This document is a Customer Field Service Report from ABM Electrical Power Solutions detailing electrical equipment testing performed in April 2020 at the VA Pittsburgh Healthcare Center. The report documents maintenance testing of electrical power equipment across multiple buildings, specifically noting several critical findings: transformers in Buildings 63-68 have power factor test results below Doble Standards and require replacement, and multiple buildings (69 and 70) have equipment with electrical component issues such as open contacts, non-operational breaker functions, and cracked equipment parts.
The related federal contract opportunity is a Request for Quote (RFQ) for Triennial Annual Electric Inspection, solicitation number 36C24426Q0055, issued by the Department of Veterans Affairs. The procurement is 100% set aside for Service-Disabled Veteran-Owned Small Business, with a NAICS code of 811210 and a size standard of $34.0M. Key dates include a January 5, 2026 deadline for questions and a January 8, 2026 submission deadline for quotes. The solicitation seeks FY26 Triennial Breaker Inspections for the VA Network Contracting Office 4 in Philadelphia, PA, with all communications to be directed to Contract Specialist Allan Tabliago.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Atch 7.Heinz_June and July 2020_Final Report.pdf | ||
| Atch 4.UD August 2020-July 2021_Final Report.pdf | ||
| 36C24426Q0055 0002_1.docx | DOCX document | |
| Atch 6.Heinz_May 2020_Final Report.pdf | ||
| Atch 3.Equipment List - Breaker Testing List UD- April 2015.xlsx | XLSX spreadsheet | |
| 36C24426Q0055 0001_1.docx | DOCX document | |
| Atch 2.UD Elect and Arc Flash Study.pdf | ||
| Atch 1.HZ Elect and Arc Flash study 2023 reduced.pdf | ||
| WD 2015-4235 R32 20251203.pdf | ||
| 36C24426Q0055_1.docx | DOCX document | |
| VAAR 852.219-75 VA Notice of Limitations on Subcontracting.pdf | ||
| 36C24426Q0055 Triennial Inspectiona.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER
ADDRESS
CUSTOMER
FIELD SERVICE REPORT
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE
Description:
In April, 2020 ABM Electrical Power Solutions Field Personnel were at Department of Veterans Affairs, VA Pittsburgh Healthcare, (Heinz) located in Pittsburgh, PA to perform testing of electrical power equipment.
Engineering Evaluation:
Testing was performed in accordance with the International Electrical Testing Association's Maintenance Testing Specifications and project specifications. Fluid Analysis was performed in accordance with IEEE Specifications.
Scope of Work:
As part of an ongoing project, this report represents the maintenance testing performed in April 2020.
Test Results / Comments:
Building #63-68 (Exterior), B63 & 68-T1; The power factor test results are below Doble Standards. Doble's engineer recommends replacing the transformer at the earliest convenience.
Building #69, 1B116, MSB, Spare-position #11; B-Phase has an open contact.
Building #69, MSB, Spare-position #8; B-Phase has an open contact.
Building #70, BA019, MSA, PNL-NH1A1; No operation on long time function.
Building #70, BA019A, ATS-LA; Plastic finger cluster divider is cracked on top side of ATS.
Building #70, BA019A, MSQ, ATS-LA; No operation on long time and short time functions.
Building #71, GA102, 71-DSBL, Breaker Spare (2nd section, position 8); No trip on long time and instantaneous functions.
All other test results are acceptable per NETA - MTS Standards. All equipment was left in Satisfactory Operational Condition.
This report certifies that the above equipment has been tested in compliance with recognized standards or for safe use in a specific manner, or in accordance with
Federal, State or Municipal regulations. The report is accurate and true to the best of our knowledge and belief. All equipment used in making physical determinations is accurate and bears recent and direct traceability to the National Institute of Standards and Technology. (NIST).
1/21/2022
By:
Josh Schoedel www.abm.comABM Electrical Power Solutions REVISED 1/21/2022
ABM Electrical Power Solutions 317 Commerce Park Drive Cranberry Township, PA 16066
Project Manager
Equipment Tested Job #86301680 www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
1PAGE
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
115910- MCB - 3 in 1 REV.1 (4) - Pass (4)
(HEINZ) BLDG #32 1ST FLOOR CORRIDOR PANEL B
215910- MCB - 3 in 1 REV.1 (5) - Pass (5)
(HEINZ) BLDG #32 2ND FLOOR CORRIDOR PANEL C
315910- MCB - 3 in 1 REV.1 (2) - Pass
(HEINZ) BLDG #32 BA106 DP
415910- MCB - 3 in 1 REV.1-MAIN
(HEINZ) BLDG #32 BA106 DP
515910- MCB - 3 in 1 REV.1 -(1) Pass - Pass
(HEINZ) BLDG #32 BA106 DP
615910- MCB - 3 in 1 REV.1 (3) - Pass
(HEINZ) BLDG #32 BA106 DP
715910- MCB - 3 in 1 REV.1 (5) - Pass (5)
(HEINZ) BLDG #32 BA109 32EA
854100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) ATS-B32
956900 - MET TWO-WINDING TRANSFORMER REV.1
(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) B32-T1
11TJH2B DGA - L710356TLLA-Tran
(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) B32-T1
13TJH2B Fluid - L710356TLLA-Tran
(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) B32-T1
1415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) GEN BREAKER
1515910- MCB - 3 in 1 REV.1 (3) - Pass (2)
(HEINZ) BLDG #32 GND FLOOR CORRIDOR PANEL A
1615910- MCB - 3 in 1 REV.1 (3) - Pass (3)
(HEINZ) BLDG #32 GND FLOOR MECH RM PANEL NB
1756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #49 1A168 B49-T2 (MDP)
1856710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #49 1A168 B49-T3 (EB-RA)
1956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #49 1A168 B49-T4 (EB-RB)
2015910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #49 1A168 EB-HB
2115910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #49 1A168 EB-MDP
2215910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #49 1A168 EB-MDP
2315910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #49 1A168 EB-RA (SEC 1)
2415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #49 1A168 EB-RA (SEC 2)
2515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #49 1A168 EB-RB
2615610 - LV DISCONNECT SWITCH
(HEINZ) BLDG #49 1A168 SW-B49-T2 (SEC)
2715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #49 1D100 PANEL D
2856710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #49 1D106 B49-T5 (PR-L)
2915910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #49 1D106 PR-H
2PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
3015910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #49 1D106 PR-L
3115910- MCB - 3 in 1 REV.1 (4)
(HEINZ) BLDG #49 WH MECH RM (EXTERIOR) MDP
3215910- MCB - 3 in 1 REV.1 (3)
(HEINZ) BLDG #49 WH MECH RM (EXTERIOR) MDP
3356710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #53 BLDG #53 (INTERIOR) B53-T-G
3415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #53 BLDG #53 (INTERIOR) G (LEFT)
3515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #53 BLDG #53 (INTERIOR) GA (LEFT)
3615910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #63 BLDG #63 (INTERIOR) VARIOUS
3715910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #63 BLDG #63 (INTERIOR) VARIOUS
3856700 - TRANSFORMER MAINTENANCE TEST (3)
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B63&68-T1
3956700 - TRANSFORMER MAINTENANCE TEST
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B64&65-T1
40TJH2B DGA - 07J835066-Tran
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B64&65-T1
42TJH2B Fluid - 07J835066-Tran
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B64&65-T1
4356700 - TRANSFORMER MAINTENANCE TEST (2)
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B66&67-T1
44TJH2B DGA - 07J835076-Tran
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B66&67-T1
46TJH2B Fluid - 07J835076-Tran
(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B66&67-T1
4715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #64 BLDG #64 (INTERIOR) VARIOUS
4815910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #64 BLDG #64 (INTERIOR) VARIOUS
4915910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #65 BLDG #65 (INTERIOR) VARIOUS
5015910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #66 BLDG #66 (INTERIOR) VARIOUS
5115910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #67 BLDG #67 (INTERIOR) VARIOUS
5215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #68 BLDG #68 (INTERIOR) VARIOUS
5354101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass
(HEINZ) BLDG #69 1B115 ATS-EQNE
5554101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass
(HEINZ) BLDG #69 1B115 ATS-LSNE
5756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #69 1B115 B69-T2
5815910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #69 1B115 EQNE
3PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
5915610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #69 1B115 SW-B69ATS-EQNE
6015610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #69 1B115 SW-B69ATS-LSNE
6115610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #69 1B115 SW-B69T2 (PRIM)
6215610 - LV DISCONNECT SWITCH - Pass
(HEINZ) BLDG #69 1B115 SW-B69T2 (SEC)
6315065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LF)
(HEINZ) BLDG #69 1B116 MSB
6415065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-2LB)
(HEINZ) BLDG #69 1B116 MSB
6515065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LB)
(HEINZ) BLDG #69 1B116 MSB
6615065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-EQNE)
(HEINZ) BLDG #69 1B116 MSB
6715065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE-POSITION 10)
(HEINZ) BLDG #69 1B116 MSB
6815065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-2LC)
(HEINZ) BLDG #69 1B116 MSB
6915065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-1SF)
(HEINZ) BLDG #69 1B116 MSB
7015065 - LOW VOLT. PWR. CKT. BKR. TEST (ELEVATOR #1)
(HEINZ) BLDG #69 1B116 MSB
7115065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-2SF)
(HEINZ) BLDG #69 1B116 MSB
7215065 - LOW VOLT. PWR. CKT. BKR. TEST (ELEVATOR #3)
(HEINZ) BLDG #69 1B116 MSB
7315065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LD)
(HEINZ) BLDG #69 1B116 MSB
7415065 - LOW VOLT. PWR. CKT. BKR. TEST (ELEVATOR #2)
(HEINZ) BLDG #69 1B116 MSB
7515065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-2LA)
(HEINZ) BLDG #69 1B116 MSB
7615065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE-POSITION 7)
(HEINZ) BLDG #69 1B116 MSB
7715065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LA)
(HEINZ) BLDG #69 1B116 MSB
7815065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE-POSITION 11)
(HEINZ) BLDG #69 1B116 MSB
7915065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE-POSITION 8)
(HEINZ) BLDG #69 1B116 MSB
8015065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-1RF)
(HEINZ) BLDG #69 1B116 MSB
8115500 - BOLTED PRESSURE SWITCH TEST (MAIN)
(HEINZ) BLDG #69 1B116 MSB
8256900 - MET TWO-WINDING TRANSFORMER REV.1 (3)
(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) B69-T1
84TJH2B DGA - 1450000870-Tran
(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) B69-T1
4PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
86TJH2B Fluid - 1450000870-Tran
(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) B69-T1
8715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 1A139 70-NH1A1
8815910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 1A139 70-NL1A1 (SEC 1)
8956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 1A139 B70-T8 (NL1A1)
9015910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 1A167 70-NL1B1 (SEC 1)
9156710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 1A167 B70-T7 (NL1B1)
9215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 2A238 70-NH2A1
9315910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 2A238 70-NL2A1 (SEC 1)
9456710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 2A238 B70-T10 (NL2A1)
9515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 2A261 70-NH2B2
9615910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 2A261 70-NH2B2
9756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 2A261 B70-T9 (NL2B1)
9815910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 2A261 NL2B1
9956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 BA019 B70-T2 (NLBA2)
10015065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)
(HEINZ) BLDG #70 BA019 MSA
10115065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH2A1)
(HEINZ) BLDG #70 BA019 MSA
10215065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH1A1)
(HEINZ) BLDG #70 BA019 MSA
10415065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH2B2)
(HEINZ) BLDG #70 BA019 MSA
10515065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NHBA2)
(HEINZ) BLDG #70 BA019 MSA
10615065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-LA)
(HEINZ) BLDG #70 BA019 MSA
10715065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-QA)
(HEINZ) BLDG #70 BA019 MSA
10815065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH1B1)
(HEINZ) BLDG #70 BA019 MSA
10915065 - LOW VOLT. PWR. CKT. BKR. TEST (MCCN)
(HEINZ) BLDG #70 BA019 MSA
11015065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH2B1)
(HEINZ) BLDG #70 BA019 MSA
11115910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 BA019 NHBA2
5PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
11215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 BA019 NLBA2
11354101 - AUTOMATIC TRANSFER SWITCH TEST W/ INS. RES.
