Bangor - Struct.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24124Q0806
About this file
This is a set of structural engineering drawings and specifications for the VA Outpatient Clinic located at 35 State Hospital Drive in Bangor, ME. The drawings detail the structural design requirements for the facility, including foundation plans, framing plans, and structural details.
The documents include comprehensive specifications for materials and construction, including concrete requirements (3500-4000 PSI compressive strength), structural steel (ASTM A992 Grade 50 for wide flange shapes), and cold-formed metal framing. The building is designed according to IBC 2006 standards with specific load requirements: floor live load of 100 PSF for mechanical penthouse, design roof snow load of 58.8 PSF, basic wind speed of 90 MPH, and seismic design category C. Key structural elements include steel joists, metal deck, concrete slabs, spread footings, and HSS steel columns. The drawings provide detailed foundation plans showing column locations and sizes, framing plans for low roof and penthouse levels, and extensive structural connection details. The project was designed by Structural Dimension Inc. and Welman Architects Inc., with drawings dated March-May 2010.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bangor Dental XRay pre-bid sign in sheet.pdf | ||
| 36C24124Q0806_2.docx | DOCX document | |
| Bangor 3D Shielding Plan.pdf | ||
| Bangor - Elec.zip | ZIP file | |
| Drawing.pdf | ||
| Bangor - Arch.pdf | ||
| SOW - Bangor Imaging and Dental Xray Prep.pdf | ||
| 36C24124Q0806.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIBER REINFORCEMENT:
MACROSYNTHETIC FIBERS ENGINEERED
& DESIGNED FOR USE IN CONCRETE SLABS
COMPLYING WITH ASTM C 1116, TYPE III, 1-1/2'' TO 2-1/2'' LONG
REINFORCING STEEL:
ALL-ASTM A 615, GRADE 60, DEFORMED
STEEL WELDED WIRE REINFORCEMENT, FLAT SHEETS
STRUCTURAL STEEL:
ROLLED WIDE FLANGE SHAPES, ASTM A 992 GRADE 50
CHANNELS, ANGLES, & S SHAPES, ASTM A 36 GRADE 50
PLATE & BAR, ASTM A 36 GRADE 50
TUBE SHAPES, ASTM A 500 GRADE B
PIPE, ASTM A 53, TYPE E OR S, GRADE B
ALL OTHER ROLLED SHAPES, ASTM A 36 GRADE 50
COLD-FORMED METAL FRAMING
GAUGE STEEL:
18 GAUGE AND LIGHTER
16 GAUGE AND HEAVIER
ALL TRACK 16 GAUGE
GALVANIZED COATING
STRUCTURAL BOLTS:
HIGH STRENGTH BOLTS, NUTS, & WASHERS, ASTM A 325
ZINC-COATED HIGH STRENGTH BOLTS, NUTS, & WASHERS, ASTM A 325
STAINLESS STEEL BOLTS, NUTS, & WASHERS, ASTM F 593
SHEAR CONNECTORS, ASTM A 108 GRADES 1015 THRU 1020
THREADED RODS, ASTM A 36 GRADE 50
CLEVISES & TURNBUCKLES, ASTM A 108, GRADE 1035
EYE BOLTS & NUTS, ASTM A 108, GRADE 1030
ANCHOR BOLTS, ASTM F 1554, GRADE A 36
WELDED CONNECTIONS:
WELDING ELECTRODES
GROUT BELOW BASE PLATES & BEARING PLATES:
NONMETALLIC, SHRINKAGE-RESISTANT ASTM C 1107
ALLOWABLE SOIL BEARING PRESSURE:
REFER TO SOILS REPORT NO. 08-1181S
DATED NOVEMBER 24, 2009 BY S.W. COLE ENGINEERING INC. FOR
DESCRIPTION OF EXISTING SOIL CONDITIONS
AND RECOMMENDATIONS.
DESIGN:
APPLICABLE CODES/STANDARDS:
-INTERNATIONAL BUILDING CODE - 2006
-INTERNATIONAL EXISTING BUILDING CODE - 2006
-ASCE 7-05 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, ASCE/SEI 2005
STRUCTURAL DESIGN STANDARDS:
-ACI 318-05 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, 2005
-ACI 530/530.1-05 BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY
STRUCTURES (AND RELATED COMMENTARIES), 2005
-AISC-ASD/LRFD (ASD ONLY) STEEL CONSTRUCTION MANUAL, 13TH EDITION
-AISC SEISMIC DESIGN MANUAL
-WS D1.1/D1.1M STRUCTURAL WELDING CODE-SEEL, 2006 EDITION
-NDS-NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION ASD/LRFD (ASD ONLY), 2005
EDITION
-NDS-NATIONAL DESIGN SPECIFICATION SUPPLEMENT, DESIGN VALUES FOR WOOD CONSTRUCTION, 2005 EDITION
BUILDING CLASSIFICATION CATEGORY:
BUILDING DESIGN LIVE LOADS/CRITERIA:
FLOOR LIVE LOADS:
FLOOR FRAMING (MECHANICAL PENTHOUSE)
ROOF SNOW LOADS & DESIGN DATA:
DESIGN ROOF SNOW LOAD
FLAT ROOF SNOW LOAD (Pf)=(0.7*Ce*Ct*Is*Pg) SNOW EXPOSURE FACTOR (Ce) SNOW LOAD IMPORTANCE FACTOR (Is) ROOF THERMAL FACTOR (Ct) GROUND SNOW (Pg)
RAIN ON SNOW SURCHARGE
SLOPED ROOF FACTOR (Cs)
WIND DESIGN DATA:
WIND IMPORTANCE FACTOR (Iw)
BASIC WIND SPEED (3-SECOND GUST)
WIND DIRECTIONALITY FACTOR (Kd)
MEAN ROOF HEIGHT
WIND EXPOSURE CATEGORY
WIND EXPOSURE CLASSIFICATION
INTERNAL PRESSURE COEFFICIENT
BUILDING LENGTH (L)
LEAST WIDTH (B)
VELOCITY PRESSURE EXPOSURE COEFFICIENT Kh (CASE 1) VELOCITY PRESSURE EXPOSURE COEFFICIENT Kh (CASE 2) TOPOGRAPHIC FACTOR Kzt EDGE STRIP (a) END ZONE (2a)
DESIGN PROCEDURE
WIND LOADS - COMPONENTS & CLADDING
ROOF
AREA
NEGATIVE ZONE 1
NEGATIVE ZONE 2
NEGATIVE ZONE 3
POSITIVE ALL ZONES
OVERHANG ZONE 1 & 2
OVERHANG ZONE 3
WALLS
AREA
NEGATIVE ZONE 4
NEGATIVE ZONE 5
POSITIVE ZONE 4 & 5
EARTHQUAKE DESIGN DATA:
OCCUPANCY CATEGORY
SEISMIC IMPORTANCE FACTOR (Ie) MAPPED SPECTRAL ACCELERATIONS AT SHORT PERIODS (Ss) MAPPED SPECTRAL ACCELERATIONS AT (1)-SECOND PERIODS (Sd1)
SITE CLASSIFICATION
DESIGN SPECTRAL RESPONSE COEFFICIENT AT SHORT PERIODS (Sds) DESIGN SPECTRAL RESPONSE COEFFICIENT AT (1)-SECOND PERIODS (Sd1)
SEISMIC DESIGN CATEGORY
BASIC SEISMIC-FORCE-RESISTING SYSTEM
DESIGN BASE SHEAR
SEISMIC RESPONSE COEFFICIENT (Cs)
SEISMIC MODIFICATION FACTOR (R)
ANALYSIS PROCEDURE FOR SEISMIC DESIGN
BUILDING IS IN PENOBSCOT COUNTY
EARTH PRESSURE:
SOIL UNIT WEIGHT
DESIGN LATERAL SOIL LOAD
100 PSF
IV
58.8 PSF
1.0 1.2 1.0
35 PSF
1.0
1.15
90 MPH
0.85
13.5 FT
60 PSF (BALANCED SNOW LOAD)
B
ENCLOSED
+/- 0.18
182 FT
182 FT
0.701 0.575 1.0
7.3 FT
14.6 FT
METHOD 1 (SIMPLIFIED PROCEDURE)
10.0 PSF
-42.3 PSF
-28.1 PSF
-16.8 PSF
10 SF
10.0 PSF
-25.4 PSF
-21.2 PSF
-15.8 PSF
50 SF
10.0 PSF
-18.2 PSF
-18.2 PSF
-15.3 PSF
100 SF
-24.1 PSF -23.1 PSF -22.7 PSF
-39.8 PSF -19.9 PSF -11.4 PSF
SURFACE PRESSURE (PSF)
15.3 PSF
-20.4 PSF
-16.6 PSF
10 SF
13.1 PSF
-15.9 PSF
-14.4 PSF
100 SF
11.5 PSF
-12.8 PSF
-12.8 PSF
500 SF
SURFACE PRESSURE (PSF)
110 PCF
60 PSF/FT OF DEPTH
MATERIAL STRENGTHS:
CAST-IN-PLACE CONCRETE:
FOOTINGS
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
FOUNDATION FROST WALLS
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
EXPOSED WALLS
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
INTERIOR SLABS
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
EXTERIOR SLABS ON GRADE
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
SLABS ON METAL DECK
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
PIERS
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
SLURRY
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
ALL OTHER CONCRETE
MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS
MAXIMUM WATER-CEMENTITIOUS RATIO
MAXIMUM AGGREGATE SIZE
SLUMP LIMIT
AIR CONTENT
0.55 1 1/2'' 5'' +/- 1''
NO
f'c = 3500 PSI
0.55 3/4'' 4'' +/- 1''
NO
f'c = 4000 PSI
0.42 3/4'' 4'' +/- 1''
YES 4 TO 6 %
f'c = 4000 PSI
0.47 3/4'' 4'' +/- 1''
NO
f'c = 3500 PSI
0.42 3/4'' 4'' +/- 1''
YES 4 TO 6 %
f'c = 3500 PSI
0.47 3/8'' 4'' +/- 1''
NO
f'c = 3500 PSI
0.47 3/4'' 4'' +/- 1''
NO
f'c = 4000 PSI
0.55 3/4'' 6'' +/- 1''
NO
f'c = 1000 PSI
0.47 3/4'' 4'' +/- 1''
NO
f'c = 4000 PSI
Fy = 60,000 PSI Fy = 60,000 PSI
Fy = 36,000 PSI Fy = 50,000 PSI
Fy = 36,000 PSI Fy = 46,000 PSI Fy = 46,000 PSI Fy = 36,000 PSI
Fy = 33,000 PSI Fy = 50,000 PSI Fy = 50,000 PSI G90
E70XX
1500 PSF (REPORT)
1.50 0.267 0.076 D 0.282 0.122 C
EQUIVALENT LATERAL
FORCE ANALYSIS
IV
NOT SPECIFICALLY DESIGNED
FOR SEISMIC RESISTANCE
0.141W 0.141
DEFLECTION LIMITS:
ROOF MEMBERS
SUPPORTING GYPSUM BOARD CEILINGS
SUPPORTING GYPSUM BOARD CEILINGS
NOT SUPPORTING CEILING
SUPPORTING RIGID MATERIALS (BRICK, MASONRY, ETC.)
FLOOR MEMBERS
SUPPORTING RIGID MATERIALS (BRICK, MASONRY, ETC.)
SUPPORTING FLEXIBLE MATERIALS
LINTEL/HEADER/BEAM MEMBERS
SUPPORTING RIGID MATERIALS (BRICK, MASONRY, ETC.)
SUPPORTING FLEXIBLE MATERIALS (EIFS, SIDING, ETC.)
EXTERIOR WALLS
WITH RIGID FINISHES (BRICK, MASONRY, ETC.)
WITH FLEXIBLE FINISHES (EIFS, SIDING, ETC.)
L/600 OR 0.3 in L/240 L/240 L/360
LIVE
L/600 OR 0.3 in L/240 L/240 L/360
SNOW OR WIND
L/600 OR 0.3 in L/180 L/240 L/360
DEAD + LIVE OR SNOW
L/360 L/600 OR 0.3 in
L/240 L/600 OR 0.3 in
L/360 L/600 OR 0.3 in
L/240 L/600 OR 0.3 inL/600 OR 0.3 in
L/600 OR 0.3 in
L/360
L/360
GENERAL:
ALL MATERIALS, CONSTRUCTION, AND DETAILS SHALL CONFORM WITH THE FOLLOWING:
PLANS AND SPECIFICATIONS
INTERNATIONAL BUILDING CODE - 2006
OSHA REGULATIONS
THE GENERAL CONTRACTOR AND SUBCONTRACTORS SHALL BE FAMILIAR WITH THE ENTIRE SET
OF CONSTRUCTION DOCUMENT (ARCHITECTURAL, CIVIL, ELECTRICAL, PLUMBING, STRUCTURAL, ETC.) IN ORDER TO PROVIDE ALL CONSTRUCTION AND MATERIALS FOR THIS PROJECT.
THE CONTRACTOR SHALL REFER TO OTHER DRAWINGS CONTAINED IN THE CONSTRUCTION
DOCUMENTS FOR ADDITIONAL SPECIFIED MEMBERS, DIMENSIONS, ELEVATIONS, DETAILS,
OPENINGS, INSERTS, SLEEVES, DEPRESSIONS, ETC. NOT SHOWN ON THE STRUCTURAL DRAWINGS
REQUIRED TO CONSTRUCT THIS PROJECT.
DETAILS SHOWN ON STRUCTURAL DRAWINGS SHALL BE APPLICABLE TO ALL PORTIONS OF THE
CONTRACT DOCUMENTS UNLESS NOTED OTHERWISE.
DIMENSIONS AND ELEVATIONS SHOWN ON ARCHITECTURAL DRAWINGS SUPERSEDE DIMENSIONS
AND ELEVATIONS SHOWN ON STRUCTURAL DRAWINGS.
DO NOT SCALE PLANS.
IN NO CASE SHALL STRUCTURAL ALTERATIONS OR WORK AFFECTING A STRUCTURAL MEMBER BE
MADE UNLESS APPROVED BY THE STRUCTURAL ENGINEER.
IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURE AND
CONSTRUCTION SEQUENCE IN ORDER TO INSURE THE SAFETY OF THE BUILDING AND WORKMEN
DURING CONSTRUCTION (MEANS & METHODS OF CONSTRUCTION). THIS INCLUDES, BUT IS NOT
LIMITED TO: SHORING, UNDERPINNING, TEMPORARY BRACING, ETC.
CONSTRUCTION DOCUMENTS SHOW DIMENSIONS AND ELEVATIONS TO SIGNIFICANT WORKING
POINTS (COLUMN CENTERLINES, OUTSIDE FACE OF WALLS, TOP OF FRAMING MEMBERS, ETC.)
MATERIAL SUPPLIERS AND DESIGNERS ARE RESPONSIBLE FOR ALL OTHER INFORMATION IN ORDER
TO DETAIL/FABRICATE THEIR WORK. CONTACT THE ARCHITECT WITH ANY DISCREPANCIES.
IN THE EVENT OF ANY DISCREPANCIES BETWEEN THE STRUCTURAL DRAWINGS AND ANY OTHER
PLANS CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS, THE CONTRACTOR SHALL BRING THE DISCREPANCY TO THE ARCHITECTS ATTENTION IN WRITING IMMEDIATELY OR SHALL BID THE
MOST EXPENSIVE INSTALLATION SPECIFIED.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
FOUNDATION & EARTHWORK:
ALL EXTERIOR FOOTINGS MUST BEAR AT A MINIMUM DEPTH OF 4'-0'' BELOW ADJACENT FINISH
EXTERIOR GRADE.
DO NOT PLACE ANY FOOTINGS ON FROZEN SUBGRADE.
BACK FILLING SHALL BE DONE SIMULTANEOUSLY ON BOTH SIDES OF FOUNDATION WALLS.
REMOVE ANY EXISTING CONCRETE 2'-0'' BELOW NEW CONCRETE FOOTINGS AND SLABS ON GRADE.
CENTER PIER AND COLUMN FOOTINGS ON COLUMN CENTERLINES AND WALL FOOTINGS ON WALL
CENTERLINES UNLESS SPECIFICALLY NOTED OTHERWISE.
TOP OF FOOTING ELEVATIONS SHOWN ON THESE CONSTRUCTION DOCUMENTS REPRESENT
MINIMUM FOOTING DEPTHS FOR FROST PROTECTION AND BEST JUDGMENT OF A SUITABLE
BEARING STRATUM. ACTUAL GRADE CONDITIONS AND SUITABLE BEARING STRATUM MUST BE
VERIFIED BY THE CONTRACTOR AND A SOILS ENGINEER AT THE TIME OF EXCAVATION.
FOOTING EXCAVATIONS MUST EXTEND TO COMPETENT BEARING MATERIAL. CONTRACTOR SHALL
HIRE A SOILS ENGINEER TO FIELD VERIFY NET ALLOWABLE SOIL BEARING CAPACITY STATED ON
THESE CONSTRUCTION DOCUMENTS AND IN GEOTECHNICAL REPORT FOR THIS PROJECT. IF
SUITABLE BEARING STRATUM DOES NOT EXIST AT FOOTING ELEVATIONS STATED ON
CONSTRUCTION DOCUMENTS, EXCAVATIONS SHALL BE EXTENDED UNTIL SOIL WITH STATED
BEARING CAPACITY IS REACHED. PLACE COMPACTED FILL BELOW FOOTINGS OR EXTEND
FOOTINGS DOWN TO SUITABLE BEARING STRATUM. ENGINEERED FILL BELOW SLABS ON GRADE
AND FOOTINGS SHALL BE FREE DRAINING GRANULAR MATERIAL COMPACTED TO 95% MODIFIED
PROCTOR AND PLACED PER THE SOIL ENGINEERS RECOMMENDATIONS.
1.
2.
3.
4.
5.
6.
7.
8.
CAST-IN-PLACE REINFORCED CONCRETE:
CONCRETE WORK SHALL CONFORM TO THE CURRENT EDITION OF ACI 318 (BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE) AND ACI 302 (GUIDE FOR CONCRETE FLOOR AND SLAB
CONSTRUCTION).
CONTRACTOR SHALL SUBMIT FIVE SETS OF STEEL REBAR SHOP DRAWINGS FOR APPROVAL PRIOR TO CONSTRUCTION. CONTRACTOR SHALL REVIEW AND STAMP ALL SHOP DRAWINGS BEFORE SUBMITTING
TO THE ARCHITECT.
GROUT BELOW BASE PLATES AND BEARING PLATES SHALL BE NON-SHRINK, NON-METALLIC GROUT 3/4''
THICK MINIMUM AND 2'' MAXIMUM.
STEEL REINFORCING BARS SHALL CONFORM TO ASTM A615 (GRADE 60). DEFORMED WELDED WIRE
FABRIC SHALL CONFORM TO ASTM A185.
CONTRACTOR SHALL PROVIDE SUITABLE WIRE SPACERS, CHAIRS, TIES, ETC FOR SUPPORTING
REINFORCING STEEL IN THE PROPER POSITION WHILE PLACING CONCRETE.
PROVIDE (2)-#5 BARS AROUND ALL OPENINGS AND (2)-#5 BARS DIAGONALLY AT ALL OPENING CORNERS.
EXTEND BARS 2'-6'' PAST OPENING.
PROVIDE 1/2'' EXPANSION JOINT MATERIAL AT INTERIOR LOCATIONS WHERE SLABS ABUT WALLS, COLUMNS, AND OTHER VERTICAL SURFACES UNLESS NOTED OTHERWISE.
PROVIDE A 1'' CHAMFER ON EXPOSED CORNERS OF CONCRETE UNLESS NOTED OTHERWISE.
DO NOT PLACE CONDUITS, PIPES, DUCTS, OR FIXTURES IN STRUCTURAL CONCRETE UNLESS NOTED
OTHERWISE.
SLEEVES, CONDUITS, OR PIPING PASSING THROUGH CONCRETE SLABS AND WALLS SHALL BE PLACED SO THAT THEY ARE NOT CLOSER THAN THREE DIAMETERS ON CENTER AND SO THAT THEY DO NOT
DISPLACE REINFORCING.
PROVIDE SAW CUT CONTROL JOINTS IN CONCRETE SLABS ON METAL DECK SPACED NO MORE THAN 20'- 0'' APART. PLACE CONTROL JOINTS ON COLUMN CENTER LINES IN EACH DIRECTION. REFER TO CONTROL
JOINT LAYOUT SHOWN ON FOUNDATION PLAN FOR REFERENCE.
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY IRREGULARITIES OR DEFECTS IN CONCRETE SLABS (CRACKS, BUMPS, FLOOR CURLING, ETC.) BEFORE ANY FLOOR FINISHES ARE APPLIED.
ALL LAPS IN REINFORCING STEEL SHALL BE CLASS ''B'' LAP SPLICES UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL HIRE A MATERIALS TESTING LABORATORY TO CAST AND TEST CONCRETE
CYLINDERS. ALL TESTING SHALL BE IN ACCORDANCE WITH ACI 318.83 SECTION 4.7. RESULTS OF CYLINDER TESTS SHALL BE SUBMITTED TO THE ARCHITECT. CONCRETE TEST REPORTS SHALL STATE
THE FOLLOWING INFORMATION:
LOCATION ON PROJECT WHERE THE CONCRETE IS USED
7 DAY COMPRESSIVE STRENGTH
28 DAY COMPRESSIVE STRENGTH
AIR CONTENT
SLUMP
AMOUNT OF WATER ADDED ON JOB SITE
MIX USED
CONCRETE TEST REPORTS SHALL DIRECTLY STATE WHETHER OR NOT THE TEST RESULT COMPLIES WITH
THE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS.
CLASS C FLY ASH OR SLAG MAY BE SUBSTITUTED FOR CEMENT ON A POUND TO POUND BASIS UP TO
10% OF THE TOTAL CEMENTITIOUS CONTENT.
ALL CONCRETE SLABS SHALL BE WET CURED PER ACI RECOMMENDATIONS FOR NO LESS THAN SEVEN
DAYS.
CALCIUM CHLORIDE OR ADMIXTURES CONTAINING CALCIUM CHLORIDE ARE NOT PERMITTED IN ANY
CONCRETE MIX.
PROVIDE THE FOLLOWING CLEAR COVER DISTANCES FOR REINFORCEMENT IN CONCRETE:
FOOTINGS - BOTTOM & SIDES
FOOTINGS - TOP
SLABS - BOTTOM & SIDES
SLABS -TOP
INTERIOR WALLS
EXTERIOR WALLS - OUTSIDE FACE
EXTERIOR WALLS - INSIDE FACE
PIERS
CONTRACTOR SHALL USE SMOOTH FORMS FOR EXPOSED CONCRETE SURFACES. ANY CONCRETE
SURFACE REPAIRS SHALL BE PERFORMED BY THE CONTRACTOR AS REQUIRED. REPAIR AND PATCH
DEFECTIVE AREAS WITH PROPRIETARY PATCHING COMPOUND IMMEDIATELY AFTER REMOVAL OF
FORMS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
3'' 2'' 1'' 3/4'' 1'' 1 1/2'' 1'' 2''
STRUCTURAL STEEL:
DESIGN, FABRICATION, AND ERECTION SHALL CONFORM TO THE CURRENT EDITION OF AISC (AMERICAN
INSTITUTE OF STEEL CONSTRUCTION) ''MANUAL OF STEEL CONSTRUCTION''.
STEEL DETAILING AND CONNECTIONS SHALL CONFORM TO THE REQUIREMENTS OF THE CURRENT
EDITION OF AISC ''SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, ALLOWABLE STRESS DESIGN
AND PLASTIC DESIGN''.
WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS HOLDING CURRENT AWS CERTIFICATES IN
THE TYPES OF WELDING SPECIFIED ON THESE CONSTRUCTION DOCUMENTS.
CONTRACTOR SHALL SUBMIT FIVE SETS OF STEEL SHOP DRAWINGS FOR APPROVAL PRIOR TO
FABRICATION. CONTRACTOR SHALL REVIEW AND STAMP ALL SHOP DRAWINGS BEFORE SUBMITTING TO
THE ARCHITECT.
CONTRACTOR SHALL DESIGN AND PROVIDE ANY TEMPORARY BRACING OR GUYS REQUIRED TO ERECT STEEL MEMBERS. TEMPORARY BRACING SHALL BE LEFT IN PLACE UNTIL THE PERMANENT STRUCTURE
IS IN PLACE AND SECURE.
PROVIDE 3/16'' CAP PLATE AT THE ENDS OF ALL EXPOSED TUBE AND PIPE MEMBERS.
STAIRS, HANDRAILS, AND GUARDRAILS SHALL BE DESIGNED BY THE STEEL SUPPLIER.
ALL STEEL BEAMS SHALL BE FABRICATED WITH THE NATURAL CAMBER (WITHIN MILL TOLERANCE).
THE STEEL SUPPLIER SHALL COORDINATE HIS WORK WITH THE STEEL JOIST SUPPLIER ON THE
PROJECT.
CAPACITY OF BOLTED OR WELDED CONNECTIONS SHALL BE EQUAL TO OR EXCEED 120% OF BEAM
REACTION PRODUCED BY MAXIMUM ALLOWABLE UNIFORM LOAD ON THE GIVEN MEMBER SPAN.
UNLESS OTHERWISE NOTED ON CONSTRUCTION DOCUMENTS, ALL BEAM CONNECTIONS SHALL BE
DOUBLE ANGLE CONNECTIONS WITH 3/4" DIAMETER A325N BOLTS. AT BEAM TO BEAM AND BEAM TO COLUMN CONNECTIONS, PROVIDE AS MANY BOLTS AS POSSIBLE INTO THE SUPPORTING MEMBER.
DOUBLE ANGLE WELDED CONNECTIONS MAY BE SUBSTITUTED FOR BOLTED CONNECTIONS. WELDED
CONNECTIONS MUST DEVELOP THE SAME LOAD CAPACITY AS BOLTED CONNECTION SPECIFIED.
ALTERNATE CONNECTIONS FROM WHAT IS SPECIFIED ON THE CONSTRUCTION DOCUMENTS WILL NOT
BE ACCEPTED WITH-OUT WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.
USE STANDARD AISC DOUBLE ANGLE CONNECTIONS WHERE POSSIBLE. ALL STANDARD DOUBLE
ANGLE CONNECTIONS SHALL BE IN ACCORDANCE WITH ASD NINTH EDITION AND SHALL BE TYPE 2
FRAMING CONNECTIONS UNLESS NOTED OTHERWISE.
PROVIDE STIFFENER PLATES ON BOTH SIDES OF BEAM WEBS AT ALL CONCENTRATED LOADS ABOVE
AND BELOW A BEAM. UNLESS NOTED OTHERWISE, FRAME THE LARGEST BEAM OVER COLUMNS AT
BEAM TO BEAM INTERSECTIONS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
STEEL JOISTS:
DESIGN, FABRICATION, AND ERECTION SHALL CONFORM TO THE CURRENT EDITION OF ''STEEL JOIST
INSTITUTE SPECIFICATIONS''.
JOIST MANUFACTURER SHALL BE A MEMBER OF THE SJI (STEEL JOIST INSTITUTE).
CONTRACTOR SHALL SUBMIT FIVE SETS OF STEEL JOISTS SHOP DRAWINGS FOR APPROVAL PRIOR
TO FABRICATION. CONTRACTOR SHALL REVIEW AND STAMP ALL SHOP DRAWINGS BEFORE
SUBMITTING TO THE ARCHITECT.
PROVIDE SJI STANDARD BRIDGING AS SHOWN ON THE CONSTRUCTION DOCUMENTS OR AS
REQUIRED BY DESIGN.
DO NOT CUT OR DRILL THROUGH ANY JOIST.
ALL CONCENTRATED LOADS SHALL BE APPLIED AT A JOIST PANEL POINT UNLESS SPECIFICALLY
NOTED OTHERWISE.
JOIST MANUFACTURER SHALL DESIGN JOISTS FOR ROOF TOP UNIT LOADS AND SUSPENDED UNIT
LOADS SHOWN ON CONSTRUCTION DOCUMENTS. COORDINATE EXACT LOCATION OF APPLIED
LOAD WITH CONTRACTOR.
DESIGN JOISTS AND BRIDGING TO RESIST A NET WIND UPLIFT LOAD OF 5 PSF.
PROVIDE CAMBER IN JOIST AS RECOMMENDED BY SJI SPECIFICATIONS.
JOIST SUPPLIER SHALL COORDINATE HIS WORK WITH THE STEEL SUPPLIER ON THE PROJECT.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
METAL DECK:
DECK, ACCESSORIES, AND ATTACHMENTS SHALL CONFORM WITH THE CURRENT EDITION OF ''STEEL
DECK INSTITUTE SPECIFICATIONS''.
PROVIDE SUPPORT AT COLUMNS AS REQUIRED FOR DECK SUPPORT. PROVIDE L2x2x3/16 MINIMUM.
AT OPENINGS IN DECK LESS THAN 12''x12'', PROVIDE A 16 GAUGE COVER PLATE FASTENED TO DECK
WITH #12 TEK SCREWS.
AT CHANGE IN DECK DIRECTION, PROVIDE A 22 GAUGE x 12'' WIDE CONTINUOUS PLATE. PROVIDE
SAME PLATE AT ALL RIDGES, VALLEYS, AND HIPS BENT TO MATCH PROFILE OF ROOF.
1.
2.
3.
4.
COLD-FORMED METAL FRAMING
LIGHT GAUGE STEEL CONTRACTOR SHALL SUBMIT (5)-SETS OF LIGHT GAUGE SHOP DRAWINGS
WITH STRUCTURAL CALCULATIONS STAMPED BY A PROFESSIONAL ENGINEER REGISTERED IN THE
STATE OF MAINE TO THE ARCHITECT AND ENGINEER FOR APPROVAL.
ALL LIGHT GAUGE MEMBERS SPECIFIED ON THE CONSTRUCTION DOCUMENTS ARE MINIMUM SIZES.
LIGHT GAUGE DESIGNER TO VERIFY ALL SIZES.
REFER TO MATERIAL STRENGTHS ON SHEET S001 COLD-FORMED METAL FRAMING YIELD STREE
(Fy).
ALL LIGHT GAUGE STEEL MEMBERS SHALL BE CLARK STEEL FRAMING SYSTEMS PRODUCTS OR
APPROVED EQUAL.
ALL STUDS SHALL BE GALVANIZED.
DESIGN, SUPPLY, AND INSTALL ANY HOT-ROLLED OR COLD-ROLLED SECTION NEEDED TO PROVIDE
A COMPLETE EXTERIOR CLADDING SYSTEM.
REFER TO DEFLECTION LIMIT CRITERIA ON SHEET S001 FOR ALL COLD-FORMED FRAMING
DEFLECTION REQUIREMENTS.
OTHER CLADDING MATERIALS.
THE NAME, ADDRESS, PHONE NUMBER, & FAX NUMBER OF THE SUPPLIER. ALL DESIGN LOADS.
PLANS & ELEVATIONS KEYING IN ALL SECTIONS.
CONNECTION DETAILS SPECIFYING ALL FASTENER TYPES, QUANTITY, & LOCATIONS.
ALL REQUIRED BRIDGING, BRACING, & OTHER LIGHT GAUGE COMPONENTS.
ALL WELDING SHALL BE AWS D1.3. WELDERS SHALL BE CERTIFIED FOR THE THICKNESS OF
MATERIAL BEING WELDED.
SCREW PENETRATION THROUGH JOINED MATERIALS SHALL NOT BE LESS THAN THREE EXPOSED
SCREW THREADS. REFER TO INSTALLATION INSTRUCTIONS OF THE SCREW MANUFACTURER
AND/OR ASTM C-954 FOR MINIMUM SPACING AND EDGE DISTANCE AND TORQUE REQUIREMENTS.
INSTALL CONTINUOUS TRACKS SIZED TO MATCH STUDS. ALIGN TRACKS ACCURATELY TO LAYOUT
AT BASE AND TOPS OF STUDS. SECURE TRACKS AS RECOMMENDED BY STUD MANUFACTURER
FOR TYPE OF CONSTRUCTION INVOLVED, EXCEPT DO NOT EXCEED 24'' o/c SPACING FOR POWDER- DRIVEN FASTENERS, OR 16'' o/c FOR OTHER TYPES OF ATTACHMENT. PROVIDE FASTENERS AT
CORNERS AND END OF TRACKS.
WHERE SPLICING OF TRACK IS NECESSARY BETWEEN STUD SPACINGS, PROVIDE A PIECE OF STUD
PLACED BETWEEN ADJACENT TRACKS AND FASTENED BY WELD OR SCREW TO EACH SIDE OF THE
TRACK EACH END.
AT NON-LOAD BEARING WALLS, PROVIDE A SLIP TRACK AT TOP OF WALL.
FASTENING OF COMPONENTS SHALL BE WITH SELF-DRILLING SCREWS OR BY WELDING. SCREWS
AND WELDS SHALL BE SUFFICIENT SIZE TO ENSURE THE STRENGTH OF THE CONNECTION.
ALL WELDS SHALL BE TOUCHED UP WITH ZINC-RICH PAINT.
INSTALL LIGHT GAUGE FRAMING MEMBERS IN ACCORDANCE WITH MANUFACTURERS PRINTED OR
WRITTEN INSTRUCTIONS AND RECOMMENDATIONS UNLESS NOTED OTHERWISE.
FIELD CUTTING OF LIGHT GAUGE MEMBERS SHALL BE BY SAW OR SHEAR. TORCH CUTTING IS NOT
PERMITTED.
TEMPORARY BRACING OF LIGHT GAUGE MEMBERS SHALL BE PROVIDED AND REMAIN IN PLACE
UNTIL WORK IS PERMANENTLY STABILIZED. ALL BRACING REQUIRED SHALL BE DESIGNED AND
SUPPLIED BY THE LIGHT GAUGE CONTRACTOR.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
21675 LONG VIEW DRIVE
SUITE 500
WAUKESHA, WI 53186
FAX (262) 798.7001
PHONE (262) 798.7000
E-MAIL welman@welmanarch.com
PROJECT NO.
DATE:
REVISION / ISSUES:
SHEET NAME:
SHEET NO:
C COPYRIGHT BY WELMAN
ARCHITECTS INC.
CONTRACTOR:
PROJECT:
CERTIFICATION:
4035 N 127th Street Brookfield, WI 53005
Fax: (262) 373-0860Tel: (262) 373-0680
Project #: 09-174
Inc.
Structural Dimension
03-19-2010 FTG/FND SUBMITTAL
03-26-2010 Design Development Review I & II
04-02-2010 75% VA Review
04-16-2010 City Submittal
05-21-2010 CB #1
05-21-2010 100% VA Review
35 State Hospital Drive
Bangor, ME 04401
S001
GENERAL NOTES
VA
Outpatient
Clinic
03-19-10
28112
B
2 3 4 5 6 7
C
D
E
F
G
H
F.8' 5.8'
7.8'
E.8'
3.9
A
4.7 5.6 6.6
2.5'
1.5'
C.3'
C.5'
D.5'
0.5'
3.5'
1.3'
2.3'
D.4
C.4
6.8'
E.4
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
W20 96'-0''
W
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
SIM.
C J
C J
C J
C J
W20 96'-0''
W20 96'-0''
W15 96'-0''
W
W
W15 96'-0''
W20 96'-0''
W20 87'-6''
W20 96'-0''
W
7' - 6" 46' - 2" 6' - 4" 122' - 0" 23' - 0" 2' - 0"
7' - 8" 1' - 0" 14' - 4" 32' - 0" 15' - 0"
1' - 4" 29' - 8" 30' - 0" 28' - 8" 1' - 4" 19' - 8" 1' - 6" 9' - 0" 11' - 7 1/2" 5' - 8 1/2" 8' - 8 3/8" 3' - 9 5/8" 18' - 0" 11' - 8" 1' - 4" 24' - 0"
182' - 0"
/4
/8
/8
146' - 7 3/4"
/4
/4
3/ 4"
8' 9"
0"
8' 9"
3/ 4"
/2
2' - 0"
14' - 8"
7' - 6"
W
24' - 7 3/8"
1' - 4 3/8"
23' - 9 5/8"
1' 4"
1' 4"
C.2
C.6
1' - 0"
1' - 0" 5' - 8"
1' 0"
1' - 0"
1' 0"
1' - 0"
1' - 0"
5' - 0"
1' - 0"
1' - 0"
9'
9' " 6
1' - 0"
1' - 0"
6" 6"
6" 6"
1' - 0"
T/L=99'-9-1/4"
T/W=100'-0"
T /L -1 /4
T /W
T /L -1 /4
T /W
T/L=99'-9-1/4"
T/W=100'-0"
T/L=99'-9-1/4"
T/W=100'-0"
T/L=99'-9-1/4"
T/W=100'-0"
T /L -1 /4
T /W
T/L=99'-9-1/4"
T/W=100'-0"
4'' CONCRETE SLAB ON GRADE
w/ 6x6-W1.4xW1.4 WWF
REINFORCEMENT.
REFER TO 1/S400 FOR SLAB ON
GRADE CONSTRUCTION.
T/SLAB ELEV=100'-0''
S400
S400
S400
S400
S400
S400
S400
S400
S400
S400
S400
F80 99'-4''
BP1
F90A 98'-0''
BP4
F100A 99'-4''
BP4
F80 98'-0''
BP1
F80A 99'-4''
BP4
F80A 99'-4''
BP4
F80A 99'-4''
BP4
F80 99'-4''
BP1
F80 99'-4''
BP1
F80 99'-4''
BP1
F80A 99'-4''
BP4
F80A 98'-0''
BP4
F80A 99'-4''
BP4
F80A 99'-4''
BP4
F90A 99'-4''
BP4
F80A 99'-4''
BP4
F80A 99'-4''
BP4
F80A 98'-0''
BP4
F80A 99'-4''
BP4
F80A 99'-4''
BP4
F80A 99'-4''
BP4
F80 98'-0''
BP1
F100A 99'-4''
BP4
F80 98'-0''
BP1
F80A 99'-4''
BP4
F60 98'-0''
BP1
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 87'-6''
P1 99'-0''
F50 87'-6''
P1 99'-4''
F50 87'-6''
P1 99'-4''
F90A 87'-6''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4'' F90A 96'-0''
P1 99'-4''
F90A 96'-0''
P1 99'-4''
F100A 96'-0''
P1 99'-4''
F50 96'-0''
P1 99'-4''
F50 96'-0''
P1 99'-4''
F110A 96'-0''
P1 99'-4''
F100A 96'-0''
P1 99'-4''
F100A 96'-0''
P1 99'-4''
F100A 96'-0''
P1 99'-4''
F50 96'-0''
P1 99'-4''
F50 96'-0''
P1 99'-4''
F40 96'-0''
P1 99'-4'' F40 96'-0''
P1 99'-4''
F40 96'-0''
P1 99'-4''
F40 96'-0''
P1 99'-4''
F40 96'-0''
P1 99'-4''
S400
S400
S400
S400
135.00°
.0
.0
.00
2' - 0" 24' - 4" 2' - 0" 28' - 6" 2' - 0" 12' - 0"
9' 1"
2' 0" 11
0" 2' 0"
9' 1"
F.9
5.9
24' - 7 3/8"
7' - 6"
8"
8"
F80A 99'-4''
BP4
T/W=99'-4"
T /W
T /W
T /W
T/W =99'-4"
T/W =99'-4"
E.6
F.3
F80A 99'-4"
BP4
F90A 99'-4"
BP4
F80A 99'-4"
BP4
F80A 99'-4''
BP4
F80A 99'-4"
BP4
5.54.6
F110A 96'-0''
P1 99'-4''
T/SLAB
ELEV 99'-6"
T/SLAB
ELEV 99'-6"
6"
6"
6"
6"
S400
S400
S400
15' - 8" 2' - 3 7/8"
/8
8' - 5 1/2"
15' - 8"
F50 87'-6''
P1 99'-4''
/8
S400
S400
S400
S400
6' - 0"
3' - 0"
1' - 0" 4' - 6"
RW-1 87'-6''
W
W
S T E P
S T E P
S T E P
S T E P
W
W
W20 93'-6''
W20 91'-6''
STEP 2'-6''
STEP 2'-0''
STEP 2'-0''
STEP 2'-0''
W20 89'-6''
PROVIDE 15# FELT PAPER
(BOND BREAKER) BETWEEN
RETAINING WALL FTG &
BLDG FTG
129' - 8" 4' - 0" 4' - 0" 4' - 0"
/4
T/W=99'-4''
T/W=99'-4''
5' - 0" 1' - 0"
4' - 0"
1' - 0"
T/W=99'-4"
5' 4"
S400
SIM.
S400
S400
S400
S400
S400
S400
1' - 0"
S400
S400
10' - 4" 51' - 0"
1' - 0"
W20 96'-0''
T/L=99'-8"
REFER TO CIVIL PLANS
REFER TO CIVIL PLANS
R E F E R T O C
IV
IL
P L A N S
R E F E R T O C
IV
IL
P L A N S
REFER TO CIVIL PLANS
NEW 12'' CONRETE MRI PAD ON
GRADE w/ NOVA MESH E3 AT
DOSAGE RATE OF 24 #/CU YD
ON 8" FREE DRAINING SUB-
BASE.
T /W
T /W
T /W
T /W
T/W=100'-0"
T/W=100'-0''
T/L=99'-9-1/4"
T/W=100'-0"
T/W=100'-0"
T/W=100'-0''
T/L=99'-9-1/4''
T/L=99'-9-1/4"
T/W=100'-0''
T/L=99'-9-1/4"
T/L=99'-9-1/4"
T /W
T /W
T /L -1 /4
T /W
T /W
T /L -1 /4
T /W
T /L -1 /4
T /L -1 /4
T /L -1 /4
T /W
T /W
T /W
T /L -1 /4
T /L -1 /4
T /W
T /W
T /W
T /L -1 /4
T /L -1 /4
T/L=99'-9-1/4"
T/L=99'-9-1/4"
T/L=99'-9-1/4"
T/W=100'-0"
T/W=100'-0"
T/W=100'-0"
T/W=100'-0"
T/L=99'-9-1/4"
T/L=99'-9-1/4"
T/L=99'-9-1/4"
T/L=99'-9-1/4"
T/W =100'-0''
T/L=99'-9-1/4"
T/W =100'-0''
T/W =100'-0''
T/W =100'-0''
T/W =99'-4''
T/W =100'-0''
T /L -1 /4
T /W
T/W=100'-0"
4" 8"
REFER TO SHEET
S300 FOR SMOKING
SHELTER PLANS
W20 100'-0''
7' - 6"
17' - 0"
1' - 4"
6" 5' - 10" 1' - 0"
2.9
2"
2.7'
3/ 4"
7' 6"
7' 6"1.0'
3/ 4"
7' 6"
7' 6"
2"
C.7
BP6
BP6
BP2
BP2
BP5
BP3
BP1
BP1
BP3
BP5
BP4
BP4
BP4
BP4BP4 BP4
BP4 BP4
BP4
BP1
BP1
BP1
BP4
BP4
BP4
BP4
BP4
BP4BP4BP4
BP4
BP1
BP1 BP1
BP1
BP1
S403
S403
S403
S403
S403
18''Wx18''D DUCT BANK
REFER TO ELECTRICAL
DWG E0.10 FOR SPECIFICS
& LOCATION
B-1 R.W.
B-4 S.W.
B-3 S.W.
B-2 S.W.
B-2 R.W.
B-1 S.W.
B-5 S.W.
/4
11' - 10 1/2" 7' - 10 1/4"
SIM.
COLUMN FOOTING SCHEDULE
SCHEDULE NOTES:
1. REFER TO GENERAL NOTES ON SHEET S001 FOR MINIMUM COVER REQUIREMENTS.
2. REFER TO FOUNDATION PLAN FOR TOP OF FOOTING ELEVATIONS.
3. NET ALLOWABLE SOIL BEARING CAPACITY = 1500 PSF. CONTRACTOR TO HIRE SOILD ENGINEER
FIELD VERIFY AT TIME OF FOOTING EXCAVATION.
4. LAP REINFORCEMENT 30'' MINIMUM.
FOOTING
MARK
FOOTING SIZE
(WIDTH x LENGTH)
THICKNESS BOTTOM REINFORCEMENT TOP REINFORCEMENT REMARKS
LONG SHORT LONG SHORT
F40
F50
F60
4'-0''x4'-0''
5'-0''x5'-0''
6'-0''x6'-0''
12''
12''
12''
(6)-#5
(6)-#5
(6)-#5
(6)-#5
(6)-#5
(6)-#5
BOTT OR TOP
REINF-LONG
BOTT OR TOP
REINF-SHORT
TOP REINF
BOTT REINF
FTG WIDTH
2" CLR 2" CLR
EQ EQ E
Q
E Q
E Q
E Q
C L R
F T G L E N G T H
C L R
FTG WIDTH
C L R
C L R
F T G
T H
IC
K N E S S
F80
F80A
F90A
8'-0''x8'-0''
8'-0''x8'-0''
9'-0''x9'-0''
14''
14''
14''
(7)-#6
(7)-#6
(10)-#6
(7)-#6
(7)-#6
(10)-#6
F100A 10'-0''x10'-0'' 16'' (8)-#7 (8)-#7
F110A 11'-0''x11'-0'' 18'' (9)-#7 (9)-#7
(6)-#5
(7)-#5
(6)-#5
(7)-#5
(8)-#5 (8)-#5
(8)-#5 (8)-#5
96'-0''F30
99'-4''P1
96'-0''W20
TOP OF FTG
ELEVATION
WALL FTG MARK
REFER TO SCHED
ON S001
COLUMN FTG
MARK. REFER
TO SCHED ON
S001
TOP OF FTG
ELEVATION
CONCRETE PIER
MARK. REFER TO
SCHED ON S001
TOP OF CONC
PIER MARK.
TOP OF WALL
ELEVATION
TOP OF LEDGE
ELEVATION.
FOUNDATION LEGEND
T/W=100'-0'' T/L=99'-4''
PIER SCHEDULE - CONCRETE
P1 24''x24'' (8)-#6 #4 AT 12'' o/c (4)-#5 (10''x39'')
SCHEDULE NOTES:
1. REFER TO GENERAL NOTES ON SHEET S001 FOR MINIMUM COVER REQUIREMENTS.
2. AT TOP OF CONCRETE PIER, PROVIDE (3)-#4 TIES AT 3'' o/c.
3. HOOK ALL VERTICAL REINFORCEMENT AT TOP OF CONCRETE PIERS WITH A 90 DEGREE HOOK 8''.
4. WHERE NO DOWELS ARE SHOWN FROM THE CONCRETE PIER TO THE CONCRETE FOOTING, EMBED VERTICAL
PIER REINFORCEMNT INTO FOOTING 9'' MINIMUM AND PROVIDE A 90 DEGREE HOOK 10''.
5. CONTINUE HORIZONTAL WALL REINFORCING THROUGH THE CONCRETE PIER.
6. CENTER CONCRETE PIER BELOW COLUMN ABOVE.
7. ALIGN VERTIVAL CONCRETE PIER REINFORCEMENT WITH VERTICAL MASONRY PIER/WALL REINFORCEMENT ABOVE.
8. LAP VERTICAL REINFORCEMENT 30 BAR DIAMETERS OR 24'', WHICH EVER IS GREATER.
PIER
MARK
SIZE
(WIDTH x CONT)
VERTICAL
REINFORCEMENT
PIER
TIES
DETAIL DOWELS REMARKS
P2 24'' DIA x 48''D (8)-#6 #4 AT 12'' o/c
REINFORCEMENT
LONGITUDINAL TRANSVERSE
REMARKS
W15 1'-6''xCONT 12'' (2)-#5xCONT
W20 2'-0''xCONT 12'' (2)-#5xCONT
WALL FOOTING SCHEDULE
SCHEDULE NOTES:
1. REFER TO GENERAL NOTES ON SHEET S001 FOR MINIMUM COVER REQUIREMENTS.
2. REFER TO FOUNDATION PLAN FOR TOP OF FOOTING ELEVATIONS.
3. NET ALLOWABLE SOIL BEARING CAPACITY = 1500 PSF. CONTRACTOR TO HIRE SOILD
ENGINEER TO FIELD VERIFY AT TIME OF FOOTING EXCAVATION.
4. LAP REINFORCEMENT 30'' MINIMUM.
FOOTING
MARK
FOOTING SIZE
(WIDTH x CONT)
THICKNESS
FOUNDATION PLAN NOTES:
REFER TO S001 FOR ADDITIONAL
STRUCTURAL NOTES AND FOUNDATION
REQUIREMENTS.
ELEVATION 100'-0'' ON STRUCTURAL
DRAWINGS CORRESPONDS TO FF
ELEVATION SHOWN ON SITE PLAN.
TYPICAL.
SLAB DEPRESSIONS: VERIFY ALL SLAB
DEPRESSIONS (SIZE, DEPTH, LOCATION)
w/ ARCHITECTURAL DRAWINGS.
MASONRY PIERS: MASONRY PIERS
SHOWN ON THE FOUNDATION PLAN ARE
ABOVE THE CONCRETE FOUNDATION.
REFER TO FRAMING PLANS & SCHEDULE
FOR PIER DESIGNATION AND SIZE.
PROVIDE DWLS MATCHING VERTICAL
MASONRY PIER REINFORCEMENT INTO
FOUNDATION.
REFER TO FRAMING PLANS FOR
LOCATION, SIZE, & SPACING OF MASONRY
WALL REINFORCEMENT.
REFER TO FRAMING PLANS FOR STEEL
COLUMN SIZES.
REFER TO BASE PLATE SCHEDULE ON
S002 FOR COLUMN BASE PLATE SIZE AND
NUMBER OF ANCHOR BOLTS &
ORIENTATION.
"RW-X" INDICATES CONCRETE RETAINING
WALL TYPE. REFER TO SCHEDULE ON
S002 FOR WALL AND FOOTING SIZE &
REINFORCEMENT.
'' '' INDICATES SOILS BORING
LOCATION. REFER TO GEOTECHNICAL
PLANS FOR SPECIFICS.
''BPX'' INDICATES STEEL COLUMN BASE
PLATE. REFER TO BASE PLATE SCHEDULE
ON S002 FOR COLUMN BASE PLATE SIZE
AND NUMBER OF ANCHOR BOLTS AND
ORIENTATION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
FOUNDATION KEYED NOTES:
5'' THICK REINFORCED STRUCTURAL
CONCRETE STOOP SLAB w/ #4 AT 12'' o/c EACH WAY. PROVIDE #4 DWLS 12''x12'' AT 12'' o/c AT PERIMETER ALL AROUND. LOCATE
REINFORCEMENT 1-1/2'' FROM BOTTOM OF
SLAB.
(2)-#5x4'-0'' CENTERED IN THICKNESS OF SLAB
ON GRADE AND LOCATED AT RE-ENTRANT
CORNERS. TYPICAL.
(8)-#5x4'-0'' CENTERED IN THICKNESS OF SLAB
ON GRADE AND LOCATED AROUND STEEL
COLUMNS AS SHOWN ON PLAN REFER TO
2/S400. TYPICAL.
21675 LONG VIEW DRIVE
SUITE 500
WAUKESHA, WI 53186
FAX (262) 798.7001
PHONE (262) 798.7000
E-MAIL welman@welmanarch.com
PROJECT NO.
DATE:
REVISION / ISSUES:
SHEET NAME:
SHEET NO:
C COPYRIGHT BY WELMAN
ARCHITECTS INC.
CONTRACTOR:
PROJECT:
CERTIFICATION:
4035 N 127th Street Brookfield, WI 53005
Fax: (262) 373-0860Tel: (262) 373-0680
Project #: 09-174
Inc.
Structural Dimension
03-19-2010 FTG/FND SUBMITTAL
03-26-2010 Design Development Review I & II
04-02-2010 75% VA Review
04-16-2010 City Submittal
05-21-2010 CB #1
05-21-2010 100% VA Review
35 State Hospital Drive
Bangor, ME 04401
S100
FOUNDATION PLAN
VA
Outpatient
Clinic
03-19-10
28112
SCALE: 3/32" = 1'-0"
FOUNDATION PLAN
THE FOLLOWING ARE ITEMS THAT
HAVE BEEN REVISED SINCE THE
FOOTING & FOUNDATION SUBMITTAL
DATED 3-19-2010 THAT ARE NOT
CLOUDED ON THIS PLAN.
1. BRICK LEDGE HAS BEEN OMITTED
AT ALL OPNGS IN EXTERIOR WALL.
B
2 3 4 5 6 7
C
D
E
F
G
H
F.8' 5.8'
7.8'
E.8'
3.9
A
4.7 5.6 6.6
2.5'
1.5'
C.3'
C.5'
D.5'
0.5'
3.5'
1.3'
2.3'
D.4
C.4
6.8'
24K7 24K7 24K7 24K7 24K7
24K7 24K7 24K7
24K7 24K7
24K7
24K7 24K7
18K3
18K5
18K5
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7 24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
22K4
22K4
22K4
22K4
22K4
22K4
22K4
22K4
22K4
12K1
12K1
12K1
12K1
12K1
12K1
E.4
C.2
C.6
F.9
5.9
E.6
F.324K7 24K7 24K7
24K7 24K7 24K7
24K7 24K7 24K7
24K7
24K7
24K7
24K7
24K7
24K7
24KCS3
24KCS3
24KCS3
24KCS3
24KCS3
24KCS3
24K7 24K7 24K7
24K724K724K7
24K7 24K7 24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
12KCS1
12KCS1
12K1
5.54.6
5" 7 3/4" 3 3/4"
1' - 2"3 3/4"
/8
/8
7 3/4" 5"
K
K
K
K
K
K
K
K
K
K
K
K
W16X26 ( 115' - 6" )
W16X26 ( 115' - 6" )
W X
/2
W X /2
W X
24K7
24K7
24K7 24K7 24K7 24K7 24K7 24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
16KCS2 24K7 24K7 24K7 24K7 24K7
24K7 24K7 24K7 24K7 24K7 24K7
24K7 24K7 24K7 24K7 24K7 24K7
24K724K724K724K724K718K4
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
24K7
12KCS1
W X
W X
W X
W X
W X2
( 1
W X2
( 1
W X
W X
W X
W X5
( 1
W14X22
W16X26 ( 113' - 6 1/2" )
W X
W18X35 ( 113' - 6 1/2" ) W18X35 ( 113' - 4" ) W18X35 ( 113' - 4" ) W18X35 ( 113' - 4" )
W18X35 ( 113' - 6 1/2" ) W18X35 ( 113' - 6 1/2" ) W18X35 ( 113' - 6 1/2" ) W18X35 ( 113' - 6 1/2" )
W16X26 ( 113' - 1" ) W16X26 ( 113' - 1" )
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
W X
( 1 /2
W X4 0( 1
/2 ( 1 /2
W X4
( 1 /2
W X
/8
( 1
W X2
( 1
( 1
W X2
( 1
W X
( 112' - 10 1/2" )
W24X55
( 113' - 6 1/2" )
W X
/2
/2
W X
/2
24K7
W X
/2
/2
W X
( 113' - 6 1/2" )W18X55
( 112' - 11" )
( 112' - 11" ) W18X55( 113' - 6 1/2" )
W X
/2
/2
W X
W X
/2
/2
W X
W X
/2
/2
W X
/2
W X
/2
/2 W X
/2
/2
W X
( 113' - 6 1/2" )W18X55 ( 112' - 11" )
( 112' - 11" )
W18X55( 113' - 6 1/2" )
/2
W X
/2
W X
/2
W18X55
( 113' - 6 1/2" )
W18X55
( 113' - 6 1/2" )
W18X55
( 113' - 6 1/2" )
W18X55
( 113' - 6 1/2" )
W12X65
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2 HSS8X8X1/2
HSS5X5X1/4
HSS5X5X1/4 HSS5X5X1/4
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS6X6X1/4
HSS6X6X1/4
HSS8X8X1/2
HSS6X6X1/4
HSS8X8X1/2
HSS8X8X1/2HSS8X8X1/2HSS8X8X1/2HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS6X6X1/4
HSS6X6X1/4
HSS6X6X3/8
HSS6X6X3/8
HSS6X6X1/4
HSS6X6X1/4
HSS6X6X3/8
HSS6X6X3/8
HSS6X6X3/8
HSS8X8X1/2
HSS8X8X1/2
HSS6X6X3/8
HSS8X8X1/2
HSS8X8X1/2
HSS6X6X3/8 HSS6X6X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2 HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS6X6X3/8
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS5X5X1/4
HSS5X5X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS6X6X1/4
1 1 1 1 1 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
(6 E Q U A L S P A C E S
(4 E Q U A L S P A C E S
(2 E Q S P
(2 E Q S P
(2 E Q S P
(3 E Q U A L S P A C E S
(4 E Q U A L S P A C E S
(3 E Q U A L S P A C E S
(2 E Q S P
/8
(2 E Q S P
/8
(3 E Q U A L S P A C E S
(6 E Q U A L S P A C E S
W X5
( 1
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401 R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
C x x C O N T B E L O W M T L S T U D W A L L
C x x C O N T B E L O W M T L S T U D W A L L
_8
_8
_8
W x F O L D
IN
G P A R T
IT
IO
N
S U P P O R T B E A M B E L O W
V E R
IF
Y B M E L E V w A R C H
5 5
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
10 3/8"
/8
10 3/8"
4 4 4
REFER TO PENTHOUSE
FLOOR FRAMING PLAN ON
S201 FOR THIS AREA.
W12X65
/8
7 3/4" 5"
/8
10"
8"
W 24X117
( 113' - 3 1/2" )
( 113' - 3 1/2" )
W 24X117
W X1 ( 1 /2
W X
/2
( 113' - 3 1/2" )W24X117
W X1
( 1 /2
( 112' - 11 1/2" )
W 14X22
( 113' - 3 1/2" )
( 113' - 3 1/2" )
W 14X22
( 112' - 11 1/2" )
W X
( 113' - 3 1/2" )
( 113' - 6 1/2" ) ( 113' - 6 1/2" )
( 113' - 3 1/2" )
( 113' - 3 1/2" )
( 113' - 6 1/2" )
S401
S401
S401
S401
S401
S401
S401
S401
S401
S401
S402
S402
S402
S402
S402
S402
S402
S402
S402
S402
S402
S402
( 112' - 11 1/2" ) W 16X26
( 113' - 6 1/2" )
( 112' - 11 1/2" )
W 16X26
( 113' - 6 1/2" )
/2 W X
( 113' - 6 1/2" ) W18X35 ( 112' - 11 1/2" )
24K7
24K7
24K7
/8
/8
( 113' - 6 1/2" )
( 113' - 2" )
( 113' - 4" )
( 113' - 6 1/2" )
( 113' - 4 1/2" )
1 1
1 1
2.9
2.7'
1.0'
C.7
HSS4X3X1/4
H
SS4X3X
1/4
HSS4X3X1/4
HSS4X3X1/4
7' - 7 1/2"
12' - 10"
/2
0"
/2
6'' MASONSY WALL w/ #5 VERT AT 72" o/c.
EXTEND WALL TO
BOTTOM OF
STRUCTURE.
S402
S402
S402
S402
S402
S402
S402
S402
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
R.D. SEE
2/S401
SURGICAL
LIGHT BY
OTHERS
_5 11
G
E.6
F.3
5.54.6
HSS8X8X1/2
18K4
18K4
18K4
18K4
18K4
18K4
18K4
18K3
18K3
18K3
18K3
18K3
18K3
18K3
W16X36 ( 128' - 0" ) W16X36 ( 128' - 0" )
W X /2
W X /2
W16X36 ( 128' - 0" )W16X36 ( 128' - 0" )
W X
/2
W X /2
W X /2
W X /2
1 1 1 1111 2 2
/8
/2
/4
HSS8X8X1/2HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
S401
S401
S401
S401
S401
W16X36
( 128' - 0" )
W16X36
( 128' - 0" )
S401
S401
ROOF OPNG
REFER TO 2/S401
ROOF OPNG
REFER TO 2/S401
/4
7 1/4"
7 1/4"
/4
LOW ROOF FRAMING PLAN NOTES:
ALL ROOF DECK SHALL BE VULCRAFT TYPE
1.5B (WIDE RIB) 22 GAUGE PAINTED METAL
ROOF DECK OR APPROVED EQUAL.
REFER TO DETAIL 1/S401 FOR ATTACHMENT
TO ROOF STRUCTURE.
(XXX'-XX'') INDICATES THE TOP OF STEEL
BEAM ELEVATION.
REFER TO 2/S401 FOR FRAMING AROUND
ROOF DRAIN OPENINGS AND OTHER ROOF
OPENINGS. COORDINATE SIZE, LOCATION,
& QUANTITY OF STEEL FRAMES WITH
MECHANICAL CONTRACTOR ON PROJECT.
VERIFY ALL MECHANICAL EQUIPMENT
WEIGHTS, SIZES, & LOCATIONS PRIOR TO
PREPARING SHOP DRAWINGS &
FABRICATING MATERIALS. CONTRACTOR
TO COORDINATE ANY CHANGES w/ JOIST
SUPPLIER.
ALL MECHANICAL EQUIPMENT SHALL BEAR
ON (2)-JOISTS MINIMUM.
DO NOT RUN JOIST BRIDGING THROUGH
ANY DECK OPENINGS. JOIST SUPPLIER
SHALL REVIEW AND PROVIDE ALTERNATE
LOCATION FOR BRIDGING ALONG JOIST
SPAN AS REQUIRED.
'' '' INDICATES A RIGID WIND
FRAME CONNECTION.
1.
2.
3.
4.
5.
6.
7.
LOW ROOF FRAMING PLAN KEYED NOTES:
CONTINUOUS HORIZONTAL JOIST BRIDGING AT
THE TOP & BOTTOM CHORDS WITH X-
BRIDGING AS SHOWN ON THE FRAMING PLAN.
PROVIDE ADDITIONAL BOTTOM CHORD
BRIDGING AS REQUIRED TO RESIST A
UNIFORM UNFACTORED UPLIFT WIND LOAD
OF 5 PSF.
ROOF TOP UNIT w/ A 3000 LB MAXIMUM
WEIGHT (INCLUDING ROOF CURB).
ROOF TOP UNIT w/ A 6000 LB MAXIMUM
WEIGHT (INCLUDING ROOF CURB).
PROVIDE HSS2-1/2x2-1/2x1/4 ON TOP OF WIDE
FLANGE BEAM BETWEEN JOISTS FOR DECK
SUPPORT.
LIGHT GAUGE BUILT-UP BOX HEADER
DESIGNED BY LIGHT GAUGE SUPPLIER.
PENTHOUSE FLOOR CONSTRUCTION:
PROVIDE 3-1/2" CONCRETE OVER 1-1/2" 22 GA
GALVD METAL DECK (5" TOTAL THICKNESS)
WELDED TO FLOOR STRUCTURE PER
MANUFACTURERS RECOMMENDATIONS (3-
SPAN MINIMUM) w/ W1.4xW1.4 WWF (FLAT
SHEET STOCK) LOCATED 3/4" FROM TOP OF
SLAB.
VULCRAFT 2.5VS3 SERIES JOIST SUBSTITUTE
OR EQUIVALENT.
TYPE R1 TOP CHORD JOSIT EXTENSION.
LIGHT GAUGE ROOF JOISTS AT 16'' o/c MAX.
DESIGNED BY LIGHT GAUGE SUPPLIER.
6''x8'' BOND BEAM LINTEL w/ (2)-#5xCONT.
BEAR 8'' EACH END ON AN 8''x8'' MASONRY PIER w/ (1)-#5 VERTICAL GROUTED SOLID
FULL HEIGHT.
PROVIDE 5/16''x5-1/2''x5-1/2'' BENT PLATE VENEER SUPPORT w/ 1/4'' STIFFENER PLATE AT 48'' o/c MAX. WELD PLATE TO LT GAUGE HEADER w/ 1/8'' x 2'' LONG FILLET WELD AT 12'' o/c.
PENTHOUSE ROOF FRAMING PLAN NOTES:
ALL ROOF DECK SHALL BE VULCRAFT TYPE
1.5B (WIDE RIB) 22 GAUGE PAINTED METAL
ROOF DECK OR APPROVED EQUAL. REFER
TO DETAIL 1/S402 FOR ATTACHMENT TO
ROOF STRUCTURE.
(XXX'-XX'') INDICATES THE TOP OF STEEL
BEAM ELEVATION.
REFER TO 2/S401 FOR FRAMING AROUND
ROOF DRAIN OPENINGS AND OTHER ROOF
OPENINGS. COORDINATE SIZE, LOCATION, &
QUANTITY OF STEEL FRAMES WITH
MECHANICAL CONTRACTOR ON PROJECT.
DO NOT RUN JOIST BRIDGING THROUGH ANY
DECK OPENINGS. JOIST SUPPLIER SHALL
REVIEW AND PROVIDE ALTERNATE LOCATION
FOR BRIDGING ALONG JOIST SPAN AS
REQUIRED.
'' '' INDICATES A RIGID WIND FRAME
CONNECTION.
1.
2.
3.
4.
5.
PENTHOUSE ROOF FRAMING PLAN KEYED
NOTES:
CONTINUOUS HORIZONTAL JOIST
BRIDGING AT THE TOP & BOTTOM CHORDS
WITH X-BRIDGING AS SHOWN ON THE
FRAMING PLAN. PROVIDE ADDITIONAL
BOTTOM CHORD BRIDGING AS REQUIRED
TO RESIST A UNIFORM UNFACTORED
UPLIFT WIND LOAD OF 5 PSF.
PROVIDE AN L2x2x1/4 DIAGONAL BRACE
FROM THE BOTTOM FLANGE OF BEAM TO
TOP CHORD OFJOIST LOCATE BRACE AT
FIRST TOP CHORD PANEL POINT.
LIGHT GAUGE BUILT-UP BOX HEADER
DESIGNED BY LIGHT GAUGE SUPPLIER.
21675 LONG VIEW DRIVE
SUITE 500
WAUKESHA, WI 53186
FAX (262) 798.7001
PHONE (262) 798.7000
E-MAIL welman@welmanarch.com
PROJECT NO.
DATE:
REVISION / ISSUES:
SHEET NAME:
SHEET NO:
C COPYRIGHT BY WELMAN
ARCHITECTS INC.
CONTRACTOR:
PROJECT:
CERTIFICATION:
4035 N 127th Street Brookfield, WI 53005
Fax: (262) 373-0860Tel: (262) 373-0680
Project #: 09-174
Inc.
Structural Dimension
03-19-2010 FTG/FND SUBMITTAL
03-26-2010 Design Development Review I & II
04-02-2010 75% VA Review
04-16-2010 City Submittal
05-21-2010 CB #1
05-21-2010 100% VA Review
35 State Hospital Drive
Bangor, ME 04401
S200
LOW ROOF & PENTHOUSE
ROOF FRAMING PLANS
VA
Outpatient
Clinic
03-19-10
28112
SCALE: 3/32" = 1'-0"
LOW ROOF FRAMING PLAN
SCALE: 3/32" = 1'-0"
PENTHOUSE ROOF FRAMING PLAN
THE FOLLOWING ARE ITEMS THAT
HAVE BEEN REVISED SINCE THE
FOOTING & FOUNDATION SUBMITTAL
DATED 3-19-2010 THAT ARE NOT
CLOUDED ON THIS PLAN.
1. ALL T/BEAM ELEVATIONS HAVE BEEN
REVISED
4 5 6 7
F
G
3.9 4.7 5.6 6.6
E.4
F.9
5.9
E.6
F.3
5.54.6
S401
S401
S401
S401
20K4 20K4
W24X55 ( 113' - 6 1/2" ) W24X55 ( 113' - 6 1/2" )
W X
W X
W24X55 ( 113' - 6 1/2" )W24X55
( 113' - 6 1/2" )
W X
W X
W X
W X
W X
HSS6X6X1/2
HSS8X8X1/2
HSS8X8X1/2HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2
HSS8X8X1/2HSS8X8X1/2
HSS8X8X1/2
(4 E Q U A L S P A C E S /8
(8 E Q U A L S P A C E S
(3 E Q U A L S P A C E S
(4 E Q U A L S P A C E S
(4 E Q U A L S P A C E S
C6x13 NESTED
INTO DECK
FLUTES AT
48'' o/c MAX.
C6x13 NESTED
INTO DECK
FLUTES AT
48'' o/c MAX.
C x x C O N T B E L O W M T L S T U D W A L L
C x x C O N T B E L O W M T L S T U D W A L L
S401
S401
S401
W12X16
20K4
20K4
20K4
20K4
W X
W X
W X
W12X14
W12X14 W12X142
/2
/2
(7 E Q U A L S P A C E S
(9 E Q U A L S P A C E S
C6x13 BELOW
RTU CURB.
TYPICAL.
C6x13 BELOW
RTU CURB.
TYPICAL.
10' - 5" 10' - 0" 1' - 8 1/2"
13' - 4 1/2" 8' - 9"
10' - 3 1/4" 7' - 4" 4' - 6 1/4"
24KCS2
24KCS2
24KCS5
24KCS5
24KCS5
24KCS5
24KCS3
24KCS3
24KCS3
24KCS3
24KCS3
24KCS2
24KCS2
24KCS5
24KCS5
( 112' - 10 1/2" ) W24X55 ( 113' - 6 1/2" )
W12X16
W12X14
W12X16
W X
20K4
20K4
20K4
12" W x 6" H CONCRETE CURB w/ (2)-#5xCONT AT
PERIMETER OF MECHANICAL
UNIT. TYPICAL.
6" W x 6" H CONCRETE CURB w/ (2)-#5xCONT AT
PERIMETER OF MECHANICAL
UNIT. TYPICAL.
OPNG
OPNG
OPNG
6" W x 6" H CONCRETE CURB w/ (2)-#5xCONT AT
PERIMETER OF MECHANICAL
UNIT. TYPICAL.
6" W x 6" H CONCRETE CURB w/ (1)-#5xCONT AT
PERIMETER OF MECHANICAL
UNIT. TYPICAL.
24KCS5
24KCS524KCS5
24KCS5
24KCS4
24KCS4
24KCS4
24KCS4
24KCS4
24KCS4
24KCS4
24KCS4
1 1
S401
S401
S402
S402
S402
S402
24KCS5
24KCS5
20K4
20K4
20K4
20K4
20K4
20K4
20K4
20K4
20K4
20K4
20K4
20K4
20K4
20K4
20K4
1 1 1
1 1
4'' CONC PAD
REFER TO
MECHANICAL
DWGS FOR
SIZE AND
LOCATION
12" W x 6" H CONCRETE CURB w/ (2)-#5xCONT AT
PERIMETER OF MECHANICAL
UNIT. TYPICAL.
W12X14
W X
W12X14
400 LB TRANSFORMER
BELOW. REFER TO
ELECTRICAL DWGS
FOR SPECIFICS
W12X16
4'' CONC PAD
REFER TO
MECHANICAL
DWGS FOR
SIZE AND
LOCATION
PENTHOUSE FLOOR FRAMING PLAN NOTES:
ALL ROOF DECK SHALL BE VULCRAFT TYPE
1.5B (WIDE RIB) 22 GAUGE PAINTED METAL
ROOF DECK OR APPROVED EQUAL. REFER
TO DETAIL 1/S401 FOR ATTACHMENT TO
ROOF STRUCTURE.
(XXX'-XX'') INDICATES THE TOP OF STEEL
BEAM ELEVATION.
REFER TO 2/S401 FOR FRAMING AROUND
ROOF DRAIN OPENINGS AND OTHER ROOF
OPENINGS. COORDINATE SIZE, LOCATION, &
QUANTITY OF STEEL FRAMES WITH
MECHANICAL CONTRACTOR ON PROJECT.
VERIFY ALL MECHANICAL EQUIPMENT
WEIGHTS, SIZES, & LOCATIONS PRIOR TO
PREPARING SHOP DRAWINGS &
FABRICATING MATERIALS. CONTRACTOR
TO COORDINATE ANY CHANGES w/ JOIST
SUPPLIER.
ALL MECHANICAL EQUIPMENT SHALL BEAR
ON (2)-JOISTS MINIMUM.
DO NOT RUN JOIST BRIDGING THROUGH ANY
DECK OPENINGS. JOIST SUPPLIER SHALL
REVIEW AND PROVIDE ALTERNATE
LOCATION FOR BRIDGING ALONG JOIST
SPAN AS REQUIRED.
'' '' INDICATES A RIGID WIND FRAME
CONNECTION.
1.
2.
3.
4.
5.
6.
7.
PENTHOUSE FLOOR FRAMING PLAN KEYED
NOTES:
CONTINUOUS HORIZONTAL JOIST BRIDGING
AT THE TOP & BOTTOM CHORDS WITH X-
BRIDGING AS SHOWN ON THE FRAMING
PLAN. PROVIDE ADDITIONAL BOTTOM
CHORD BRIDGING AS REQUIRED TO RESIST
A UNIFORM UNFACTORED UPLIFT WIND
LOAD OF 5 PSF.
ROOF TOP UNIT w/ A 3000 LB MAXIMUM
WEIGHT (INCLUDING ROOF CURB).
ROOF TOP UNIT w/ A 6000 LB MAXIMUM
WEIGHT (INCLUDING ROOF CURB).
PENTHOUSE FLOOR CONSTRUCTION:
PROVIDE 3-1/2" CONCRETE OVER 1-1/2" 22
GA GALVD METAL DECK (5" TOTAL
THICKNESS) WELDED TO FLOOR
STRUCTURE PER MANUFACTURERS
RECOMMENDATIONS (3-SPAN MINIMUM) w/ W1.4xW1.4 WWF (FLAT SHEET STOCK)
LOCATED 3/4" FROM TOP OF SLAB.
TOP OF PENTHOUSE FLOOR CONCRETE SLAB
ELEVATION = 113'-9 1/2"
TOP OF PENTHOUSE FLOOR BEAMS
SUPPORTING METAL DECK
ELEVATION = 113'-6 1/2"
TOP OF PENTHOUSE FLOOR BEAMS AT JOIST
BEARING ELEVATION = 113'-4"
21675 LONG VIEW DRIVE
SUITE 500
WAUKESHA, WI 53186
FAX (262) 798.7001
PHONE (262) 798.7000
E-MAIL welman@welmanarch.com
PROJECT NO.
DATE:
REVISION / ISSUES:
SHEET NAME:
SHEET NO:
C COPYRIGHT BY WELMAN
ARCHITECTS INC.
CONTRACTOR:
PROJECT:
CERTIFICATION:
4035 N 127th Street Brookfield, WI 53005
Fax: (262) 373-0860Tel: (262) 373-0680
Project #: 09-174
Inc.
Structural Dimension
03-19-2010 FTG/FND SUBMITTAL
03-26-2010 Design Development Review I & II
04-02-2010 75% VA Review
04-16-2010 City Submittal
05-21-2010 CB #1
05-21-2010 100% VA Review
35 State Hospital Drive
Bangor, ME 04401
S201
PENTHOUSE FLOOR
FRAMING PLAN
VA
Outpatient
Clinic
03-19-10
28112
SCALE: 1/4" = 1'-0"
PENTHOUSE FLOOR FRAMING PLAN
| S001 |
| S002 |
| S100 |
| S200 |
| S201 |
| S300 |
| S400 |
| S401 |
| S402 |
| S403 |
File details come from the government source that posted it. Updated .