANICAL
502F-128
ELECT
502F-130VESTIBULE
502F-110
SPEC. VEST.
502F-111
N. ASSESS.
502F-109
N. ASSESS.
502F-108
TRIAGE
502F-104
CHECK IN
502F-102
LOBBY
502F-100
PAT. T.
502F-101
WAITING
502F-103
CORR. A
502F-C1
MEDS
502F-106
N. STATION
502F-107
CORR. B
502F-C2
VAV-2-08
VAV-2-07
VAV-2-05
VAV-2-11
VAV-2-10
VAV-2-03
VAV-2-06
VAV-2-04
D
B
B
B
B
B
200B
B
B
A
A
A
C
C
C
C
B
A
D
A
A
A
B
B
B
D
B
B
B
B
B
8"ø
8"ø
20"x15" 20"x15"16"x16"12"x14"
12"ø 16"x15"
10"ø 10"ø
12"ø
10"ø
6"ø
10"ø
10"ø
12"x10"
8"ø 6"ø 8"ø
6"ø
8" x1
0"
"x
"x
5"ø
8"x6"
8"ø 8"ø
8"ø
8"ø
6"ø 6"ø
8"ø
8"ø
6"ø
12"x8"
8"ø
8"ø
8"ø
12"x8"
12"x10"
8"ø
8"ø8"ø
6"ø
12"x12"
7"ø
7"ø
8"ø
12"x8"
8"ø
8"ø
8"ø
7"ø
VAV-2-02
6"ø
"x
8"
AC-1
MANAGER
502F-123
B
170 STAFF T.
502F-124
SPEC. T.
502F-112
18"x12" 14"x12"
22"x14"18"x14" 10"x8"
8"x8"
12"x12"
"x
"x
"x
"x
"x
"x
8" x8
"x
"x
8"
10"x8"
8"x8"
E
175 E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
F
F
VAV-2-09
EF-2
EF-2
EF-2
EF-2
CU-1
VAV-2-01
N. STATION
502F-105
MH401
A
6"ø
AC-9
CU-9
MH401
23 23
22 22
21.4 21.4
21 21
20 20
AA
AA
BB
BB
CC
CC
DD
DD
EE
EE
FF
FF
1/8" = 1'-0"
DOMICILARY DUCTWORK PLAN
th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR DUCTWORK PLAN - DOM CLINIC CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MH102
613-121
JUNE 27, 2018 WAW WNW
1. EXHAUST DUCT UP THROUGH ROOF.
2. ROUTE DUCT UNDER STEEL BEAM AND THEN UP IN
BETWEEN BAR JOIST.
3. TAP OUT OF BOTTOM OF RETURN DUCT.
4. DUCT THROUGH A SMOKE PARTITION. SEE DETAIL ON
SHEET M502.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
502F
A. THERE IS LIMITED CEILING SPACE. COORDINATE WITH
ALL DISCIPLINES TO PREVENT CONFLICTS.
B. CHILLED WATER SUPPLY SHALL BE MAINTAINED TO
THE EXISTING SYSTEM. REMOVE AND REPLACE
PUMPS ONE AT A TIME.
C. PROVIDE A MANUAL VOLUME DAMPER ON ALL LOW
PRESSURE TAKEOFFS ON SUPPLY, RETURN, AND
EXHAUST.
C
12108 9
H
F
G
K
A
I
C.4
4.8 10.59.94.5 5.3 6.5 7.5
EF-1
CU-3
CU-4 CU-5
GV-1
RE
B
B5
C.2
C C C C
G.5
9.7 9.8 th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ROOF PLAN - CLC ADMIN CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MH103
613-121
JUNE 27, 2018 WAW WNW
1/8" = 1'-0"
ROOF PLAN - CLC ADMIN
1. 4" OUTSIDE AIR DUCT DOWN TO CEILING CASSETTE.
2. REFRIGERANT AND CONDENSATE PIPING DOWN TO
CEILING CASSETTE. SEE SHEET MP101 FOR CONTINUATION.
3. OUTSIDE AIR INTAKE HOOD FOR AHU-1. SEE SHEET
MH101 FOR CONTINUATION.
4. PROVIDE ROOF PIPING SUPPORT. MAXIMUM SPACING
SHALL BE AS DEFINED IN SPECIFICATION SECTIONS 23 21 13
AND 23 23 00.
5. SEE DETAIL ON M502 FOR UNIT SUPPORT.
6. ROUTE CONDENSATE PIPING TO NEAREST ROOF DRAIN.
7. CONDENSATE PIPING UP FROM AC-6.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
501D
6 6 6 6
HWR1 1/2" HWR
HWS1 1/2" HWSCWS2" CWS
CWR2" CWR
GV-1
21.4
AABBCCDDEEFF
th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ROOF PLAN - DOM CLINIC CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MH104
613-121
JUNE 27, 2018 WAW WNW
1/8" = 1'-0"
ROOF PLAN - DOM CLINIC
1. PIPING DOWN THROUGH ROOF. SEE CONTINUATION ON
SHEET MP102.
2. 6" EXHAUST DUCT TO CEILING MOUNTED EXHAUST FAN.
SEE SHEET MH102 FOR CONTINUATION.
3. OUTDOOR AIR INTAKE HOOD FOR AHU-2. SEE SHEET
MH102 FOR CONTINUATION.
4. PROVIDE ROOF PIPING SUPPORT. MAXIMUM SPACING
SHALL BE AS DEFINED IN SPECIFICATION SECTIONS 23 21
13 AND 23 23 00.
5. PROVIDE FLEXIBLE EXPANSION JOINT TO ALLOW FOR A
1" DEFLECTION BETWEEN BUILDINGS. SEE DETAIL C ON
SHEET M501.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
502F
C-108
C-109
C-109A
C-110
CW-1
C-112
E-1
C-113
C-111
C-125
C-126
CC-4
MECHANICAL ROOM
ELECTRIC ROOM
GENERATOR ROOM
STAIR # 1
WALKWAY
SERVICE ELEVATOR
LOBBY
ELEV.
SOILED UTILITY
OXYGEN STORAGE
DINING
TOILET
RECREATION
CORRIDOR
B
IO
M E D
S E R V
IC
E C
O R R
S C -1
M U L E S
T O R A G E
UPDN.
D.F.
F.E.C.
F.E.C.
C
12108 9
H
F
G
K
A
113.41
I
C.4
4.8
QE
10.59.94.5 5.3 6.5 7.5 8.4
RE
B
B5
C.2
ELECTRICAL
501D-104
LOADING
501D-103
LIGHTWELL
501C-125A
MECHANICAL
501D-102
IT
501D-101
AC-3 AC-4 AC-5 AC-6
AC-2
AC-8
CU-6 CU-7 CU-8
AC-7
UH-1
EF-3
CU-2
UH-ALT
UH-ALT
UH-ALT
UH-ALT
GV-ALT
EF-ALT
EF-ALT
4 44
G.5
9.7 9.83.1 th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR MECHANCIAL PLAN - CLC ADMIN
- ALTERNATE NO.5 - (BID ITEM NO. 6)
CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MH105
613-121
JUNE 27, 2018 WAW WNW
1/8" = 1'-0"
FIRST FLOOR MECHANCIAL PLAN - CLC ADMIN - ALTERNATE NO. 5 - (BID ITEM NO. 6)
1. ELECTRIC UNIT HEATER. MOUNT 10' AFF.
2. EXHAUST FAN ON ROOF, OPEN TO SPACE BELOW.
PROVIDE WITH ROOF CURB AND BACKDRAFT DAMPER.
3. GRAVITY VENTILATOR ON ROOF, OPEN TO SPACE
BELOW. PROVIDE WITH ROOF CURB AND GRAVITY
DAMPER.
4. SEE SHEET MH103 FOR CONDENSING UNIT LOCATION
ON ROOF.
5. 4" OUTSIDE AIR DUCT UP TO ROOF.
6. REFRIGERANT AND CONDENSATE PIPING TO ROOF.
SEE SHEET MH103 FOR CONTINUATION.
7. ROUTE CONDENSATE PIPING TO FLOOR DRAIN IN
MECHANICAL ROOM. FOLLOW AHU HOUSE KEEPING PAD
OVER TO FLOOR DRAIN. SEE PLUMBING DRAWINGS FOR
DRAIN LOCATION.
8. ROUTE REFRIGERANT PIPING UP WALL AND INTO
BUILDING ABOVE CEILING. ROUTE PIPING IN ELECTRICAL
ROOM TO AVOID RUNNING ABOVE A ELECTRICAL PANEL.
9. MOUNT AC-2 DIRECTLY ABOVE THE DOOR. ROUTE
CONDENSATE PIPING THROUGH WALL TO MECHANICAL
ROOM.
10. ROUTE CONDENSATE PIPING TO ROOF DRAIN.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
A. THIS PLAN SHOWS WORK REQUIRED IF BID ITEM NO. 6
IS TAKEN. CLC ADMIN SPACE SHALL BE HEATED AND
VENTILATED ONLY.
501D
F
G
1110.5
EF-3
26"x20"
30"x16"
26"x20"
14"x60"
AHU-1
1-RF1
24"x16"
40"x14"
30"x16"
AVD
AVD
UH-1
MH401PMP-1
H W
S
1/ 2"
H W
S H
W R
1/
2" H
W R
C W
R 2"
C W
R
CWS2" CWS
MECHANICAL
501D-102
1-SH1
DDC
11 1210.5
PMP-1
PMP-2
30"x16"
CB B.5 C.2
12"ø
6"x6" VAV-1-12 5"ø14"x10" 8"x8"
OFFICE/EXAM
501D-124
CORR. A
501D-C3
CC
12"x18"12"x14"
30"x12"
DOM SUPV.
SCREEN.
502F-117
E
CC
40"x16"
2-RF1 AHU-2
24"x16"
24"x24"
EF-4
UH-2
24"x24"
AVD
AVD
MECHANICAL
502F-128
2-SH1
DDC
CC
th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
ENLARGED PLANS CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MH401
613-121
JUNE 27, 2018 WAW WNW
501D & 502F
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
1/4" = 1' - 0" 0 5' 10' 15'1'
1/4" = 1'-0"
LARGE SCALE MECHANICAL ROOM PLAN - CLC ADMIN
1. RELIEF AIR DAMPER.
2. RETURN AIR DAMPER.
3.24X24 O.A. INTAKE UP TO INTAKE HOOD ON ROOF.
OFFSET TO MISS STRUCTURE.
4. CHILLED WATER PUMP IN PARALLEL. MOUNT ON WALL
ABOUT DOMESTIC WATER PUMPS.