(HEINZ) BLDG #70 BA019A ATS-LA
11554101 - AUTOMATIC TRANSFER SWITCH TEST W/ INS. RES.
(HEINZ) BLDG #70 BA019A ATS-QA
11756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 BA019A B70-T3 (QLBA1)
11856710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 BA019A B70-T4 (QL2B1)
11956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 BA019A B70-T5 (LL1A2)
12056710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #70 BA019A B70-T6 (LLBA1)
12115065 - LOW VOLT. PWR. CKT. BKR. TEST (BLDG 69) - Pass - Pass
(HEINZ) BLDG #70 BA019A MSQ
12215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-LA)
(HEINZ) BLDG #70 BA019A MSQ
12415065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-QA)
(HEINZ) BLDG #70 BA019A MSQ
12515910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #70 BA019A QHBA1
12615065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #70 BA019B GEN BREAKER
12756900 - MET TWO-WINDING TRANSFORMER REV.1 (2)
(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) B70-T1
129TJH2B DGA - 07J830296-Tran
(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) B70-T1
131TJH2B Fluid - 07J830296-Tran
(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) B70-T1
13215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA102 71-DPBH
13315065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #71 GA102 71-DSBL
13415910- MCB - 3 in 1 REV.1 (5)
(HEINZ) BLDG #71 GA102 71-DSBL
13515910- MCB - 3 in 1 REV.1 (3)
(HEINZ) BLDG #71 GA102 71-DSBL
13615910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA102 71-DSBL
13715910- MCB - 3 in 1 REV.1 (8)
(HEINZ) BLDG #71 GA102 71-DSBL
13815910- MCB - 3 in 1 REV.1 (4)
(HEINZ) BLDG #71 GA102 71-DSBL
13915910- MCB - 3 in 1 REV.1 (6)
(HEINZ) BLDG #71 GA102 71-DSBL
14015910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #71 GA102 71-DSBL
14115910- MCB - 3 in 1 REV.1 (7)
(HEINZ) BLDG #71 GA102 71-DSBL
6PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
14215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA102 71-EQBLC
14315065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-EQ)
(HEINZ) BLDG #71 GA102 71-MSG
14415065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL 71-DPBH) - Pass - Pass
(HEINZ) BLDG #71 GA102 71-MSG
14515065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE) (1C)
(HEINZ) BLDG #71 GA102 71-MSG
14615065 - LOW VOLT. PWR. CKT. BKR. TEST (71-1HB 71-2HB)
(HEINZ) BLDG #71 GA102 71-MSG
14715065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL 71-BHA) - Pass
(HEINZ) BLDG #71 GA102 71-MSG
14815065 - LOW VOLT. PWR. CKT. BKR. TEST (71-1HC 71-2HC)
(HEINZ) BLDG #71 GA102 71-MSG
14915065 - LOW VOLT. PWR. CKT. BKR. TEST (DSBL) (2B) - Pass
(HEINZ) BLDG #71 GA102 71-MSG
15015065 - LOW VOLT. PWR. CKT. BKR. TEST (71-1HA 71-2HA)
(HEINZ) BLDG #71 GA102 71-MSG
15115065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-ELEV)
(HEINZ) BLDG #71 GA102 71-MSG
15215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-LS)
(HEINZ) BLDG #71 GA102 71-MSG
15315065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN) - Pass
(HEINZ) BLDG #71 GA102 71-MSG
15415065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE) (1D)
(HEINZ) BLDG #71 GA102 71-MSG
15515065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-CC)
(HEINZ) BLDG #71 GA102 71-MSG
15615065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE) (3B)
(HEINZ) BLDG #71 GA102 71-MSG
15756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #71 GA102 B71-T-DSBL
15856710 - TRANSFORMER DRY MAINTENANCE (<500KVA) (2)
(HEINZ) BLDG #71 GA102 B71-T-EQBLC
15915610 - LV DISCONNECT SWITCH (2)
(HEINZ) BLDG #71 GA102 SW-B71-EQBH-B
16015610 - LV DISCONNECT SWITCH
(HEINZ) BLDG #71 GA102 SW-B71-T-EQBLC
16115910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA117 71-CCBHA
16215910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA117 71-CCBLA
16315910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #71 GA117 71-CCBLA
16415910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA117 71-EBHA
16515910- MCB - 3 in 1 REV.1 (9) (2)
(HEINZ) BLDG #71 GA117 71-EBHA
16615910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA117 71-EQBHA
7PAGE
www.abm.comABM Electrical Power Solutions REVISED 2/3/2016
PAGE
NO.Asset
Equip IDSubstationPlant
Department of Veterans AffairsCustomer
VA Pittsburgh Healthcare CenterOwner
16715910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA117 71-EQBLA
16815910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA117 71-EVBHA
16915910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA117 71-LSBHA
17015910- MCB - 3 in 1 REV.1
(HEINZ) BLDG #71 GA117 71-LSBLA
17115910- MCB - 3 in 1 REV.1 (2)
(HEINZ) BLDG #71 GA117 71-LSBLA
17254101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass
(HEINZ) BLDG #71 GA117 ATS-CC
17454101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass
(HEINZ) BLDG #71 GA117 ATS-ELEV
17654101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass
(HEINZ) BLDG #71 GA117 ATS-EQ
17854101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass
(HEINZ) BLDG #71 GA117 ATS-LS
18056710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #71 GA117 B71-CCBLA
18156710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #71 GA117 B71-EQBLA
18256710 - TRANSFORMER DRY MAINTENANCE (<500KVA)
(HEINZ) BLDG #71 GA117 B71-LSBLA
18315065 - LOW VOLT. PWR. CKT. BKR. TEST
(HEINZ) BLDG #71 GA117 GEN BREAKER
18454100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.
(HEINZ) BLDG #71 GA117 MTS-1
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION 1ST FLOOR CORRIDOR PANEL B Pass
240VOLTAGE
CAH315W FRAME SIZE/RATING PLUG
WESTINGHOUSE TYPE CAH3
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
150 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
1 POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
551 551
21.74 21.74
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
478 478
19.38 19.38
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
524 524
27.99 27.99
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
COMMENTS:
DEFICIENCIES:
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION 2ND FLOOR CORRIDOR PANEL C Pass
240VOLTAGE
CAH3150W FRAME SIZE/RATING PLUG
WESTINGHOUSE TYPE CAH3
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
150 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
1 POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
488 488
27.48 27.48
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
437 437
28.55 28.55
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
570 570
27.17 27.17
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO. JD3250F
WESTINGHOUSE TYPE JD25K
WESTINGHOUSE TYPE JD25K
JD3250FCATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA106 DP Pass
240VOLTAGE
JD3250F FRAME SIZE/RATING PLUG
WESTINGHOUSE TYPE JD25K
65KAINT. RATING
VOLTAGE
250/200FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
ATS AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS 492 492 503 503 479 479
TIME AT 300% RATED CURRENT IN SECONDS 57.38 57.38 79.22 79.22 56.28 56.28
INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A
ACROSS OPEN POLE
POLE - POLE - GND
2200 2200 2200 2200 2200 2200
2200 2200 2200 2200 2200 2200
250/200 INT. RATING 65KA
AHU-1
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
1 POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT
403 403
69.45 69.45
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
467 467
73.63 73.63
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
487 487
59.07 59.07
N/A N/A
2200 2200
2200 2200
250/250 65KA
MANUFACTURER
PNL C
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
450 450
86.23 86.23
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
488 488
103.5 103.5
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
467 467
70.95 70.95
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
N/A
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0550/P0521/010023
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 72 °F HUMIDITY 30 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA106 DP Pass
240VOLTAGE
LCA3600F FRAME SIZE/RATING PLUG
WESTINGHOUSE TYPE LCA
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
600/500 INT. RATING 42KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
118 118
33.41 33.41
TRIP TRIP
2200 2200
2200 2200
AS FOUND AS LEFT
123 123
33.41 33.41
TRIP TRIP
2200 2200
2200 2200
AS FOUND AS LEFT
166 166
33.41 33.41
TRIP TRIP
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
COMMENTS: Used Westinghouse Seltronic secondary injection test set.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO. JD3250F
WESTINGHOUSE TYPE JD25K
WESTINGHOUSE TYPE JD25K
JD3250FCATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA106 DP Pass
240VOLTAGE
JD3250F FRAME SIZE/RATING PLUG
WESTINGHOUSE TYPE JD25K
65KAINT. RATING
VOLTAGE
250/200FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
PNL A AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS 395 395 437 437 483 483
TIME AT 300% RATED CURRENT IN SECONDS 75.24 75.24 78.92 78.92 72.92 72.92
INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A
ACROSS OPEN POLE
POLE - POLE - GND
2200 2200 2200 2200 2200 2200
2200 2200 2200 2200 2200 2200
250/200 INT. RATING 65KA
PNL NA/NB
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
1 POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT
497 497
65.55 65.55
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
518 518
67.61 67.61
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
428 428
69.38 69.38
N/A N/A
2200 2200
2200 2200
250/225 65KA
MANUFACTURER
PNL B
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
424 424
68.85 68.85
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
459 459
84.77 84.77
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
464 464
61.44 61.44
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
N/A
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO. FD3225
CUTLER-HAMMER TYPE FD 35K
TYPE
CATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA106 DP Pass
240VOLTAGE
HFD3125 FRAME SIZE/RATING PLUG
CUTLER-HAMMER TYPE HFD 65K
65KAINT. RATING
VOLTAGE
225FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
ELEV AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS 470 470 443 443 486 486
TIME AT 300% RATED CURRENT IN SECONDS 38.24 38.24 36.15 36.15 29.57 29.57
INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A NA N/A NA N/A NA
ACROSS OPEN POLE
POLE - POLE - GND
2200 2200 2200 2200 2200 2200
2200 2200 2200 2200 2200 2200
125 INT. RATING 100KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
1 POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
PNL PP32B1
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
980 980
44.37 44.37
N/A NA
2200 2200
2200 2200
AS FOUND AS LEFT
770 770
45.58 45.58
N/A NA
2200 2200
2200 2200
AS FOUND AS LEFT
992 992
52.03 52.03
N/A NA
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BA109 32EA Pass
240VOLTAGE
JD3250F FRAME SIZE/RATING PLUG
WESTINGHOUSE TYPE JD 25K
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
250/200 INT. RATING 65KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
1 POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
497 497
135.45 135.45
TRIP TRIP
2200 2200
2200 2200
AS FOUND AS LEFT
464 464
122.31 122.31
TRIP TRIP
2200 2200
2200 2200
AS FOUND AS LEFT
528 528
131.68 131.68
TRIP TRIP
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
EQUIPMENT TEMPERATURE
R T = R M K
K sT T
+ T
+ TM
Matthew Moore / Keith SpearTESTED BY:
www.abm.comABM Electrical Power Solutions 54100, REVISED 2/18/2020
REVIEWED BY:EQPT. INVENTORY NO. P0098
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 04/17/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BLDG #32 (EXTERIOR) ATS-B32 Pass
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE:
R
R M s
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
157 157 157
161 161 161
154 154 154
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
NA
C
C
NA
C
C
C
NA
C/L
NA
NA
NA
N/A
MANUFACTURER
NAMEPLATE DATA
CATALOG NO.
WIRING NO.
SYSTEM VOLTAGE AMPACITY
SPECTRUM SERIAL NO. K58176 TYPE AUTOMATIC TRANSFER SWITCH
N/A 208V 225A
N/A CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
DESCRIPTION
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
Matthew Moore / Keith SpearTESTED BY:
www.abm.comABM Electrical Power Solutions 56900, REVISED 8/6/2019
REVIEWED BY:EQPT. INVENTORY NO. P0580 / P0082 / P0041
RAIN
INDOOR OUTDOOR
ENVIRONMENTAL DATA
WEATHER CONDITIONS %AMBIENT TEMPERATURE 876degC
CONTROLS
CONTROL VOLTAGE
GOOD POOR EXPLAIN: NO FANS
GOOD FAIR POOR
GOOD FAIR POOR
GOOD FAIR
GOOD FAIR POOR
FAIR
POOR
VOLTS
EXPLAIN:
EXPLAIN:
EXPLAIN:
EXPLAIN:
LIQUID GAS AIR NONE DETECTED DESCRIBE:
TRANSFORMER LOCATED OUTSIDE OF METAL CLAD BLDG #55.
PAINT
GROUNDS
DESCRIBE OPERATING ENVIRONMENT
LEAKS
FANS
CONNECTIONS
VISUAL INSPECTION
YES
HUMIDITY
1.98 130
NAMEPLATE DATA
L710356TLLASERIAL NO.
4,264 4,160 4,056
1 2 3 4 5
GENERAL ELECTRIC YR MFR N/A
KVA
IMPEDANCE
3,952
CAPACITY
WYE
TAP VOLTAGES
DELTA
DELTA
MANUFACTURER
WYE
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
TWO-WINDING TRANSFORMER
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 04/17/2020 TEMPERATURE 42 °F HUMIDITY 87 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BLDG #32 (EXTERIOR) B32-T1 Pass
/ OA FA FOA FOW OW FOW
OIL
CLASS
PRIMARY
SECONDARY
VOLTS
