TRANE 2019 AHU Spec Sheets.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24221B0003
About this file
This document is a pre-solicitation notice for an upcoming competitive solicitation to replace air handler equipment at the Syracuse VA Medical Center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 intends to release an invitation for bid to replace Air Handler Units 04, 06, 22, 34, and 36. The contractor will replace the units in two phases based on work location, with a period of performance of 365 calendar days from notice to proceed. The project value is estimated between $2 million and $5 million. The solicitation is set aside 100% for Service-Disabled Veteran-Owned Small Businesses. Firms must self-perform 25% of the work and provide details in their bid. Payment and performance bonds and a 20% bid bond will be required. Unless additional notice is given, the full invitation for bid will be posted to SAM.gov.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid Walk Thru Attendees.pdf | ||
| 20532 Fellenzer Engineering VAMC Asbestos Sampling 7.22.20.pdf | ||
| 36C24221B0003 0004.docx | DOCX document | |
| 36C24221B0003 0003.docx | DOCX document | |
| 230923 rev Oct 2020 Siemens and JCI no POT.pdf | ||
| 36C24221B0003 0002.docx | DOCX document | |
| 232500 HVAC Water Treatment.pdf | ||
| RFI 36C24221B0003 Replace AHU 04 06 22 34 36 rev 2.docx | DOCX document | |
| 100 Bid Document Specifications.pdf | ||
| P07- NY202000026 9-25-2020 02.pdf | ||
| 36C24221B0003_1.docx | DOCX document | |
| 9 17 20 VA SYRACUSE 100 SET.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
Rental Services
Air Handling Units
April 2012 CHS-SVX02A-EN
Installation, Operation and Maintenance
© 2012 Trane All rights reserved CHS-SVX02A-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servicing this unit.
Important
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTIONs Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE:
Indicates a situation that could result in equipment or property-damage only
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
• Before installing/servicing this unit, technicians
MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken.
ALWAYS refer to appropriate MSDS sheets and
OSHA guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
• If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
CHS-SVX02A-EN 3
Table of Contents
Introduction
General Information
RSAU0025F0 AHU
RSAU0025F1 AHU
RSAU0050F1 AHU
RSAU0062F0 AHU
RSAU0062F1 AHU
Electrical Information
Piping Connection Configuration
RSAU0025F0
RSAU0025F1
RSAU0050F1
RSAU0062F0
RSAU0062F1
Duct Connection Configuration
RSAU0025F0
RSAU0025F1
RSAU0050F1
RSAU0062F0
RSAU0062F1
Controls Information Series F1 Rental AHU Controls
Series F0 Rental AHU Controls
Rigging Guidelines
Installation and Startup Guidelines
Maintenance Guidelines
Decommissioning Guidelines
4 CHS-SVX02A-EN
Introduction
This Installation Operation Manual (IOM) the rental air handling units (AHU) available to rent from Trane Rental Services for temporary cooling solutions. This includes AHU technical information, start-up information, and unit maintenance. The information contained in this document is provided to ensure the safe installation and operation of the equipment and its surroundings.
The information provided is to be used as a reference for each AHU to aid in determining unit size, power requirements, or lifting requirements.
If additional information regarding a particular unit is required, please contact Trane Rental Services.
Contact Trane Rental Services Marketing for availability of equipment (including ancillary items: pumps, flexible hose, flexible duct) prior to proceeding with securing the rental equipment. Equipment is available on a first-come, first-serve basis, but can be reserved with a signed rental agreement.
Call Rental Services 24 x 7 at (800) 755-5115 for specific questions.
Units Affected.
RSAU0025F0XX – 10,000cfm AHU with cooling only
RSAU0025F1XX – 10,000cfm AHU with cooling and heat
RSAU0050F1XX – 20,000cfm AHU with cooling and heat
RSAU0062F0XX – 25,000cfm AHU with cooling only
RSAU0062F1XX – 25,000cfm AHU with cooling and heat
Note: Where xx represents the unique inventory number.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
CHS-SVX02A-EN 5
General Information
Our rental air handling units are custom Trane air handlers that have been modified for use as rental units. The majority of the modifications are related to framing for rigging purposes, connection of chilled water piping, and temporary duct connection.
RSAU0025F0 and RSAU0062F0 Rental Air
Handlers
These air handling units contain only chilled water coils and do not have heating capability. Each unit has been selected for use with 100% outside air. Return plenums can be field fabricated by others if required.
An MP580 controller with touch screen display and wireless zone sensor is included with each unit. In addition, each unit includes a Trane TR1 variable frequency drive (VFD) that controls the fan motor. For additional information on the unit controls see “Controls Information”.
RSAU0025F1, RSAU0050F1, and RSAU0062F1
Rental Air Handlers
These AHUs contain both chilled water and hot water coils for year-round operation. Each unit has been selected for use with 100% outside air, but include return plenums and dampers to allow for 100% return air as well.
A Trane TR2 variable frequency drive (VFD) is included to control the fan motor. The VFD is controlled with a potentiometer dial. For additional information on the unit controls see "Controls Information."
Order of AHU Sections in Direction of Airflow
The figure below illustrates the general construction of all Trane Rental Air Handling Units
0 123�4��
6 CHS-SVX02A-EN
RSAU0025F0 AHU
Model Number ......................................................... TCCA
Water Connection Size ............................ 2.5 in. Victaulic
Ambient Operating Conditions1 ........................14–104°F
Supply Motor............................................................ 20 hp
Fused Disconnect .........................................................Yes
Number of Electrical Circuits
Discharge Configuration.................................. Horizontal
Flex Duct Connection Size ........................... 19 in. round
Number of Discharge Air Connections
Max Discharge Static Pressure .....................5.82 in. ESP
Filter Rack (Quantity and size)2 .....(4) 24” x 24”, (2) 24” x 12”
Nominal Air Flow (cfm) ..........................................10,000
Min/Max Air Flow (cfm)3 ..............................5,500/11,250 Selection is required for actual AHU performance.
1For ambient conditions below 40°F, glycol is recommended.
2Unit provided with standard 2 in. filters. Filter rack will accept up to 95% efficient MERV 14 filters.
3Min/Max airflow is dependent upon external static pressure requirement.
Contact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ........................................................ 460V 3-phase
Frequency ..................................................................60 Hz
Lug(s) can accept wire up to ......................#3 AWG wire
Minimum Circuit Ampacity (MCA) ................ 42.5 amps
Maximum Overcurrent Protection (MOP) ......... 60 amps Provided with 50 ft of 4 conductor, 8 awg multicable
For additional electrical information, contact Trane Rental Services.
Performance Data
Water Flow Rates
Dimensions and Weights
CFM 10,000
Air Pressure Drop through Unit (in H20) 2.98
Entering Air DB/WB Temp (F) 84/77
Leaving Air DB/WB Temp (F) 50/49.9
GPM 150
Entering Water Temp (F) 44
Leaving Water Temp (F) 56
Coil Water Pressure Drop (ft H20) 4.55
Sensible Capacity (MBH) 379.73
Total Capacity (MBH) 909.85
Coil Face Area (sqft) 20.43
Coil Rows 10
Minimum Maximum
Flow (GPM) 70 340
Pressure Drop (ft H20) 1.38 19.57
Maximum water side pressure is 150 psi (2.31’ H20 = 1 psi)
Length 16 ft 1 in
Width 7 ft 4 in
Height 7 ft 6 in
Weight 6,000 lb
Width includes permanently mounted piping manifold.
Lifting Device: Fork Lift or Crane
CHS-SVX02A-EN 7
Figure 1. RSAU0025F0 Fan Curve
.0 h p
.5 h p
.0 h p
.0 h p
.0 h p
.5 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
800 RPM
1000 RPM
1200 RPM
1400 RPM
1600 RPM
1800 RPM
2000 RPM
2200 RPM
2400 RPM
2600 RPM
2750 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
BHP adjusted 5% for approximate drive loss
UnitSize: 2000
Operating Airflow: 10000.00 cfm
Operating Static Pressure: 8.80 in H2O
Operating RPM: 2380.41
Operating Brake Power: 20.00 hp
Altitude: 0.00 ft
Design Temp: 70.00 F
Max BHP: 22.55 hp
Date: 10/30/12
Datafile: C:\Program Files\Trane Company\TOPSS\TCCA\TCC
0.0
2.5
5.0
7.5
10.0
12.5
15.0
0 5000 10000 15000 20000 25000
AHU-1 - Supply Fan [4]-1 Comefri ATZAF 20-20 DWDI Class II Centrifugal Air Foil Fan
T o ta l S ta tic
P re ss u re in H
O
Airflow (cfm)
8 CHS-SVX02A-EN
Figure 2. RSAU0025F0 Submittal
CHS-SVX02A-EN 9
RSAU0025F1 AHU
Model Number ......................................................... TCCB
Water Connection Size ............................ 2.5 in. Victaulic
Ambient Operating Conditions1 ........................14–104°F
Supply Motor............................................................ 25 hp
Fused Disconnect .........................................................Yes
Number of Electrical Circuits
Discharge Configuration.................................. Horizontal
Flex Duct Connection Size ........................... 19 in. round
Number of Discharge Air Connections
Max Discharge Static Pressure .......................6.0 in. ESP
Number of Return Air Connectors
Filter Rack (Quantity and size)2 .....(4) 24” x 24”, (2) 24” x 12”
Nominal Air Flow (cfm) ..........................................10,000
Min/Max Air Flow (cfm)3 ..............................5,500/11,250 Selection is required for actual AHU performance.
1For ambient conditions below 40°F, glycol is recommended.
2Unit provided with standard 2 in. filters. Filter rack will accept up to 95% efficient MERV 14 filters.
3Min/Max airflow is dependent upon external static pressure requirement.
Contact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ........................................................ 460V 3-phase
Frequency ..................................................................60 Hz
Lug(s) can accept wire up to ......................#3 AWG wire
Minimum Circuit Ampacity (MCA) ................... 44 amps
Maximum Overcurrent Protection (MOP) ......... 70 amps Provided with 50 ft of 4 conductor, 8 awg multicable
For additional electrical information, contact Trane Rental Services.
Performance Data
Water Flow Rates
Dimensions and Weights
CFM 10,000
Air Pressure Drop through Unit (in H20) 2.8
Cooling Coil
Entering Air DB/WB Temp (F) 84/77
Leaving Air DB/WB Temp (F) 55/54.9
GPM 155
Entering Water Temp (F) 45
Leaving Water Temp (F) 55
Coil Water Pressure Drop (ft H20) 8.53
Sensible Capacity (MBH) 323.9
Total Capacity (MBH) 778.8
Coil Face Area (sqft) 19.9
Coil Rows 8
Heating Coil
Entering Air DB/WB Temp (F) 45
Leaving Air DB/WB Temp (F) 78
GPM 36
Entering Water Temp (F) 180
Leaving Water Temp (F) 160
Coil Water Pressure Drop (ft H20) 2.38
Total Capacity (MBH) 357.89
Coil Face Area (sq ft) 19.9
Coil Rows 1
Minimum Maximum
CW Coil Flow (GPM) 70 200
CW Coil Pressure Drop (ft H20) 2.14 13.66
HW Coil Flow (GPM) 10 125
HW Coil Pressure Drop (ft H20) 0.2 28.07
Length 19 ft 0 in
Width 6 ft 11 in
Height 7 ft 6 in
Weight 8,350 lb
10 CHS-SVX02A-EN
Figure 3. RSAU0025F1 Fan Curve
.0 h p
.5 h p
.0 h p
.0 h p
.0 h p
.5 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
800 RPM
1000 RPM
1200 RPM
1400 RPM
1600 RPM
1800 RPM
2000 RPM
2200 RPM
2400 RPM
2600 RPM
2750 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
BHP adjusted 5% for approximate drive loss
UnitSize: 2000
Operating Airflow: 10000.00 cfm
Operating Static Pressure: 8.80 in H2O
Operating RPM: 2380.41
Operating Brake Power: 20.00 hp
Altitude: 0.00 ft
Design Temp: 70.00 F
Max BHP: 22.55 hp
Date: 10/30/12
Datafile: C:\Program Files\Trane Company\TOPSS\TCCA\TCC
0.0
2.5
5.0
7.5
10.0
12.5
15.0
0 5000 10000 15000 20000 25000
AHU-10k - Supply Fan [4]-1 Comefri ATZAF 20-20 DWDI Class II Centrifugal Air Foil Fan
T o ta l S ta tic P re ss u re in
H O
CHS-SVX02A-EN 11
Figure 4. RSAU0025F1 Submittal
12 CHS-SVX02A-EN
RSAU0050F1 AHU
Model Number ......................................................... TCCB
Supply and Return Water Connection Sizes (inches) ..................................... 2.5 in. Victaulic
Ambient Operating Conditions1 ...................... 14 – 104°F
Supply Motor.............................................................50 Hp
Fused Disconnect ..........................................................Yes
Number of Electrical Circuits
Discharge Air Configuration............................. Horizontal
Flex Duct Connection Size............................. 19 in. round
Number of Discharge Air Connections
Number of Return Air Connections
Max Discharge Static Pressure ....................... 6.3 in. ESP
Filters (Quantity and size)2 ...........................(9) 24” X 24” .................................................................. (3) 24” x 12”
Nominal Air Flow (cfm) .......................................... 20,000
Min/Max Air Flow (cfm)3 .............................. 8,500/22,250 Selection is required for actual AHU performance.
1For ambient conditions below 40°F, glycol is recommended.
2Unit provided with standard 2 in. filters. Filter rack will accept up to 95% efficient MERV 14 filters.
3Min/Max airflow is dependent upon external static pressure requirement.
Contact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ......................................................... 460V 3-phase
Frequency ..................................................................60 Hz
Minimum Circuit Ampacity (MCA) .................... 83 amps
Lug(s) can accept wire up to ..............................250MCM
Maximum Overcurrent Protection (MOP) ....... 125 amps Provided with 50 ft of 4 conductor, 4 awg multicable
For additional electrical information contact Trane Rental Services.
Performance Data
Water Flow Rates
Dimensions and Weights
CFM 20,000
Air Pressure Drop through Unit (in H20) 2.83
Cooling Coil
Entering Air DB/WB Temp (F) 84/77
Leaving Air DB/WB Temp (F) 55/54.9
GPM 310
Entering Water Temp (F) 45
Leaving Water Temp (F) 55
Coil Water Pressure Drop (ft H20) 14.29
Sensible Capacity (MBH) 647.8
Total Capacity (MBH) 1557.6
Coil Face Area (sqft) 40.6
Coil Rows 8
Heating Coil
Entering Air DB/WB Temp (F) 45
Leaving Air DB/WB Temp (F) 78
GPM 71
Entering Water Temp (F) 180
Leaving Water Temp (F) 160
Coil Water Pressure Drop (ft H20) 3.56
Total Capacity (MBH) 715.77
Coil Face Area (sqft) 40.6
Coil Rows 1
Minimum Maximum
CW Coil Flow (GPM) 100 350
CW Coil Pressure Drop (ft H20) 2.03 17.82
HW Coil Flow (GPM) 20 185
HW Coil Pressure Drop (ft H20) 0.31 22.71
Length 21 ft 7 in
Width 8 ft 6 in
Height 9 ft 1 in
Weight 11,600 lb
CHS-SVX02A-EN 13
Figure 5. RSAU0050F1 Fan Curve
.0 h p
.0 h p
.0 h p
.5 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p700 RPM
800 RPM
900 RPM
1000 RPM
1100 RPM
1200 RPM
1300 RPM
1400 RPM
1500 RPM
1600 RPM
1700 RPM
1800 RPM
1900 RPM
2000 RPM
2100 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
BHP adjusted 5% for approximate drive loss
UnitSize: 2500
Operating Airflow: 20000.00 cfm
Operating Static Pressure: 9.13 in H2O
Operating RPM: 1986.90
Operating Brake Power: 40.59 hp
Altitude: 0.00 ft
Design Temp: 70.00 F
Max BHP: 45.78 hp
Date: 10/30/12
Datafile: C:\Program Files\Trane Company\TOPSS\TCCA\TCC
0.0
2.5
5.0
7.5
10.0
12.5
15.0
0 5000 10000 15000 20000 25000 30000 35000
AHU-20k - Supply Fan [4]-1 Comefri ATZAF 25-25 DWDI Class II Centrifugal Air Foil Fan
T o ta l S ta tic P re ss u re in
H O
14 CHS-SVX02A-EN
Figure 6. RSAU0050F1 Submittal
CHS-SVX02A-EN 15
RSAU0062F0 AHU
Model Number ......................................................... TCCA
Water Connection Size ................................4 in. Victaulic
Ambient Operating Conditions1 ...................... 14 - 104°F
Supply Motor............................................................ 50 Hp
Fused Disconnect ......................................................... Yes
Number of Electrical Circuits
Discharge Configuration...................................Horizontal
Flex Duct Connection Size.............................19 in. round
Number of Discharge Air Connections
Max Discharge Static Pressure ..................... 6.00 in. ESP
Filter Rack (Quantity and size)2
........................ .(9) 24” x 24”, (3) 24” x 12”, (3) 12” x 24”
Nominal Air Flow (cfm) .......................................... 25,000
Min/Max Air Flow (cfm)3 ............................ 11,000/27,000 Selection is required for actual AHU performance.
1For ambient conditions below 40°F, glycol is recommended.
2Unit provided with standard 2” filters. Filter rack will accept up to 95% efficient MERV 14 filters.
3Min/Max airflow is dependent upon external static pressure requirement.
Contact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ......................................................... 460V 3-phase
Frequency ..................................................................60 Hz
Lug(s) can accept wire up to .......................... 2 awg wire
Minimum Circuit Ampacity (MCA) .................... 91 amps
Maximum Overcurrent Protection (MOP) ....... 100 amps For additional electrical information contact Trane Rental Services.
Provided with 50 ft of 4 conductor, 4 awg multicable
Performance Data
Water Flow Rates
Dimensions and Weights
CFM 25,000
Air Pressure Drop through Unit (in H20) 3
Entering Air DB/WB Temp (F) 84/77
Leaving Air DB/WB Temp (F) 50/49.9
GPM 378
Entering Water Temp (F) 44
Leaving Water Temp (F) 56
Coil Water Pressure Drop (ft H20) 12.26
Sensible Capacity (MBH) 949.3
Total Capacity (MBH) 2274.6
Coil Face Area (sq ft) 49.2
Coil Rows 10
Minimum Maximum
Coil Flow (GPM) 110 475
Pressure Drop (ft H20) 1.61 18.47
Maximum water side pressure is 150psi (2.31’ H20 = 1 psi)
Length 18 ft 2 in
Width4 8 ft 6 in
Height 10 ft 1 in
Weight 10,500 lbs
4Width does not include field installed piping manifold.
16 CHS-SVX02A-EN
Figure 7. RSAU0062F0 Fan Curve
.0 h p
.0 h p
.5 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p600 RPM
700 RPM
800 RPM
900 RPM
1000 RPM
1100 RPM
1200 RPM
1300 RPM
1400 RPM
1500 RPM
1600 RPM
1700 RPM
1800 RPM
1880 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
BHP adjusted 5% for approximate drive loss
UnitSize: 2800
Operating Airflow: 25000.00 cfm
Operating Static Pressure: 9.00 in H2O
Operating RPM: 1743.96
Operating Brake Power: 48.74 hp
Altitude: 0.00 ft
Design Temp: 70.00 F
Max BHP: 54.97 hp
Date: 10/30/12
Datafile: C:\Program Files\Trane Company\TOPSS\TCCA\TCC
0.0
2.5
5.0
7.5
10.0
12.5
15.0
0 5000 10000 15000 20000 25000 30000 35000 40000 45000
AHU 1-10 - Supply Fan [4]-1 Comefri ATZAF 28-28 DWDI Class II Centrifugal Air Foil Fan
T o ta l S ta tic
P re ss u re in H
O
CHS-SVX02A-EN 17
Figure 8. RSAU0062F0 Submittal
18 CHS-SVX02A-EN
RSAU0062F1 AHU
Model Number ..........................................................TCCB
Water Connection Size ................................4 in. Victaulic
Ambient Operating Conditions1 ...................... 14 - 104°F
Supply Motor............................................................ 50 Hp
Fused Disconnect ......................................................... Yes
Number of Electrical Circuits
Discharge Configuration...................................Horizontal
Flex Duct Connection Size.............................19 in. round
Number of Discharge Air Connections
Max Discharge Static Pressure ..................... 5.72 in. ESP
Number of Return Air Connections
Filter Rack (Quantity and size)2..... (12) 24” x 24”, (4) 12” x 24”
Nominal Air Flow (cfm) .......................................... 25,000
Min/Max Air Flow (cfm)3 ............................ 11,000/27,500 Selection is required for actual AHU performance.
1For ambient conditions below 40°F, glycol is recommended.
2Unit provided with standard 2” filters. Filter rack will accept up to 95% efficient MERV 14 filters.
3Min/Max airflow is dependent upon external static pressure requirement.
Contact Rental Services for specific airflow and static pressure information.
Electrical Data
Voltage ......................................................... 460V 3-phase
Frequency ..................................................................60 Hz
Lug(s) can accept wire up to .............................250 MCM
Minimum Circuit Ampacity (MCA) .................... 83 amps
Maximum Overcurrent Protection (MOP) ....... 125 amps For additional electrical information contact Trane Rental Services.
Provided with 50 ft of 4 conductor, 4 awg multicable
Performance Data
Water Flow Rates
Dimensions and Weights
CFM 25,000
Air Pressure Drop through Unit (in H20) 3.28
Cooling Coil
Entering Air DB/WB Temp (F) 84/77
Leaving Air DB/WB Temp (F) 50/49.9
GPM 378
Entering Water Temp (F) 44
Leaving Water Temp (F) 56
Coil Water Pressure Drop (ft H20) 11.78
Sensible Capacity (MBH) 949.3
Total Capacity (MBH) 2274.6
Coil Face Area (sqft) 50
Coil Rows 10
Heating Coil
Entering Air DB/WB Temp (F) 45
Leaving Air DB/WB Temp (F) 78
GPM 89
Entering Water Temp (F) 180
Leaving Water Temp (F) 160
Coil Water Pressure Drop (ft H20) 3.56
Total Capacity (MBH) 894.72
Coil Face Area (sqft) 40.6
Coil Rows 1
Minimum Maximum
CW Coil Flow (GPM) 125 500
CW Coil Pressure Drop (ft H20) 1.88 19.48
HW Coil Flow (GPM) 30 200
HW Coil Pressure Drop (ft H20) 0.55 21.77
Length 22 ft 9 in
Width4 8 ft 6 in
Height 9 ft 10.5 in
Weight 15,100 lbs
4Width does not include field installed piping manifold.
CHS-SVX02A-EN 19
Figure 9. RSAU0062F1 Fan Curve
.0 h p
.0 h p
.5 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p
.0 h p600 RPM
700 RPM
800 RPM
900 RPM
1000 RPM
1100 RPM
1200 RPM
1300 RPM
1400 RPM
1500 RPM
1600 RPM
1700 RPM
1800 RPM
1880 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
BHP adjusted 5% for approximate drive loss
UnitSize: 2800
Operating Airflow: 25000.00 cfm
Operating Static Pressure: 9.00 in H2O
Operating RPM: 1743.96
Operating Brake Power: 48.74 hp
Altitude: 0.00 ft
Design Temp: 70.00 F
Max BHP: 54.97 hp
Date: 10/30/12
Datafile: C:\Program Files\Trane Company\TOPSS\TCCA\TCC
0.0
2.5
5.0
7.5
10.0
12.5
15.0
0 5000 10000 15000 20000 25000 30000 35000 40000 45000
AHU-25k - Supply Fan [4]-1 Comefri ATZAF 28-28 DWDI Class II Centrifugal Air Foil Fan
T o ta l S ta tic P re ss u re in
H O
20 CHS-SVX02A-EN
Figure 10. RSAU0062F1 Submittal
CHS-SVX02A-EN 21
Electrical Information
Each AHU has an external fused disconnect as shown in Figure 11. In addition to the external fused disconnect, each unit has an external “start/stop” button on the outside of the control cabinet access door (Figure 12) and a circuit breaker inside the control cabinet (Figure 13).
Each 10,000 cfm unit is provided with a minimum of 50-ft of #8/4 600V electrical cable connected to the external fused disconnect. Each 20,000 cfm and 25,000 cfm unit is provided with a minimum of 50-ft of #4/4 600V electrical cable connected to the external fused disconnect.
Figure 11. Disconnect
Figure 12. Emergency stop
Figure 13. Circuit breaker
22 CHS-SVX02A-EN
Piping Connection Configuration
RSAU0025F0
To provide a single chilled water connection point for each 10,000 cfm air handling unit, a piping manifold has been made to connect each unit’s chilled water coils. Each 10,000 cfm unit has a manifold that is permanently installed on the unit for easy piping connection (Figure 14).
The contents of the drop down kit for the 10,000 cfm units are listed in the bill of material below. The manifold kit will ship in the mixed air chamber and can be accessed through the filter access door.
Bill of Material for RSAU0025F0 Piping Manifold
RSAU0025F1
Piping manifolds have been added to bring water connections to a more convenient elevation (Figure 14).
There are (2) separate manifolds for the chilled and hot water coils. For identification, the hot water piping has been painted red.
RSAU0050F1
To provide a single chilled water connection point and a single hot water connection point for each 20,000 cfm air handling unit, a piping manifold has been made to connect each of the unit's chilled water and hot water coils. Each 20,000 cfm unit has a manifold that is permanently installed on the unit for easy piping connection (Figure 15).
For identification purposes, the chilled water piping has been painted grey and the hot water piping has been painted red.
RSAU0062F0
To provide a single chilled water connection point for each 25,000 cfm air handling unit, a piping manifold has been made to connect each unit’s chilled water coils. Each 25,000 cfm unit has a manifold that must be field installed on each unit for easy piping connection (Figure 16). The contents of the piping manifold kit for the 25,000 cfm units are listed in the bill of material below. The manifold kit will ship in the mixed air chamber and can be accessed through the filter access door.
Bill of Material for RSAU0062F0 Unit Piping Manifold
Quantity Description of Items
8 2.5” Victaulic quick-snap couplings
2 2.5” 30” pipe section
4 2.5” Victaulic 90 degree elbows
Figure 14. RSAU0025F0 piping manifold
Figure 15. RSAU0050F1 piping manifold
Quantity Description of items
2 4” Manifold pipe section
2 4” Victaulic blank off
8 4” Victaulic quick-snap couplings
24 2.5” Victaulic quick-snap couplings
4 2.5” x 3” flex hose section
2 2.5” x 6” pipe section
8 2.5” Victaulic 90 degree elbows
2 4” x 6” Victaulic reducers
2 4” x 43” pipe section
4 4” Victaulic 90 degree elbows
Piping Connection Configuration
CHS-SVX02A-EN 23
Reference the Rental Services flexible water hose IOM, CHS-SVX01A-EN, for further information.
RSAU0062F1
Multiple coils need to be manifolded together in order to connect with a single water connection. The unit is supplied with manifolds for both the hot and cold water coils. Due to shipping restrictions, these manifolds ship loose in the discharge section of the unit and must be field installed. Due to variances in header locations, the cooling coil manifolds are not interchangeable. Each is labeled with (2) four letter codes. The first four letters (F1AO, for example) correspond to the last four letter of the AHU's identifying stencil. The second set of four letters designates where the piece should be installed on that unit (i.e. TLFT indicates it should be installed in the upper left position). The labels are painted onto each pipe in the cooling coil manifolds. See Figure 17.
Bill of Material for RSAU62F1 Unit Piping Manifold Figure 16. RSAU0062F0 piping manifold
Chilled Water Manifolds
Quantity Description of items 30 2.5" Coupling
4 2.5" Elbow
4 2.5" Tee
4 2.5" x 4" Reducer
2 4" Tee
4 4" Couplings
8 2.5" pipes of 3.25" nominal length
2 2.5" pipes of 16" nominal length
2 2.5" pipes of 15" nominal length
2 2.5" pipes of 3.5" nominal length
Hot Water Manifolds
Quantity Description of items 4 1.5" Elbow
8 1.5" Coupling
4 1.5" x 2.5" Reducer
4 2.5" Elbow
2 2.5" Tee
14 2.5" Coupling
2 2.5" pipes of 19" nominal length
2 2.5" pipes of 43" nominal length
1 2.5" pipe of 20" nominal length
1 2.5" pipe of 9" nominal length
Figure 17. New 25k Manifold Callout
BRGT:
Bottom Right Piece
TRGT:
Top Right Piece
TLFT:
Top Left Piece
BLFT:
Bottom Left Piece
24 CHS-SVX02A-EN
Duct Connection Configuration
RSAU0025F0
Each unit has two 19 in. diameter discharge air connections. Both discharge air connections have a manual damper to control air flow. The connections were made to accept one 20 in. diameter flexible duct. These units have a louver panel for 100% outside air operation.
Return plenums are not included but may be field fabricated and installed by others. Field fabricated plenums must be removed and the unit returned to the as-shipped condition prior to their return.
RSAU0025F1
Each unit has two 19 in. diameter discharge air connections and three 19 in. diameter return air connections. All of the discharge air connections and one of the return air connections have manual dampers to control air flow. The connections were made to accept one 20 in. diameter flexible duct. In addition to the return duct connections, these units have a louver panel for 100% outside air operation that may be used instead of the return air duct connections. A handle on the side of the unit (Figure 19) controls the linked dampers and allows you to choose either 100% outside air, 100% return air, or a combination of the two.
RSAU0050F1
Each unit has four 19 in. diameter discharge air connections and five 19 in. diameter return air connections (Figure 18). All four of the discharge air connections and two of the return air connections have manual dampers to control air flow. The connections were made to accept one 20 in. diameter flexible duct. In addition to the return duct connections, these units have a louver panel for 100% outside air operation that may be used instead of the return air duct connections. A handle on the side of the unit (Figure 19) controls the linked dampers and allows you to choose either 100% outside air, 100% return air, or combination of the two.
RSAU0062F0
Each unit has four 19 in. diameter discharge air connections. All four discharge air connections have a manual damper to control air flow. The connections were made to accept one 20 in. diameter flexible duct. These units have a louver panel for 100% outside air operation.
Return plenums are not included but may be field fabricated and installed by others. Field fabricated plenums must be removed and the unit returned to the as-shipped condition prior to their return.
RSAU0062F1
Each unit has four 19 in. diameter discharge air connections and five 19 in. diameter return air connections (Figure 18). All four of the discharge air connections and two of the return air connections have manual dampers to control air flow. The connections were made to accept one 20 in. diameter flexible duct. In addition to the return duct connections, these units have a louver panel for 100% outside air operation that may be used instead of the return air duct connections. A handle on the side of the unit (Figure 19) controls the linked dampers and allows you to choose either 100% outside air, 100% return air, or a combination of the two.
Reference the Rental Services flex duct engineering bulletin, CHS-PRB004-EN, for further information.
Figure 18. RSAU0050F1 and RSAU0062F1 return air connections
Figure 19. Handle to control linked dampers
Figure 20. Discharge Air Flex Duct Connection
CHS-SVX02A-EN 25
Controls Information
Series F1 Rental AHU Controls
Rental AHU's with the F1 designator come equipped with a Trane TR2 VFD (Figure 21) mounted in a control cabinet inside the unit. The VFD is controlled by using a digital potentiometer (Figure 22) that is located in a weatherproof box mounted on the exterior of the unit, just above the fused disconnect. The digital potentiometer is used to manually increase or decreased the fan speed of the unit.
For adjustment purposes, the number ‘0000’ on the Digital Potentiometer represents 20 Hz, while ‘1000’ represents 100% (60 Hz).
Series F0 Rental AHU Controls
Rental AHU's with the F0 designator come equipped with a Trane MP-580 controller (Figure 23) and Trane TR-1 VFD (Figure 24) mounted in a control cabinet inside the unit.
The controller is accessed by opening the external control cabinet door with an emergency stop button.
The unit control program can be accessed using a laptop computer with the Rover™ service tool software or the unit-mounted stand alone display. The stand alone display is mounted in a sealed cabinet on the front of the unit next to the external disconnect (Figure 25). The operator display touch screen is an intuitive operator interface for monitoring and changing unit control functions. With the operator display you can:
• Choose between “constant volume” or “VAV.”
• Choose specific air flow within specified range.
• Monitor space temperature, air flow, filter status, etc.
• Identify and troubleshoot problems.
• View and reset controller alarms.
Figure 21. Trane TR2 VFD
Figure 22. Digital Potentiometer
Figure 23. MP-580 controller
Figure 24. TR1 VFD
Controls Information
26 CHS-SVX02A-EN
The operator display includes a 7-day time clock that allows for time-of-day scheduling with two on/off times per day and up to 20 exception schedules per year.
Both the 10,000 cfm and 25,000 cfm units can be configured to run based on a specified air flow (constant volume CV) or be controlled by space temperature (VAV) using the Rover service tool or the stand alone display. If the unit is configured as CV, the unit air flow can be specified within a certain air flow range.
If the unit is configured as VAV, the unit will be controlled by the zone set-point using the wireless zone sensor that is provided with each unit. The wireless zone sensor can be found inside the control cabinet and is strapped in place for shipment. BAS-SVX04E-EN (or latest version) for additional information on wireless zone sensors.)
Figure 25. Unit Mounted Display
Figure 26. Typical Status Screen
CHS-SVX02A-EN 27
Rigging Guidelines
Each AHU has forklift pockets and either an overhead lifting frame or base mounted lifting lugs (Figure 27).Refer to pages 6 through 20 for unit dimensions and weights.
WARNING
Heavy Objects!
Use a forklift/crane of suitable capacity to move the unit. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Figure 27. 10,000 cfm Unit in Frame
28 CHS-SVX02A-EN
Installation and Startup Guidelines
In addition to the startup guidelines below, please refer to startup information contained in the Custom Climate Changer Installation, Operation and Maintenance Manual CAH-SVX01B-EN (or most recent version).
[ ] Install piping manifold supplied with unit (if applicable) and ensure all temporary piping is properly secured.
See piping configuration information on page 16.
[ ] Install the P-trap supplied with unit. The unit P-trap is located in a bin in the mixed air chamber that is accessed through the filter access door.
[ ] Close all coil drains.
[ ] Install all temporary supply ductwork and open manual dampers.
[ ] For F1 Series units only: Install temporary return air ductwork.
a. It is recommended that the number of return ducts exceeds the number of supply ducts by at least (1).
For example, if 4 supply ducts are used, 5 return ducts are recommended.
b. The return section consists of (2) separate louvers.
The bottom louver is open to the atmosphere and is used for fresh air intake. The top louver is covered with a return plenum and is used for return air ductwork.
c. The damper handle on the side of the unit operates the dampers for both the return and fresh air louvers. Moving the handle in one direction closes the fresh air intake while opening the return air intake, while moving the handle in the other direction does the opposite.
Connect any return ductwork to the duct connections without dampers first, then connect any additional return ducts on the bottom side of the plenum to the duct connectors with dampers.
For F0 Series Units Only: If the provided wireless zone sensor will be used, locate it, remove it from unit, and install it in the desired location before applying main power to the Air Handler.
[ ] Ensuring the power supply is de-energized, connect electrical cable supplied with unit to the breaker at the powersupply. See electrical information on page 15.
[ ] Ensure all personnel are in a safe location and that all doors on the Air Handler are closed.
[ ] Make sure all access doors are properly closed.
[ ] Energize the breaker at the power supply.
[ ] Depress Red Start/Stop button on exterior of electrical section door
[ ] Energize the fused disconnect on the Rental Air Handler.
[ ] Pull out red start/stop button to start fan operation
a. Locate the Digital Potentiometer in the externally mounted enclosure. Turn it clockwise to increase the fan speed. The number '0000' represents 20 Hz fan speed, while '1000' represents 100% fan speed (60 Hz).
b. If the fan does not start, depress the start/stop button. Open the door and ensure on the VFD interface that the unit is in HAND/ON mode.
[ ] For F0 Series Units only: Using the unit mounted stand alone touch screen display select either “CV” or “VAV.”
See page 18 for display location and explanation of the CV and VAV options.
Note: Power must be supplied to the unit to operate the touch screen display.
[ ] The Red start/stop button on the exterior of the electrical door will stop fan operation. To de-energize the unit, you must switch the fused disconnect to the open position.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concerning these procedures.
Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
CHS-SVX02A-EN 29
Maintenance Guidelines
Please refer to the Custom Climate Changer Installation, Operation and Maintenance Manual CAH-SVX01B-EN (or latest version).
[ ] Monitor differential pressure across the unit filters using the pressure gauge mounted on the outside of the filter access door and change the filters as necessary (see pages 6, 9 and 12 for unit filter rack quantities).
Filter status can also be monitored using the stand alone touch screen display mounted in a cabinet on the front of the unit.
30 CHS-SVX02A-EN
Decommissioning Guidelines
Reference the following guidelines for decommissioning rental AHUs prior to their return at the end of a rental job.
Please contact Trane Rental Services at 800-755-5115 for any additional information.
[ ] Turn the fused disconnect located on the front of the unit to the “OFF” position. Allow enough time for the supply fan to come to a complete stop before opening any unit access doors.
[ ] Once the fan operation has stopped, de-energize the main power supply.
[ ] Remove all external piping, temporary manifold pieces (see piping configuration section on page 22), and P-trap. Return P-trap and temporary manifold pieces to the bin located in the mixed air chamber that is accessed through the filter access door.
[ ] Open all coil drains.
1. Ensure the machine is either level, or tilted toward the water connections
2. Open all drains and vents. Ensure that fluid is draining freely. Check for drain line restriction if necessary.
a. Ensure drained fluid is collected and disposed of in accordance with any applicable environmental laws and regulations
3. Leave unit to drain until there is no more fluid coming out. This may take up to an hour or more. Do not relocate or release the unit for shipment until draining is complete.
4. Do not close the vents or valves. Leave all drains and vents open even after draining is complete
Recommended
5. In extreme cold conditions, flush coil with antifreeze solution to ensure residual fluid cannot freeze. Please contact Trane Rental Services if assistance is needed.
[ ] Remove all temporary ductwork and close manual dampers.
[ ] Disconnect electrical cable supplied with the unit from the power supply.
[ ] Make sure all access doors are properly closed.
[ ] Return additional hose, fittings, or cable (if furnished by Trane Rental Services) to appropriate containers for return shipment.
[ ] Notify Trane Rental Services (800-755-5115) if unit needs repair or has damage.
NOTICE:
Freezing Damage!
Trane Rental AHU units are prone to freeze damage caused by cold ambient temperatures. In addition to the guidelines below, please refer to the Trane Rental Services Freeze Protection Policy referenced in your rental agreement. Failure to take the outlined precautions may result in equipment damage for which customer will be liable.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts.
For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
We are committed to using environmentally conscious print practices that reduce waste.
© 2012 Trane All rights reserved
CHS-SVX02A-EN 02 April 2013
Supersedes CHS-SVN01A-EN
/ASCII85EncodePages false /AllowTransparency false /AutoPositionEPSFiles true /AutoRotatePages /None /Binding /Left /CalGrayProfile (Dot Gain 20%) /CalRGBProfile (sRGB IEC61966-2.1) /CalCMYKProfile (U.S. Web Coated \050SWOP\051 v2) /sRGBProfile (sRGB IEC61966-2.1) /CannotEmbedFontPolicy /Error /CompatibilityLevel 1.4 /CompressObjects /Tags /CompressPages true /ConvertImagesToIndexed true /PassThroughJPEGImages true /CreateJobTicket false /DefaultRenderingIntent /Default /DetectBlends true /DetectCurves 0.0000 /ColorConversionStrategy /CMYK /DoThumbnails false /EmbedAllFonts true /EmbedOpenType false /ParseICCProfilesInComments true /EmbedJobOptions true /DSCReportingLevel 0 /EmitDSCWarnings false /EndPage -1 /ImageMemory 1048576 /LockDistillerParams false /MaxSubsetPct 100 /Optimize true
/OPM 1
/ParseDSCComments true /ParseDSCCommentsForDocInfo true /PreserveCopyPage true /PreserveDICMYKValues true /PreserveEPSInfo true /PreserveFlatness true /PreserveHalftoneInfo false /PreserveOPIComments true /PreserveOverprintSettings true /StartPage 1 /SubsetFonts true /TransferFunctionInfo /Apply /UCRandBGInfo /Preserve /UsePrologue false /ColorSettingsFile () /AlwaysEmbed [ true /NeverEmbed [ true /AntiAliasColorImages false /CropColorImages true /ColorImageMinResolution 300 /ColorImageMinResolutionPolicy /OK /DownsampleColorImages true /ColorImageDownsampleType /Bicubic /ColorImageResolution 300 /ColorImageDepth 8 /ColorImageMinDownsampleDepth 1 /ColorImageDownsampleThreshold 1.50000 /EncodeColorImages true /ColorImageFilter /FlateEncode /AutoFilterColorImages false /ColorImageAutoFilterStrategy /JPEG /ColorACSImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] /ColorImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] /JPEG2000ColorACSImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 /JPEG2000ColorImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] /GrayImageDict << /QFactor 0.15 /HSamples [1 1 1 1] /VSamples [1 1 1 1] /JPEG2000GrayACSImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 /JPEG2000GrayImageDict << /TileWidth 256 /TileHeight 256 /Quality 30 /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict << /K -1 /AllowPSXObjects false /CheckCompliance [ /None /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False
/CreateJDFFile false…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .