16. CS502 Construction Details.pdf

PDF 2 MB Posted

Attached to
Z1DA--528A4-18-203 GROUND WATER MITIGATION BUILDING 30
Solicitation number
36C24222B0037
Issued by

About this file

This document contains construction drawings and details for the Z1DA--528A4-18-203 GROUND WATER MITIGATION BUILDING 30 federal contract opportunity. The drawings show plans for ground water pipe trench excavation and backfill, concrete flared end sections, precast concrete storm manholes, electric handholes for grass areas, and a level spreader earthen detail. Relevant construction details include specifications for non-woven geotextile fabric, Class I riprap stone, gravel base, compacted subgrade, concrete, reinforced precast structures, and asphalt waterproofing. The opportunity is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 for mitigation of ground water issues at the Batavia VA Medical Center in Batavia, New York.

View the file

Other files

File Type Posted
36C24222B0037 0005.docx DOCX document
014529-Testing_Laboratory.pdf PDF
333000 - Sanitary Sewer Utilities.pdf PDF
079200-Joint_Sealant.pdf PDF
12. CG101 Erosion and Sedimentation Control Plan A.pdf PDF
260519-Low-Voltage_EPower_Cond_and_Cables.pdf PDF
040100-Maintenance_of_Masonry.pdf PDF
15. CS501 Construction Details.pdf PDF
220523-General_Duty_Valves_for_Plumbing_Piping.pdf PDF
022113-Site_Survey.pdf PDF
13. CG102 Erosion and Sedimentation Control Plan B.pdf PDF
015719-Temporary_Enviromental_Controls.pdf PDF
3. GI003 Contractor Submittal List.pdf PDF
23. EP101 Power Basement New Work Plan.pdf PDF
101400-Signage.pdf PDF
312011-Earthwork_Short_Form.pdf PDF
018113-Sustanabile_Construction_Requirements.pdf PDF
36C24222B0037 0004.pdf PDF
220511-Common_Work_Results_for_Plumbing.pdf PDF
010000-General_Requirements.pdf PDF
329000-Planting.pdf PDF
4. CD100 Overall Existing Features Plan.pdf PDF
260526-Grounding_and_Bonding_for_Electrical_Systems.pdf PDF
024100-Demolition.pdf PDF
055000-Metal_Fabrication.pdf PDF
6. CD102 Existing Features and Demolition Plan B.pdf PDF
000115-List_of_Drawings.pdf PDF
260541-Underground_Electrical_Construction.pdf PDF
262911-Motor_Controllers.pdf PDF
Drawings Amendment 2.pdf PDF
1. GI001 Title Sheet.pdf PDF
321723-Pavement_Markings.pdf PDF
18. PP101 Plumbing Piping Plan.pdf PDF
320523-Cement_and_Conc_for_Ext_Imp.pdf PDF
040513-Masonry_Mortaring.pdf PDF
11. CU103 Groundwater Force Main Plan & Profile C.pdf PDF
321216-Asphalt_Paving.pdf PDF
2. GI002 General Notes Sheet.pdf PDF
17. CS503 Construction Details.pdf PDF
220512-General_Motor_Requirements_for_Plumbing_Equipment.pdf PDF
334000-Storm_Sewer_Utilities.pdf PDF
20. ED101 Electrical Systems Demolition Plan.pdf PDF
312319-Dewatering.pdf PDF
14. CG103 Erosion and Sedimentation Control Plan C.pdf PDF
014219-Reference_Standards.pdf PDF
10. CU102 Groundwater Force Main Plan & Profile B.pdf PDF
_CoverBatavia.pdf PDF
033053-Concrete_Short_Form.pdf PDF
323113-Chain_Link_Fences_and_Gates.pdf PDF
21. ES101 Electrical Systems New Work Plan.pdf PDF
Show 40 more

Latest 50 of 76 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

8/1/2022

Batavia VA Medical Center Batavia, NY

528A4-18-203

CHRIS GEARY PE# 099085

Schadler/Waldron Geary

Project Number

Building Number

Sheet Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORDSTAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date: Dwg. of

REVISED PER CONFERENCE CALL ON MARCH 9, 2021

REVISED PER 60% DESIGN REVIEW LETTERS

REVISED PER 90% DESIGN REVIEW LETTERS

REVISED PER FONT ISSUE/LINE ISSUE

5/11/2021 9/10/2021 2/4/2022 7/26/2022

CS502

16 23

Construction Details Bid Documents For Construction

Improve Ground Water, Building 30

NOTES:

1. ALL DISTURBED AREAS SHALL BE HYDROSEEDED FOLLOWING THE

PERMANENT SEEDING CHART.

RIPRAP GRADATION CHART

NON-WOVEN GEOTEXTILE FABRIC

(US 160NW OR APPROVED EQUIVALENT)

CLASS I RIPRAP STONE PER

RIPRAP GRADATION CHART

GRAVEL BASE (NYSDOT TYPE 2)

COMPACTED PER SPECIFICATIONS

(EXTEND UNDER END SECTION)

COMPACTED SUBGRADE

6"

10'

6'4'

5'

APPROXIMATELY

PROPERTY LINE

BURIED 9"

CONCRETE FLARED

END SECTION

8'

FLOW

COMPACTED SUBGRADE

1' 1'

8'

5'

898.75898.75

898.75898.75

898.75

CONCRETE FLARED

END SECTION

FLOW

898.25

898.25

4'

898.75

898.75

~ 899.5

899.5

899.5

899.5

2' 2.

2.

2'

FLOW

FLOW

EARTHEN LEVEL SPREADER DETAIL9 NTS

SOURCE: MODIFIED FROM NRCS LEVEL SPREADER DETAIL (10/1/2013)

(DESIGN FLOWS: 4 CFS OR LESS)

FLOWFLOW

1.5'

8 PRECAST CONCRETE STORM MANHOLE

NTS

VARIES

SEE PLANS

PIPE INVERT

NON SHRINK GROUT

PIPE SIZE AND ELEVATION

AS PER PLAN

6" BOTTOM SLAB (MIN.)

6"

(TYP.)

OPENING ECCENTRIC

OVER STEPS

8" THICK OPENING TO BE

OFFSET AS REQUIRED FOR

STEPS. DO NOT CAST FRAME &

COVER INTO ROOF OPENING

NON WOVEN

SEPARATION FABRIC

MANHOLE STEPS 12"

O.C.

12" MIN. OF SUBBASE (NYSDOT TYPE 2)

UNDISTURBED/UNEXCAVATED

EARTH

4000 PSI MIN. REINFORCED

CONCRETE MANHOLE BY FORT

MILLER CO., OR APPROVED

EQUAL. ASPHALT

WATERPROOFING COMPOUND

APPLIED TO ENTIRE EXTERIOR

SURFACE STRUCTURE, 3 MIL DFT.

BUTYL ROPE SEALANT

BETWEEN PRECAST

CONCRETE SECTIONS (TYP.)

24" MIN (TYP.)

ADJUST MANHOLE FRAME TO

GRADE WITH MIN. 4000 PSI

CONCRETE RISER SECTION OR

GRADE RINGS WITH

NON-SHRINKING CEMENT MORTAR

(NYSDOT ITEM NO. 705-21). GRADE

RINGS TO BE 3" MIN TO 12" MAX.

CEMENT FILLET AROUND

PERIMETER OF FRAME

LIGHT DUTY FRAME AND

COVER LABELED "STORM"

FINISHED GRADE

INSTALL CONCRETE FLOW

CHANNEL

3" HDPE

PRE-CAST HOLE WITH

FLEXIBLE RUBBER GASKET

PER ASTM C923. SEAL WITH

NON-SHRINK GROUT

NOTES:

1. MANHOLE LIDS SHALL PROVIDE MINIMUM 24-INCH OPENING AND INCLUDE THE WORDS "STORM".

2. THE CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FOR EACH STRUCTURE FOR APPROVAL PRIOR TO ORDERING.

3. ALL OPENINGS SHALL BE PRE-CAST. NO FIELD CUT OPENINGS ARE PERMITTED.

CONCRETE FLARED END SECTION10 NTS

SOURCE: OLDCASTLE PRE-CAST

USE 12" CONCRETE FLARED END SECTION THAT MEETS ASTM C76

11 ELECTRIC HANDHOLE - GRASS AREA

NTS

6"

6"

NYSDOT TYPE 1 STONE

COMPACTED TO 95% OF ASTM D698

MAXIMUM DENSITY UNLESS

OTHERWISE NOTED

LINE SIDES OF EXCAVATION

WITH MIRAFI HP270 GEOTEXTILE

OR APPROVED EQUIVALENT

PULLBOX

(SEE SPECIFICATION 26 05 33)

FIBERCRETE COVER

GRADE, FEATHER & HAND TAMP

BACKFILL TO CREATE FLUSH

INSTALLATION AND POSITIVE

DRAINAGE AWAY FROM BOX

PREFABRICATED FIBERCRETE

HANDHOLE (PEDESTRIAN RATED)

SUBGRADE COMPACTED TO 95% OF

ASTM D698 MAXIMUM DENSITY

UNLESS OTHERWISE NOTED

CLASS I RIPRAP STONE PER

RIPRAP GRADATION CHART

STORMWATER TRENCH DETAIL7 NTS

NOTES:

1. INTENT OF DETAIL IS TO SHOW WIDTHS AND MATERIAL FOR GROUND WATER PIPE TRENCH OPENING.

2. SEE O.S.H.A. SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION, SECTION 1926.652. TRENCH WALLS

SHALL BE IN COMPLIANCE WITH THE CURRENT O.S.H.A. REQUIREMENTS.

3. PRIOR TO COMMENCEMENT OF WORK, THE CONTRACTOR SHALL PROVIDE A SUBMITTAL OF THE TRENCHING

DETAIL FOR REVIEW AND APPROVAL TO MEET THE SAFETY SPECIFICATIONS 01 35 26 AND OSHA REGULATIONS.

4. MATERIAL AND COMPACTION REQUIREMENTS FOR STONE AND SUITABLE BACKFILL SHALL BE IN ACCORDANCE

WITH THE SPECIFICATIONS.

5. ALL DEPTHS SHOWN ARE AFTER BEING FULLY COMPACTED AS PER THE SPECIFICATIONS.

6. REFER TO GENERAL NOTE 8 ON DRAWING GI002.

12"

MIN.

3.

M

IN

4.

M

IN

IMPORTED ADDITIONAL

BEDDING MATERIAL WHERE

SOFT OR UNSTABLE MATERIAL

HAS BEEN REMOVED

IMPORTED STONE BEDDING

MATERIAL 12 O.D. + 8" 8" M

IN

M

IN

.IMPORTED STONE BACKFILL

MATERIAL 12 O.D. + 12"

M

IN

.IMPORTED CLEAN SAND

ENCASEMENT, 18" DEPTH

24"

MIN.

EXCAVATED

MATERIAL

RESTORATION AS

SHOWN ON PLAN

GROUND

SURFACE

UNDISTURBED

SUBGRADE

2" PVC CONDUIT WITH PULL STRINGS.

CONDUITS FROM INSIDE CRAWL SPACE IN

BUILDING 30 TO FINAL LOCATION

IDENTIFIED ON DRAWING CU103, EHH

JUST PRIOR TO THE 4' DIAMTER FLAT TOP

STORM MH A2. PROVIDE END CAPS TO

COVER PIPE ON ALL 4 ENDS. PVC PIPE

SHALL BE SUITABLE FOR DIRECT BURY.

TRENCH WIDTH=4.00'

3" HPDE FORCE MAIN

SUITABLE BACKFILL ABOVE

BEDDING MATERIAL WARNING

TAPE

STATION 0+00 TO 10+50

IMPORTED ADDITIONAL

BEDDING MATERIAL WHERE

SOFT OR UNSTABLE MATERIAL

HAS BEEN REMOVED

IMPORTED STONE BEDDING

MATERIAL 12 O.D. + 8" 8" M

IN

M

IN

.IMPORTED STONE BACKFILL

MATERIAL 12 O.D. + 12"

24"

MIN.

EXCAVATED

MATERIAL

RESTORATION AS

SHOWN ON PLAN

GROUND

SURFACE

UNDISTURBED

SUBGRADE

TRENCH WIDTH=4.00'

3" HPDE FORCE MAIN /

12" CONCRETE PIPE

SUITABLE BACKFILL ABOVE

BEDDING MATERIAL

STATION 10+50 TO 13+45

DE

PT

H

PE

R

PR

OF

IL

E O.

D.

TOPSOIL, 6" DEPTH TOPSOIL, 6" DEPTH

12" 12"