Static Uninterruptible Power Supply Guide Specification – Powerware 9390 40-160 kVA
This is a technical guide specification for a Static Uninterruptible Power Supply (UPS) system, Model Powerware 9390, rated 40-160 kVA. The specification describes a three-phase continuous duty, on-line, double conversion, solid-state UPS designed to operate with existing building electrical systems to provide power conditioning, back-up, and distribution for critical electrical loads. The UPS system shall consist of the UPS module containing a rectifier, inverter, battery charger, static bypass, and control/monitor panel; battery string(s) in line-and-match battery cabinets; and line-and-match accessory cabinets for transformers, maintenance bypass, parallel tie, and distribution applications.
The specification establishes comprehensive technical requirements across multiple operational modes (Normal, Battery, Recharge, and Bypass), environmental conditions (0 to +40°C operating temperature; -25 to +60°C storage temperature; 95% maximum relative humidity; up to 6,600 ft operational elevation), safety certifications (UL 1778 and CSA C22.2 NO.107.1-M91), and performance characteristics including output voltage regulation (±1% steady-state), transient voltage response (<±5%), efficiency up to 94%, and total harmonic distortion less than 2% for linear loads and 5% for non-linear loads. The manufacturer must be Eaton Electrical Inc. (Powerware brand) with minimum 40 years' experience in solid-state UPS design and manufacturing, ISO 9001 certification, a nationwide 7x24x365 call center, dedicated field service engineers deployed in key population areas with 24-hour emergency response capability, spare parts support providing 80% of emergency needs within 24 hours, and comprehensive preventive and corrective maintenance contracts. The system supports multiple UPS ratings from 40 kVA to 160 kVA with optional lower ratings, parallel configurations for up to eight modules for capacity or redundancy, and extensive monitoring/control features including digital LCD front panel display, SNMP network adapter for remote monitoring via standard web browsers, battery management system with automatic testing and runtime calculation, and multiple communication interfaces (RS232, building alarm monitoring, external emergency power-off contacts).
View the file
Other files
| File | Type | Posted |
|---|---|---|
| UPS Eaton 9390 product info.pdf | ||
| UPS Manual Section II Operation.pdf | ||
| 36C24127Q0030_3.docx | DOCX document | |
| UPS Installation Instructions.pdf | ||
| UPS Drawings and Other Info.pdf | ||
| UPS Eaton PowerWare Replacement Photos.docx | DOCX document | |
| 36C24127Q0030_2.docx | DOCX document | |
| 36C24127Q0030_1.docx | DOCX document | |
| Attachment B - Wage Determination No 2015-4019 rev 35.pdf | ||
| Attachment A - Eaton 93E UPS manufacturer cut sheets and site electrical drawings Start-Up.pdf | ||
| 36C24127Q0030.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .