Fire Alarm Inspection Report.pdf
PDF 68 KB Posted
- Attached to
- J042--Jackson Fire Suppression Maintenance Federal contract opportunity
- Solicitation number
- 36C10D25Q0129
- Issued by
- Department of Veterans Affairs
About this file
This document is a Fire Alarm Annual Inspection Report for the VA Regional Office located at 1600 E. Woodrow Wilson, Jackson, MS 39216, conducted on 10/23/2024 and 10/24/2024 by inspector Kendarrian Oshay Boyd. The comprehensive inspection covered multiple fire safety systems and devices, including smoke detectors, heat detectors, pull stations, water flow switches, and sprinkler devices across various building levels such as basement, 1st, 2nd, 3rd floors, and garage areas.
The inspection revealed several key findings: two pull stations on the 4th floor garage failed functional tests due to being previously water-damaged, two duct detectors on the 3rd floor had broken housing that needs replacement, and one battery on the 3rd floor NAC panel failed a load test with only 15% load voltage. Overall, out of 186 total devices tested, 177 passed, 5 failed, and 4 could not be inspected. The devices that failed or could not be inspected were primarily located in hard-to-access areas or had physical damage that compromised their functionality, indicating potential maintenance and accessibility issues that should be addressed to ensure comprehensive fire safety system reliability.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C10D25Q0129 0004.docx | DOCX document | |
| 36C10D25Q0129 0003.docx | DOCX document | |
| Initial Site Visit Attendees 8-14-2025.pdf | ||
| 36C10D25Q0129 0002.docx | DOCX document | |
| Photos for RFIs.zip | ZIP file | |
| Second Site Visit Attendees 9-4-2025.pdf | ||
| Fire Alarm and Fire Suppression Labels.pdf | ||
| 36C10D25Q0129 0001.docx | DOCX document | |
| 36C10D25Q0129.docx | DOCX document | |
| Wage Determination Jackson.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CUSTOMER NAME: VA Regional Office BUILDING NAME: VA Regional Office BUILDING ADDRESS: 1600 E. Woodrow Wilson, Jackson, MS 39216
INSPECTION START DATE: 10/23/2024
INSPECTION END DATE: 10/24/2024
FIRE ALARM INSPECTION REPORT
GENERAL DEFICIENCIES
DESCRIPTION IMAGES
Garage 4th level center stairwell (m2-43)PS
3rd Floor door 345 (P519) trouble point abnormal
Pipe Bsmt service elev PIT zone B-1 (M1-88) WF
DEVICE DEFICIENCIES
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES
4th FL Garage Garage 4th Floor Center Stairwell
M2-43 Pull Station — — — 10/24/2024
FUNCTIONAL
FAILURE
DEFICIENCY
IMAGES APPENDIX
1.1
FAILURE REASON: No alarm when tested. Device failed last year due to being full of water.
4th FL Garage Garage 4th Floor
West Stairwell M2-44 Pull Station — — — 10/24/2024
FUNCTIONAL
FAILURE
DEFICIENCY
IMAGES APPENDIX
1.2
FAILURE REASON: No alarm when tested. Device failed last year due to being full of water.
3rd Floor Main Building 3rd Floor AHU1 West
Chase Rm323 M2-9 Duct Detector — — — 10/24/2024 VISUAL FAILURE
DEFICIENCY
IMAGES APPENDIX
1.3
FAILURE REASON: The device works but the housing that the device is in is broken and needs to be replaced… you can swap it out with a 40978-9756
3rd Floor Main Building 3rd Floor AHU1 West
Chase Rm323 M2-10 Duct Detector — — — 10/24/2024 VISUAL FAILURE
DEFICIENCY
IMAGES APPENDIX
1.4
FAILURE REASON: The device works but the housing that the device is in is broken and needs to be replaced… you can swap it out with a 40978-9756
3rd Floor
NAC Panel on the 3rd Floor
Communication Closet
— Battery — — — 10/24/2024
FUNCTIONAL
FAILURE
DEFICIENCY
IMAGES APPENDIX
1.5
FAILURE REASON: Batteries failed a load test
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
Address: 1600 E. Woodrow Wilson, Jackson, MS 39216
Fire Alarm v2 | 10/24/2024
CANNOT INSPECT REPORT
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES
3rd Floor Main Building 3rd Floor AHU3 East
Chase M2-4 Duct Detector — — — 10/24/2024 Cannot Inspect —
Reason cannot inspect: Couldn’t find the access chase to get to device to test it
3rd Floor Main Building 3rd Floor AHU3 East
Chase M2-5 Duct Detector — — — 10/24/2024 Cannot Inspect —
Reason cannot inspect: Couldn’t find the access chase to get to device to test it
3rd Floor Main Building 3rd Floor Room 318
M2-71 Duct Detector — — — 10/24/2024 Cannot Inspect —
Reason cannot inspect: Could not locate
3rd Floor Main Building 3rd Floor Room 318
M2-70 Duct Detector — — — 10/24/2024 Cannot Inspect —
Reason cannot inspect: Could not locate
INSPECTION RESULTS SUMMARY
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Battery 3 2 1 0
Duct Detector 13 7 2 4
Heat Detector 7 7 0 0
MAZAM 6 6 0 0
Panel 3 3 0 0
Pull Station 36 34 2 0
Smoke Detector 71 71 0 0
Tamper Switch 31 31 0 0
Water Flow Switch 16 16 0 0
TOTAL 186 177 5 4
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
Panels/Initiating Devices
INSPECTION RESULTS SUMMARY
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Battery 3 2 1 0
Duct Detector 13 7 2 4
Heat Detector 7 7 0 0
MAZAM 6 6 0 0
Panel 3 3 0 0
Pull Station 36 34 2 0
Smoke Detector 71 71 0 0
Tamper Switch 31 31 0 0
Water Flow Switch 16 16 0 0
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
FACP PANELS
# LOCATION DESCRIPTION MANUFACTURER MODEL DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 1st Floor 1st Floor Security Room by North
Exit Simplex 4100 Panel —
Kendarrian Oshay Boyd
10/24/2024 Passed
Is the panel in a normal condition at the start of the inspection? No
* 3 Pull Stations iNo Answer Troubles on arrival
Alarm, Supervisory, and Trouble Signals (Inputs) Yes
Circuit Supervisory (Including Opens, Shorts & Ground Faults) Yes
Alarm verification sequence verified Yes
POWER SUPPLY SUPV - LOSS OF AC POWER/BATTS Yes
Fuses/Lamps/LED Tested & Verified Yes
INTERFACE EQUIP VERIFICATION OF REQUIRED SIGNALS Yes
MAIN POWER SUPPLY TESTED UNDER FULL LOAD Yes
AMPLIFIER/TONE GENERATORS VERIFIED Yes
CALL-IN SIGNAL SILENCE - VISUAL & AUDIBLE Yes
OFF-HOOK INDICATOR VERIFIED Yes
PHONE JACKS Yes
PHONE SETS VERIFIED Yes
SYST PERF- 5 HANDSET QUALITY & CLARITY VERIFIED Yes
DOOR HOLDERS Yes
REMOTE ANNUNCIATOR(S) - OPERATION/VERIFICATION Yes
INITIATING DEVICES TEST Yes
ELEVATOR RECALL FUNCTION & SHUNT TRIP OPERATION Yes
HVAC SHUT DOWN Yes
MASTERBOX / CENTRAL STATION CONNECTION TESTED Yes
MASTERBOX / CENTRAL STATION ACCOUNT # 212-5123
ALARM NOTIFICATION APPLIANCES TESTED Yes
* Customer did not want to test audio visual devices during business hours.
MULTIPLEX COMMUNICATIONS TESTED Yes
Primary Power- Nominal Voltage 120VAC
Primary Power- Amps 20A
Primary Power- Location 1st Floor East Electrical Room
Primary Power- Overcurrent Protection Type/Amps Circuit breaker/ 20A
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
NAC PANELS
# LOCATION DESCRIPTION MANUFACTURER MODEL DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 1st Floor 1st Floor Telco Closet East Hall
Near Dock Simplex 4009 Panel —
Kendarrian Oshay Boyd
10/24/2024 Passed
Lamps/LEDs/LCDs Yes
Fuses Yes
Primary Power Supply Yes
Secondary Power Supply Yes
Trouble Signals Yes
Ground-fault monitoring Yes
Panel supervision Yes
2 3rd Floor 3rd Floor
Communication Closet
Simplex 4009 Panel — Kendarrian Oshay
Boyd 10/24/2024 Passed
Lamps/LEDs/LCDs Yes
Fuses Yes
Primary Power Supply Yes
Secondary Power Supply Yes
Trouble Signals Yes
Ground-fault monitoring Yes
Panel supervision Yes
BATTERIES
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 1st Floor FACP Security Room by
North Exit Battery — Kendarrian Oshay Boyd 10/24/2024 Passed
Quantity (Enter 2 if answering for a set) 2
Amp hour rating 33 AH
Visual inspection Pass
Has the Alarm Equipment or Battery Manufacturer’s Replacement Date Been Exceeded? Pass
Manufacturer Date Code 11/15/2023
Voltage with charger 24.00 VDC
Voltage without charger 24.00 VDC
Load Voltage Test Pass
Load Voltage Test Results (%) 100%
2 1st Floor NAC panel on1st Floor Telco Closet Near Dock
Panel Battery — Kendarrian Oshay Boyd 10/24/2024 Passed
Quantity (Enter 2 if answering for a set) 2
Amp hour rating 10 AH
Has the Alarm Equipment or Battery Manufacturer’s Replacement Date Been Exceeded? Pass
Manufacturer Date Code 2020
Voltage with charger 27.79 VDC
Voltage without charger 2765 VDC
Load Voltage Test Pass
Load Voltage Test Results (%) 100%
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
BATTERIES
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
3 3rd Floor NAC Panel on the 3rd Floor Communication
Closet Battery — Kendarrian Oshay Boyd 10/24/2024 Failed
Quantity (Enter 2 if answering for a set) 2
Amp hour rating 18 AH
Visual inspection Pass
Has the Alarm Equipment or Battery Manufacturer’s Replacement Date Been Exceeded? Pass
Manufacturer Date Code 2020
Voltage with charger 27.79
Voltage without charger 27.65
Load Voltage Test Fail
Load Voltage Test Results (%) 15%
Reason for failure: (Functional Failure) Batteries failed a load test
SMOKE DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 2nd Floor 2nd floor east atrium at fire doors M1-52 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
2 2nd Floor 2nd floor east corridor M1-93 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
3 2nd Floor 2nd floor west corridor M1-94 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
4 1st Floor Garage 1st floor Elevator Lobby
M2-29 Smoke Detector — Kendarrian Oshay
Boyd 10/24/2024 Passed
5 2nd FL Garage Garage 2nd Floor
Elevator Lobby M2-33 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
6 3rd Floor Garage 3rd Floor Elevator Lobby
M2-37 Smoke Detector — Kendarrian Oshay
Boyd 10/24/2024 Passed
7 — Garage 4th Floor
Elevator Hoist Way M2-42 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
8 — Garage 4th Floor Elevator Lobby
M2-41 Smoke Detector — Kendarrian Oshay
Boyd 10/24/2024 Passed
9 — Garage Ground Elevator Lobby
M2-26 Smoke Detector — Kendarrian Oshay
Boyd 10/24/2024 Passed
10 1st Floor Main Building 1st Floor East Comm
Room 138 M1-110 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
11 1st Floor Main Building 1st
Floor East Corridor At Smoke Door
M1-72 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
12 1st Floor Main Building 1st
Floor East Lobby At Smoke Doors
M1-71 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
13 1st Floor Main Building 1st Floor East Lobby
Waiting M1-6 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
14 1st Floor Main Building 1st
Floor Electrical Room M1-2 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
15 1st Floor Main Building 1st
Floor Electrical Room East
M1-80 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
SMOKE DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
16 1st Floor
Main Building 1st Floor Elevator
Equipment Room
M1-68 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
17 1st Floor Main Building 1st
Floor Elevator Lobby M1-4 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
18 1st Floor Main Building 1st
Floor In Agent Cashier Room
M1-96 Smoke Detector — Kendarrian Oshay
Boyd 10/24/2024 Passed
19 1st Floor Main Building 1st
Floor Lobby At Agent Cashier
M1-100 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
20 1st Floor Main Building 1st
Floor Main Electrical Room
M1-29 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
21 1st Floor Main Building 1st
Floor Maintenance Shop Room 142
M1-28 Smoke Detector — Kendarrian Oshay
Boyd 10/24/2024 Passed
22 1st Floor Main Building 1st
Floor Security Office At FACP
M1-119 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
23 1st Floor
Main Building 1st Floor Service
Elevator Equipment Room
M1-32 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
24 1st Floor Main Building 1st
Floor Service Elevator Lobby
M1-74 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
25 1st Floor Main Building 1st Floor West Comm
Room 107 M1-111 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
26 1st Floor Main Building 1st
Floor West Corridor At Smoke Door
M1-73 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
27 1st Floor Main Building 1st
Floor West Corridor At Smoke Doors
M1-3 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
28 1st Floor Main Building 1st Floor West Lobby
Waiting M1-69 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
29 2nd Floor
Main Building 2nd Floor Computer
Room Above Ceiling
NE
M1-41 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
30 2nd Floor
Main Building 2nd Floor Computer
Room Above Ceiling
NW
M1-38 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
31 2nd Floor
Main Building 2nd Floor Computer
Room Above Ceiling
SW
M1-47 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
32 2nd Floor Main Building 2nd
Floor Computer Room Below Floor E
M1-44 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
33 2nd Floor
Main Building 2nd Floor Computer
Room Below Floor
NE
M1-43 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
34 2nd Floor
Main Building 2nd Floor Computer
Room Below Floor
NW
M1-40 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
35 2nd Floor
Main Building 2nd Floor Computer
Room Below Floor
SW
M1-45 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
36 2nd Floor Main Building 2nd
Floor Computer Room Below Floor W
M1-49 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
37 2nd Floor Main Building 2nd
Floor Computer Room NE
M1-42 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
38 2nd Floor Main Building 2nd
Floor Computer Room NW
M1-39 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
39 2nd Floor Main Building 2nd
Floor Computer Room SW
M1-46 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
40 2nd Floor Main Building 2nd Floor East Comm
Room 238 M1-112 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
41 2nd Floor Main Building 2nd
Floor Electrical Room East
M1-34 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
42 2nd Floor Main Building 2nd
Floor Electrical Room West
M1-57 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
43 2nd Floor Main Building 2nd
Floor Elevator Lobby M1-53 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
44 2nd Floor Main Building 2nd
Floor Service Elevator Lobby
M1-35 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
45 2nd Floor Main Building 2nd
Floor West Atrium At Fire Doors
M1-54 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
Notes:
• Label on device says (m1-51) needs to be changed to (m1-54) reads correct at FACP
• Label on device needs to read (M1-54) Images: DEVICE NOTES IMAGES APPENDIX 1.1
46 2nd Floor Main Building 2nd Floor West Comm
Room 224 M1-113 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
47 3rd Floor Main Building 3rd Floor East Comm Room Near 341
M2-114 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
48 3rd Floor Main Building 3rd Floor East Corridor
At Fire Doors M2-50 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
49 3rd Floor Main Building 3rd
Floor East Lobby At Smoke Doors
M2-6 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
50 3rd Floor Main Building 3rd
Floor Electrical Room East
M2-1 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
51 3rd Floor Main Building 3rd
Floor Electrical Room West
M2-11 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
52 3rd Floor Main Building 3rd
Floor Elevator Lobby M2-7 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
53 3rd Floor Main Building 3rd
Floor Quality Review Storage Room
M2-72 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
54 3rd Floor Main Building 3rd
Floor Service Elevator Hoist Way
M2-3 Smoke Detector — Kendarrian Oshay
Boyd 10/24/2024 Passed
55 3rd Floor Main Building 3rd
Floor Service Elevator Lobby
M2-2 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
56 3rd Floor Main Building 3rd Floor West Comm
Room 321 M2-115 Smoke Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
57 3rd Floor Main Building 3rd
Floor West Corridor At Fire Doors
M2-51 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
58 3rd Floor Main Building 3rd
Floor West Lobby At Smoke Door
M2-8 Smoke Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
59 — P1 Elevator Hoist
Way M2-15 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
60 — P2 Elevator Hoist
Way M2-14 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
61 Basement Parking Garage
Basement File Room M2-74 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
62 Basement Parking Garage
Basement File Room M2-76 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
63 Basement Parking Garage
Basement File Room M2-75 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
64 Basement Parking Garage
Basement File Room M2-77 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
65 Basement Parking Garage
Basement File Room M2-79 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
66 Basement Parking Garage
Basement File Room M2-80 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
67 Basement Parking Garage
Basement File Room M2-81 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
68 Basement Parking Garage
Basement File Room M2-82 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
69 Basement Parking Garage
Basement File Room M2-83 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
70 Basement Parking Garage
Basement File Room M2-84 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
71 Basement Parking Garage
Basement File Room M2-85 Smoke Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
HEAT DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 1st Floor Main Building 1st Floor Boiler Room
Left Chiller M1-108 Heat Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
2 1st Floor Main Building 1st Floor Boiler Room
North M1-25 Heat Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
3 1st Floor Main Building 1st Floor Boiler Room
Right Chiller M1-107 Heat Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
4 1st Floor Main Building 1st Floor Boiler Room
South M1-24 Heat Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
5 1st Floor Main Building 1st
Floor Chiller Room M1-23 Heat Detector —
Kendarrian Oshay Boyd
10/23/2024 Passed
6 1st Floor
Main Building 1st Floor Elevator
Equipment Room
M1-67 Heat Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
7 1st Floor
Main Building 1st Floor Service
Elevator Equipment Room
M1-31 Heat Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
DUCT DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 2nd Floor 2nd Floor East AHU
Chase M1-50 Duct Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
2 2nd Floor 2nd Floor East AHU
Chase M1-51 Duct Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
3 1st Floor Main Building 1st Floor Boiler Room
M1-26 Duct Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
4 2nd Floor Main Building 2nd Floor AHU1 West
Chase Rm 227 M1-56 Duct Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
5 2nd Floor Main Building 2nd Floor AHU1 West
Chase Rm 227 M1-55 Duct Detector —
Kendarrian Oshay Boyd
10/24/2024 Passed
6 3rd Floor Main Building 3rd Floor AHU1 West
Chase Rm323 M2-9 Duct Detector —
Kendarrian Oshay Boyd
10/24/2024 Failed
Reason for failure: (Visual Failure) The device works but the housing that the device is in is broken and needs to be replaced… you can swap it out with a 40978-9756
7 3rd Floor Main Building 3rd Floor AHU1 West
Chase Rm323 M2-10 Duct Detector —
Kendarrian Oshay Boyd
10/24/2024 Failed
Reason for failure: (Visual Failure) The device works but the housing that the device is in is broken and needs to be replaced… you can swap it out with a 40978-9756
8 3rd Floor Main Building 3rd Floor AHU3 East
Chase M2-4 Duct Detector —
Kendarrian Oshay Boyd
10/24/2024 Cannot Inspect
Reason cannot inspect: Couldn’t find the access chase to get to device to test it
9 3rd Floor Main Building 3rd Floor AHU3 East
Chase M2-5 Duct Detector —
Kendarrian Oshay Boyd
10/24/2024 Cannot Inspect
Reason cannot inspect: Couldn’t find the access chase to get to device to test it
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
DUCT DETECTORS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
10 3rd Floor Main Building 3rd Floor Room 318
M2-71 Duct Detector — Kendarrian Oshay
Boyd 10/24/2024 Cannot Inspect
Reason cannot inspect: Could not locate
11 3rd Floor Main Building 3rd Floor Room 318
M2-70 Duct Detector — Kendarrian Oshay
Boyd 10/24/2024 Cannot Inspect
Reason cannot inspect: Could not locate
12 3rd Floor Main Building 3rd Floor Room 341
M2-66 Duct Detector — Kendarrian Oshay
Boyd 10/23/2024 Passed
13 3rd Floor Main Building 3rd Floor Room 341
M2-67 Duct Detector — Kendarrian Oshay
Boyd 10/24/2024 Passed
PULL STATIONS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 1st FL Garage Garage 1st Floor Center Stairwell
M2-30 Pull Station — Kendarrian Oshay
Boyd 10/24/2024 Passed
2 1st FL Garage Garage 1st Floor
East Stairwell M2-32 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
3 1st FL Garage Garage 1st Floor
West Stairwell M2-31 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
4 2nd FL Garage Garage 2nd Floor Center Stairwell
M2-34 Pull Station — Kendarrian Oshay
Boyd 10/24/2024 Passed
5 2nd FL Garage Garage 2nd Floor
East Stairwell M2-36 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
6 2nd FL Garage Garage 2nd floor west stairwell M2-35 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
7 3rd FL Garage Garage 3rd Floor Center Stairwell
M2-38 Pull Station — Kendarrian Oshay
Boyd 10/24/2024 Passed
8 3rd FL Garage Garage 3rd Floor
East Stairwell M2-40 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
9 3rd FL Garage Garage 3rd Floor
West Stairwell M2-39 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
10 4th FL Garage Garage 4th Floor Center Stairwell
M2-43 Pull Station — Kendarrian Oshay
Boyd 10/24/2024 Failed
Reason for failure: (Functional Failure) No alarm when tested. Device failed last year due to being full of water.
11 4th FL Garage Garage 4th Floor
East Stairwell M2-45 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
12 4th FL Garage Garage 4th Floor
West Stairwell M2-44 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Failed
Reason for failure: (Functional Failure) No alarm when tested. Device failed last year due to being full of water.
13 Basement Garage Basement
Crawl Space M2-24 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
14 Basement Garage Basement
File Room M2-78 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
15 Basement Garage Basement
File Room M2-73 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
16 — Garage Ground Level
Center Stairwell M2-27 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
17 — Garage Ground Level
East Stairwell M2-28 Pull Station —
Kendarrian Oshay Boyd
10/24/2024 Passed
18 1st Floor Main Building 1st
Floor Dock M1-27 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
PULL STATIONS
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
19 1st Floor Main Building 1st Floor East Exit To
Dock M1-30 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
20 1st Floor Main Building 1st
Floor Lobby Entrance M1-5 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
21 1st Floor Main Building 1st
Floor Mailroom Exit To Dock
M1-33 Pull Station — Kendarrian Oshay
Boyd 10/23/2024 Passed
22 1st Floor Main Building 1st
Floor North East Exit To Garage
M1-18 Pull Station — Kendarrian Oshay
Boyd 10/23/2024 Passed
23 1st Floor Main Building 1st Floor North Exit
M1-7 Pull Station — Kendarrian Oshay
Boyd 10/23/2024 Passed
24 1st Floor Main Building 1st
Floor West Exit M1-1 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
25 2nd Floor Main Building 2nd
Floor Computer Room Ramp
M1-37 Pull Station — Kendarrian Oshay
Boyd 10/23/2024 Passed
26 2nd Floor Main Building 2nd Floor East Corridor
At Stairwell M1-48 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
27 2nd Floor Main Building 2nd Floor East Stairwell
M1-58 Pull Station — Kendarrian Oshay
Boyd 10/23/2024 Passed
28 2nd Floor Main Building 2nd
Floor Kitchen M1-36 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
29 3rd Floor Main Building 3rd
Floor East Stairwell M2-13 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
30 3rd Floor Main Building 3rd
Floor West Stairwell M2-12 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
31 Basement Pipe Basement East
Stairwell M1-81 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
32 Basement Pipe Basement
North East M1-82 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
33 Basement Pipe Basement
North West M1-86 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
34 Basement Pipe Basement
South East M1-83 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
35 Basement Pipe Basement
South West M1-85 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
36 Basement Pipe Basement West
Stairwell M1-84 Pull Station —
Kendarrian Oshay Boyd
10/23/2024 Passed
MISCELLANEOUS ALARM & SUPERVISORY DEVICES
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Garage Elevator
Equipment Room Recall
M1-78 MAZAM —
Kendarrian Oshay
Boyd 10/24/2024 Passed
2 — Garage Elevator
Equipment Room Recall Alt.
M1-79 MAZAM —
Kendarrian Oshay
Boyd 10/24/2024 Passed
3 1st Floor
Main Building 1st Floor Alt. Recall Service Elevator
Equipment Room
M1-76 MAZAM —
Kendarrian Oshay
Boyd 10/24/2024 Passed
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
MISCELLANEOUS ALARM & SUPERVISORY DEVICES
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
4 1st Floor
Main Building 1st Floor Primary Recall
Service Elevator Equipment Room
M1-75 MAZAM —
Kendarrian Oshay
Boyd 10/24/2024 Passed
5 1st Floor Main Building 1st
Floor Roll-up Window Agent Cashier
M1-70 MAZAM —
Kendarrian Oshay
Boyd 10/24/2024 Passed
6 1st Floor
Main Building 1st Floor Service
Elevator Equipment Room Shunt
M1-77 MAZAM —
Kendarrian Oshay
Boyd 10/24/2024 Passed
WATER FLOW DEVICES
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Basement Garage Basement
File Room M1-116 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
2 1st Floor Main Building 1st
East Stairwell M1-13 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
3 1st Floor Main Building 1st
Floor East Stairwell M1-12 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
4 1st Floor Main Building 1st
Floor East Stairwell M1-10 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
5 1st Floor Main Building 1st
Floor East Stairwell M1-11 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
6 1st Floor Main Building 1st
Floor East Stairwell M1-14 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
7 2nd Floor Main Building 2nd Floor East Stairwell
M1-63 Water Flow Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
Time Delay (in seconds) Less than 90
8 2nd Floor Main Building 2nd Floor East Stairwell
M1-64 Water Flow Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
Time Delay (in seconds) Less than 90
9 2nd Floor Main Building 2nd Floor East Stairwell
M1-66 Water Flow Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
Time Delay (in seconds) Less than 90
10 2nd Floor Main Building 2nd Floor East Stairwell
M1-65 Water Flow Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
Time Delay (in seconds) Less than 90
11 3rd Floor Main Building 3rd
Floor East Stairwell M2-21 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
12 3rd Floor Main Building 3rd
Floor East Stairwell M2-17 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
WATER FLOW DEVICES
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
13 3rd Floor Main Building 3rd
Floor East Stairwell M2-19 Water Flow Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
Time Delay (in seconds) Less than 90
14 Basement Main Building
Basement Main Elevator Pit
M1-87 Water Flow Switch — Kendarrian Oshay
Boyd 10/23/2024 Passed
Time Delay (in seconds) Less than 90
15 Basement Main Building
Basement Service Elevator Pit
M1-88 Water Flow Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
Time Delay (in seconds) Less than 90
16 Basement Small Backflow
Preventer - Flow Switch
M1-97 Water Flow Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
SPRINKLER DEVICES
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Basement Basement backflow preventer BP-1 M1-92 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
2 Basement Garage Basement
Center M2-48 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
3 Basement Garage Basement
East M2-49 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
4 Basement Garage Basement
South West M2-47 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
5 1st Floor Main Building 1st Floor Boiler Room
Bypass P-3 M1-19 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
6 1st Floor Main Building 1st Floor Boiler Room
Bypass P-4 M1-20 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
7 1st Floor Main Building 1st Floor Boiler Room
HDR P-5
M1-21 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
8 1st Floor Main Building 1st Floor Boiler Room
HDR P-9
M1-22 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
9 1st Floor Main Building 1st Floor Dock Anti-freeze Loop M1-103 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
10 1st Floor Main Building 1st
Floor East Building M1-59 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
11 1st Floor Main Building 1st
Floor East Stairwell 1-1
M1-17 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
12 1st Floor Main Building 1st
Floor East Stairwell 1-2
M1-16 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
13 1st Floor Main Building 1st
Floor East Stairwell 1-3
M1-9 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
14 1st Floor Main Building 1st
Floor East Stairwell 1-4
M1-15 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
SPRINKLER DEVICES
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
15 1st Floor Main Building 1st
Floor East Stairwell 1-5
M1-8 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
16 1st Floor Main Building 1st
Floor Fire Pump Cont P-1
M1-102 Tamper Switch — Kendarrian Oshay
Boyd 10/23/2024 Passed
17 1st Floor Main Building 1st
Floor Fire Pump Cont P-2
M1-101 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
18 1st Floor Main Building 1st
Floor PIV Near Dock East Drive
M1-99 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
19 2nd Floor Main Building 2nd
Floor East Stair M1-62 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
20 2nd Floor Main building 2nd floor east stairwell
M1-61 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
21 2nd Floor Main Building 2nd Floor East Stairwell
Exit M1-60 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
22 3rd Floor Main Building 3rd
Floor East Stair M2-20 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
23 3rd Floor Main building 3rd floor east stairwell
M2-22 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
24 3rd Floor Main Building 3rd
Floor East Stairwell.
M2-18 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
25 Basement Main Building
Basement Backflow Northeast
M1-91 Tamper Switch — Kendarrian Oshay
Boyd 10/24/2024 Passed
26 Basement Main Building
Basement East Stairs M1-98 Tamper Switch —
Kendarrian Oshay Boyd
10/24/2024 Passed
27 Basement Main Building
Basement Main Elevator Pit
M1-89 Tamper Switch — Kendarrian Oshay
Boyd 10/23/2024 Passed
28 Basement Main Building
Basement Service Elevator Pit
M1-90 Tamper Switch — Kendarrian Oshay
Boyd 10/23/2024 Passed
29 Basement Main Building
Basement West Stairs
M1-98 Tamper Switch — Kendarrian Oshay
Boyd 10/23/2024 Passed
30 Basement Small Backflow
Preventer - Valves #1 and #2
M1-97 Tamper Switch — Kendarrian Oshay
Boyd 10/23/2024 Passed
31 Basement Valve for Garage File
Room M1-117 Tamper Switch —
Kendarrian Oshay Boyd
10/23/2024 Passed
Fire Alarm v2–Annual
Customer: VA Regional Office Building: VA Regional Office
File details come from the government source that posted it. Updated .