SINGLE PHASE
SINGLE PHASE
ALUMINUM COPPER
ALUMINUM COPPER
WINDING MATERIALCONNECTIONS
/4,160
/208 120
4,368
TAP POSITION
4,056 / VOLTS PERCENT )(
LIQUID-FILLED GAS-FILLED AIR FIELD SAMPLE YES NO
SILICONE OIL AIR RTEMP GASWESCOLPCB
GALLONSPSI
TEMPERATURE RISE
TEMPERATURE GAUGE
WINDING TEMPERATURE
°C
°C
58 °C
°C
FAN SET TO °C
LOCATED ON POLE PAD
MAXIMUM TEMPERATURE INDICATOR RESET TO
TAP POSITION LEFT
INSULATING MEDIUM
MEDIUM TYPE
BELOW NORMALMEDIUM LEVEL
MAXIMUM TEMPERATURE INDICATOR
PRESSURE CAPACITY
°C
GALLONS TYPE CATALOG NUMBER N/A
TWO-WINDING TRANSFORMER
10PAGE
www.abm.comABM Electrical Power Solutions 56900, REVISED 8/6/2019
404.000 403.000 403.000 528.0000 517.0000 521.0000
1 2 3 4 5
WINDING
TESTED
H1-H2 H2-H3 H3-H1 X0-X1 X0-X2 X0-X3
WINDING RESISTANCE TESTS
ARE WINDING POLARITIES AS PER NAMEPLATE? YES
IF NO, DESCRIBE:
TAP POSITION
H WINDING X WINDINGNO MicrohmsWINDING RESISTANCE UNITS: Milliohms
DEMAGNETIZATION COMPLETE YES NO
PRIMARY SECONDARY
INSULATION RESISTANCE TEST
TESTED
PRIMARY TO
SECONDARY AND GROUND
SECONDARY TO
PRIMARY AND GROUND
VOLTAGE
(VOLTS DC)
2,500
1,000
0.5 MINUTE
4,150
1,055
1.0 MINUTE
4,870
1,220
10 MINUTES
7,020
1,740
MINIMUM
(MEGOHMS)
1,000
(MEGOHMS)
YES NO
YES NO
DIELECTRIC ABSORPTION: (RATIO OF 1 MINUTE TO 0.5 MINUTE RESULT)
POLARIZATION INDEX: (RATIO OF 10 MINUTE RESULT TO 1 MINUTE RESULT)
PRIMARY
WINDING
1.174
1.442
SECONDARY
WINDING
1.156
1.426
ACCEPTABLE
YES NO
YES NO
Windings TEST RESISTANCE RECOMMENDED
ACCEPTABLE
TEMPERATURE CORRECTION FACTOR: AIR MEDIUM TEMPERATURE WAS 5degC MULTIPLY RESULT BY CORRECTION FACTOR 0.36
PASS/FAIL
H2-H3
Calculated PASS/FAIL Calculated
4,264
4,160
4,056 33.842
3,952
33.8460.12 % PASS 0.14 % PASS 0.12 %
PASS/FAIL
PASS
TO
% DEVIATION
H3-H1
33.840
Measured
TO
% DEVIATIONMeasured
TO
% DEVIATIONMeasuredCalculated
RATIO
36.400
35.533
34.667
33.800
TAP
NAMEPLATE
VOLTAGE
YES NO
H1-H2
TRANSFORMER TURNS RATIO TESTS
ASTERICK (*) DENOTES RESULTS NOT WITHIN TOLERANCE
4,368
TURNS RATIO RESULTS: ARE THEY WITHIN +/- 0.5% OF ADJACENT PHASES AND/OR CALCULATED RATIO.
32.933
Calculated
B32-T1 L710356TLLA
TwoWindingTransformerReport Source
4/17/2020 5:53:22 PMSession Test Date
Nameplate - Two-winding Transformer Company ABM Serial Number L710356TLLA
Location VA HOSPITAL - HEINZ Special ID B32-T1
Division PITTSBURGH Circuit Designation B32-T1
Manufacturer General Electric Configuration D_Y
Year Manufactured Tank Type Sealed
Mfr Location U.S.A. Coolant Oil
Phases Three Class OA
Oil Volume 130 UG BIL 60 kV
Weight 3350 LB kV 4.16, 0.21 VA Rating 300, *, *, *, kVA
Administration Test Date 4/17/2020 Test Time: 5:53 PM Weather Rain
Air Temperature 65.8°C Apparatus Temperature
20°C Humidity 72.674 %
Tester MM / KS Work Order 86301680 Date Last Tested
Verified Test Set Type M4100 Date Retested
Verification Date 4/17/2020 Set Top Serial # 70101514 Reason Routine
Last Sheet # Test Set Model M4100 Travel Time
Purchase Order Ins. Book # Duration
Copies Sheet # Crew Size 2
Overall Tests Insulation Test kV mA Watts PF*TCF
Corr Fctr
Cap (pF) FRANK™ Manual
1 CH+CHL 2.400 28.649 2.583 0.888 0.994 7599.144
2 CH 2.401 1.894 0.133 0.685 0.994 502.259 Good Good
3 CHL
(Measured)
2.400 26.756 2.452 0.903 0.994 7096.908 Good Good
4 CHL * 26.756 2.450 0.910 0.994 7096.885 Good Good
5 CL+CHL 0.250 42.883 3.538 0.810 0.994 11374.654
6 CL 0.250 16.165 1.032 0.622 0.994 4287.863 Good Good
7 CHL
(Measured)
0.250 26.729 2.401 0.885 0.994 7089.766 Good Good
8 CHL * 26.718 2.505 0.932 0.994 7086.791 Good Good
Winding without Attached Bushing Calculation
CH-C1 CH' 1.894 0.133 0.685 0.994 502.259
CL-C1 CL' 16.165 1.032 0.622 0.994 4287.863
Report generated on 4/17/2020 6:35:50 PM 1 - 2
FRANK™ Message 2 (Good) - Power factor results are acceptable compared to the limits.
For this apparatus, the low power factor limit is 0.1%, the degraded limit is 1.0%, and the high limit is 1.5%.
The relative humidity is above 70%, which is likely cause some increases in measured watts and power factor. If higher than expected results are obtained, clean and dry all porcelain surfaces before retesting, using heat if necessary.
3 (Good) - Power factor results are acceptable compared to the limits.
4 (Good) - The calculated values compare to the measured values.
6 (Good) - Power factor results are acceptable compared to the limits.
7 (Good) - Power factor results are acceptable compared to the limits.
8 (Good) - The calculated values compare to the measured values.
Excitation Current & Losses Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 5 * * 4 4 *
H1 H2 H2 H3 H3 H1
Winding :
Tap Position
(s)
Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
HV: 4 2.4 43.347 117.268 L 60.702 117.268 L 55.224 113.678 L Good Good
Report generated on 4/17/2020 6:35:50 PM 2 - 2
Equipment Type:
Model:
Bank & Phase: 4160-208
Breathing:
Cooling:
Fluid Volume:
Fluid Type:
VA-Heinz
B22 T1 3 Ph 300 KVA
4105690
DISSOLVED GAS ANALYSIS
Page: 11
L710356TLLA
Location: Year of Mfg.:
86301680 kV Rating:
B32-T1Position:BLDG #32 (EXTERIOR)Substation:
86301680
PO Number:Report Number:
5/4/2020 Job Number:
Serial Number:
Manufacturer:
Transformer
GE
ABM Electrical Power Solutions, LLC
Report Date:
Cranberry Township, PA 16066 Mineral Oil
317 Commerce Park Drive
Laboratory No.:
Container No.:
Temperature:
Methane (ppm):
Ethane (ppm):
Ethylene (ppm):
Acetylene (ppm):
Carbon Monoxide (ppm):
Carbon Dioxide (ppm):
Nitrogen (ppm):
Oxygen (ppm):
TDCG Rate (ppm/day):
TDCG (gallons):
TDHHG (ppm):
ETCG (% in blanket):
C2H2 / C2H4:
C2H2 / CH4:
C2H6 / C2H2:
C2H4 / C2H6:
CO2 / CO:
Rodgers Ratios (4):
Heat Index:
Doernenburg Ratios:
CO2 / CO:
Dissolved Gas Diagnostics
4/17/2020
All gases are within normal limits
Not in table
Not in table.
Higher than normal temperature in insulation
0.01
Rodgers Ratios (3):
3123 Fite Circle Sacrmento, CA 95827
(916) 361-7177
1000 Riverbend Blvd: Suite O St. Rose, LA 70087
(604) 468-8837
3098 Happy Valley Road Sun Prairie, WI 53590
(608) 825-2022
204 Gale Lane Kennett Square, PA 19348
(610) 925-0688
REVISED 8/5/2019
0.65
5,198
80,568
3,336
4105690
89,867
2.59
9,999.99
7.68
Sample Date:
Hydrogen (ppm):
Total (ppm):
TDCG (ppm):
CH4 / H2:
Key Gas Method:
Operating Procedure:
Sampling Interval:
Condition: 3
Repeat test immediately to establish trend. Fault(s) are probably present
TDCG Level (ppm): TDCG Rate (ppm/day):IEEE Std. C57.104 - 1991
Comments:
DISSOLVED GAS ANALYSIS
Page: 12
(C2H4)
(C2H2)
CARBON DIOXIDE
NITROGEN
AVERAGE (SOLID LINES) AND
HISTORICAL DATA WITH
COMBUSTIBLE GAS
(C0)
2-SIGMA (DOTTED LINES)
4/17/2020
4/17/2020
OXYGEN
(N2)
(C02)
* ACETYLENE
* ETHANE
(CH4)
3123 Fite Circle Sacrmento, CA 95827
(916) 361-7177
1000 Riverbend Blvd: Suite O St. Rose, LA 70087
(604) 468-8837
3098 Happy Valley Road Sun Prairie, WI 53590
(608) 825-2022
204 Gale Lane Kennett Square, PA 19348
(610) 925-0688
REVISED 8/5/2019
* METHANE
* ETHYLENE
(H2)
(C2H6)
AVERAGE (SOLID LINES) AND
2-SIGMA (DOTTED LINES)
HISTORICAL DATA WITH
* HYDROGEN
(O2)
* CARBON MONOXIDE
* COMBUSTIBLE GAS
TOTAL
D1500
D1524
D877
D1816
D924
D924
(dynes/cm)
(ppm):
(kV):
(kV):
(% at 25 C):
(% at 100 C):
Moisture
Acid Number
Visual Examination
Color Number
Dielectric BV
POWER FACTOR
POWER FACTOR
D1533
Equipment Type:
Model:
Bank & Phase: 4160-208
Breathing:
Cooling:
Fluid Volume:
Fluid Type:
VA-Heinz
B22 T1 3 Ph 300 KVA
4105690
INSULATING FLUID EVALUATION
Page: 13
L710356TLLA
Location: Year of Mfg.:
86301680 kV Rating:
B32-T1Position:BLDG #32 (EXTERIOR)Substation:
86301680
PO Number:Report Number:
5/4/2020 Job Number:
Serial Number:
Manufacturer:
Transformer
GE
ABM Electrical Power Solutions, LLC
Report Date:
Cranberry Township, PA 16066 Mineral Oil
317 Commerce Park Drive
Laboratory No.:
Container No.:
Temperature:
Sample Date:
D971 Interfacial Tension
Dielectric BV
Specific Gravity
(%):D2668 Oxidation Inhibitor
D129
Pour Point
Flash Point
Fire Point
Refractive Index
Corrosive Sulfur
(SUS):
( C):
( C):
( C):
D88
D97
D92
D92
D1807
D1275
Viscosity
(mg/KOH/g):
34.099998
0.062
1.5
Clear/Bright
0.431
0.898
4/17/2020
4105690
Insulating Fluid Daignostics
3123 Fite Circle Sacrmento, CA 95827
(916) 361-7177
1000 Riverbend Blvd: Suite O St. Rose, LA 70087
(604) 468-8837
3098 Happy Valley Road Sun Prairie, WI 53590
(608) 825-2022
204 Gale Lane Kennett Square, PA 19348
(610) 925-0688
REVISED 8/5/2019
Acceptable
26 min
26 min
Acceptable
Acceptable
Acceptable
0.2 max
20 max35 max 25 max
23 min
24 min 30 min
IEEE Group I
0.5 max
Acceptable
Acceptable
16 min
<69
26 min
0.1 max Acceptable
>69<288 >345
0.2 max
Acceptable
26 min
IEEE Group IIIIEEE Group II
24 min
0.2 max
26 min
26 min
D974
Specific Gravity:
Viscosity @ 40 C:
Pour Point:
Flash Point:
Fire Point:
Refractive Index:
Corrosive Sulfur:
Comments:
Acid Number:
Color Number:
Visual Examination:
Dielectric BV D877:
Dielectric BV D1816:
Power Factor @ 25 C:
Interfacial Tension:
Power Factor @ 100 C:
Moisture:
Oxidation Inhibitor:
0.5 max clear & bright
30 min
28 min
0.05 max
40 min
0.30 max
35 max
0.3 max
ASTM D3487
-40 max
145 min noncorrosive
0.91 max
66 max
0.03 max clear & bright
30 min
28 min
0.05 max
40 min
0.30 max
35 max
0.3 max
ASTM D3487
-40 max
145 min noncorrosive
0.91 max
66 max
0.03 max
0.5 max
Percent Saturation = 13
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
Matthew Moore / Keith SpearTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0568 / P0097 / P0120
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 04/17/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION BLDG #32 (EXTERIOR) GEN BREAKER Pass
208/120VVOLTAGE
Q2L3225 FRAME SIZE/RATING PLUG
SQUARE D TYPE Q2L
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
225A/225A INT. RATING 10ka @240
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
GEN MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
616 616
68.56 68.56
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
642 642
71.25 71.25
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
623 623
69.66 69.66
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable C
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION GND FLOOR CORRIDOR PANEL A Pass
240VOLTAGE
CAH3175W FRAME SIZE/RATING PLUG
WESTINGHOUSE TYPE CAH3
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
175 INT. RATING 22KA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
1 POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
377 377
23.11 23.11
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
426 426
22.74 22.74
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
389 389
25.61 25.61
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CKT DESIG.
INSULATION RESISTANCE IN MEGOHMS
AT * KV
CATALOG NO.
TYPE
TYPE
CATALOG NO.
CATALOG NO.
CL/JWTESTED BY:
www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019
REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550
EQPT. LOCATION
OWNER
ADDRESS
CUSTOMER
MOLDED CASE CIRCUIT BREAKER
NONADJUSTABLE
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32
EQUIPMENT ID TEST STATUSSUBSTATION GND FLOOR MECH RM PANEL NB Pass
240VOLTAGE
NA FRAME SIZE/RATING PLUG
FPE TYPE NEJ
INT. RATING
VOLTAGE
FRAME SIZE/RATING PLUG
VOLTAGE
INT. RATINGFRAME SIZE/RATING PLUG
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
ACROSS OPEN POLE
POLE - POLE - GND
125 INT. RATING NA
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
1 POLE - POLE - GND
ACROSS OPEN POLE
AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT
MANUFACTURER
MAIN (ECB)
CONTACT RESISTANCE IN MICROHMS
TIME AT 300% RATED CURRENT IN SECONDS
INSTANT TESTED ON * SETTING TRIP / NO TRIP
INSULATION RESISTANCE IN MEGOHMS
AT * KV1
ACROSS OPEN POLE
POLE - POLE - GND
AS FOUND AS LEFT
597 597
17.51 17.51
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
674 674
16.95 16.95
N/A N/A
2200 2200
2200 2200
AS FOUND AS LEFT
692 692
23.13 23.13
N/A N/A
2200 2200
2200 2200
Acceptable NA
Acceptable
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
Acceptable NA
Acceptable NA
Acceptable NA
INSPECTED CONDITION CLEAN/LUBE
NA
OVERALL CLEANLINESS
MECHANICAL CONDITION
Operation
DESCRIPTION
ANCHORAGE AND ALIGNMENT
CONTACT FINGERS
ARC CHUTES
FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
DESCRIPTION
MANUFACTURER
POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:
N/A
EQPT. LOCATION
ADDRESS
CUSTOMER
TRANSFORMER (<500KVA) TEST
TELEPHONE
VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215
412-360-3664
JOB #4100 Allequippa St; Pittsburgh PA 15213
Department of Veterans Affairs PAGE
86301680
CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov
DATE 04/16/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #49
EQUIPMENT ID TEST STATUSSUBSTATION 1A168 B49-T2 (MDP) Pass
Matthew Moore / Keith SpearTESTED BY:
www.abm.comABM Electrical Power Solutions 56710, REVISED 8/5/2019
REVIEWED BY:EQPT. INVENTORY NO. P0140
VISUAL AND MECHANICAL INSPECTION
INSPECT PHYSICAL AND MECHANICAL CONDITION
VERIFY FANS OPERATE (IF APPLICABLE)
INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING
INSPECTION REPORT
FAIL
FAIL
FAIL
PASS
PASS
PASS
INSPECTION REMARKS
NO FANS
3.37838
1,000
2.17865
1,000
3.37838
MINUTES
PRIMARY TO
GROUND
SECONDARY TO
GROUND
PRIMARY TO
SECONDARY
TEST…