5. DOMESTIC WATER PUMPS.
6. 72X30 RELIEF AIR LOUVER ABOVE THE DOOR.
7. DUCT ROUTED BETWEEN JOIST.
1/4" = 1'-0"
CHILLED WATER PUMP SECTION - CLC ADMIN
1/4" = 1'-0"
CLC ADMIN SECTION
1/4" = 1'-0"
DUCT ROUTING SECTION DETAIL - DOM CLINIC
1/4" = 1'-0"
LARGE SCALE MECHANICAL ROOM PLAN - DOM CLINIC
DN
P-1P-2
4" C
W R
4" C
W S
4"
4" CWR
CWS
4"
C W S
C W R
3" CWS
3" CWR
C W S
5" CWS
5" CWR
P-3P-4
H W R
H W S
1"
H W S
H W R
1/2"
1 1/4"
1/2"
1 1/4" HWS
HWS 3"
1 1/4"
H W R
2" 2"
3"
H W S
HWR
H W R
3" HWR
C-107
C-108
C-109
C-109A
C-110
181 SQ. FT.
CW-1
507 SQ. FT.
C-112
E-1
C-113
C-114
C-111
C-125
59 SQ. FT.
C-124
C-126
C-127
623 SQ. FT.
C-128
660 SQ. FT.
CC-4
WOMEN'S LOCKER
MECHANICAL ROOM
ELECTRIC ROOM
GENERATOR ROOM
STAIR # 1
WALKWAY
SERVICE ELEVATOR
LOBBY
ELEV.
SOILED UTILITY
PHARMACY
OXYGEN STORAGE
DINING
ALCOVE
TOILET
RECREATION
RECREATIONEXAM
CORRIDOR
B
IO
M E D
S E R V
IC
E C
O R R
S C -1
M U L E S
T O R A G E
UPDN.
D.F.
F.E.C.
F.E.C.
C
12108 9
H
F
G
K
A
113.41
I
C.4
4.8
QE
10.59.94.5 5.3 6.5 7.5 8.4
AD. ASST.
501D-129
BUS. MAN.
501D-127
PROG. MAN.
501D-126
OFFICE/EXAM
501D-125
OFFICE/EXAM
501D-124
N. ADMIN.
501D-123
LIGHTWELL
501C-125A CORR.
501D-105
ELECTRICAL
501D-104
LOADING
501D-103
MECHANICAL
501D-102
IT
501D-101
ENTRANCE
501D-100
CONNECTOR
RAMP
501D-C5
CORRIDOR
501D-C1
CORRIDOR
501D-C2
WAITING
501D-106
ADMIN. SUPP.
501D-107
OFF. / EX.
501D-109
OFF. / EX.
501D-111
CONFERENCE
ROOM
501D-122
CORR. A
501D-C3
COPY /
WORKROOM
501D-120
BREAK ROOM
501D-121
CUBICLES
501D-128
SERV. CHIEF.
501D-130
ENTRANCE
501D-131
LANDING
501D-136
CORR. B
501D-C4
GUEST T.
501D-132
STAFF T.
501D-133
HAC
501D-134
STAFF T.
501D-118
GUEST T.
501D-117
G. FELLOW
501D-116
G. FELLOW
501D-115
PSYCHOL.
501D-114
N. CASE MAN.
501D-113
OFF. / EX.
501D-112
OFF. / EX.
501D-110
N. CASE MAN.
501D-108
VAV-1-03VAV-1-04
VAV-1-02
VAV-1-01
VAV-1-07
VAV-1-06
VAV-1-05
VAV-1-08
VAV-1-10 HWR3/4" HWR
HWS3/4" HWS
HWR1" HWR
HWS1" HWS
C W
S 2"
C W
S
H W
S
1/ 2"
H W
S H
W R
1/
2" H
W R
C W
S 2"
C W
S C
W R
2" C
W R
H W
S
1/ 2"
H W
S H
W R
1/
2" H
W R
HWS1 1/4" HWS
HWR1 1/4" HWR
R
AC-2
CU-2
AC-3 AC-4
AC-5
AC-6
AC-7
C
H W
S
1/ 2"
H W
S H
W R
1/
2" H
W R
CU-6
CU-7
AHU-1
VAV-1-13
VAV-1-12
VAV-1-09
T
VAV-1-12
T
VAV-1-08TVAV-1-09
TVAV-1-10
T
VAV-1-06
T
VAV-1-07
TVAV-1-13
T VAV-1-05
VAV-1-11
T
VAV-1-11
T
VAV-1-04
T
VAV-1-03
T
VAV-1-02 T
VAV-1-01
AC-8
CU-8
RE
B
B5
C.2
T
UH-1
UH-1
TEF-3
EF-3
C
G.5
9.7 9.83.1 th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR PIPING PLAN - CLC ADMIN CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MP101
613-121
JUNE 27, 2018 WAW WNW
1/8" = 1'-0"
FIRST FLOOR PIPING PLAN - CLC ADMIN
1. CONNECT TO EXISTING PIPING. REPAIR INSULATION.
2. ROUTE CONDENSATE PIPING TO DRAIN. SEE PLUMBING
DRAWINGS FOR DRAIN LOCATIONS.
3. REFRIGERANT AND CONDENSATE PIPING TO ROOF.
SEE SHEET MH103 FOR CONTINUATION.
4. ROUTE CONDENSATE PIPING TO FLOOR DRAIN IN
MECHANICAL ROOM. ROUTE DOWN WALL AND ALONG
AHU HOUSE KEEPING PAD TO FLOOR DRAIN. SEE
PLUMBING DRAWINGS FOR DRAIN LOCATION.
5. ROUTE REFRIGERANT PIPING UP WALL AND INTO
BUILDING ABOVE CEILING. ROUTE PIPING IN ELECTRICAL
ROOM TO AVOID RUNNING ABOVE A ELECTRICAL PANEL.
6. PIPE THROUGH A SMOKE PARTITION. SEE DETAIL ON
SHEET M502.
7. ROUTE CONDENSATE PIPING TO ROOF DRAIN.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
A. ALL RUNOUTS TO VAVs ARE 3/4" UNLESS NOTED
OTHERWISE.
TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
501D
CD-3
D-90
D-88
D-86
D-84
D-83
CD-5
CD-6
D-154
D-155
D-156
D-157
D-158
D-177
CD-1
E-138B E-138A
E-138C E-138E-116A
E-116B
E-118
CORRIDOR
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
CORRIDOR
CORRIDOR
2 BEDROOM
TOILET
2 BEDROOM
TOILET
KITCWSENETTE
KITCWSENETTEOFFICE
OFFICE
CORRIDOR
MECWS. RM.
ELEC. RM.
TELE. RM.
EMERGENCY
GENERATOR
VENDING
STORAGE
PRIVATE DINING
T
T
T
T
T
H W S
H W R
FAN COIL UNIT
1/ 2"
1/ 2"
3/4"
1/ 2"
2 1/2"
HWR
HWS
3/4"
3/4"
H W S
H W R
3"
3"
HWR
HWS
1 1/4"
HWS
HWR
3/4" 3/4"1"
3/4"
3/4"
3/4"
3/4"
1"
3/4" 3/4"
3/4"
3/4"
3/4" 1"
3/4"
HWS HWR
3/4"1" 3/4"
1/2"
3/4"
3/4"3/4" 3/4"
502-TU-1A
2-
TU
2A
HWS
H W S
HWS
H W R
H W R
HWR
HWR
H W R
H W S
1"
4"
3"
3"
3/4"
4" 502 RF1
502-P3
502-P4
4"
4"
4"
HWR
HWS
H W S
INSTANT HW GEN
INSTANT HW GEN
C W R C W S
3"3"
3/4"
CWS
CWR
C W R
C W S
4"
4"
1 1/2"
CWR
CWS 1 1/2"3/4" CWS
CWR
1"
1 1/2"1" 3/4"
3/4"
1 1/4"
3/4"
3/4"
CWS CWR
3/4"
1 1/4"1 1/4"
3/4"
1/2"
3/4"
3/4"
2 1/2"
3/4"
1 1/4"
1"
C W S
C W R
CWR CWS
4"
6"
4"
4"
6"
6"
6"
6"
2-1/2"
6"
C W S
CWS
CWS
CWR
CWR
CWS
6"
VA
V
FF
DD CC AAEE
BB
21.4
MEDS
502F-106
N. STATION
502F-107
WAITING
502F-103
PAT. T.
502F-101
LOBBY
502F-100
CHECK IN
502F-102
TRIAGE
502F-104
N. ASSESS.
502F-108
N. ASSESS.
502F-109
SPEC. VEST.
502F-111
SPEC. T.
502F-112
VESTIBULE
502F-110
N. ASSESS.
502F-114
ELECT
502F-130
MECHANICAL
502F-128
REC. THER.
502F-116
DIETICIAN
502F-118
IT
502F-120
STAFF T.
502F-124
PA OFFICE
502F-126
CORR. B
502F-C2
PSYCH.
502F-125
PSYCH.
502F-127
PSYCH.
502F-129
MANAGER
502F-123
HAC
502F-122
SOC. WORK.
502F-121
PEER SUPP.
502F-119
DOM SUPV.
SCREEN.
502F-117
DOM STAFF
SCREENER
502F-115
DOM SCREENING
CLERK
502F-113
N. STATION
502F-105
CORR. A
502F-C1
VAV-2-08
VAV-2-07
VAV-2-10
VAV-2-11
VAV-2-05
VAV-2-03
VAV-2-06VAV-2-04
VAV-2-02
AC-1
VAV-2-01
VAV-2-09
HWR1 1/2" HWR
HWS1 1/2" HWS
CWS2" CWS
CWR2" CWR
HWR1" HWR
HWS1" HWS
C W
S 2"
C W
S C
W R
2" C
W R
HWR1 1/2" HWR
HWS1 1/2" HWS
CWS2" CWS
CWR2" CWR
H W
S
1/ 2"
H W
S H
W R
1/
2" H
W R
CU-1
R
EF-2 EF-2
EF-2
EF-2
CWP-1
CWP-2
T
VAV-2-01
T
VAV-2-04
TVAV-2-06
T
VAV-2-07
T VAV-2-09
T VAV-2-10
T
VAV-2-08
T
VAV-2-05
TVAV-2-03
TVAV-2-02
T
VAV-2-11
R
AC-9
CU-9
UH-2
T UH-2T
EF-4
EF-4
MH401
th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
FIRST FLOOR PIPING PLAN - DOM CLINIC CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
MP102
613-121
JUNE 27, 2018 WAW WNW
1/8" = 1'-0"
FIRST FLOOR PIPING PLAN - DOM CLINIC
1. CONNECT CHILLED WATER PUMP TO EXISTING PIPING,
REPAIR INSULATION.
2. PIPING DOWN FROM ROOF. CONNECT TO EXISTING
PIPING. REPAIR INSULATION.
3. PIPING UP TO ROOF. SEE SHEET MH104 FOR
CONTINUATION.
4. ROUTE CONDENSATE PIPING TO FLOOR DRAIN. SEE
PLUMBING DRAWING FOR CONTINUATION.
5. PROVIDE CONCRETE PAD FOR CONDENSING UNIT.
6. THERE IS VERY LIMITED CEILING SPACE, THE TAPS
FOR THE HOT AND CHILLED WATER PIPING SHALL BE
MADE ON TOP OF THE PIPE. ACCESS TO THE TOP OF
THE PIPE WILL BE THROUGH THE ROOF.
7. PIPE THROUGH A SMOKE PARTITION. SEE DETAIL ON
SHEET M502.
8. ROUTE CONDENSATE TO FLOOR DRAIN IN CORNER OF
ROOM.
9. ROUTE CONDENSATE THROUGH THE WALL AND INTO
THE MECHANICAL ROOM. ROUTE DOWN THE WALL AND
OVER TO THE AHU HOUSE KEEPING PAD AND TO FLOOR
DRAIN.
GENERAL NOTES
KEY NOTES
GRAPHIC SCALE(S)
A. ALL RUNOUTS TO VAVs ARE 3/4" UNLESS NOTED
OTHERWISE.
TRUE
NORTH
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
502F
A
NTS
PIPE HANGERS
B
DETAIL FOR SUPPORTING PIPE ON ROOF
NTS
8"x8"x3/8" [203x203x8.0mm] STEEL
PLATE
WELD PLATE TO
PIPE
SECURE TO ROOF SLAB WITH
(4) 3/8" [8.0mm]∅ EXPANSION
BOLTS OR WELD TO STEEL
DECK
CONCRETE ROOF SLAB OR
STEEL ROOF DECK
NOTES:
PROVIDE RESTRAINING CLAMPS 8'-0" [2438] O.C.
C
NTS
NOTE:
1. SEISMIC SEPARATION ASSEMBLY DETAIL SHOWN IN NFPA 13 (SPRINKLER PIPING),
UTILIZING FLEXIBLE MECHANICAL COUPLINGS, MAY BE USED IN LIEU OF PIPING DETAIL
SHOW ABOVE.
DETAIL "A"
(STEEL PIPE FOR WATER/GLYCOL)
HANGER (TYPICAL)
ANCHOR (TYPICAL)
FLEXIBLE
MECHANICAL
COUPLING
(TYPICAL)
SEISMIC
JOINT
PIPING CROSSING A SEISMIC
JOINT DETAIL "A"
d
PIPING CONNECTIONS
D
NTS
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION CONNECTIONS (TYP.)
WATER SUPPLY
TERMINAL UNIT WATER COILS -
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MV
MODULATION CONTROL VALVE
E
NTS
DUCTWORK SQUARE VANE ELBOWS F
NTS
(WITH EQUIPMENT MOUNTED IN DUCT)
DUCTWORK TRANSITIONS
G
NTS
SUPPLY DUCTWORK TAKE-OFFS
BRANCH DUCT TAKE-OFF PLAN VIEW
AIR FLOW
AIR FLOW
AI
R
FL
O W
PROVIDE VOLUME
DAMPER
1/4 W OR
4" [100mm]
MIN.
AIR FLOW
MAIN SUPPLY DUCT
AI
R
FL
O W
H
NTS
SUPPLY DUCT TAKEOFF - AIR TERMINAL UNIT
SCHEDULE FOR PIPING CROSSING
A SEISMIC JOINT
LOCATION PIPE
DIMENSIONS INCHES [mm]
502F-DOM CLINIC CW 12 12 72 60 - -
--HW
a b c d e f
12 12 72 60502F-DOM CLINIC5 FT
THRU [20]
6 8 10
[32][25] [40]
[65]
[50]
[75]
-1312 14 -16 -
[125][100]
[150]
[250]
[200]
[300]
[400]
[350]
[450]
[600]
[500]
20 241814 16128 1064 532 2 1/21 1/21 1 1/4
[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]
--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]
THRU 3/4
[2100] [2100]
[2100]
[2700]
[2400]
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000
LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1
- SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE
43 - SEE SPECIFICATIONS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
[2 5m m
1"
M
AX
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
8"
[2 m m
4" [1 m m
M
IN
[3 m m
ROOF SYSTEM INSULATION
AND MEMBRANE
PRE-MOULDED FLEXIBLE
PIPE COUNTER FLASHING
CLAMPING RING
ROOF SURFACE
WELD PIPE SADDLE
SUPPORT TO PIPE.
PROVIDE WATER TIGHT
CONNECTION
HIGH COMPRESSIVE
STRENGTH INSULATION
INSERT UNDER SHIELD
PIPE AND
INSULATION
INSULATION
PROTECTION
SHIELD
SEALANT
2" [50mm] STEEL
PIPE
2-1/2" [65mm] STEEL
PIPE
PROVIDE ALUMINUM JACKET
NOTE:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE
TYPE REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING
EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL
BE DOUBLE VANE TYPE.
W
W1
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS,
MAXIMUM ANGLES SHOWN SHALL APPLY.
M
AX
30°
MAX.
EQ
U
IP
M
EN
T
AIR FLOW AIR FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
MA
X.
M
AX.
M
AX
M
AX
AIR SPLIT DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER
TAKE-OFF PLAN
VIEW
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN SUPPLY
DUCT
SEE FLOOR PLAN
FOR SPLIT DIMENSION
PROVIDE VOLUME
DAMPER
ADJUSTABLE METAL
ROD OR LINKAGE
TOP REGISTER
MAIN SUPPLY DUCT
VOLUME EXTRACTOR; ADJUSTABLE FROM
FULLY CLOSED POSITION TO CFM NOTED ON
FLOOR PLANS
AIR FLOW AIR FLOW
RIGID DUCT TO AIR
TERMINAL UNIT.
ROUND SHEET
METAL DUCT.
MAIN SUPPLY
"D"
45°M
AX.
PLAN VIEW
AT ANCHOR POINTS
PROVIDE SECURE
CONNECTION
WELD
SADDLE
HANGER ROD
d c b a b
15°
W th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
DETAILS CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
M501
613-121
501D & 502F
A
NTS
DUCT CONNECTIONS - AIR TERMINAL UNITS
NOTE:
1.
2.
3.
4.
5.
6.
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A
MINIMUM OF 3 TIMES THE DIAMETER OF INLET
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT
ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0" [900mm].
A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX
INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES
NOT EXCEED 10 FEET (3 METERS). FOR LONGER LENGTHS, INCREASE THE DUCT
SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE
DROP AT OR BELOW 0.2"/100' [1.64Pa/m].
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR
DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID ELBOWS FOR
CHANGE OF DIRECTION GREATER THAN 45°.
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED FOR THE
DEDICATED AHU SERVING THE SURGICAL SUITE.
AIR TERMINAL UNIT
(CV OR VAV)
REHEAT COIL
SOUND ATTENUATOR
SEE EQUIPMENT
SCHEDULE
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
DIFFUSER (TYP.)
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
SEE NOTE 5
F
NTS
EXHAUST OR RETURN BRANCH DUCTWORK
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR FLOW
AIR FLOW
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" [100mm]
MIN.
BRANCH DUCT
VD
G
NTS
VOLUME DAMPER DETAIL
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE
DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE ALL
AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING QUADRANT
INSULATION STAND-OFF
1/2" [15mm] ROUND
ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
SECTION "A-A"
"B" "B"
D
ACCESS PANEL AND DOOR DETAIL
NTS
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
ACCESS PANEL
ACCESS DOOR
CASING
GASKET
HANDLE INSIDE
FLEXIBLE
WASHER
FACTORY
FABRICATED
LATCH
SECTION "B-B"
INSULATION
DUCT
GASKET
INSULATION
INSULATION
"A"
"A"
E
NTS
FLEXIBLE DUCT CONNECTIONS
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED CONNECTION
ON FAN SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS ON 12"
[300mm] CENTERS
RIVET ON 4"
[100mm] CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEMALTERNATE
POSITION OF
BOLT 1 1/2" [40mm]
POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLANGED
CONNECTION ON
FAN SIDE
WASHER
FLEXIBLE MATERIAL AS
SPECIFIED
WATER COILS - PIPING CONNECTIONS
B
NTS
SINGLE COIL
WATER COIL
AIR VENT WHEN
COIL
IS NOT
SELF-VENTING
DRAIN WHEN COIL IS NOT
SELF-DRAINING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT PIPING
INDEPENDENT OF COIL
REDUCER, IF REQUIRED
DRAIN
WATER COIL
AIR VENT WHEN
COIL
IS NOT
SELF-VENTING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT PIPING
INDEPENDENT OF COIL
WATER COIL
REDUCER, IF REQUIRED
FLOW ELEMENT
DRAIN WHEN COIL IS NOT
SELF-DRAINING
DRAIN
DOUBLE COIL
NOTE:
1.
2.
3.
WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 4" [100mm]∅ PIPE & SMALLER. TYPE "H-P" FOR 5" [125mm]∅ PIPE & LARGER.
PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALES, OR
EQUIPMENT.
THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM
UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE RETURN PIPING.
FE
MV
MV
MV
MV
MVMV
FE
TI
TI
TEMPERATURE
INDICATION TO ECC
SEE CONTROL DIAGRAM
MV
PIPING CONNECTIONS
C
NTS
UNIT HEATERS (HOT WATER) -
TYPICAL CONNECTIONS TO VERTICAL HOT
WATER UNIT HEATER
TYPICAL CONNECTIONS TO HORIZONTAL HOT
WATER UNIT HEATER
UNIT HEATER
HO
T
WA
TE
R
SU
PP
LY
HO
T
WA
TE
R
RE
TU
RN
HO
T
WA
TE
R
SU
PP
LY
HO
T
WA
TE
R
RE
TU
RN
UNIT HEATER
AIR VENT
TEST PLUG, TYP.
SHUTOFF BALL
VALVE, TYP.
WYE STRAINER,
TYP.
MV
MV
AUTOMATIC FLOW
CONTROL VALVE
NOTE: UNIT MOUNTED
THERMOSTAT SHALL
MAINTAIN SPACE
TEMPERATURE BY
CYCLING
AUTOMATIC FLOW
CONTROL VALVE
H
NTS
INLINE FAN SUPPORT DETAIL
VIBRATION ISOLATORS
TRANSITION
FLEXIBLE CONNECTION
RETURN FAN
MOTOR
SEE FLOOR PLAN
FOR DUCT SIZES
FLEXIBLE CONNECTION
3/8" THREADED ROD
I
NTS
AHU-1 AND AHU-2 COMPONENT DIAGRAM
NOTE:
1.
2.
3.
MIXING BOX
AIR FILTER
HOT WATER COIL
4.
5.
CHILLED WATER COIL
SUPPLY AIR PLENUM FAN
1 2 3 4 5RETURN AIR
SUPPLY AIROUTSIDE AIR
MAX DIMENSIONS
(LXWXH)
13' 4" X 5' 7" X 3' 5"
MOUNTING PLATFORM
ROOF
PIPING
SUSPENDED CEILING
CEILING RECESSED INDOOR UNIT
SPLIT-TYPE AIR CONDITIONER
ROOF CAP
W/ BIRDSCREENSHEET METAL CAP
REFRIGERANT
GALV. METAL
FLASHING
24 GAUGE
FLASHING
AIR CONDITIONER
SPLIT-TYPE
FRONT FAN GRILLE
OUTDOOR UNIT.
ANCHOR BOLTS
OUTSIDE AIR DUCT
SEE FLOOR PLAN
FOR DUCT SIZE
J
NTS
SPLIT SYSTEM AC - CEILING MOUNTED CASSETTE
K
PENETRATION OF SMOKE/FIRE BARRIERS
NTS
NOTE:
1. APPLICABLE TO PENETRATIONS OF ALL
FIRE RATED MEMBRANES, IN ACCORDANCE
WITH NFPA 101. REFER TO
SPECIFICATIONS SECTION 07 84 00, FIRE
STOPPING SYSTEMS.
PARTITION OR CHASE PENETRATION
PIPE/DUCT
[150mm] [150mm]
MASONRY PARTITION
PARTITION SUPPORT
FIRESTOP
MATERIAL
[150mm] [150mm]
3/4" [19mm] APPROVED
FIRESTOP INSULATION WITH
VAPOR BARRIER
DRYWALL PARTITION
INSULATED
DUCT
OR PIPE
SE
E N O
TE
SEE NOTE 3
SEE NOTE 2
SEE NOTE 1
W
1/2" 1/2" 1 1/2"
6" 6"
6" 6" th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
DETAILS CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
M502
613-121 th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
SCHEDULES CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
M601
613-121 th re e in ch es o ne fo ot 6"
Department of Veterans Affairs on e an d on e ha lf in ch es o ne fo ot
6" on e in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot on e ei gh th in ch o ne fo ot
6"
6"
VA FORM 08-6231
Revisions:
1 2 3 4 5 6 7 8 9
Date:
CONSULTANTS: ARCHITECT/ENGINEERS:
590 MEANS ST NW ATLANTA, GA 30318
Drawing Title:
Approved Project Director:
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number:
Building Number:
Project Number:
Dwg. of
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
BID DOCUMENTS
SCHEDULES CONSTRUCT DOM CLINIC
AND CLC ADMINISTRATION
ADDITION
MARTINSBURG, WV
M602
613-121
CWR
CWR
CWR
CWR
NTS
HWS
HWR
V-2ROOM THERMOSTAT/SENSOR
WALL MOUNTED
48" [1200mm] AFF.
ROOM THERMOSTAT/SENSOR
WALL MOUNTED
48" [1200mm] AFF.
VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM
NO SUPPLEMENTAL HEATING WITH SUPPLEMENTAL HEATING
A
IR
F L O
W (C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
VAV BOX CONTROL SEQUENCE
SP
TU
RHCHWS
HWR
V-1
REHEAT
COIL
AIR
TERMINAL
UNIT
AIR FLOW
TE
ATU
CONTROLLERPC
TE
TU
RHC
HWS
HWR
V-1
REHEAT
COIL
AIR
TERMINAL
UNIT
AIR FLOW
TE
ATU
CONTROLLER
PC
TE
A
IR
F L O
W (C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
SP
A
IR
F L O
W (C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
SP
A
IR
F L O
W (C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
NO DEADBAND
VAV BOX CONTROL SEQUENCE
W/DEADBAND
VAV BOX CONTROL SEQUENCE
NO DEADBAND
VAV BOX CONTROL SEQUENCE
W/DEADBAND
SUPPLEMENTAL
HEAT
SP
FE
100% 100%
100% 100%
R
EH
EAT FLO
W
VAV A
IR
F
LO
W
V A V A
IR
F
LO
W
VAV A
IR
F
LO
W
V A V A
IR
F
LO
W
R E H E A
T FLO
W
REHEAT FLO
W
SUPP FLO
W
R E H E
AT FLO
W
S U
PP
FLO
W
A. UPON FALL IN SPACE TEMPERATURE THE
VAV DAMPER WILL MODULATE TO MINIMUM
POSITION.
B. UPON FURTHER DROP IN SPACE
TEMPERATURE VALVE V-1 WILL MODULATE
TO MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5° F HAS
BEEN SELECTED TO PREVENT VALVE
HUNTING
C. THE REVERSE SHALL OCCUR ON THE RISE
IN SPACE TEMPERATURE.
A. SET POINTS SHALL BE SET AS FOLLOWS:
COOLING 75°F (ADJ)
HEATING 70°F(ADJ)
DEADBAND OF 5° F BETWEEN HEATING AND
COOLING SET POINTS WILL BE MAINTAINED.
B. UPON FALL IN SPACE TEMPERATURE THE
VAV DAMPER WILL MODULATE TO MINIMUM
POSITION.
C. UPON FURTHER DROP IN SPACE
TEMPERATURE VALVE V-1 WILL MODULATE
TO MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5° F HAS
BEEN SELECTED TO PREVENT VALVE
HUNTING
D. THE REVERSE SHALL OCCUR ON THE RISE
IN SPACE TEMPERATURE.
A. UPON FALL IN SPACE TEMPERATURE THE
VAV DAMPER WILL MODULATE TO MINIMUM
POSITION.
B. UPON FURTHER DROP IN SPACE
TEMPERATURE VALVE V-1 WILL MODULATE
TO MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5° F HAS
BEEN SELECTED TO PREVENT VALVE
HUNTING
C. VALVE V-2 SHALL BE ENABLED WHEN
OUTSIDE AIR FALLS BELOW 40° F (ADJ)
AND VALVE V-1 HAS BEEN MODULATED
OPEN ABOVE 30% (ADJ). VALVE V-2
SHALL MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5°F HAS
BEEN SELECTED TO PREVENT VALVE
HUNTING. THE REVERSE SHALL OCCUR ON
A RISE IN SPACE TEMPERATURE.
A. SET POINTS SHALL BE SET AS FOLLOWS:
COOLING 75°F (ADJ)
HEATING 70°F(ADJ)
DEADBAND OF 5° F BETWEEN HEATING AND
COOLING SET POINTS WILL BE MAINTAINED.
B. UPON FALL IN SPACE TEMPERATURE THE
VAV DAMPER WILL MODULATE TO MINIMUM
POSITION.
C. UPON FURTHER DROP IN SPACE
TEMPERATURE VALVE V-1 WILL MODULATE
TO MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5° F HAS
BEEN SELECTED TO PREVENT VALVE
HUNTING
D. VALVE V-2 SHALL BE ENABLED WHEN
OUTSIDE AIR FALLS BELOW 40° F (ADJ)
AND VALVE V-1 HAS BEEN MODULATED
OPEN ABOVE 30% (ADJ). VALVE V-2
SHALL MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5°F HAS
BEEN SELECTED TO PREVENT VALVE
HUNTING.
E. THE REVERSE SHALL OCCUR ON THE RISE
IN SPACE TEMPERATURE.
FE
NTS
VARIABLE AIR VOLUME AIR HANDLING UNIT WITH OUTSIDE AIR CONTROL DIAGRAM (AHU-1 AND AHU-2)
EXHAUST AIR
D-3
D-2
P R
E
F
IL
T E
R
OUTSIDE
AIR
D-1
C O
IL
P
R E
H E
A T
C O
IL
C
O O
L
IN
G
LOCATE SENSOR
OUTSIDE UNDER
SHIELD
MPS
V-2
V-1
CHR
CHS
RETURN FAN
SUPPLY FAN
A F
M D
RETURN
AIR
A F
M D
SUPPLY AIR TO
TERMINAL UNIT
TT
TT
TT TT
FTA
F T
E R
F
IL
T
E R
TT MT
D-4
A F
M D
MINIMUM
OUTSIDE
AIR
HS
IT
VSMC
HSVSMC
FT
3 6
H-1
SD
HOT WATER
CURRENT
TRANSMITTER
FOR FAN
STATUS ,TYP.
PRESSURE SWITCH LOW
TO DISABLE RETURN FAN WHEN SMOKE
DAMPER IN RETURN DUCT CLOSES
PRESSURE SWITCH HIGH
TO DISABLE FAN WHEN
HIGH PRESSURE LIMIT
SETPOINT IS REACHED
PSH
SMOKE
DETECTOR
VARIABLE SPEED MOTOR
CONTROLLER, TYP.
ZC
ZC
ZC
ZC
FT PDS PDS
TT
SST
PSL
IT
SST
SD
SPSTSL
TSL-1
NO
V-3
LPS
V-4
ELECTRIC TO STEAM HUMIDIFIER
MS
MC
ECC
ECC
MT
1. GENERAL
1.1 UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE
"AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS
"OFF" D-1, D-3, SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" D-1, SD-1 AND SD-2 SHALL BE FULLY OPEN. D-2
AND D-3 SHALL MODULATE IN ACCORDANCE WITH THE FOLLOWING SEQUENCE:
2. TEMPERATURE CONTROL
2.1
2.2
2.3
2.4
3. AIR FLOW CONTROL
3.1
3.2
3.3
4. HUMIDITY CONTROL
4.1
4.2
5. FREEZE PROTECTION
5.1
6. AUTOMATIC SHUTDOWN/RESTART
6.1
6.2
7. EMERGENCY CONSTANT SPEED OPERATION
7.1
SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT VIA DIGITAL CONTROL
PANEL BY MODULATING V-1 OR D-2 AND D-3 OR V-2 IN SEQUENCE.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS ABOVE 75°F (ADJ) [23.8°C], THE DIGITAL
CONTROL PANEL SHALL PREVENT…