Attachment J - Internal Inspection of Sprinkler System Piping and Valves_Main Bldg..pdf

PDF 1 MB Posted

Attached to
SPRINKLER SYSTEM INSPECTION AND REPAIR
Solicitation number
36C24426Q0619
Issued by

About this file

This document contains internal examination reports for sprinkler system piping and valves at VA Medical Center, 1111 East End Blvd, Wilkes-Barre, PA 18702. The reports are prepared by Johnson Controls Fire Protection LP and document the results of systematic inspections conducted between May and July 2021.

The examinations cover multiple sprinkler systems across different stairwells and floors, including dry systems, wet systems, boiler room systems, warehouse storage systems, and sectional systems. Each examination form documents the system identification, number of branchlines and feed mains examined, and other points inspected (such as Viking MJ-I alarm valves, siamese check valves, and sectional piping). All systems examined passed their internal inspections. The reports recommend that copies be forwarded to the facility's insurance carrier for rating purposes. All inspections were conducted and witnessed by authorized personnel with signatures and dates documented on each form. The examination standard appears to follow industry practices for fire protection system compliance and maintenance verification.