Bangor 3D Shielding Plan.pdf
PDF 360 KB Posted
- Solicitation number
- 36C24124Q0806
About this file
This is a shielding design specification sheet for Room 1404 Core Beam Dental Room at the Bangor VA facility, dated 11/8/22. The document details the required radiation shielding measurements for various barriers (doors, walls, and windows) in the dental room, with specifications given in millimeters of lead-equivalent protection. The barriers are designated A-B through L-M, each classified as "SECONDARY" protection type, with occupancy factors (OCC) ranging from 0.125 to 1, and distance factors (DIST) between 1.2 to 2.7. The required shielding thicknesses vary from 0.37 mm Pb to 1.33 mm Pb, with structural shielding equivalence measurements of 0.14 throughout, and recommended shielding additions ranging from 0.23 mm Pb to 1.24 mm Pb.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bangor Dental XRay pre-bid sign in sheet.pdf | ||
| 36C24124Q0806_2.docx | DOCX document | |
| Bangor - Elec.zip | ZIP file | |
| Bangor - Struct.pdf | ||
| Drawing.pdf | ||
| Bangor - Arch.pdf | ||
| SOW - Bangor Imaging and Dental Xray Prep.pdf | ||
| 36C24124Q0806.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .