RFI 1 - Answered.pdf
PDF 65 KB Posted
- Solicitation number
- 36C24226B0038
About this file
This document is a Request for Information (RFI) submitted by an Electrical Subcontractor for the HFC & Whole Health in OPC project (Contract Number 528A5-25-509) at Canandaigua VAMC. The subcontractor seeks clarification on six critical system locations referenced in the contract documents that could not be clearly identified in the provided drawings and specifications.
The RFI addresses the following location clarifications: (a) Fire Alarm Control Panel (FACP) location—confirmed as main lobby of the OPC on ground floor; (b) Data closet location—identified as either OIT Closet 2D078 or 2A013A; (c) CATV closet location—identified as either OIT Closet 2D078 or 2A013A; (d) Smoke detector requirements within the new space—clarified as not required; (e) CCTV home run location—all termination points in either OIT Closet with a Client Viewing Station in Room 7; and (f) Security/Dispatch Office location—identified as Building 37 Room 1 with a request to review site plans for relative location to the OPC. The subcontractor additionally requests that any available supplementary drawings, including whole-building plans or system drawings indicating these locations, be provided for review.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24226B0038 0006.docx | DOCX document | |
| RFI -2.docx | DOCX document | |
| 36C24226B0038 0005.docx | DOCX document | |
| 36C24226B0038 0004.docx | DOCX document | |
| Construction Documents.pdf | ||
| OPC Floor 2 OIT Locations.pdf | ||
| PRE BID SITE VISIT SIGN IN SHEET - HFC AND WH - CAN.pdf | ||
| 36C24226B0038 0003.docx | DOCX document | |
| OPC Floor 1 Fire Panel Location.pdf | ||
| 36C24226B0038 0002.docx | DOCX document | |
| 36C24226B0038 0001.docx | DOCX document | |
| P07 - WAGE DETERMINATION.pdf | ||
| BUY AMERICAN ACT CERTIFICATE 52.225-2.docx | DOCX document | |
| HFC and WH combined SPECS.pdf | ||
| LIMITATIONS OF SUBCONTRACTING CERTIFICATE 852.219-75.docx | DOCX document | |
| Construction Drawings.pdf | ||
| 36C24226B0038_1.docx | DOCX document |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HFC & WHOLE HEALTH IN OPC
528A5-25-509
CANANDAIGUA VAMC
RFIs
1. The Electrical Subcontractor respectfully requests clarification regarding several system locations referenced in the contract documents. After reviewing the provided drawings and specifications, the following items could not be clearly identified:
a. Fire Alarm Control Panel (FACP) location – Panel is located in main lobby of the OPC on the ground floor.
b. Data closet location– Closest OIT Closets 2D078 or 2A013A
c. CATV closet location – Closest OIT Closets 2D078 or 2A013A
d. Smoke detector requirements within the new space – Not required
e. CCTV home run location (please confirm if Office 7 is the correct termination point, or advise if different) – All termination will be made in either OIT Closet.
Room 7 will have Client Viewing Station
f. Security/Dispatch Office location (Building 37) – Building 37 Room 1, please review site plan in drawings for relative location of Building 37 to the OPC.
If additional drawings are available — including whole-building plans or system drawings that indicate these locations — please provide them for review. Please see attached
File details come from the government source that posted it. Updated .