Atch 6.Heinz_May 2020_Final Report.pdf

PDF 2 MB Posted

Attached to
H961--VAPHS Triennial Electrical Inspections Federal contract opportunity
Solicitation number
36C24426Q0055
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

This document is a Customer Field Service Report from ABM Electrical Power Solutions detailing electrical power equipment testing performed in May 2020 at the VA Pittsburgh Healthcare Center (Heinz). The report documents maintenance testing and inspection of electrical equipment in multiple buildings, specifically noting critical findings including a defective B-Phase cable lug with melted insulation in Building #50, 1A-123, and a breaker in Building #50 GA140 MSB Distribution Panels that failed to trip during long time, short time, and instantaneous tests.

The related federal contract opportunity is Solicitation Number 36C24426Q0055 for "H961--VAPHS Triennial Electrical Inspections" issued by the Department of Veterans Affairs. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Business, seeking FY26 Triennial Breaker Inspections. The solicitation has a NAICS code of 811210 with a size standard of $34.0M, and critical dates include a question submission deadline of January 5, 2026, and a quote submission deadline of January 8, 2026. The point of contact is Allan Tabliago, and all communications must be via email.

View the file

Other files for this federal contract opportunity

Other files attached to H961--VAPHS Triennial Electrical Inspections, newest first.
File Type Posted
Atch 7.Heinz_June and July 2020_Final Report.pdf PDF
Atch 4.UD August 2020-July 2021_Final Report.pdf PDF
36C24426Q0055 0002_1.docx DOCX document
Atch 5.Heinz_April 2020_Final Report.pdf PDF
Atch 3.Equipment List - Breaker Testing List UD- April 2015.xlsx XLSX spreadsheet
Atch 2.UD Elect and Arc Flash Study.pdf PDF
Atch 1.HZ Elect and Arc Flash study 2023 reduced.pdf PDF
36C24426Q0055 0001_1.docx DOCX document
VAAR 852.219-75 VA Notice of Limitations on Subcontracting.pdf PDF
36C24426Q0055 Triennial Inspectiona.pdf PDF
WD 2015-4235 R32 20251203.pdf PDF
36C24426Q0055_1.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER

ADDRESS

CUSTOMER

FIELD SERVICE REPORT

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE

Description:

In May, 2020 ABM Electrical Power Solutions Field Personnel were at Department of Veterans Affairs, VA Pittsburgh Healthcare, (Heinz) located in Pittsburgh, PA to perform testing of electrical power equipment.

Engineering Evaluation:

Testing was performed in accordance with the International Electrical Testing Association's Maintenance Testing Specifications and project specifications.

Scope of Work:

Perform Maintenance testing and cleaning of electrical power equipment.

Test Results / Comments:

(Heinz) Building #50, 1A-123, ECIE; B-Phase, Line side Cable lug is defective. There are signs of the lug heating up and the lug is discolored, also the cable insulation is melted.

(Heinz) Building # 50, GA140, MSB, Distribution Panels: GAPA/1APA; Breaker failed due to no trip during long time, short time and instantaneous tests.

(Heinz) Building # 52, BA107, MSG; Long and Short time function will not trip per test set.

All other test results are acceptable per NETA - MTS Standards. All equipment was left in Satisfactory Operational Condition.

This report certifies that the above equipment has been tested in compliance with recognized standards or for safe use in a specific manner, or in accordance with

Federal, State or Municipal regulations. The report is accurate and true to the best of our knowledge and belief. All equipment used in making physical determinations is accurate and bears recent and direct traceability to the National Institute of Standards and Technology. (NIST).

1/24/2022

By:

Josh Schoedel www.abm.comABM Electrical Power Solutions REVISED 1/24/2022

ABM Electrical Power Solutions 317 Commerce Park Drive Cranberry Township, PA 16066

Project Manager

Equipment Tested Job #86301680 www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

1PAGE

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

115910- MCB - 3 in 1 REV.1 (7)

(HEINZ) BLDG #50 1A-123 1ELA

215910- MCB - 3 in 1 REV.1 (8)

(HEINZ) BLDG #50 1A-123 1EPA

315910- MCB - 3 in 1 REV.1 (8)

(HEINZ) BLDG #50 1A-123 1EPB

415910- MCB - 3 in 1 REV.1 (8)

(HEINZ) BLDG #50 1A-123 1EPC

515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 1A-123 EC1E

615910- MCB - 3 in 1 REV.1 (7)

(HEINZ) BLDG #50 1A-133 1APA

715910- MCB - 3 in 1 REV.1 (6)

(HEINZ) BLDG #50 1A-133 1APB

815910- MCB - 3 in 1 REV.1 (9)

(HEINZ) BLDG #50 1A-146 1WLA

915910- MCB - 3 in 1 REV.1 (10)

(HEINZ) BLDG #50 1A-146 1WPA

1015910- MCB - 3 in 1 REV.1 (10)

(HEINZ) BLDG #50 1A-146 1WPB

1115910- MCB - 3 in 1 REV.1 (10)

(HEINZ) BLDG #50 1A-146 1WPC

1215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 1A-146 EC1W

1356710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #50 2A101 50-T-AC1

1415065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 2A101 MCC-P1

1615910- MCB - 3 in 1 REV.1 (7)

(HEINZ) BLDG #50 2A101 MCC-P1

1715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 GA125 ECGE

1815910- MCB - 3 in 1 REV.1 (6)

(HEINZ) BLDG #50 GA125 GELA

1915910- MCB - 3 in 1 REV.1 (3)

(HEINZ) BLDG #50 GA125 GEPA

2015910- MCB - 3 in 1 REV.1 (4)

(HEINZ) BLDG #50 GA125 GEPB

2115910- MCB - 3 in 1 REV.1 (5)

(HEINZ) BLDG #50 GA125 GEPC

2215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 GA135 ELGA

2315910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #50 GA135 GALA

2415910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #50 GA135 GAPA

2515910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #50 GA135 GAPC

2615610 - LV DISCONNECT SWITCH

(HEINZ) BLDG #50 GA135 SMOKING SHELTER

2754100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #50 GA140 ATS-1

2854100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #50 GA140 ATS-2

2PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

2954100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #50 GA140 ATS-3

3015910- MCB - 3 in 1 REV.1 (HEINZ) BLDG #50 GA140 ATS-3 Emergency Disconnect

3154101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass

(HEINZ) BLDG #50 GA140 ATS-4

3315065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA140 ATS-4 Emergency Disconnect

3556710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #50 GA140 B50-TX1

3756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #50 GA140 B50-TX2

3856710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #50 GA140 B50-TX3

3915065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)

(HEINZ) BLDG #50 GA140 ECGS

4015910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 GA140 ECGS

4115065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN) - Pass

(HEINZ) BLDG #50 GA140 ELCG

4215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-1) - Pass

(HEINZ) BLDG #50 GA140 ELCG

4315910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 GA140 ELCG

4415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 GA140 ELGS

4515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 GA140 GAPB

4615065 - LOW VOLT. PWR. CKT. BKR. TEST (SANIPAC) - Pass

(HEINZ) BLDG #50 GA140 MSB

4715065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. 1WPA/1WPB/1WPC)

(HEINZ) BLDG #50 GA140 MSB

4815065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE POSITION 4)

(HEINZ) BLDG #50 GA140 MSB

4915065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GEPA/GEPB/GEPC)

(HEINZ) BLDG #50 GA140 MSB

5015065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GWPA/GWPB/GWPC)

(HEINZ) BLDG #50 GA140 MSB

5115065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL K)

(HEINZ) BLDG #50 GA140 MSB

5215065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GWLA/1WLA) - Pass

(HEINZ) BLDG #50 GA140 MSB

5315065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS #3)

(HEINZ) BLDG #50 GA140 MSB

5415065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. 1EPA/1EPB/1EPC)

(HEINZ) BLDG #50 GA140 MSB

5515065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)

(HEINZ) BLDG #50 GA140 MSB

5615065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL. GAPB) - Pass

(HEINZ) BLDG #50 GA140 MSB

3PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

5715065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE POSITION 3)

(HEINZ) BLDG #50 GA140 MSB

5815065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE POSITION 15) - Pass

(HEINZ) BLDG #50 GA140 MSB

5915065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS #4)

(HEINZ) BLDG #50 GA140 MSB

6015065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS #1)

(HEINZ) BLDG #50 GA140 MSB

6115065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GAPA/1APA)

(HEINZ) BLDG #50 GA140 MSB

6215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS #2)

(HEINZ) BLDG #50 GA140 MSB

6315065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GELA/1ELA)

(HEINZ) BLDG #50 GA140 MSB

6415065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GALA/1ALA)

(HEINZ) BLDG #50 GA140 MSB

6515065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GAPC/1APB) - Pass

(HEINZ) BLDG #50 GA140 MSB

6615065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL. GALB) - Pass

(HEINZ) BLDG #50 GA140 MSB

6715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #50 GA153 ECGW

6815910- MCB - 3 in 1 REV.1 (6)

(HEINZ) BLDG #50 GA153 GWLA

6915910- MCB - 3 in 1 REV.1 (3)

(HEINZ) BLDG #50 GA153 GWPA

7015910- MCB - 3 in 1 REV.1 (4)

(HEINZ) BLDG #50 GA153 GWPB

7115910- MCB - 3 in 1 REV.1 (5)

(HEINZ) BLDG #50 GA153 GWPC

7215610 - LV DISCONNECT SWITCH

(HEINZ) BLDG #50 GA169 ELEV-PS1

7315610 - LV DISCONNECT SWITCH

(HEINZ) BLDG #50 GA169 ELEV-PS2

7415065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #52 1A104 52-CCU-3 (CHILLER NO.3)

7531300 - MEDIUM VOLTGE VACUUM MOTOR START

(HEINZ) BLDG #52 1A104 52-CT-1

7731300 - MEDIUM VOLTGE VACUUM MOTOR START

(HEINZ) BLDG #52 1A104 52-CT-2

7956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #52 1A104 B52-T-C

8056700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BLDG #52 1A104 B52-T-CHILL3

8115910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #52 1A104 C

8215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #52 1A104 CA

8329000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #52 1A104 SW-B52CHILL

4PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

8429000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #52 1A104 SW-B52CHILL3

8515065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-1) - Fail

(HEINZ) BLDG #52 BA107 MSG

8715065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL CA) - Pass

(HEINZ) BLDG #52 BA107 MSG

8915065 - LOW VOLT. PWR. CKT. BKR. TEST (TRANSFER SWITCH) - Pass

(HEINZ) BLDG #52 BA107 MSG

9115065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL GA) - Pass - Pass

(HEINZ) BLDG #52 BA107 MSG

9315065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-2) - Pass

(HEINZ) BLDG #52 BA107 MSG

9515065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)

(HEINZ) BLDG #52 BA107 MSG

9716100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - 5KV CHILLER (CKT #9)

9841200 - DIGITRIP OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - 5KV CHILLER (CKT #9)

9916100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - BLDG 50/51 (CKT #10)

10041200 - DIGITRIP OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - BLDG 50/51 (CKT #10)

10116100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - BLDG 70/71/IT (CKT #11)

10241200 - DIGITRIP OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER A - BLDG 70/71/IT (CKT #11)

10316100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - 5KV CHILLER (CKT #13)

10441200 - DIGITRIP OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - 5KV CHILLER (CKT #13)

10516100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - BLDG 50/51 (CKT #14)

10641200 - DIGITRIP OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - BLDG 50/51 (CKT #14)

10716100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - BLDG 70/71/IT (CKT #15)

10841200 - DIGITRIP OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING FEEDER B - BLDG 70/71/IT (CKT #15)

10915065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LC)

(HEINZ) BLDG #69 1B116 MSB

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 1ELA Pass

208VOLTAGE

CAH31505W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

150 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

641 641

37.21 37.21

N/A N/A

AS FOUND AS LEFT

480 480

29.34 29.34

N/A N/A

AS FOUND AS LEFT

564 564

27.76 27.76

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

COMMENTS: Could not perform Insulation Resistance test due to connected devices.

DEFICIENCIES:

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 1EPA Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

370 370

48.50 48.50

N/A N/A

AS FOUND AS LEFT

330 331

45.40 45.40

N/A N/A

AS FOUND AS LEFT

356 356

42.21 42.21

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 1EPB Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

638 638

45.51 45.51

N/A N/A

AS FOUND AS LEFT

543 543

46.87 46.87

N/A N/A

AS FOUND AS LEFT

570 570

44.11 44.11

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 1EPC Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

472 472

58.07 58.07

N/A N/A

AS FOUND AS LEFT

353 353

45.14 45.14

N/A N/A

AS FOUND AS LEFT

375 375

41.02 41.02

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

BK/CPTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0042/P0022/P0585

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-123 EC1E Needs Attention

240 VACVOLTAGE

CAH3150W FRAME SIZE/RATING PLUG

Westinghouse TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

150/150 INT. RATING 22KA @ 240VAC

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

EC1E Main Breaker

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

521 511

36.63 36.63

2200 2200

2200 2200

AS FOUND AS LEFT

577 534

37.70 37.70

2200 2200

2200 2200

AS FOUND AS LEFT

519 501

31.94 31.94

2200 2200

2200 2200

Acceptable

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable C

N/A

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

C

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

COMMENTS:

DEFICIENCIES: Found B-Phase, Line side Cable lug is defective. There are signs of the lug heating up and the lug is discolored, also the Cable insulation is melted.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/16/20 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-133 1APA Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

371 371

43.95 43.95

N/A N/A

AS FOUND AS LEFT

324 324

37.18 37.18

N/A N/A

AS FOUND AS LEFT

374 374

35.17 35.17

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-133 1APB Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

441 441

41.86 41.86

N/A N/A

AS FOUND AS LEFT

400 400

45.58 45.58

N/A N/A

AS FOUND AS LEFT

523 523

42.35 42.35

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 1WLA Pass

208VOLTAGE

CAH31505W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

150 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

553 553

24.37 24.37

N/A N/A

AS FOUND AS LEFT

557 557

22.59 22.59

N/A N/A

AS FOUND AS LEFT

543 543

20.46 20.46

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 1WPA Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

380 380

29.03 29.03

N/A N/A

AS FOUND AS LEFT

376 376

32.27 32.27

N/A N/A

AS FOUND AS LEFT

370 370

29.87 29.87

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 1WPB Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

366 366

43.97 43.97

N/A N/A

AS FOUND AS LEFT

343 343

40.60 40.60

N/A N/A

AS FOUND AS LEFT

418 418

38.06 38.06

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 1WPC Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

378 378

39.71 39.71

N/A N/A

AS FOUND AS LEFT

373 373

33.12 33.12

N/A N/A

AS FOUND AS LEFT

403 403

34.15 34.15

N/A N/A

Acceptable

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

BK/CPTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0042/P0022/P0585

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 1A-146 EC1W Pass

240 VACVOLTAGE

CAH3150W FRAME SIZE/RATING PLUG

Westinghouse TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

150/150 INT. RATING 22KA @ 240VAC

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

EC1W Main Breaker

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

573 548

24.69 24.69

2200 2200

2200 2200

AS FOUND AS LEFT

511 503

23.59 23.59

2200 2200

2200 2200

AS FOUND AS LEFT

540 529

24.48 24.48

2200 2200

2200 2200

Acceptable

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable C

N/A

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

C

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

EQPT. LOCATION

ADDRESS

CUSTOMER

TRANSFORMER (<500KVA) TEST

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 2A101 50-T-AC1 Pass

BK/CP/KS/MMTESTED BY:

www.abm.comABM Electrical Power Solutions 56710, REVISED 8/5/2019

REVIEWED BY:EQPT. INVENTORY NO. P0090

VISUAL AND MECHANICAL INSPECTION

INSPECT PHYSICAL AND MECHANICAL CONDITION

VERIFY FANS OPERATE (IF APPLICABLE)

INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING

INSPECTION REPORT

FAIL

FAIL

FAIL

PASS

PASS

PASS

INSPECTION REMARKS

NO FANS

1.82502

1,000

1.33231

1,000

1.82502

MINUTES

PRIMARY TO

GROUND

SECONDARY TO

GROUND

PRIMARY TO

SECONDARY

TEST V

0.50

1.00

10.00

P. I.

PHASE B PHASE CCALCTAP

762000

1103000

2013000

974000

1300000

1732000

762000

1103000

2013000

TRANSFORMER TURN RATIO TEST (OPTIONAL)

PASS FAILVERIFY SHIPPING BRACKETS REMOVED

PASS FAILVERIFY THAT RESILIENT MOUNTS ARE FREE

PASS FAILVERIFY THE UNIT IS CLEAN

PASS FAILVERIFY BOLTED ELECTRICAL CONNECTIONS

INSULATION RESISTANCE IN MEGOHMS

PHASE A

1-5

/112.5 NA

5.1

NAMEPLATE DATA

NoneSERIAL NO.

504 492 480 468

1-2 1-3 1-4 1-5 1-6

468 VOLTS

Westinghouse YR MFR NA

KVA

IMPEDANCE /AA

WINDING MATERIAL °CCOPPER

1-5

CLASSTYPE

B.I.L. RATINGTEMPERATURE RISE

PRIMARY V

TAP POSITION

TAP SETTING

TAP VOLTAGES

DT-3

MANUFACTURER

SECONDARY V 208 WYE

120/

DELTA

1-8

432444

1-7

1-5AL

ELECTRICAL TESTS

1,000

WORKING TAP AFP.I. = 10 min/1 min

COMMENTS: Insulation Resistance includes cables to 480V MCB load side, also includes cables and 208V MCB line side.

D.O.

ZONE INTLK

GRD. FLT.

GRD. FLT.

CU

THERMAL MEMORY

4W3W

AL

FRAME SIZE(F)

MM/KSTESTED BY:

www.abm.comABM Electrical Power Solutions 15055, REVISED 5/5/2020

REVIEWED BY:EQPT. INVENTORY NO. P0568/P0097

BREAKER TYPE

TRIP UNIT TYPE

NA

CUBICLE CODE

SN / SO NO.

MOUNTING

TARGETS

20°C

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

SIZE

A=

AA

x

A

A

A

A = A

AS

LEFT

TEST

AMPERES

POLE 1

FUNCTION

INSTANTANEOUS

SHORT TIME

LONG TIME

POLE 2

AS

FOUND

TIME BAND

MINIMUM

IPU

GFPU

VOLTAGE DROP @ LONG TIME TEST CURRENT

LTPU

STPU

GROUND FAULT

READING

POLE 3POLE 2POLE 1

20°C

LOAD CONDUCTOR NO.

READING 20°C 20°C

Westinhouse

MAXIMUM

20°C

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

LOW VOLTAGE

POWER CIRCUIT BREAKER TEST

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 2A101 MCC-P1 Pass

HMC3800F

1.25

2,200

2,200

2,200

2,200

2,200

2,200

2,750.002,200 2,750.00

2,750.00 2,750.00

2,750.00

2,750.00

2,750.00

2,200 2,750.00 2,200 2,750.00

READING

107.88 93.17 109.84

NA

CAcceptable

N/A

Acceptable C

N/A

Acceptable C

Acceptable C

Acceptable

TRIP

44.39

TRIP

44.39

TRIP

44.39

TRIP

44.39

TRIP

44.39

TRIP

44.39

DESCRIPTION

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

DESCRIPTION

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY

(P1-P2) (P2-P3) (P3-P4)

°C

800 800

4W3W A x

SENSOR TAP 800

DELAY

RATING PLUG(R)

SENSOR TAP

POLE 3

RATING PLUG(R)

B.I.

OffON

CURVE DRAWING

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

PICKUP

CONTROL WIRING

POLE TO FRAME

POLE TO POLE

READING READING

CURRENT

MULTIPLE

AS

FOUND

INST.

GRD. FLT.

LINE TO LOAD

TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

POLE RESISTANCE - MICRO-OHMS

AS

FOUND

AS

LEFT

AS

LEFT

HMC

FUSE CAT. NO.

Seltronic

SENSOR TAPS

NA

CATALOG NO.

SETTINGS AS FOUND

A

SETTINGS AS LEFT FUNCTION PICKUP DELAY CURVE DRAWING

COUNTER READING BEG/END

INSULATION

RESISTANCE

25EQUIPMENT TEMPERATURE

MANUFACTURER

Fixed

Fixed

Fixed

Fixed

POLE1 POLE2 POLE3MEGOHMS MEGOHMS MEGOHMS

COMMENTS: Performed secondary injection testing with the Seltronic Test Kit Insulation Resistance performed load side only because line side is connected to ATS-4.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO. HKD3400F

WESTINGHOUSE TYPE HKD 65k

TYPE

CATALOG NO.

CATALOG NO.

Matthew Moore / Keith SpearTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0097 / P0568 / P0555

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 05/30/2020 TEMPERATURE 70 °F HUMIDITY 50 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION 2A101 MCC-P1 Pass

208/120VVOLTAGE

HKD3400F FRAME SIZE/RATING PLUG

WESTINGHOUSE TYPE HKD 65k

208/120V

100ka @240INT. RATING

VOLTAGE

400A/300AFRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

PANEL PH AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS 435 435 445 445 455 455

TIME AT 300% RATED CURRENT IN SECONDS 69.69 69.69 73.56 73.56 71.15 71.15

INSTANT TESTED ON * SETTING TRIP / NO TRIP TRIP TRIP TRIP TRIP TRIP TRIP

ACROSS OPEN POLE

POLE - POLE - GND

2200 2200 2200 2200 2200 2200

2200 2200 2200 2200 2200 2200

400A/300A INT. RATING 100ka @240

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

50-AC-1

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

450 450

68.95 68.95

TRIP TRIP

2200 2200

2200 2200

AS FOUND AS LEFT

475 475

71.56 71.56

TRIP TRIP

2200 2200

2200 2200

AS FOUND AS LEFT

462 462

72.57 72.57

TRIP TRIP

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

BK/CPTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0042/P0022/P0585

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/30/20 TEMPERATURE 73 °F HUMIDITY 50 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION GA125 ECGE Pass

240 VACVOLTAGE

CAH3150W FRAME SIZE/RATING PLUG

Westinghouse TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

150/150 INT. RATING 22KA @ 240VAC

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

ECGE Main Breaker

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

542 528

27.56 27.56

2200 2200

2200 2200

AS FOUND AS LEFT

799 582

34.93 34.93

2200 2200

2200 2200

AS FOUND AS LEFT

521 503

24.65 24.65

2200 2200

2200 2200

Acceptable

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable C

N/A

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

C

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5-16-2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION GA125 GELA Pass

208VOLTAGE

CAH31505W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

150 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

721 721

32.31 32.31

N/A N/A

AS FOUND AS LEFT

634 634

36.88 36.88

N/A N/A

AS FOUND AS LEFT

653 653

39.13 39.13

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/16/2020 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION GA125 GEPA Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

469 469

52.13 52.13

N/A N/A

AS FOUND AS LEFT

638 638

54.52 54.52

N/A N/A

AS FOUND AS LEFT

569 569

52.81 52.81

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/16/20 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION GA125 GEPB Pass

208VOLTAGE

CAH32255W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

225 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

250 250

55.36 55.36

N/A N/A

AS FOUND AS LEFT

266 266

58.39 58.39

N/A N/A

AS FOUND AS LEFT

323 323

54.44 54.44

N/A N/A

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Chris Leone/Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 5/16/20 TEMPERATURE 55 °F HUMIDITY 85 % (HEINZ) BLDG #50

EQUIPMENT ID TEST STATUSSUBSTATION GA125 GEPC Pass

208VOLTAGE

CAH32005W FRAME SIZE/RATING PLUG

CULTER-HAMMER TYPE CAH

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

200 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

431 431

27.84 27.84

N/A N/A

AS FOUND AS LEFT

502 502

34.86 34.86

N/A N/A

AS FOUND AS LEFT

4…