20532 Fellenzer Engineering VAMC Asbestos Sampling 7.22.20.pdf
PDF 4 MB Posted
- Solicitation number
- 36C24221B0003
About this file
This document includes an asbestos sampling report and a notice for an upcoming federal contract solicitation. The asbestos sampling report details testing conducted at the Veterans Affairs Medical Center in Syracuse, New York, where samples were taken from various building materials and analyzed for asbestos content. None of the samples contained more than 1% asbestos. The related federal contract opportunity notice indicates the Syracuse VAMC will release an invitation for bid around November 2, 2020 for project number 528A7-18-720 to replace air handler units 04, 06, 22, 34, and 36. The work will be conducted in two phases, with a 365-day period of performance and estimated value between $2,000,000 to $5,000,000. The solicitation is reserved as a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid Walk Thru Attendees.pdf | ||
| 36C24221B0003 0004.docx | DOCX document | |
| 36C24221B0003 0003.docx | DOCX document | |
| 230923 rev Oct 2020 Siemens and JCI no POT.pdf | ||
| 36C24221B0003 0002.docx | DOCX document | |
| TRANE 2019 AHU Spec Sheets.pdf | ||
| 232500 HVAC Water Treatment.pdf | ||
| RFI 36C24221B0003 Replace AHU 04 06 22 34 36 rev 2.docx | DOCX document | |
| 100 Bid Document Specifications.pdf | ||
| P07- NY202000026 9-25-2020 02.pdf | ||
| 36C24221B0003_1.docx | DOCX document | |
| 9 17 20 VA SYRACUSE 100 SET.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C O L D E N C O R P O R A T I O N | 5 8 4 2 H E R I T A G E L A N D I N G D R I V E | E A S T S Y R A C U S E , N Y 1 3 0 5 7
P H O N E : 3 1 5 . 4 4 5 . 0 8 4 7 | F A X : 3 1 5 . 4 4 5 . 0 9 5 1
WWW.COLDEN.COM
July 30, 2020
Mr. Eric Fellenzer, P.E.
Fellenzer Engineering LLP 22 Mulberry Street Middletown NY 10940
Re: Asbestos Sampling
Veterans Affair Medical Center Colden Project No. 20532
Dear Mr. Fellenzer:
This letter and attachments will serve as our final report for the referenced project.
1.0 Introduction
Colden Corporation was retained by the Fellenzer Engineering LLP to conduct asbestos sampling of suspect materials at the Veterans Affairs Medical Center located at 800 Irving Avenue in Syracuse, New York. The areas to be surveyed were identified by Fellenzer Engineering. The materials to be sampled were identified by Colden. Joseph Cantone, CSP, an Industrial Hygienist with Colden, conducted the asbestos sampling on July 22, 2020. A copy of Mr. Cantone’s New York State Department of Labor (NYSDOL) asbestos inspector certificate and Colden’s NYSDOL asbestos license is provided in Attachment A.
2.0 Analytical Methods
Asbestos samples were submitted to and analyzed by AmeriSci Laboratories of New York, New York. The laboratory is certified for bulk asbestos analysis by the New York State Department of Health (NYSDOH) under the Environmental Laboratory Approval Program (ELAP). The Laboratory’s ELAP number is 11480. Friable bulk samples were analyzed for asbestos content using polarized light microscopy (PLM) in accordance with ELAP PLM Analysis Protocol
198.1. Non-friable asbestos samples were analyzed by PLM and by transmission electron microscopy (TEM) in accordance with ELAP PLM/TEM Analysis Protocol 198.6/198.4.
3.0 Results and Discussion
Sampling results are summarized and discussed in the following section. A copy of the laboratory reports is provided in Attachment B.
3.1 Asbestos Sampling Results
http://www.colden.com/
Mr. Eric Fellenzer Fellenzer Engineering 7/30/2020
Asbestos sampling results are summarized in Table 1. Material conditions were listed as good, damaged, or significantly damaged in accordance with the U.S. Environmental Protection Agency (EPA) definitions noted below.
• Good – Material with no visible damage, or showing only very limited damage.
• Damaged – Less than one-tenth of the material is damaged if the damage is evenly distributed, or one-quarter of the material is damaged and the damage is localized.
• Significantly Damaged – One-tenth or more of the material is damaged if the damage is evenly distributed or one-quarter or more of the material is damaged and the damage is localized.
The U.S. EPA and the NYSDOL define Asbestos Containing Materials (ACM) as materials that contain greater than 1 percent asbestos.
Table 1 Summary of Asbestos Bulk Sampling Results
Sample No. Sample Location Material
Description Condition Friable or non-friable
NOB
Lab Result
(percent asbestos)
20532-1A Roof top duct-adjacent to Unit 34 by exhaust vent Gray duct insulation coating
NA NA NA No asbestos detected
20532-1B Roof top duct-adjacent to Unit 34 by the door
NA NA NA No asbestos detected
20532-2A
Inside Unit 36- GLY REC Return line, at end of fiberglass insulation White insulation paint
NA NA NA No asbestos detected
20532-2B
Inside Unit 36- GLY REC Supply line, at end of fiberglass insulation
NA NA NA No asbestos detected
20532-3A Exterior of Unit 36, tube exiting at the base of the unit
Gray caulk
NA NA NA No asbestos detected
20532-3B Exterior of Unit 34, tube exiting at the base of the unit
NA NA NA No asbestos detected
7/30/2020
Sample No. Sample Location Material
Description Condition Friable or non-friable
NOB
Lab Result
(percent asbestos)
20532-4A Exterior of Unit 36, seam at base of the unit
White caulk
NA NA NA No asbestos detected
20532-4B Exterior of Unit 34, seam at base of the unit
NA NA NA No asbestos detected
20532-5A Exterior of Unit 36, upper vent seam
Dark gray caulk
NA NA NA No asbestos detected
20532-5B Exterior of Unit 34, upper vent seam NA NA NA No asbestos detected
20532-6A Roof- temporary AHU gooseneck exhaust
Seam sealant
NA NA NA No asbestos detected
20532-6B Roof- temporary AHU gooseneck exhaust
NA NA NA No asbestos detected
20532-7A Auditorium- ducts along stage ceiling
White duct seam tape
NA NA NA No asbestos detected
20532-7B Auditorium- ducts along stage ceiling NA NA NA No asbestos detected
20532-8A Auditorium roof-roof vent, exterior base seam
White caulk
NA NA NA No asbestos detected
20532-8B Auditorium roof-roof vent, exterior base seam
NA NA NA No asbestos detected
20532-9A Auditorium roof-roof vent, applied to exterior screws
Black sealant
NA NA NA No asbestos detected
20532-9B Auditorium roof-roof vent, applied to exterior screws
NA NA NA No asbestos detected
Bold indicates an asbestos containing material (ACM) NOB- non-friable organically bound NA- not applicable
7/30/2020
As indicated in Table 1, none of the materials sampled contain asbestos. In accordance with EPA and NYSDOL regulations, materials containing 1 percent or less of asbestos may be treated as non-ACM.
Photographs of the sampled materials are provided in Attachment C.
3.2 Survey Area Discussion
3.2.1 Kitchen and Pantry Area
The area identified for assessment was above the ceiling and in a chase. The ceiling is a metal pan ceiling system. The Veterans Affairs Medical Center employees opened up the ceiling system and provided access for Colden. No suspect materials were identified. The pipes and elbows are wrapped in fiberglass insulation.
3.2.2 Roof Top Units 34 and 36
The two units are stand alone and have interior access. The suspect materials identified were white caulk, gray caulk, dark gray caulk, white insulation paint and gray duct insulation coating.
None of the materials sampled contain asbestos.
3.2.3 Auditorium
The auditorium stage area was assessed. The only suspect material was seam tape applied to the ducts.
There was no asbestos detected in the seam tape.
3.2.3 Auditorium Roof
A roof top vent system and a gooseneck exhaust vent were assessed. White caulk and black sealant were identified on the roof vent system and seam sealant was identified on the gooseneck exhaust vent. None of the materials sampled contain asbestos.
If you have any questions or need additional information, please contact me at (315) 445-0847.
Sincerely, Colden Corporation
Prepared by: Reviewed by:
Colden Corporation Colden Corporation
Joseph Cantone, CSP Michael Howe, CIH Project Manager Principal/Senior Consultant
ATTACHMENT A
NYSDOL Certification and License
C O L D E N C O R P O R A T I O N | 5 8 4 2 H E R I T A G E L A N D I N G D R I V E | E A S T S Y R A C U S E , N Y 1 3 0 5 7
W W W . C O L D E N . C O M
NEW YORK STATE DEPT. OF LABOR HANDLING CERTIFICATE
CLASS C- AIR SAMPLING TECH
CLASS D- INSPECTOR
CLASS H- PROJECT MONITOR
CLASS I- PROJECT DESIGNER
(DOSH442)
C O L D E N C O R P O R A T I O N | 5 8 4 2 H E R I T A G E L A N D I N G D R I V E | E A S T S Y R A C U S E , N Y 1 3 0 5 7
W W W . C O L D E N . C O M
NEW YORK STATE DEPT. OF LABOR HANDLING LICENSE
ATTACHMENT B
Laboratory Reports
ATTACHMENT C
Photographs
Location- roof adjacent to Unit 34
Sample 20532-1A, gray duct insulation coating (Non-ACM)
Gray duct insulation coating
Location- inside Unit 36
Sample 20532-2A, white insulation paint (Non-ACM)
White insulation paint
Location- exterior of Unit 36
Sample 20532-3A, gray caulk (Non-ACM)
Gray caulk
Location- exterior of Unit 36
Sample 20532-4A, white caulk (Non-ACM)
White caulk
Location- exterior of Unit 36 vent
Sample 20532-5A dark gray caulk (Non-ACM)
Gray caulk
Location- Auditorium roof gooseneck exhaust vent
Sample 20532-6A, seam sealant (Non-ACM)
Seam sealant
Location- Auditorium ceiling
Sample 20532-7A, duct seam tape (Non-ACM)
Seam tape
Location- Auditorium roof-roof vent
Sample 20532-8A white caulk (Non-ACM) Sample 20532-9A black sealant (Non-ACM)
White caulk
Black sealant