S02 Drawings - 36C24425R0001 EEPP 3 .pdf

PDF 29 MB Posted

Attached to
S112--Correct Power Deficiencies - EEPG III
Solicitation number
36C24425R0001
Issued by

About this file

This document appears to be related to a Pre-Solicitation for a Request for Proposal (RFP) issued by the Department of Veterans Affairs Veterans Integrated Service Network 4 (VISN 4) for the Erie VA Medical Center. The intended contract is for Construction Services related to the Correct Power Deficiencies EEPG III project at the Erie VAMC. The contract will be a single, firm fixed-price award with a 365-calendar day period of performance. The contract will be set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), with a NAICS code of 236220 (Commercial & Institutional Building Construction) and a small business size standard of $45 million in annual receipts. The estimated construction cost range is between $2,000,000 and $5,000,000. The solicitation will be posted on or about November 19, 2024, and a pre-bid conference/site visit will be scheduled approximately one week after posting. All offerors must be verified in the Veterans Small Business Certification (VetCert) System at the time of proposal submittal.

View the file

Other files

File Type Posted
S04 Sign-In Sheet 36C24425R0001 12-10-24 .pdf PDF
S06 Amend. A0003 to 36C24425R0001 01-02-25 .docx DOCX document
36C24425R0001 0003_1.docx DOCX document
SWBD-2A 600A SPARE.jpg JPG image
E-SWGR-1 LINE UP.jpg JPG image
SWBD-2B NAME PLATE.jpg JPG image
PP-1 LINE UP.jpg JPG image
E-SWGR-1 BREAKER.jpg JPG image
E-SWBD-2A NAME PLATE.jpg JPG image
E-SWGR-1 NAME PLATE.jpg JPG image
36C24425R0001 0002.docx DOCX document
E-SWBD-2A BREAKER 2.jpg JPG image
E-SWBD-2A BREAKER 1.jpg JPG image
SWBD-2A NAME PLATE.jpg JPG image
PNL. PP-1 NAME PLATE.jpg JPG image
S05 Question and Responses 36C24425R0001_.doc DOC document
SG-PP1.docx DOCX document
SWBD-2B LINEUP.jpg JPG image
SWBD-2A LINEUP.jpg JPG image
36C24425R0001_3.docx DOCX document
S06 Amend 0001 to 36C24425R0001 11-26-24 .docx DOCX document
P03 Sole Source Justification - JCI Metasys - redacted .pdf PDF
EXHIBIT B - Subcontractor Information and Consent Form .docx DOCX document
S02 Wage Determination 10-25-24 .pdf PDF
EXHIBIT D - Sample Letter for PPQ.docx DOCX document
P03 Sole Source Justification - BEST locksets - Redacted .pdf PDF
P03 Sole Source Justification - Notifier System - redacted .pdf PDF
P03 Sole Source Justification - Generac Generator - Redacted.pdf PDF
S02 Solicitation 36C24425R0001 11-12-24 .docx DOCX document
36C24425R0001_2.docx DOCX document
EXHIBIT C - Past Performance Questionnaire .docx DOCX document
S02 Specifications - 36C24425R0001 EEPP 3 .pdf PDF
EXHIBIT A - Statement of Prior Experience.docx DOCX document
36C24425R0001_1.docx DOCX document
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NORTH

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

SITE

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

COVER SHEET &

DRAWING INDEX

GI001

DRTH

CO

W

W W

W

W

W

S

T

E

E

CO

CO

W

W W

W

W

W

S

T

E

E

E

T

CIVIL

PROPOSED CONDITIONS SITE PLAN

CS101

DJLJRS

562-21-708

2023-07-12

KEYPLAN

BLDG 8

BLDG 14

BLDG 18

EAST 38th STREET

BL

D

G

BL

DG

6BL

D

G

BLDG 1

O

LD

F

RE

NC

H

RO

AD

BL

DG

SITE

AREA OF

WORK

AREA OF

WORK

PROPOSED SITE PLANEXISTING SITE PLAN

NO. DESCRIPTION DATE

VA FORM 08-6231

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

321 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

A

C

D

E

F

Civil Engineering:

PENNTERRA ENGINEERING, INC.

AutoCAD SHX Text

TANK

AutoCAD SHX Text F

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text Fire

AutoCAD SHX Text Fire

AutoCAD SHX Text

NO PARKING

AutoCAD SHX Text Fire

AutoCAD SHX Text Shed

AutoCAD SHX Text Fire

AutoCAD SHX Text Conn

AutoCAD SHX Text

%%UPARKING

AutoCAD SHX Text H

AutoCAD SHX Text Salt

AutoCAD SHX Text (Location Approximate)

AutoCAD SHX Text Trans- former

AutoCAD SHX Text Ex. Building 11

AutoCAD SHX Text Ex. Pump House

AutoCAD SHX Text Ex. Building 6

AutoCAD SHX Text Underground Storm Water Retention Area

AutoCAD SHX Text Ex Window Well Not Field Verified

AutoCAD SHX Text Ex. Enclosed Structure Not Field Verified

AutoCAD SHX Text

PROPOSED GENERATOR (REFER TO ELECTRICAL PLANS)

AutoCAD SHX Text

PROPOSED ELECTRIC LINE FOR NEW GENERATOR (REFER TO ELECTRICAL PLANS)

AutoCAD SHX Text

PROPOSED 12' GATE ENTRANCE

AutoCAD SHX Text

CONNECT NEW FENCE TO EXISTING

AutoCAD SHX Text

CONNECT NEW FENCE TO EXISTING

AutoCAD SHX Text 850.97

AutoCAD SHX Text 850.32

AutoCAD SHX Text 851.20

AutoCAD SHX Text 851.32

AutoCAD SHX Text 850.82

AutoCAD SHX Text

1,512 S.F. ASPHALT EXPANSION AREA

AutoCAD SHX Text N

AutoCAD SHX Text

MAGNETIC

AutoCAD SHX Text

TANK

AutoCAD SHX Text F

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text W

AutoCAD SHX Text Fire

AutoCAD SHX Text Fire

AutoCAD SHX Text

NO PARKING

AutoCAD SHX Text Fire

AutoCAD SHX Text Shed

AutoCAD SHX Text Fire

AutoCAD SHX Text Conn

AutoCAD SHX Text

%%UPARKING

AutoCAD SHX Text H

AutoCAD SHX Text Salt

AutoCAD SHX Text (Location Approximate)

AutoCAD SHX Text Trans- former

AutoCAD SHX Text Edge of conduit duct bank

AutoCAD SHX Text Ex. Water Line "3-5' Deep"

AutoCAD SHX Text Ex. Electric Line "5-7' Deep"

AutoCAD SHX Text Ex. Building 11

AutoCAD SHX Text Ex. Pump House

AutoCAD SHX Text Ex. Building 6

AutoCAD SHX Text Underground Storm Water Retention Area

AutoCAD SHX Text Ex. Communications Lines As Shown On VA Mapping (Not Field Verified)

AutoCAD SHX Text Ex. Generators

AutoCAD SHX Text Ex. Electric Line As Shown On VA Mapping (Not Field Verified)

AutoCAD SHX Text Ex. Gas Regulator Set

AutoCAD SHX Text Ex. Water Tank

AutoCAD SHX Text Ex. Storm Pipe As Shown On VA Plans (Not Field Verified)

AutoCAD SHX Text Ex. Gas Lines 1'-2' Deep

AutoCAD SHX Text

(TO BE REMOVED)

AutoCAD SHX Text Ex. Unknown Utility Lines (Assumed Electric)

AutoCAD SHX Text Ex. Generator Connection Cabinet

AutoCAD SHX Text Ex. Above Ground Gas Lines, Valves, Regulators and Generator Feeds

AutoCAD SHX Text Ex. Light Mast On Fence

AutoCAD SHX Text Ex. Water Line 3'-4' Deep

AutoCAD SHX Text Ex. Electric Line 5' Deep

AutoCAD SHX Text Ex. Electric Lines 1'-2' Deep

AutoCAD SHX Text Ex Window Well Not Field Verified

AutoCAD SHX Text Ex. Enclosed Structure Not Field Verified

AutoCAD SHX Text Seams In Pavement

AutoCAD SHX Text Seams In Pavement

AutoCAD SHX Text Ex. Unknown Utility Lines (Assumed Electric)

