Atch 4.UD August 2020-July 2021_Final Report.pdf
PDF 6 MB Posted
- Attached to
- H961--VAPHS Triennial Electrical Inspections Federal contract opportunity
- Solicitation number
- 36C24426Q0055
About this file
This document is a Customer Field Service Report from ABM Electrical Power Solutions detailing electrical power equipment testing performed at the VA Pittsburgh Healthcare Center from August 2020 to July 31, 2021. The report documents comprehensive electrical equipment inspections across multiple buildings, identifying numerous equipment issues including damaged oil port gate valves, breakers failing to trip correctly, transformer and panel anomalies, and contact resistance problems.
The related federal contract opportunity is Solicitation Number 36C24426Q0055 for "H961--VAPHS Triennial Electrical Inspections", which is a 100% set-aside for Service-Disabled Veteran-Owned Small Business. The solicitation seeks FY26 Triennial Breaker Inspections for the Department of Veterans Affairs, with a NAICS code of 811210. Key dates include a question submission deadline of January 5, 2026, and a quote submission deadline of January 8, 2026. The point of contact is Allan Tabliago, and all communications must be via email to allan.tabliago@va.gov, with no phone calls accepted.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Atch 6.Heinz_May 2020_Final Report.pdf | ||
| Atch 5.Heinz_April 2020_Final Report.pdf | ||
| Atch 7.Heinz_June and July 2020_Final Report.pdf | ||
| 36C24426Q0055 0002_1.docx | DOCX document | |
| Atch 3.Equipment List - Breaker Testing List UD- April 2015.xlsx | XLSX spreadsheet | |
| Atch 2.UD Elect and Arc Flash Study.pdf | ||
| Atch 1.HZ Elect and Arc Flash study 2023 reduced.pdf | ||
| 36C24426Q0055 0001_1.docx | DOCX document | |
| VAAR 852.219-75 VA Notice of Limitations on Subcontracting.pdf | ||
| 36C24426Q0055 Triennial Inspectiona.pdf | ||
| WD 2015-4235 R32 20251203.pdf | ||
| 36C24426Q0055_1.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER
ADDRESS
CUSTOMER
FIELD SERVICE REPORT
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE
Description:
From August 2020 to July 31, 2021, ABM Electrical Power Solutions Field Personnel were at VA Pittsburgh Healthcare Center, located in Pittsburgh, PA, on behalf of Department of Veterans Affairs, to perform testing of electrical power equipment.
Engineering Evaluation:
Testing was performed in accordance with the International Electrical Testing Association's Maintenance Testing Specifications and project specifications. Fluid Analysis was performed in accordance with IEEE Specifications.
Scope of Work:
Perform Maintenance testing and cleaning of electrical power equipment.
Test Results / Comments:
Heinz Building #32, Outside, B32IT Transformer; Oil Port Gate Valve is damaged and needs replaced.
University Drive, 3C-110, SR6; Main Breaker failed to Trip on A-Phase.
University Drive, 3C-110, SR-6; Breaker #1 will not Trip on Long Time Function.
University Drive, 3C-110, SR6A; Breaker #3 and Breaker #4 will not Trip on Long Time Function.
University Drive, Fed from ATS BT-EQ, MS2; Does not Trip. Trip unit needs to be replaced.
University Drive, Fed from ATS BT-EQ, MS2; UPS B 3W123; Breaker Trips Instant, out of tolerance for Long Time Trip.
University Drive, Various, PNL NEDPEQ; Not operational on Instant.
University Drive, Various, TR-BTGLEQ Transformer; 150 VAC measured on the Neutral when isolating to test. Could not test.
University Drive, Building #1, 1st Floor, C1AY; Breaker would not Trip on C-Phase Long Time.
University Drive, Building #1, BN101, MDPY; Lugs are too big for Conductor.
University Drive, Building #1, MDP-1, RM AW-121B; GWC Main, C-Phase Contact Resistance is out of tolerance.
University Drive, Building #1, MDP-X, Across from 3N-116; Trip time out of tolerance.
University Drive, Building #1, Room 2E104, PNL 2-LCA; Excessive corrosion, unable to test.
University Drive, Building #10, 7W-139C, CRDS; Breaker W4CP; Trip coil will not reset.
University Drive, Building #10, 7W-139C, EQDS, Breaker MCCMCEM; Trip coil will not reset. Breaker Elevator S1, out of tolerance.
All other test results are acceptable per NETA - MTS Standards. All equipment was left in Satisfactory Operational Condition.
This report certifies that the above equipment has been tested in compliance with recognized standards or for safe use in a specific manner, or in accordance with
Federal, State or Municipal regulations. The report is accurate and true to the best of our knowledge and belief. All equipment used in making physical determinations is accurate and bears recent and direct traceability to the National Institute of Standards and Technology. (NIST).
7/7/2022
By:
Josh Schoedel www.abm.comABM Electrical Power Solutions REVISED 7/7/2022
ABM Electrical Power Solutions 317 Commerce Park Drive Cranberry Township, PA 16066
Project Manager
Equipment Tested Job #86301680 www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
1PAGE
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
115065 - LOW VOLT. PWR. CKT. BKR. TEST (CAP BANK 51A1)
(HEINZ) BLDG #32 BA117 A1
215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 BA117 A1
315910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 BA117 B1
415610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #32 BA117 B32-SW-T3
554100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #32 BA117 MTS-A
654100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #32 BA117 MTS-B
756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #32 BA117 T-B32--T3
815910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 BA118A MAINT BY PASS (PNL A)
915910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 BA118A MAINT BY PASS (PNL B)
1029000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #32 BUILDING 32 MAIN DISCONNECT
1154560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #32 BUILDING 32 SELECTOR SWITCH
1315065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-B) - Pass
(HEINZ) BLDG #32 GENERATOR ROOM EMDP
1415065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN) - Pass
(HEINZ) BLDG #32 GENERATOR ROOM EMDP
1515065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-A)
(HEINZ) BLDG #32 GENERATOR ROOM EMDP
1615910- MCB - 3 in 1 REV.1 (3) - Pass (2)
(HEINZ) BLDG #32 GND FLOOR CORRIDOR NE2A
1754100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM ATS-A
1854100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM ATS-B
1915065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-B)
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM MDP
2015065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE)
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM MDP
2115065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM MDP
2215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-A)
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM MDP
2315910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD A
2415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD A
2515065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD A MAIN
2615065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD B
2715910- MCB - 3 in 1 REV.1 (3)
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD B
2815910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 MAIN ELECTRICAL ROOM SWBD B
2PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
2956700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BLDG #32 OUTSIDE B32IT XFMR
3015910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 SERVER ROOM PDU-A
3115910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 SERVER ROOM PDU-A
3315910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 SERVER ROOM PDU-B
3415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 SERVER ROOM PDU-B
3515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 SERVER ROOM PDU-C
3615910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 SERVER ROOM PDU-C
3715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 SERVER ROOM PDU-D
3815910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 SERVER ROOM PDU-D
3915910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 SERVER ROOM PDU-E
4015910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 SERVER ROOM PDU-E
4115910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 SERVER ROOM PNL RD
4215910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 SERVER ROOM UPS-DP-A
4315910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 SERVER ROOM UPS-DP-A
4415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 SERVER ROOM UPS-DP-B
4515910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 SERVER ROOM UPS-DP-B
4615910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 UPS DP-8
4715910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #32 UPS DP-8
4856700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BLDG #49 OUTSIDE B49 XFMR
49TJH2B DGA - 07J722043-Tran
(HEINZ) BLDG #49 OUTSIDE B49 XFMR
51TJH2B Fluid - 07J722043-Tran
(HEINZ) BLDG #49 OUTSIDE B49 XFMR
5215065 - LOW VOLT. PWR. CKT. BKR. TEST (2)
(HEINZ) BLDG #50 GA139 EDP-1 ATS 5A
5315065 - LOW VOLT. PWR. CKT. BKR. TEST (2)
(HEINZ) BLDG #50 GA139 EDP-1 ATS 5B
5415065 - LOW VOLT. PWR. CKT. BKR. TEST (2)
(HEINZ) BLDG #50 GA139 EDP-1 ATS-4
5515065 - LOW VOLT. PWR. CKT. BKR. TEST (2)
(HEINZ) BLDG #50 GA139 EDP-1 ATS-4A
3PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
5615065 - LOW VOLT. PWR. CKT. BKR. TEST (2)
(HEINZ) BLDG #50 GA139 EDP-1 ATS-6A
5715065 - LOW VOLT. PWR. CKT. BKR. TEST (2)
(HEINZ) BLDG #50 GA139 EDP-1 ATS-6B
5815065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 EPD BLDG 51 LIFE SAFETY
5915065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 EPD-1 GENERATOR LOAD BANK
6015065 - LOW VOLT. PWR. CKT. BKR. TEST (3)
(HEINZ) BLDG #50 GA139 EPD-1 SPARE
6115065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 GENERATOR MAIN EPD
6215065 - LOW VOLT. PWR. CKT. BKR. TEST (2)
(HEINZ) BLDG #50 GA139 GENERATOR MAIN EPD-1
6315065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 50 TX-1 ELEVATOR
6415065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 50 TX-2 LS CRIT
6515065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 ATS-7A
6615065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 CRITICAL
6715065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 EK6 AND EK7
6815065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 ELEVATORS
6915065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #50 GA139 SWBD EPD BLDG 51 EQUIPMENT
7029000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #50 GA140 SW-B50 MAIN DISC
7154560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #50 GA140 SW-B50 SELECTOR SWITCH
7356700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BLDG #50 GA140 T- B50-T1
74TJH2B DGA - PBL2577-0101-Tran
(HEINZ) BLDG #50 GA140 T- B50-T1
76TJH2B Fluid - PBL2577-0101-Tran
(HEINZ) BLDG #50 GA140 T- B50-T1
7815910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 1A120 1ALB
7915910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 1A120 1ALC
