  • ICRA barrier walls with airtight construction, 36" steel doors, and negative air monitoring are required for the 9th West, 9th East, and warehouse areas.
  • 6 mil plastic sheeting is required on stairwells and elevator doors.
  • HEPA negative air units vented to the outside are needed, with the number determined by the work area.
  • All furniture and supplies in the work areas must be moved, covered, and returned to their original locations.
  • An ICRA permit is required, which the VA has the right to modify for patient safety.
  • The related federal contract opportunity is for the overall 9th Floor Mental Health unit renovation project, solicitation number 36C24424R0007.

View the file

Other files

File Type Posted
36C24424R0007 0006.pdf PDF
Amend 6 - Updated Pricing Sheet.pdf PDF
RFI Responses 3.pdf PDF
36C24424R0007 0005.pdf PDF
Amend 4 - 1. RFI Responses 2.pdf PDF
Amend 4 - 2. Pricing Sheet.pdf PDF
36C24424R0007 0004.pdf PDF
5 ALUMINUM CANOPY SYSTEM.pdf PDF
36C24424R0007 0003.pdf PDF
3 SOLID SURFACING FABRICATIONS.pdf PDF
1 000110 Table of Contents.pdf PDF
9 17-H4 ICRA.pdf PDF
8 A3 ICRA.pdf PDF
2 Addendum 1 Drawings.pdf PDF
10 01-A ICRA.pdf PDF
6 Noise and Vibration Control.pdf PDF
11 G-009 ICRA.pdf PDF
13 ICRA.pdf PDF
4 Door Hardware.pdf PDF
7 RFI RESPONSES.pdf PDF
01-20-083-pGen100.pdf PDF
221100 FacWaterDistr MH.pdf PDF
36C24424R0007 0002.pdf PDF
Drawings General.pdf PDF
Wilkes Barre PA Campus Site Plan crane locations.pdf PDF
17-E43 Revisions 2024-05-30.pdf PDF
17-A15 Revisions 2024-05-30.pdf PDF
220523 GenDut ValvesPlumbPiping MH 9th.pdf PDF
36C24424R0007 0001.pdf PDF
Drawings 1.2 33-60.pdf PDF
P03 Brand Name JA 9F MHU 20241804.pdf PDF
S02 SafetyHealthDuringConstruction 18S-15-346.pdf PDF
Cut Sheets.pdf PDF
P07 4.5.24 Wage Determination.pdf PDF
Drawings 1.1 1-32.pdf PDF
Specs.pdf PDF
EXHIBIT B - Subcontractor Info Consent.docx DOCX document
EXHIBIT C - Performance Relevancy Info.docx DOCX document
ICRA.docx DOCX document
EXHIBIT A - Calculation of Self-Performed Work.docx DOCX document
Structural Calcs.pdf PDF
Drawings 2.pdf PDF
Safety.pdf PDF
Drawings 1.3.pdf PDF
Estimate - 693 19 106 M P Calcs.pdf PDF
36C24424R0007.docx DOCX document
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF VETERANS AFFAIRS

Medical Center

1111 East End Boulevard

Wilkes-Barre, PA 18711

July 9, 2024

SUBJECT: 9th Floor Mental Health Project - ICRA

ICRA drawings and permit

• Drawings. 3 drawings are of different locations: 9 west, 9 east and warehouse. All marked areas are in red on the drawing.

1. ICRA barrier wall. Wall from floor to underdeck. 2x4 metal stud, 5/8 drywall both sides, taped and painted with base. Top, bottom and side shall be airtight.

36” steel door and jamb, Yale door lock 522 core, self-closer, gasket around door jamb, door sweep. Sticky pad outside the door.

2. 6 mil plastic shall be installed on all stairwells exit with a zipper. And the elevator door shall be plastic over.

3. Electric negative air monitor shall be mounted outside the door. The monitor shall be recorded every hour during working hours.

4. HEPA Negative air unit shall be vented to the outside through a window. The number of units that will be needed depends on how many it will take to get the work area negative.

• Working on the 8th floor will need ICRA for each areas/ room. All furniture and supplies in the room are moved, will need to be covered when working, and removed when work is completed for the night. The room shall be clean, and all furniture and supplies are returned to their original location. The COR can make change to what needs to be done to accommodate a clean and safe environment.

• An ICRA permit is needed for this project. The VA has the right to make changes to the permit for patient safety.

Sincerely, Michael Somoga