13CD Narrative 1of2.pdf

PDF 23 MB Posted

Attached to
Z1DA--RENOVATE BUILDING 13CD FOR RESIDENTIAL PROGRAMS MONTROSE VAMC
Solicitation number
36C24223B0004
Issued by

About this file

This solicitation is for renovating Building 13CD at the Montrose VA Medical Center to accommodate residential programs. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 is seeking bids for the project under solicitation number 36C24223B0004. The scope of work involves renovating the existing building to convert it into housing facilities, which may include work such as installing new plumbing and electrical systems, renovating bathrooms and living spaces, and addressing any code or safety issues. Bids are due by the date listed on SAM.gov and the contract is slated to be awarded by late 2023. Pricing should be firm-fixed price and the opportunity is open to all responsible sources.

View the file

Other files

File Type Posted
27 52 23 Attachement.pdf PDF
T-102_2023.01.06.pdf PDF
Amendment 0003 36C24223B0004 Renovate Building 13 CD.pdf PDF
620-20-106 Updated RFI Responses.pdf PDF
27 52 23 Nurse Call and Code Blue Systems.pdf PDF
T-501_2023.01.06.pdf PDF
PA System Equipment Cut Sheets.pdf PDF
620-20-106 13CD RFI Responses.pdf PDF
AE102C_2023.01.06.pdf PDF
Sound Masking Layout.pdf PDF
AE304_2023.01.06.pdf PDF
CCTV Video Equipment Cut Sheets.pdf PDF
36C24223B0004 0002 13CD Amendment 0002.pdf PDF
AE303_2023.01.06.pdf PDF
28 13 00 Physical Access Control System.pdf PDF
28 23 00 Video Surveilance.pdf PDF
Plumbing Cut Sheets.pdf PDF
36C24223B0004 Amendment 0001.pdf PDF
13CD Specs 1of2.pdf PDF
13CD Narrative 2of2.pdf PDF
13CD Specs 2of2.pdf PDF
006_Fire Protection.zip ZIP file
005_Plumb.zip ZIP file
36C24223B0004_1.docx DOCX document
Wage Determination - Westchester County NY.pdf PDF
001A_Arch.zip ZIP file
003_Struct.zip ZIP file
007_Elec.zip ZIP file
001B_Arch.zip ZIP file
FAR 52.225-2 BUY AMERICAN CERTIFICATE.docx DOCX document
002_Hazard.zip ZIP file
004_Mech.zip ZIP file
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Design Narrative

Prepared for

RENOVATE BUILDING 13CD

Montrose VA Medical Center

Montrose, NY

Project No. 620-20-106

Submittal Date: August 15, 2022

100% WORKING DRAWINGS SUBMISSION

DEPARTMENT OF VETERANS AFFAIRS VA PROJECT NO. 620-20-106

MONTROSE VA MEDICAL CENTER

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-2 MONTROSE, NY

TABLE OF CONTENTS

CHAPTER 01

ARCHITECTURAL DESIGN 3

CHAPTER 02

STRUCTURAL DESIGN 11

CHAPTER 03

MECHANICAL DESIGN 15

CHAPTER 04

PLUMBING DESIGN 21

CHAPTER 05

ELECTRICAL DESIGN 24

CHAPTER 06

FIRE PROTECTION DESIGN 27

APPENDIX A

HAZMAT REPORT 37

ARCHITECTURAL CUTSHEETS 103

APPENDIX B

STRUCTURAL CALCULATIONS 165

MECHANICAL CUTSHEETS AND CALCULATIONS 287

ELECTRICAL CUTSHEETS AND CALCULATIONS 633

PLUMBING CUTSHEETS AND CALCULATIONS 725

APPENDIX C

WATER SUPPLY REPORT 775

AUDIBILITY ANALYSIS 781

FLOW AND PRESSURE DEMAND ESTIMATE 788

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-3 MONTROSE, NY

CHAPTER 01

ARCHITECTURAL

OVERVIEW

The architectural scope of work for this project includes the design and planning of on-site domiciliary facilities for Veterans contending with substance abuse transitioning back into the community through the Domiciliary Residential Rehabilitation and Treatment Program. Domiciliary programs provide a safe, secure, therapeutic, home-like environment designed to facilitate attainment of each resident’s optimal level of functional independence through active participation in individually developed treatment plans and job placement programs. To address the high rate of Veteran self-destructive dependencies, predisposition to homelessness, and associated elevated suicide rate, the FDR Campus has been identified as a facility for the construction of a domiciliary for providing shelter for Veterans recovering from substance abuse. Building 13 Ward CD will be converted to accomplish this task. Building 13 Ward CD is approximately 17,300 square feet and is the third-story of a three-story building. The ground and second stories shall be assumed to be occupied during construction, though there is a chance that separate construction activities may occur simultaneously on the second story of the building. This should be a consideration during the design phase of the project.

CODES AND STANDARDS

The following is a list of VA and other design and construction criteria that shall be utilized by the A/E for the development of the design of this project:

• PG-18-1, Master Construction Specification Index

• PG-18-3, Design and Construction Procedures

• PG-18-4, Standard Details and CAD Standards

• PG-18-5, Equipment Guide List

• PG-18-9, Space and Facility Planning Criteria

• PG-18-10, VA Design Manual - Architectural

• PG-18-12, Design Guides - Small House Model Design Guide

• PG-18-13, Accessibility Information / Barrier Free Design Guide

• PG-18-14, Room Finishes, Door and Hardware Schedule

• PG-18-15, VA A/E Design Submission Requirements

• PG-18-17, Environmental Compliance program

• H-18-8, Seismic Design Handbook

• Special Design Requirements

• Cost Estimating Requirements

• A/E Quality Alerts

• A/E Design Alerts

• NFPA 101 – Most recent version

• International Building Code (IBC) – Most recent version

Supplementary to current technical manuals, codes, and other VA criteria, the following VA Design Guides are to be consulted during the design phase of the project:

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-4 MONTROSE, NY

• PG 18-3 Design and Construction Procedures

• PG 18-9 Space Planning Criteria

• Chapter 202: Substance Abuse

• Chapter 312: Domiciliary

• PG 18-13 VA Barrier Free Design Standard

ARCHITECTURAL DESIGN APPROACH

The objective of this acquisition is for the planning, design and construction management for the renovation of the third floor of Building 13 Ward CD, otherwise known as “13 CD”, to provide living accommodations for Veterans recovering from substance abuse. The goal is to use the space to provide a 100% ADA Compliant design that meets the VA Domiciliary design criteria as per the Domiciliary Residential Rehabilitation and Treatment Program.

Per the program in the Scope of Work, the renovation shall include a minimum of:

• 30 individual patient quarters consisting of bedroom and bathroom

- 5 quarters reserved for female patient needs

• 8 offices for medical professionals to meet with patients

• 1 group room large enough to accommodate all patients and staff together

• 1 dayroom

• 1 galley-style kitchen

• 1 nursing station (designed with the expectation that it will be staffed 24/7)

• 1 conference room

• 2 staff bathrooms (M/F)

• 2 public bathrooms (Unisex)

• 1 staff breakroom with adjacent locker rooms

• 1 Pyxis™ MedStation™ medication storage room

• 1 Treatment Room

• 1 laundry room

The proposed design solution provides:

• 30 individual patient quarters consisting of bedroom and bathroom

- 25 quarters for male patients

- 4 quarters for female patients and separate female patient lounge

- 1 quarter that can accommodate a male or female patient according to the current patient population

• 8 offices for medical professionals to meet with patients

• 3 group rooms (Group Room 1 at approx. 600 SF; Group Room 2 at approx.. 220 SF; Group Room 3 at approx. 430 SF)

- Group Room 3 can also function as the conference room

• 1 dayroom with kitchenette

• 2 nursing stations (designed with the expectation that they will be staffed 24/7)

- 1 main nursing station controlling entry to the floor

- 1 satellite nursing station monitoring west wing of patient rooms

• 2 staff bathrooms (M/F)

• 3 public bathrooms (Unisex)

- 1 bathroom for urine drug screening (UDS)

• 1 staff breakroom with lockers

• 1 Pyxis™ MedStation™ medication storage room

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-5 MONTROSE, NY

• 1 treatment room

• 1 telehealth room

• 1 laundry room

• 1 EMS closet

• 1 clean supply room

• 1 clean linen room

• 1 soiled linen room

• Approx. 200 SF storage

• 1 IT room

• 1 electrical room

INTERIOR CONSTRUCTION, FINISHES

Interior finishes for the VA Montrose Domiciliary Residential Rehabilitation and Treatment Program Building 13 Ward CD will incorporate the National VA finish standards and Montrose Campus Design Standards while following the Small House design guidelines to provide a home-like environment.

Specifications for these finishes will be written as performance specifications in accordance with the VA Master Construction Specifications (PG-18-1).

Wall Construction

• Non-bearing interior partitions shall be capable of supporting equipment and furnishings as specified. For special requirements, use framing sizes or systems as appropriate. All walls for patient work/discussion to achieve minimum STC rating. Where pipe spaces are required, the partition size framing thickness to conceal piping. Installation of metal studs shall comply with ASTM C754. Provide support required for equipment, furnishings, and work of other trades.

o Studs floor to deck o Drywall to deck typical to prevent sound transmission.

o Fire rated blocking in all walls

• Corridor walls: Due to the heavy use consideration shall be given to the durability of partitions.

Walls are fitted with wall protection in high traffic areas or areas where movable equipment and carts could come in to contact with wall surfaces. VA Room Finishes, Door, & Hardware Schedule (PG-18-14) recommends impact resistant wall material in various locations for additional wall protection.

• Accent finishes in Patient Bedrooms, Hallways, Offices, Group Rooms, and Staff Lounge may include accent paints and flooring patterns.

• Accent finishes in Elevator Lobby and Day Room include wall covering illustrating a nature, biophilic image.

• Consider wall penetrations such as doors, view windows, electrical outlets, and mechanical ductwork to avoid sound transmission in a partition system.

Ceilings

• General: Follow existing VA Montrose campus standards to minimize overall life cycle costs.

Where not hard boarded, use Armstrong Ultima Health Zone High NRC with 15/16” white grid as Basis of Design.

• A minimum of 8-feet 6-inches AFF shall be used for staff areas, offices, and consultation rooms.

A minimum of 9-feet AFF is recommended in resident rooms to limit the ability of residents to

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-6 MONTROSE, NY

reach ceilings and ceiling fixtures to conceal hazardous items as determined by VA Mental Health Residential Program Design Guide. If existing conditions prohibit the recommended ceiling heights, adjustments may need to be made to accommodate those items.

• The following rooms to receive lay-in acoustical ceiling tile as determined by VA Room Finishes, Door, & Hardware Schedule PG 18-14.

o Patient Bedroom o Laundry Room o EMS o Clean Linen Room (special faced, SP) o Clean Supply (special faced, SP) o Soiled Linen (special faced, SP) o Office o Tele Health o Staff Lounge o Group Room o Med/Treatment Room o Nurse Station o Hallways o Day Room o Elevator Lobby

• The following rooms to receive gypsum board ceilings as determined by VA Room Finishes, Door, & Hardware Schedule PG 18-14.

o Patient Bathroom o Public Toilet & Staff Toilet o Bio Storage o General Storage

• The following rooms to receive exposed ceilings as determined by VA Room Finishes, Door, & Hardware Schedule PG 18-14.

o Electrical o IT

Floors

• General: Follow existing VA Montrose campus standards to minimize overall life cycle costs.

• The following room(s) to receive luxury vinyl tile flooring (LVT) as determined by VA Room Finishes, Door, & Hardware Schedule PG 18-14 and reviewed with the VA Interior Designer to match Building 13AB.

o Patient Bedroom o Tele Health o Group Room o Day Room o Med/Treatment Room o Nurse Station o Elevator Lobby o Hallway o Offices o Soiled Linen o Staff Lounge o Clean Linen o Clean Supply

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-7 MONTROSE, NY

o Bio Storage o General Storage

• Toilet Rooms (Patient and Public) to receive porcelain tile (floor and base) as determined by VA Room Finishes, Door, & Hardware Schedule PG 18-14.

o Patient Bedroom Toilet Rooms to receive maximum of 2”x2” porcelain floor tile with COF tested in accordance with ANSI A137.1 at shower locations and measured per the TCNA DCOF AcuTest equal to or greater than 0.42 for level interior tile floors that will be walked on when wet.

• Laundry Room and EVS to receive bio-based vinyl composite tile (floor) per direction from the VA Montrose Interior Designer.

• The following room(s) to receive concrete to match Building 13AB floor type:

o Electrical Room o IT Room

Casework

• General: Countertops to be made of impervious, solid surface to reduce life cycle costs.

Casework to be veneered with plastic laminate.

• Nurse Station countertop: Solid surface counters or other impervious high-quality material to hold up to scratching, abuse and fingerprinting.

• Nurse areas: casework storage systems should be utilized for flexibility including the incorporation of typical dimensions for ease of multiple reuse applications.

Acoustics

• General: Acoustics are critical for a domiciliary facility as excessive noise may negatively impact a therapeutic environment for both patient/resident and staff. Noise should be minimized by the planning and design of the physical environment by isolating the spoken word and staff workflow that requires quiet environments from the noisier functions.

• In group rooms, the folding partition will be studied if it will be needed to provide additional acoustic treatment.

• A minimum NRC of 0.85 and 35 CAC rating is required at locations where acoustic ceiling tiles are used as determined by VA document Inpatient Mental Health & Mental Health Residential Rehabilitation Treatment Program Design Guide (PG-18-12).

• Walls shall meet STC levels appropriate to support patient and resident privacy and limit room-to-room sound transmission that may disturb other patients, staff, and residents.

o Room types to support the minimum STC rating as determined by VA document IPMH & MH RRTP Design Guide Section 5.

• Interior partitions between a patient/resident room and shared space shall provide sound attenuation features such as insulation between studs, a double layer of gypsum board, and partitions extending to the underside of deck above.

Doors

• General: VA Document Room Finishes, Door & Hardware Schedule Program Guide (PG-18-14) indicates sizes and types of doors required. Interior doors shall be solid-core, flush-panel wood doors with hollow metal frames unless otherwise indicated in VA PG-18-14.

o View panels shall be provided in group/meeting areas that meet staff visibility and patient/resident privacy if needed.

• Fire rated door and frame assemblies shall comply with NFPA 80.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-8 MONTROSE, NY

• Doors installed in all Group Rooms shall swing out in accordance with FGI 2.11-3.2.5.3. Such doors shall be recessed from corridor to maintain corridor width and hazard to passersby in the corridor.

• Spaces accessed only by staff (i.e. medication, team conference, soiled utility rooms) shall be secured under normal operation with card readers, key or key pads to allow authorized access.

Doors need to close automatically.

• Patient Toilet/Shower Doors shall consider one of the three options: soft suicide prevention doors, sliding door, out-swinging door with sloped top (open top and bottom).

• At Patient Rooms, utilize sound door sweeps to control sound migration.

Finish Hardware

• General: Locks and keyway shall match the standards of the VA Montrose campus.

• ABAAS compliant hardware shall be provided throughout facility.

Interior Finishes

• General: Interior Finishes Refer to the Room Finishes, Door & Hardware Schedule Program Guide (PG-18-14) and the following will be considered in the design process, which will have an impact on the built environment and the user experience:

o Maintenance o Durability o Life cycle cost o Warranty o Therapeutic attributes

• Wall protection: Includes corner guards, handrails, and rigid sheet wall protection as needed to provide added durable wall protection.

o Flexible wall protection shall be considered for use as wainscot in corridors for additional protection.

• Window shades: Roller shades to match Building 13AB and allow filtration of natural light into space with capabilities to shade direct sun and patient accessible control.

• Patient Toilet Rooms to receive porcelain floor and wall tile. Floors to receive mosaic porcelain tile and meet DCOF requirements in wet areas. Walls to receive porcelain tile with a glass mosaic accent tile at locations indicated on drawings.

• Single Toilet Rooms and Staff Toilet Rooms to receive porcelain floor and wall tile. Floors to receive mosaic porcelain tile and meet DCOF requirements in wet areas. Walls to receive porcelain tile partial high with paint above as indicated on drawings.

• Printed graphic images of nature themes on Type II wall covering shall be considered to add way-finding imagery throughout the floor.

• See above for descriptions of finishes based on surface type. Additionally, refer to digital/physical boards for more information.

Lighting

• General: VA document Lighting Design Manual and VA Standard Electrical Design Manual provide guidance for lighting design and indicates recommended types of luminaries for specific room types.

• VA document IPMH & MH RRTP Design Guide Section 5 provides reflected ceiling plans illustrating placement of luminaires.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-9 MONTROSE, NY

• Emphasis on daylighting and views outside will be integrated into the design where possible, balanced by artificial lighting: general, ambient, and task lighting. Daylight and views to the exterior can provide sensory stimulation and reinforce the normal rhythm of a day.

INTERIOR DESIGN AND FINISHES

• Floor coverings shall be classified for commercial use and when identified shall be classified for heavy duty use. Interior floor finishes shall meet code requirements for slip resistance.

• Accessible and barrier free design shall be incorporated throughout the building. Floor changes shall be minimized to prevent trip hazards. Select durable interior finishes that comply with VA Room Finishes, Door, & Hardware Schedule PG 18-14 schedule.

• The primary objective of the interior design is to provide a therapeutic and safe environment with a residential aesthetic that promotes positive engagement. Finishes, fixtures, and furnishings that maintain the safety and security of the facility will be integrated into the design without detracting from this primary objective.

A warm, welcoming environment can help calm promote participation, rehabilitation and recovery while providing support to staff. Integration of natural light and biophilic design may evoke less stress and anxiety while a connection to the outdoors bridges the gap between the interior and exterior environment providing a connection to nature.

This facility is to provide a supportive interior environment that is conducive to rehabilitation, promotes positive engagement, and is a comfortable, safe environment.

• Functional requirements dictate maintainable colors, textures, patterns, materials selections, combination of materials, flexibility and adjustability, and installation techniques. Materials must be chosen for longevity and good appearance retention. Integration of naturalistic materials and color within the built environment aid in promotion of rehabilitation and independence.

• Acoustic wall panels may be considered for additional sound absorption in large spaces such as a group or day room.

WAYFINDING

1) General: Wayfinding design should provide a clear and consistent visual communication system empowering patients and visitors to navigate throughout the facility with ease.

2) Interior design shall reinforce wayfinding through consideration of the following:

o Architectural elements at door openings to create a cue signifying arrival o Color and/or material changes at destinations o Landmarks at key decision points o Ceiling soffits that tie into flooring patterns

3) Walls at key decision circulation points shall be considered incorporating graphics and finishes to enhance wayfinding.

ARTWORK

1) Artwork should support the primary interior design objective of creating a therapeutic, safe, comfortable environment. Artwork can personalize patient/resident rooms and serve as an identifier for gathering or socialization areas. Artwork with biophilic design should be considered

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-10 MONTROSE, NY

as it provides positive engagement with their physical environment for patients, visitors, and staff.

Photography is recommended; abstract art with un-defined shapes and optical illusions should be avoided.

HAZARDOUS MATERIALS

The design team completed a HazMat survey of the project scope area. Based on the results of this survey, we have developed drawings and specifications instructing the contractor where the hazardous materials are located and how to abate them. Design team has provided specifications containing procedures to be followed by the contractor for removal and disposal of hazardous materials. The specification section related to asbestos is 02 82 11 Traditional Asbestos Abatement.

[End of Chapter]

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-11 MONTROSE, NY

CHAPTER 02

STRUCTURAL

The proposed newly renovated third floor of Building 13 Ward CD, otherwise known as “13 CD” will provide living accommodations for Veterans recovering from substance abuse. Structural scope of work for this project includes modifications to the existing attic of the building to accommodate new HVAC equipment that will be located in this space. The attic modifications include modification of the existing structural steel frames that support the timber roof rafters and reinforcements to the existing concrete floor to support the weight of the new equipment.

The following is a list of VA and other design and construction criteria that shall be utilized by the A/E for

• PG-18-4, Standard Details and CAD Standards

• PG-18-5, Equipment Guide List

• PG-18-9, Space and Facility Planning Criteria

• PG-18-10, VA Design Manual - Architectural

• PG-18-12, Design Guides - Small House Model Design Guide

• PG-18-13, Accessibility Information / Barrier Free Design Guide

• PG-18-14, Room Finishes, Door and Hardware Schedule

• PG-18-15, VA A/E Design Submission Requirements

• PG-18-17, Environmental Compliance program

• H-18-8, Seismic Design Handbook

• Special Design Requirements

• Cost Estimating Requirements

• A/E Quality Alerts

• A/E Design Alerts

• NFPA 101 – Most recent version

• International Building Code (IBC) – Most recent version

DESIGN APPROACH

Existing conditions: All the existing HVAC systems serving the existing third floor are in poor condition and shall be demolished. Steam coils for perimeter heating located throughout this floor shall be demolished and removed and steam pipes/connections to the coils shall be demolished starting from the coils to the point of connection to the PRV located in the basement. The basement houses an existing steam plant that includes PRVs and all necessary accessories required for steam to hot water conversion.

New heat exchangers shall be provided to generate hot water from the existing steam plant. The same

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-12 MONTROSE, NY

steam system in the basement generates low pressure steam that provides humidfication for the existing AHUs in the penthouse.

Design Concept

Heating, cooling and ventilation for the spaces on this floor shall be provided by three Air Handling Units (AHUs) located in the penthouse. The following components included but not limited to, shall be provided for the AHUs:

1. Fan array supply fans, with each fan having its own VFD.

2. Chilled water-Cooling coil section.

3. Hot water Heating coil section.

4. Humidification section.

5. Access sections for all the coils and filters.

6. Mixing box/plenum.

7. Prefilter, MERV-7 and MERV 11

8. After Filter, MERV 14.

Supply air ducted from the AHUs shall provide cooling and heating to all the spaces on this floor. Air shall be supplied at the room levels via Variable Air Volume (VAV) units equipped with hot water reheat coils. Return air from these areas shall be ducted back to the mixing box of the AHUs via inline, centrifugal, return fans. The VAV units shall be controlled by wall mounted thermostats located in the rooms the VAV units would be serving. AHUs and chilled water pumps shall be located in the penthouse.

a. Chilled water System

Chilled water capacity for this floor shall be provided by two 70 tons rotary scroll air cooled chillers arranged in an N+1(sized for full capacity) configuration and located on grade in the mechanical yard adjacent to the building. Both the chillers will run at 50% capacity each, at all times and when one of the chillers is down for maintenance or repair, the other chiller will ramp up to full capacity of 70 tons of cooling. Centrifugal, chilled water pumps in N+1 configuration, equipped with variable frequency drives, shall distribute the chilled water from the air-cooled chillers to the cooling coils of the AHUs via Schedule 40, Carbon black steel, chilled water pipes. Chilled water pumps, Buffer tank, Air separator and all other appurtenances shall be provided as part of the Chiller skid package.

Heating System

Heating shall be provided at the AHU preheat coils and the reheat coils at the VAVs by hot water generated in the basement via heat exchangers. There is an existing steam Pressure Regulator Valve(PRV) located in the basement to convert high pressure steam to medium and low pressure steam. Existing heat exchangers provided as part of 13AB project generate hot water to meet with the heating needs of this floor. Hot water generated by existing heat exchangers are circulated within the building via two, 180 gpm, 80 ft head, end suction centrifugal pumps, in N+1 configuration and equipped with variable frequency drives. A new end suction, centrifugal hot water pump of 180 gpm and 80 ft head shall be added in order to serve this floor while one of the existing hot water

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-13 MONTROSE, NY

pumps shall be made a standby pump, required during maintenance of the hot water system. New hot water pump shall be located in the basement and integrated into the existing hot water system. Radiant hot water heating panels shall be provided for each of the patient rooms along the perimeter to provide perimeter heating capacity. Existing low pressure steam generated in the basement travels up to the penthouse to provide humidification at the AHUs.

c. Mechanical and Electrical Rooms

The Mechanical Room shall be ventilated via exhaust fan and an outside air intake louver.

Electrical Room shall be cooled by a dedicated, energy star split air conditioning (AC) unit.

d. Patient and general use restrooms

Patient restrooms and general restrooms shall be exhausted via exhaust fans located in the penthouse.

e. Telecommunication/IT Rooms

Telecommunication Rooms shall be cooled by energy star, dedicated, Direct expansion (DX) split air conditioning (AC) unit.

f. Controls:

All new HVAC Equipment for this building will be operated by a new Building Automation System (BAS) capable of enabling/disabling and monitoring of HVAC equipment. Building Automation System shall be BACnet compliant.

ASSUMPTIONS AND BASIS OF ANALYSIS

Structural Design Criteria

Design Loads are in accordance with ASCE 7-16 Risk Category III Allowable Soil Bearing Pressure 1500 psf (assumed) Structural Loads:

Dead Load - weight of structure and equipment Attic Live Load - 20 psf Roof Live Load 20 psf (reducible) Roof Snow Load –

Ground Snow Load 30 psf Importance Factor 1.1 (Risk Category III) Exposure Factor 1.0 Thermal Factor 1.0 Wind Design Criteria - Exposure Category B Basic Wind Speed 122 mph (Risk Category III) Internal Pressure Coef. +/- 0.18 (enclosed structure)

Seismic Design Criteria – Spectral Response Acceleration

Ss (short period) 0.287

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-14 MONTROSE, NY

S1 (1 second period) 0.061 SMS (short period) 0.301 SM1 (1 second period) 0.098

Site Class D Seismic Design Category B Importance Factor 1.25 (Risk Category III)

Attic Modifications

The modifications to the structural steel frame that supports the existing roof rafters will consist of removal of one set of vertical cross bracing that extends between two vertical posts of the frame. The bracing must be removed to provide space for the new HVAC unit to fit under the frame. To provide a continuous load path for lateral loads after the removal of the vertical braces, new horizontal bracing members will be added at the top of the frame to transfer the lateral loads to the adjacent vertical cross bracing. A structural analysis of the modified bracing system was conducted using RAM Elements software to verify that the capacity of the modified frame was adequate to support the design roof loads.

The reinforced concrete attic floor will be modified to support the weight of the of the new HVAC equipment that will be located on the floor. The existing attic floor is a reinforced concrete slab with integral concrete beams. The floor will be modified by anchoring new structural steel members to the sides of the existing concrete beams. The new steel beams have sufficient capacity to support the equipment independent of the existing concrete beams.

Equipment Pads

New reinforced concrete pads will be provided to support the new HVAC equipment that will be located on the exterior of the building. The new pads will be 16 inches thick to provide a top surface approximately 4” above grade and provide 12” embedment below grade. The pads have been designed based on an assumed soil bearing capacity of 1500 psf. The calculated pressure based on the weight of the equipment is under 1000 psf.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-15 MONTROSE, NY

CHAPTER 03

MECHANICAL

The proposed newly renovated third floor of Building 13 Ward CD, otherwise known as “13 CD” will provide living accommodations for Veterans recovering from substance abuse. Mechanical scope of work for this project includes providing all new Heating, Ventilation and Air Conditioning (HVAC) systems including Air Handling Units (AHUs) with associated ductwork and air terminal units, Chiller with associated pumps and chilled water piping, heat exchangers for heating hot water etc, to meet with HVAC requirements of this space within this building.

The following is a list of VA and other design and construction criteria that shall be utilized by the A/E for

• PG-18-4, Standard Details and CAD Standards

• PG-18-5, Equipment Guide List

• PG-18-9, Space and Facility Planning Criteria

• PG-18-10, VA Design Manual o HVAC Design Manual o Sustainable Design Manual

• PG-18-12, Design Guides – Small House Model Design Guide

• PG-18-15, VA A/E Design Submission Requirements

• PG-18-17, Environmental Compliance program

• H-18-8, Seismic Design Handbook

• Special Design Requirements

• Cost Estimating Requirements

• A/E Quality Alerts

• A/E Design Alerts

• NFPA 101 – Most recent version

• International Building Code (IBC) – Most recent version

• International Mechanical Code 2018

• PG-18-15, VA A/E Design Submission Requirements

• VA 0055, Energy and Water Management Program

• VA 0056, Sustainable Buildings Program

• VA 0065, Climate Change Adaptation Planning

• Guiding Principles for Sustainable Federal Buildings

• Whole Building Commissioning Process Manual

• VA 0066, Sustainable Locations Program

• VA 1061, Prevention of Healthcare-Associated Legionella Disease

• VA 7545, Cultural Resource Management

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-16 MONTROSE, NY

• CAD: National CAD Standard, VHA Application Guide

• SMACNA Guidelines Sheet Metal and Air Conditioning Contractors’ National Association

• ASHRAE Standard 170 – 2008

• ASHRAE Standard 62.1 – 2019, Ventilation for Acceptable Indoor Air Quality

• ASHRAE Standard 90.1-2019, Energy Standard for Buildings Except Low-Rise Residential Buildings

Existing conditions: All the existing HVAC systems serving the existing third floor are in poor condition and shall be demolished. Steam coils for perimeter heating located throughout this floor shall be demolished and removed and steam pipes/connections to the coils shall be demolished starting from the coils to the point of connection to the PRV located in the basement. The basement houses an existing steam plant that includes PRVs and all necessary accessories required for steam to hot water conversion.

New heat exchangers shall be provided to generate hot water from the existing steam plant. The same steam system in the basement generates low pressure steam that provides humidification for the existing AHUs in the penthouse.

Design Concept

Heating, cooling, and ventilation for the spaces on this floor shall be provided by three Air Handling Units (AHUs) located in the penthouse. The following components included but not limited to, shall be provided for the AHUs:

9. Fan array supply fans, with each fan having its own VFD.

10. Chilled water-Cooling coil section.

11. Hot water Heating coil section.

12. Humidification section.

13. Access sections for all the coils and filters.

14. Mixing box/plenum.

15. Prefilter, MERV-7 and MERV 11

16. After Filter, MERV 15.

Supply air ducted from the AHUs shall provide cooling and heating to all the spaces on this floor. Air shall be supplied at the room levels via Variable Air Volume (VAV) units equipped with hot water reheat coils. Return air from these areas shall be ducted back to the mixing box of the AHUs via inline, centrifugal, return fans. The VAV units shall be controlled by wall mounted thermostats located in the rooms the VAV units would be serving. AHUs and chilled water pumps shall be located in the penthouse.

b. Chilled water System

Chilled water capacity for this floor shall be provided by two 80 tons rotary scroll air cooled chillers arranged in an N+1(sized for full capacity) configuration and located on grade in the mechanical yard adjacent to the building. Centrifugal, chilled water pumps in N+1

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-17 MONTROSE, NY

configuration, equipped with variable frequency drives, shall distribute the chilled water from the air-cooled chillers to the cooling coils of the AHUs via Schedule 40, Carbon black steel, chilled water pipes. Chilled water pumps, Buffer tank, Air separator and all other appurtenances shall be provided as part of the Chiller skid package.

Heating System

Heating shall be provided at the AHU preheat coils and the reheat coils at the VAVs by hot water generated in the basement via heat exchangers. There is an existing steam Pressure Regulator Valve (PRV) located in the basement to convert high pressure steam to medium and low-pressure steam. Existing heat exchangers provided as part of 13AB project generate hot water to meet with the heating needs of this floor. Hot water generated by existing heat exchangers are circulated within the building via two, 180 gpm, 80 ft head, end suction centrifugal pumps, in N+1 configuration and equipped with variable frequency drives. A new end suction, centrifugal hot water pump of 160 gpm and 80 ft head shall be added to serve this floor while one of the existing hot water pumps shall be made a standby pump, required during maintenance of the hot water system.

New hot water pump shall be located in the basement and integrated into the existing hot water system. Radiant hot water heating panels shall be provided for each of the patient rooms and restrooms along the perimeter to provide perimeter heating capacity. Existing low-pressure steam generated in the basement travels up to the penthouse to provide humidification at the AHUs.

g. Electrical Rooms

Electrical Room shall be cooled by a dedicated, energy star split air conditioning (AC) unit.

h. Patient and general use restrooms

Patient restrooms and general restrooms shall be exhausted via exhaust fans located in the penthouse.

i. Telecommunication/IT Rooms

Telecommunication Rooms shall be cooled by energy star, dedicated, Direct expansion (DX) split air conditioning (AC) unit.

j. Controls:

All new HVAC Equipment for this building will be operated by a new Building Automation System (BAS) capable of enabling/disabling and monitoring of HVAC equipment. Building Automation System shall be BACnet compliant.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-18 MONTROSE, NY

Outdoor Design Conditions This project is located at the Montrose, NY. Climatic design information is taken from the VA HVAC Design Manual, Chapter 7.1 and reproduced here:

As per VA Security Design Manual, the 1% summer and 99% winter values will be used.

Indoor Design Conditions:

Indoor design conditions will be in accordance with Chapter 6 room data sheets from the VA HVAC Design Manual.

Patient Rooms:

Cooling 75°F dry bulb occupied, 85°F dry bulb unoccupied

Heating 70°F dry bulb occupied, 55°F dry bulb unoccupied

Relative Humidity 30%-50%

Office rooms, Group rooms:

Cooling 75°F dry bulb occupied, 85°F dry bulb unoccupied

Heating 70°F dry bulb occupied, 55°F dry bulb unoccupied

Relative Humidity 30%-50%

Nursing stations/Workrooms:

Cooling 75°F dry bulb occupied, 85°F dry bulb unoccupied

Heating 70°F dry bulb occupied, 55°F dry bulb unoccupied

Relative Humidity 30%-50%

Electrical Room:

Cooling 80°F dry bulb

Heating 55°F dry bulb

HVAC Design Manual November 1, 2017 Location Weather

Station N o rt h L a ti tu d e

M S

L E le v a ti o n col. la

0.4% Col.

1b

99.6%

Col. 2a 1% col. 2b 99%

Col. 3 Wet Bulb

Annual Extreme Daily-Mean Db

Temperatures

Summer Winter Summer Winter 0.4% 1% Maximum Minimum

Db Wb Db Db Wb Db

NEW YORK

Montrose Stewart AFB 41.5 492 90.2 72.9 4.6 86.4 71.9 9.5 76 74.4 93.9 -2.0

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-19 MONTROSE, NY

Conditioned minimum supply air rates are as follows:

Patient rooms 6 ACH

Nursing Workroom/Stations 4 ACH

Medication room 6 ACH

Conditioned minimum outside air rates are as follows:

Patient rooms 2 ACH

Nursing Workroom/Stations 2 ACH

Medication room 2 ACH

Hallway/Corridor 0.06 cfm per sq. ft.

Office and Administration 2 ACH

Acoustic Criteria is as follows:

a. Patient rooms: NC 30 – 35

b. Nursing stations: NC 30 - 40

c. Group Rooms: NC 30 – 35

Vibration Criteria

a. Vibration isolators will be provided for all rotating and reciprocating equipment such as fans, pumps, and compressors.

b. Flexible piping and duct connections will be provided for all fans and pumps.

c. Isolation hangers will be provided for all piping located within 50 feet of pumps.

d. Concrete inertia bases will be provided for all distribution pumps.

HVAC Design Considerations

Ventilation calculations, as a minimum, shall be in accordance with the current edition of the ASHRAE Handbook of Fundamentals and International Mechanical Code. Computer generated loads shall be submitted with complete input and output summaries during the design phase. Load calculation software must be ASHRAE based.

Heating shall be provided to interior of the building for comfort and as needed to prevent any equipment and piping from freezing.

HVAC systems shall provide uniform and consistent interior space temperature while using equipment that meets or exceeds minimum energy efficiency requirements and is easily serviceable for maintenance needs.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-20 MONTROSE, NY

HVAC Materials and Accessories

All HVAC system materials shall be provided and installed in accordance with ASHRAE, SMACNA, and other applicable codes as listed herein. All HVAC ductwork and piping shall be insulated in accordance with ASHRAE 90.1.

Flexible duct shall be in conformance with NFPA 90A and UL 181 and may be used only for connections to air distribution devices to adapt minor offsets. Flexible duct shall be UL 181 listed and in accordance with SMACNA. Provide the minimum length required to make connections, but not greater than 5-feet in total length. Flexible connectors shall be provided between all fans and ducts.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-21 MONTROSE, NY

CHAPTER 04

PLUMBING

The proposed newly renovated third floor of Building 13 Ward CD, otherwise known as “13 CD” will provide living accommodations for Veterans recovering from substance abuse. Plumbing scope of work for this project includes providing all new low flow plumbing fixtures that meet VA criteria and ADA requirements including domestic hot-water, cold-water and hot water return piping. All sanitary waste piping will tie into existing building sanitary waste system. Domestic water will be from the building water supply. This floor will not contain any medical gas piping or natural gas piping.

The following is a list of VA and other design and construction criteria that shall be utilized by the A/E for the development of the design of this project:

• PG-18-1, Master Construction Specification Index

• PG-18-3, Design and Construction Procedures

• PG-18-4, Standard Details and CAD Standards

• PG-18-5, Equipment Guide List

• PG-18-9, Space and Facility Planning Criteria

• PG-18-10, VA Design Manual Plumbing

• PG-18-12, Design Guides – Small House Design Guide

• PG-18-13, Accessibility Information / Barrier Free Design Guide

• PG-18-14, Room Finishes, Door and Hardware Schedule

• PG-18-15, VA A/E Design Submission Requirements

• PG-18-17, Environmental Compliance program

• H-18-8, Seismic Design Handbook

• Special Design Requirements

• Cost Estimating Requirements

• A/E Quality Alerts

• A/E Design Alerts

• NFPA 101 – Most recent version

• International Building Code (IBC) – Most recent version

• International Plumbing Code

• VA 0055, Energy and Water Management Program

• VA 0056, Sustainable Buildings Program

• VA 0065, Climate Change Adaptation Planning

• VA 0066, Sustainable Locations Program

• VA 1061, Prevention of Healthcare-Associated Legionella Disease

• VA 7545, Cultural Resource Management

• CAD: National CAD Standard, VHA Application Guide

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-22 MONTROSE, NY

Existing conditions

All existing water piping will be removed to the main piping serving the floor. New water pipes will connect all the new plumbing fixtures to the hot and cold-water piping. The return piping system will be modified as needed to complete the existing hot water return piping to the existing water heater. All existing waste piping will be removed with the associated plumbing fixtures being removed. All vent lines will be routed to new walls and connected to existing vents through roof (VTR’s) that will remain. All waste and water risers passing through the floor will be relocated to new walls or chases as needed.

Design Concept

a. Plumbing Fixtures

i. Water closets will be white china wall hung with manual flush valve. Flow rate will be 1.28 gallons per flush.

ii. Lavatories will be white wall hung china fixtures with manual spread faucets.

Aerators will not be specified or allowed in this design. Water flow will be 0.5 GPM for public lavatories and 0.5 GPM for patient lavatories.

iii. Showers will as be noted in architectural narrative with a manual shower valve and ADA shower head.

iv. Break room sinks will be drop in stainless-steel with a manual faucet and sprayer.

v. Housekeeping rooms will have a floor sink and manual faucet.

vi. All fixtures will meet VA standard specifications.

vii. All faucets and shower heads will be selected to prevent legionella.

viii. All plumbing fixture numbers will be as outlined in the VA guide specification.

b. Domestic Water

i. The domestic water will be extended from the building systems. Hot water will be provided from the existing building water heater. No domestic water piping will be left on the floor that will not flow water and serve plumbing fixtures. Dead ends will be limited to no more than 2 pipe diameters.

c. Sanitary Waste

i. Sanitary will be extended from existing waste piping the building and floor

ii. In Group Room 2 there is an abandoned sanitary stack that will not be used in this design. We will work with the staff to ensure that the abandoned stack is properly addressed in this design.

The plumbing fixtures have been identified to determine if the water and waste demand for the floor is increasing or decreasing. The services to the floor have adequate water flow and pressure and waste service for the new design. This design does not include any medical gas, emergency fixtures or special waste.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-23 MONTROSE, NY

Plumbing Materials and Accessories

All Plumbing system materials shall be provided and installed in accordance with PG 18-10, and other applicable codes as listed herein.

Water piping will be copper with fiberglass insulation.

All waste piping will be cast iron with hub-less joints.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-24 MONTROSE, NY

CHAPTER 05

ELECTRICAL

The proposed newly renovated third floor of Building 13 Ward CD, otherwise known as “13 CD ” will provide living accommodations for Veterans recovering from substance abuse. The renovated space for veterans will provide offices, a conference room, resident rooms, nurse stations, storage spaces, electrical and mechanical rooms, group rooms, restrooms, corridors, and replacement of finish materials to incorporate current VA Standards.

The electrical fixtures in this building (receptacles, switches, lights, panelboards, disconnects, etc,) shall be replaced and updated to meet the current VA standards. Existing electrical panels located in the corridors on the floor shall be replaced with new electrical panels.

The following is a list of VA and other design and construction criteria that shall be utilized by the A/E for the development of the design of this project:

NFPA 70 National Electrical Code 2017

NFPA 75 Standard for protection of Electronic Computer / Data processing equipment.

NFPA 101 Life Safety Code

TIA-569 Commercial Building Standard for Telecommunication Pathways and Spaces

TIA/E1A-606 Administration Standard for the Telecommunications Infrastructure

TIA J-STD-607 Commercial Building Grounding and Bonding Requirements for

Telecommunications

PG-18-10 VA Electrical Design Manual (December 2015)

PG-18-10 VA Lighting Design Manual (December 2015)

PG-18-10 VA Telecommunications and Special Telecommunications Systems Design

Manual (February 2016)

DEMOLITION

Existing receptacles, light fixtures, disconnect switches, panelboards, wall switches, etc., shall be removed, all communication devices and cabling shall be removed, existing telecommunications infrastructure including racks, patch panels and active network equipment shall be demolished. Existing

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-25 MONTROSE, NY

fluorescent light fixtures shall be removed. Power to all existing mechanical equipment in this space shall be removed. All existing conductors and conduits shall be removed back to source.

NEW CONSTRUCTION

Interior Electrical Systems

New 84 and 42 pole, 3-phase, 4-wire 208Y/120V branch circuit panelboards shall be provided in the electrical rooms. The electrical panels shall serve loads such as special equipment, smoke detectors, receptacles, normal lights, IT equipment, HVAC loads, etc. The panels will be segregated by load type according to NEC. Existing life safety panel B13-LS shall be used to power emergency lights and any other life safety load.

Interior Lighting

The existing fluorescent fixtures shall be replaced with new LED downlights and 2’X2’ light fixtures in all areas. 0-10v dimming light switches, occupancy sensors, vacancy sensors and daylight sensors shall be provided as necessary for each space. Color temperature of fixtures will follow VA standard. Current standard calls for 3500K LED fixtures.

Telephone LAN/System

A new telecommunications main ground bar (TMGB) will be provided on a new backboard and will be bonded with a #4/0 Cu ground to the main electrical ground bar near panel MDP. Two new 2-post 19”

45U racks will be provided in the new telecom room on the second floor.

There will be fire rated plywood on three of the four perimeter walls. A new telecommunications ground bar (TGB) will be provided in the telecom room and will be bonded with a #4/0 Cu ground to the TMGB in the basement. Ladder type cable tray will be provided above the equipment racks. All horizontal cabling will be in basket type cable tray, J-hook, or conduit outside of the telecommunications room. Each space will get one combination voice data outlet per wall. Typical voice/data drops shall be two (2) data and one

(1) voice per drop. New voice/data cabling shall be Category 6. Category 6 wiring shall be colored as such: green for Access Points (AP’s), blue for data, white for voice, and red for APS.

Cable TV is brought into the building through the outside plant. Coaxial RG-6 cabling with F-type connectors and data outlets will be provided at all TV locations.

Security Systems

New access control system will be installed on all egress doors and where required by the Owner. A new access control system panel will be installed on the second floor’s Telecommunication Room.

CCTV cameras shall be installed to monitor hallways and on both sides of egress doors.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-26 MONTROSE, NY

Materials

• All conductors and cables will be installed in conduit with exception of communications cables. Rigid steel conduit or IMC conduit will be used in all exposed locations. EMT will be utilized with compression fittings only, where installed above ceilings and areas not exposed to physical damage.

• All power conductors will be copper, 600 volt, with type THHN/THWN insulation. MC cable will not be used. Minimum conductor for power and lighting circuits will be No.12 AWG. Control circuits will use No.14 AWG minimum.

• Critical power receptacles shall be hospital grade with a red face and stainless-steel faceplate.

Labeling shall be white lettering on red background.

Normal power receptacles shall be hospital grade with ivory face and stainless-steel faceplate. Labeling shall be white lettering on black background.

100% WORKING DRAWINGS SUBMISSION AUGUST 15, 2022

CB DESIGN GROUP, INC. 1-27 MONTROSE, NY

CHAPTER 06

FIRE PROTECTION

The project includes demolition and renovation of the VA Hudson Valley Healthcare System, Montrose Campus, Building 13, 2rd Floor, Ward CD totaling approximately 17,300 square feet. The ground and first stories shall be assumed to be occupied during construction. The construction type is Type II (222).

The scope of work for this project includes the reconstruction of the second floor in accordance with NFPA 101 §43.1.2.1. Newly constructed elements, components, and systems shall comply with the requirements of NFPA 101 applicable to new construction.

The existing building wet-pipe sprinkler system will be modified throughout all heated/conditioned areas of the reconstructed building.

The existing EST-3 Fire Alarm System will be modified to include new devices.

APPLICATION

VA has adopted the National Fire Codes (NFC) published by the National Fire Protection Association (NFPA), which establish a minimum acceptable level of life safety and property protection. Life safety requirements are specifically addressed in the Life Safety Code, NFPA 101. Where conflicts exist between codes, the designer shall follow the code specified in the text under the subject section of this VA Fire Protection Design Manual. Fire Protection design shall be based on the latest editions of the NFC at the Date of Award. See codes and standards section for editions used.

Fire protection features not addressed by the NFC or otherwise addressed by this…