Atch 6.Heinz_May 2020_Final Report.pdf
PDF 2 MB Posted
- Attached to
- H961--VAPHS Triennial Electrical Inspections Federal contract opportunity
- Solicitation number
- 36C24426Q0055
About this file
This document is a Customer Field Service Report from ABM Electrical Power Solutions detailing electrical power equipment testing performed in May 2020 at the VA Pittsburgh Healthcare Center (Heinz). The report documents maintenance testing and inspection of electrical equipment in multiple buildings, specifically noting critical findings including a defective B-Phase cable lug with melted insulation in Building #50, 1A-123, and a breaker in Building #50 GA140 MSB Distribution Panels that failed to trip during long time, short time, and instantaneous tests.
The related federal contract opportunity is Solicitation Number 36C24426Q0055 for "H961--VAPHS Triennial Electrical Inspections" issued by the Department of Veterans Affairs. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Business, seeking FY26 Triennial Breaker Inspections. The solicitation has a NAICS code of 811210 with a size standard of $34.0M, and critical dates include a question submission deadline of January 5, 2026, and a quote submission deadline of January 8, 2026. The point of contact is Allan Tabliago, and all communications must be via email.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Atch 7.Heinz_June and July 2020_Final Report.pdf | ||
| Atch 4.UD August 2020-July 2021_Final Report.pdf | ||
| 36C24426Q0055 0002_1.docx | DOCX document | |
| Atch 5.Heinz_April 2020_Final Report.pdf | ||
| Atch 3.Equipment List - Breaker Testing List UD- April 2015.xlsx | XLSX spreadsheet | |
| Atch 2.UD Elect and Arc Flash Study.pdf | ||
| Atch 1.HZ Elect and Arc Flash study 2023 reduced.pdf | ||
| 36C24426Q0055 0001_1.docx | DOCX document | |
| VAAR 852.219-75 VA Notice of Limitations on Subcontracting.pdf | ||
| 36C24426Q0055 Triennial Inspectiona.pdf | ||
| WD 2015-4235 R32 20251203.pdf | ||
| 36C24426Q0055_1.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER
ADDRESS
CUSTOMER
FIELD SERVICE REPORT
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE
Description:
In May, 2020 ABM Electrical Power Solutions Field Personnel were at Department of Veterans Affairs, VA Pittsburgh Healthcare, (Heinz) located in Pittsburgh, PA to perform testing of electrical power equipment.
Engineering Evaluation:
Testing was performed in accordance with the International Electrical Testing Association's Maintenance Testing Specifications and project specifications.
Scope of Work:
Perform Maintenance testing and cleaning of electrical power equipment.
Test Results / Comments:
(Heinz) Building #50, 1A-123, ECIE; B-Phase, Line side Cable lug is defective. There are signs of the lug heating up and the lug is discolored, also the cable insulation is melted.
(Heinz) Building # 50, GA140, MSB, Distribution Panels: GAPA/1APA; Breaker failed due to no trip during long time, short time and instantaneous tests.
(Heinz) Building # 52, BA107, MSG; Long and Short time function will not trip per test set.
All other test results are acceptable per NETA - MTS Standards. All equipment was left in Satisfactory Operational Condition.
This report certifies that the above equipment has been tested in compliance with recognized standards or for safe use in a specific manner, or in accordance with
Federal, State or Municipal regulations. The report is accurate and true to the best of our knowledge and belief. All equipment used in making physical determinations is accurate and bears recent and direct traceability to the National Institute of Standards and Technology. (NIST).
1/24/2022
By:
Josh Schoedel www.abm.comABM Electrical Power Solutions REVISED 1/24/2022
ABM Electrical Power Solutions 317 Commerce Park Drive Cranberry Township, PA 16066
Project Manager
Equipment Tested Job #86301680 www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
1PAGE
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
115910- MCB - 3 in 1 REV.1 (7)
(HEINZ) BLDG #50 1A-123 1ELA
215910- MCB - 3 in 1 REV.1 (8)
(HEINZ) BLDG #50 1A-123 1EPA
315910- MCB - 3 in 1 REV.1 (8)
(HEINZ) BLDG #50 1A-123 1EPB
415910- MCB - 3 in 1 REV.1 (8)
(HEINZ) BLDG #50 1A-123 1EPC
515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 1A-123 EC1E
615910- MCB - 3 in 1 REV.1 (7)
(HEINZ) BLDG #50 1A-133 1APA
715910- MCB - 3 in 1 REV.1 (6)
(HEINZ) BLDG #50 1A-133 1APB
815910- MCB - 3 in 1 REV.1 (9)
(HEINZ) BLDG #50 1A-146 1WLA
915910- MCB - 3 in 1 REV.1 (10)
(HEINZ) BLDG #50 1A-146 1WPA
1015910- MCB - 3 in 1 REV.1 (10)
(HEINZ) BLDG #50 1A-146 1WPB
1115910- MCB - 3 in 1 REV.1 (10)
(HEINZ) BLDG #50 1A-146 1WPC
1215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 1A-146 EC1W
1356710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #50 2A101 50-T-AC1
1415065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 2A101 MCC-P1
1615910- MCB - 3 in 1 REV.1 (7)
(HEINZ) BLDG #50 2A101 MCC-P1
1715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 GA125 ECGE
1815910- MCB - 3 in 1 REV.1 (6)
(HEINZ) BLDG #50 GA125 GELA
1915910- MCB - 3 in 1 REV.1 (3)
(HEINZ) BLDG #50 GA125 GEPA
2015910- MCB - 3 in 1 REV.1 (4)
(HEINZ) BLDG #50 GA125 GEPB
2115910- MCB - 3 in 1 REV.1 (5)
(HEINZ) BLDG #50 GA125 GEPC
2215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 GA135 ELGA
2315910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #50 GA135 GALA
2415910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #50 GA135 GAPA
2515910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #50 GA135 GAPC
2615610 - LV DISCONNECT SWITCH
(HEINZ) BLDG #50 GA135 SMOKING SHELTER
2754100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #50 GA140 ATS-1
2854100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #50 GA140 ATS-2
2PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
2954100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #50 GA140 ATS-3
3015910- MCB - 3 in 1 REV.1 (HEINZ) BLDG #50 GA140 ATS-3 Emergency Disconnect
3154101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass
(HEINZ) BLDG #50 GA140 ATS-4
3315065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA140 ATS-4 Emergency Disconnect
3556710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #50 GA140 B50-TX1
3756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #50 GA140 B50-TX2
3856710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #50 GA140 B50-TX3
3915065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)
(HEINZ) BLDG #50 GA140 ECGS
4015910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 GA140 ECGS
4115065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN) - Pass
(HEINZ) BLDG #50 GA140 ELCG
4215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-1) - Pass
(HEINZ) BLDG #50 GA140 ELCG
4315910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 GA140 ELCG
4415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 GA140 ELGS
4515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 GA140 GAPB
4615065 - LOW VOLT. PWR. CKT. BKR. TEST (SANIPAC) - Pass
(HEINZ) BLDG #50 GA140 MSB
4715065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. 1WPA/1WPB/1WPC)
(HEINZ) BLDG #50 GA140 MSB
4815065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE POSITION 4)
(HEINZ) BLDG #50 GA140 MSB
4915065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GEPA/GEPB/GEPC)
(HEINZ) BLDG #50 GA140 MSB
5015065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GWPA/GWPB/GWPC)
(HEINZ) BLDG #50 GA140 MSB
5115065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL K)
(HEINZ) BLDG #50 GA140 MSB
5215065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GWLA/1WLA) - Pass
(HEINZ) BLDG #50 GA140 MSB
5315065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS #3)
(HEINZ) BLDG #50 GA140 MSB
5415065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. 1EPA/1EPB/1EPC)
(HEINZ) BLDG #50 GA140 MSB
5515065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)
(HEINZ) BLDG #50 GA140 MSB
5615065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL. GAPB) - Pass
(HEINZ) BLDG #50 GA140 MSB
3PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
5715065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE POSITION 3)
(HEINZ) BLDG #50 GA140 MSB
5815065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE POSITION 15) - Pass
(HEINZ) BLDG #50 GA140 MSB
5915065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS #4)
(HEINZ) BLDG #50 GA140 MSB
6015065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS #1)
(HEINZ) BLDG #50 GA140 MSB
6115065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GAPA/1APA)
(HEINZ) BLDG #50 GA140 MSB
6215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS #2)
(HEINZ) BLDG #50 GA140 MSB
6315065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GELA/1ELA)
(HEINZ) BLDG #50 GA140 MSB
6415065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GALA/1ALA)
(HEINZ) BLDG #50 GA140 MSB
6515065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GAPC/1APB) - Pass
(HEINZ) BLDG #50 GA140 MSB
6615065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL. GALB) - Pass
(HEINZ) BLDG #50 GA140 MSB
6715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #50 GA153 ECGW
6815910- MCB - 3 in 1 REV.1 (6)
(HEINZ) BLDG #50 GA153 GWLA
6915910- MCB - 3 in 1 REV.1 (3)
(HEINZ) BLDG #50 GA153 GWPA
7015910- MCB - 3 in 1 REV.1 (4)
(HEINZ) BLDG #50 GA153 GWPB
7115910- MCB - 3 in 1 REV.1 (5)
(HEINZ) BLDG #50 GA153 GWPC
7215610 - LV DISCONNECT SWITCH
(HEINZ) BLDG #50 GA169 ELEV-PS1
7315610 - LV DISCONNECT SWITCH
(HEINZ) BLDG #50 GA169 ELEV-PS2
7415065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #52 1A104 52-CCU-3 (CHILLER NO.3)
7531300 - MEDIUM VOLTGE VACUUM MOTOR START
(HEINZ) BLDG #52 1A104 52-CT-1
7731300 - MEDIUM VOLTGE VACUUM MOTOR START
(HEINZ) BLDG #52 1A104 52-CT-2
7956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #52 1A104 B52-T-C
8056700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BLDG #52 1A104 B52-T-CHILL3
8115910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #52 1A104 C
8215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #52 1A104 CA
8329000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #52 1A104 SW-B52CHILL
4PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
8429000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #52 1A104 SW-B52CHILL3
8515065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-1) - Fail
(HEINZ) BLDG #52 BA107 MSG
8715065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL CA) - Pass
(HEINZ) BLDG #52 BA107 MSG
8915065 - LOW VOLT. PWR. CKT. BKR. TEST (TRANSFER SWITCH) - Pass
(HEINZ) BLDG #52 BA107 MSG
9115065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL GA) - Pass - Pass
(HEINZ) BLDG #52 BA107 MSG
9315065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-2) - Pass
(HEINZ) BLDG #52 BA107 MSG
9515065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)
(HEINZ) BLDG #52 BA107 MSG
9716100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - 5KV CHILLER (CKT #9)
9841200 - DIGITRIP OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - 5KV CHILLER (CKT #9)
9916100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - BLDG 50/51 (CKT #10)
10041200 - DIGITRIP OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - BLDG 50/51 (CKT #10)
10116100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - BLDG 70/71/IT (CKT #11)
10241200 - DIGITRIP OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - BLDG 70/71/IT (CKT #11)
10316100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - 5KV CHILLER (CKT #13)
10441200 - DIGITRIP OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - 5KV CHILLER (CKT #13)
10516100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - BLDG 50/51 (CKT #14)
10641200 - DIGITRIP OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - BLDG 50/51 (CKT #14)
10716100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - BLDG 70/71/IT (CKT #15)
10841200 - DIGITRIP OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - BLDG 70/71/IT (CKT #15)
10915065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LC)
(HEINZ) BLDG #69 1B116 MSB
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 1ELA Pass
208VOLTAGE
CAH31505W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
150 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
641 641
37.21 37.21
N/A N/A
AS FOUND AS LEFT
480 480
29.34 29.34
N/A N/A
AS FOUND AS LEFT
564 564
27.76 27.76
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
COMMENTS: Could not perform Insulation Resistance test due to connected devices.
DEFICIENCIES:
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 1EPA Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
370 370
48.50 48.50
N/A N/A
AS FOUND AS LEFT
330 331
45.40 45.40
N/A N/A
AS FOUND AS LEFT
356 356
42.21 42.21
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 1EPB Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
638 638
45.51 45.51
N/A N/A
AS FOUND AS LEFT
543 543
46.87 46.87
N/A N/A
AS FOUND AS LEFT
570 570
44.11 44.11
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 1EPC Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
472 472
58.07 58.07
N/A N/A
AS FOUND AS LEFT
353 353
45.14 45.14
N/A N/A
AS FOUND AS LEFT
375 375
41.02 41.02
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
BK/CPTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0042/P0022/P0585
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 EC1E Needs Attention
240 VACVOLTAGE
CAH3150W FRAME SIZE/RATING PLUG
Westinghouse TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
150/150 INT. RATING 22KA @ 240VAC
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
EC1E Main Breaker
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
521 511
36.63 36.63
2200 2200
2200 2200
AS FOUND AS LEFT
577 534
37.70 37.70
2200 2200
2200 2200
AS FOUND AS LEFT
519 501
31.94 31.94
2200 2200
2200 2200
Acceptable
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable C
N/A
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
C
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
COMMENTS:
DEFICIENCIES: Found B-Phase, Line side Cable lug is defective. There are signs of the lug heating up and the lug is discolored, also the Cable insulation is melted.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/16/20 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-133 1APA Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
371 371
43.95 43.95
N/A N/A
AS FOUND AS LEFT
324 324
37.18 37.18
N/A N/A
AS FOUND AS LEFT
374 374
35.17 35.17
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-133 1APB Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
441 441
41.86 41.86
N/A N/A
AS FOUND AS LEFT
400 400
45.58 45.58
N/A N/A
AS FOUND AS LEFT
523 523
42.35 42.35
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 1WLA Pass
208VOLTAGE
CAH31505W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
150 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
553 553
24.37 24.37
N/A N/A
AS FOUND AS LEFT
557 557
22.59 22.59
N/A N/A
AS FOUND AS LEFT
543 543
20.46 20.46
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 1WPA Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
380 380
29.03 29.03
N/A N/A
AS FOUND AS LEFT
376 376
32.27 32.27
N/A N/A
AS FOUND AS LEFT
370 370
29.87 29.87
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 1WPB Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
366 366
43.97 43.97
N/A N/A
AS FOUND AS LEFT
343 343
40.60 40.60
N/A N/A
AS FOUND AS LEFT
418 418
38.06 38.06
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 1WPC Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
378 378
39.71 39.71
N/A N/A
AS FOUND AS LEFT
373 373
33.12 33.12
N/A N/A
AS FOUND AS LEFT
403 403
34.15 34.15
N/A N/A
Acceptable
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
BK/CPTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0042/P0022/P0585
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 EC1W Pass
240 VACVOLTAGE
CAH3150W FRAME SIZE/RATING PLUG
Westinghouse TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
150/150 INT. RATING 22KA @ 240VAC
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
EC1W Main Breaker
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
573 548
24.69 24.69
2200 2200
2200 2200
AS FOUND AS LEFT
511 503
23.59 23.59
2200 2200
2200 2200
AS FOUND AS LEFT
540 529
24.48 24.48
2200 2200
2200 2200
Acceptable
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable C
N/A
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
C
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
EQPT. LOCATION
ADDRESS
CUSTOMER
TRANSFORMER (<500KVA) TEST
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 2A101 50-T-AC1 Pass
BK/CP/KS/MMTESTED BY:
www.abm.comABM Electrical Power Solutions 56710, REVISED 8/5/2019
REVIEWED BY:EQPT. INVENTORY NO. P0090
VISUAL AND MECHANICAL INSPECTION
INSPECT PHYSICAL AND MECHANICAL CONDITION
VERIFY FANS OPERATE (IF APPLICABLE)
INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING
INSPECTION REPORT
FAIL
FAIL
FAIL
PASS
PASS
PASS
INSPECTION REMARKS
NO FANS
1.82502
1,000
1.33231
1,000
1.82502
MINUTES
PRIMARY TO
GROUND
SECONDARY TO
GROUND
PRIMARY TO
SECONDARY
TEST V
0.50
1.00
10.00
P. I.
PHASE B PHASE CCALCTAP
762000
1103000
2013000
974000
1300000
1732000
762000
1103000
2013000
TRANSFORMER TURN RATIO TEST (OPTIONAL)
PASS FAILVERIFY SHIPPING BRACKETS REMOVED
PASS FAILVERIFY THAT RESILIENT MOUNTS ARE FREE
PASS FAILVERIFY THE UNIT IS CLEAN
PASS FAILVERIFY BOLTED ELECTRICAL CONNECTIONS
INSULATION RESISTANCE IN MEGOHMS
PHASE A
1-5
/112.5 NA
5.1
NAMEPLATE DATA
NoneSERIAL NO.
504 492 480 468
1-2 1-3 1-4 1-5 1-6
468 VOLTS
Westinghouse YR MFR NA
KVA
IMPEDANCE /AA
WINDING MATERIAL °CCOPPER
1-5
CLASSTYPE
B.I.L. RATINGTEMPERATURE RISE
PRIMARY V
TAP POSITION
TAP SETTING
TAP VOLTAGES
DT-3
MANUFACTURER
SECONDARY V 208 WYE
120/
DELTA
1-8
432444
1-7
1-5AL
ELECTRICAL TESTS
1,000
WORKING TAP AFP.I. = 10 min/1 min
COMMENTS: Insulation Resistance includes cables to 480V MCB load side, also includes cables and 208V MCB line side.
D.O.
ZONE INTLK
GRD. FLT.
GRD. FLT.
CU
THERMAL MEMORY
4W3W
AL
FRAME SIZE(F)
MM/KSTESTED BY:
www.abm.comABM Electrical Power Solutions 15055, REVISED 5/5/2020
REVIEWED BY:EQPT. INVENTORY NO. P0568/P0097
BREAKER TYPE
TRIP UNIT TYPE
NA
CUBICLE CODE
SN / SO NO.
MOUNTING
TARGETS
20°C
INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE
SIZE
A=
AA
x
A
A
A
A = A
AS
LEFT
TEST
AMPERES
POLE 1
FUNCTION
INSTANTANEOUS
SHORT TIME
LONG TIME
POLE 2
AS
FOUND
TIME BAND
MINIMUM
IPU
GFPU
VOLTAGE DROP @ LONG TIME TEST CURRENT
LTPU
STPU
GROUND FAULT
READING
POLE 3POLE 2POLE 1
20°C
LOAD CONDUCTOR NO.
READING 20°C 20°C
Westinhouse
MAXIMUM
20°C
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
LOW VOLTAGE
POWER CIRCUIT BREAKER TEST
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 2A101 MCC-P1 Pass
HMC3800F
1.25
2,200
2,200
2,200
2,200
2,200
2,200
2,750.002,200 2,750.00
2,750.00 2,750.00
2,750.00
2,750.00
2,750.00
2,200 2,750.00 2,200 2,750.00
READING
107.88 93.17 109.84
NA
CAcceptable
N/A
Acceptable C
N/A
Acceptable C
Acceptable C
Acceptable
TRIP
44.39
TRIP
44.39
TRIP
44.39
TRIP
44.39
TRIP
44.39
TRIP
44.39
DESCRIPTION
ARC CHUTES
AUXILIARY DEVICES
GROUND CONNECTION
DESCRIPTION
CUBICLE AND RACKING DEVICES
CONTACT FINGERS
LOADING AND ARCING CONTACTS
OVERCURRENT DEV. BATTERY
(P1-P2) (P2-P3) (P3-P4)
°C
800 800
4W3W A x
SENSOR TAP 800
DELAY
RATING PLUG(R)
SENSOR TAP
POLE 3
RATING PLUG(R)
B.I.
OffON
CURVE DRAWING
GRD. FLT.
INST.
SHORT
LONG
FUNCTION
SHORT
LONG
PICKUP
CONTROL WIRING
POLE TO FRAME
POLE TO POLE
READING READING
CURRENT
MULTIPLE
AS
FOUND
INST.
GRD. FLT.
LINE TO LOAD
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
POLE RESISTANCE - MICRO-OHMS
AS
FOUND
AS
LEFT
AS
LEFT
HMC
FUSE CAT. NO.
Seltronic
SENSOR TAPS
NA
CATALOG NO.
SETTINGS AS FOUND
A
SETTINGS AS LEFT FUNCTION PICKUP DELAY CURVE DRAWING
COUNTER READING BEG/END
INSULATION
RESISTANCE
25EQUIPMENT TEMPERATURE
MANUFACTURER
Fixed
Fixed
Fixed
Fixed
POLE1 POLE2 POLE3MEGOHMS MEGOHMS MEGOHMS
COMMENTS: Performed secondary injection testing with the Seltronic Test Kit Insulation Resistance performed load side only because line side is connected to ATS-4.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO. HKD3400F
WESTINGHOUSE TYPE HKD 65k
TYPE
CATALOG NO.
CATALOG NO.
Matthew Moore / Keith SpearTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0097 / P0568 / P0555
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 05/30/2020 TEMPERATURE 70 °F HUMIDITY 50 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION 2A101 MCC-P1 Pass
208/120VVOLTAGE
HKD3400F FRAME SIZE/RATING PLUG
WESTINGHOUSE TYPE HKD 65k
208/120V
100ka @240INT. RATING
VOLTAGE
400A/300AFRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
PANEL PH AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS 435 435 445 445 455 455
TIME AT 300% RATED CURRENT IN SECONDS 69.69 69.69 73.56 73.56 71.15 71.15
INSTANT TESTED ON * SETTING TRIP / NO TRIP TRIP TRIP TRIP TRIP TRIP TRIP
ACROSS OPEN POLE
POLE - POLE - GND
2200 2200 2200 2200 2200 2200
2200 2200 2200 2200 2200 2200
400A/300A INT. RATING 100ka @240
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
50-AC-1
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
450 450
68.95 68.95
TRIP TRIP
2200 2200
2200 2200
AS FOUND AS LEFT
475 475
71.56 71.56
TRIP TRIP
2200 2200
2200 2200
AS FOUND AS LEFT
462 462
72.57 72.57
TRIP TRIP
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
BK/CPTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0042/P0022/P0585
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION GA125 ECGE Pass
240 VACVOLTAGE
CAH3150W FRAME SIZE/RATING PLUG
Westinghouse TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
150/150 INT. RATING 22KA @ 240VAC
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
ECGE Main Breaker
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
542 528
27.56 27.56
2200 2200
2200 2200
AS FOUND AS LEFT
799 582
34.93 34.93
2200 2200
2200 2200
AS FOUND AS LEFT
521 503
24.65 24.65
2200 2200
2200 2200
Acceptable
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable C
N/A
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
C
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION GA125 GELA Pass
208VOLTAGE
CAH31505W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
150 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
721 721
32.31 32.31
N/A N/A
AS FOUND AS LEFT
634 634
36.88 36.88
N/A N/A
AS FOUND AS LEFT
653 653
39.13 39.13
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/16/2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION GA125 GEPA Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
469 469
52.13 52.13
N/A N/A
AS FOUND AS LEFT
638 638
54.52 54.52
N/A N/A
AS FOUND AS LEFT
569 569
52.81 52.81
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/16/20 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION GA125 GEPB Pass
208VOLTAGE
CAH32255W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
225 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
250 250
55.36 55.36
N/A N/A
AS FOUND AS LEFT
266 266
58.39 58.39
N/A N/A
AS FOUND AS LEFT
323 323
54.44 54.44
N/A N/A
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Chris Leone/Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 5/16/20 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50
EQUIPMENT ID TEST STATUSSUBSTATION GA125 GEPC Pass
208VOLTAGE
CAH32005W FRAME SIZE/RATING PLUG
CULTER-HAMMER TYPE CAH
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
200 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
431 431
27.84 27.84
N/A N/A
AS FOUND AS LEFT
502 502
34.86 34.86
N/A N/A
AS FOUND AS LEFT
4…