Attachment 2_SprinklerScan.pdf
PDF 86 KB Posted
- Solicitation number
- 36C24126Q0613
About this file
This is a fire protection system inspection and testing report for Bedford VAMC Building 78 located at 200 Spring Road, Bedford, MA 01730. The inspection was completed on December 11, 2025, by Raymond Pratt of Vets Fire & Life Safety, with Stephen LaDuke serving as the building contact.
The report documents comprehensive testing of 60 devices across the building's wet pipe fire sprinkler system, including 16 tamper switches, 17 waterflow switches, 1 drain, 2 fire department connections, 1 check valve, 3 control valves, and 20 pressure gauges. Of the devices tested, 40 passed inspection while 20 gauges failed because their calibration dates have expired, requiring replacement per NFPA 25 13.2.4.2 standards. All tamper switches and waterflow switches passed their semi-annual and annual tests respectively. The failed gauges are distributed across multiple locations including the basement police dispatch, basement stairs 1-3, and first through fourth floor stairs. The proposed solutions report recommends replacing all 20 expired gauges on a time and materials basis. The inspection also confirmed proper operation of supervisory signal devices, fire department connections, check valves, and control valves throughout the system. Pressure readings from the main drain test at the basement police dispatch showed a supply pressure of 90 psi, restored pressure of 90 psi, and residual pressure of 60 psi over 15 seconds, all within acceptable parameters.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page of 1 19 Download Date: 06/03/2026
Executive Summary Generated by: BuildingReports.com
Building Information Building: Bedford VAMC BLDG 78 Contact: Stephen LaDuke
Address: 200 SPring Rd Phone: 781-885-9725
Address: Fax:
City/State/ZIP Code: Bedford, MA 01730 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Raymond Pratt
Address: 7 Sherri Lane Phone: (781) 779-9621
Address: Fax:
City/State/ZIP Code: St Peters, MO 63376 Mobile:
Country: United States of America Email: rpratt@feinewengland.com
Page of 2 19 Download Date: 06/03/2026
Inspection Completion Date: Dec 11, 2025 Building: Bedford VAMC BLDG 78 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Tamper Switch 16 16 0 16 0 16
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Waterflow Switch 17 17 0 17 0 17
EC 02.03.05 EP 09 Annual test of main drains at system low point or at all system risers. NFPA 25 (2023) 13.2.2
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Drain 1 1 0 1 0 1
EC 02.03.05 EP 10 Quarterly inspection of all fire department water supply connections
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Fire Dep't Connection 2 2 0 2 0 2
LS 02.01.35 EP 14 All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2024 18/19.3.5
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Check Valve 1 1 0 1 0 1
Control Valve 3 3 0 3 0 3
Gauge 20 0 20 20 0 20
Total Device Count: 60
Page of 3 19 Download Date: 06/03/2026
Certification
Building: Bedford VAMC BLDG 78
Inspector: Raymond Pratt Contact: Stephen LaDuke
Signed: Dec 12, 2025 Signed:
Page of 4 19 Download Date: 06/03/2026
Discrepancy Report Generated by: BuildingReports.com
Building: Bedford VAMC BLDG 78 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Reference
Building- Wet Pipe, Building- Gauge
42078539 Basement police dispatch Date Expired NFPA25 13.2.4.2
42078540 Basement police dispatch Date Expired NFPA25 13.2.4.2
84463270 Basement stair 1 Date Expired NFPA25 13.2.4.2
84463281 Basement stair 2 Date Expired NFPA25 13.2.4.2
84463282 Basement stair 3 Date Expired NFPA25 13.2.4.2
84463271 1st stair 1 Date Expired NFPA25 13.2.4.2
84463280 1st stair 2 Date Expired NFPA25 13.2.4.2
84463283 1st stair 3 Date Expired NFPA25 13.2.4.2
84463272 2nd stair 1 Date Expired NFPA25 13.2.4.2
84463279 2nd stair 2 Date Expired NFPA25 13.2.4.2
84463284 2nd stair 3 Date Expired NFPA25 13.2.4.2
84463273 3rd stair 1 Date Expired NFPA25 13.2.4.2
84463278 3rd stair 2 Date Expired NFPA25 13.2.4.2
84463285 3rd stair 3 Date Expired NFPA25 13.2.4.2
84463274 4th stair 1 Date Expired NFPA25 13.2.4.2
84463275 4th stair 1 Date Expired NFPA25 13.2.4.2
84463276 4th stair 2 Date Expired NFPA25 13.2.4.2
84463277 4th stair 2 Date Expired NFPA25 13.2.4.2
84463286 4th stair 3 Date Expired NFPA25 13.2.4.2
84463287 4th stair 3 Date Expired NFPA25 13.2.4.2
Code References NFPA25 13.2.4.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.
javascript:editViewDevice('42078539');
javascript:editViewDevice('42078540');
javascript:editViewDevice('84463270');
javascript:editViewDevice('84463281');
javascript:editViewDevice('84463282');
javascript:editViewDevice('84463271');
javascript:editViewDevice('84463280');
javascript:editViewDevice('84463283');
javascript:editViewDevice('84463272');
javascript:editViewDevice('84463279');
javascript:editViewDevice('84463284');
javascript:editViewDevice('84463273');
javascript:editViewDevice('84463278');
javascript:editViewDevice('84463285');
javascript:editViewDevice('84463274');
javascript:editViewDevice('84463275');
javascript:editViewDevice('84463276');
javascript:editViewDevice('84463277');
javascript:editViewDevice('84463286');
javascript:editViewDevice('84463287');
Page of 5 19 Download Date: 06/03/2026
Proposed Solutions Report Generated by: BuildingReports.com
Building: Bedford VAMC BLDG 78 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
Building- Wet Pipe, Building- Gauge
42078539 Basement police dispatch Replace T/M 42078540 Basement police dispatch Replace T/M 84463270 Basement stair 1 Replace T/M 84463281 Basement stair 2 Replace T/M 84463282 Basement stair 3 Replace T/M 84463271 1st stair 1 Replace T/M 84463280 1st stair 2 Replace T/M 84463283 1st stair 3 Replace T/M 84463272 2nd stair 1 Replace T/M 84463279 2nd stair 2 Replace T/M 84463284 2nd stair 3 Replace T/M 84463273 3rd stair 1 Replace T/M 84463278 3rd stair 2 Replace T/M 84463285 3rd stair 3 Replace T/M 84463274 4th stair 1 Replace T/M 84463275 4th stair 1 Replace T/M 84463276 4th stair 2 Replace T/M 84463277 4th stair 2 Replace T/M 84463286 4th stair 3 Replace T/M 84463287 4th stair 3 Replace T/M
Customer WO/PO #: (none)
Internal WO/PO #: (none)
T/M
Page of 6 19 Download Date: 06/03/2026
Inspection & Testing Generated by: BuildingReports.com
Building: Bedford VAMC BLDG 78 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q4/25 Pass Q4/25 Fail Q4/25 Tested YTD (2025) Total Quantity Tamper Switch 16 16 0 16 16
Device Type Location ScanID Address Q1/25 Q2/25 Q3/25 Q4/25 Tamper Switch outside ambulatory entrance 71417648 0 03/28-P 09/24-P 12/11-P Tamper Switch Basement stair 1 58984499 0 03/27-P 09/12-P 12/11-P Tamper Switch Basement stair 2 58984554 0 03/27-P 09/12-P 12/11-P Tamper Switch Basement stair 3 58984497 0 03/27-P 09/12-P 12/11-P Tamper Switch 1st stair 1 58984574 0 03/27-P 09/12-P 12/11-P Tamper Switch 1st stair 2 58984556 0 03/27-P 09/12-P 12/11-P Tamper Switch 1st stair 3 58984551 0 03/27-P 09/12-P 12/11-P Tamper Switch 2nd stair 1 58984572 0 03/27-P 09/12-P 12/11-P Tamper Switch 2nd stair 2 58984558 0 03/27-P 09/12-P 12/11-P Tamper Switch 2nd stair 3 58984493 0 03/27-P 09/12-P 12/11-P Tamper Switch 3rd stair 1 58984569 0 03/27-P 09/12-P 12/11-P Tamper Switch 3rd stair 2 58984560 0 03/27-P 09/12-P 12/11-P Tamper Switch 3rd stair 3 58984491 0 03/27-P 09/12-P 12/11-P Tamper Switch 4th stair 1 58984566 0 03/27-P 09/12-P 12/11-P Tamper Switch 4th stair 2 58984562 0 03/27-P 09/12-P 12/11-P Tamper Switch 4th stair 3 58984489 0 03/27-P 09/12-P 12/11-P
Device Total: 16 Return to Executive Summary
Page of 7 19 Download Date: 06/03/2026
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table
14.4.3.2 (17)(11)) Devices Tested Q4/25 Pass Q4/25 Fail Q4/25 Tested YTD (2025) Total Quantity Waterflow Switch 17 17 0 17 17
Device Type Location ScanID Address Q1/25 Q2/25 Q3/25 Q4/25 Waterflow Switch Basement police dispatch 58984500 0 03/27-P 09/12-P 12/11-P Waterflow Switch Basement stair 1 58984498 0 03/27-P 09/12-P 12/11-P Waterflow Switch Basement stair 2 58984553 0 03/27-P 09/12-P 12/11-P Waterflow Switch Basement stair 3 58984494 0 03/27-P 09/12-P 12/11-P Waterflow Switch 1st stair 1 58984573 0 03/27-P 09/12-P 12/11-P Waterflow Switch 1st stair 2 58984555 0 03/27-P 09/12-P 12/11-P Waterflow Switch 1st stair 3 58984550 0 03/27-P 09/12-P 12/11-P Waterflow Switch 2nd stair 1 58984570 0 03/27-P 09/12-F 12/11-P Waterflow Switch 2nd stair 2 58984557 0 03/27-P 09/12-P 12/11-P Waterflow Switch 2nd stair 3 58984492 0 03/27-P 09/12-P 12/11-P Waterflow Switch 3rd stair 1 58984568 0 03/27-P 09/12-P 12/11-P Waterflow Switch 3rd stair 2 58984559 0 03/27-P 09/12-P 12/11-P Waterflow Switch 3rd stair 3 58984490 0 03/27-P 09/12-P 12/11-P Waterflow Switch 4th stair 1 58984565 0 03/27-P 09/12-P 12/11-P Waterflow Switch 4th stair 2 58984561 0 03/27-P 09/24-P 12/11-P Waterflow Switch 4th stair 3 58984488 0 03/27-P 09/12-P 12/11-P Waterflow Switch Penthouse 58984563 0 03/27-P 09/24-P 12/11-P
Device Total: 17 Return to Executive Summary
Page of 8 19 Download Date: 06/03/2026
EC 02.03.05 EP 09
Annual test of main drains at system low point or at all system risers. NFPA 25 (2023) 13.2.2
A main drain test shall be conducted annually for each water supply lead-in to a building water-based fire protection system to determine whether there has been a change in the condition of the water supply. (NFPA 25-23 13.2.2) Devices Tested Q4/25 Pass Q4/25 Fail Q4/25 Tested YTD (2025) Total Quantity Drain 1 1 0 1 1
Device Type Location ScanID Address Q1/25 Q2/25 Q3/25 Q4/25 Drain Basement police dispatch 58984431 0 03/27-P 06/11-P 09/12-P 12/11-P
Device Total: 1 Return to Executive Summary
Page of 9 19 Download Date: 06/03/2026
EC 02.03.05 EP 10 Quarterly inspection of all fire department water supply connections
Fire department connections shall be inspected quarterly to verify the following: Connections are visible and accessible, couplings or swivels are not damaged and rotate smoothly, plugs or caps are in place and undamaged, gaskets are in place and in good condition, identification signs are in place, the check valve is not leaking, the automatic drain valve is in place and operating properly, the clapper is in place and operating properly, there are no obstructions, and visible piping supplying the fire department connection is undamaged. (NFPA 25-23 13.8.1) Devices Tested Q4/25 Pass Q4/25 Fail Q4/25 Tested YTD (2025) Total Quantity Fire Dep't Connection 2 2 0 2 2
Device Type Location ScanID Address Q1/25 Q2/25 Q3/25 Q4/25 Fire Dep't Connection Ground Rear Loading 58984430 0 03/28-P 06/11-P 09/12-P 12/11-P Fire Dep't Connection 1st 1st floor ambulatory entrance 58984429 0 03/28-P 06/11-P 09/12-P 12/11-P
Device Total: 2 Return to Executive Summary
Page of 10 19 Download Date: 06/03/2026
LS 02.01.35 EP 14
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2024 18/19.3.5
Internal components shall be cleaned, repaired, or replaced as necessary in accordance with the manufacturer's instructions. (NFPA 25-23 13.4.2.2) Devices Tested Q4/25 Pass Q4/25 Fail Q4/25 Tested YTD (2025) Total Quantity Check Valve 1 1 0 1 1
Device Type Location ScanID Address Q1/25 Q2/25 Q3/25 Q4/25 Check Valve Basement police dispatch 58984432 0 03/27-P 09/12-P 12/11-P
Device Total: 1 Return to Executive Summary
Page of 11 19 Download Date: 06/03/2026
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2024 18/19.3.5
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q4/25 Pass Q4/25 Fail Q4/25 Tested YTD (2025) Total Quantity Control Valve 3 3 0 3 3
Device Type Location ScanID Address Q1/25 Q2/25 Q3/25 Q4/25 Control Valve Basement police dispatch 58984501 0 03/27-P 09/12-P 12/11-P Control Valve Basement police dispatch 58984502 0 03/27-P 09/12-P 12/11-P Control Valve Penthouse 58984564 0 03/27-P 09/12-P 12/11-P
Device Total: 3 Return to Executive Summary
Page of 12 19 Download Date: 06/03/2026
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2024 18/19.3.5
Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (NFPA 25- 23 13.2.5.2) Devices Tested Q4/25 Pass Q4/25 Fail Q4/25 Tested YTD (2025) Total Quantity Gauge 20 0 20 20 20
Device Type Location ScanID Address Q1/25 Q2/25 Q3/25 Q4/25 Gauge Basement police dispatch 42078540 0 03/27-P 09/12-P 12/11-F Gauge Basement police dispatch 42078539 0 03/27-P 09/12-P 12/11-F Gauge Basement stair 1 84463270 0 03/27-P 09/12-P 12/11-F Gauge Basement stair 2 84463281 0 03/27-P 09/12-P 12/11-F Gauge Basement stair 3 84463282 0 03/27-P 09/12-P 12/11-F Gauge 1st stair 1 84463271 0 03/27-P 09/12-P 12/11-F Gauge 1st stair 2 84463280 0 03/27-P 09/12-P 12/11-F Gauge 1st stair 3 84463283 0 03/27-P 09/12-P 12/11-F Gauge 2nd stair 1 84463272 0 03/27-P 09/12-P 12/11-F Gauge 2nd stair 2 84463279 0 03/27-P 09/12-P 12/11-F Gauge 2nd stair 3 84463284 0 03/27-P 09/12-P 12/11-F Gauge 3rd stair 1 84463273 0 03/27-P 09/12-P 12/11-F Gauge 3rd stair 2 84463278 0 03/27-P 09/12-P 12/11-F Gauge 3rd stair 3 84463285 0 03/27-P 09/12-P 12/11-F Gauge 4th stair 1 84463275 0 03/27-P 09/12-P 12/11-F Gauge 4th stair 1 84463274 0 03/27-P 09/12-P 12/11-F Gauge 4th stair 2 84463276 0 03/27-P 09/12-P 12/11-F Gauge 4th stair 2 84463277 0 03/27-P 09/12-P 12/11-F Gauge 4th stair 3 84463286 0 03/27-P 09/12-P 12/11-F Gauge 4th stair 3 84463287 0 03/27-P 09/12-P 12/11-F
Device Total: 20 Return to Executive Summary
Page of 13 19 Download Date: 06/03/2026
Service Summary Generated by: BuildingReports.com
Building: Bedford VAMC BLDG 78 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other Gauge Visually Checked 20
Total 20
Passed Check Valve Visually Checked 1 Control Valve Visually Checked 3 Drain Quarterly 1 Fire Dep't Connection Quarterly 2 Tamper Switch Visually Checked 16 Waterflow Switch Visually Checked 17
Total 40 Grand Total 60
Page of 14 19 Download Date: 06/03/2026
Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Bedford VAMC BLDG 78 Building-, Building- This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was tested and passed; however, if the OK checkbox is unchecked, refer to the Inspection & Testing section for test status.
Alarms Tamper Switch
Type Description Location # of Turns Zone/Address OK ScanID Lever Supervisory outside ambulatory entrance 0 71417648 Lever Supervisory Basement stair 3 0 58984497 Lever Supervisory Basement stair 2 0 58984554 Lever Supervisory Basement stair 1 0 58984499 Lever Supervisory 1st stair 3 0 58984551 Lever Supervisory 1st stair 2 0 58984556 Lever Supervisory 1st stair 1 0 58984574 Lever Supervisory 2nd stair 3 0 58984493 Lever Supervisory 2nd stair 2 0 58984558 Lever Supervisory 2nd stair 1 0 58984572 Lever Supervisory 3rd stair 3 0 58984491 Lever Supervisory 3rd stair 2 0 58984560 Lever Supervisory 3rd stair 1 0 58984569 Plug Supervisory 4th stair 3 0 58984489 Lever Supervisory 4th stair 2 0 58984562 Lever Supervisory 4th stair 1 0 58984566
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor 6 0 58984500 Vane System Sensor 4 0 58984494 Vane Potter 4 0 58984553 Vane Potter VSR 4 0 58984498 Vane Potter 4 0 58984550 Vane System Sensor 4 0 58984555 Vane Potter VSR 4 0 58984573 Vane Potter 4 0 58984492 Vane Potter 4 0 58984557 Vane Potter 4 0 58984570 javascript:editViewDevice('71417648');
javascript:editViewDevice('58984497');
javascript:editViewDevice('58984554');
javascript:editViewDevice('58984499');
javascript:editViewDevice('58984551');
javascript:editViewDevice('58984556');
javascript:editViewDevice('58984574');
javascript:editViewDevice('58984493');
javascript:editViewDevice('58984558');
javascript:editViewDevice('58984572');
javascript:editViewDevice('58984491');
javascript:editViewDevice('58984560');
javascript:editViewDevice('58984569');
javascript:editViewDevice('58984489');
javascript:editViewDevice('58984562');
javascript:editViewDevice('58984566');
javascript:editViewDevice('58984500');
javascript:editViewDevice('58984494');
javascript:editViewDevice('58984553');
javascript:editViewDevice('58984498');
javascript:editViewDevice('58984550');
javascript:editViewDevice('58984555');
javascript:editViewDevice('58984573');
javascript:editViewDevice('58984492');
javascript:editViewDevice('58984557');
javascript:editViewDevice('58984570');
Page of 15 19 Download Date: 06/03/2026
Vane Potter 4 0 58984490 Vane Potter 4 0 58984559 Vane Potter 4 0 58984568 Vane Potter 4 0 58984488 Vane Potter VSR 4 0 58984561 Vane Potter VSR 4 0 58984565 Vane potter electric 2.5 0 58984563
Components Check Valve
Type Location Manufacturer Model # Internal Date Size OK ScanID
Grooved Basement police dispatch
Victaulic 08/27/2023 4" 58984432
Control Valve Type Location Manufacturer Model # OK ScanID Butterfly Basement police dispatch Victaulic 58984501
Position Size Status Description Open 6" Supervised Main Control
Control Valve Type Location Manufacturer Model # OK ScanID Butterfly Basement police dispatch Victaulic 58984502
Position Size Status Description Open 6" Supervised Main Control
Control Valve Type Location Manufacturer Model # OK ScanID Butterfly Penthouse Victaulic 58984564
Position Size Status Description 4" Main Control
Devices Drain
Current Inspection
Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID Main Basement police dispatch 2" 90 90 60 15 58984431
Previous Inspections
September 12, 2025
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Basement police dispatch 2" 85 85 55 3 58984431
June 11, 2025
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Basement police dispatch 2" 60 60 50 58984431 javascript:editViewDevice('58984490');
javascript:editViewDevice('58984559');
javascript:editViewDevice('58984568');
javascript:editViewDevice('58984488');
javascript:editViewDevice('58984561');
javascript:editViewDevice('58984565');
javascript:editViewDevice('58984563');
javascript:editViewDevice('58984432');
javascript:editViewDevice('58984501');
javascript:editViewDevice('58984502');
javascript:editViewDevice('58984564');
javascript:editViewDevice('58984431');
javascript:editViewDevice('58984431');
javascript:editViewDevice('58984431');
Page of 16 19 Download Date: 06/03/2026
Fire Dep't Connection
Location Type Size Qty BallDrip Rotating Swivels
Hydro Test
PSI
Length of Test
5-Year Hydro
OK ScanID
Ground Rear Loading
Siamese 2.5" 1 Yes Yes 07/28 /2023
58984430
1st 1st floor ambulatory entrance
Freestanding 4" 1 Yes Yes 07/28 /2023
58984429
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure United Brass 1/4 Air/Water 42078540
Location Service Date Static psi Min. Range Max. Range Basement police dispatch 06/27/2025 90 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure United Brass 1/4 Air/Water 42078539
Location Service Date Static psi Min. Range Max. Range Basement police dispatch 06/27/2025 90 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID
System Sensor 1/4 Air/Water 84463282
Location Service Date Static psi Min. Range Max. Range Basement stair 3 06/27/2025 130 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463281
Location Service Date Static psi Min. Range Max. Range Basement stair 2 06/27/2025 125 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure United Brass 1/4 Air/Water 84463270
Location Service Date Static psi Min. Range Max. Range Basement stair 1 06/27/2025 125 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463283
Location Service Date Static psi Min. Range Max. Range 1st stair 3 06/27/2025 125 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID javascript:editViewDevice('58984430');
javascript:editViewDevice('58984429');
javascript:editViewDevice('42078540');
javascript:editViewDevice('42078539');
javascript:editViewDevice('84463282');
javascript:editViewDevice('84463281');
javascript:editViewDevice('84463270');
javascript:editViewDevice('84463283');
Page of 17 19 Download Date: 06/03/2026
System Pressure System Sensor 1/4 Air/Water 84463280
Location Service Date Static psi Min. Range Max. Range 1st stair 2 06/27/2025 110 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463271
Location Service Date Static psi Min. Range Max. Range 1st stair 1 06/27/2025 110 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463284
Location Service Date Static psi Min. Range Max. Range 2nd stair 3 06/27/2025 110 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463279
Location Service Date Static psi Min. Range Max. Range 2nd stair 2 06/27/2025 110 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463272
Location Service Date Static psi Min. Range Max. Range 2nd stair 1 06/27/2025 110 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463285
Location Service Date Static psi Min. Range Max. Range 3rd stair 3 06/27/2025 100 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463278
Location Service Date Static psi Min. Range Max. Range 3rd stair 2 06/27/2025 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463273
Location Service Date Static psi Min. Range Max. Range 3rd stair 1 06/27/2025 120 0 300
Gauge javascript:editViewDevice('84463280');
javascript:editViewDevice('84463271');
javascript:editViewDevice('84463284');
javascript:editViewDevice('84463279');
javascript:editViewDevice('84463272');
javascript:editViewDevice('84463285');
javascript:editViewDevice('84463278');
javascript:editViewDevice('84463273');
Page of 18 19 Download Date: 06/03/2026
Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463286
Location Service Date Static psi Min. Range Max. Range 4th stair 3 06/27/2025 100 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463287
Location Service Date Static psi Min. Range Max. Range 4th stair 3 06/27/2025 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463276
Location Service Date Static psi Min. Range Max. Range 4th stair 2 06/27/2025 70 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463277
Location Service Date Static psi Min. Range Max. Range 4th stair 2 06/27/2025 100 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID
Potter 1/4 Air/Water 84463275
Location Service Date Static psi Min. Range Max. Range 4th stair 1 06/27/2025 100 0 300
Gauge Type Manufacturer Model # Size Fill Type OK ScanID System Pressure Potter 1/4 Air/Water 84463274
Location Service Date Static psi Min. Range Max. Range 4th stair 1 06/27/2025 70 0 300 javascript:editViewDevice('84463286');
javascript:editViewDevice('84463287');
javascript:editViewDevice('84463276');
javascript:editViewDevice('84463277');
javascript:editViewDevice('84463275');
javascript:editViewDevice('84463274');
Page of 19 19 Download Date: 06/03/2026
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Bedford VAMC BLDG 78 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Check Valve LS 02.01.35 EP 14 1.67% 1
Control Valve LS 02.01.35 EP 14 5.00% 3
Drain EC 02.03.05 EP 09 1.67% 1
Fire Dep't Connection EC 02.03.05 EP 10 3.33% 2
Gauge LS 02.01.35 EP 14 33.33% 20
Tamper Switch EC 02.03.05 EP 01 26.67% 16
Waterflow Switch EC 02.03.05 EP 02 28.33% 17
Device Type Qty Model # Type Description Install Date
In Service - 5 Years to 10 Years Building- Wet Pipe, Building-
Waterflow Switch 1 Vane Alarm 09/04/2020 Control Valve 2 Butterfly Main Control 09/04/2020 Drain 1 Main 06/30/2020 Fire Dep't Connection 1 Freestanding 06/30/2020 Fire Dep't Connection 1 Siamese 06/30/2020 Gauge 1 06/30/2020 Gauge 14 System Pressure 06/30/2020 Tamper Switch 11 Lever Supervisory 06/30/2020 Tamper Switch 1 Plug Supervisory 06/30/2020 Tamper Switch 1 pcvs 2 Lever Supervisory 06/30/2020 Waterflow Switch 9 Vane Alarm 06/30/2020 Waterflow Switch 4 VSR Vane Alarm 06/30/2020 Gauge 1 06/30/2020 Gauge 1 System Pressure 06/30/2020 Tamper Switch 3 Lever Supervisory 06/30/2020 Waterflow Switch 2 Vane Alarm 06/30/2020 Gauge 1 System Pressure 06/30/2020 Check Valve 1 Grooved 06/30/2020 Control Valve 1 Butterfly Main Control 06/30/2020 Waterflow Switch 1 Vane Alarm 06/30/2020 Gauge 2 System Pressure 06/04/2020
| Sprinkler Inspection, Testing and/or Maintenance Certificate |
| Executive Summary |
| Discrepancy Report |
| Proposed Solutions Report |
| Inspection & Testing |
| Service Summary |
| Wet Pipe Fire Sprinkler Systems |
| Inventory & Warranty Report |