About this file

This document is a fire alarm system inspection report for Bedford VAMC Building 78 located at 200 Spring Road, Bedford, MA 01730, conducted on April 22, 2026, by Vets Fire & Life Safety inspector Julian Thomas.

The inspection covered 411 total devices across multiple categories, with 405 devices passing and 6 devices failing or requiring attention. Key findings include: all duct detectors (12), heat detectors (17), pull stations (39), and smoke detectors (101) tested and passed; all visual and audible alarm devices including 2 horn/strobes, 18 releasing devices, 116 speaker/strobes, and 82 strobes passed their annual tests; 1 control panel (EST3 model, installed February 2020 in Basement Rm B14E) passed its protected fire alarm control panel test; and 6 annunciators and expander panels passed their tests. The primary discrepancy identified involves 6 batteries with expired dates located at: 1st Rm 1228 electrical closet (2 batteries), Basement Electrical closet B16C (2 batteries), and 3rd Electrical closet 358 (2 batteries). All failed batteries require replacement per NFPA72 Table 14.4.3.2 (9)(5), which mandates battery replacement or load testing every 3 years. The proposed solutions report indicates these replacements are available on a time-and-materials basis with model BPS 10a specified for two units and other units unspecified. The system contains EST, Edwards, System Sensor, and other manufacturers' equipment with most devices installed between February 2018 and February 2025, with inventory showing 24.57% smoke detectors and 28.22% speaker/strobes as primary notification components.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page of 1 42 Executive Summary

Vets Fire & Life Safety Download Date: 06/03/2026

Executive Summary Generated by: BuildingReports.com

Building Information Building: Bedford VAMC BLDG 78 Contact: Stephen LaDuke

Address: 200 SPring Rd Phone: 781-885-9725

Address: Fax:

City/State/ZIP Code: Bedford, MA 01730 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Vets Fire & Life Safety Inspector: Julian Thomas

Address: 7 Sherri Lane Phone: (781) 910-6142

Address: Fax:

City/State/ZIP Code: St Peters, MO 63376 Mobile:

Country: United States of America Email: jthomas@feinewengland.com

System Control Unit Manufacturer: EST Inspection Date: 04/22/2026 IDC Style:

Model Number: EST3 Install Date: 02/25/2020 SLC Style:

Software Version: Version Date: 02/27/2020 NAC Style:

Location: Basement Rm B14E Telecommunications/Fire Alarm

Current Protection: Breaker

Page of 2 42

Vets Fire & Life Safety Download Date: 06/03/2026

Inspection Completion Date: Apr 22, 2026 Building: Bedford VAMC BLDG 78 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2026) Untested YTD

(2026) Total

Quantity Duct Detector 9 9 0 12 0 12

Heat Detector 0 0 0 17 0 17

Pull Station 26 26 0 39 0 39

Smoke Detector 70 70 0 101 0 101

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2026) Untested YTD

(2026) Total

Quantity Horn/Strobe 1 1 0 2 0 2

Releasing Device 11 11 0 18 0 18

Speaker/Strobe 80 80 0 116 0 116

Strobe 69 69 0 82 0 82

EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Devices Tested This

Quarter Pass Fail Tested YTD

(2026) Untested YTD

(2026) Total

Quantity Duct Detector 9 9 0 12 0 12

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2026) Untested YTD

(2026) Total

Quantity Control Panel 1 1 0 1 0 1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2026) Untested YTD

(2026) Total

Quantity Annunciator 2 2 0 2 0 2

Battery 9 3 6 15 0 15

Expander Panel 5 5 0 6 0 6

Total Device Count: 411

Page of 3 42

Vets Fire & Life Safety Download Date: 06/03/2026

Certification

Company: Vets Fire & Life Safety Building: Bedford VAMC BLDG 78

Inspector: Julian Thomas Contact: Stephen LaDuke

Page of 4 42 Discrepancy Report

Vets Fire & Life Safety Download Date: 06/03/2026

Discrepancy Report Generated by: BuildingReports.com

Building: Bedford VAMC BLDG 78 Control Panel: 1 - EST EST3 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade

No items found during this inspection.

ScanID Location Problem Address Reference

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Battery

65575364 1st Rm 1228 electrical closet Date Expired 1 NFPA72 Table

14.4.3.2 (9)(5)

Y401522 1st Rm 1228 electrical closet Date Expired 1 NFPA72 Table

14.4.3.2 (9)(5)

Code References NFPA72 Table 14.4.3.2 (9) (5)

Replace the battery or conduct a load test of the battery capacity every 3 years.

Building: Bedford VAMC BLDG 78 Control Panel: 16 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade

No items found during this inspection.

ScanID Location Problem Address Reference

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Battery

65575426 Basement At Electrical closet B16C Date Expired 16-9 NFPA72 Table

14.4.3.2 (9)(5)

65575427 Basement At Electrical closet B16C Date Expired 16-9 NFPA72 Table

14.4.3.2 (9)(5)

84464401 3rd Electrical closet 358 Date Expired 16-9 NFPA72 Table

14.4.3.2 (9)(5)

84464402 3rd Electrical closet 358 Date Expired 16-9 NFPA72 Table

14.4.3.2 (9)(5) javascript:editViewDevice('65575364');

javascript:editViewDevice('Y401522');

javascript:editViewDevice('65575426');

javascript:editViewDevice('65575427');

javascript:editViewDevice('84464401');

javascript:editViewDevice('84464402');

Page of 5 42 Discrepancy Report

Vets Fire & Life Safety Download Date: 06/03/2026

Code References NFPA72 Table 14.4.3.2 (9) (5)

Replace the battery or conduct a load test of the battery capacity every 3 years.

Page of 6 42 Proposed Solutions Report

Vets Fire & Life Safety Download Date: 06/03/2026

Proposed Solutions Report Generated by: BuildingReports.com

Building: Bedford VAMC BLDG 78 Control Panel: 1 - EST EST3 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Battery 65575364 1st Rm 1228 electrical closet Replace BPS 10a T/M Y401522 1st Rm 1228 electrical closet Replace BPS 10a T/M

Building: Bedford VAMC BLDG 78 Control Panel: 16 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Battery 65575426 Basement At Electrical closet B16C Replace T/M 65575427 Basement At Electrical closet B16C Replace T/M 84464401 3rd Electrical closet 358 Replace T/M 84464402 3rd Electrical closet 358 Replace T/M

Internal WO/PO #: (none) T/M

Page of 7 42 Notes & Recommendations

Download Date: 06/03/2026

Notes & Recommendations Generated by: BuildingReports.com

Building: Bedford VAMC BLDG 78 Control Panel: 1 - EST EST3 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

Note Device Type Location Comment ScanID

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

1 Smoke Detector 2nd Elevator Lobby Passed 51496481 Elevator recall

2 Smoke Detector 3rd Elevator Lobby Elevator Recall Passed 51496521 Visual Only

Building: Bedford VAMC BLDG 78 Control Panel: 16 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

Note Device Type Location Comment ScanID

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

3 Smoke Detector Basement By Service Elevator Passed 51496312 Visual inspection

4 Smoke Detector 3rd Freight Elevator Passed 51496527 Elevator recall smoke javascript:editViewDevice('51496481');

javascript:editViewDevice('51496521');

javascript:editViewDevice('51496312');

javascript:editViewDevice('51496527');

Page of 8 42 Inspection & Testing

Download Date: 06/03/2026

Inspection & Testing Generated by: BuildingReports.com

Building: Bedford VAMC BLDG 78 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Duct Detector 9 9 0 12 12

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Duct Detector Basement Rm B26 51496328 16-9-278 04/22-P Duct Detector Basement By B16 Pharmacy 51496329 16-9 273 04/22-P Duct Detector Basement Rm B13C Clothing

Room AHU Rm B13 51496582 1-9-261 03/25-P

Duct Detector 1st Main Entrance 51496453 16-9-301 04/22-P Duct Detector 4th By Rm 443 51496585 16-5-39 04/22-P Duct Detector 4th By Rm 436 Electrical Closet 51496584 16-5 37 04/22-P Duct Detector 4th Rm 480 Nurse Station 59134006 16-5 38 04/22-P Duct Detector 4th By Rm 456 51496610 16-5-32 04/22-P Duct Detector 4th By Rm 476 51496609 16-5-35 04/22-P Duct Detector 4th By Family Room 416 51496591 16-5 31 04/22-P Duct Detector Penthouse Elevator Equipment

Rm 51496548 16-45416 05/10-P 03/25-P

Duct Detector Penthouse Elevator Equipment Rm HV-1

32820242 16-45435 03/25-P

Device Total: 12 Return to Executive Summary

Page of 9 42

Download Date: 06/03/2026

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.

(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Heat Detector 0 0 0 17 17

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Heat Detector Penthouse Elevator Equipment

Rm 63167605 1-16050002 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

63167604 1-16050006 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

63167603 1-16050022 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

63167602 1-16050019 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

63167601 1-16050020 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496568 1-16050010 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496565 1-16050009 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496564 1-16050011 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496562 1-16050015 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496561 1-16050013 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496560 1-16050012 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496555 1-16050007 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496554 1-16050016 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496553 1-16050014 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496552 1-16050033 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496551 1-16050021 05/10-P 03/25-P

Heat Detector Penthouse Elevator Equipment Rm

51496550 1-16050008 05/10-P 03/25-P

Device Total: 17 Return to Executive Summary

Page of 10 42

Download Date: 06/03/2026

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Pull Station 26 26 0 39 39

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Pull Station Basement Exit in room B28 51496320 16-9 436 04/22-P Pull Station Basement Exit in room B27 51496321 16-9-434 04/22-P Pull Station Basement Exit in room B19A

Canteen 60240028 16-9 404 03/25-P 04/22-P

Pull Station Basement Exit in rear of kitchen 60240029 16-9-405 04/22-P Pull Station Basement Patriot Store Storage

Room 96545024 16-9-140 04/22-P

The above device replaced ScanID 60240043:

Pull Station Basement Patriot Store Storage Room

60240043 16-9-140 04/22-R

Pull Station Basement Exit in room B25 Pharmacy

51496326 16-9-439 03/25-P 04/22-P

Pull Station Basement By elevator/By room B14G

60240026 16-9 411 03/25-P

Pull Station Basement Stair 4/Exit in room B12F

51496358 16-9 379 03/25-P

Pull Station Basement Stair 3/Exit in room B13F

51496347 16-9 378 03/25-P

Pull Station Basement By Stair 2 51496313 16-9 410 03/25-P Pull Station Basement Exit by Rm B29 51496318 16-9 435 03/25-P Pull Station Basement By Rm B18 Patriot

Store 51496343 16-9-408 03/25-P

Pull Station 1st By Stair 5 51496380 16-9-387 04/22-P Pull Station 1st By Stair 4/In room 1217 51496576 16-9-390 04/22-P Pull Station 1st Exit by Room 1216 51496378 16-9-391 04/22-P Pull Station 1st By Stair 3 51496376 16-9-393 04/22-P Pull Station 1st By Stair 2 51496361 16-9-412 04/22-P Pull Station 1st Main Entrance 51496367 16-9-394 04/22-P Pull Station 1st By Stair 1 51496403 16-9-415 04/22-P Pull Station 1st Exit by Rm 1118 51496407 16-9-416 04/22-P Pull Station 2nd At Stair 1 51496431 16-9-133 04/22-P Pull Station 2nd Rm 236 Nurse Station 51496429 16-9-153 04/22-P Pull Station 2nd By Stair 4 51496450 16-9-131 03/25-P Pull Station 2nd By Stair 3 51496440 16-9-132 03/25-P Pull Station 2nd By Stair 2 51496416 16-9-159 03/25-P

Page of 11 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Pull Station 3rd rm320 nurses station 51496518 16-9 129 04/22-P Pull Station 3rd At Stair 4 59133991 16-9 126 03/25-P 04/22-P Pull Station 3rd By Stair 1 51496600 16-9-130 04/22-P Pull Station 3rd By Stair 2 51496508 16-9-128 03/25-P 04/22-P Pull Station 3rd At Stair 3 59133986 16-9-127 03/25-P Pull Station 4th By Stair 1 32820247 16-9-147 04/22-P Pull Station 4th Rm 429 Nurse Station 37477740 16-9-149 04/22-P Pull Station 4th Rm 480 Nurse Station 51496593 16-9-148 04/22-P Pull Station 4th By Stair by Rm 465 51496596 16-9-152 04/22-P Pull Station 4th By Rm 457 51496595 16-9-151 04/22-P Pull Station 4th By Rm 478 51496594 16-9 150 04/22-P Pull Station 4th By Stair 2 51496542 16-9-140 03/25-P Pull Station Penthouse Elevator Room

Equipment Rm Roof Exit 51496570 16-5-141 03/25-P

Pull Station Penthouse Elevator Room Equipment Rm Entrance

51496556 16-5-142 03/25-P

Device Total: 39 Return to Executive Summary

Page of 12 42

Download Date: 06/03/2026

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Smoke Detector 70 70 0 101 101

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Smoke Detector Basement By Restroom B11 51496355 16-21429 04/22-P Smoke Detector Basement Patriot Store Storage

Room 96544904 16-19238 04/22-P

The above device replaced ScanID 51496339:

Smoke Detector Basement Patriot Store Storage Room

51496339 16-19238 04/22-R

Smoke Detector Basement Patriot Store Storage Room

96544895 16-9 50 04/22-P

The above device replaced ScanID 3935396491:

Smoke Detector Basement Patriot Store Storage Room

3935396491 16-9 50 04/22-R

Smoke Detector Basement Patriot Store 60240044 16-9 51 04/22-P Smoke Detector Basement Rm B16 Pharmacy 51496333 16-9 306 04/22-P Smoke Detector Basement Rm B16 Pharmacy 51496332 16-9-305 04/22-P Smoke Detector Basement Rm B16 Pharmacy 51496330 16-9 307 04/22-P Smoke Detector Basement By elevator/By ATM 51496307 16-9 283 03/25-P 04/22-P Smoke Detector Basement By room B14 51496311 16-9 251 03/25-P Smoke Detector Basement By elevator/By room

B14F 60240052 16-9 259 05/10-P 03/25-P

Smoke Detector Basement By elevator/By room B14F

51496306 16-9 282 03/25-P

Smoke Detector Basement In corridor to Bldg 2 /by ATM

51496309 16-9 281 03/25-P

Smoke Detector Basement By Service Elevator 51496312 16-9-280 05/10-P 03/25-P Smoke Detector Basement By Rm B15B 51496316 16-9 277 03/25-P Smoke Detector Basement Rm B14E

Telecommunications 51496300 16-9 310 03/25-P

Smoke Detector 1st By Service Elevator 51496451 16-9-266 05/10-P 04/22-P Smoke Detector 1st Primary Care Firm B Waiting

Area by Desk 51496462 16-9-286 04/22-P

Smoke Detector 1st Main Entrance Hallway to Admissions

51496452 16-9-268 04/22-P

Smoke Detector 1st By Rm 1238 51496455 16-9-286 04/22-P Smoke Detector 1st Lunch/ urgent care staff rm

51496457 16-9-286 04/22-P

Smoke Detector 1st Main Entrance Hallway to 3943452073 16-9 284 04/22-P

Page of 13 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Admissions

Smoke Detector 1st By room 1206 51496468 16-9-255 04/22-P Smoke Detector 1st By room 1201 51496467 16-9-256 04/22-P Smoke Detector 1st By room 1213 51496466 16-9-253 04/22-P Smoke Detector 1st By room 1216 51496465 16-9-254 04/22-P Smoke Detector 1st Primary Care Firm B Waiting

Area 51496463 16-9-257 04/22-P

Smoke Detector 1st By Rm 1193 51496461 16-9-260 04/22-P Smoke Detector 1st By room 1189 51496460 16-9-263 04/22-P Smoke Detector 1st In room 1191 32823114 16-9-309 04/22-P Smoke Detector 1st Urgent Care by Rm 1183 51496387 16-9-264 04/22-P Smoke Detector 1st Elevator Lobby 51496389 1-16090031 05/10-P 04/22-P Smoke Detector 1st Data Rm by Service Elevator 51496362 16-9-267 05/10-P 04/22-P Smoke Detector 1st Main Entrance 51496454 16-9-270 04/22-P Smoke Detector 1st By Rm 1156 51496392 16-9-291 04/22-P Smoke Detector 1st By Rm 1156 door 51496470 16-9-289 04/22-P Smoke Detector 1st By room 1153 51496471 16-9-288 04/22-P Smoke Detector 1st By Rm 1142 51496474 16-9-290 04/22-P Smoke Detector 1st By Rm 1135 51496473 16-9-292 04/22-P Smoke Detector 1st By Primary Care Firm A

Check In 51496475 16-9-293 04/22-P

Smoke Detector 1st Waiting Rm/By Primary Care Firm A Check In

51496476 16-9-294 04/22-P

Smoke Detector 1st Outside Stair 1 51496477 16-9-256 04/22-P Smoke Detector 1st By room 1121 51496478 16-9-297 04/22-P Smoke Detector 1st By room 1118 51496480 16-9-296 04/22-P Smoke Detector 1st Elevator Lobby 32820243 16-9-265 05/10-P 03/25-P Smoke Detector 2nd Rm 223 reception 51496499 16-45563 04/22-P Smoke Detector 2nd By room 249 51496490 16-25082 04/22-P Smoke Detector 2nd By Restroom 239 51496482 16-12663 04/22-P Smoke Detector 2nd By Rm 204B 51496494 16-13759 04/22-P Smoke Detector 2nd By room 243 51496491 16-25082 04/22-P Smoke Detector 2nd By room 237 51496489 16-23621 04/22-P Smoke Detector 2nd By Restroom 252 51496488 16-23255 04/22-P Smoke Detector 2nd By Service Elevator 51496483 16-12298 05/10-P 04/22-P Smoke Detector 2nd By Rm 236 51496487 16-23986 04/22-P Smoke Detector 2nd By Restroom 254 51496486 16-24351 04/22-P Smoke Detector 2nd By Rm 255A 51496485 16-22525 04/22-P Smoke Detector 2nd Data Room by Service

Elevator 51496412 16-11933 05/10-P 04/22-P

Smoke Detector 2nd By Rm 215 51496500 16-45562 03/25-P

Page of 14 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Smoke Detector 2nd By Rm 218 51496501 16-45561 03/25-P Smoke Detector 2nd By Rm 209 51496502 16-45560 03/25-P Smoke Detector 2nd By Rm 208G 51496498 16-45558 03/25-P Smoke Detector 2nd Waiting Area By Rm 208 51496497 16-45564 03/25-P Smoke Detector 2nd By Rm 207 51496496 16-45557 03/25-P Smoke Detector 2nd By Rm 226 51496495 16-45565 03/25-P Smoke Detector 2nd By Rm 202B 51496493 16-13028 03/25-P Smoke Detector 2nd By Rm 203 51496492 16-13394 03/25-P Smoke Detector 2nd Elevator Lobby 51496481 1-16090031 05/10-P 03/25-P Smoke Detector 2nd By Rm 256 51496484 16-45556 03/25-P Smoke Detector 3rd By Restroom 339 51496534 16-18142 04/22-P Smoke Detector 3rd Rm 302K 51496529 16-14489 04/22-P Smoke Detector 3rd By Restroom 332 51496537 16-17777 04/22-P Smoke Detector 3rd By Rm 323 51496540 16-16681 04/22-P Smoke Detector 3rd By Rm 323 51496533 16-17411 04/22-P Smoke Detector 3rd By Rm 324 59133982 16-17046 04/22-P Smoke Detector 3rd Rm 327 51496640 16-16316 04/22-P Smoke Detector 3rd By Rm 312 51496599 16-45555 04/22-P Smoke Detector 3rd By Rm 319A 51496532 16-15950 04/22-P Smoke Detector 3rd By Rm 306A 51496531 16-15585 04/22-P Smoke Detector 3rd By Rm 311 51496530 16-15220 04/22-P Smoke Detector 3rd Rm 302F 51496597 16-45552 04/22-P Smoke Detector 3rd Rm 302F 51496598 16-45553 04/22-P Smoke Detector 3rd Data Rm by Freight Elevator 51496507 16-45551 05/10-P 04/22-P Smoke Detector 3rd Outside Room 342 hallway 59133995 16-18142 03/25-P Smoke Detector 3rd Elevator Lobby Elevator

Recall 51496521 1 05/10-P 03/25-P

Smoke Detector 3rd Rm 302K 51496522 16-14855 03/25-P Smoke Detector 3rd Freight Elevator 51496527 16-45554 05/10-P 03/25-P Smoke Detector 4th By Rm 417 51496643 16-5-147 04/22-P Smoke Detector 4th By Freight Elevator 51496588 16-45441 05/10-P 04/22-P Smoke Detector 4th Elevator freight 51496545 16-50003 05/10-P 04/22-P Smoke Detector 4th Elevator Equipment Rm 51496544 1-16005003 05/10-P 04/22-P Smoke Detector 4th By Rm 453 51496608 16-13271 04/22-P Smoke Detector 4th By Rm 479 51496590 16-45438 04/22-P Smoke Detector 4th By Rm 420 51496589 16-45439 04/22-P Smoke Detector 4th By Rm 415 51496592 16-45437 04/22-P Smoke Detector 4th By Rm 423 Nourishment

Station 51496587 16-45442 05/10-P 03/25-P

Smoke Detector 4th By Elevator Lobby 51496541 16-45436 05/10-P 03/25-P

Page of 15 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Smoke Detector Penthouse Elevator Equipment

Rm 51496573 1-16050020 05/10-P 03/25-P

Smoke Detector Penthouse Elevator Equipment Rm

51496569 1-16050019 05/10-P 03/25-P

Smoke Detector Penthouse Elevator Equipment Rm

51496567 1-16050017 05/10-P 03/25-P

Smoke Detector Penthouse Elevator Equipment Rm

51496566 1-16050018 05/10-P 03/25-P

Smoke Detector Penthouse Elevator Equipment Rm

51496563 1-16050002 05/10-P 03/25-P

Smoke Detector Penthouse Elevator Equipment Rm

51496549 1-16050001 05/10-P 03/25-P

Device Total: 101 Return to Executive Summary

Page of 16 42

Download Date: 06/03/2026

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Horn/Strobe 1 1 0 2 2

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Horn/Strobe 1st inside Bathroom rm 1147 51496396 1 04/22-P Horn/Strobe Penthouse Elevator Equipment

Rm Roof Exit 51496557 1 03/25-P

Device Total: 2 Return to Executive Summary

Page of 17 42

Download Date: 06/03/2026

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Releasing Device 11 11 0 18 18

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Releasing Device Basement Rm B16 Pharmacy

Back Office 51496338 1 04/22-P

Releasing Device Basement Rm B16A Pharmacy 51496337 1 04/22-P Releasing Device Basement Doors by Rm B12

Nutrition 18142156 1 03/25-P

Releasing Device Basement Doors by Elevator Lobby/ATM

18142160 1 03/25-P

Releasing Device Basement Doors by Elevator Lobby/ATM

18142161 1 03/25-P

Releasing Device Basement Near patriot store hallway

18142173 16 03/25-P

Releasing Device Basement Near patriot store hallway

18142174 16 03/25-P

Releasing Device 1st By room 1154 18142139 1 04/22-P Releasing Device 1st By room 1156 18142138 1 04/22-P Releasing Device 1st By room 1216 51496578 1 04/22-P Releasing Device 1st By room 1189 18142149 1 04/22-P Releasing Device 1st By room 1188 18142148 1 04/22-P Releasing Device 2nd By room 204 18142115 1 03/25-P Releasing Device 2nd By room 226 18142114 1 03/25-P Releasing Device 3rd Doors by Rm 306A 18142071 1 04/22-P Releasing Device 3rd Doors by Rm 312 18142070 1 04/22-P Releasing Device 4th Doors By Rm 420 51496641 1 04/22-P Releasing Device 4th Doors By Rm 420 51496642 1 04/22-P

Device Total: 18 Return to Executive Summary

Page of 18 42

Download Date: 06/03/2026

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Speaker/Strobe 80 80 0 116 116

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Speaker/Strobe Basement By elevator/By ATM 51496310 1 04/22-P Speaker/Strobe Basement In room B28 51496319 1 04/22-P Speaker/Strobe Basement Exit in kitchen by room B19D 60240045 1 04/22-P

Speaker/Strobe Basement In room B27 51496322 1 04/22-P Speaker/Strobe Basement Exit in kitchen by room B19D 60240031 1 04/22-P

Speaker/Strobe Basement In room B19A Canteen

60240047 1 03/25-P 04/22-P

Speaker/Strobe Basement Patriot Store Storage Room

51496342 1 04/22-P

Speaker/Strobe Basement Rm B16D Prescription Pickup

51496344 1 04/22-P

Speaker/Strobe Basement Patriot Store 60240034 1 03/25-P 04/22-P Speaker/Strobe Basement Rm B16 Pharmacy 51496336 1 04/22-P Speaker/Strobe Basement Rm B16 Pharmacy

Cage 51496335 1 04/22-P

Speaker/Strobe Basement Rm B16 Pharmacy 51496334 1 04/22-P Speaker/Strobe Basement In room B25 51496325 1 03/25-P 04/22-P Speaker/Strobe Basement By room B3B 60240050 1 03/25-P 04/22-P Speaker/Strobe Basement By elevator/By room

B14E 60240051 1 03/25-P 04/22-P

Speaker/Strobe Basement In room B19A Canteen

18142168 1 03/25-P

Speaker/Strobe Basement Rm B13C Clothing Rm

51496583 1 03/25-P

Speaker/Strobe Basement By room B12F/Stair 4 51496357 1 03/25-P Speaker/Strobe Basement In room B08 51496352 1 03/25-P Speaker/Strobe Basement By room B07 51496351 1 03/25-P Speaker/Strobe Basement By Restroom B11 51496353 1 03/25-P Speaker/Strobe Basement By elevator/By room

B15A pharmacy 60240049 1 03/25-P

Speaker/Strobe Basement By Stair 2 51496314 1 03/25-P Speaker/Strobe Basement Exit by Rm B29 51496317 1 03/25-P Speaker/Strobe Basement By Rm B24 51496324 1 03/25-P Speaker/Strobe Basement In room

B19AGCanteen Dishwasher 60240046 1 03/25-P

Page of 19 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 room

Speaker/Strobe Basement In room B19A Canteen/By rear exit

60240030 1 03/25-P

Speaker/Strobe Basement In room B19A Canteen

60242566 1 03/25-P

Speaker/Strobe Basement In room B19A Canteen

60240027 1 03/25-P

Speaker/Strobe Basement By Rm B18 Patriot Store

51496323 1 03/25-P

Speaker/Strobe 1st Rm 1217 51496577 1 04/22-P Speaker/Strobe 1st Rm 1134 51496394 1 04/22-P Speaker/Strobe 1st Primary Care Firm A by Rm

51496393 1 04/22-P

Speaker/Strobe 1st By Rm 1238 51496372 1 04/22-P Speaker/Strobe 1st In room 1229 51496373 1 04/22-P Speaker/Strobe 1st By Stair 5 51496382 1 04/22-P Speaker/Strobe 1st By room 1210 51496381 1 04/22-P Speaker/Strobe 1st Main Entrance by Doors 51496368 1 04/22-P Speaker/Strobe 1st By room 1216 51496377 1 04/22-P Speaker/Strobe 1st By Rm 1193 51496375 1 04/22-P Speaker/Strobe 1st By room 1186 51496384 1 04/22-P Speaker/Strobe 1st By room 1178 51496388 1 04/22-P Speaker/Strobe 1st By Rm 1170 51496360 1 04/22-P Speaker/Strobe 1st By Rm 1159 51496364 1 04/22-P Speaker/Strobe 1st Area 1241 51496369 1 04/22-P Speaker/Strobe 1st Main Entrance by Help Desk 51496366 1 04/22-P Speaker/Strobe 1st Primary Care Firm A by Rm

51496390 1 04/22-P

Speaker/Strobe 1st Rm 1140 51496398 1 04/22-P Speaker/Strobe 1st By room 1110 51496402 1 04/22-P Speaker/Strobe 1st By Stair 1 51496405 1 04/22-P Speaker/Strobe 1st By Room 1126 51496404 1 04/22-P Speaker/Strobe 1st Primary Care Firm A by Rm

51496406 1 04/22-P

Speaker/Strobe 2nd By room 222B 51496445 1 04/22-P Speaker/Strobe 2nd In room 237 51496430 1 04/22-P Speaker/Strobe 2nd In room 254 51496420 1 04/22-P Speaker/Strobe 2nd Rm 227 51496413 1 04/22-P Speaker/Strobe 2nd By room 245 51496434 1 04/22-P Speaker/Strobe 2nd By room 239 51496432 1 04/22-P Speaker/Strobe 2nd In room 236 51496427 1 04/22-P

Page of 20 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Speaker/Strobe 2nd By room 272 51496424 1 04/22-P Speaker/Strobe 2nd By room 235 51496422 1 04/22-P Speaker/Strobe 2nd By room 233 51496419 1 04/22-P Speaker/Strobe 2nd By room 231a 51496418 1 04/22-P Speaker/Strobe 2nd By room 220 51496446 1 03/25-P 04/22-P Speaker/Strobe 2nd By room 204a 51496437 1 03/25-P 04/22-P Speaker/Strobe 2nd By room 214 51496449 1 03/25-P Speaker/Strobe 2nd By room 208C 51496443 1 03/25-P Speaker/Strobe 2nd By room 226 51496439 1 03/25-P Speaker/Strobe 2nd By room 265 51496436 1 03/25-P Speaker/Strobe 2nd By room 203 51496435 1 03/25-P Speaker/Strobe 2nd By Rm 262 51496408 1 03/25-P Speaker/Strobe 2nd Rm 256 51496417 1 03/25-P Speaker/Strobe 3rd By Rm 322A 51496515 1 04/22-P Speaker/Strobe 3rd Inside room 311 conference 59133989 1 04/22-P Speaker/Strobe 3rd At Elevator lobby 59133992 1-16090017 04/22-P Speaker/Strobe 3rd Room 357 59134002 1 04/22-P Speaker/Strobe 3rd Rm 340 65575362 1 04/22-P Speaker/Strobe 3rd By Rm 323 59134003 1 04/22-P Speaker/Strobe 3rd By Rm 339 51496535 1 04/22-P Speaker/Strobe 3rd By Rm 335 65575367 1 04/22-P Speaker/Strobe 3rd By Rm 324 51496514 1 04/22-P Speaker/Strobe 3rd Rm 327 51496639 1 04/22-P Speaker/Strobe 3rd By Rm 319 51496511 1 04/22-P Speaker/Strobe 3rd By 3011 51496510 1 04/22-P Speaker/Strobe 3rd By Stair 2 51496509 1 03/25-P 04/22-P Speaker/Strobe 3rd By Rm 302H 51496526 1 04/22-P Speaker/Strobe 3rd By Rm 302F 51496525 1 04/22-P Speaker/Strobe 3rd By Rm 302C 51496524 1 04/22-P Speaker/Strobe 3rd Outside Room 353 59133990 1 03/25-P Speaker/Strobe 3rd Outside Room 371 hallway 59133999 1 03/25-P Speaker/Strobe 3rd Near Room 380 hallway 59134001 1 03/25-P Speaker/Strobe 3rd Inside Bathroom rm 368 59133983 1 03/25-P Speaker/Strobe 3rd Outside Room 372 hallway 59133988 1 03/25-P Speaker/Strobe 3rd Outside Room 358 hallway 59133987 1 03/25-P Speaker/Strobe 3rd Outside Room 346 hallway 59134005 1 03/25-P Speaker/Strobe 4th By Rm 424 Quiet Rm 32820254 1 03/25-P 04/22-P Speaker/Strobe 4th By Rm 440 32820245 1 04/22-P Speaker/Strobe 4th By Rm 405 78-I 32820263 1 03/25-P 04/22-P Speaker/Strobe 4th By Rm 480 Nurse Station 32820271 1 04/22-P

Page of 21 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Speaker/Strobe 4th By Stair by Rm 465 32820256 1 04/22-P Speaker/Strobe 4th By Rm 457 32820257 1 04/22-P Speaker/Strobe 4th By Rm 470 32820258 1 04/22-P Speaker/Strobe 4th By Rm 478 32820266 1 04/22-P Speaker/Strobe 4th inside Rm 420 59133985 1 04/22-P Speaker/Strobe 4th inside Rm 420 32820279 1 04/22-P Speaker/Strobe 4th By Rm 420 32820276 1 04/22-P Speaker/Strobe 4th By Rm 422 Inventory 32820277 1 04/22-P Speaker/Strobe 4th By Rm 415 32820284 1 04/22-P Speaker/Strobe 4th At Elevator 32820235 1 03/25-P 04/22-P Speaker/Strobe 4th By Rm 439 32820246 1 03/25-P Speaker/Strobe 4th By Rm 447 32820250 1 03/25-P Speaker/Strobe 4th By Rm 433 32820252 1 03/25-P Speaker/Strobe 4th By Rm 429 Nurse Station 32820251 1 03/25-P Speaker/Strobe 4th By Rm 452 Laundry 32820253 1 03/25-P Speaker/Strobe 4th By Rm 404 32820237 1 03/25-P Speaker/Strobe 4th By Rm 409 32820236 1 03/25-P

Device Total: 116 Return to Executive Summary

Page of 22 42

Download Date: 06/03/2026

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Strobe 69 69 0 82 82

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Strobe Basement Rm B26 51496327 1 04/22-P Strobe Basement In room B13F restroom 51496348 1 04/22-P

Strobe Basement In room B06 51496350 1 04/22-P Strobe Basement In restroom B33 51496315 1 04/22-P Strobe Basement In room B03D 60240091 1 04/22-P Strobe Basement in police station 60240054 16-9 04/22-P Strobe Basement In restroom B21 60240053 1 04/22-P Strobe Basement By room B15F 60240025 1 04/22-P Strobe Basement Outside Patriot Store in corr 60240092 1 04/22-P

Strobe Basement Patriot Store Storage Room

51496340 1 04/22-P

Strobe Basement Patriot Store Storage Room

96544977 1 04/22-P

Strobe Basement Front Patriot Store 60240033 1 04/22-P Strobe Basement In room B11 51496354 1 03/25-P Strobe Basement Rm B12 Nutrition 51496356 1 03/25-P Strobe Basement Patriot Store Storage

Room 51496341 1 04/22

Removed Strobe 1st In room 1186 51496385 1 04/22-P Strobe 1st By Rm 1237 51496365 1 04/22-P Strobe 1st Rm 1240 51496459 1 04/22-P Strobe 1st Restroom 1196 51496469 1 04/22-P Strobe 1st Restroom 1216 51496379 1 04/22-P Strobe 1st In waiting room/By room

51496464 1 04/22-P

Strobe 1st By Rm 1191 51496374 1 04/22-P Strobe 1st By Rm 1188 51496383 1 04/22-P Strobe 1st In room 1187 51496386 1 04/22-P Strobe 1st Elevator Lobby 51496359 1 04/22-P Strobe 1st By Service Elevator 51496363 1 04/22-P Strobe 1st Main Entrance Entryway 51496370 1 04/22-P Strobe 1st Restroom 1103 51496456 1 04/22-P Strobe 1st In room 1156 51496391 1 04/22-P Strobe 1st By Rm 1154 51496401 1 04/22-P

Page of 23 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Strobe 1st Rm 1138 51496397 1 04/22-P Strobe 1st Primary Care Firm A by

Check-in Desk 51496395 1 04/22-P

Strobe 1st By room 1126 51496479 1 04/22-P Strobe 2nd In room 236a 60240133 1 04/22-P Strobe 2nd In room 223B 60240093 1 04/22-P Strobe 2nd In room 220 51496447 1 04/22-P Strobe 2nd By room 222E 51496444 1 04/22-P Strobe 2nd By room 208 51496442 1 04/22-P Strobe 2nd In room 224 51496441 1 04/22-P Strobe 2nd Room 227D 51496438 1 04/22-P Strobe 2nd In room 252 51496425 1 04/22-P Strobe 2nd In room 254 51496421 1 04/22-P Strobe 2nd Rm 231 51496415 1 04/22-P Strobe 2nd Rm 227B 51496414 1 04/22-P Strobe 2nd Staff Restroom 259 51496410 1 04/22-P Strobe 2nd In room 239 51496433 1 04/22-P Strobe 2nd In room 236 51496428 1 04/22-P Strobe 2nd By room 237 51496426 1 04/22-P Strobe 2nd By room 253 51496423 1 04/22-P Strobe 2nd By Service Elevator 51496411 1 03/25-P 04/22-P Strobe 2nd In room 219 51496448 1 03/25-P Strobe 2nd rest room in 265 51496581 1 03/25-P Strobe 2nd Restroom 229 51496409 1 03/25-P Strobe 3rd Restroom 332 51496536 1 04/22-P Strobe 3rd Restroom 320B 51496519 1 04/22-P Strobe 3rd rm320 nurses station 51496517 1 04/22-P Strobe 3rd Inside Room 357 break room 59133996 1 04/22-P Strobe 3rd Inside Bathroom rm 303 59133997 1 04/22-P Strobe 3rd Inside Bathroom 380 59134000 1 04/22-P Strobe 3rd Restroom 340F 65575363 1 04/22-P Strobe 3rd Restroom 340E 65575406 1 04/22-P Strobe 3rd Inside Bathroom room 305 59133994 16 03/25-P 04/22-P Strobe 3rd Restroom 328 51496516 1 04/22-P Strobe 3rd By Rm 323 51496513 1 04/22-P Strobe 3rd By Rm 319A 51496512 1 04/22-P Strobe 3rd Rm 302F 59133993 16-45553 04/22-P Strobe 3rd By Service Elevator 51496528 1 04/22-P Strobe 3rd Rm 302K 51496523 1 03/25-P 04/22-P Strobe 3rd Inside Mens bathrm 361 65575368 16-23986 03/25-P

Page of 24 42

Download Date: 06/03/2026

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Strobe 3rd At waiting area 59134004 1 03/25-P Strobe 3rd At waiting area 59133998 1-16090017 03/25-P Strobe 4th Visitor Room 417 32820283 1 04/22-P Strobe 4th Rm 415 32820280 1 04/22-P Strobe 4th Rm 478 51496607 1 04/22-P Strobe 4th Rm 475 51496611 1 04/22-P Strobe 4th At Quite Room 468 65575369 16 04/22-P Strobe 4th At Room 445H 65575370 16 04/22-P Strobe 4th Rm 479 32820270 1 04/22-P Strobe 4th Room 451 65575371 1 03/25-P Strobe 4th Restroom 410 51496543 1 03/25-P Strobe 4th Restroom 411 51496520 1 03/25-P Strobe Penthouse Elevator Equipment

Rm 51496547 1 03/25-P

Strobe Penthouse Elevator Equipment Rm Entrance

51496546 1 03/25-P

Device Total: 82 Return to Executive Summary

Page of 25 42

Download Date: 06/03/2026

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Duct Detector 9 9 0 12 12

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Duct Detector Basement Rm B26 51496328 16-9-278 04/22-P Duct Detector Basement By B16 Pharmacy 51496329 16-9 273 04/22-P Duct Detector Basement Rm B13C Clothing

Room AHU Rm B13 51496582 1-9-261 03/25-P

Duct Detector 1st Main Entrance 51496453 16-9-301 04/22-P Duct Detector 4th By Rm 443 51496585 16-5-39 04/22-P Duct Detector 4th By Rm 436 Electrical Closet 51496584 16-5 37 04/22-P Duct Detector 4th Rm 480 Nurse Station 59134006 16-5 38 04/22-P Duct Detector 4th By Rm 456 51496610 16-5-32 04/22-P Duct Detector 4th By Rm 476 51496609 16-5-35 04/22-P Duct Detector 4th By Family Room 416 51496591 16-5 31 04/22-P Duct Detector Penthouse Elevator Equipment

Rm 51496548 16-45416 05/10-P 03/25-P

Duct Detector Penthouse Elevator Equipment Rm HV-1

32820242 16-45435 03/25-P

Device Total: 12 Return to Executive Summary

Page of 26 42

Download Date: 06/03/2026

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Control Panel 1 1 0 1 1

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Control Panel Basement Rm B14E

Telecommunications/Fire Alarm 51496606 1 03/25-P 04/22-P

Device Total: 1 Return to Executive Summary

Page of 27 42

Download Date: 06/03/2026

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Annunciator 2 2 0 2 2

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Annunciator Basement In corridor to Bldg 2

/Exit by vending machines 60240048 1 03/25-P 04/22-P

Annunciator 1st Main Entrance Entryway 51496371 1 04/22-P

Device Total: 2 Return to Executive Summary

Page of 28 42

Download Date: 06/03/2026

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Battery 9 3 6 15 15

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Battery Basement At Telephone left of

FACP FACR

65575423 16-9 03/25-P

Battery Basement At Telephone left of

FACP FACR

65575424 16-9 03/25-P

Battery Basement Rm B14E Telecommunications/Fire Alarm

51496302 1 03/25-P

Battery Basement Rm B14E Telecommunications/Fire Alarm

51496301 1 03/25-P

Battery Basement Inside Room B14E main

51496305 2 03/25-P

Battery Basement Inside Room B14E main

51496304 2 03/25-P

Battery Basement At Electrical closet B16C

65575427 16-9 04/22-F

Battery Basement At Electrical closet B16C

65575426 16-9 04/22-F

Battery 1st Rm 1228 electrical closet Y401522 1 04/22-F Battery 1st Rm 1228 electrical closet 65575364 1 04/22-F Battery 2nd Electrical closet 227C 84464405 16-9 04/22-P Battery 2nd Electrical closet 227C 84464403 16-9 04/22-P Battery 3rd Electrical closet 358 84464402 16-9 04/22-F Battery 3rd Electrical closet 358 84464401 16-9 04/22-F Battery 4th Electrical Closet Booster 31149274 16-9 03/25-P 04/22-P

Device Total: 15 Return to Executive Summary

Page of 29 42

Download Date: 06/03/2026

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

At a minimum, control equipment shall be tested to verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity Expander Panel 5 5 0 6 6

Device Type Location ScanID Address Q2/25 Q1/26 Q2/26 Expander Panel Basement At Electrical closet

B16C 65575425 16-9 04/22-P

Expander Panel Basement At Telephone left of

FACP FACR

65575422 16-9 03/25-P

Expander Panel 1st Rm 1228 electrical closet 65575365 1 04/22-P Expander Panel 2nd Electrical Closet 227C 84464400 16-9 04/22-P Expander Panel 3rd Electrical Closet 358 84464399 16-9 04/22-P Expander Panel 4th 413 Electrical Closet 31149275 16-9 03/25-P 04/22-P

Device Total: 6 Return to Executive Summary

Page of 30 42 Service Summary

Download Date: 06/03/2026

Service Summary Generated by: BuildingReports.com

Building: Bedford VAMC BLDG 78 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Failed/Other Battery Visually Checked 6

Total 6

Passed Annunciator Tested 2 Battery Tested 6 Battery Visually Checked 3 Control Panel Tested 1 Duct Detector Tested 12 Expander Panel Tested 6 Heat Detector Tested 17 Horn/Strobe Tested 2 Pull Station Tested 39 Releasing Device Tested 18 Smoke Detector Tested 63 Smoke Detector Tested/Cleaned 32 Smoke Detector Visually Checked 6 Speaker/Strobe Tested 116 Strobe Tested 82

Total 405 Grand Total 411

Page of 31 42 Auxiliary Functions Testing

Download Date: 06/03/2026

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Bedford VAMC BLDG 78 Control Panel: 1 - EST EST3 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Releasing Device

Door Holder Basement Doors by Elevator Lobby/ATM Passed 18142161 Door Holder Basement Doors by Elevator Lobby/ATM Passed 18142160 Door Holder Basement Doors by Rm B12 Nutrition Passed 18142156 Door Holder Basement Rm B16 Pharmacy Back Office Passed 51496338 Door Holder Basement Rm B16A Pharmacy Passed 51496337 Door Holder 1st By room 1154 Passed 18142139 Door Holder 1st By room 1156 Passed 18142138 Door Holder 1st By room 1188 Passed 18142148 Door Holder 1st By room 1189 Passed 18142149 Door Holder 1st By room 1216 Passed 51496578 Door Holder 2nd By room 204 Passed 18142115 Door Holder 2nd By room 226 Passed 18142114 Door Holder 3rd Doors by Rm 306A Passed 18142071 Door Holder 3rd Doors by Rm 312 Passed 18142070 Door Holder 4th Doors By Rm 420 Passed 51496642 Door Holder 4th Doors By Rm 420 Passed 51496641

Duct Detector AHU Shutdown Basement Rm B13C Clothing Room AHU Rm

B13 Passed 51496582

Building: Bedford VAMC BLDG 78 Control Panel: 16 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Releasing Device

Door Holder Basement Near patriot store hallway Passed 18142174 Basement Near patriot store hallway Passed 18142173 javascript:editViewDevice('18142161');

javascript:editViewDevice('18142160');

javascript:editViewDevice('18142156');

javascript:editViewDevice('51496338');

javascript:editViewDevice('51496337');

javascript:editViewDevice('18142139');

javascript:editViewDevice('18142138');

javascript:editViewDevice('18142148');

javascript:editViewDevice('18142149');

javascript:editViewDevice('51496578');

javascript:editViewDevice('18142115');

javascript:editViewDevice('18142114');

javascript:editViewDevice('18142071');

javascript:editViewDevice('18142070');

javascript:editViewDevice('51496642');

javascript:editViewDevice('51496641');

javascript:editViewDevice('51496582');

javascript:editViewDevice('18142174');

javascript:editViewDevice('18142173');

Page of 32 42 Auxiliary Functions Testing

Download Date: 06/03/2026

Building: Bedford VAMC BLDG 78 Control Panel: 16 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Smoke Detector

Elevator Recall Basement By Service Elevator Passed 51496312

Duct Detector AHU Shutdown Basement By B16 Pharmacy Passed 51496329 AHU Shutdown Basement Rm B26 Passed 51496328 AHU Shutdown 1st Main Entrance Passed 51496453 AHU Shutdown 4th By Family Room 416 Passed 51496591 AHU Shutdown 4th By Rm 436 Electrical Closet Passed 51496584 AHU Shutdown 4th By Rm 443 Passed 51496585 AHU Shutdown 4th By Rm 456 Passed 51496610 AHU Shutdown 4th By Rm 476 Passed 51496609 AHU Shutdown 4th Rm 480 Nurse Station Passed 59134006 AHU Shutdown Penthouse Elevator Equipment Rm HV-1 Passed 32820242 javascript:editViewDevice('51496312');

javascript:editViewDevice('51496329');

javascript:editViewDevice('51496328');

javascript:editViewDevice('51496453');

javascript:editViewDevice('51496591');

javascript:editViewDevice('51496584');

javascript:editViewDevice('51496585');

javascript:editViewDevice('51496610');

javascript:editViewDevice('51496609');

javascript:editViewDevice('59134006');

javascript:editViewDevice('32820242');

Page of 33 42 Battery & Power Supply Testing

Download Date: 06/03/2026

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Bedford VAMC BLDG 78 Control Panel: 1 - EST EST3 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid Basement Rm B14E

Telecommunications/Fire Alarm

8 12

Sealed Lead Acid Basement Rm B14E Telecommunications/Fire Alarm

8 12

Failed/Other Sealed Lead Acid 1st Rm 1228 electrical closet 7 12 Sealed Lead Acid 1st Rm 1228 electrical closet 7 12

Building: Bedford VAMC BLDG 78 Control Panel: 2 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid Basement Inside Room B14E main 55 12

Sealed Lead Acid Basement Inside Room B14E main

55 12

Building: Bedford VAMC BLDG 78 Control Panel: 16 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid Basement At Telephone left of

FACP FACR

18 12

Sealed Lead Acid Basement At Telephone left of

FACP FACR

18 12

Page of 34 42 Battery & Power Supply Testing

Download Date: 06/03/2026

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Sealed Lead Acid 2nd Electrical closet 227C 7 12 Sealed Lead Acid 2nd Electrical closet 227C 7 12 Sealed Lead Acid 4th Electrical Closet Booster 7 12

Failed/Other Sealed Lead Acid Basement At Electrical closet

B16C 7 12

Sealed Lead Acid Basement At Electrical closet B16C

7 12

Sealed Lead Acid 3rd Electrical closet 358 7 12 Sealed Lead Acid 3rd Electrical closet 358 7 12

Page of 35 42 Inventory & Warranty Report

Download Date: 06/03/2026

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Bedford VAMC BLDG 78 Control Panel: 1 - EST EST3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Annunciator Control 0.49% 2

Battery Control 3.65% 15

Control Panel Control 0.24% 1

Duct Detector…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .