This document is Chapter 7 of the EATON Powerware 9390 UPS (20-80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual, specifically addressing UPS system operation and configuration modes.

The manual details three primary operating modes for single-module and multiple-module parallel UPS systems. In Normal mode, utility AC power is converted to DC by a rectifier, with the inverter converting it back to regulated three-phase AC for the critical load while simultaneously charging the battery through a battery converter. Battery mode activates automatically during utility power outages or out-of-specification conditions, with the battery providing DC power to the inverter to maintain uninterrupted AC output to the load; the system sounds an audible horn and illuminates a visual indicator lamp on the front panel during this mode. Bypass mode provides direct utility AC power to the load through a static switch and backfeed protection contactor when the UPS detects an overload, load fault, or internal failure; this mode is a normal operating condition but provides no active power conditioning or battery support. The system automatically transitions between these modes based on power conditions and can be manually transferred to bypass mode using front panel controls. For parallel systems, up to four Uninterruptible Power Modules (UPMs) can be connected to provide increased load capacity and redundancy, with the system automatically distributing loads equally among available modules and switching all modules to bypass if any module becomes overloaded or unavailable. The manual emphasizes that bypass mode does not protect the critical load from voltage or frequency fluctuations, as indicated by a caution statement in the document.

View the file

Other files

File Type Posted
UPS Eaton 9390 product info.pdf PDF
36C24127Q0030_3.docx DOCX document
UPS Installation Instructions.pdf PDF
UPS Drawings and Other Info.pdf PDF
UPS Eaton PowerWare Replacement Photos.docx DOCX document
UPS Guide Specification.pdf PDF
36C24127Q0030_2.docx DOCX document
36C24127Q0030_1.docx DOCX document
Attachment B - Wage Determination No 2015-4019 rev 35.pdf PDF
Attachment A - Eaton 93E UPS manufacturer cut sheets and site electrical drawings Start-Up.pdf PDF
36C24127Q0030.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .