Atch 5.Heinz_April 2020_Final Report.pdf

PDF 11 MB Posted

Attached to
H961--VAPHS Triennial Electrical Inspections Federal contract opportunity
Solicitation number
36C24426Q0055
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

This document is a Customer Field Service Report from ABM Electrical Power Solutions detailing electrical equipment testing performed in April 2020 at the VA Pittsburgh Healthcare Center. The report documents maintenance testing of electrical power equipment across multiple buildings, specifically noting several critical findings: transformers in Buildings 63-68 have power factor test results below Doble Standards and require replacement, and multiple buildings (69 and 70) have equipment with electrical component issues such as open contacts, non-operational breaker functions, and cracked equipment parts.

The related federal contract opportunity is a Request for Quote (RFQ) for Triennial Annual Electric Inspection, solicitation number 36C24426Q0055, issued by the Department of Veterans Affairs. The procurement is 100% set aside for Service-Disabled Veteran-Owned Small Business, with a NAICS code of 811210 and a size standard of $34.0M. Key dates include a January 5, 2026 deadline for questions and a January 8, 2026 submission deadline for quotes. The solicitation seeks FY26 Triennial Breaker Inspections for the VA Network Contracting Office 4 in Philadelphia, PA, with all communications to be directed to Contract Specialist Allan Tabliago.

View the file

Other files for this federal contract opportunity

Other files attached to H961--VAPHS Triennial Electrical Inspections, newest first.
File Type Posted
Atch 7.Heinz_June and July 2020_Final Report.pdf PDF
Atch 4.UD August 2020-July 2021_Final Report.pdf PDF
36C24426Q0055 0002_1.docx DOCX document
Atch 6.Heinz_May 2020_Final Report.pdf PDF
Atch 3.Equipment List - Breaker Testing List UD- April 2015.xlsx XLSX spreadsheet
36C24426Q0055 0001_1.docx DOCX document
Atch 2.UD Elect and Arc Flash Study.pdf PDF
Atch 1.HZ Elect and Arc Flash study 2023 reduced.pdf PDF
WD 2015-4235 R32 20251203.pdf PDF
36C24426Q0055_1.docx DOCX document
VAAR 852.219-75 VA Notice of Limitations on Subcontracting.pdf PDF
36C24426Q0055 Triennial Inspectiona.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER

ADDRESS

CUSTOMER

FIELD SERVICE REPORT

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE

Description:

In April, 2020 ABM Electrical Power Solutions Field Personnel were at Department of Veterans Affairs, VA Pittsburgh Healthcare, (Heinz) located in Pittsburgh, PA to perform testing of electrical power equipment.

Engineering Evaluation:

Testing was performed in accordance with the International Electrical Testing Association's Maintenance Testing Specifications and project specifications. Fluid Analysis was performed in accordance with IEEE Specifications.

Scope of Work:

As part of an ongoing project, this report represents the maintenance testing performed in April 2020.

Test Results / Comments:

Building #63-68 (Exterior), B63 & 68-T1; The power factor test results are below Doble Standards. Doble's engineer recommends replacing the transformer at the earliest convenience.

Building #69, 1B116, MSB, Spare-position #11; B-Phase has an open contact.

Building #69, MSB, Spare-position #8; B-Phase has an open contact.

Building #70, BA019, MSA, PNL-NH1A1; No operation on long time function.

Building #70, BA019A, ATS-LA; Plastic finger cluster divider is cracked on top side of ATS.

Building #70, BA019A, MSQ, ATS-LA; No operation on long time and short time functions.

Building #71, GA102, 71-DSBL, Breaker Spare (2nd section, position 8); No trip on long time and instantaneous functions.

All other test results are acceptable per NETA - MTS Standards. All equipment was left in Satisfactory Operational Condition.

This report certifies that the above equipment has been tested in compliance with recognized standards or for safe use in a specific manner, or in accordance with

Federal, State or Municipal regulations. The report is accurate and true to the best of our knowledge and belief. All equipment used in making physical determinations is accurate and bears recent and direct traceability to the National Institute of Standards and Technology. (NIST).

1/21/2022

By:

Josh Schoedel www.abm.comABM Electrical Power Solutions REVISED 1/21/2022

ABM Electrical Power Solutions 317 Commerce Park Drive Cranberry Township, PA 16066

Project Manager

Equipment Tested Job #86301680 www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

1PAGE

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

115910- MCB - 3 in 1 REV.1 (4) - Pass (4)

(HEINZ) BLDG #32 1ST FLOOR CORRIDOR PANEL B

215910- MCB - 3 in 1 REV.1 (5) - Pass (5)

(HEINZ) BLDG #32 2ND FLOOR CORRIDOR PANEL C

315910- MCB - 3 in 1 REV.1 (2) - Pass

(HEINZ) BLDG #32 BA106 DP

415910- MCB - 3 in 1 REV.1-MAIN

(HEINZ) BLDG #32 BA106 DP

515910- MCB - 3 in 1 REV.1 -(1) Pass - Pass

(HEINZ) BLDG #32 BA106 DP

615910- MCB - 3 in 1 REV.1 (3) - Pass

(HEINZ) BLDG #32 BA106 DP

715910- MCB - 3 in 1 REV.1 (5) - Pass (5)

(HEINZ) BLDG #32 BA109 32EA

854100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) ATS-B32

956900 - MET TWO-WINDING TRANSFORMER REV.1

(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) B32-T1

11TJH2B DGA - L710356TLLA-Tran

(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) B32-T1

13TJH2B Fluid - L710356TLLA-Tran

(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) B32-T1

1415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #32 BLDG #32 (EXTERIOR) GEN BREAKER

1515910- MCB - 3 in 1 REV.1 (3) - Pass (2)

(HEINZ) BLDG #32 GND FLOOR CORRIDOR PANEL A

1615910- MCB - 3 in 1 REV.1 (3) - Pass (3)

(HEINZ) BLDG #32 GND FLOOR MECH RM PANEL NB

1756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #49 1A168 B49-T2 (MDP)

1856710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #49 1A168 B49-T3 (EB-RA)

1956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #49 1A168 B49-T4 (EB-RB)

2015910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #49 1A168 EB-HB

2115910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #49 1A168 EB-MDP

2215910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #49 1A168 EB-MDP

2315910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #49 1A168 EB-RA (SEC 1)

2415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #49 1A168 EB-RA (SEC 2)

2515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #49 1A168 EB-RB

2615610 - LV DISCONNECT SWITCH

(HEINZ) BLDG #49 1A168 SW-B49-T2 (SEC)

2715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #49 1D100 PANEL D

2856710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #49 1D106 B49-T5 (PR-L)

2915910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #49 1D106 PR-H

2PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

3015910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #49 1D106 PR-L

3115910- MCB - 3 in 1 REV.1 (4)

(HEINZ) BLDG #49 WH MECH RM (EXTERIOR) MDP

3215910- MCB - 3 in 1 REV.1 (3)

(HEINZ) BLDG #49 WH MECH RM (EXTERIOR) MDP

3356710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #53 BLDG #53 (INTERIOR) B53-T-G

3415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #53 BLDG #53 (INTERIOR) G (LEFT)

3515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #53 BLDG #53 (INTERIOR) GA (LEFT)

3615910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #63 BLDG #63 (INTERIOR) VARIOUS

3715910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #63 BLDG #63 (INTERIOR) VARIOUS

3856700 - TRANSFORMER MAINTENANCE TEST (3)

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B63&68-T1

3956700 - TRANSFORMER MAINTENANCE TEST

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B64&65-T1

40TJH2B DGA - 07J835066-Tran

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B64&65-T1

42TJH2B Fluid - 07J835066-Tran

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B64&65-T1

4356700 - TRANSFORMER MAINTENANCE TEST (2)

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B66&67-T1

44TJH2B DGA - 07J835076-Tran

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B66&67-T1

46TJH2B Fluid - 07J835076-Tran

(HEINZ) BLDG #63-68 XFMRS BLDG #63-68 (EXTERIOR) B66&67-T1

4715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #64 BLDG #64 (INTERIOR) VARIOUS

4815910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #64 BLDG #64 (INTERIOR) VARIOUS

4915910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #65 BLDG #65 (INTERIOR) VARIOUS

5015910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #66 BLDG #66 (INTERIOR) VARIOUS

5115910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #67 BLDG #67 (INTERIOR) VARIOUS

5215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #68 BLDG #68 (INTERIOR) VARIOUS

5354101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass

(HEINZ) BLDG #69 1B115 ATS-EQNE

5554101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass

(HEINZ) BLDG #69 1B115 ATS-LSNE

5756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #69 1B115 B69-T2

5815910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #69 1B115 EQNE

3PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

5915610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #69 1B115 SW-B69ATS-EQNE

6015610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #69 1B115 SW-B69ATS-LSNE

6115610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #69 1B115 SW-B69T2 (PRIM)

6215610 - LV DISCONNECT SWITCH - Pass

(HEINZ) BLDG #69 1B115 SW-B69T2 (SEC)

6315065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LF)

(HEINZ) BLDG #69 1B116 MSB

6415065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-2LB)

(HEINZ) BLDG #69 1B116 MSB

6515065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LB)

(HEINZ) BLDG #69 1B116 MSB

6615065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-EQNE)

(HEINZ) BLDG #69 1B116 MSB

6715065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE-POSITION 10)

(HEINZ) BLDG #69 1B116 MSB

6815065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-2LC)

(HEINZ) BLDG #69 1B116 MSB

6915065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-1SF)

(HEINZ) BLDG #69 1B116 MSB

7015065 - LOW VOLT. PWR. CKT. BKR. TEST (ELEVATOR #1)

(HEINZ) BLDG #69 1B116 MSB

7115065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-2SF)

(HEINZ) BLDG #69 1B116 MSB

7215065 - LOW VOLT. PWR. CKT. BKR. TEST (ELEVATOR #3)

(HEINZ) BLDG #69 1B116 MSB

7315065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LD)

(HEINZ) BLDG #69 1B116 MSB

7415065 - LOW VOLT. PWR. CKT. BKR. TEST (ELEVATOR #2)

(HEINZ) BLDG #69 1B116 MSB

7515065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-2LA)

(HEINZ) BLDG #69 1B116 MSB

7615065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE-POSITION 7)

(HEINZ) BLDG #69 1B116 MSB

7715065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-1LA)

(HEINZ) BLDG #69 1B116 MSB

7815065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE-POSITION 11)

(HEINZ) BLDG #69 1B116 MSB

7915065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE-POSITION 8)

(HEINZ) BLDG #69 1B116 MSB

8015065 - LOW VOLT. PWR. CKT. BKR. TEST (AHU-1RF)

(HEINZ) BLDG #69 1B116 MSB

8115500 - BOLTED PRESSURE SWITCH TEST (MAIN)

(HEINZ) BLDG #69 1B116 MSB

8256900 - MET TWO-WINDING TRANSFORMER REV.1 (3)

(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) B69-T1

84TJH2B DGA - 1450000870-Tran

(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) B69-T1

4PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

86TJH2B Fluid - 1450000870-Tran

(HEINZ) BLDG #69 BLDG #69 (EXTERIOR) B69-T1

8715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 1A139 70-NH1A1

8815910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 1A139 70-NL1A1 (SEC 1)

8956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 1A139 B70-T8 (NL1A1)

9015910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 1A167 70-NL1B1 (SEC 1)

9156710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 1A167 B70-T7 (NL1B1)

9215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 2A238 70-NH2A1

9315910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 2A238 70-NL2A1 (SEC 1)

9456710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 2A238 B70-T10 (NL2A1)

9515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 2A261 70-NH2B2

9615910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 2A261 70-NH2B2

9756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 2A261 B70-T9 (NL2B1)

9815910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 2A261 NL2B1

9956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 BA019 B70-T2 (NLBA2)

10015065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN)

(HEINZ) BLDG #70 BA019 MSA

10115065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH2A1)

(HEINZ) BLDG #70 BA019 MSA

10215065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH1A1)

(HEINZ) BLDG #70 BA019 MSA

10415065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH2B2)

(HEINZ) BLDG #70 BA019 MSA

10515065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NHBA2)

(HEINZ) BLDG #70 BA019 MSA

10615065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-LA)

(HEINZ) BLDG #70 BA019 MSA

10715065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-QA)

(HEINZ) BLDG #70 BA019 MSA

10815065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH1B1)

(HEINZ) BLDG #70 BA019 MSA

10915065 - LOW VOLT. PWR. CKT. BKR. TEST (MCCN)

(HEINZ) BLDG #70 BA019 MSA

11015065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL-NH2B1)

(HEINZ) BLDG #70 BA019 MSA

11115910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 BA019 NHBA2

5PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

11215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 BA019 NLBA2

11354101 - AUTOMATIC TRANSFER SWITCH TEST W/ INS. RES.

(HEINZ) BLDG #70 BA019A ATS-LA

11554101 - AUTOMATIC TRANSFER SWITCH TEST W/ INS. RES.

(HEINZ) BLDG #70 BA019A ATS-QA

11756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 BA019A B70-T3 (QLBA1)

11856710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 BA019A B70-T4 (QL2B1)

11956710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 BA019A B70-T5 (LL1A2)

12056710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #70 BA019A B70-T6 (LLBA1)

12115065 - LOW VOLT. PWR. CKT. BKR. TEST (BLDG 69) - Pass - Pass

(HEINZ) BLDG #70 BA019A MSQ

12215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-LA)

(HEINZ) BLDG #70 BA019A MSQ

12415065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-QA)

(HEINZ) BLDG #70 BA019A MSQ

12515910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #70 BA019A QHBA1

12615065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #70 BA019B GEN BREAKER

12756900 - MET TWO-WINDING TRANSFORMER REV.1 (2)

(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) B70-T1

129TJH2B DGA - 07J830296-Tran

(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) B70-T1

131TJH2B Fluid - 07J830296-Tran

(HEINZ) BLDG #70 BLDG #70 (EXTERIOR) B70-T1

13215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA102 71-DPBH

13315065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #71 GA102 71-DSBL

13415910- MCB - 3 in 1 REV.1 (5)

(HEINZ) BLDG #71 GA102 71-DSBL

13515910- MCB - 3 in 1 REV.1 (3)

(HEINZ) BLDG #71 GA102 71-DSBL

13615910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA102 71-DSBL

13715910- MCB - 3 in 1 REV.1 (8)

(HEINZ) BLDG #71 GA102 71-DSBL

13815910- MCB - 3 in 1 REV.1 (4)

(HEINZ) BLDG #71 GA102 71-DSBL

13915910- MCB - 3 in 1 REV.1 (6)

(HEINZ) BLDG #71 GA102 71-DSBL

14015910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #71 GA102 71-DSBL

14115910- MCB - 3 in 1 REV.1 (7)

(HEINZ) BLDG #71 GA102 71-DSBL

6PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

14215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA102 71-EQBLC

14315065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-EQ)

(HEINZ) BLDG #71 GA102 71-MSG

14415065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL 71-DPBH) - Pass - Pass

(HEINZ) BLDG #71 GA102 71-MSG

14515065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE) (1C)

(HEINZ) BLDG #71 GA102 71-MSG

14615065 - LOW VOLT. PWR. CKT. BKR. TEST (71-1HB 71-2HB)

(HEINZ) BLDG #71 GA102 71-MSG

14715065 - LOW VOLT. PWR. CKT. BKR. TEST (PNL 71-BHA) - Pass

(HEINZ) BLDG #71 GA102 71-MSG

14815065 - LOW VOLT. PWR. CKT. BKR. TEST (71-1HC 71-2HC)

(HEINZ) BLDG #71 GA102 71-MSG

14915065 - LOW VOLT. PWR. CKT. BKR. TEST (DSBL) (2B) - Pass

(HEINZ) BLDG #71 GA102 71-MSG

15015065 - LOW VOLT. PWR. CKT. BKR. TEST (71-1HA 71-2HA)

(HEINZ) BLDG #71 GA102 71-MSG

15115065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-ELEV)

(HEINZ) BLDG #71 GA102 71-MSG

15215065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-LS)

(HEINZ) BLDG #71 GA102 71-MSG

15315065 - LOW VOLT. PWR. CKT. BKR. TEST (MAIN) - Pass

(HEINZ) BLDG #71 GA102 71-MSG

15415065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE) (1D)

(HEINZ) BLDG #71 GA102 71-MSG

15515065 - LOW VOLT. PWR. CKT. BKR. TEST (ATS-CC)

(HEINZ) BLDG #71 GA102 71-MSG

15615065 - LOW VOLT. PWR. CKT. BKR. TEST (SPARE) (3B)

(HEINZ) BLDG #71 GA102 71-MSG

15756710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #71 GA102 B71-T-DSBL

15856710 - TRANSFORMER DRY MAINTENANCE (<500KVA) (2)

(HEINZ) BLDG #71 GA102 B71-T-EQBLC

15915610 - LV DISCONNECT SWITCH (2)

(HEINZ) BLDG #71 GA102 SW-B71-EQBH-B

16015610 - LV DISCONNECT SWITCH

(HEINZ) BLDG #71 GA102 SW-B71-T-EQBLC

16115910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA117 71-CCBHA

16215910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA117 71-CCBLA

16315910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #71 GA117 71-CCBLA

16415910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA117 71-EBHA

16515910- MCB - 3 in 1 REV.1 (9) (2)

(HEINZ) BLDG #71 GA117 71-EBHA

16615910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA117 71-EQBHA

7PAGE

www.abm.comABM Electrical Power Solutions REVISED 2/3/2016

PAGE

NO.Asset

Equip IDSubstationPlant

Department of Veterans AffairsCustomer

VA Pittsburgh Healthcare CenterOwner

16715910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA117 71-EQBLA

16815910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA117 71-EVBHA

16915910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA117 71-LSBHA

17015910- MCB - 3 in 1 REV.1

(HEINZ) BLDG #71 GA117 71-LSBLA

17115910- MCB - 3 in 1 REV.1 (2)

(HEINZ) BLDG #71 GA117 71-LSBLA

17254101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass

(HEINZ) BLDG #71 GA117 ATS-CC

17454101 - AUTOMATIC TRANSFER SWITCH TEST REV.1- Pass

(HEINZ) BLDG #71 GA117 ATS-ELEV

17654101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass

(HEINZ) BLDG #71 GA117 ATS-EQ

17854101 - AUTOMATIC TRANSFER SWITCH TEST REV.1 - Pass

(HEINZ) BLDG #71 GA117 ATS-LS

18056710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #71 GA117 B71-CCBLA

18156710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #71 GA117 B71-EQBLA

18256710 - TRANSFORMER DRY MAINTENANCE (<500KVA)

(HEINZ) BLDG #71 GA117 B71-LSBLA

18315065 - LOW VOLT. PWR. CKT. BKR. TEST

(HEINZ) BLDG #71 GA117 GEN BREAKER

18454100 - AUTOMATIC TRANSFER SWITCH TEST W/O INS. RES.

(HEINZ) BLDG #71 GA117 MTS-1

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION 1ST FLOOR CORRIDOR PANEL B Pass

240VOLTAGE

CAH315W FRAME SIZE/RATING PLUG

WESTINGHOUSE TYPE CAH3

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

150 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

1 POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

551 551

21.74 21.74

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

478 478

19.38 19.38

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

524 524

27.99 27.99

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

COMMENTS:

DEFICIENCIES:

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION 2ND FLOOR CORRIDOR PANEL C Pass

240VOLTAGE

CAH3150W FRAME SIZE/RATING PLUG

WESTINGHOUSE TYPE CAH3

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

150 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

1 POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

488 488

27.48 27.48

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

437 437

28.55 28.55

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

570 570

27.17 27.17

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO. JD3250F

WESTINGHOUSE TYPE JD25K

WESTINGHOUSE TYPE JD25K

JD3250FCATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA106 DP Pass

240VOLTAGE

JD3250F FRAME SIZE/RATING PLUG

WESTINGHOUSE TYPE JD25K

65KAINT. RATING

VOLTAGE

250/200FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

ATS AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS 492 492 503 503 479 479

TIME AT 300% RATED CURRENT IN SECONDS 57.38 57.38 79.22 79.22 56.28 56.28

INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A

ACROSS OPEN POLE

POLE - POLE - GND

2200 2200 2200 2200 2200 2200

2200 2200 2200 2200 2200 2200

250/200 INT. RATING 65KA

AHU-1

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

1 POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT

403 403

69.45 69.45

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

467 467

73.63 73.63

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

487 487

59.07 59.07

N/A N/A

2200 2200

2200 2200

250/250 65KA

MANUFACTURER

PNL C

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

450 450

86.23 86.23

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

488 488

103.5 103.5

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

467 467

70.95 70.95

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

N/A

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0550/P0521/010023

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 72 °F HUMIDITY 30 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA106 DP Pass

240VOLTAGE

LCA3600F FRAME SIZE/RATING PLUG

WESTINGHOUSE TYPE LCA

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

600/500 INT. RATING 42KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

118 118

33.41 33.41

TRIP TRIP

2200 2200

2200 2200

AS FOUND AS LEFT

123 123

33.41 33.41

TRIP TRIP

2200 2200

2200 2200

AS FOUND AS LEFT

166 166

33.41 33.41

TRIP TRIP

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

COMMENTS: Used Westinghouse Seltronic secondary injection test set.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO. JD3250F

WESTINGHOUSE TYPE JD25K

WESTINGHOUSE TYPE JD25K

JD3250FCATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA106 DP Pass

240VOLTAGE

JD3250F FRAME SIZE/RATING PLUG

WESTINGHOUSE TYPE JD25K

65KAINT. RATING

VOLTAGE

250/200FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

PNL A AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS 395 395 437 437 483 483

TIME AT 300% RATED CURRENT IN SECONDS 75.24 75.24 78.92 78.92 72.92 72.92

INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A N/A N/A N/A N/A N/A

ACROSS OPEN POLE

POLE - POLE - GND

2200 2200 2200 2200 2200 2200

2200 2200 2200 2200 2200 2200

250/200 INT. RATING 65KA

PNL NA/NB

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

1 POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT

497 497

65.55 65.55

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

518 518

67.61 67.61

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

428 428

69.38 69.38

N/A N/A

2200 2200

2200 2200

250/225 65KA

MANUFACTURER

PNL B

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

424 424

68.85 68.85

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

459 459

84.77 84.77

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

464 464

61.44 61.44

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

N/A

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO. FD3225

CUTLER-HAMMER TYPE FD 35K

TYPE

CATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA106 DP Pass

240VOLTAGE

HFD3125 FRAME SIZE/RATING PLUG

CUTLER-HAMMER TYPE HFD 65K

65KAINT. RATING

VOLTAGE

225FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

ELEV AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS 470 470 443 443 486 486

TIME AT 300% RATED CURRENT IN SECONDS 38.24 38.24 36.15 36.15 29.57 29.57

INSTANT TESTED ON * SETTING TRIP / NO TRIP N/A NA N/A NA N/A NA

ACROSS OPEN POLE

POLE - POLE - GND

2200 2200 2200 2200 2200 2200

2200 2200 2200 2200 2200 2200

125 INT. RATING 100KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

1 POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

PNL PP32B1

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

980 980

44.37 44.37

N/A NA

2200 2200

2200 2200

AS FOUND AS LEFT

770 770

45.58 45.58

N/A NA

2200 2200

2200 2200

AS FOUND AS LEFT

992 992

52.03 52.03

N/A NA

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BA109 32EA Pass

240VOLTAGE

JD3250F FRAME SIZE/RATING PLUG

WESTINGHOUSE TYPE JD 25K

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

250/200 INT. RATING 65KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

1 POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

497 497

135.45 135.45

TRIP TRIP

2200 2200

2200 2200

AS FOUND AS LEFT

464 464

122.31 122.31

TRIP TRIP

2200 2200

2200 2200

AS FOUND AS LEFT

528 528

131.68 131.68

TRIP TRIP

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

EQUIPMENT TEMPERATURE

R T = R M K

K sT T

+ T

+ TM

Matthew Moore / Keith SpearTESTED BY:

www.abm.comABM Electrical Power Solutions 54100, REVISED 2/18/2020

REVIEWED BY:EQPT. INVENTORY NO. P0098

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 04/17/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BLDG #32 (EXTERIOR) ATS-B32 Pass

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE:

R

R M s

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

157 157 157

161 161 161

154 154 154

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

NA

C

C

NA

C

C

C

NA

C/L

NA

NA

NA

N/A

MANUFACTURER

NAMEPLATE DATA

CATALOG NO.

WIRING NO.

SYSTEM VOLTAGE AMPACITY

SPECTRUM SERIAL NO. K58176 TYPE AUTOMATIC TRANSFER SWITCH

N/A 208V 225A

N/A CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

DESCRIPTION

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

Matthew Moore / Keith SpearTESTED BY:

www.abm.comABM Electrical Power Solutions 56900, REVISED 8/6/2019

REVIEWED BY:EQPT. INVENTORY NO. P0580 / P0082 / P0041

RAIN

INDOOR OUTDOOR

ENVIRONMENTAL DATA

WEATHER CONDITIONS %AMBIENT TEMPERATURE 876degC

CONTROLS

CONTROL VOLTAGE

GOOD POOR EXPLAIN: NO FANS

GOOD FAIR POOR

GOOD FAIR POOR

GOOD FAIR

GOOD FAIR POOR

FAIR

POOR

VOLTS

EXPLAIN:

EXPLAIN:

EXPLAIN:

EXPLAIN:

LIQUID GAS AIR NONE DETECTED DESCRIBE:

TRANSFORMER LOCATED OUTSIDE OF METAL CLAD BLDG #55.

PAINT

GROUNDS

DESCRIBE OPERATING ENVIRONMENT

LEAKS

FANS

CONNECTIONS

VISUAL INSPECTION

YES

HUMIDITY

1.98 130

NAMEPLATE DATA

L710356TLLASERIAL NO.

4,264 4,160 4,056

1 2 3 4 5

GENERAL ELECTRIC YR MFR N/A

KVA

IMPEDANCE

3,952

CAPACITY

WYE

TAP VOLTAGES

DELTA

DELTA

MANUFACTURER

WYE

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

TWO-WINDING TRANSFORMER

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 04/17/2020 TEMPERATURE 42 °F HUMIDITY 87 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BLDG #32 (EXTERIOR) B32-T1 Pass

/ OA FA FOA FOW OW FOW

OIL

CLASS

PRIMARY

SECONDARY

VOLTS

SINGLE PHASE

SINGLE PHASE

ALUMINUM COPPER

ALUMINUM COPPER

WINDING MATERIALCONNECTIONS

/4,160

/208 120

4,368

TAP POSITION

4,056 / VOLTS PERCENT )(

LIQUID-FILLED GAS-FILLED AIR FIELD SAMPLE YES NO

SILICONE OIL AIR RTEMP GASWESCOLPCB

GALLONSPSI

TEMPERATURE RISE

TEMPERATURE GAUGE

WINDING TEMPERATURE

°C

°C

58 °C

°C

FAN SET TO °C

LOCATED ON POLE PAD

MAXIMUM TEMPERATURE INDICATOR RESET TO

TAP POSITION LEFT

INSULATING MEDIUM

MEDIUM TYPE

BELOW NORMALMEDIUM LEVEL

MAXIMUM TEMPERATURE INDICATOR

PRESSURE CAPACITY

°C

GALLONS TYPE CATALOG NUMBER N/A

TWO-WINDING TRANSFORMER

10PAGE

www.abm.comABM Electrical Power Solutions 56900, REVISED 8/6/2019

404.000 403.000 403.000 528.0000 517.0000 521.0000

1 2 3 4 5

WINDING

TESTED

H1-H2 H2-H3 H3-H1 X0-X1 X0-X2 X0-X3

WINDING RESISTANCE TESTS

ARE WINDING POLARITIES AS PER NAMEPLATE? YES

IF NO, DESCRIBE:

TAP POSITION

H WINDING X WINDINGNO MicrohmsWINDING RESISTANCE UNITS: Milliohms

DEMAGNETIZATION COMPLETE YES NO

PRIMARY SECONDARY

INSULATION RESISTANCE TEST

TESTED

PRIMARY TO

SECONDARY AND GROUND

SECONDARY TO

PRIMARY AND GROUND

VOLTAGE

(VOLTS DC)

2,500

1,000

0.5 MINUTE

4,150

1,055

1.0 MINUTE

4,870

1,220

10 MINUTES

7,020

1,740

MINIMUM

(MEGOHMS)

1,000

(MEGOHMS)

YES NO

YES NO

DIELECTRIC ABSORPTION: (RATIO OF 1 MINUTE TO 0.5 MINUTE RESULT)

POLARIZATION INDEX: (RATIO OF 10 MINUTE RESULT TO 1 MINUTE RESULT)

PRIMARY

WINDING

1.174

1.442

SECONDARY

WINDING

1.156

1.426

ACCEPTABLE

YES NO

YES NO

Windings TEST RESISTANCE RECOMMENDED

ACCEPTABLE

TEMPERATURE CORRECTION FACTOR: AIR MEDIUM TEMPERATURE WAS 5degC MULTIPLY RESULT BY CORRECTION FACTOR 0.36

PASS/FAIL

H2-H3

Calculated PASS/FAIL Calculated

4,264

4,160

4,056 33.842

3,952

33.8460.12 % PASS 0.14 % PASS 0.12 %

PASS/FAIL

PASS

TO

% DEVIATION

H3-H1

33.840

Measured

TO

% DEVIATIONMeasured

TO

% DEVIATIONMeasuredCalculated

RATIO

36.400

35.533

34.667

33.800

TAP

NAMEPLATE

VOLTAGE

YES NO

H1-H2

TRANSFORMER TURNS RATIO TESTS

ASTERICK (*) DENOTES RESULTS NOT WITHIN TOLERANCE

4,368

TURNS RATIO RESULTS: ARE THEY WITHIN +/- 0.5% OF ADJACENT PHASES AND/OR CALCULATED RATIO.

32.933

Calculated

B32-T1 L710356TLLA

TwoWindingTransformerReport Source

4/17/2020 5:53:22 PMSession Test Date

Nameplate - Two-winding Transformer Company ABM Serial Number L710356TLLA

Location VA HOSPITAL - HEINZ Special ID B32-T1

Division PITTSBURGH Circuit Designation B32-T1

Manufacturer General Electric Configuration D_Y

Year Manufactured Tank Type Sealed

Mfr Location U.S.A. Coolant Oil

Phases Three Class OA

Oil Volume 130 UG BIL 60 kV

Weight 3350 LB kV 4.16, 0.21 VA Rating 300, *, *, *, kVA

Administration Test Date 4/17/2020 Test Time: 5:53 PM Weather Rain

Air Temperature 65.8°C Apparatus Temperature

20°C Humidity 72.674 %

Tester MM / KS Work Order 86301680 Date Last Tested

Verified Test Set Type M4100 Date Retested

Verification Date 4/17/2020 Set Top Serial # 70101514 Reason Routine

Last Sheet # Test Set Model M4100 Travel Time

Purchase Order Ins. Book # Duration

Copies Sheet # Crew Size 2

Overall Tests Insulation Test kV mA Watts PF*TCF

Corr Fctr

Cap (pF) FRANK™ Manual

1 CH+CHL 2.400 28.649 2.583 0.888 0.994 7599.144

2 CH 2.401 1.894 0.133 0.685 0.994 502.259 Good Good

3 CHL

(Measured)

2.400 26.756 2.452 0.903 0.994 7096.908 Good Good

4 CHL * 26.756 2.450 0.910 0.994 7096.885 Good Good

5 CL+CHL 0.250 42.883 3.538 0.810 0.994 11374.654

6 CL 0.250 16.165 1.032 0.622 0.994 4287.863 Good Good

7 CHL

(Measured)

0.250 26.729 2.401 0.885 0.994 7089.766 Good Good

8 CHL * 26.718 2.505 0.932 0.994 7086.791 Good Good

Winding without Attached Bushing Calculation

CH-C1 CH' 1.894 0.133 0.685 0.994 502.259

CL-C1 CL' 16.165 1.032 0.622 0.994 4287.863

Report generated on 4/17/2020 6:35:50 PM 1 - 2

FRANK™ Message 2 (Good) - Power factor results are acceptable compared to the limits.

For this apparatus, the low power factor limit is 0.1%, the degraded limit is 1.0%, and the high limit is 1.5%.

The relative humidity is above 70%, which is likely cause some increases in measured watts and power factor. If higher than expected results are obtained, clean and dry all porcelain surfaces before retesting, using heat if necessary.

3 (Good) - Power factor results are acceptable compared to the limits.

4 (Good) - The calculated values compare to the measured values.

6 (Good) - Power factor results are acceptable compared to the limits.

7 (Good) - Power factor results are acceptable compared to the limits.

8 (Good) - The calculated values compare to the measured values.

Excitation Current & Losses Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 5 * * 4 4 *

H1 H2 H2 H3 H3 H1

Winding :

Tap Position

(s)

Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual

HV: 4 2.4 43.347 117.268 L 60.702 117.268 L 55.224 113.678 L Good Good

Report generated on 4/17/2020 6:35:50 PM 2 - 2

Equipment Type:

Model:

Bank & Phase: 4160-208

Breathing:

Cooling:

Fluid Volume:

Fluid Type:

VA-Heinz

B22 T1 3 Ph 300 KVA

4105690

DISSOLVED GAS ANALYSIS

Page: 11

L710356TLLA

Location: Year of Mfg.:

86301680 kV Rating:

B32-T1Position:BLDG #32 (EXTERIOR)Substation:

86301680

PO Number:Report Number:

5/4/2020 Job Number:

Serial Number:

Manufacturer:

Transformer

GE

ABM Electrical Power Solutions, LLC

Report Date:

Cranberry Township, PA 16066 Mineral Oil

317 Commerce Park Drive

Laboratory No.:

Container No.:

Temperature:

Methane (ppm):

Ethane (ppm):

Ethylene (ppm):

Acetylene (ppm):

Carbon Monoxide (ppm):

Carbon Dioxide (ppm):

Nitrogen (ppm):

Oxygen (ppm):

TDCG Rate (ppm/day):

TDCG (gallons):

TDHHG (ppm):

ETCG (% in blanket):

C2H2 / C2H4:

C2H2 / CH4:

C2H6 / C2H2:

C2H4 / C2H6:

CO2 / CO:

Rodgers Ratios (4):

Heat Index:

Doernenburg Ratios:

CO2 / CO:

Dissolved Gas Diagnostics

4/17/2020

All gases are within normal limits

Not in table

Not in table.

Higher than normal temperature in insulation

0.01

Rodgers Ratios (3):

3123 Fite Circle Sacrmento, CA 95827

(916) 361-7177

1000 Riverbend Blvd: Suite O St. Rose, LA 70087

(604) 468-8837

3098 Happy Valley Road Sun Prairie, WI 53590

(608) 825-2022

204 Gale Lane Kennett Square, PA 19348

(610) 925-0688

REVISED 8/5/2019

0.65

5,198

80,568

3,336

4105690

89,867

2.59

9,999.99

7.68

Sample Date:

Hydrogen (ppm):

Total (ppm):

TDCG (ppm):

CH4 / H2:

Key Gas Method:

Operating Procedure:

Sampling Interval:

Condition: 3

Repeat test immediately to establish trend. Fault(s) are probably present

TDCG Level (ppm): TDCG Rate (ppm/day):IEEE Std. C57.104 - 1991

Comments:

DISSOLVED GAS ANALYSIS

Page: 12

(C2H4)

(C2H2)

CARBON DIOXIDE

NITROGEN

AVERAGE (SOLID LINES) AND

HISTORICAL DATA WITH

COMBUSTIBLE GAS

(C0)

2-SIGMA (DOTTED LINES)

4/17/2020

4/17/2020

OXYGEN

(N2)

(C02)

* ACETYLENE

* ETHANE

(CH4)

3123 Fite Circle Sacrmento, CA 95827

(916) 361-7177

1000 Riverbend Blvd: Suite O St. Rose, LA 70087

(604) 468-8837

3098 Happy Valley Road Sun Prairie, WI 53590

(608) 825-2022

204 Gale Lane Kennett Square, PA 19348

(610) 925-0688

REVISED 8/5/2019

* METHANE

* ETHYLENE

(H2)

(C2H6)

AVERAGE (SOLID LINES) AND

2-SIGMA (DOTTED LINES)

HISTORICAL DATA WITH

* HYDROGEN

(O2)

* CARBON MONOXIDE

* COMBUSTIBLE GAS

TOTAL

D1500

D1524

D877

D1816

D924

D924

(dynes/cm)

(ppm):

(kV):

(kV):

(% at 25 C):

(% at 100 C):

Moisture

Acid Number

Visual Examination

Color Number

Dielectric BV

POWER FACTOR

POWER FACTOR

D1533

Equipment Type:

Model:

Bank & Phase: 4160-208

Breathing:

Cooling:

Fluid Volume:

Fluid Type:

VA-Heinz

B22 T1 3 Ph 300 KVA

4105690

INSULATING FLUID EVALUATION

Page: 13

L710356TLLA

Location: Year of Mfg.:

86301680 kV Rating:

B32-T1Position:BLDG #32 (EXTERIOR)Substation:

86301680

PO Number:Report Number:

5/4/2020 Job Number:

Serial Number:

Manufacturer:

Transformer

GE

ABM Electrical Power Solutions, LLC

Report Date:

Cranberry Township, PA 16066 Mineral Oil

317 Commerce Park Drive

Laboratory No.:

Container No.:

Temperature:

Sample Date:

D971 Interfacial Tension

Dielectric BV

Specific Gravity

(%):D2668 Oxidation Inhibitor

D129

Pour Point

Flash Point

Fire Point

Refractive Index

Corrosive Sulfur

(SUS):

( C):

( C):

( C):

D88

D97

D92

D92

D1807

D1275

Viscosity

(mg/KOH/g):

34.099998

0.062

1.5

Clear/Bright

0.431

0.898

4/17/2020

4105690

Insulating Fluid Daignostics

3123 Fite Circle Sacrmento, CA 95827

(916) 361-7177

1000 Riverbend Blvd: Suite O St. Rose, LA 70087

(604) 468-8837

3098 Happy Valley Road Sun Prairie, WI 53590

(608) 825-2022

204 Gale Lane Kennett Square, PA 19348

(610) 925-0688

REVISED 8/5/2019

Acceptable

26 min

26 min

Acceptable

Acceptable

Acceptable

0.2 max

20 max35 max 25 max

23 min

24 min 30 min

IEEE Group I

0.5 max

Acceptable

Acceptable

16 min

<69

26 min

0.1 max Acceptable

>69<288 >345

0.2 max

Acceptable

26 min

IEEE Group IIIIEEE Group II

24 min

0.2 max

26 min

26 min

D974

Specific Gravity:

Viscosity @ 40 C:

Pour Point:

Flash Point:

Fire Point:

Refractive Index:

Corrosive Sulfur:

Comments:

Acid Number:

Color Number:

Visual Examination:

Dielectric BV D877:

Dielectric BV D1816:

Power Factor @ 25 C:

Interfacial Tension:

Power Factor @ 100 C:

Moisture:

Oxidation Inhibitor:

0.5 max clear & bright

30 min

28 min

0.05 max

40 min

0.30 max

35 max

0.3 max

ASTM D3487

-40 max

145 min noncorrosive

0.91 max

66 max

0.03 max clear & bright

30 min

28 min

0.05 max

40 min

0.30 max

35 max

0.3 max

ASTM D3487

-40 max

145 min noncorrosive

0.91 max

66 max

0.03 max

0.5 max

Percent Saturation = 13

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

Matthew Moore / Keith SpearTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0568 / P0097 / P0120

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 04/17/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION BLDG #32 (EXTERIOR) GEN BREAKER Pass

208/120VVOLTAGE

Q2L3225 FRAME SIZE/RATING PLUG

SQUARE D TYPE Q2L

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

225A/225A INT. RATING 10ka @240

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

GEN MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

616 616

68.56 68.56

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

642 642

71.25 71.25

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

623 623

69.66 69.66

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable C

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION GND FLOOR CORRIDOR PANEL A Pass

240VOLTAGE

CAH3175W FRAME SIZE/RATING PLUG

WESTINGHOUSE TYPE CAH3

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

175 INT. RATING 22KA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

1 POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

377 377

23.11 23.11

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

426 426

22.74 22.74

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

389 389

25.61 25.61

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CKT DESIG.

INSULATION RESISTANCE IN MEGOHMS

AT * KV

CATALOG NO.

TYPE

TYPE

CATALOG NO.

CATALOG NO.

CL/JWTESTED BY:

www.abm.comABM Electrical Power Solutions 15910, REVISED 5/31/2019

REVIEWED BY:EQPT. INVENTORY NO. P0555/P0521/P0550

EQPT. LOCATION

OWNER

ADDRESS

CUSTOMER

MOLDED CASE CIRCUIT BREAKER

NONADJUSTABLE

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 4-17-2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #32

EQUIPMENT ID TEST STATUSSUBSTATION GND FLOOR MECH RM PANEL NB Pass

240VOLTAGE

NA FRAME SIZE/RATING PLUG

FPE TYPE NEJ

INT. RATING

VOLTAGE

FRAME SIZE/RATING PLUG

VOLTAGE

INT. RATINGFRAME SIZE/RATING PLUG

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

ACROSS OPEN POLE

POLE - POLE - GND

125 INT. RATING NA

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

1 POLE - POLE - GND

ACROSS OPEN POLE

AS FOUND AS LEFT AS FOUND AS LEFT AS FOUND AS LEFT

MANUFACTURER

MAIN (ECB)

CONTACT RESISTANCE IN MICROHMS

TIME AT 300% RATED CURRENT IN SECONDS

INSTANT TESTED ON * SETTING TRIP / NO TRIP

INSULATION RESISTANCE IN MEGOHMS

AT * KV1

ACROSS OPEN POLE

POLE - POLE - GND

AS FOUND AS LEFT

597 597

17.51 17.51

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

674 674

16.95 16.95

N/A N/A

2200 2200

2200 2200

AS FOUND AS LEFT

692 692

23.13 23.13

N/A N/A

2200 2200

2200 2200

Acceptable NA

Acceptable

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

Acceptable NA

Acceptable NA

Acceptable NA

INSPECTED CONDITION CLEAN/LUBE

NA

OVERALL CLEANLINESS

MECHANICAL CONDITION

Operation

DESCRIPTION

ANCHORAGE AND ALIGNMENT

CONTACT FINGERS

ARC CHUTES

FRONT IDENTIFICATION - LEFT TO RIGHT: POLE 1 POLE 2 POLE 3

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

DESCRIPTION

MANUFACTURER

POLE 1 POLE 2 POLE 3FRONT IDENTIFICATION - LEFT TO RIGHT:

N/A

EQPT. LOCATION

ADDRESS

CUSTOMER

TRANSFORMER (<500KVA) TEST

TELEPHONE

VA Pittsburgh Healthcare Center; University Drive; Pittsburgh PA 15215

412-360-3664

JOB #4100 Allequippa St; Pittsburgh PA 15213

Department of Veterans Affairs PAGE

86301680

CUSTOMER REPRESENTATIVE Todd Guarnieri@va.gov

DATE 04/16/2020 TEMPERATURE 70 °F HUMIDITY 35 % (HEINZ) BLDG #49

EQUIPMENT ID TEST STATUSSUBSTATION 1A168 B49-T2 (MDP) Pass

Matthew Moore / Keith SpearTESTED BY:

www.abm.comABM Electrical Power Solutions 56710, REVISED 8/5/2019

REVIEWED BY:EQPT. INVENTORY NO. P0140

VISUAL AND MECHANICAL INSPECTION

INSPECT PHYSICAL AND MECHANICAL CONDITION

VERIFY FANS OPERATE (IF APPLICABLE)

INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING

INSPECTION REPORT

FAIL

FAIL

FAIL

PASS

PASS

PASS

INSPECTION REMARKS

NO FANS

3.37838

1,000

2.17865

1,000

3.37838

MINUTES

PRIMARY TO

GROUND

SECONDARY TO

GROUND

PRIMARY TO

SECONDARY

TEST…

This is the start of the file's text. The full file is on GovTribe.