AutoCAD SHX Text Ex. Fuel Tank

AutoCAD SHX Text

(TO BE REMOVED)

AutoCAD SHX Text Ex. Trees

AutoCAD SHX Text

(TO BE PROTECTED WITH FILTREXX GROSOXX BERM DURING CONSTRUCTION)

AutoCAD SHX Text Ex. Building 12

AutoCAD SHX Text Ex. 8' Steel Slat Fence

AutoCAD SHX Text Ex. 8' Steel Slat Fence

AutoCAD SHX Text Ex. Gasline

AutoCAD SHX Text

(TO BE REMOVED)

AutoCAD SHX Text Ex. Electrical Duct Bank

AutoCAD SHX Text

(TO BE ABANDONED)

AutoCAD SHX Text Ex. Electrical Duct Bank

AutoCAD SHX Text Ex. Electrical Line

AutoCAD SHX Text

(TO BE REMOVED)

AutoCAD SHX Text Ex. Electrical Line

AutoCAD SHX Text

(TO BE REMOVED)

AutoCAD SHX Text Existing Underground Electric w/ Manhole

AutoCAD SHX Text Existing Underground Telephone

AutoCAD SHX Text Existing Waterline

AutoCAD SHX Text Existing Gas Line

AutoCAD SHX Text Existing Storm Sewer w/ Inlet

AutoCAD SHX Text S

AutoCAD SHX Text Existing Sanitary Sewer w/ Manhole

AutoCAD SHX Text Existing Fire Line w/ Fire Alarm Junction Box

AutoCAD SHX Text F

AutoCAD SHX Text Existing Overhead Utility Line w/ Pole

AutoCAD SHX Text Existing Underground Electric Ductbank

AutoCAD SHX Text Existing Sign

AutoCAD SHX Text Existing Fire Hydrant

AutoCAD SHX Text Existing Steam Line

AutoCAD SHX Text Existing Light Pole

AutoCAD SHX Text Existing Tree

AutoCAD SHX Text Existing Bush

AutoCAD SHX Text Existing Treeline

AutoCAD SHX Text Existing Building

AutoCAD SHX Text Existing Fenceline

AutoCAD SHX Text

EXISTING FEATURES LEGEND

AutoCAD SHX Text

PROPOSED FEATURES LEGEND

AutoCAD SHX Text Existing Property Line

AutoCAD SHX Text Existing Property Line Adjoiner

AutoCAD SHX Text

PROPOSED EDGE OF PAVEMENT

AutoCAD SHX Text

PROPOSED FENCE / TYPE

AutoCAD SHX Text PROPOSED MINOR CONTOURS W/ ELEVATION (1's & 2's)

AutoCAD SHX Text PROPOSED MAJOR CONTOURS W/ ELEVATION (5's & 10's)

AutoCAD SHX Text

EXISTING BUILDING TO BE REMOVED

AutoCAD SHX Text

DEMOLITION FEATURES LEGEND

AutoCAD SHX Text

18" FILTREXX GROSOXX TREE WELL PROTECTION BERM

AutoCAD SHX Text

EXISTING FENCELINE TO BE REMOVED

AutoCAD SHX Text

PROPOSED SPOT ELEVATION

AutoCAD SHX Text 69.87

AutoCAD SHX Text

EXISTING UNDERGROUND ELECTRIC LINE TO BE REMOVED

AutoCAD SHX Text

EXISTING GAS LINE TO BE REMOVED

AutoCAD SHX Text

PLAN ABBREVIATIONS LEGEND

AutoCAD SHX Text CO = CLEAN-OUT FOR UNDERGROUND PIPE DC = DEPRESSED CURB D.I.P. = DUCTILE IRON PIPE EX = EXISTING FFE = FINISHED FLOOR ELEVATION GM = GAS METER HDPEP = HIGH DENSITY POLYETHYLENE PIPE H.P. = HIGH POINT ELEVATION INV. = INVERT ELEVATION LF = LINEAR FEET MH = MANHOLE PR = PROPOSED RB = RECORD BOOK TBR = TO BE REMOVED TC = TOP OF CASTING TG = TOP OF GRATE

AutoCAD SHX Text 1 inch = 20 ft.

AutoCAD SHX Text

( IN FEET )

AutoCAD SHX Text

GRAPHIC SCALE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text %%uGENERAL NOTES

AutoCAD SHX Text

1. All temporary Erosion and Sedimentation measures shall be in accordance with Sections 01 57 19, 31 20 00 All temporary Erosion and Sedimentation measures shall be in accordance with Sections 01 57 19, 31 20 00 and 32 90 00. 2. All site demolition shall be in accordance with sections 02 41 00 and 22 05 11 Para 3.6C. All site demolition shall be in accordance with sections 02 41 00 and 22 05 11 Para 3.6C. 3. Trench backfill compaction requirements shall be per section 31 20 00. Trench backfill compaction requirements shall be per section 31 20 00. 4. Contractor shall hand dig all excavation within six feet of any known utilities. Contractor shall hand dig all excavation within six feet of any known utilities. 5. All turf work shall be in accordance with sections 31 20 00 and 32 90 00. All turf work shall be in accordance with sections 31 20 00 and 32 90 00. 6. The contractor is fully responsible for verifying and locating all underground utilities within the work area and The contractor is fully responsible for verifying and locating all underground utilities within the work area and shall provide utility location service prior to construction. The contractor shall verify the locations of manholes, inlets, valves, inverts, etc. depicted upon these plans. The contractor (with prior VA approval) shall test pit existing utilities as deemed necessary within the limits of construction to verify the exact location and depth, as required. Any noted discrepancies shall be reported to PennTerra Engineering, Inc.

AutoCAD SHX Text

M-R PROJECT NO: 0517-0002

CIVIL

DETAILS

CS501

DJLJRS

562-21-708

SITE

NO. DESCRIPTION DATE

VA FORM 08-6231

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

321 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

A

C

D

E

F

Civil Engineering:

PENNTERRA ENGINEERING, INC.

2023-07-12

BID DOCUMENTS

NOT FOR CONSTRUCTION

Double gate Arrangement

16" [4.1mm]

TYPICAL

3" [76.2mm]

(Latch Clearance) Ameristar Standard

Leaf Widths 2" [50.8mm] (Hinge Clearance)

Over all Out to Out .2

2" [50.8mm] (Hinge Clearance)

4" [32.4mm]

16" [17.2mm]

7'

6'-6" Min.

Footing depth

2" [50.8mm]

2" [50.8mm]

Pale welded to rail

Gate Rail

Values shown are nominal and not to be used for installation purposes. See product specification for installation requirements.

Weld on Box Hinge

3" I-BEAM

Gate Upright 2" [50.8mm] x 12 ga.

Gate Rail 2" [50.8mm] x 12 ga.

4" [69.9mm] Pale

(.075 [1.69mm] wall)

8'

6'-6"

8' 7'

12" DIA. PIER

12" DIA. PIER

AutoCAD SHX Text

4 1/2" - SUPERPAVE WMA BASE COURSE

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

1 1/2" - SUPERPAVE WMA WEARING COURSE

AutoCAD SHX Text

4 1/2" - NO. 2A STONE SUB-BASE

AutoCAD SHX Text

WELL COMPACTED SUBGRADE

AutoCAD SHX Text

WEARING SURFACE:

AutoCAD SHX Text

SUPERPAVE ASPHALT MIXTURE DESIGN, WMA WEARING COURSE

AutoCAD SHX Text

PG 64-22, < 0.3 MILLION ESAL'S, 9.5 MM MIX,

AutoCAD SHX Text

1-1/2" DEPTH, SRL-M

AutoCAD SHX Text

BASE COURSE SURFACE:

AutoCAD SHX Text

SUPERPAVE ASPHALT MIXTURE DESIGN, WMA BASE COURSE

AutoCAD SHX Text

PG 64-22, < 0.3 MILLION ESAL'S, 25.0 MM MIX,

AutoCAD SHX Text

4 1/2" DEPTH

AutoCAD SHX Text

STANDARD PAVEMENT SECTION

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

TEMPORARY E&S CONTROL - COMPOST FILTER SOCK DETAIL

AutoCAD SHX Text

WATER FLOW

AutoCAD SHX Text

PLAN VIEW

AutoCAD SHX Text

UPSLOPE

AutoCAD SHX Text

DOWNSLOPE

AutoCAD SHX Text

AREA TO BE PROTECTED

AutoCAD SHX Text

10' LINEAR SPACING (TYP.)

AutoCAD SHX Text

NOTES:

AutoCAD SHX Text

1. All material to meet EPA compost filter sock specifications. specifications. specifications. 2. Silt sock compost/soil/rock/seed fill to meet application requirements. 3. Silt socks depicted are for use on minimal slopes. Greater slopes may require larger silt socks per the Engineer. 4. Compost material to be dispersed on site, as determined by Engineer.

AutoCAD SHX Text

COMPOST FILTER SOCK

AutoCAD SHX Text

DISTURBED AREA

AutoCAD SHX Text

COMPOST FILTER SOCK

AutoCAD SHX Text

DISTURBED AREA

AutoCAD SHX Text

AREA TO BE PROTECTED

AutoCAD SHX Text

SECTION VIEW

AutoCAD SHX Text 3"-4"

AutoCAD SHX Text

(12" TYP.)

AutoCAD SHX Text

12" MIN.

AutoCAD SHX Text

BLOWN/PLACED FILTER MEDIA

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING CONTOUR

AutoCAD SHX Text 2"x2" WOODEN STAKE

AutoCAD SHX Text

PLACED 10' O.C.

AutoCAD SHX Text 2"x2" WOODEN STAKE

AutoCAD SHX Text

PLACED 10' O.C.

AutoCAD SHX Text Material Type

AutoCAD SHX Text Material Characteristics

AutoCAD SHX Text 3 mil HDPE

AutoCAD SHX Text 5 mil HDPE

AutoCAD SHX Text 5 mil HDPE

AutoCAD SHX Text Multi-Filament Polypropylene (MFPP)

AutoCAD SHX Text Heavy Duty Multi-Filament Polypropelene (HDMFPP)

AutoCAD SHX Text Photo- degradable

AutoCAD SHX Text Bio- degradable

AutoCAD SHX Text Photo- degradable

AutoCAD SHX Text Photo- degradable

AutoCAD SHX Text Photo- degradable

AutoCAD SHX Text Sock Diameters

AutoCAD SHX Text 12" 18"

AutoCAD SHX Text 12" 18" 24" 32"

AutoCAD SHX Text 12" 18" 24" 32"

AutoCAD SHX Text 12" 18" 24" 32"

AutoCAD SHX Text 12" 18" 24" 32"

AutoCAD SHX Text Mesh Opening

AutoCAD SHX Text 3/8"

AutoCAD SHX Text 1/8"

AutoCAD SHX Text 3/8"

AutoCAD SHX Text 3/8"

AutoCAD SHX Text 3/8"

AutoCAD SHX Text Tensile Strength

AutoCAD SHX Text 26 psi

AutoCAD SHX Text 26 psi

AutoCAD SHX Text 44 psi

AutoCAD SHX Text 202 psi

AutoCAD SHX Text Ultraviolet Stability % Original Strength (ASTM G-155)

AutoCAD SHX Text 23% at 1000 hr.

AutoCAD SHX Text 23% at 1000 hr.

AutoCAD SHX Text 100% at 1000 hr.

AutoCAD SHX Text 100% at 1000 hr.

AutoCAD SHX Text Minimum Functional Longevity

AutoCAD SHX Text 6 months

AutoCAD SHX Text 9 months

AutoCAD SHX Text 6 months

AutoCAD SHX Text 1 year

AutoCAD SHX Text 2 years

AutoCAD SHX Text Two-Ply Systems

AutoCAD SHX Text Inner Containment Netting

AutoCAD SHX Text HDPE biaxial net

AutoCAD SHX Text Continuously wound

AutoCAD SHX Text Fusion-welded junctures

AutoCAD SHX Text 3/4"x3/4" Max. aperture size

AutoCAD SHX Text Composite Polypropylene Fabric (Woven layer and non-woven fleece mechanically fused via needle punch)

AutoCAD SHX Text 3/16" Max. aperture size

AutoCAD SHX Text Sock fabrics composed of burlap may be used on projects lasting 6 months or less.

AutoCAD SHX Text TABLE 4.1 Compost Sock Fabric Minimum Specifications

AutoCAD SHX Text Outer Filtration Mesh

AutoCAD SHX Text Organic Matter Content

AutoCAD SHX Text Organic Portion

AutoCAD SHX Text pH

AutoCAD SHX Text Moisture Content

AutoCAD SHX Text Particle Size

AutoCAD SHX Text Soluble Salt Concentration

AutoCAD SHX Text 25%-100% (dry weight basis)

AutoCAD SHX Text Fibrous and elongated

AutoCAD SHX Text 5.5-8.5

AutoCAD SHX Text 30%-60%

AutoCAD SHX Text 30% - 50% pass through 3/8" sieve

AutoCAD SHX Text

5.0 dS/m (mmhos/cm) Maximum

AutoCAD SHX Text TABLE 4.2 Compost Standards

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

IMPASSE II ANTI-SCALE STEEL PANEL

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

3" I-BEAM FOR 3R EXT 8'T IMPASSE II

AutoCAD SHX Text

M-R PROJECT NO: 0517-0002

AutoCAD SHX Text NOTES: 1. SOXX SHALL BE USED TO PROTECT EXISTING TREE TRUNKS FROM FILL PLACEMENT. 2. SOXX SHALL BE FILLED WITH FILTREXX ENGINEERED SOIL (OR EQUAL) AND INCLUDE THE TURF GRASS PERMANENT SEEDING MIXTURE. 3. PRIOR TO PLACING FILL AROUND EXISTING TREES, INSTALL SOXX FILLED WITH MEDIA AND SEEDING OFFSET A MINIMUM OF 12" FROM THE TREE TRUNK.

AutoCAD SHX Text

18" WEIGHTED, SEEDED

AutoCAD SHX Text

SECTION VIEW

AutoCAD SHX Text

12" MIN.

AutoCAD SHX Text 2"x2" WOODEN STAKE

AutoCAD SHX Text

PLACED 10' O.C.

AutoCAD SHX Text

FILTREXX GROSOXX

AutoCAD SHX Text

18" FILTREXX GROSOXX TREE WELL PROTECTION BERM

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text NOTES: 1.) Post size depends on fence height, weight and wind loads. See IMPASSE post sizing chart. post sizing chart. 2.) See Ameristar gate table for standard out to outs. Custom gate openings available for special out to out/leaf widths. 3.) Additional styles of gate hardware are available on request. This could change the Latch & Hinge Clearance. 4.) Third rail optional. (Some heights noted require the third rail.)

AutoCAD SHX Text

NOT TO SCALE

IMPASSE II STRONGHOLD GATE DETAIL

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

N/A

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

ABBREVIATIONS & NOTES

S-001

DSER

EXISTING SWITCHGEAR BUILDING #11

EXISTING UNDERGROUND FUEL TANK

BUILDING #12

MECHANICAL YARD

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

SITE

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

KEYPLAN

AREA OF

WORK

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

DEMOLITION SITE PLAN

12-SD101

RPER

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

BUILDING #12 DEMOLITION

SECTIONS & ELEVATIONS

12-SD201

W

W

W PUMP HOUSE

EXISTING

SWITCHGEAR BUILDING #11

ROOF

EXISTING

WATER TANK

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

SITE

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

KEYPLAN

AREA OF

WORK

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

SITE PLAN

SS101

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

SITE

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

KEYPLAN

AREA OF

WORK

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

ENLARGED PARTIAL SITE PLAN

SS401

MEDICAL

GAS

STOR

2D50B

OXYGEN

STOR

2D50C

GAS STORAGE

2D38 (2E336)

LOADING DOCK

2D50

ELECTRICAL

EE200

OFFICE SUPPLY STORAGE

2D33

HOUSEKEEPING/E.M.S.

STORAGE 2D39

WAREHOUSE

2D28 (2E300)

SURGICAL STORAGE

2D34

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

KEYPLAN

AREA OF

WORK

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

PARTIAL FRAMING PLAN

BUILDING #01 - 2ND FLOOR

01-SF121

BC06-1

BC0

B C -1

BC07A-1

BC10A-1

ELECTRIC

BC11 (NB-59A)

FEC

PHONE

BC

J J

BC06-1

BC0

B C -1

BC07A-1

ELECTRIC

BC11 (NB-59A)

PHONE

BC1

2N214-1

2N216-1

2N215-1 OF

CORRIDOR

2C4 (2N210)

OF

ELEC

2C16

ELEC

2C14

R

2N214-1

2N216-1

2N215-1 OF

CORRIDOR

2C4 (2N210)

OF

ELEC

2C16

ELEC

2C14

J

J

SP1W465-1

ROOM

1W458)

(1W235)

ELECTRICAL

1B17

TOILET 1B15A

(1W458A)

SP1W465-1

M ROOM

(1W458)

(1W235)

ELECTRICAL

1B17

TOILET 1B15A

(1W458A)

R

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

KEYPLAN

AREA OF

WORK

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

ENLARGED PLANS

BLDG #01 - BASEMENT, 1ST & 2ND FLR

S-401

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

N/A

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

SECTIONS & DETAILS

S-501

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

N/A

Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

STRUCTURAL

SECTIONS & DETAILS

S-502 on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

N/A Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

ELECTRICAL

LEGENDS, NOTES, &

ABBREVIATIONS

E-001

DRRLIB

AutoCAD SHX Text

FUSE WITH RATING

AutoCAD SHX Text

MOLDED CASE CIRCUIT BREAKER

AutoCAD SHX Text

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

AutoCAD SHX Text

TRANSFORMER, DELTA CONNECTION

AutoCAD SHX Text

TRANSFORMER, SINGLE LINE

AutoCAD SHX Text

GROUND ROD

AutoCAD SHX Text

JUNCTION BOX

AutoCAD SHX Text

PULL BOX

AutoCAD SHX Text

VARIABLE FREQUENCY DRIVE

AutoCAD SHX Text

GENERATOR, POWER

AutoCAD SHX Text

DISCONNECT SWITCH, FUSED

AutoCAD SHX Text

DISCONNECT SWITCH, UNFUSED

AutoCAD SHX Text

STARTER, COMBINATION WITH DISCONNECT SWITCH

AutoCAD SHX Text

STARTER OR MOTOR CONTROLLER

AutoCAD SHX Text

METER

AutoCAD SHX Text

WATT-HOUR METER

AutoCAD SHX Text

TRANSFORMER, PLAN

AutoCAD SHX Text

MOTOR

AutoCAD SHX Text

TRANSFORMER, WYE CONNECTION

AutoCAD SHX Text

PUSH BUTTON

AutoCAD SHX Text

RECEPTACLE, DUPLEX

AutoCAD SHX Text

RECEPTACLE, DUPLEX ISOLATED GROUND

AutoCAD SHX Text

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER

AutoCAD SHX Text

RECEPTACLE, QUADRAPLEX

AutoCAD SHX Text

RECEPTACLE, DUPLEX W/ GROUND FAULT CIRCUIT INTERRUPTER & ISOLATED GROUND

AutoCAD SHX Text

RECEPTACLE, QUADRAPLEX ISOLATED GROUND

AutoCAD SHX Text RECEPTACLE, SPECIAL PURPOSE A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R. B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R. C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R. D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R. E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R. F = 208V, 30A, 3 PHASE, 3-POLE, 4W, NEMA 15-30R. G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R. H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

AutoCAD SHX Text ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.

AutoCAD SHX Text

ELECTRICAL SYMBOLS

AutoCAD SHX Text

RECEPTACLE, QUADRAPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER

AutoCAD SHX Text

DP#__

AutoCAD SHX Text

DISTRIBUTION PANEL

AutoCAD SHX Text

LP#__/PP#__

AutoCAD SHX Text

LIGHTING OR POWER PANEL

AutoCAD SHX Text

PANELBOARD CABINET, FLUSH MOUNTED

AutoCAD SHX Text

PANELBOARD CABINET, SURFACE MOUNTED

AutoCAD SHX Text RECEPTACLE, DUPLEX (DASHED LINE INDICATES FLOOR MOUNTED, TYPICAL ALL TYPES OF RECEPTACLES)

AutoCAD SHX Text

MULTIPLE KEY NOTES APPLYING TO THE SAME ITEM

AutoCAD SHX Text

CR

AutoCAD SHX Text

ST

AutoCAD SHX Text

CONTROL RELAY; COIL RELAY

AutoCAD SHX Text

SHUNT-TRIP COIL

AutoCAD SHX Text

TRANSFORMER, SINGLE LINE

AutoCAD SHX Text

PRIMARY

AutoCAD SHX Text

SECONDARY

AutoCAD SHX Text

TRANSFORMER SIZE

AutoCAD SHX Text

INDICATES EQUIPMENT TO BE DEMOLISHED

AutoCAD SHX Text

DWM

AutoCAD SHX Text

DIGITAL POWER METER

AutoCAD SHX Text

CURRENT TRANSFORMER

AutoCAD SHX Text

POTENTIAL TRANSFORMER

AutoCAD SHX Text BRANCH CIRCUIT HOMERUN. HALF-ARROWS INDICATE NUMBER OF CIRCUITS. ONE SEPARATE GREEN GROUNDING CONDUCTOR SHALL BE PROVIDED FOR EACH HOMERUN; NOT SHOWN

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text J

AutoCAD SHX Text G

AutoCAD SHX Text

HP

AutoCAD SHX Text

CIRCUIT #

AutoCAD SHX Text

RECEPTACLE, DUPLEX - EMERGENCY

AutoCAD SHX Text

RECEPTACLE, QUADRAPLEX - EMERGENCY

AutoCAD SHX Text

RECEPTACLE, QUADRAPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER & ISOLATED GROUND

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text

WH

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EMERGENCY POWER OFF

AutoCAD SHX Text

LIGHTING OR POWER PANEL, SINGLE LINE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 112.5

AutoCAD SHX Text

ENCLOSED CIRCUIT BREAKER

AutoCAD SHX Text ???A/3P

AutoCAD SHX Text

ENCLOSED CIRCUIT BREAKER, SINGLE LINE

AutoCAD SHX Text

ENCLOSED CIRCUIT BREAKER

AutoCAD SHX Text

RECEPTACLE, DUPLEX - CEILING

AutoCAD SHX Text

RECEPTACLE, SIMPLEX - EMERGENCY

AutoCAD SHX Text

RECEPTACLE, SIMPLEX

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EP101

AutoCAD SHX Text

KEY NOTE SYMBOL

AutoCAD SHX Text

DETAIL IDENTIFIER DETAIL # DRAWING # (WHERE DETAIL IS FOUND)

AutoCAD SHX Text

CEILING MOUNTED, SINGLE CONVENIENCE OUTLET

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

OR

AutoCAD SHX Text

ELECTRICAL ABBREVIATIONS

AutoCAD SHX Text

TELE/DATA OUTLET

AutoCAD SHX Text

TELEPHONE OUTLET

AutoCAD SHX Text

DATA OUTLET

AutoCAD SHX Text

AUX/DATA/COMMUNICATION SYMBOLS

AutoCAD SHX Text

SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND

AutoCAD SHX Text SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND. MTD. 7'-6" AFF UNLESS MTD. 7'-6" AFF UNLESS OTHERWISE NOTED.

AutoCAD SHX Text

TV

AutoCAD SHX Text

TELEVISION OUTLET

AutoCAD SHX Text S

AutoCAD SHX Text X

AutoCAD SHX Text S

AutoCAD SHX Text X

AutoCAD SHX Text

SWITCH BLANK = SINGLE POLE M = MOTOR RATED

AutoCAD SHX Text

AutoCAD SHX Text

FIRE ALARM SYMBOLS

AutoCAD SHX Text

LIGHTING SYMBOLS

AutoCAD SHX Text H

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text

FACP

AutoCAD SHX Text

CM

AutoCAD SHX Text

FS

AutoCAD SHX Text

RA

AutoCAD SHX Text

NAC

AutoCAD SHX Text H

AutoCAD SHX Text

SD

AutoCAD SHX Text

TS

AutoCAD SHX Text

PS

AutoCAD SHX Text C

AutoCAD SHX Text

CD

AutoCAD SHX Text

SS

AutoCAD SHX Text C

AutoCAD SHX Text

CD

AutoCAD SHX Text

MM

AutoCAD SHX Text R

AutoCAD SHX Text

DH

AutoCAD SHX Text

DR

AutoCAD SHX Text

RTS

AutoCAD SHX Text

FATC

AutoCAD SHX Text FIRE ALARM CONTROL PANEL (MOUNT 6'-0" ABOVE FINISHED FLOOR TO TOP) PROVIDED WITH BACK-UP BATTERIES RATED FOR 24 HOUR MIN. SERVICE / 5 MINUTES IN ALARM MODE

AutoCAD SHX Text

FIRE ALARM TERMINAL CABINET (MOUNT 5'-0" ABOVE FINISHED FLOOR TO TOP)

AutoCAD SHX Text

FIRE ALARM REMOTE ANNUNIATOR (MOUNT 5'-0" ABOVE FINISHED FLOOR TO TOP)

AutoCAD SHX Text NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL (MOUNT 6'-0" ABOVE FINISHED FLOOR TO TOP) PROVIDED WITH BACK-UP BATTERIES RATED FOR 24 HOUR MIN. SERVICE / 5 MINUTES IN ALARM MODE

AutoCAD SHX Text

MANUAL PULLSTATION (MOUNT 48" ABOVE FINISHED FLOOR TO TOP OF DEVICE)

AutoCAD SHX Text DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS: R/T = COMBINATION F = FIXED TEMP. RISE (135°) F = FIXED TEMP. RISE (135°) R/C = RATE COMPENSATION R = RATE OFR = RATE OF

AutoCAD SHX Text DETECTOR; LETTER INDICATES AS FOLLOWS: BLANK = PHOTOELECTRIC SMOKE DETECTOR H = HEAT I = IONIZATION IH = IONIZATION AND HEAT IP = IONIZATION AND PHOTOELECTRIC PH = PHOTOELECTRIC AND HEAT IPH = IONIZATION, PHOTOELECTRIC, AND HEAT

AutoCAD SHX Text DETECTOR, SMOKE, FOR DUCT (FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR; WIRED BY THE ELECTRICAL CONTRACTOR)

AutoCAD SHX Text SPRINKLER ALARM VALVE TAMPER SWITCH (FURNISHED AND INSTALLED BY OTHERS; WIRED BY THE ELECTRICAL CONTRACTOR)

AutoCAD SHX Text SPRINKLER ALARM VALVE WATER FLOW SWITCH (FURNISHED AND INSTALLED BY OTHERS; WIRED BY THE ELECTRICAL CONTRACTOR)

AutoCAD SHX Text SPRINKLER ALARM PRESSURE SWITCH (FURNISHED AND INSTALLED BY OTHERS; WIRED BY THE ELECTRICAL CONTRACTOR)

AutoCAD SHX Text AUTO SYNC STROBE UNIT WITH SELECTABLE CANDELA ADA COMPLIANT (MOUNT 80" ABOVE FINISHED FLOOR OR 6" BELOW FINISHED CEILING TO TOP OF DEVICE) BLANK = WALL MOUNTED C = CEILING P = PENDANT C = CEILING P = PENDANT P = PENDANT CD = CANDELA LEVEL

AutoCAD SHX Text FIRE SPEAKER UNIT BLANK = WALL MOUNTED C = CEILING P = PENDANTC = CEILING P = PENDANTP = PENDANT

AutoCAD SHX Text FIRE SPEAKER STROBE (AUTO SYNC) UNIT WITH SELECTABLE CANDELA; ADA COMPLIANT (MOUNT 80" ABOVE FINISHED FLOOR OR 6" BELOW FINISHED CEILING TO TOP OF DEVICE) BLANK = WALL MOUNTED C = CEILING P = PENDANT C = CEILING P = PENDANT P = PENDANT CD = CANDELA LEVEL

AutoCAD SHX Text

CONTROL MODULE

AutoCAD SHX Text

MONITORING MODULE

AutoCAD SHX Text

120VAC, 20A RELAY IN NEMA 1 ENLCOSURE

AutoCAD SHX Text

MAGNETIC DOOR HOLDER

AutoCAD SHX Text

ELECTROMAGNETIC DOOR RELEASE OR DOOR RELEASE RELAY

AutoCAD SHX Text

DUCT SMOKE DETECTOR REMOTE TEST/TEST SWITCH

AutoCAD SHX Text

END OF LINE RESISTOR

AutoCAD SHX Text CARD ACCESS READER; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION D-DESK F-FLUSH H-HIDDEN M-MULLION F-FLUSH H-HIDDEN M-MULLION H-HIDDEN M-MULLION M-MULLION P-PEDESTAL R-RACK S-SURFACE W-WALL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL H-ELEVATOR HALL CALL M-MAG STRIP P-PROXIMITY S-SMART CARD P-PROXIMITY S-SMART CARD S-SMART CARD T-TOKEN

AutoCAD SHX Text ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION D-DESK F-FLUSH H-HIDDEN M-MULLION F-FLUSH H-HIDDEN M-MULLION H-HIDDEN M-MULLION M-MULLION P-PEDESTAL R-RACK S-SURFACE W-WALL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKEH-HYBRID L-LATCH SET M-MAGNETIC S-STRIKEL-LATCH SET M-MAGNETIC S-STRIKEM-MAGNETIC S-STRIKES-STRIKE

AutoCAD SHX Text MOTION DETECTOR; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION D-DESK F-FLUSH H-HIDDEN M-MULLION F-FLUSH H-HIDDEN M-MULLION H-HIDDEN M-MULLION M-MULLION P-PEDESTAL R-RACK S-SURFACE W-WALL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC IR-INFRARED M-MICROWAVE U-ULTRASONIC M-MICROWAVE U-ULTRASONIC U-ULTRASONIC X-REQUEST-FOR-EXIT

AutoCAD SHX Text SECURITY ACCESS, VIDEO CAMERA WITH LENS M = MOTION DETECTOR PZ = MOTION DETECTOR WITH PAN AND ZOOM PTZ = MOTION DETECTOR WITH PAN, TILT, AND ZOOM

AutoCAD SHX Text

SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW

AutoCAD SHX Text PUSH BUTTON; LETTER INDICATES AS FOLLOWS: M=MOUNT C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION D-DESK F-FLUSH H-HIDDEN M-MULLION F-FLUSH H-HIDDEN M-MULLION H-HIDDEN M-MULLION M-MULLION P-PEDESTAL R-RACK S-SURFACE W-WALL R-RACK S-SURFACE W-WALL S-SURFACE W-WALL W-WALL T=TECHNOLOGY/TYPE B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE D-DURESS P-PANIC R-DOOR RELEASE P-PANIC R-DOOR RELEASE R-DOOR RELEASE X-REQUEST-FOR-EXIT

AutoCAD SHX Text

SECURITY SYMBOLS

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text T

AutoCAD SHX Text 40%%d

AutoCAD SHX Text M

AutoCAD SHX Text

PTZ

AutoCAD SHX Text

AIR TERMINAL

AutoCAD SHX Text

WIRELESS ACCESS POINT

AutoCAD SHX Text

DENOTES MOUNTING HEIGHT OF +60" A.F.F. TYPICAL ALL TYPES OF OUTLETS

AutoCAD SHX Text

AutoCAD SHX Text

ELECTRICAL SYMBOLS

AutoCAD SHX Text FLOORBOX. FB1 = 2 COMPARTMENT FLOOR BOX WITH (1) QUAD RECEPTACLE AND (1) QUAD DATA FB2 = 3 COMPARTMENT FLOOR BOX WITH (1) QUAD RECEPTACLE, (1) QUAD DATA AND A 2-1/2" CONDUIT FOR RGB AV

AutoCAD SHX Text

FB1

AutoCAD SHX Text

DOWN CONDUCTOR AT AIR TERMINAL

AutoCAD SHX Text

CONDUCTOR DROP FROM HIGHER ROOF TO LOWER ROOF

AutoCAD SHX Text SWITCH a = (LOWER CASE) LIGHT CONTROLLED BY TAGGED SWITCH = (LOWER CASE) LIGHT CONTROLLED BY TAGGED SWITCH 2 = 2 POLE = 2 POLE 3 = 3 WAY = 3 WAY 4 = 4 WAY = 4 WAY D = DIMMER = DIMMER F = FUSED SWITCH = FUSED SWITCH IL = ILLUMINATED TOGGLE = ILLUMINATED TOGGLE ILLUMINATED TOGGLE K = KEY OPERATED = KEY OPERATED L = LOCK = LOCK LM = LOW VOLTAGE MASTER = LOW VOLTAGE MASTER LV = LOW VOLTAGE = LOW VOLTAGE M = MANUAL MOTOR STARTING = MANUAL MOTOR STARTING MC = MOMENTARY CONTACT = MOMENTARY CONTACT MP = MOTOR SNAP W/PILOT LIGHT (THERMAL TYPE) = MOTOR SNAP W/PILOT LIGHT (THERMAL TYPE) OS = OCCUPANCY SENSOR (W/ MANUAL OVERRIDE) = OCCUPANCY SENSOR (W/ MANUAL OVERRIDE) P = WITH PILOT LIGHT = WITH PILOT LIGHT PB = PUSH BUTTON STATION = PUSH BUTTON STATION RC = REMOTE CONTROL = REMOTE CONTROL WP = WEATHER PROOF = WEATHER PROOF X = EXPLOSION PROOF= EXPLOSION PROOF

AutoCAD SHX Text

OCCUPANCY SENSOR - WALL MOUNTED

AutoCAD SHX Text

OCCUPANCY SENSOR - CEILING MOUNTED

AutoCAD SHX Text

EMERGENCY LIGHT WITH 2 HEADS (90 MINUTE BATTERY)

AutoCAD SHX Text A

AutoCAD SHX Text EXIT SIGN: ARROW DIRECTION INDICATED ON PLANS. SINGLE SHADING INDICATES SINGLE FACE OR 2 SHADED AREAS INDICATES DOUBLE FACED UNIT.

AutoCAD SHX Text

PX-##

AutoCAD SHX Text LIGHTING FIXTURE: UPPER CASE LETTER ABOVE FIXTURE DENOTES FIXTURE TYPE IN LIGHTING FIXTURE SCHEDULE. UPPER CASE LETTERS BELOW INDICATES PANEL AND/OR CIRCUIT POWERING FIXTURE. LOWER CASE LETTERS INDICATE SWITCH LEG.

AutoCAD SHX Text HALF SHADED FIXTURE INDICATES FIXTURE IS ON EMERGENCY CIRCUIT OR NIGHT LIGHT (SEE FIXTURE SCHEDULE)

AutoCAD SHX Text

EMERGENCY COMBO LIGHT/SIGN WITH 2 HEADS (90 MINUTE BATTERY)

AutoCAD SHX Text

EMERGENCY LIGHT REMOTE DUAL HEAD

AutoCAD SHX Text

EMERGENCY LIGHT REMOTE SINGLE HEAD

AutoCAD SHX Text

PC

AutoCAD SHX Text

PHOTOCELL

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text a

AutoCAD SHX Text

OS

AutoCAD SHX Text

OS

AutoCAD SHX Text

WAP

AutoCAD SHX Text

INDICATES POINT OF DISCONNECT

AutoCAD SHX Text

FIRE

AutoCAD SHX Text

CEILING - HEIGHT VARIES

AutoCAD SHX Text

ALIGN WHEN MOUNTED ON SAME WALL

AutoCAD SHX Text

LIGHT SWITCH OR DIMMER

AutoCAD SHX Text

FIRE ALARM PULL STATION

AutoCAD SHX Text

TELEPHONE OR DATA JACK

AutoCAD SHX Text MOUNT STROBE, SPEAKER/STOBE OR HORN/STROBE DEVICE 80" (MIN), 96" (MAX.) AFF TO STROBE LENS.

AutoCAD SHX Text

WALL MOUNTED TELEPHONE

AutoCAD SHX Text RECEPTACLE: ABOVE COUNTER REFER TO ARCH DWGS FOR HEIGHT. (GFCI TYPE IF WITHIN 6' OF WATER SOURCE)

AutoCAD SHX Text

RECEPTACLE

AutoCAD SHX Text 5'-0"

AutoCAD SHX Text 5'-0"

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

AutoCAD SHX Text

TYPICAL DEVICE MOUNTING HEIGHTS

AutoCAD SHX Text

ALL DIMENSIONS SHOWN ARE TYPICAL UNLESS OTHERWISE NOTED.

AutoCAD SHX Text

NTS

AutoCAD SHX Text

WALL MOUNTED TV/MONITOR. REFER TO ARCH DWGS FOR HEIGHT.

AutoCAD SHX Text

FLOOR

AutoCAD SHX Text

FAUCET

AutoCAD SHX Text

COUNTERTOP

+ DEVICE MOUNTED ABOVE STD DEVICE MOUNTED ABOVE STD HEIGHT. REFER TO ARCH. PLANS FOR ELEVATION 1PH SINGLE-PHASE SINGLE-PHASE 1P SINGLE POLE SINGLE POLE 2/C TWO-CONDUCTOR TWO-CONDUCTOR 3/C THREE-CONDUCTOR THREE-CONDUCTOR 3PH THREE-PHASE THREE-PHASE 4/C FOUR-CONDUCTOR FOUR-CONDUCTOR 4W FOUR-WIRE FOUR-WIRE A/C AIR CONDITIONING UNIT AIR CONDITIONING UNIT A/E ARCHITECT/ENGINEER ARCHITECT/ENGINEER AC ALTERNATING CURRENT ALTERNATING CURRENT AF AMPERE FRAME OR AMP FUSE AMPERE FRAME OR AMP FUSE AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE ABOVE FINISHED GRADE AH AMPERE HOUR AMPERE HOUR AHJ AUTHORITY HAVING JURISDICTION AUTHORITY HAVING JURISDICTION AIC AMPERE INTERRUPTING CAPACITY AMPERE INTERRUPTING CAPACITY ALT ALTERNATE ALTERNATE AMB AMBIENT AMBIENT AMP AMPERE AMPERE ASC AMPS SHORT CIRCUIT AMPS SHORT CIRCUIT AT AMPERE TRIP AMPERE TRIP ATS AUTOMATIC TRANSFER SWITCH AUTOMATIC TRANSFER SWITCH BAT BATTERY BATTERY BIL BASIC INSULATION LEVEL BASIC INSULATION LEVEL BLDG BUILDING BUILDING BRKR BREAKER BREAKER BYP BY PASS BY PASS C CONDUIT CONDUIT CAB CABINET CABINET CALC CALCULATE CALCULATE CAP CAPACITY CAPACITY CAT CATALOG CATALOG CATV COMMUNITY ANTENNA TELEVISION COMMUNITY ANTENNA TELEVISION CCTV CLOSED CIRCUIT TELEVISION CLOSED CIRCUIT TELEVISION cd CANDELA CANDELA CD CONSTRUCTION DOCUMENTS CONSTRUCTION DOCUMENTS CF CONTRACTOR FURNISHED CONTRACTOR FURNISHED CKT CIRCUIT CIRCUIT CLF CURRENT LIMITING FUSE CURRENT LIMITING FUSE CLG CEILING CEILING CMU CONCRETE MASONRY UNIT CONCRETE MASONRY UNIT COMM COMMUNICATION COMMUNICATION COMPT COMPARTMENT COMPARTMENT CONC CONCRETE CONCRETE CONT CONTINUE CONTINUE CONTR CONTRACTOR CONTRACTOR CRI COLOR RENDERING INDEX COLOR RENDERING INDEX CT CURRENT TRANSFORMER CURRENT TRANSFORMER CTV CABLE TELEVISION CABLE TELEVISION CU COPPER COPPER CU FT CUBIC FEET CUBIC FEET (D) DEMOLISH DEMOLISH DB DECIBEL OR DIRECT BURIAL DECIBEL OR DIRECT BURIAL DC DIRECT CURRENT DIRECT CURRENT DEMO DEMOLITION DEMOLITION DIAG DIAGRAM DIAGRAM DISC DISCONNECT DISCONNECT DN DOWN DOWN DPDT DOUBLE POLE, DOUBLE THROW DOUBLE POLE, DOUBLE THROW DPST DOUBLE POLE, SINGLE THROW DOUBLE POLE, SINGLE THROW DS DISCONNECT SWITCH DISCONNECT SWITCH DWG DRAWING DRAWING (E) EXISTING EXISTING (ER) EXISTING TO BE RELOCATED EXISTING TO BE RELOCATED EC EMPTY CONDUIT EMPTY CONDUIT EG EQUIPMENT GROUND EQUIPMENT GROUND EL ELEVATION ELEVATION ELEC ELECTRIC OR ELECTRICAL ELECTRIC OR ELECTRICAL ELEV ELEVATOR ELEVATOR EMER EMERGENCY EMERGENCY EMI ELECTROMAGNETIC INTERFERENCE ELECTROMAGNETIC INTERFERENCE EMT ELECTRICAL METALLIC TUBING ELECTRICAL METALLIC TUBING ENCL ENCLOSURE ENCLOSURE EPO EMERGENCY POWER OFF EMERGENCY POWER OFF EWC ELECTRIC WATER COOLER ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER ELECTRIC WATER HEATER EXIST EXISTING EXISTING FA FIRE ALARM FIRE ALARM FAAP FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FIRE ALARM CONTROL PANEL FC FOOTCANDLE FOOTCANDLE FIXT FIXTURE FIXTURE FLA FULL LOAD AMPS FULL LOAD AMPS FLEX FLEXIBLE METALLIC CONDUIT FLEXIBLE METALLIC CONDUIT FLUOR FLUORESCENT FLUORESCENT FP FIRE PROTECTION FIRE PROTECTION FT FEET OR FOOT FEET OR FOOT FU SW FUSED SWITCH FUSED SWITCH FVNR FULL VOLTAGE NON-REVERSING FULL VOLTAGE NON-REVERSING FVR FULL VOLTAGE REVERSING FULL VOLTAGE REVERSING G OR GND GROUND OR GENERATOR GROUND OR GENERATOR GEN GENERATOR GENERATOR GFCI GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT CIRCUIT INTERRUPTER HID HIGH INTENSITY DISCHARGE HIGH INTENSITY DISCHARGE HOA HAND-OFF-AUTOMATIC HAND-OFF-AUTOMATIC HP HORSEPOWER HORSEPOWER HT HEIGHT HEIGHT HZ HERTZ HERTZ IMC INTERMEDIATE METAL CONDUIT INTERMEDIATE METAL CONDUIT IR INFRARED INFRARED J-BOX JUNCTION BOX JUNCTION BOX kV KILOVOLT KILOVOLT kVA KILOVOLT AMPERE KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE KILOVOLT AMPERE REACTIVE kW KILOWATT KILOWATT kWH KILOWATT HOUR KILOWATT HOUR kWHM KILOWATT HOUR METER KILOWATT HOUR METER LED LIGHT EMITTING DIODE LIGHT EMITTING DIODE LF LINEAR FEET (FOOT) LINEAR FEET (FOOT) LP LIGHT POLE LIGHT POLE LRA LOCKED ROTOR AMPS LOCKED ROTOR AMPS LT LIGHT LIGHT LTG LIGHTING LIGHTING LTG PNL LIGHTING PANEL LIGHTING PANEL LV LOW VOLTAGE LOW VOLTAGE MAX MAXIMUM MAXIMUM MC METAL-CLAD METAL-CLAD MCA MINIMUM CIRCUIT AMPS MINIMUM CIRCUIT AMPS MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MDP MAIN DISTRIBUTION PANEL MAIN DISTRIBUTION PANEL MECH MECHANICAL MECHANICAL MH MANHOLE MANHOLE MIN MINIMUM MINIMUM MOCP MAXIMUM OVERCURRENT PROTECTION MAXIMUM OVERCURRENT PROTECTION MLO MAIN LUGS ONLY MAIN LUGS ONLY MT MOUNT MOUNT MTD MOUNTED MOUNTED MTG MOUNTING MOUNTING MTS MANUAL TRANSFER SWITCH MANUAL TRANSFER SWITCH MV MEDIUM VOLTAGE MEDIUM VOLTAGE MVA MEGAVOLT-AMPERE MEGAVOLT-AMPERE MW MEGAWATT MEGAWATT NA NOT APPLICABLE NOT APPLICABLE NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEUT OR N NEUTRAL NEUTRAL NFPA NATIONAL FIRE PROTECTION NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NOT IN CONTRACT NO NORMALLY OPEN NORMALLY OPEN NTS NOT TO SCALE NOT TO SCALE OC ON CENTER ON CENTER OD OUTSIDE DIAMETER OUTSIDE DIAMETER P POLE POLE PA PUBLIC ADDRESS PUBLIC ADDRESS PB PUSHBUTTON PUSHBUTTON PC PHOTOELECTRIC CELL PHOTOELECTRIC CELL PED PEDESTAL PEDESTAL PEND PENDANT PENDANT PF POWER FACTOR POWER FACTOR PH PHASE PHASE PNL PANEL PANEL PT POTENTIAL TRANSFORMER POTENTIAL TRANSFORMER PVC POLYVINYL CHLORIDE (PLASTIC) POLYVINYL CHLORIDE (PLASTIC) PWR POWER POWER (R) REMOVE (DEMOLISH) REMOVE (DEMOLISH) (RE) RELOCATED EXISTING RELOCATED EXISTING RCP REFLECTED CEILING PLAN REFLECTED CEILING PLAN REC RECESSED RECESSED RECPT RECEPTACLE RECEPTACLE RGS RIGID GALVANIZED STEEL RIGID GALVANIZED STEEL RM ROOM ROOM RMS ROOT MEAN SQUARE ROOT MEAN SQUARE REQD REQUIRED REQUIRED SCC SHORT CIRCUIT CAPACITY SHORT CIRCUIT CAPACITY SCHED SCHEDULE SCHEDULE SD SMOKE DETECTOR SMOKE DETECTOR SF SQUARE FOOT (FEET) SQUARE FOOT (FEET) SHT SHEET SHEET SI INTERNATIONAL SYSTEM OF UNITS INTERNATIONAL SYSTEM OF UNITS SPEC SPECIFICATION SPECIFICATION SPST SINGLE POLE, SINGLE THROW SINGLE POLE, SINGLE THROW SURF SURFACE SURFACE SW SWITCH SWITCH SWBD SWITCHBOARD SWITCHBOARD SWGR SWITCHGEAR SWITCHGEAR TC TIME CLOCK TIME CLOCK TEL TELEPHONE TELEPHONE TP TWISTED PAIR TWISTED PAIR TPS TWISTED PAIR SHIELDED TWISTED PAIR SHIELDED TTB TELEPHONE TERMINAL BOARD TELEPHONE TERMINAL BOARD TV TELEVISION TELEVISION TYP TYPICAL TYPICAL UL UNDERWRITERS LABORATORY UNDERWRITERS LABORATORY UON UNLESS OTHERWISE NOTED UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY UNINTERRUPTIBLE POWER SUPPLY UTIL UTILITY UTILITY V VOLT VOLT VA VOLT AMPERE VOLT AMPERE VAR VOLT AMPERE REACTIVE VOLT AMPERE REACTIVE VFD VARIABLE FREQUENCY DRIVE VARIABLE FREQUENCY DRIVE VOLT VOLTAGE VOLTAGE W WATT WATT WH WATER HEATER WATER HEATER WP WEATHERPROOF WEATHERPROOF XFER TRANSFER TRANSFER XFMR TRANSFORMER TRANSFORMER on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

NOT FOR CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseENGINEER OF RECORDCONSULTANT EXPAND EMERGENCY POWER

PHASE 3

ERIE VA MEDICAL CENTER, PA

562-21-708

Project Director

2023-07-12

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

N/A Civil Engineering:

PENNTERRA ENGINEERING, INC.

M-R PROJECT NO: 0517-0002

ELECTRICAL

NOTES

E-002

DRRLIB

AutoCAD SHX Text

1. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE AVAILABLE THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE AVAILABLE BUILDING DRAWINGS, ARCHITECTURAL BACKGROUNDS PROVIDED BY THE OWNER AND FIELD SURVEY INFORMATION COMPILED BY THE ENGINEERING DESIGN TEAM FOR THE PURPOSE OF ENGINEERING DESIGN. EXISTING CONDITIONS ARE SHOWN AS ACCURATELY AS POSSIBLE. THERE IS THE POSSIBILITY THAT CONDITIONS SHOWN ARE NOT EXACTLY AS EXISTING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, LOCATIONS, SIZES AND CONDITIONS AT THE SITE AND REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO BEGINNING INSTALLATION OR FABRICATION WORK. 1.1. DRAWINGS ARE DIAGRAMMATIC. DRAWINGS ARE DIAGRAMMATIC. 1.2. SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR RELATED SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR RELATED WORK ARE NOT SUFFICIENTLY DETAILED OR EXPLAINED ON THE DRAWINGS, OR IN THE SPECIFICATIONS, CONSULT THE ENGINEER FOR NECESSARY CLARIFICATIONS, AND CONFORM TO THOSE CLARIFICATIONS INSOFAR AS THEY ARE CONSISTENT WITH THE ORIGINAL DRAWINGS AND SPECIFICATIONS. IN NO CASE SHALL WORK PROCEED IN UNCERTAINTY. 1.3. EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED CONFIGURATIONS TO SUIT KNOWN CONDITIONS. ACTUAL INSTALLATION BY CONTRACTOR MAY BE ALTERED AS REQUIRED TO SUIT FIELD CONDITIONS ENCOUNTERED DURING CONSTRUCTION WITHOUT COMPROMISING THE INTENT OF THE ORIGINAL DESIGN. 1.4. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT SITE PRIOR TO STARTING WORK. 2. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND REGULATIONS, INCLUDING THOSE WHICH MAY BE ISSUED BY THE OWNER, ARE BEING OBSERVED, PARTICULARLY WORKPLACE SAFETY AND THE CONDUCT OF ALL THOSE EMPLOYED DIRECTLY AND INDIRECTLY BY HIM ON THE PREMISES, AND THE OWNER'S EMPLOYEES WHO MAY BE IMPACTED OR AFFECTED BY CONSTRUCTION ACTIVITIES. THE CONTRACTOR WILL INSTALL SIGNAGE, BARRIERS, AND OTHER MEANS TO PROVIDE WARNING AND PERSONNEL SAFETY. PLACEMENT OF THESE ITEMS WILL BE COORDINATED WITH THE OWNER AND HIS ONGOING OPERATIONS AND WILL PROMPTLY BE REVISED WHEN WORK IN A PARTICULAR AREA HAS BEEN COMPLETED. 2.1. DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE RESPONSIBLE DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT SIGNAL DEVICES, GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND OTHER DEVICES, APPROPRIATELY LOCATED ON AND AROUND THE JOB SITE WHICH GIVE PROPER AND UNDERSTANDABLE WARNING TO PERSONS WITH REGARD TO HAZARDOUS CONDITIONS, EQUIPMENT AND OPERATIONS BEING PERFORMED IN CONJUNCTION WITH THE WORK. 3. THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF FEDERAL, STATE, AND LOCAL REGULATORY AGENCIES HAVING JURISDICTION INCLUDING, BUT NOT LIMITED TO THE FOLLOWING: ELECTRICAL: NATIONAL ELECTRIC CODE: NFPA 70 - CURRENT VERSION NATIONAL ELECTRIC CODE: NFPA 70 - CURRENT VERSION 4. ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND WILL BE COMPLETED IN ACCORDANCE WITH THE GOVERNING CODES (ABOVE), INDUSTRY STANDARDS, AND IN CONFORMANCE WITH THE MANUFACTURERS RECOMMENDATIONS AND REQUIREMENTS. 5. WORK UNDER THIS CONTRACT SHALL CONSIST OF THE CONTRACTOR PROVIDING ALL WORK UNDER THIS CONTRACT SHALL CONSIST OF THE CONTRACTOR PROVIDING ALL LABOR, MATERIALS, AND SERVICES, INCLUDING WORK NOT SPECIFICALLY SHOWN BUT REASONABLY IMPLIED. THIS SHALL INCLUDE CUTTING, PATCHING AND RESTORATION OF EXISTING SURFACES DAMAGED DURING THE CONSTRUCTION. CONTRACTOR SHALL ALSO PROVIDE ALL EQUIPMENT SHOWN OR SPECIFIED OR AN APPROVED EQUIVALENT. SUBSTITUTED EQUIPMENT OR MATERIALS SHALL NOT BE INSTALLED UNTIL GIVEN WRITTEN APPROVAL BY THE OWNER. 6. EACH TRADE CONTRACTOR SHALL BE WHOLLY RESPONSIBLE FOR PROVIDING, EACH TRADE CONTRACTOR SHALL BE WHOLLY RESPONSIBLE FOR PROVIDING, INSTALLING, AND MAINTAINING ALL TEMPORARY POWER SOURCES AND ANY REQUIRED UTILITIES FOR ANY TEMPORARY MECHANICAL, PLUMBING, AND/OR ELECTRICAL EQUIPMENT OR SYSTEMS (REQUIRED BY THEIR INDIVIDUAL TRADES SCOPE OF WORK) DURING THE COURSE OF CONSTRUCTION AND PHASING/SEQUENCING OF WORK. THIS SHALL INCLUDE BUT NOT BE LIMITED TO THE INSTALLATION AND ROUTING OF: TEMPORARY FEEDERS, CONDUIT, TRANSFORMERS, ON-SITE GENERATOR PACKAGES, OVERCURRENT PROTECTION DEVICES, DISCONNECTS, CONNECTIONS AND DISCONNECTION OF EQUIPMENT, ETC. ALL ELECTRICAL WORK MUST BE PERFORMED BY A LICENSED ELECTRICIAN. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. 7. CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS INCURRED FOR NONCOMPLIANCE CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS INCURRED FOR NONCOMPLIANCE WITH THESE CONTRACT DOCUMENTS. CONTRACTOR WILL NOT BE ALLOWED CHANGE ORDERS FOR PROBLEMS ARISING FROM NEGLECT OF PROVISIONS INCLUDED IN THESE CONDITIONS. 8. MAINTAIN ORDERLY HOUSEKEEPING DURING CONSTRUCTION, AND UPON SUBSTANTIAL MAINTAIN ORDERLY HOUSEKEEPING DURING CONSTRUCTION, AND UPON SUBSTANTIAL COMPLETION PERFORM FINAL CLEANUP. REMOVE CONSTRUCTION RUBBISH, SCAFFOLDING, EQUIPMENT, TEMPORARY PROTECTION, TEMPORARY FIELD STRUCTURES, AND OTHER MATERIALS OR EQUIPMENT THAT WAS REQUIRED IN CONNECTION WITH THE CONSTRUCTION, BUT NOT A PERMANENT PART THEREOF. 9.

This is the start of the file's text. The full file is on GovTribe.