36C24118R0304-00002001.pdf
PDF 462 KB Posted
- Solicitation number
- 36C24118R0304
About this file
36C24118R0304 00002 4HA101 First Floor Asbestos Abatement Plan.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24118R0304-0006000.docx | DOCX document | |
| 36C24118R0304-0005000.docx | DOCX document | |
| 36C24118R0304-0004000.docx | DOCX document | |
| 36C24118R0304-00003000.docx | DOCX document | |
| 36C24118R0304-00002000.docx | DOCX document | |
| 36C24118R0304-00001000.docx | DOCX document | |
| 36C24118R0304-00001001.pdf | ||
| 36C24118R0304-020.pdf | ||
| 36C24118R0304-017.pdf | ||
| 36C24118R0304-024.pdf | ||
| 36C24118R0304-023.pdf | ||
| 36C24118R0304-016.pdf | ||
| 36C24118R0304-018.pdf | ||
| 36C24118R0304-022.pdf | ||
| 36C24118R0304-015.docx | DOCX document | |
| 36C24118R0304-019.pdf | ||
| 36C24118R0304-021.pdf | ||
| 36C24118R0304-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL ASBESTOS REMOVAL NOTES:
1. REMOVAL AND DISPOSAL OF ASBESTOS-CONTAINING MATERIAL (ACM), ASBESTOS-CONTAMINATED ELEMENTS (ACE), AND OTHER POTENTIAL ACM AND ACE (EG, FLOORING, WALLS, AND CAULKING) USING FULL
CONTAINMENT PROCEDURES. REFER TO SPECIFICATION SECTIONS 02 82 11 ASBESTOS ABATEMENT; AND 02 82 13.31 ASBESTOS TRANSITE ABATEMENT FOR ADDITIONAL REQUIREMENTS.
2. GENERAL CONTRACTOR TO SUBMIT FOR EACH MAJOR DECONTAMINATION AREA THE LIMITS OF SEALING OFF THE LOCATION, QUANTITIES OF ASBESTOS MATERIAL, ARRANGEMENTS FOR AUXILIARY ROOMS, THE
ENGINEERING OF THE NEGATIVE AIR SYSTEMS, THE PATH OF ASBESTOS TRANSPORATION TO THE LOADING PLATFORM, AND LOCATION AND CONNECTION TO REQUIRED UTILITIES.
3. INACCESSIBLE OR ENCLOSED ACM IS ASSUMED BASED ON INSPECTION AND CONFIRMATION OF PREVIOUS BUILDING SURVEYS.
4. DRAWINGS DO NOT CLAIM TO IDENTIFY ALL OF THE ACM PRESENT IN THE BUILDING AND SHOULD NOT BE THE SOLE BASIS FOR IDENTIFYING ACM. CDW'S SURVEY WAS PERFORMED WITH LIMITATIONS INHERENT
TO NON-DESTRUCTIVE VISUAL INSPECTIONS. ANY SUSPECT MATERIAL ENCOUNTERED DURING RENOVATION/DEMOLITION THAT IS NOT IDENTIFIED AS BEING NON-ACM SHOULD BE ASSUMED TO BE ACM UNLESS
SAMPLE RESULTS PROVE OTHERWISE.
5. CAULKING NOT TESTED FOR PCBS. CONTRACTOR MUST TEST FOR PCBS TO CONFIRM WASTE STREAM REQUIREMENTS AT NO COST TO OWNER.
6. POTENTIAL ACM AND ACE INCLUDES BUT MAY NOT BE LIMITED TO THE FOLLOWING:
EXTERIOR OLD CAULK AT LENTIL, TYPICAL
EXTERIOR GREY CAULK AT CANOPY, TYPICAL
BLACK SEALANT ON COPPER FLASHING ALONG RAMP/ROOF, TYPICAL
TRANSITE PANELS AT HEATING UNIT, TYPICAL
VAPOR BARRIER BEHIND MASONRY, TYPICAL