8015065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-GA1/MCC-1A1)
(HEINZ) BLDG #51 1A122 MCC-1A1
8115065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL. GALF)
(HEINZ) BLDG #51 1A127 51A2-MSG
8215065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GALA/1ALA)
(HEINZ) BLDG #51 1A127 51A2-MSG
8315065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. GALB/1ALB)
(HEINZ) BLDG #51 1A127 51A2-MSG
4PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
8415065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)
(HEINZ) BLDG #51 1A127 51A2-MSG
8515065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE)
(HEINZ) BLDG #51 1A127 51A2-MSG
8615065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS 2ALB/3ALB)
(HEINZ) BLDG #51 1A127 51A2-MSG
8715065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-1A)
(HEINZ) BLDG #51 1A127 51A2-MSG
8815065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL 1ALE)
(HEINZ) BLDG #51 1A127 51A2-MSG
8915065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. 2ALA/3ALA)
(HEINZ) BLDG #51 1A127 51A2-MSG
9015065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL 1ALC/1ALD)
(HEINZ) BLDG #51 1A127 51A2-MSG
9115065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL GALC/GALD)
(HEINZ) BLDG #51 1A127 51A2-MSG
9215065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNLS. 2ALC/3ALC)
(HEINZ) BLDG #51 1A127 51A2-MSG
9354100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #51 1A127 ATS-1A
9454100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #51 1A127 ATS-2A
9554101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass
(HEINZ) BLDG #51 1A127 ATS-4A
9754101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass
(HEINZ) BLDG #51 1A127 ATS-5A
9956700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BLDG #51 1A127 B51-T-51A2
100TJH2B DGA - PBL2578-0101-Tran
(HEINZ) BLDG #51 1A127 B51-T-51A2
102TJH2B Fluid - PBL2578-0101-Tran
(HEINZ) BLDG #51 1A127 B51-T-51A2
10456710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #51 1A127 B51-T-ATS-1A
10529000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #51 1A127 SW-B51A1 MAIN DISC
10654560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #51 1A127 SW-B51A1 SELECTOR SWITCH
10829000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #51 1A127 SW-B51A2 MAIN DISC
10954560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #51 1A127 SW-B51A2 SELECTOR SWITCH
11129000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #51 1A127 SW-B51A3 MAIN DISC
11254560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #51 1A127 SW-B51A3 SELECTOR SWITCH
11415610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #51 1A127 SW-B51ATS-1A (PRI)
11515610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #51 1A127 SW-B51ATS-1A (SEC)
5PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
11615910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 1B145 MCC-1B1
11715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 1B150 EC1B
11854100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #51 1B161 ATS 2B
11954100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #51 1B161 ATS-1B
12054101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass
(HEINZ) BLDG #51 1B161 ATS-5B
12254101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass
(HEINZ) BLDG #51 1B161 ATS-6B
12456710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #51 1B161 B51-T-ATS-1B
12515610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #51 1B161 SW-B51ATS-1B (PRI)
12615610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #51 1B161 SW-B51ATS-1B (SEC)
12715610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #51 1B161 SW-B51ATS-2B
12829000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #51 1B161 SW-B51B1 MAIN DISC
12954560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #51 1B161 SW-B51B1 SELECTOR SWITCH
13129000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #51 1B161 SW-B51B2 MAIN DISC
13254560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #51 1B161 SW-B51B2 SELECTOR SWITCH
13415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 2A129 2ALA
13515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 2A129 2ALB
13615910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 2A129 2ALC
13715065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-GA1/MCC-1A1)
(HEINZ) BLDG #51 2A131 MCC-2A1
13815065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-GA1/MCC-1A1)
(HEINZ) BLDG #51 2B168 MCC-2B1
13915910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 3A129 3ALA
14015910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 3A129 3ALB
14115910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 3A129 3ALC
14215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 3A131 MCC-3A1
14315910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 3B170 MCC-3B1
14415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 3B172 EC3B
6PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
14515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 GA113 ECGA
14615910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 GA113 GALA
14715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 GA113 GALB
14815910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 GA113 GALC
14915910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 GA115 MCC-GA1
15015065 - LOW VOLT. PWR. CKT. BKR. TEST (MCC-GA1/MCC-1A1)
(HEINZ) BLDG #51 GB135 MCC-GB1
15115910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 GB-137 ECGB
15254100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #51 KITCHEN ATS ATS EK-6
15354100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #51 KITCHEN ATS ATS EK-7
15415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 KITCHEN ATS PANEL EK-6
15515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #51 KITCHEN ATS PANEL EK-7
15615610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #51 KITCHEN ATS SW-EK6
15715610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #51 KITCHEN ATS SW-EK7
15856700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BLDG #51 KITCHEN ATS XFMR EK-6 EK-7
15916100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING MAIN #1
16045000 - OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING MAIN #1
16116100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING MAIN #2
16245000 - OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING MAIN #2
16316100 - VACUUM CIRCUIT BREAKER ORIG
(HEINZ) BLDG #55 METAL CLAD BUILDING TIE
16441200 - DIGITRIP OVERCURRENT RELAY
(HEINZ) BLDG #55 METAL CLAD BUILDING TIE
16529000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) SW-B63-68-T1 MAIN DISC
16654560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) SW-B63-68-T1 SELCTOR SWITCH
16829000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) SW-B69-T1 MAIN DISC
17054560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) SW-B69-T1 SELCTOR SWITCH
17229000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) SW-B70-T1 MAIN DISC
7PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
17354560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) SW-B70-T1 SELECTOR SWITCH
17529000 - LOADBREAK DISCONNECT- USE
(HEINZ) BLDG #71 GA102 SW-B71-T1 MAIN DISC
17654560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BLDG #71 GA102 SW-B71-T1 SELCTOR SWITCH
17856700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BLDG #71 GA102 T1- MAIN
179TJH2B DGA - S2924-01-001-Tran
(HEINZ) BLDG #71 GA102 T1- MAIN
181TJH2B Fluid - S2924-01-001-Tran
(HEINZ) BLDG #71 GA102 T1- MAIN
18229000 - LOADBREAK DISCONNECT- USE
(HEINZ) BOILER ROOM BOILER ROOM MAIN DISCONNECT
18356700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BOILER ROOM BOILER ROOM MAIN TRANSFORMER
184TJH2B DGA - M156433-Tran
(HEINZ) BOILER ROOM BOILER ROOM MAIN TRANSFORMER
186TJH2B Fluid - M156433-Tran
(HEINZ) BOILER ROOM BOILER ROOM MAIN TRANSFORMER
18754560 - MANUAL TRANSFER SWITCH TEST REPORT
(HEINZ) BOILER ROOM BOILER ROOM SELECTOR SWITCH
18915065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)
(UD) 5/15/21 TESTING 208V SWGR PANEL NBNA
19015910- MCB - 3 in 1 REV.1
(UD) 5/15/21 TESTING 3C-110 SR6
19115910- MCB - 3 in 1 REV.1 -(2)
(UD) 5/15/21 TESTING 3C-110 SR-6
19215910- MCB - 3 in 1 REV.1 -(3)-
(UD) 5/15/21 TESTING 3C-110 SR-6
19315910- MCB - 3 in 1 REV.1 -(2)- Fail
(UD) 5/15/21 TESTING 3C-110 SR6A
19415910- MCB - 3 in 1 REV.1
(UD) 5/15/21 TESTING FED FROM ATS BT-EQ MS2
19515910- MCB - 3 in 1 REV.1 (2)
(UD) 5/15/21 TESTING FED FROM ATS BT-EQ MS2
19615910- MCB - 3 in 1 REV.1 (3)
(UD) 5/15/21 TESTING FED FROM ATS BT-EQ MS2
19754101 - AUTOMATIC TRANSFER SWITCH TEST REV.1
(UD) 5/15/21 TESTING FED FROM NBNA & 600A SW ATS #2LS
19915910- MCB - 3 in 1 REV.1
(UD) 5/15/21 TESTING VARIOUS PNL BTGDPHEQ
20015910- MCB - 3 in 1 REV.1
(UD) 5/15/21 TESTING VARIOUS PNL NBNA
20115910- MCB - 3 in 1 REV.1
(UD) 5/15/21 TESTING VARIOUS PNL NEDPEQ
20215910- MCB - 3 in 1 REV.1 (2)
(UD) 5/15/21 TESTING VARIOUS PNL NEDPEQ
20356710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(UD) 5/15/21 TESTING VARIOUS TR-BTGLEQ TRANSFORMER
8PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
20415065 - LOW VOLT. PWR. CKT. BKR. TEST
(UD) BLDG #1 1ST FLOOR C1AX
20515910- MCB - 3 in 1 REV - Pass
(UD) BLDG #1 1ST FLOOR C1AX
20615910- MCB - 3 in 1 REV - Pass (2)
(UD) BLDG #1 1ST FLOOR C1AX
20715065 - LOW VOLT. PWR. CKT. BKR. TEST
(UD) BLDG #1 1ST FLOOR C1AY
20815910- MCB - 3 in 1 REV - Pass (2)
(UD) BLDG #1 1ST FLOOR C1AY
20915910- MCB - 3 in 1 REV - Pass (3)
(UD) BLDG #1 1ST FLOOR C1AY
21015910- MCB - 3 in 1 REV - Pass
(UD) BLDG #1 1ST FLOOR C1AY
21115910- MCB - 3 in 1 REV.1
(UD) BLDG #1 4TH FL NW CARD CATH RM BC102
21215910- MCB - 3 in 1 REV - Pass
(UD) BLDG #1 5TH FLOOR INTERSTITIAL
21315910- MCB - 3 in 1 REV - Pass
(UD) BLDG #1 5TH FLOOR INTERSTITIAL
21456700 - TRANSFORMER MAINTENANCE TEST (10)
(UD) BLDG #1 5TH FLOOR INTERSTITIAL
21556700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #1 BEDTOWER (OUTSIDE) ASU / SDU TRANSFORMER
217TJH2B DGA - 0950008133-Tran
(UD) BLDG #1 BEDTOWER (OUTSIDE) ASU / SDU TRANSFORMER
219TJH2B Fluid - 0950008133-Tran
(UD) BLDG #1 BEDTOWER (OUTSIDE) ASU / SDU TRANSFORMER
22056700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #1 BEDTOWER (OUTSIDE) BEDTOWER TRANSFORMER
222TJH2B DGA - Q549962-TWP-Tran
(UD) BLDG #1 BEDTOWER (OUTSIDE) BEDTOWER TRANSFORMER
224TJH2B Fluid - Q549962-TWP-Tran
(UD) BLDG #1 BEDTOWER (OUTSIDE) BEDTOWER TRANSFORMER
22615065 - LOW VOLT. PWR. CKT. BKR. TEST (4TH FL NW CARDIAC CATH)
(UD) BLDG #1 BN101 480V SWITCHGEAR
22715065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL MDPX-1BK)
(UD) BLDG #1 BN101 480V SWITCHGEAR
22815065 - LOW VOLT. PWR. CKT. BKR. TEST (MDPY-23H)
(UD) BLDG #1 BN101 480V SWITCHGEAR
22915910- MCB - 3 in 1 REV.1 (3)
(UD) BLDG #1 BN101 MDPX
23015910- MCB - 3 in 1 REV.1
(UD) BLDG #1 BN101 MDPX
23115910- MCB - 3 in 1 REV.1 (2)
(UD) BLDG #1 BN101 MDPX
23215065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL NBNB) Pass
(UD) BLDG #1 BN101 MDPY
23315065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU 7-11E RF1 & SF1)Pass - Pass
(UD) BLDG #1 BN101 MDPY
9PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
23415065 - LOW VOLT. PWR. CKT. BKR. TEST (UROLOGY 2ND FLOOR 2CAF)
(UD) BLDG #1 BN101 MDPY
23515065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL 4HN1) - Pass
(UD) BLDG #1 BN101 MDPY
23615065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL BACX) - Pass
(UD) BLDG #1 BN101 MDPY
23715065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS NEW ICU-C)
(UD) BLDG #1 BN101 MDPY
23815065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE) - Pass
(UD) BLDG #1 BN101 MDPY
23915065 - LOW VOLT. PWR. CKT. BKR. TEST (DIST. PNL 2HCA)
(UD) BLDG #1 BN101 MDPY
24015065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS- 6) - Pass (2)
(UD) BLDG #1 BN101 MDPY
24115065 - LOW VOLT. PWR. CKT. BKR. TEST (SPD) - Pass
(UD) BLDG #1 BN101 MDPY
24315065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU 7-11E RF2 & SF2)Pass - Pass
(UD) BLDG #1 BN101 MDPY
24415065 - LOW VOLT. PWR. CKT. BKR. TEST (PANEL C2AF 2ND FLOOR UROLOGY)-Pass
(UD) BLDG #1 BN101 MDPY
24515910- MCB - 3 in 1 REV.1 (6)
(UD) BLDG #1 BN101 PNL NBNB
24656700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #1 BN101 XFMR NBNB
24715910- MCB - 3 in 1 REV.1 (4)
(UD) BLDG #1 CLOSET 5A116B PNL'S 5LN1 & 5LN2 NORMAL POWER
24856700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #1 CLOSET 2A-239 PNL S2AC 25KVA XFMR
24915910- MCB - 3 in 1 REV.1 (5)
(UD) BLDG #1 CLOSET 2A-239 PNL'S C2AF & S2AC
25015065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-1RF)
(UD) BLDG #1 ECM INTERSITITIAL
25115065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-1RF) (2)
(UD) BLDG #1 ECM INTERSITITIAL
25215910- MCB - 3 in 1 REV.1
(UD) BLDG #1 ECM INTERSITITIAL
25356700 - TRANSFORMER MAINTENANCE TEST (10)
(UD) BLDG #1 ECM INTERSITITIAL
25415910- MCB - 3 in 1 REV.1
(UD) BLDG #1 ECM RM 2A110
25515910- MCB - 3 in 1 REV.1
(UD) BLDG #1 ECM RM 3A138
25656700 - TRANSFORMER MAINTENANCE TEST (10)
(UD) BLDG #1 ECM RM 3A138
25715910- MCB - 3 in 1 REV.1
(UD) BLDG #1 ECM RM 3A168
25856700 - TRANSFORMER MAINTENANCE TEST (10)
(UD) BLDG #1 ECM RM 3A168
25915910- MCB - 3 in 1 REV.1
(UD) BLDG #1 ECM RM 3N107
10PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
26015910- MCB - 3 in 1 REV.1
(UD) BLDG #1 ECM RM NEAR RM 2A110
26156700 - TRANSFORMER MAINTENANCE TEST (10)
(UD) BLDG #1 ECM RM NEAR RM 2A110
26215910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-1 RM 1A106
26315910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-1 RM 1A176
26415910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-1 RM 1A206
26515910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-1 RM 1A242
26615910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-1 RM 2A133
26715910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-1 RM AA127
26815910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-1 RM AW-121B
26915910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDPX RM BW224
27015910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-X 4TH FL. PENTHOUSE (SLEEP LAB)
27115910- MCB - 3 in 1 REV.1 (2)
(UD) BLDG #1 MDP-X ACROSS FROM 3N-116
27256700 - TRANSFORMER MAINTENANCE TEST (10)
(UD) BLDG #1 MDP-X ACROSS FROM 3N-116
27315910- MCB - 3 in 1 REV.1 (2)
(UD) BLDG #1 MDP-X RM 3N-214
27456700 - TRANSFORMER MAINTENANCE TEST (10)
(UD) BLDG #1 MDP-X RM 3N-214
27515910- MCB - 3 in 1 REV.1
(UD) BLDG #1 MDP-X RM BW-224
27615910- MCB - 3 in 1 REV.1 (2)
(UD) BLDG #1 MDP-X RM BW-224
27756700 - TRANSFORMER MAINTENANCE TEST (10)
(UD) BLDG #1 MDP-X RM BW-224
278DISCONNECT
(UD) BLDG #1 MDPY DISC MDPY
27915910- MCB - 3 in 1 REV.1 (3)
(UD) BLDG #1 MDPY PNL SPD
28056700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #1 MDPY TRANSFORMER MDPY
28115910- MCB - 3 in 1 REV.1
(UD) BLDG #1 ROOM 2E104 PNL 2-HCA
28215910- MCB - 3 in 1 REV.1 (2)
(UD) BLDG #1 ROOM 2E104 PNL 2-HCA
28315910- MCB - 3 in 1 REV.1
(UD) BLDG #1 ROOM 2E104 PNL 2-LCA
28456700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #1 ROOM 2E104 TRANSFORMER T1
11PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
28515910- MCB - 3 in 1 REV.(1st Floor Check In Elec Closet)
(UD) BLDG #1 PARKING GARAGE B1G106 B1TN TRANSFORMER
28656700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #10 4TH FLOOR ELEC CLOSET 4W144 30KVA XFMR
28756700 - TRANSFORMER MAINTENANCE TEST (2)
(UD) BLDG #10 4TH FLOOR ELEC CLOSET 4W144 XFMR
28815910- MCB - 3 in 1 REV.1 (3)
(UD) BLDG #10 4TH FLOOR ELEC CLOSET PNL W4AR1
28956700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #10 5TH FLOOR ELEC CLOSET 5W144 30KVA XFMR
29056700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #10 5TH FLOOR ELEC CLOSET 5W144B XFMR
29115910- MCB - 3 in 1 REV.1 (2)
(UD) BLDG #10 5TH FLOOR ELEC CLOSET PNL W5AR1
29256700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #10 6TH FLOOR ELEC CLOSET 6W144 30KVA XFMR
29315910- MCB - 3 in 1 REV.1
(UD) BLDG #10 6TH FLOOR ELEC CLOSET PNL W6AR1
29456700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #10 6TH FLOOR ELEC CLOSET W144 XFMR
29556700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #10 7W-139C 112.5 KVA XFMR
29654101 - AUTOMATIC TRANSFER SWITCH TEST REV.1
(UD) BLDG #10 7W-139C ATS 10EM
29854101 - AUTOMATIC TRANSFER SWITCH TEST REV.1
(UD) BLDG #10 7W-139C ATS 8LS
30054101 - AUTOMATIC TRANSFER SWITCH TEST REV.1
(UD) BLDG #10 7W-139C ATS 9EC
30215910- MCB - 3 in 1 REV.1 (5)
(UD) BLDG #10 7W-139C CRDS
30315910- MCB - 3 in 1 REV.1 (5)
(UD) BLDG #10 7W-139C CRDS
30456700 - TRANSFORMER MAINTENANCE TEST
(UD) BLDG #10 7W-139C CRITICAL ATS CRDS XFMR
30515910- MCB - 3 in 1 REV.1 (4)
(UD) BLDG #10 7W-139C EQDS
30615055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1
(UD) BLDG #10 7W-139C Main Swbd
30715055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)
(UD) BLDG #10 7W-139C MAIN SWBD/CRITICAL ATS
30815055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)
(UD) BLDG #10 7W-139C MAIN SWBD/EQUIPMENT ATS
30915055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)
(UD) BLDG #10 7W-139C MAIN SWBD/LIFE SAFETY
31015055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)
(UD) BLDG #10 7W-139C MAIN SWBD/MAIN CHILLER
31115055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)
(UD) BLDG #10 7W-139C MAIN SWBD/SPARE
31215055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)
(UD) BLDG #10 7W-139C MAIN SWBD/W4AP1
12PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
31315055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (3)
(UD) BLDG #10 7W-139C MAIN SWBD/W5AP1
31415055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (2)
(UD) BLDG #10 7W-139C MAIN SWBD/W6AP1
31515055 - LOW VOLT. PWR. CKT. BKR. TEST REV 1 (4)
(UD) BLDG #10 7W-139C MAIN SWBD/W7AP1
31615910- MCB - 3 in 1 REV.1 (6)
(UD) BLDG #10 7W-139C RDSC
31715910- MCB - 3 in 1 REV.1 (5)
(UD) BLDG #10 7W-139C XFMR 9WECM
31815910- MCB - 3 in 1 REV.1 (6)
(UD) BLDG #10 7W-139C XFMR NECCB
31956710 - TRANSFORMER DRY ACCEPTANCE (<500KVA)
(UD) BLDG #10 NEXT TO GENERATORS 1ECGA TRANSFORMER
32054100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(UD) BLDG #10 NEXT TO GENERATORS ATS 10-OR
32115800- MCB - 3 tests 1 sheet
(UD) BLDG #10 NEXT TO GENERATORS MAIN SWBD NO1
32215800- MCB - 3 tests 1 sheet (4)
(UD) BLDG #10 NEXT TO GENERATORS MAIN SWBD NO1
32315800- MCB - 3 tests 1 sheet (3)
(UD) BLDG #10 NEXT TO GENERATORS MAIN SWBD NO1
32415800- MCB - 3 tests 1 sheet (2)
(UD) BLDG #10 NEXT TO GENERATORS MAIN SWBD NO1
32515910- MCB - 3 in 1 REV.1
(UD) BLDG #10 NEXT TO GENERATORS PANEL 1ECGA
32615065 - LOW VOLT. PWR. CKT. BKR. TEST MAIN
(UD) BLDG #10 NEXT TO GENERATORS PANEL ECM
32715910- MCB - 3 in 1 REV.1 EC2A/EC31/EC1A
(UD) BLDG #10 NEXT TO GENERATORS PANEL ECM
32815910- MCB - 3 in 1 REV.1 4HEC1/EC2AB/E3CAB
(UD) BLDG #10 NEXT TO GENERATORS PANEL ECM
32916100 - VACUUM CIRCUIT BREAKER ORIG
(UD) BLDG #31 4160V SWITCHGEAR ROOM FEEDER 1I BEDTOWER
33016100 - VACUUM CIRCUIT BREAKER ORIG
(UD) BLDG #31 4160V SWITCHGEAR ROOM FEEDER 2I BEDTOWER
D.O.
ZONE INTLK
GRD. FLT.
GRD. FLT.
CU
THERMAL MEMORY
4W3W
AL
FRAME SIZE(F)
Matthew Moore / Jason RittkoTESTED BY:
www.abm.comABM Electrical Power Solutions 15055, REVISED 12/28/2019
REVIEWED BY:EQPT. INVENTORY NO. 008183 / P0568 / 008829
BREAKER TYPE
TRIP UNIT TYPE
N/A
CUBICLE CODE
SN / SO NO.
MOUNTING
TARGETS
400A
20°C
INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE
SIZE
A=
AA
x
A
A
A
A = A
AS
LEFT
TEST
AMPERES
POLE 1
FUNCTION
INSTANTANEOUS
SHORT TIME
LONG TIME
POLE 2
AS
FOUND
TIME BAND
MINIMUM
IPU
GFPU
VOLTAGE DROP @ LONG TIME TEST CURRENT
LTPU
STPU
GROUND FAULT
READING
POLE 3POLE 2POLE 1
20°C
LOAD CONDUCTOR NO.
READING 20°C 20°C
WESTINGHOUSE
MAXIMUM
20°C
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
LOW VOLTAGE
POWER CIRCUIT BREAKER TEST
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA117 A1 Pass
KD3400F
2,200
2,200
2,200
2,200
2,200
2,200
2,200.002,200 2,200.00
2,200.00 2,200.00
2,200.00
2,200.00
2,200.00
2,200 2,200.00 2,200 2,200.00
READING
878.00 845.00 925.00
N/A
400A
CAcceptable
Acceptable C/L
Acceptable C
Acceptable NA
Acceptable C
Acceptable NA
Acceptable NA
TRIP
38.27
TRIP
38.27
TRIP
38.27
TRIP
38.27
TRIP
38.27
TRIP
38.27
DESCRIPTION
ARC CHUTES
AUXILIARY DEVICES
GROUND CONNECTION
DESCRIPTION
CUBICLE AND RACKING DEVICES
CONTACT FINGERS
LOADING AND ARCING CONTACTS
OVERCURRENT DEV. BATTERY
(P1-P2) (P2-P3) (P3-P4)
NT
°C
400 400
4W3W A x
SENSOR TAP 400
DELAY
RATING PLUG(R)
SENSOR TAP
POLE 3
RATING PLUG(R)
B.I.
OffON
CURVE DRAWING
GRD. FLT.
INST.
SHORT
LONG
FUNCTION
SHORT
LONG
PICKUP
CONTROL WIRING
POLE TO FRAME
POLE TO POLE
READING READING
CURRENT
MULTIPLE
AS
FOUND
INST.
GRD. FLT.
LINE TO LOAD
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
POLE RESISTANCE - MICRO-OHMS
AS
FOUND
AS
LEFT
AS
LEFT
KD 65K
FUSE CAT. NO.
DIGITRIP RMS 310
SENSOR TAPS
A1 MAIN
CATALOG NO.
SETTINGS AS FOUND
A
SETTINGS AS LEFT FUNCTION PICKUP DELAY CURVE DRAWING
COUNTER READING BEG/END
INSULATION
RESISTANCE
20EQUIPMENT TEMPERATURE
MANUFACTURER
100ms
FIXED
100ms
FIXED
POLE1 POLE2 POLE3MEGOHMS MEGOHMS MEGOHMS
COMMENTS: Secondary Injected w/ Seltronic test kit.
DEFICIENCIES:
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Matthew Moore / Jason RittkoTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0568 / 008183 / P0555
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA117 A1 Pass
480/277VVOLTAGE
FDB3125 FRAME SIZE/RATING PLUG
EATON TYPE FDB 14k
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
125A/125A INT. RATING 14KA @ 480VAC
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
T3 (PRIMARY SIDE)
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
645 645
28.56 28.56
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
687 687
29.45 29.45
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
691 691
30.22 30.22
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
COMMENTS:
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO. FDB3125
EATON TYPE FDB 14k
TYPE
CATALOG NO.
CATALOG NO.
Matthew Moore / Jason RittkoTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0568 / 008183 / P0555
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA117 B1 Pass
480/277VVOLTAGE
KD3400F FRAME SIZE/RATING PLUG
EATON TYPE KD 35k
480/277V
14KA @ 480VACINT. RATING
VOLTAGE
125A/125AFRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
B1 (FEEDER BREAKER) AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS 674 674 625 625 655 655
TIME AT 300% RATED CURRENT IN SECONDS 29.44 29.44 31.12 31.12 28.89 28.89
INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A
ACROSS OPEN POLE
POLE - POLE - GND
2200 2200 2200 2200 2200 2200
2200 2200 2200 2200 2200 2200
400A/400A INT. RATING 35KA @ 480VAC
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
B1 MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
750 750
88.56 88.56
TRIP TRIP
2200 2200
2200 2200
AS FOUND AS LEFT
789 789
89.68 89.68
TRIP TRIP
2200 2200
2200 2200
AS FOUND AS LEFT
811 811
85.25 85.25
TRIP TRIP
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
TEMPERATURE CORRECTION FACTOR TO 20°C, TCFEQUIPMENT TEMPERATURE
INSULATION TEST VOLTAGE
KV
kA
B.I.L. RATING
INTERRUPTING RATING
SERIAL NO.
OTHER NAMEPLATE DATA
AGE
AMPERESTYPE
MOMENTARY FAULT CLOSING AMPS
TYPE OPERATING MECHANISM
VOLTAGE
MANUFACTURER
KVVOLTAGETCC NO.
MAX. AMPS
CAT. NO.
HOLDER
SIZE
TYPE
REFILL ELEMENT TYPE
MANUFACTURER
Matthew Moore / Jerry GordonTESTED BY:
www.abm.comABM Electrical Power Solutions 15610, REVISED 2/18/2020
REVIEWED BY:EQPT. INVENTORY NO. P0568 / 008183
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
LV DISCONNECT SWITCH
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA117 B32-SW-T3 Pass
200CLIP
FRN-R-200 N/A 0.250
FUSETRON
kA
Heavy Duty Safety Switch
N/A
200A
DESCRIPTION
OVERALL CLEANLINESS
MECHANICAL CONNECTIONS
INTERLOCK SYSTEM
INSPECTED CONDITION DESCRIPTION
BLADE ALIGNMENT
TRAVEL STOPS
GROUND CONNECTION
INSPECTED CONDITION
BLADE PENETRATION
CONTACT SEQUENCE
INSULATING MEMBERS
STRUCTURAL MEMBERS
AUXILIARY DEVICES
POLE 3
POLE 2 POLE 3
BLADES CONTACT RES.
IN MICRO-OHMS
RDG.
20°C
N/A
°C
20°C
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
POLE 1
READING
POLE 1 (P1-P2)
20°C READING
POLE 2 (P2-P3)
20°C
POLE 3 (P1-P3)
READING
CLEAN/LUBE
C
L
C
NA
NA
CLEAN/LUBE
NA
NA
NA
NA
NA
FUSE DATA
NAMEPLATE DATA
KVDC
BUSSMAN
N/A
Eaton/Cutler Hammer
240V
MECHANICAL
N/A
N/A
N/A
N/A
LINE TO GROUND CLOSED
LINE TO LOAD & GROUND OPEN
POLE 2
POLE 1
2200 2200
2200 2200
2200 2200
2200 2200
2200 2200
10 11 11
250 251 245
75 77
77 81
TOP OF FUSE TO CLIP
BOTTOM OF FUSE TO CLIP
THRU FUSE
FUSE CLIP RESISTANCE IN MICRO-OHMS
INSULATION TESTS IN MEGOHMS
EQUIPMENT TEMPERATURE
R T = R M K
K sT T
+ T
+ TM
Matthew Moore / Jerry GordonTESTED BY:
www.abm.comABM Electrical Power Solutions 54100, REVISED 2/18/2020
REVIEWED BY:EQPT. INVENTORY NO. 008183
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 45 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA117 MTS-A Pass
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE:
R
R M s
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
450 450 450
467 467 467
497 497 497
0 0 0
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
C/L
C
N/A
MANUFACTURER
NAMEPLATE DATA
CATALOG NO.
WIRING NO.
SYSTEM VOLTAGE AMPACITY
CATERPILLAR SERIAL NO. TSH01899 TYPE MANUAL TRANSFER SWITCH
CTSD 480V 400
N/A CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
DESCRIPTION
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
COMMENTS: Normal position is Switchboard A. Emergency position is Switchboard B.
K
K sT T
+ T
+ TM
Matthew Moore / Jerry GordonTESTED BY:
www.abm.comABM Electrical Power Solutions 54100, REVISED 2/18/2020
REVIEWED BY:EQPT. INVENTORY NO. 008183
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 45 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA117 MTS-B Pass
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE:
R
R M s
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
125 125 125
121 121 121
119 119 119
0 0 0
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
C/L
C
N/A
MANUFACTURER
NAMEPLATE DATA
CATALOG NO.
WIRING NO.
SYSTEM VOLTAGE AMPACITY
CATERPILLAR SERIAL NO. TSH01900 TYPE MANUAL TRANSFER SWITCH
CTSD 480V 400
N/A CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
DESCRIPTION
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
COMMENTS: Normal position is Switchboard A. Emergency position is Switchboard B.
EQPT. LOCATION
ADDRESS
CUSTOMER
TRANSFORMER (<500KVA) TEST
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 12/30/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA117 T-B32--T3 Pass
Matthew Moore / Jerry GordonTESTED BY:
www.abm.comABM Electrical Power Solutions 56710, REVISED 8/5/2019
REVIEWED BY:EQPT. INVENTORY NO. P0568
VISUAL AND MECHANICAL INSPECTION
INSPECT PHYSICAL AND MECHANICAL CONDITION
VERIFY FANS OPERATE (IF APPLICABLE)
INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING
INSPECTION REPORT
FAIL
FAIL
FAIL
PASS
PASS
PASS
INSPECTION REMARKS
NO FANS
1,000
1,000
MINUTES
PRIMARY TO
GROUND
SECONDARY TO
GROUND
PRIMARY TO
SECONDARY
TEST V
0.50
1.00
10.00
P. I.
PHASE B PHASE CCALCTAP
2,200
2,200
2,200
2,200
2,200
2,200
2,200
2,200
2,200
TRANSFORMER TURN RATIO TEST (OPTIONAL)
PASS FAILVERIFY SHIPPING BRACKETS REMOVED
PASS FAILVERIFY THAT RESILIENT MOUNTS ARE FREE
PASS FAILVERIFY THE UNIT IS CLEAN
PASS FAILVERIFY BOLTED ELECTRICAL CONNECTIONS
INSULATION RESISTANCE IN MEGOHMS
PHASE A
/75 N/A
5.42
NAMEPLATE DATA
J06E05558SERIAL NO.
504 492 480 468
1 2 3 4 5
480 VOLTS
GE YR MFR 2006
KVA
IMPEDANCE /AA
WINDING MATERIAL °CCOPPER
CLASSTYPE
B.I.L. RATINGTEMPERATURE RISE
PRIMARY V
TAP POSITION
TAP SETTING
TAP VOLTAGES
DT-3
MANUFACTURER
SECONDARY V 208 WYE
120/
DELTA
432444
3AL
ELECTRICAL TESTS
1,000
WORKING TAP AFP.I. = 10 min/1 min
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO. LD3600WK
CUTLER HAMMER TYPE LD-K
TYPE
CATALOG NO.
CATALOG NO.
TESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO.
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 06/12/2021 TEMPERATURE 68 °F HUMIDITY 20 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA118A MAINY BY PASS (PNL A) Pass
480/277VVOLTAGE
LD3600WK FRAME SIZE/RATING PLUG
CUTLER HAMMER TYPE LD-K
480/277V
?KA @ 480VACINT. RATING
VOLTAGE
600AFRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
MIS (UPS-A) AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS 192 192 174 174 223 223
TIME AT 300% RATED CURRENT IN SECONDS N/A N/A N/A N/A N/A N/A
INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A
ACROSS OPEN POLE
POLE - POLE - GND
2200 2200 2200 2200 2200 2200
2200 2200 2200 2200 2200 2200
600A INT. RATING ?KA @ 480VAC
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MBP (SWBD-B)
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
405 405
N/A N/A
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
435 435
N/A N/A
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
490 490
N/A N/A
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
C
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO. LD3600WK
CUTLER HAMMER TYPE LD-K
TYPE
CATALOG NO.
CATALOG NO.
TESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO.
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 06/12/2021 TEMPERATURE °F HUMIDITY % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA118A MAINY BY PASS (PNL B) Pass
480/277VVOLTAGE
LD3600WK FRAME SIZE/RATING PLUG
CUTLER HAMMER TYPE LD-K
480/277V
?KA @ 480VACINT. RATING
VOLTAGE
600AFRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
MIS (UPS-B) AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS 308 308 284 284 317 317
TIME AT 300% RATED CURRENT IN SECONDS N/A N/A N/A N/A N/A N/A
INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A
ACROSS OPEN POLE
POLE - POLE - GND
2200 2200 2200 2200 2200 2200
2200 2200 2200 2200 2200 2200
600A INT. RATING ?KA @ 480VAC
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MBP (SWBD-A)
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
420 420
N/A N/A
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
380 380
N/A N/A
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
411 411
N/A N/A
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
C
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
N/A
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST VOLTAGE MULTIPLIER, K1 =
EQUIPMENT TEMPERATURE
INSULATION TEST VOLTAGE
KV
kA
B.I.L. RATING
INTERRUPTING RATING
SERIAL NO.
OTHER NAMEPLATE DATA
AGE
AMPERESTYPE
MOMENTARY FAULT CLOSING AMPS
TYPE OPERATING MECHANISM
VOLTAGE
MANUFACTURER
KVVOLTAGETCC NO.
MAX. AMPS
CAT. NO.
HOLDER
SIZE
TYPE
REFILL ELEMENT TYPE
MANUFACTURER
Brad Barnhart / Jack GordonTESTED BY:
www.abm.comABM Electrical Power Solutions 29000, REVISED 9/22/2020
REVIEWED BY:EQPT. INVENTORY NO. P0109, P0027
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
LOADBREAK DISCONNECT TEST
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 10-4-2020 TEMPERATURE 68 °F HUMIDITY 25 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BUILDING 32 MAIN DISCONNECT Pass
100CLAMP
5CLE-100E 5.5
CLE
kA
MVS 2 600
DESCRIPTION
OVERALL CLEANLINESS
MECHANICAL CONNECTION
CUBICLE
INSPECTED CONDITION DESCRIPTION
MAIN CONTACTS
BEARINGS
GROUND CONNECTION
INSPECTED CONDITION
HEATERS
CONTACT SEQUENCE
INSULATING MEMBERS
STRUCTURAL MEMBERS
AUXILIARY DEVICES
POLE 3
POLE 2 POLE 3
CONTACT RESISTANCE
MICRO-OHMS
RDG.
20°C
°C
2.5
4,300.000
20°C
32.00
32 31
31.0029.00
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
POLE 1
TOP OF FUSE TO CLIP
BOTTOM OF FUSE TO CLIP
THRU FUSE
READING
3,250.00
20°C
3,250.000
READING
3,925.00
20°C
3,925.000
READING
4,300.00
CLEAN/LUBE
C
C
CLEAN/LUBE
C/L
FUSE DATA
NAMEPLATE DATA
INSULATION TESTS
FUSE CLIP RESISTANCE
KVDC K2 = (K1) (TCF)
EATON
N/A
EATON
5KV
SPRING 60
K2
1.000
RANGE
MULTIPLIER
1.000
LINE TO GROUND CLOSED
LINE TO LOAD & GROUND OPEN
6,590
7,100
6,850
POLE 2
POLE 1
OVER POTENTIAL TEST
TEST TIME A PHASE
B PHASE
C PHASE
B PHASE
MICRO-AMP LEAKAGE
PASS FAIL@ KVDC
POLE1 (P1-P2) POLE3POLE2 (P2-P3) (P1-P3)
COMMENTS: Closed insulation test not completed due to interlocked transfer switch.
Brad Barnhart / Jack GordonTESTED BY:
www.abm.comABM Electrical Power Solutions 54560, REVISED 7/16/2019
REVIEWED BY:EQPT. INVENTORY NO. P0109, P0027
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MANUAL TRANSFER SWITCH TEST REPORT
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 10-4-2020 TEMPERATURE 68 °F HUMIDITY 25 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BUILDING 32 SELECTOR SWITCH Pass
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
INSPECTED CONDITION CLEAN/LUBE
CU ALSIZE:
POLE
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
NA
C/L
MANUFACTURER
NAMEPLATE DATA
CATALOG NO. SYSTEM VOLTAGE AMPACITY
EATON SERIAL NO. TYPE MSV
4160 V 1200
DESCRIPTION
°C
N - G
READING POLE
CONTACT RESISTANCE
POLE
A - G
POLE
A - B
B - C
C - A
B - G
INSULATION RESISTANCE 1,000 Vdc
READING
READINGS IN
POLE
A - G
POLE
A - B
B - C
C - A
B - G
READING
READINGS IN
C - G
B
C
N
READING
READING IN MICRO-OHMS
TEMPERATURE CORRECTION FACTOR 20°C, TCFEQUIPMENT TEMPERATURE
LOAD CONDUCTOR NO./ PHASE: 1/PHASE
A
A - N
20°C
B - N
C - G C - N
20°C READING
N - G
MEGOHMS
20°C
NORMAL / PREFERRED
B
READING
A - N
20°C
B - N
C - N
20°C POLE READING 20°C
MEGOHMS
C
N
EMERGENCY / ALTERNATE
POLE
READING20°C
NORMAL / PREFERRED
A
29 29
20°C
EMERGENCY / ALTERNATE
COMMENTS: Contact Resistance preferred Source Readings are for Ckt. #15; Alternate Source Readings are for Ckt. # 11.
Insulation test not completed due to connected equipment.
MANUAL TRANSFER SWITCH TEST REPORT
12PAGE
www.abm.comABM Electrical Power Solutions 54560, REVISED 7/16/2019
GRD. FLT.
GRD. FLT.
CU
THERMAL MEMORY
4W3W
AL
FRAME SIZE(F)
Matthew Moore / Jason CatleyTESTED BY:
www.abm.comABM Electrical Power Solutions 15055, REVISED 12/28/2019
REVIEWED BY:EQPT. INVENTORY NO. P0568 / 010023 / 8063
BREAKER TYPE
TRIP UNIT TYPE
N/A
CUBICLE CODE
SN / SO NO.
MOUNTING
TARGETS
1200A
20°C
INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE
SIZE
A=
AA
x
A
A
A
A = A
AS
LEFT
TEST
AMPERES
POLE 1
FUNCTION
INSTANTANEOUS
SHORT TIME
LONG TIME
POLE 2
AS
FOUND
TIME BAND
MINIMUM
IPU
GFPU
VOLTAGE DROP @ LONG TIME TEST CURRENT
LTPU
STPU
GROUND FAULT
READING
POLE 3POLE 2POLE 1
20°C
LOAD CONDUCTOR NO.
READING 20°C 20°C
EATON CUTLER HAMMER
MAXIMUM
20°C
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
LOW VOLTAGE
POWER CIRCUIT BREAKER TEST
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 11/05/2020 TEMPERATURE 65 °F HUMIDITY 40 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION GENERATOR…