Atch 4.UD August 2020-July 2021_Final Report.pdf

PDF 6 MB Posted

Attached to
H961--VAPHS Triennial Electrical Inspections Federal contract opportunity
Solicitation number
36C24426Q0055
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

This document is a Customer Field Service Report from ABM Electrical Power Solutions detailing electrical power equipment testing performed at the VA Pittsburgh Healthcare Center from August 2020 to July 31, 2021. The report documents comprehensive electrical equipment inspections across multiple buildings, identifying numerous equipment issues including damaged oil port gate valves, breakers failing to trip correctly, transformer and panel anomalies, and contact resistance problems.

The related federal contract opportunity is Solicitation Number 36C24426Q0055 for "H961--VAPHS Triennial Electrical Inspections", which is a 100% set-aside for Service-Disabled Veteran-Owned Small Business. The solicitation seeks FY26 Triennial Breaker Inspections for the Department of Veterans Affairs, with a NAICS code of 811210. Key dates include a question submission deadline of January 5, 2026, and a quote submission deadline of January 8, 2026. The point of contact is Allan Tabliago, and all communications must be via email to allan.tabliago@va.gov, with no phone calls accepted.

View the file

Other files for this federal contract opportunity

Other files attached to H961--VAPHS Triennial Electrical Inspections, newest first.
File Type Posted
Atch 6.Heinz_May 2020_Final Report.pdf PDF
Atch 5.Heinz_April 2020_Final Report.pdf PDF
Atch 7.Heinz_June and July 2020_Final Report.pdf PDF
36C24426Q0055 0002_1.docx DOCX document
Atch 3.Equipment List - Breaker Testing List UD- April 2015.xlsx XLSX spreadsheet
Atch 2.UD Elect and Arc Flash Study.pdf PDF
Atch 1.HZ Elect and Arc Flash study 2023 reduced.pdf PDF
36C24426Q0055 0001_1.docx DOCX document
VAAR 852.219-75 VA Notice of Limitations on Subcontracting.pdf PDF
36C24426Q0055 Triennial Inspectiona.pdf PDF
WD 2015-4235 R32 20251203.pdf PDF
36C24426Q0055_1.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER

ADDRESS

CUSTOMER

FIELD SERVICE REPORT

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE

Description:

From August 2020 to July 31, 2021, ABM Electrical Power Solutions Field Personnel were at VA Pittsburgh Healthcare Center, located in Pittsburgh, PA, on behalf of Department of Veterans Affairs, to perform testing of electrical power equipment.

Engineering Evaluation:

Testing was performed in accordance with the International Electrical Testing Association's Maintenance Testing Specifications and project specifications. Fluid Analysis was performed in accordance with IEEE Specifications.

Scope of Work:

Perform Maintenance testing and cleaning of electrical power equipment.

Test Results / Comments:

Heinz Building #32, Outside, B32IT Transformer; Oil Port Gate Valve is damaged and needs replaced.

University Drive, 3C-110, SR6; Main Breaker failed to Trip on A-Phase.

University Drive, 3C-110, SR-6; Breaker #1 will not Trip on Long Time Function.

University Drive, 3C-110, SR6A; Breaker #3 and Breaker #4 will not Trip on Long Time Function.

University Drive, Fed from ATS BT-EQ, MS2; Does not Trip. Trip unit needs to be replaced.

University Drive, Fed from ATS BT-EQ, MS2; UPS B 3W123; Breaker Trips Instant, out of tolerance for Long Time Trip.

University Drive, Various, PNL NEDPEQ; Not operational on Instant.

University Drive, Various, TR-BTGLEQ Transformer; 150 VAC measured on the Neutral when isolating to test. Could not test.

University Drive, Building #1, 1st Floor, C1AY; Breaker would not Trip on C-Phase Long Time.

University Drive, Building #1, BN101, MDPY; Lugs are too big for Conductor.

University Drive, Building #1, MDP-1, RM AW-121B; GWC Main, C-Phase Contact Resistance is out of tolerance.

University Drive, Building #1, MDP-X, Across from 3N-116; Trip time out of tolerance.

University Drive, Building #1, Room 2E104, PNL 2-LCA; Excessive corrosion, unable to test.

University Drive, Building #10, 7W-139C, CRDS; Breaker W4CP; Trip coil will not reset.

University Drive, Building #10, 7W-139C, EQDS, Breaker MCCMCEM; Trip coil will not reset. Breaker Elevator S1, out of tolerance.

All other test results are acceptable per NETA - MTS Standards. All equipment was left in Satisfactory Operational Condition.

This report certifies that the above equipment has been tested in compliance with recognized standards or for safe use in a specific manner, or in accordance with

Federal, State or Municipal regulations. The report is accurate and true to the best of our knowledge and belief. All equipment used in making physical determinations is accurate and bears recent and direct traceability to the National Institute of Standards and Technology. (NIST).

7/7/2022

By:

Josh Schoedel www.abm.comABM Electrical Power Solutions REVISED 7/7/2022

ABM Electrical Power Solutions 317 Commerce Park Drive Cranberry Township, PA 16066

Project Manager

Equipment Tested Job #86301680 www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

1PAGE

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

115065 - LOW VOLT. PWR. CKT. BKR. TEST (CAP BANK 51A1)

(HEINZ) BLDG #32 BA117 A1

215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 BA117 A1

315910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 BA117 B1

415610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #32 BA117 B32-SW-T3

554100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #32 BA117 MTS-A

654100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #32 BA117 MTS-B

756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #32 BA117 T-B32--T3

815910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 BA118A MAINT BY PASS (PNL A)

915910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 BA118A MAINT BY PASS (PNL B)

1029000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #32 BUILDING 32 MAIN DISCONNECT

1154560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #32 BUILDING 32 SELECTOR SWITCH

1315065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-B) - Pass

(HEINZ) BLDG #32 GENERATOR ROOM EMDP

1415065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN) - Pass

(HEINZ) BLDG #32 GENERATOR ROOM EMDP

1515065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-A)

(HEINZ) BLDG #32 GENERATOR ROOM EMDP

1615910- MCB - 3 in 1 REV.1 (3) - Pass (2)

(HEINZ) BLDG #32 GND FLOOR CORRIDOR NE2A

1754100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM ATS-A

1854100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM ATS-B

1915065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-B)

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM MDP

2015065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE)

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM MDP

2115065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM MDP

2215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-A)

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM MDP

2315910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD A

2415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD A

2515065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD A MAIN

2615065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD B

2715910- MCB - 3 in 1 REV.1 (3)

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD B

2815910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD B

2PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

2956700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BLDG #32 OUTSIDE B32IT XFMR

3015910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 SERVER ROOM PDU-A

3115910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 SERVER ROOM PDU-A

3315910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 SERVER ROOM PDU-B

3415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 SERVER ROOM PDU-B

3515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 SERVER ROOM PDU-C

3615910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 SERVER ROOM PDU-C

3715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 SERVER ROOM PDU-D

3815910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 SERVER ROOM PDU-D

3915910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 SERVER ROOM PDU-E

4015910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 SERVER ROOM PDU-E

4115910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 SERVER ROOM PNL RD

4215910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 SERVER ROOM UPS-DP-A

4315910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 SERVER ROOM UPS-DP-A

4415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 SERVER ROOM UPS-DP-B

4515910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 SERVER ROOM UPS-DP-B

4615910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 UPS DP-8

4715910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #32 UPS DP-8

4856700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BLDG #49 OUTSIDE B49 XFMR

49TJH2B DGA - 07J722043-Tran

(HEINZ) BLDG #49 OUTSIDE B49 XFMR

51TJH2B Fluid - 07J722043-Tran

(HEINZ) BLDG #49 OUTSIDE B49 XFMR

5215065 - LOW VOLT. PWR. CKT. BKR. TEST (2)

(HEINZ) BLDG #50 GA139 EDP-1 ATS 5A

5315065 - LOW VOLT. PWR. CKT. BKR. TEST (2)

(HEINZ) BLDG #50 GA139 EDP-1 ATS 5B

5415065 - LOW VOLT. PWR. CKT. BKR. TEST (2)

(HEINZ) BLDG #50 GA139 EDP-1 ATS-4

5515065 - LOW VOLT. PWR. CKT. BKR. TEST (2)

(HEINZ) BLDG #50 GA139 EDP-1 ATS-4A

3PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

5615065 - LOW VOLT. PWR. CKT. BKR. TEST (2)

(HEINZ) BLDG #50 GA139 EDP-1 ATS-6A

5715065 - LOW VOLT. PWR. CKT. BKR. TEST (2)

(HEINZ) BLDG #50 GA139 EDP-1 ATS-6B

5815065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 EPD BLDG 51 LIFE SAFETY

5915065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 EPD-1 GENERATOR LOAD BANK

6015065 - LOW VOLT. PWR. CKT. BKR. TEST (3)

(HEINZ) BLDG #50 GA139 EPD-1 SPARE

6115065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 GENERATOR MAIN EPD

6215065 - LOW VOLT. PWR. CKT. BKR. TEST (2)

(HEINZ) BLDG #50 GA139 GENERATOR MAIN EPD-1

6315065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 50 TX-1 ELEVATOR

6415065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 50 TX-2 LS CRIT

6515065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 ATS-7A

6615065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 CRITICAL

6715065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 EK6 AND EK7

6815065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 ELEVATORS

6915065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 EQUIPMENT

7029000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #50 GA140 SW-B50 MAIN DISC

7154560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #50 GA140 SW-B50 SELECTOR SWITCH

7356700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BLDG #50 GA140 T- B50-T1

74TJH2B DGA - PBL2577-0101-Tran

(HEINZ) BLDG #50 GA140 T- B50-T1

76TJH2B Fluid - PBL2577-0101-Tran

(HEINZ) BLDG #50 GA140 T- B50-T1

7815910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 1A120 1ALB

7915910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 1A120 1ALC

8015065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-GA1/MCC-1A1)

(HEINZ) BLDG #51 1A122 MCC-1A1

8115065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL. GALF)

(HEINZ) BLDG #51 1A127 51A2-MSG

8215065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GALA/1ALA)

(HEINZ) BLDG #51 1A127 51A2-MSG

8315065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GALB/1ALB)

(HEINZ) BLDG #51 1A127 51A2-MSG

4PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

8415065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)

(HEINZ) BLDG #51 1A127 51A2-MSG

8515065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE)

(HEINZ) BLDG #51 1A127 51A2-MSG

8615065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS 2ALB/3ALB)

(HEINZ) BLDG #51 1A127 51A2-MSG

8715065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-1A)

(HEINZ) BLDG #51 1A127 51A2-MSG

8815065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL 1ALE)

(HEINZ) BLDG #51 1A127 51A2-MSG

8915065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. 2ALA/3ALA)

(HEINZ) BLDG #51 1A127 51A2-MSG

9015065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL 1ALC/1ALD)

(HEINZ) BLDG #51 1A127 51A2-MSG

9115065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL GALC/GALD)

(HEINZ) BLDG #51 1A127 51A2-MSG

9215065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. 2ALC/3ALC)

(HEINZ) BLDG #51 1A127 51A2-MSG

9354100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #51 1A127 ATS-1A

9454100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #51 1A127 ATS-2A

9554101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass

(HEINZ) BLDG #51 1A127 ATS-4A

9754101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass

(HEINZ) BLDG #51 1A127 ATS-5A

9956700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BLDG #51 1A127 B51-T-51A2

100TJH2B DGA - PBL2578-0101-Tran

(HEINZ) BLDG #51 1A127 B51-T-51A2

102TJH2B Fluid - PBL2578-0101-Tran

(HEINZ) BLDG #51 1A127 B51-T-51A2

10456710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #51 1A127 B51-T-ATS-1A

10529000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #51 1A127 SW-B51A1 MAIN DISC

10654560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #51 1A127 SW-B51A1 SELECTOR SWITCH

10829000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #51 1A127 SW-B51A2 MAIN DISC

10954560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #51 1A127 SW-B51A2 SELECTOR SWITCH

11129000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #51 1A127 SW-B51A3 MAIN DISC

11254560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #51 1A127 SW-B51A3 SELECTOR SWITCH

11415610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #51 1A127 SW-B51ATS-1A (PRI)

11515610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #51 1A127 SW-B51ATS-1A (SEC)

5PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

11615910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 1B145 MCC-1B1

11715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 1B150 EC1B

11854100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #51 1B161 ATS 2B

11954100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #51 1B161 ATS-1B

12054101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass

(HEINZ) BLDG #51 1B161 ATS-5B

12254101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass

(HEINZ) BLDG #51 1B161 ATS-6B

12456710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #51 1B161 B51-T-ATS-1B

12515610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #51 1B161 SW-B51ATS-1B (PRI)

12615610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #51 1B161 SW-B51ATS-1B (SEC)

12715610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #51 1B161 SW-B51ATS-2B

12829000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #51 1B161 SW-B51B1 MAIN DISC

12954560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #51 1B161 SW-B51B1 SELECTOR SWITCH

13129000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #51 1B161 SW-B51B2 MAIN DISC

13254560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #51 1B161 SW-B51B2 SELECTOR SWITCH

13415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 2A129 2ALA

13515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 2A129 2ALB

13615910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 2A129 2ALC

13715065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-GA1/MCC-1A1)

(HEINZ) BLDG #51 2A131 MCC-2A1

13815065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-GA1/MCC-1A1)

(HEINZ) BLDG #51 2B168 MCC-2B1

13915910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 3A129 3ALA

14015910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 3A129 3ALB

14115910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 3A129 3ALC

14215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 3A131 MCC-3A1

14315910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 3B170 MCC-3B1

14415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 3B172 EC3B

6PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

14515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 GA113 ECGA

14615910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 GA113 GALA

14715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 GA113 GALB

14815910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 GA113 GALC

14915910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 GA115 MCC-GA1

15015065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-GA1/MCC-1A1)

(HEINZ) BLDG #51 GB135 MCC-GB1

15115910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 GB-137 ECGB

15254100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #51 KITCHEN ATS ATS EK-6

15354100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #51 KITCHEN ATS ATS EK-7

15415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 KITCHEN ATS PANEL EK-6

15515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #51 KITCHEN ATS PANEL EK-7

15615610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #51 KITCHEN ATS SW-EK6

15715610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #51 KITCHEN ATS SW-EK7

15856700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BLDG #51 KITCHEN ATS XFMR EK-6 EK-7

15916100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING MAIN #1

16045000 - OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING MAIN #1

16116100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING MAIN #2

16245000 - OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING MAIN #2

16316100 - VACUUM CIRCUIT BREAKER ORIG

(HEINZ) BLDG #55 METAL CLAD BUILDING TIE

16441200 - DIGITRIP OVERCURRENT RELAY

(HEINZ) BLDG #55 METAL CLAD BUILDING TIE

16529000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) SW-B63-68-T1 MAIN DISC

16654560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) SW-B63-68-T1 SELCTOR SWITCH

16829000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) SW-B69-T1 MAIN DISC

17054560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) SW-B69-T1 SELCTOR SWITCH

17229000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) SW-B70-T1 MAIN DISC

7PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

17354560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) SW-B70-T1 SELECTOR SWITCH

17529000 - LOADBREAK DISCONNECT- USE

(HEINZ) BLDG #71 GA102 SW-B71-T1 MAIN DISC

17654560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BLDG #71 GA102 SW-B71-T1 SELCTOR SWITCH

17856700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BLDG #71 GA102 T1- MAIN

179TJH2B DGA - S2924-01-001-Tran

(HEINZ) BLDG #71 GA102 T1- MAIN

181TJH2B Fluid - S2924-01-001-Tran

(HEINZ) BLDG #71 GA102 T1- MAIN

18229000 - LOADBREAK DISCONNECT- USE

(HEINZ) BOILER ROOM BOILER ROOM MAIN DISCONNECT

18356700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BOILER ROOM BOILER ROOM MAIN TRANSFORMER

184TJH2B DGA - M156433-Tran

(HEINZ) BOILER ROOM BOILER ROOM MAIN TRANSFORMER

186TJH2B Fluid - M156433-Tran

(HEINZ) BOILER ROOM BOILER ROOM MAIN TRANSFORMER

18754560 - MANUAL TRANSFER SWITCH TEST REPORT

(HEINZ) BOILER ROOM BOILER ROOM SELECTOR SWITCH

18915065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)

(UD) 5/15/21 TESTING 208V SWGR PANEL NBNA

19015910- MCB - 3 in 1 REV.1

(UD) 5/15/21 TESTING 3C-110 SR6

19115910- MCB - 3 in 1 REV.1 -(2)

(UD) 5/15/21 TESTING 3C-110 SR-6

19215910- MCB - 3 in 1 REV.1 -(3)-

(UD) 5/15/21 TESTING 3C-110 SR-6

19315910- MCB - 3 in 1 REV.1 -(2)- Fail

(UD) 5/15/21 TESTING 3C-110 SR6A

19415910- MCB - 3 in 1 REV.1

(UD) 5/15/21 TESTING FED FROM ATS BT-EQ MS2

19515910- MCB - 3 in 1 REV.1 (2)

(UD) 5/15/21 TESTING FED FROM ATS BT-EQ MS2

19615910- MCB - 3 in 1 REV.1 (3)

(UD) 5/15/21 TESTING FED FROM ATS BT-EQ MS2

19754101 - AUTOMATIC TRANSFER SWITCH TEST REV.1

(UD) 5/15/21 TESTING FED FROM NBNA & 600A SW ATS #2LS

19915910- MCB - 3 in 1 REV.1

(UD) 5/15/21 TESTING VARIOUS PNL BTGDPHEQ

20015910- MCB - 3 in 1 REV.1

(UD) 5/15/21 TESTING VARIOUS PNL NBNA

20115910- MCB - 3 in 1 REV.1

(UD) 5/15/21 TESTING VARIOUS PNL NEDPEQ

20215910- MCB - 3 in 1 REV.1 (2)

(UD) 5/15/21 TESTING VARIOUS PNL NEDPEQ

20356710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(UD) 5/15/21 TESTING VARIOUS TR-BTGLEQ TRANSFORMER

8PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

20415065 - LOW VOLT. PWR. CKT. BKR. TEST

(UD) BLDG #1 1ST FLOOR C1AX

20515910- MCB - 3 in 1 REV - Pass

(UD) BLDG #1 1ST FLOOR C1AX

20615910- MCB - 3 in 1 REV - Pass (2)

(UD) BLDG #1 1ST FLOOR C1AX

20715065 - LOW VOLT. PWR. CKT. BKR. TEST

(UD) BLDG #1 1ST FLOOR C1AY

20815910- MCB - 3 in 1 REV - Pass (2)

(UD) BLDG #1 1ST FLOOR C1AY

20915910- MCB - 3 in 1 REV - Pass (3)

(UD) BLDG #1 1ST FLOOR C1AY

21015910- MCB - 3 in 1 REV - Pass

(UD) BLDG #1 1ST FLOOR C1AY

21115910- MCB - 3 in 1 REV.1

(UD) BLDG #1 4TH FL NW CARD CATH RM BC102

21215910- MCB - 3 in 1 REV - Pass

(UD) BLDG #1 5TH FLOOR INTERSTITIAL

21315910- MCB - 3 in 1 REV - Pass

(UD) BLDG #1 5TH FLOOR INTERSTITIAL

21456700 - TRANSFORMER MAINTENANCE TEST (10)

(UD) BLDG #1 5TH FLOOR INTERSTITIAL

21556700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #1 BEDTOWER (OUTSIDE) ASU / SDU TRANSFORMER

217TJH2B DGA - 0950008133-Tran

(UD) BLDG #1 BEDTOWER (OUTSIDE) ASU / SDU TRANSFORMER

219TJH2B Fluid - 0950008133-Tran

(UD) BLDG #1 BEDTOWER (OUTSIDE) ASU / SDU TRANSFORMER

22056700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #1 BEDTOWER (OUTSIDE) BEDTOWER TRANSFORMER

222TJH2B DGA - Q549962-TWP-Tran

(UD) BLDG #1 BEDTOWER (OUTSIDE) BEDTOWER TRANSFORMER

224TJH2B Fluid - Q549962-TWP-Tran

(UD) BLDG #1 BEDTOWER (OUTSIDE) BEDTOWER TRANSFORMER

22615065 - LOW VOLT. PWR. CKT. BKR. TEST (4TH FL NW CARDIAC CATH)

(UD) BLDG #1 BN101 480V SWITCHGEAR

22715065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL MDPX-1BK)

(UD) BLDG #1 BN101 480V SWITCHGEAR

22815065 - LOW VOLT. PWR. CKT. BKR. TEST (MDPY-23H)

(UD) BLDG #1 BN101 480V SWITCHGEAR

22915910- MCB - 3 in 1 REV.1 (3)

(UD) BLDG #1 BN101 MDPX

23015910- MCB - 3 in 1 REV.1

(UD) BLDG #1 BN101 MDPX

23115910- MCB - 3 in 1 REV.1 (2)

(UD) BLDG #1 BN101 MDPX

23215065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL NBNB) Pass

(UD) BLDG #1 BN101 MDPY

23315065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU 7-11E RF1 & SF1)Pass - Pass

(UD) BLDG #1 BN101 MDPY

9PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

23415065 - LOW VOLT. PWR. CKT. BKR. TEST (UROLOGY 2ND FLOOR 2CAF)

(UD) BLDG #1 BN101 MDPY

23515065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL 4HN1) - Pass

(UD) BLDG #1 BN101 MDPY

23615065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL BACX) - Pass

(UD) BLDG #1 BN101 MDPY

23715065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS NEW ICU-C)

(UD) BLDG #1 BN101 MDPY

23815065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE) - Pass

(UD) BLDG #1 BN101 MDPY

23915065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL 2HCA)

(UD) BLDG #1 BN101 MDPY

24015065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS- 6) - Pass (2)

(UD) BLDG #1 BN101 MDPY

24115065 - LOW VOLT. PWR. CKT. BKR. TEST (SPD) - Pass

(UD) BLDG #1 BN101 MDPY

24315065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU 7-11E RF2 & SF2)Pass - Pass

(UD) BLDG #1 BN101 MDPY

24415065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL C2AF 2ND FLOOR UROLOGY)-Pass

(UD) BLDG #1 BN101 MDPY

24515910- MCB - 3 in 1 REV.1 (6)

(UD) BLDG #1 BN101 PNL NBNB

24656700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #1 BN101 XFMR NBNB

24715910- MCB - 3 in 1 REV.1 (4)

(UD) BLDG #1 CLOSET 5A116B PNL'S 5LN1 & 5LN2 NORMAL POWER

24856700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #1 CLOSET 2A-239 PNL S2AC 25KVA XFMR

24915910- MCB - 3 in 1 REV.1 (5)

(UD) BLDG #1 CLOSET 2A-239 PNL'S C2AF & S2AC

25015065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-1RF)

(UD) BLDG #1 ECM INTERSITITIAL

25115065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-1RF) (2)

(UD) BLDG #1 ECM INTERSITITIAL

25215910- MCB - 3 in 1 REV.1

(UD) BLDG #1 ECM INTERSITITIAL

25356700 - TRANSFORMER MAINTENANCE TEST (10)

(UD) BLDG #1 ECM INTERSITITIAL

25415910- MCB - 3 in 1 REV.1

(UD) BLDG #1 ECM RM 2A110

25515910- MCB - 3 in 1 REV.1

(UD) BLDG #1 ECM RM 3A138

25656700 - TRANSFORMER MAINTENANCE TEST (10)

(UD) BLDG #1 ECM RM 3A138

25715910- MCB - 3 in 1 REV.1

(UD) BLDG #1 ECM RM 3A168

25856700 - TRANSFORMER MAINTENANCE TEST (10)

(UD) BLDG #1 ECM RM 3A168

25915910- MCB - 3 in 1 REV.1

(UD) BLDG #1 ECM RM 3N107

10PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

26015910- MCB - 3 in 1 REV.1

(UD) BLDG #1 ECM RM NEAR RM 2A110

26156700 - TRANSFORMER MAINTENANCE TEST (10)

(UD) BLDG #1 ECM RM NEAR RM 2A110

26215910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-1 RM 1A106

26315910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-1 RM 1A176

26415910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-1 RM 1A206

26515910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-1 RM 1A242

26615910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-1 RM 2A133

26715910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-1 RM AA127

26815910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-1 RM AW-121B

26915910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDPX RM BW224

27015910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-X 4TH FL. PENTHOUSE (SLEEP LAB)

27115910- MCB - 3 in 1 REV.1 (2)

(UD) BLDG #1 MDP-X ACROSS FROM 3N-116

27256700 - TRANSFORMER MAINTENANCE TEST (10)

(UD) BLDG #1 MDP-X ACROSS FROM 3N-116

27315910- MCB - 3 in 1 REV.1 (2)

(UD) BLDG #1 MDP-X RM 3N-214

27456700 - TRANSFORMER MAINTENANCE TEST (10)

(UD) BLDG #1 MDP-X RM 3N-214

27515910- MCB - 3 in 1 REV.1

(UD) BLDG #1 MDP-X RM BW-224

27615910- MCB - 3 in 1 REV.1 (2)

(UD) BLDG #1 MDP-X RM BW-224

27756700 - TRANSFORMER MAINTENANCE TEST (10)

(UD) BLDG #1 MDP-X RM BW-224

278DISCONNECT

(UD) BLDG #1 MDPY DISC MDPY

27915910- MCB - 3 in 1 REV.1 (3)

(UD) BLDG #1 MDPY PNL SPD

28056700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #1 MDPY TRANSFORMER MDPY

28115910- MCB - 3 in 1 REV.1

(UD) BLDG #1 ROOM 2E104 PNL 2-HCA

28215910- MCB - 3 in 1 REV.1 (2)

(UD) BLDG #1 ROOM 2E104 PNL 2-HCA

28315910- MCB - 3 in 1 REV.1

(UD) BLDG #1 ROOM 2E104 PNL 2-LCA

28456700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #1 ROOM 2E104 TRANSFORMER T1

11PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

28515910- MCB - 3 in 1 REV.(1st Floor Check In Elec Closet)

(UD) BLDG #1 PARKING GARAGE B1G106 B1TN TRANSFORMER

28656700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #10 4TH FLOOR ELEC CLOSET 4W144 30KVA XFMR

28756700 - TRANSFORMER MAINTENANCE TEST (2)

(UD) BLDG #10 4TH FLOOR ELEC CLOSET 4W144 XFMR

28815910- MCB - 3 in 1 REV.1 (3)

(UD) BLDG #10 4TH FLOOR ELEC CLOSET PNL W4AR1

28956700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #10 5TH FLOOR ELEC CLOSET 5W144 30KVA XFMR

29056700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #10 5TH FLOOR ELEC CLOSET 5W144B XFMR

29115910- MCB - 3 in 1 REV.1 (2)

(UD) BLDG #10 5TH FLOOR ELEC CLOSET PNL W5AR1

29256700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #10 6TH FLOOR ELEC CLOSET 6W144 30KVA XFMR

29315910- MCB - 3 in 1 REV.1

(UD) BLDG #10 6TH FLOOR ELEC CLOSET PNL W6AR1

29456700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #10 6TH FLOOR ELEC CLOSET W144 XFMR

29556700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #10 7W-139C 112.5 KVA XFMR

29654101 - AUTOMATIC TRANSFER SWITCH TEST REV.1

(UD) BLDG #10 7W-139C ATS 10EM

29854101 - AUTOMATIC TRANSFER SWITCH TEST REV.1

(UD) BLDG #10 7W-139C ATS 8LS

30054101 - AUTOMATIC TRANSFER SWITCH TEST REV.1

(UD) BLDG #10 7W-139C ATS 9EC

30215910- MCB - 3 in 1 REV.1 (5)

(UD) BLDG #10 7W-139C CRDS

30315910- MCB - 3 in 1 REV.1 (5)

(UD) BLDG #10 7W-139C CRDS

30456700 - TRANSFORMER MAINTENANCE TEST

(UD) BLDG #10 7W-139C CRITICAL ATS CRDS XFMR

30515910- MCB - 3 in 1 REV.1 (4)

(UD) BLDG #10 7W-139C EQDS

30615055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1

(UD) BLDG #10 7W-139C Main Swbd

30715055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)

(UD) BLDG #10 7W-139C MAIN SWBD/CRITICAL ATS

30815055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)

(UD) BLDG #10 7W-139C MAIN SWBD/EQUIPMENT ATS

30915055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)

(UD) BLDG #10 7W-139C MAIN SWBD/LIFE SAFETY

31015055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)

(UD) BLDG #10 7W-139C MAIN SWBD/MAIN CHILLER

31115055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)

(UD) BLDG #10 7W-139C MAIN SWBD/SPARE

31215055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)

(UD) BLDG #10 7W-139C MAIN SWBD/W4AP1

12PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

31315055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (3)

(UD) BLDG #10 7W-139C MAIN SWBD/W5AP1

31415055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (2)

(UD) BLDG #10 7W-139C MAIN SWBD/W6AP1

31515055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)

(UD) BLDG #10 7W-139C MAIN SWBD/W7AP1

31615910- MCB - 3 in 1 REV.1 (6)

(UD) BLDG #10 7W-139C RDSC

31715910- MCB - 3 in 1 REV.1 (5)

(UD) BLDG #10 7W-139C XFMR 9WECM

31815910- MCB - 3 in 1 REV.1 (6)

(UD) BLDG #10 7W-139C XFMR NECCB

31956710 - TRANSFORMER DRY ACCEPTANCE (<500KVA)

(UD) BLDG #10 NEXT TO GENERATORS 1ECGA TRANSFORMER

32054100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(UD) BLDG #10 NEXT TO GENERATORS ATS 10-OR

32115800- MCB - 3 tests 1 sheet

(UD) BLDG #10 NEXT TO GENERATORS MAIN SWBD NO1

32215800- MCB - 3 tests 1 sheet (4)

(UD) BLDG #10 NEXT TO GENERATORS MAIN SWBD NO1

32315800- MCB - 3 tests 1 sheet (3)

(UD) BLDG #10 NEXT TO GENERATORS MAIN SWBD NO1

32415800- MCB - 3 tests 1 sheet (2)

(UD) BLDG #10 NEXT TO GENERATORS MAIN SWBD NO1

32515910- MCB - 3 in 1 REV.1

(UD) BLDG #10 NEXT TO GENERATORS PANEL 1ECGA

32615065 - LOW VOLT. PWR. CKT. BKR. TEST MAIN

(UD) BLDG #10 NEXT TO GENERATORS PANEL ECM

32715910- MCB - 3 in 1 REV.1 EC2A/EC31/EC1A

(UD) BLDG #10 NEXT TO GENERATORS PANEL ECM

32815910- MCB - 3 in 1 REV.1 4HEC1/EC2AB/E3CAB

(UD) BLDG #10 NEXT TO GENERATORS PANEL ECM

32916100 - VACUUM CIRCUIT BREAKER ORIG

(UD) BLDG #31 4160V SWITCHGEAR ROOM FEEDER 1I BEDTOWER

33016100 - VACUUM CIRCUIT BREAKER ORIG

(UD) BLDG #31 4160V SWITCHGEAR ROOM FEEDER 2I BEDTOWER

D.O.

ZONE INTLK

GRD. FLT.

GRD. FLT.

CU

THERMAL MEMORY

4W3W

AL

FRAME SIZE(F)

Matthew Moore / Jason RittkoTESTED BY:

www.abm.comABM Electrical Power Solutions 15055, REVISED 12/28/2019

REVIEWED BY:EQPT. INVENTORY NO. 008183 / P0568 / 008829

BREAKER TYPE

TRIP UNIT TYPE

N/A

CUBICLE CODE

SN / SO NO.

MOUNTING

TARGETS

400A

20°C

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

SIZE

A=

AA

x

A

A

A

A = A

AS

LEFT

TEST

AMPERES

POLE 1

FUNCTION

INSTANTANEOUS

SHORT TIME

LONG TIME

POLE 2

AS

FOUND

TIME BAND

MINIMUM

IPU

GFPU

VOLTAGE DROP @ LONG TIME TEST CURRENT

LTPU

STPU

GROUND FAULT

READING

POLE 3POLE 2POLE 1

20°C

LOAD CONDUCTOR NO.

READING 20°C 20°C

WESTINGHOUSE

MAXIMUM

20°C

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

LOW VOLTAGE

POWER CIRCUIT BREAKER TEST

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA117 A1 Pass

KD3400F

2,200

2,200

2,200

2,200

2,200

2,200

2,200.002,200 2,200.00

2,200.00 2,200.00

2,200.00

2,200.00

2,200.00

2,200 2,200.00 2,200 2,200.00

READING

878.00 845.00 925.00

N/A

400A

CAcceptable

Acceptable C/L

Acceptable C

Acceptable NA

Acceptable C

Acceptable NA

Acceptable NA

TRIP

38.27

TRIP

38.27

TRIP

38.27

TRIP

38.27

TRIP

38.27

TRIP

38.27

DESCRIPTION

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

DESCRIPTION

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY

(P1-P2) (P2-P3) (P3-P4)

NT

°C

400 400

4W3W A x

SENSOR TAP 400

DELAY

RATING PLUG(R)

SENSOR TAP

POLE 3

RATING PLUG(R)

B.I.

OffON

CURVE DRAWING

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

PICKUP

CONTROL WIRING

POLE TO FRAME

POLE TO POLE

READING READING

CURRENT

MULTIPLE

AS

FOUND

INST.

GRD. FLT.

LINE TO LOAD

TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

POLE RESISTANCE - MICRO-OHMS

AS

FOUND

AS

LEFT

AS

LEFT

KD 65K

FUSE CAT. NO.

DIGITRIP RMS 310

SENSOR TAPS

A1 MAIN

CATALOG NO.

SETTINGS AS FOUND

A

SETTINGS AS LEFT FUNCTION PICKUP DELAY CURVE DRAWING

COUNTER READING BEG/END

INSULATION

RESISTANCE

20EQUIPMENT TEMPERATURE

MANUFACTURER

100ms

FIXED

100ms

FIXED

POLE1 POLE2 POLE3MEGOHMS MEGOHMS MEGOHMS

COMMENTS: Secondary Injected w/ Seltronic test kit.

DEFICIENCIES:

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Matthew Moore / Jason RittkoTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0568 / 008183 / P0555

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA117 A1 Pass

480/277VVOLTAGE

FDB3125 FRAME SIZE/RATING PLUG

EATON TYPE FDB 14k

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

125A/125A INT. RATING 14KA @ 480VAC

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

T3 (PRIMARY SIDE)

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

645 645

28.56 28.56

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

687 687

29.45 29.45

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

691 691

30.22 30.22

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

COMMENTS:

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO. FDB3125

EATON TYPE FDB 14k

TYPE

CATALOG NO.

CATALOG NO.

Matthew Moore / Jason RittkoTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0568 / 008183 / P0555

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA117 B1 Pass

480/277VVOLTAGE

KD3400F FRAME SIZE/RATING PLUG

EATON TYPE KD 35k

480/277V

14KA @ 480VACINT. RATING

VOLTAGE

125A/125AFRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

B1 (FEEDER BREAKER) AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS 674 674 625 625 655 655

TIME AT 300% RATED CURRENT IN SECONDS 29.44 29.44 31.12 31.12 28.89 28.89

INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A

ACROSS OPEN POLE

POLE - POLE - GND

2200 2200 2200 2200 2200 2200

2200 2200 2200 2200 2200 2200

400A/400A INT. RATING 35KA @ 480VAC

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

B1 MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

750 750

88.56 88.56

TRIP TRIP

2200 2200

2200 2200

AS FOUND AS LEFT

789 789

89.68 89.68

TRIP TRIP

2200 2200

2200 2200

AS FOUND AS LEFT

811 811

85.25 85.25

TRIP TRIP

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

TEMPERATURE CORRECTION FACTOR TO 20°C, TCFEQUIPMENT TEMPERATURE

INSULATION TEST VOLTAGE

KV

kA

B.I.L. RATING

INTERRUPTING RATING

SERIAL NO.

OTHER NAMEPLATE DATA

AGE

AMPERESTYPE

MOMENTARY FAULT CLOSING AMPS

TYPE OPERATING MECHANISM

VOLTAGE

MANUFACTURER

KVVOLTAGETCC NO.

MAX. AMPS

CAT. NO.

HOLDER

SIZE

TYPE

REFILL ELEMENT TYPE

MANUFACTURER

Matthew Moore / Jerry GordonTESTED BY:

www.abm.comABM Electrical Power Solutions 15610, REVISED 2/18/2020

REVIEWED BY:EQPT. INVENTORY NO. P0568 / 008183

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

LV DISCONNECT SWITCH

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA117 B32-SW-T3 Pass

200CLIP

FRN-R-200 N/A 0.250

FUSETRON

kA

Heavy Duty Safety Switch

N/A

200A

DESCRIPTION

OVERALL CLEANLINESS

MECHANICAL CONNECTIONS

INTERLOCK SYSTEM

INSPECTED CONDITION DESCRIPTION

BLADE ALIGNMENT

TRAVEL STOPS

GROUND CONNECTION

INSPECTED CONDITION

BLADE PENETRATION

CONTACT SEQUENCE

INSULATING MEMBERS

STRUCTURAL MEMBERS

AUXILIARY DEVICES

POLE 3

POLE 2 POLE 3

BLADES CONTACT RES.

IN MICRO-OHMS

RDG.

20°C

N/A

°C

20°C

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

POLE 1

READING

POLE 1 (P1-P2)

20°C READING

POLE 2 (P2-P3)

20°C

POLE 3 (P1-P3)

READING

CLEAN/LUBE

C

L

C

NA

NA

CLEAN/LUBE

NA

NA

NA

NA

NA

FUSE DATA

NAMEPLATE DATA

KVDC

BUSSMAN

N/A

Eaton/Cutler Hammer

240V

MECHANICAL

N/A

N/A

N/A

N/A

LINE TO GROUND CLOSED

LINE TO LOAD & GROUND OPEN

POLE 2

POLE 1

2200 2200

2200 2200

2200 2200

2200 2200

2200 2200

10 11 11

250 251 245

75 77

77 81

TOP OF FUSE TO CLIP

BOTTOM OF FUSE TO CLIP

THRU FUSE

FUSE CLIP RESISTANCE IN MICRO-OHMS

INSULATION TESTS IN MEGOHMS

EQUIPMENT TEMPERATURE

R T = R M K

K sT T

+ T

+ TM

Matthew Moore / Jerry GordonTESTED BY:

www.abm.comABM Electrical Power Solutions 54100, REVISED 2/18/2020

REVIEWED BY:EQPT. INVENTORY NO. 008183

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 45 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA117 MTS-A Pass

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE:

R

R M s

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

450 450 450

467 467 467

497 497 497

0 0 0

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

C/L

C

N/A

MANUFACTURER

NAMEPLATE DATA

CATALOG NO.

WIRING NO.

SYSTEM VOLTAGE AMPACITY

CATERPILLAR SERIAL NO. TSH01899 TYPE MANUAL TRANSFER SWITCH

CTSD 480V 400

N/A CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

DESCRIPTION

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

COMMENTS: Normal position is Switchboard A. Emergency position is Switchboard B.

K

K sT T

+ T

+ TM

Matthew Moore / Jerry GordonTESTED BY:

www.abm.comABM Electrical Power Solutions 54100, REVISED 2/18/2020

REVIEWED BY:EQPT. INVENTORY NO. 008183

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 45 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA117 MTS-B Pass

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE:

R

R M s

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

125 125 125

121 121 121

119 119 119

0 0 0

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

C/L

C

N/A

MANUFACTURER

NAMEPLATE DATA

CATALOG NO.

WIRING NO.

SYSTEM VOLTAGE AMPACITY

CATERPILLAR SERIAL NO. TSH01900 TYPE MANUAL TRANSFER SWITCH

CTSD 480V 400

N/A CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

DESCRIPTION

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

COMMENTS: Normal position is Switchboard A. Emergency position is Switchboard B.

EQPT. LOCATION

ADDRESS

CUSTOMER

TRANSFORMER (<500KVA) TEST

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA117 T-B32--T3 Pass

Matthew Moore / Jerry GordonTESTED BY:

www.abm.comABM Electrical Power Solutions 56710, REVISED 8/5/2019

REVIEWED BY:EQPT. INVENTORY NO. P0568

VISUAL AND MECHANICAL INSPECTION

INSPECT PHYSICAL AND MECHANICAL CONDITION

VERIFY FANS OPERATE (IF APPLICABLE)

INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING

INSPECTION REPORT

FAIL

FAIL

FAIL

PASS

PASS

PASS

INSPECTION REMARKS

NO FANS

1,000

1,000

MINUTES

PRIMARY TO

GROUND

SECONDARY TO

GROUND

PRIMARY TO

SECONDARY

TEST V

0.50

1.00

10.00

P. I.

PHASE B PHASE CCALCTAP

2,200

2,200

2,200

2,200

2,200

2,200

2,200

2,200

2,200

TRANSFORMER TURN RATIO TEST (OPTIONAL)

PASS FAILVERIFY SHIPPING BRACKETS REMOVED

PASS FAILVERIFY THAT RESILIENT MOUNTS ARE FREE

PASS FAILVERIFY THE UNIT IS CLEAN

PASS FAILVERIFY BOLTED ELECTRICAL CONNECTIONS

INSULATION RESISTANCE IN MEGOHMS

PHASE A

/75 N/A

5.42

NAMEPLATE DATA

J06E05558SERIAL NO.

504 492 480 468

1 2 3 4 5

480 VOLTS

GE YR MFR 2006

KVA

IMPEDANCE /AA

WINDING MATERIAL °CCOPPER

CLASSTYPE

B.I.L. RATINGTEMPERATURE RISE

PRIMARY V

TAP POSITION

TAP SETTING

TAP VOLTAGES

DT-3

MANUFACTURER

SECONDARY V 208 WYE

120/

DELTA

432444

3AL

ELECTRICAL TESTS

1,000

WORKING TAP AFP.I. = 10 min/1 min

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO. LD3600WK

CUTLER HAMMER TYPE LD-K

TYPE

CATALOG NO.

CATALOG NO.

TESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO.

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 06/12/2021 TEMPERATURE 68 °F HUMIDITY 20 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA118A MAINY BY PASS (PNL A) Pass

480/277VVOLTAGE

LD3600WK FRAME SIZE/RATING PLUG

CUTLER HAMMER TYPE LD-K

480/277V

?KA @ 480VACINT. RATING

VOLTAGE

600AFRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

MIS (UPS-A) AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS 192 192 174 174 223 223

TIME AT 300% RATED CURRENT IN SECONDS N/A N/A N/A N/A N/A N/A

INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A

ACROSS OPEN POLE

POLE - POLE - GND

2200 2200 2200 2200 2200 2200

2200 2200 2200 2200 2200 2200

600A INT. RATING ?KA @ 480VAC

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MBP (SWBD-B)

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

405 405

N/A N/A

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

435 435

N/A N/A

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

490 490

N/A N/A

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

C

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO. LD3600WK

CUTLER HAMMER TYPE LD-K

TYPE

CATALOG NO.

CATALOG NO.

TESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO.

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 06/12/2021 TEMPERATURE °F HUMIDITY % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA118A MAINY BY PASS (PNL B) Pass

480/277VVOLTAGE

LD3600WK FRAME SIZE/RATING PLUG

CUTLER HAMMER TYPE LD-K

480/277V

?KA @ 480VACINT. RATING

VOLTAGE

600AFRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

MIS (UPS-B) AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS 308 308 284 284 317 317

TIME AT 300% RATED CURRENT IN SECONDS N/A N/A N/A N/A N/A N/A

INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A

ACROSS OPEN POLE

POLE - POLE - GND

2200 2200 2200 2200 2200 2200

2200 2200 2200 2200 2200 2200

600A INT. RATING ?KA @ 480VAC

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MBP (SWBD-A)

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

420 420

N/A N/A

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

380 380

N/A N/A

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

411 411

N/A N/A

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

C

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

N/A

TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST VOLTAGE MULTIPLIER, K1 =

EQUIPMENT TEMPERATURE

INSULATION TEST VOLTAGE

KV

kA

B.I.L. RATING

INTERRUPTING RATING

SERIAL NO.

OTHER NAMEPLATE DATA

AGE

AMPERESTYPE

MOMENTARY FAULT CLOSING AMPS

TYPE OPERATING MECHANISM

VOLTAGE

MANUFACTURER

KVVOLTAGETCC NO.

MAX. AMPS

CAT. NO.

HOLDER

SIZE

TYPE

REFILL ELEMENT TYPE

MANUFACTURER

Brad Barnhart / Jack GordonTESTED BY:

www.abm.comABM Electrical Power Solutions 29000, REVISED 9/22/2020

REVIEWED BY:EQPT. INVENTORY NO. P0109, P0027

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

LOADBREAK DISCONNECT TEST

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 10-4-2020 TEMPERATURE 68 °F HUMIDITY 25 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BUILDING 32 MAIN DISCONNECT Pass

100CLAMP

5CLE-100E 5.5

CLE

kA

MVS 2 600

DESCRIPTION

OVERALL CLEANLINESS

MECHANICAL CONNECTION

CUBICLE

INSPECTED CONDITION DESCRIPTION

MAIN CONTACTS

BEARINGS

GROUND CONNECTION

INSPECTED CONDITION

HEATERS

CONTACT SEQUENCE

INSULATING MEMBERS

STRUCTURAL MEMBERS

AUXILIARY DEVICES

POLE 3

POLE 2 POLE 3

CONTACT RESISTANCE

MICRO-OHMS

RDG.

20°C

°C

2.5

4,300.000

20°C

32.00

32 31

31.0029.00

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

POLE 1

TOP OF FUSE TO CLIP

BOTTOM OF FUSE TO CLIP

THRU FUSE

READING

3,250.00

20°C

3,250.000

READING

3,925.00

20°C

3,925.000

READING

4,300.00

CLEAN/LUBE

C

C

CLEAN/LUBE

C/L

FUSE DATA

NAMEPLATE DATA

INSULATION TESTS

FUSE CLIP RESISTANCE

KVDC K2 = (K1) (TCF)

EATON

N/A

EATON

5KV

SPRING 60

K2

1.000

RANGE

MULTIPLIER

1.000

LINE TO GROUND CLOSED

LINE TO LOAD & GROUND OPEN

6,590

7,100

6,850

POLE 2

POLE 1

OVER POTENTIAL TEST

TEST TIME A PHASE

B PHASE

C PHASE

B PHASE

MICRO-AMP LEAKAGE

PASS FAIL@ KVDC

POLE1 (P1-P2) POLE3POLE2 (P2-P3) (P1-P3)

COMMENTS: Closed insulation test not completed due to interlocked transfer switch.

Brad Barnhart / Jack GordonTESTED BY:

www.abm.comABM Electrical Power Solutions 54560, REVISED 7/16/2019

REVIEWED BY:EQPT. INVENTORY NO. P0109, P0027

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MANUAL TRANSFER SWITCH TEST REPORT

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 10-4-2020 TEMPERATURE 68 °F HUMIDITY 25 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BUILDING 32 SELECTOR SWITCH Pass

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

INSPECTED CONDITION CLEAN/LUBE

CU ALSIZE:

POLE

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

NA

C/L

MANUFACTURER

NAMEPLATE DATA

CATALOG NO. SYSTEM VOLTAGE AMPACITY

EATON SERIAL NO. TYPE MSV

4160 V 1200

DESCRIPTION

°C

N - G

READING POLE

CONTACT RESISTANCE

POLE

A - G

POLE

A - B

B - C

C - A

B - G

INSULATION RESISTANCE 1,000 Vdc

READING

READINGS IN

POLE

A - G

POLE

A - B

B - C

C - A

B - G

READING

READINGS IN

C - G

B

C

N

READING

READING IN MICRO-OHMS

TEMPERATURE CORRECTION FACTOR 20°C, TCFEQUIPMENT TEMPERATURE

LOAD CONDUCTOR NO./ PHASE: 1/PHASE

A

A - N

20°C

B - N

C - G C - N

20°C READING

N - G

MEGOHMS

20°C

NORMAL / PREFERRED

B

READING

A - N

20°C

B - N

C - N

20°C POLE READING 20°C

MEGOHMS

C

N

EMERGENCY / ALTERNATE

POLE

READING20°C

NORMAL / PREFERRED

A

29 29

20°C

EMERGENCY / ALTERNATE

COMMENTS: Contact Resistance preferred Source Readings are for Ckt. #15; Alternate Source Readings are for Ckt. # 11.

Insulation test not completed due to connected equipment.

MANUAL TRANSFER SWITCH TEST REPORT

12PAGE

www.abm.comABM Electrical Power Solutions 54560, REVISED 7/16/2019

GRD. FLT.

GRD. FLT.

CU

THERMAL MEMORY

4W3W

AL

FRAME SIZE(F)

Matthew Moore / Jason CatleyTESTED BY:

www.abm.comABM Electrical Power Solutions 15055, REVISED 12/28/2019

REVIEWED BY:EQPT. INVENTORY NO. P0568 / 010023 / 8063

BREAKER TYPE

TRIP UNIT TYPE

N/A

CUBICLE CODE

SN / SO NO.

MOUNTING

TARGETS

1200A

20°C

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

SIZE

A=

AA

x

A

A

A

A = A

AS

LEFT

TEST

AMPERES

POLE 1

FUNCTION

INSTANTANEOUS

SHORT TIME

LONG TIME

POLE 2

AS

FOUND

TIME BAND

MINIMUM

IPU

GFPU

VOLTAGE DROP @ LONG TIME TEST CURRENT

LTPU

STPU

GROUND FAULT

READING

POLE 3POLE 2POLE 1

20°C

LOAD CONDUCTOR NO.

READING 20°C 20°C

EATON CUTLER HAMMER

MAXIMUM

20°C

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

LOW VOLTAGE

POWER CIRCUIT BREAKER TEST

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 11/05/2020 TEMPERATURE 65 °F HUMIDITY 40 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION GENERATOR…

This is the start of the file's text. The full file is on GovTribe.